SUMMARY OF TECHNICAL INFORMATION


FOR DESIGNING THE
CAST-IRON HEATING BODIES

KALOR, KALOR 3, TERMO and BOHEMIA

TABLE OF CONTENTS

CAST-IRON HEATING BODIES KALOR

Chapter 1

THERMAL POWER TABLES FOR INDIVIDUAL MODELS


- WARM-WATER HEATING
- STEAM HEATING

CAST-IRON HEATING BODIES KALOR 3

Chapter 2

THERMAL POWER TABLES FOR INDIVIDUAL MODELS


- WARM-WATER HEATING
- STEAM HEATING

CAST-IRON HEATING BODIES TERMO

Chapter 3

THERMAL POWER TABLES FOR INDIVIDUAL MODELS


- WARM-WATER HEATING
- STEAM HEATING

CAST-IRON HEATING BODIES BOHEMIA

Chapter 4

THERMAL POWER TABLES FOR INDIVIDUAL MODELS


- WARM-WATER HEATING
- STEAM HEATING

SUPPLEMENTARY DATA

Chapter 5

SURFACE FINISHING
INSTALLATION INSTRUCTIONS
PACKAGING, TRANSPORT, STORAGE, ORDERING
WARRANTY

DESIGNING DATA

Chapter 6

PRESSURE LOSSES

INTEGRATED THERMOSTATIC VALVE

Chapter 7

ACCESSORIES

Chapter 8

ROSES, PLUGS, NIPPLES AND PACKING


FIXATION OF HEATING BODIES

Page 2 of 114

CAST-IRON HEATING BODIES


KALOR

Page 3 of 114

KALOR
DESCRIPTION
Heating body consisting of sections connected into heating systems using steel nipples with external right-hand
or left-hand thread G 5/4 is manufactured in eight models:
350/160 mm, 500/70 mm, 500/110 mm, 500/160 mm, 500/220 mm, 600/160 mm, 900/70 mm and 900/160
mm.
Heating bodies comply with CSN EN 442 1:1995 and CSN EN 442 2:1997. The material used is a grey
cast-iron corresponding to CSN 422415:1989. The design of castings ensures a long life cycle of products.

350/160

500/70

500/110 500/160

500/220

600/160

900/70

900/160

Fig. 1: Kalor line heating bodies

USAGE
All heating bodies of Kalor line are designed for warm-water central heating systems with gravity and forced
circulation of heating water with the highest operating temperature not exceeding 120 C and highest operating
overpressure of up to 0.6 MPa. In addition to this all models manufactured are approved for steam central
heating systems with the maximum operating overpressure of up to 0.07 MPa.

Page 4 of 114

THERMAL AND TECHNICAL PARAMETERS


Table 1: Significant thermal and technical parameters of Kalor heating sections
Property

Symbol

Unit

350/160

500/70

total height
spacing
depth
width
connection
thread

H
h
B
L

(mm)
(mm)
(mm)
(mm)

430
350
160
60

580
500
70
60

580
500
110
60

580
500
160
60

580
500
220
60

"

5/4

5/4

5/4

5/4

weight
equivalent
heating area
water volume

(kg/section)

4.30

3.20

4.00

0.185

0.120

thermal power
thermal
temperature
exponent

SL

(m /section)
3

500/110 500/160 500/220 600/160

900/70

900/160

680
600
160
60

980
900
70
60

980
900
160
60

5/4

5/4

5/4

5/4

5.60

6.95

6.60

5.20

10.60

0.180

0.255

0.345

0.306

0.205

0.440

(dm /section

0.8

0.5

0.8

1.1

1.3

1.2

0.8

1.5

s
L

(W/section)
(W/m)

70
1162

53
889

73
1162

94
1516

120
1979

110
1815

89
1370

152
2475

(-)

1.250

1.240

1.250

1.250

1.285

1.270

1.280

1.310

All Kalor models are certified by SZ Brno. Thermal and technical parameters are verified experimentally in
compliance with CSN EN 442-2: 1997.
Tables 2 through to 29 provide values of thermal power for individual models of cast-iron heating bodies for
number of sections ranging from 2 up to 30, variable required air temperature and temperature gradient of the
heat-transfer fluid (water) equal to 90/70C, 75/65C, 55/45C and steam.

Fig. 2: Standard dimensions of Kalor sections


Basic thermal and technical parameters for the heat-transfer fluid water with the temperature gradient of
75/65 C and one-sided lateral connection (supply) of the heat-transfer fluid (water) at the top are provided in
Table 1. Individual models of heating bodies are measured without cover.

Page 5 of 114

TESTING OVERPRESSURE
Units manufactured are subject to the pressure test performed in manufacturers facility using overpressure of
cold water equal to 1 MPa.

ASSEMBLY
In order to achieve required thermal power of heating bodies it is necessary to maintain the installation position
indicated on Fig. 3. In addition to this a minimum overlap of the window sill shall be adhered to.
Window sill overlap

Window sill

Wall

Floor
Fig. 3: Installation of Kalor heating bodies

Kalor heating bodies are connected to the distribution piping using roses provided with external right-hand or
left hand thread G 5/4 with G 1/8, G 1/4, G 3/8, G 1/2, G 3/4 and G 1 bores. Openings of the heating
body on the opposite side to the inlet and outlet connections of the heat-transfer fluid (water) are usually
terminated by plugs provided with external right-hand or left-hand thread G 5/4. The upper plug can be
provided with a bore with eccentrically positioned thread G 3/8 or G 1/4 for the air relief valve. Automatic air
relief valves are suitable for this purpose. Prior to combining the individual units supplied into the heating body
of required size it is necessary to perform a thorough cleaning of contact surfaces of sections and individual
connections shall be sealed by Clingerite, which is normally used during production and it is suitable both for
warm-water and steam systems. The sections shall be coupled with the torque of min. 180 Nm and max.
250 Nm.
Other installation data are provided in the section of instruction manual common for all models of heating bodies
manufactured.

Page 6 of 114

THERMAL POWER TABLES


FOR INDIVIDUAL MODELS OF HEATING BODIES

Page 7 of 114

WARM-WATER HEATING

Temperature gradient to CSN EN 442 2:1997


Temperature gradients

75/65 C
90/70 C
55/45 C

Page 8 of 114

Table 2: Thermal power for all models of Kalor heating bodies depending on the number of sections
tw1 = 90 C
tw2 = 70 C
ti
= 20 C

Warm-water heating

T h e r m a l p o w e r QN (W)
No. of
sections (n)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

350/160

500/70

500/110

500/160

900/70

900/160

198
289
379
469
559
649
740
830
920
1010
1100
1191
1281
1371
1461
1552
1642
1732
1822
1912
2003
2093
2183
2273
2363
2454
2544
2634
2724

166
233
300
367
434
501
568
635
702
769
836
903
970
1037
1104
1171
1238
1305
1372
1439
1506
1573
1640
1707
1774
1841
1908
1975
2042

198
289
379
469
559
649
740
830
920
1010
1100
1191
1281
1371
1461
1552
1642
1732
1822
1912
2003
2093
2183
2273
2363
2454
2544
2634
2724

259
376
494
612
729
847
965
1082
1200
1318
1435
1553
1671
1788
1906
2024
2141
2259
2377
2494
2612
2730
2847
2965
3083
3200
3318
3435
3553

261
364
468
572
675
779
883
986
1090
1194
1297
1401
1505
1608
1712
1816
1919
2023
2127
2230
2334
2438
2542
2645
2749
2853
2956
3060
3164

473
662
850
1038
1227
1415
1603
1792
1980
2168
2357
2545
2733
2922
3110
3298
3487
3675
3863
4052
4240
4428
4617
4805
4994
5182
5370
5559
5747

Page 9 of 114

Table 3: Thermal power of Kalor type heating bodies depending on the number of sections
tw1 = 55 C
tw2 = 45 C
ti
= 20 C

Warm-water heating

T h e r m a l p o w e r QN (W)
No. of
sections (n)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

350/160

500/70

500/110

500/160

900/70

900/160

83
121
159
197
235
273
311
349
387
425
463
501
539
576
614
652
690
728
766
804
842
880
918
956
994
1032
1070
1107
1145

70
98
127
155
184
212
240
269
297
325
354
382
411
439
467
496
524
552
581
609
638
666
694
723
751
779
808
836
865

83
121
159
197
235
273
311
349
387
425
463
501
539
576
614
652
690
728
766
804
842
880
918
956
994
1032
1070
1107
1145

109
158
208
257
307
356
406
455
505
554
603
653
702
752
801
851
900
950
999
1049
1098
1148
1197
1247
1269
1346
1395
1444
1494

107
150
193
235
278
321
363
406
449
492
534
577
620
662
705
748
790
833
876
918
961
1004
1047
1089
1132
1175
1217
1260
1303

191
267
343
419
495
571
647
723
799
875
951
1026
1102
1178
1254
1330
1406
1482
1558
1634
1710
1786
1862
1938
2014
2090
2166
2242
2318

Page 10 of 114

Table 4: Thermal power of heating bodies Kalor 350/160 and 500/110 depending on required air
temperature and number of sections
tw1 = 90 C
tw2 = 70 C

Warm-water heating

T h e r m a l p o w e r Q (W) at air temperature of ti (C)


No. of
sections (n)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

241
350
459
569
678
787
897
1006
1116
1225
1334
1444
1553
1662
1772
1881
1991
2100
2209
2319
2428
2537
2647
2756
2866
2975
3084
3194
3303

219
319
419
518
618
718
818
917
1017
1117
1216
1316
1416
1515
1615
1715
1841
1914
2014
2114
2213
2313
2413
2512
2612
2712
2811
2911
3011

207
301
395
489
583
677
771
865
959
1053
1147
1241
1334
1428
1522
1616
1710
1804
1898
1992
2086
2180
2274
2368
2462
2556
2650
2744
2838

198
289
379
469
559
649
740
830
920
1010
1100
1191
1281
1371
1461
1552
1642
1732
1822
1912
2033
2093
2183
2273
2363
2454
2544
2634
2724

190
277
363
450
536
623
709
795
882
968
1055
1141
1228
1314
1401
1487
1574
1660
1747
1833
1919
2006
2092
2179
2265
2352
2438
2525
2611

182
265
348
430
513
596
679
761
844
927
1010
1092
1175
1258
1341
1423
1506
1589
1672
1754
1837
1920
2003
2085
2168
2251
2334
2416
2499

Page 11 of 114

Table 5: Thermal power of heating bodies Kalor 350/160 and 500/110 depending on required air
temperature and number of sections
tw1 = 55 C
tw2 = 45 C

Warm-water heating

T h e r m a l p o w e r Q (W) at air temperature of ti (C)


No. of
sections (n)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

120
174
228
283
337
391
446
500
554
609
663
717
772
826
880
935
989
1043
1098
1152
1206
1261
1315
1369
1424
1478
1532
1587
1641

101
147
193
239
285
331
377
423
469
515
561
607
653
699
745
791
837
883
929
975
1021
1067
1113
1159
1205
1251
1297
1343
1389

90
132
173
214
255
296
337
378
419
460
502
543
584
625
666
707
748
789
830
872
913
954
995
1036
1077
1118
1159
1200
1242

83
121
159
197
235
273
311
349
387
425
463
501
539
576
614
652
690
728
766
804
842
880
918
956
994
1032
1070
1107
1145

77
111
146
181
216
251
285
320
355
390
424
549
494
529
564
598
633
668
703
738
772
807
842
877
912
946
981
1016
1051

70
101
133
165
197
228
260
292
323
355
387
419
450
482
514
545
577
609
641
672
704
736
767
799
831
863
894
926
958

Page 12 of 114

Table 6: Thermal power of heating bodies Kalor 500/70 depending on required air temperature and
number of sections
tw1 = 90 C
tw2 = 70 C

Warm-water heating

T h e r m a l p o w e r Q (W) at air temperature of ti (C)


No. of
sections (n)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

15

18

20

22

24

183
257
331
405
479
553
627
701
775
849
923
997
1071
1145
1219
1293
1367
1441
1515
1589
1663
1737
1811
1885
1959
2033
2107
2181
2255

172
242
312
382
452
521
591
661
731
801
870
940
1010
1080
1150
1219
1289
1359
1429
1499
1568
1638
1708
1778
1848
1917
1987
2057
2127

166
233
300
367
434
501
568
635
702
769
836
903
970
1037
1104
1171
1238
1305
1372
1439
1506
1573
1640
1707
1774
1841
1908
1975
2042

159
223
287
352
416
480
544
609
673
737
801
866
930
994
1058
1123
1187
1251
1315
1380
1444
1508
1572
1637
1701
1765
1829
1894
1958

152
214
275
337
398
460
521
583
644
706
767
829
890
952
1013
1075
1136
1198
1259
1321
1382
1444
1505
1567
1628
1690
1751
1813
1875

Page 13 of 114

Table 7: Thermal power of heating bodies Kalor 500/70 depending on required air temperature and
number of sections
tw1 = 55 C
tw2 = 45 C

Warm-water heating

T h e r m a l p o w e r Q (W) at air temperature of ti (C)


No. of
sections (n)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

15

18

20

22

24

85
119
154
188
222
257
291
325
360
394
428
463
497
531
566
600
634
669
703
737
772
806
841
875
909
944
1012
1047
1047

76
107
137
168
199
230
260
291
322
353
383
414
445
476
506
537
568
598
629
660
691
721
752
783
814
844
906
937
937

70
98
127
155
184
212
240
269
297
325
354
382
411
439
467
496
524
552
581
609
638
666
694
723
751
779
836
865
865

64
90
116
142
169
195
221
247
273
299
325
351
377
403
429
455
481
507
533
559
585
611
637
663
689
715
768
794
794

59
82
106
130
154
178
201
225
249
273
296
320
344
368
391
415
439
463
486
510
534
558
581
605
629
653
700
724
724

Page 14 of 114

Table 8: Thermal power of heating bodies Kalor 500/160 depending on required air temperature and
number of sections
tw1 = 90 C
tw2 = 70 C

Warm-water heating

T h e r m a l p o w e r Q (W) at air temperature of ti (C)


No. of
sections (n)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

314
456
599
742
884
1027
1170
1312
1455
1598
1740
1883
2026
2168
2311
2454
2596
2739
2882
3024
3167
3310
3452
3595
3738
3880
4023
4166
4308

286
416
546
676
806
936
1066
1196
1326
1456
1586
1716
1846
1977
2107
2237
2367
2497
2627
2757
2887
3017
3147
3277
3407
3537
3667
3797
3927

270
392
515
637
760
883
1005
1128
1250
1373
1495
1618
1741
1863
1986
2108
2231
2353
2476
2599
2721
2844
2966
3089
3211
3334
3457
3579
3702

259
376
494
612
729
847
965
1082
1200
1318
1435
1553
1671
1788
1906
2024
2141
2259
2377
2494
2612
2730
2847
2965
3083
3200
3318
3435
3553

248
361
474
586
699
812
925
1037
1150
1263
1376
1489
1601
1714
1827
1940
2052
2165
2278
2391
2504
2616
2729
2842
2955
3067
3180
3293
3406

237
345
453
561
669
777
885
993
1101
1209
1317
1425
1533
1641
1748
1856
1964
2072
2180
2288
2396
2504
2612
2720
2828
2936
3044
3152
3260

Page 15 of 114

Table 9: Thermal power of heating bodies Kalor 500/160 depending on required air temperature and
number of sections
tw1 = 55 C
tw2 = 45 C

Warm-water heating

T h e r m a l p o w e r Q (W) at air temperature of ti (C)


No. of
sections (n)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

156
227
298
369
439
510
581
652
723
794
865
936
1006
1077
1148
1219
1290
1361
1432
1503
1573
1644
1715
1786
1857
1928
1999
2070
2140

132
192
252
312
372
432
492
552
612
672
732
792
852
912
972
1032
1092
1152
1212
1272
1332
1392
1451
1511
1571
1631
1691
1751
1811

118
172
225
279
332
386
440
493
547
601
654
708
761
815
869
922
976
1030
1083
1137
1190
1244
1298
1351
1405
1459
1512
1566
1619

109
158
208
257
307
356
406
455
505
554
603
653
702
752
801
851
900
950
. 999
1049
1098
1148
1197
1247
1296
1346
1395
1444
1494

100
145
191
236
281
327
372
417
463
508
554
599
644
690
735
781
826
871
917
962
1007
1053
1098
1144
1189
1234
1280
1325
1370

91
132
174
215
256
298
339
381
422
463
505
546
587
629
670
711
753
794
836
877
918
960
1001
1042
1084
1125
1166
1208
1249

Page 16 of 114

Table 10: Thermal power of heating bodies Kalor 900/70 depending on required air temperature and
number of sections
tw1 = 90 C
tw2 = 70 C

Warm-water heating

T h e r m a l p o w e r Q (W) at air temperature of ti (C)


No. of
sections (n)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

317
444
570
696
823
949
1075
1201
1328
1454
1580
1707
1833
1959
2086
2212
2338
2464
2591
2717
2843
2970
3096
3222
3348
3475
3601
3727
3854

289
404
518
633
748
863
978
1098
1208
1322
1437
1552
1667
1782
1897
2012
2127
2241
2356
2471
2586
2701
2810
2931
3045
3160
3275
3390
3505

272
380
488
596
704
812
920
1029
1137
1245
1353
1461
1569
1677
1785
1894
2002
2110
2218
2326
2434
2542
2650
2759
2867
2975
3083
3191
3299

261
364
468
572
675
779
883
986
1090
1194
1297
1401
1505
1608
1712
1816
1919
2023
2127
2230
2334
2438
2542
2645
2749
2853
2956
3060
3164

249
349
448
547
647
746
845
944
1044
1143
1242
1342
1441
1540
1639
1739
1838
1937
2036
2136
2235
2334
2434
2433
2632
2731
2831
2930
3029

239
333
428
523
618
713
808
903
998
1093
1188
1283
1378
1472
1567
1662
1757
1852
1947
2042
2137
2232
2327
2422
2517
2611
2706
2801
2896

Page 17 of 114

Table 11: Thermal power of heating bodies Kalor 900/70 depending on required air temperature and
number of sections
tw1 = 55 C
tw2 = 45 C

Warm-water heating

T h e r m a l p o w e r Q (W) at air temperature of ti (C)


No. of
sections (n)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

155
217
278
340
402
464
525
587
649
710
772
834
895
957
1019
1081
1142
1204
1266
1327
1389
1451
1513
1574
1636
1698
1759
1821
1883

131
183
235
287
339
391
443
495
547
599
651
703
755
807
859
911
963
1015
1067
1119
1171
1223
1275
1327
1379
1431
1483
1535
1587

117
163
209
256
302
348
395
441
488
534
580
627
673
719
766
812
858
905
951
998
1044
1090
1137
1183
1229
1276
1322
1369
1415

107
150
193
235
278
321
363
406
449
492
534
577
620
662
705
748
790
833
876
918
961
1004
1047
1089
1132
1175
1217
1260
1303

98
137
176
215
255
294
333
372
411
450
489
528
567
606
645
685
724
763
802
841
880
919
958
997
1036
1075
1114
1154
1193

89
125
160
196
232
267
303
338
374
409
445
480
516
551
587
623
658
694
729
765
800
836
871
907
943
978
1014
1049
1085

Page 18 of 114

Table 12: Thermal power of heating bodies Kalor 900/160 depending on required air temperature and
number of sections
tw1 = 90 C
tw2 = 70 C

Warm-water heating

T h e r m a l p o w e r Q (W) at air temperature of ti (C)


No. of
sections (n)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

579
810
1040
1271
1501
1732
1962
2193
2423
2654
2884
3115
3345
3576
3806
4037
4267
4497
4728
4958
5189
5419
5650
5880
6111
6341
6572
6802
7033

526
735
944
1153
1362
1571
1781
1990
2199
2408
2617
2826
3036
3245
3454
3663
3872
4081
4291
4500
4709
4918
5127
5336
5546
5755
5964
6173
6382

494
691
887
1084
1280
1477
1674
1870
2067
2264
2460
2657
2853
3050
3247
3443
3640
3836
4033
4230
4426
4623
4819
5016
5213
5409
5606
5802
5999

473
662
850
1038
1227
1415
1603
1792
1980
2168
2357
2545
2733
2922
3110
3298
3487
3675
3863
4052
4240
4428
4617
4805
4994
5182
5370
5559
5747

453
633
813
993
1173
1354
1534
1714
1894
2074
2254
2435
2615
2795
2975
3155
3335
3515
3696
3876
4056
4236
4416
4596
4777
4957
5137
5317
5497

432
604
777
949
1121
1293
1465
1637
1809
1981
2153
2325
2497
2669
2841
3013
3185
3358
3530
3702
3874
4046
4218
4390
4562
4734
4906
5078
5250

Page 19 of 114

Table 13: Thermal power of heating bodies Kalor 900/160 depending on required air temperature and
number of sections
tw1 = 55 C
tw2 = 45 C

Warm-water heating

T h e r m a l p o w e r Q (W) at air temperature of ti (C)


No. of
sections
(n)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

278
389
500
610
721
832
943
1053
1164
1275
1386
1496
1607
1718
1828
1936
2050
2161
2271
2382
2493
2604
2714
2825
2936
3047
3157
3268
3379

234
327
420
512
605
698
727
884
977
1070
1163
1256
1349
1442
1535
1628
1721
1814
1907
2000
2093
2186
2279
2372
2465
2558
2651
2744
2836

208
290
373
456
538
621
704
786
869
952
1034
1117
1200
1282
1365
1448
1530
1613
1696
1778
1861
1944
2026
2109
2192
2274
2357
2440
2522

191
267
343
419
495
571
647
723
799
875
951
1026
1102
1178
1254
1330
1406
1482
1558
1634
1710
1786
1862
1938
2014
2090
2166
2242
2318

174
244
313
383
452
521
591
660
730
799
868
938
1007
1077
1146
1215
1285
1354
1424
1493
1562
1632
1701
1771
1840
1909
1979
2048
2118

158
221
284
347
410
473
536
599
662
725
788
851
914
977
1040
1103
1166
1229
1292
1255
1418
1481
1544
1607
1670
1733
1796
1859
1922

Page 20 of 114

STEAM HEATING

Steam condensation temperature

tpk = 101.5 C

Page 21 of 114

Table 14: Thermal power for all models of Kalor heating bodies depending on the number of sections
Steam heating

tpk
ti

= 101.5 C
= 20 C

T h e r m a l p o w e r QN (W)
No. of sections
(n)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

350/160

500/110

500/160

900/70

900/160

328
478
627
776
925
1075
1224
1373
1522
1672
1821
1970
2119
2269
2418
2567
2716
2866
3015
3164
3313
3463
3612
3761
3910
4060
4209
4358
4507

335
488
640
793
945
1098
1250
1403
1555
1707
1860
2012
2165
2317
2470
2622
2775
2927
3080
3232
3385
3537
3689
3842
3994
4147
4299
4452
4604

426
620
814
1008
1202
1396
1590
1783
1977
2171
2365
2559
2753
2946
3140
3334
3528
3722
3916
4110
4303
4497
4691
4885
5079
5273
5466
5660
5854

454
634
815
995
1175
1356
1536
1717
1897
2078
2258
2439
2619
2799
2980
3160
3341
3521
3702
3882
4063
4243
4423
4604
4784
4965
5145
5326
5506

737
1030
1323
1616
1909
2202
2495
2788
3081
3374
3667
3960
4253
4546
4839
5132
5425
5718
6011
6304
6597
6890
7183
7476
7769
8062
8355
8648
8941

Page 22 of 114

Table 15: Thermal power of heating bodies Kalor 350/160 depending on required air temperature and
number of sections
Steam heating

tpk

= 101.5 C

T h e r m a l p o w e r Q (W) at air temperature of ti (C)


No. of sections
(n)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

382
556
730
904
1078
1252
1426
1600
1774
1947
2121
2295
2469
2643
2817
2991
3165
3338
3512
3686
3860
4034
4208
4382
4556
4729
4903
5077
5251

355
517
678
839
1001
1162
1324
1485
1647
1808
1969
2131
2292
2454
2615
2777
2938
3100
3261
3422
3584
3745
3907
4068
4230
4391
4552
4717
4875

339
493
647
801
955
1109
1263
1418
1572
1726
1880
2034
2188
2342
2496
2650
2804
2958
3112
3266
3421
3575
3729
3883
4037
4191
4345
4499
4653

328
478
627
776
925
1075
1224
1373
1522
1672
1821
1970
2119
2269
2418
2567
2716
2766
3015
3164
3313
3463
3612
3761
3910
4060
4209
4358
4507

318
462
607
751
895
1040
1184
1329
1473
1618
1726
1907
2051
2195
2340
2484
2629
2773
2918
3062
3206
3351
3495
3640
3784
3929
4073
4217
4362

307
447
587
726
866
1005
1145
1285
1424
1564
1704
1843
1983
2123
2262
2402
2542
2681
2821
2961
3100
3240
3380
3519
3659
3799
3938
4078
4218

Page 23 of 114

Table 16: Thermal power of heating bodies Kalor 500/110 depending on required air temperature and
number of sections
Steam heating

tpk

= 101.5 C

T h e r m a l p o w e r Q (W) at air temperature of ti (C)


No. of sections
(n)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

392
570
749
927
1105
1283
1462
1640
1818
1996
2175
2353
2531
2710
2888
3066
3244
3423
3601
3779
3957
4136
4314
4492
4670
4849
5027
5205
5383

363
529
649
859
1024
1190
1355
1520
1685
1851
2016
2181
2346
2511
2677
2842
3007
3172
3338
3503
3668
3833
3998
4164
4329
4494
4659
4825
4990

347
504
662
819
977
1134
1292
1449
1607
1764
1922
2079
2237
2394
2552
2710
2867
3025
3182
3340
3497
3655
3812
3970
4127
4285
4442
4600
4757

335
488
640
793
945
1098
1250
1403
1555
1707
1860
2012
2165
2317
2470
2622
2775
2927
3080
3232
3385
3537
3689
3842
3994
4147
4299
4452
4604

324
472
619
767
914
1061
1209
1356
1504
1651
1799
1946
2093
2241
2388
2536
2683
2831
2978
3125
3273
3420
3568
3715
3862
4010
4157
4305
4452

313
456
598
741
883
1026
1168
1310
1453
1595
1738
1880
2023
2165
2307
2450
2592
2735
2877
3020
3162
3304
3447
3589
3732
3874
4017
4159
4302

Page 24 of 114

Table 17: Thermal power of heating bodies Kalor 500/160 depending on required air temperature and
number of sections
tPK = 101.5 C

Steam heating

T h e r m a l p o w e r Q (W) at air temperature of ti (C)


No. of sections
(n)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

497
723
949
1175
1401
1627
1853
2078
2304
2530
2756
2982
3208
3434
3660
3886
4112
4338
4564
4789
5015
5241
5467
5693
5919
6145
6371
6597
6823

461
671
881
1091
1300
1510
1720
1930
2139
2349
2559
2768
2978
3188
3398
3607
3817
4027
4237
4446
4656
4866
5076
5285
5495
5705
5914
6124
6334

440
640
841
1041
1241
1441
1641
1841
2042
2242
2442
2642
2842
3042
3243
3443
3643
3843
4043
4243
4444
4644
4844
5044
5244
5444
5645
5845
6045

426
620
814
1008
1202
1396
1590
1783
1977
2171
2365
2559
2753
2946
3140
3334
3528
3722
3916
4110
4303
4497
4691
4885
5079
5273
5466
5660
5854

413
600
788
975
1163
1351
1538
1726
1913
2101
2288
2476
2664
2851
3039
3226
3414
3601
3789
3977
4164
4352
4539
4727
4915
5102
5290
5477
5665

399
580
762
943
1124
1306
1487
1668
1850
2031
2213
2394
2575
2757
2938
3119
3301
3482
3663
3845
4026
4208
4389
4570
4752
4933
5114
5296
5477

Page 25 of 114

Table 18: Thermal power of heating bodies Kalor 900/70 depending on required air temperature and
number of sections
tPK = 101.5 C

Steam heating

T h e r m a l p o w e r Q (W) at air temperature of ti (C)


No. of sections
(n)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

529
736
946
1155
1365
1575
1784
1994
2203
2413
2622
2832
3042
3251
3461
3670
3880
4089
4299
4509
4718
4928
5137
5347
5556
5766
5976
6185
6395

490
685
880
1074
1269
1464
1659
1854
2049
2240
2439
2633
2828
3023
3218
3413
3608
3803
3998
4193
4387
4582
4777
4972
5167
5362
5557
5752
5947

468
654
840
1026
1213
1399
1585
1771
1957
2144
2330
2516
2702
2888
3075
3261
3447
3633
3819
4006
4192
4378
4564
4750
4936
5123
5309
5495
5681

454
634
815
995
1175
1356
1536
1717
1897
2078
2258
2436
2619
2799
2980
3160
3341
3521
3702
3882
4063
4243
4423
4604
4784
4965
5145
5326
5506

439
614
789
963
1138
1313
1488
1662
1837
2012
2187
2361
2536
2711
2885
3060
3235
3410
3584
3759
3937
4109
4283
4458
4633
4808
4982
5157
5332

425
594
763
932
1101
1270
1439
1608
1778
1947
2116
2116
2454
2623
2792
2961
3130
3299
3468
3637
3806
3976
4145
4314
4483
4652
4821
4990
5159

Page 26 of 114

Table 19: Thermal power of heating bodies Kalor 900/160 depending on required air temperature and
number of sections
tPK = 101.5 C

Steam heating

T h e r m a l p o w e r Q (W) at air temperature of ti (C)


No. of sections
(n)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

858
1200
1542
1883
2225
2566
2908
3249
3591
3933
4274
4616
4957
5299
5641
5982
6324
6665
7007
7348
7690
8032
8373
8715
9056
9398
9740
10081
10423

797
1114
1431
1748
2065
2382
2699
3016
3333
3650
3968
4285
4602
4919
5236
5553
5870
6187
6504
6821
7138
7455
7772
8089
8407
8724
9041
9358
9675

760
1063
1366
1668
1971
2273
2576
2878
3181
3484
3786
4089
4391
4694
4997
5299
5602
5904
6207
6510
6812
7115
7417
7720
8022
8325
8628
8930
9233

737
1030
1323
1616
1909
2202
2495
2788
3081
3374
3667
3960
4253
4546
4839
5132
5425
5718
6011
6304
6597
6890
7183
7476
7769
8062
8355
8648
8941

713
996
1280
1563
1847
2130
2414
2697
2981
3264
3548
3831
4114
4399
4682
4966
5249
5533
5816
6100
6383
6667
6950
7234
7518
7801
8085
8368
8652

689
963
1237
1511
1785
2060
2334
2608
2882
3156
3530
3704
3978
4253
4527
4801
5075
5349
5623
5897
6171
6446
6720
6994
7268
7542
7816
8090
8365

Page 27 of 114

CAST-IRON HEATING BODIES


KALOR 3

Page 28 of 114

KALOR

DESCRIPTION
Cast-iron heating body consisting of sections with extended transfer surface forming the front panel area of the
heating body connected into heating systems using steel nipples with external right-hand or left-hand thread
G 5/4 is manufactured in five sizes:
350/160 mm, 500/70 mm, 500/110 mm, 500/160 mm and 900/70 mm.
Heating bodies comply with CSN EN 442 1:1995 and CSN EN 442 2:1997. The material used is a grey
cast-iron corresponding to CSN EN 1561. The design of castings ensures a long life cycle of products.

350/160

500/70

500/110

500/160

900/70

Fig. 1: Heating sections of Kalor 3 type

USAGE
All heating bodies of Kalor 3 line are designed for warm-water central heating systems with gravity and forced
circulation of heating water with the highest operating temperature not exceeding 115 C and highest operating

Page 29 of 114

overpressure of up to 0.6 MPa. In addition to this all sizes except 500/70 mm are also designed for steam central
heating systems with the maximum operating overpressure of up to 0.07 MPa.

THERMAL AND TECHNICAL PARAMETERS


Both types of Kalor 3 are certified by SZ Brno (certificate No. 0-70-1265-006/40 and 0-95-0107/40). Thermal
and technical parameters of the heat-transfer fluid (water) have been verified experimentally in compliance with
CSN EN 442-1:1995 and CSN EN 442-2:1997 by the Structural Engineering Research Institute in Prague and
for the low-pressure steam by the State Research Institute of Machinery Design in Prague.
The basic technical properties are provided in Table 29. Indicated thermal power applies to the heat-transfer fluid
(water) with the temperature gradient of 90/70C. Connection of bodies is one-sided and the heat-transfer fluid is
supplied at the top. The body is measured without covers.
Tables 1 through 18 provide thermal power values for various numbers of sections (2 30), various room
temperatures, water temperature gradient of 55/45 C and steam heating.
Table 1: Significant thermal and technical parameters of Kalor 3 heating sections
Property

Symbol

350/160

500/70

500/110

500/160

900/70

total height
spacing
depth
width
connection
thread

H (mm)
h (mm)
B (mm)
L (mm)

430
350
160
60

580
500
70
60

580
500
110
60

580
500
160
60

980
900
70
60

5/4

5/4

5/4

5/4

5/4

M (kg/pc.)

4.90

3.70

4.70

6.20

6.10

SL (m /pc.)

0.208

0.163

0.215

0.290

0.240

V (dm3/pc.)

0.8

0.5

0.8

1.1

0.8

103.8
1782

78
1305

102.6
1688

134.7
2216

126.7
2084

1.251

1.26

1.255

1.294

1.306

weight
equivalent
heating area
water volume

thermal power QN1 (W/section)


thermal module QM (W/m)
temperature
m(-)
exponent

Fig. 2: Standard dimensions of Kalor 3 sections

Page 30 of 114

TESTING OVERPRESSURE
Units manufactured are subject to the pressure test performed in manufacturers facility using overpressure of
cold water equal to 1 MPa.

ASSEMBLY
In order to achieve required thermal power it is necessary to maintain the installation position indicated on
Fig. 9. In addition to this it is most beneficial to secure a minimum overlap of window sill from the viewpoint
of thermal power.
Window sill overlap

Window sill

Wall

Floor
Fig. 3: Installation of Kalor 3 heating bodies

Kalor 3 line heating bodies are connected to the distribution piping using roses provided with external thread
G 5/4 with G 3/8, G 1/2, G 3/4 and G 1 bores. When facing the front panel surface, the bodies are provided
on the left side with rose with right-hand thread and on the right side with rose with left-hand thread G 5/4.
Openings of the heating body on the opposite side to the connection are usually terminated by solid plugs
provided with external left-hand thread G 5/4. The upper plug can be provided with a bore with eccentrically
positioned thread G 1/4 for the air relief valve. Automatic air relief valves are suitable for this purpose. Prior to
combining the individual units supplied it is necessary to perform a thorough cleaning of contact surfaces of
sections. We recommend to seal joints by Clingerite, which is normally used during production and it is suitable
both for warm-water and steam systems. The sections shall be coupled with the torque of min. 180 Nm and max.
250 Nm.
Other installation data are provided in the section of instruction manual common for all models of heating bodies
manufactured.

Page 31 of 114

THERMAL POWER TABLES


FOR INDIVIDUAL MODELS OF HEATING BODIES

Page 32 of 114

WARM-WATER HEATING

Temperature gradient to CSN EN 442 2:1997


Temperature gradients

75/65 C
90/70 C
55/45 C

Page 33 of 114

Table 2: Thermal power for all models of Kalor 3 heating bodies depending on the number of sections
tw1 = 90 C
tw2 = 70 C
ti
= 20 C

Warm-water heating

T h e r m a l p o w e r QN (W)
No. of sections
(n)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

350/160

500/70

500/110

500/160

900/70

252
356
460
564
668
772
876
980
1084
1188
1292
1396
1500
1604
1708
1812
1916
2020
2124
2228
2332
2436
2540
2644
2748
2852
2956
3060
3164

188
264
340
417
493
569
645
721
797
873
949
1026
1102
1178
1254
1330
1406
1482
1559
1635
1711
1787
1863
1939
2015
2091
2168
2244
2320

241
339
437
535
633
731
829
927
1026
1123
1221
1319
1417
1515
1613
1711
1809
1907
2005
2103
2201
2299
2397
2495
2593
2691
2789
2887
2985

318
445
572
699
826
935
1080
1207
1347
1474
1601
1728
1855
1982
2109
2236
2363
2490
2617
2744
2871
2998
3125
3252
3379
3506
3633
3760
3887

297
418
539
660
781
902
1023
1144
1267
1388
1509
1630
1751
1872
1993
2114
2235
2356
2477
2598
2719
2840
2961
3082
3203
3324
3445
3566
3687

Page 34 of 114

Table 3: Thermal power for all models of Kalor 3 heating bodies depending on the number of sections
tw1 = 55 C
tw2 = 45 C
ti
= 20 C

Warm-water heating

T h e r m a l p o w e r QN (W)
No. of sections
(n)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

350/160

500/70

500/110

500/160

900/70

107
150
193
236
279
322
365
408
455
498
541
584
627
670
713
756
799
842
885
928
971
1014
1057
1100
1143
1186
1229
1272
1315

79
110
142
174
206
237
269
301
333
365
396
428
460
492
524
555
587
619
651
683
714
746
778
810
841
873
905
937
969

101
142
183
224
265
306
347
388
430
471
512
553
594
635
676
717
758
799
840
881
922
963
1004
1045
1086
1127
1168
1209
1250

128
181
234
287
340
393
446
499
549
602
655
708
761
814
867
920
973
1026
1079
1132
1185
1238
1291
1344
1397
1450
1503
1556
1609

120
169
218
267
316
365
414
463
513
562
611
660
709
758
807
856
905
954
1003
1052
1101
1150
1199
1248
1297
1346
1395
1444
1494

Page 35 of 114

Table 4: Thermal power of heating bodies Kalor 3 350/160 depending on required air temperature and
number of sections
tw1 = 90 C
tw2 = 70 C

Warm-water heating

T h e r m a l p o w e r Q (W) at air temperature of ti (C)


No. of sections
(n)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

306
431
558
684
810
936
1062
1188
1314
1440
1566
1692
1818
1944
2070
2196
2322
2450
2575
2702
2828
2954
3080
3206
3332
3458
3585
3711
3837

279
394
509
623
738
853
968
1083
1198
1313
1428
1543
1658
1773
1888
2003
2118
2233
2348
2463
2578
2692
2808
2823
3037
3152
3267
3385
3497

262
371
479
587
696
804
912
1021
1129
1238
1346
1454
1562
1671
1779
1888
1996
2105
2213
2321
2429
2538
2646
2754
2851
2971
3080
3188
3297

252
356
460
564
668
772
876
980
1084
1188
1292
1396
1500
1604
1708
1812
1916
2020
2124
2228
2332
2436
2540
2644
2748
2852
2956
3060
3164

242
341
441
541
640
740
839
939
1039
1139
1238
1338
1438
1538
1637
1737
1837
1936
2036
2135
2235
2335
2435
2534
2635
2734
2733
2933
3033

231
387
422
518
613
708
804
899
995
1089
1185
1281
1376
1471
1566
1662
1758
1853
1948
2044
2139
2235
2330
2425
2520
2616
2712
2791
2782

Page 36 of 114

Table 5: Thermal power of heating bodies Kalor 3 350/160 depending on required air temperature and
number of sections
tw1 = 55 C
tw2 = 45 C

Warm-water heating

T h e r m a l p o w e r Q (W) at air temperature of ti (C)


No. of sections
(n)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

153
215
277
238
400
462
523
585
652
714
775
837
899
960
1022
1084
1145
1207
1268
1330
1392
1453
1515
1577
1638
1699
1618
1823
1885

130
182
234
286
338
390
443
495
552
604
656
708
760
813
864
916
969
1021
1073
1125
1178
1230
1282
1334
1386
1438
1469
1543
1594

116
163
209
256
303
349
396
442
493
540
587
633
679
723
773
820
866
913
954
1006
1053
1009
1146
1193
1293
1286
1224
1379
1426

107
150
193
236
279
322
365
408
455
498
541
584
627
670
713
756
799
842
885
928
971
1014
1057
1100
1143
1186
1129
1272
1315

98
138
177
217
256
295
335
374
417
457
496
536
575
615
654
694
733
772
812
851
891
930
970
1009
1049
1088
1036
1167
1206

89
126
161
197
233
269
305
341
381
416
452
488
524
560
596
632
668
704
740
776
812
848
884
920
956
992
944
1064
1100

Page 37 of 114

Table 6: Thermal power of heating bodies Kalor 3 500/70 depending on required air temperature and
number of sections
tw1 = 90 C
tw2 = 70 C

Warm-water heating

T h e r m a l p o w e r Q (W) at air temperature of ti (C)


No. of sections
(n)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

15

18

20

22

24

208
292
377
461
545
629
713
798
882
966
1050
1134
1219
1303
1387
1471
1555
1640
1724
1808
1892
1977
2061
2145
2229
2313
2398
2482
2566

196
275
355
434
513
593
672
751
831
910
990
1069
1148
1228
1307
1386
1466
1545
1624
1704
1783
1862
1942
2021
2100
2180
2259
2338
2418

188
264
340
417
493
569
645
721
797
873
949
1026
1102
1178
1254
1330
1406
1482
1559
1635
1711
1787
1863
1939
2015
2091
2168
2244
2320

180
253
326
399
472
545
618
691
764
837
910
983
1056
1129
1202
1275
1347
1420
1493
1566
1639
1712
1785
1858
1931
2004
2077
2150
2223

172
242
312
382
452
521
591
661
731
801
870
940
1010
1080
1150
1219
1289
1359
1429
1499
1568
1638
1708
1778
1848
1917
1987
2057
2127

Page 38 of 114

Table 7: Thermal power of heating bodies Kalor 3 500/70 depending on required air temperature and
number of sections
tw1 = 55 C
tw2 = 45 C

Warm-water heating

T h e r m a l p o w e r Q (W) at air temperature of ti (C)


No. of sections
(n)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

15

18

20

22

24

95
134
173
211
250
288
327
366
404
443
481
520
559
597
636
674
713
752
790
829
867
906
945
983
1022
1060
1099
1138
1176

85
120
154
189
223
258
292
327
361
396
430
465
499
533
568
602
637
671
706
740
775
809
844
878
913
947
982
1016
1051

79
110
142
174
206
237
269
301
333
365
396
428
460
492
524
555
587
619
651
683
714
746
778
810
841
873
905
937
969

72
101
130
159
189
218
247
276
305
334
363
393
422
451
480
509
538
567
597
626
655
684
713
742
771
801
830
859
888

66
92
119
145
172
198
225
251
278
304
331
358
384
411
437
464
490
517
543
570
596
623
650
676
703
729
756
782
809

Page 39 of 114

Table 8: Thermal power of heating bodies Kalor 3 500/110 depending on required air temperature and
number of sections
tw1 = 90 C
tw2 = 70 C

Warm-water heating

T h e r m a l p o w e r Q (W) at air temperature of ti (C)


No. of sections
(n)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

293
411
530
649
768
887
1005
1124
1245
1363
1482
1610
1720
1838
1957
2076
2195
2314
2433
2552
2671
2790
2809
3028
3147
3265
3384
3503
3622

266
375
483
592
700
808
916
1024
1134
1241
1350
1458
1566
1675
1783
1892
2000
2109
2217
2325
2434
2542
2650
2758
2867
2975
3084
3192
3300

251
353
455
557
660
762
864
966
1069
1170
1272
1374
1476
1579
1681
1783
1885
1987
2089
2119
2294
2396
2498
2600
2702
2804
2906
3008
3110

241
339
437
535
633
731
829
927
1026
1123
1221
1319
1417
1515
1613
1711
1809
1907
2005
2103
2201
2299
2397
2495
2593
2691
2789
2887
2985

231
325
419
513
607
701
795
888
983
1076
1170
1264
1358
1452
1546
1640
1734
1828
1922
2015
2109
2203
2297
2391
2485
2579
2673
2767
2860

221
311
401
491
581
670
760
850
941
1029
1119
1210
1300
1389
1479
1569
1659
1749
1839
1929
2019
2108
2198
2288
2378
2468
2558
2648
2737

Page 40 of 114

Table 9: Thermal power of heating bodies Kalor 3 500/110 depending on required air temperature and
number of sections
tw1 = 55 C
tw2 = 45 C

Warm-water heating

T h e r m a l p o w e r Q (W) at air temperature of ti (C)


No. of sections
(n)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

145
204
263
321
380
439
498
557
617
676
735
794
852
911
970
1029
1088
1147
1205
1264
1323
1382
1441
1499
1558
1617
1676
1735
1794

123
172
222
272
322
371
421
471
522
572
621
671
721
771
820
870
920
970
1019
1069
1119
1169
1218
1268
1318
1368
1418
1467
1517

110
154
199
243
287
322
376
420
466
510
555
599
644
688
723
778
822
867
912
955
1000
1044
1089
1133
1178
1222
1276
1311
1356

101
142
183
224
265
306
347
388
430
471
512
553
594
635
676
717
758
799
840
881
922
963
1004
1045
1086
1127
1168
1209
1250

93
130
168
205
243
281
318
356
394
432
470
507
545
582
620
658
695
733
770
808
846
883
921
958
996
1034
1071
1109
1146

84
119
153
187
222
256
290
324
359
394
428
462
496
531
565
599
633
668
702
736
771
805
839
873
908
942
976
1010
1045

Page 41 of 114

Table 10: Thermal power of heating bodies Kalor 3 500/160 depending on required air temperature and
number of sections
tw1 = 90 C
tw2 = 70 C

Warm-water heating

T h e r m a l p o w e r Q (W) at air temperature of ti (C)


No. of sections
(n)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

388
543
698
853
1008
1163
1318
1474
1644
1799
1954
2109
2265
2420
2575
2730
2885
3040
3195
3350
3505
3660
3815
3970
4125
4208
4450
4590
4745

353
494
635
775
916
1057
1198
1339
1494
1635
1776
1917
2058
2198
2339
2480
2621
2762
2903
3044
3184
3325
3466
3607
3748
3889
4029
4170
4311

332
403
594
729
862
944
1127
1259
1405
1538
1670
1803
1935
2068
2200
2333
2466
2598
2730
2863
2996
3128
3260
3393
3525
3658
3791
3923
4056

318
445
572
699
826
953
1080
1207
1347
1447
1601
1728
1855
1982
2109
2236
2363
2490
2617
2744
2871
2998
3125
3252
3379
3506
3633
3760
3887

304
426
548
669
791
912
1034
1155
1289
1411
1532
1654
1753
1897
2019
2140
2262
2383
2505
2626
2748
2869
2991
3113
3234
3356
3447
3599
3720

291
407
523
639
755
872
988
1104
1232
1348
1464
1580
1697
1813
1929
2045
2161
2277
2394
2510
2626
2742
2858
2974
3090
3207
3323
3439
3555

Page 42 of 114

Table 11: Thermal power of heating bodies Kalor 3 500/160 depending on required air temperature and
number of sections
tw1 = 55 C
tw2 = 45 C

Warm-water heating

T h e r m a l p o w e r Q (W) at air temperature of ti (C)


No. of sections
(n)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

186
263
340
417
493
570
647
724
797
874
950
1027
1104
1181
1258
1335
1412
1489
1566
1643
1720
1796
1873
1950
2027
2104
2181
2258
2335

156
221
286
350
415
480
545
609
670
735
800
864
929
994
1058
1123
1188
1253
1317
1382
1447
1511
1576
1641
1705
1770
1835
1899
1964

139
197
254
312
370
427
485
543
597
655
712
770
827
885
943
1000
1058
1115
1173
1231
1288
1346
1404
1461
1519
1576
1634
1692
1749

128
181
234
287
340
393
446
499
549
602
655
708
761
814
867
920
973
1026
1079
1132
1185
1238
1291
1344
1397
1450
1503
1556
1609

117
166
214
263
311
359
408
456
502
551
599
648
696
745
793
842
890
938
987
1035
1084
1132
1181
1229
1278
1326
1375
1423
1472

106
150
195
239
283
327
371
415
456
500
544
588
632
676
720
765
808
853
897
941
985
1029
1073
1117
1161
1205
1249
1293
1337

Page 43 of 114

Table 12: Thermal power of heating bodies Kalor 3 900/70 depending on required air temperature and
number of sections
tw1 = 90 C
tw2 = 70 C

Warm-water heating

T h e r m a l p o w e r Q (W) at air temperature of ti (C)


No. of sections
(n)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

363
511
659
807
955
1103
1251
1399
1590
1698
1846
1994
2142
2290
2438
2586
2733
2882
3029
3177
3325
3473
3621
3769
3917
4065
4213
4361
4509

329
464
598
733
867
1001
1136
1270
1340
1541
1675
1810
1944
2078
2213
2347
2481
2616
2750
2884
3019
3153
3287
3421
3556
3690
3825
3959
4093

310
436
563
689
815
942
1068
1194
1323
1449
1575
1701
1828
1954
2080
2207
2333
2459
2585
2712
2838
2964
3091
3217
3343
3470
3596
3722
3848

297
418
539
660
781
902
1023
1144
1667
1388
1509
1630
1751
1872
1993
2114
2235
2356
2477
2598
2719
2840
2961
3082
3203
3324
3445
3566
3687

284
400
516
632
747
863
979
1095
1212
1328
1444
1559
1675
1791
1907
2023
2138
2254
2370
2486
2601
2717
2833
2949
3064
3180
3296
3412
3527

271
382
493
603
714
824
935
1046
1158
1268
1379
1490
1600
1711
1821
1932
2042
2153
2264
2374
2485
2595
2706
2817
2744
3038
3148
3259
3369

Page 44 of 114

Table 13: Thermal power of heating bodies Kalor 3 900/70 depending on required air temperature and
number of sections
tw1 = 55 C
tw2 = 45 C

Warm-water heating

T h e r m a l p o w e r Q (W) at air temperature of ti (C)


No. of sections
(n)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

175
246
317
389
460
532
603
674
747
818
890
961
1032
1104
1175
1246
1318
1389
1460
1532
1603
1675
1746
1817
1889
1960
2031
2103
2174

147
207
267
327
387
446
506
566
627
687
747
807
867
927
987
1047
1107
1167
1227
1287
1347
1407
1466
1526
1586
1648
1706
1766
1826

131
184
237
291
344
397
450
504
558
612
665
724
771
825
878
931
986
1038
1091
1145
1198
1251
1305
1358
1411
1464
1518
1571
1624

120
169
218
267
316
365
414
463
513
562
611
660
709
758
807
856
905
954
1003
1052
1101
1150
1199
1248
1297
1346
1395
1444
1493

110
154
199
244
289
334
378
423
469
514
558
603
648
693
738
782
827
872
917
961
1006
1051
1096
1141
1185
1230
1275
1320
1364

100
140
181
222
262
303
344
384
426
466
507
548
588
629
670
710
751
791
832
873
913
954
995
1035
1074
1117
1157
1095
1132

Page 45 of 114

STEAM HEATING

Steam condensation temperature

tpk = 101.5 C

Page 46 of 114

Table 14: Thermal power for all models of Kalor 3 heating bodies depending on the number of sections
Steam heating

tpk
ti

= 101.5 C
= 20 C

T h e r m a l p o w e r QN (W)
No. of sections
(n)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

350/160

500/110

500/160

900/70

398
561
724
886
1049
1212
1375
1537
1700
1863
2026
2188
2351
2514
2676
2839
3002
3165
3327
3490
3653
3815
3978
4141
4303
4466
4629
4792
4954

385
543
701
858
1016
1173
1331
1489
1646
1804
1961
2119
2276
2434
2592
2749
2907
3064
3222
3379
3537
3694
3852
4010
4167
4325
4482
4640
4798

486
685
884
1083
1281
1480
1679
1877
2076
2275
2474
2672
2871
3070
3268
3467
3666
3865
4063
4262
4461
4659
4858
5057
5255
5454
5653
5852
6050

463
653
843
1033
1222
1412
1602
1791
1981
2171
2361
2550
2740
2930
3119
3309
3499
3688
3878
4068
4258
4447
4637
4827
5017
5206
5396
5586
5775

Page 47 of 114

Table 15: Thermal power of heating bodies Kalor 3 350/160 depending on required air temperature and
number of sections
Steam heating

tpk

= 101.5 C

T h e r m a l p o w e r Q (W) at air temperature of ti (C)


No. of sections
(n)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

472
665
858
1050
1243
1436
1629
1821
2014
2207
2490
2592
2786
2979
3171
3364
3557
3750
3942
4135
4328
4520
4713
4906
5098
5291
5484
5678
5870

434
612
790
967
1144
1322
1500
1677
1855
2033
2210
2387
2656
2743
2919
3097
3275
3453
3630
3808
3985
4162
4340
4518
4694
4872
5050
5228
5405

412
581
750
918
1087
1256
1425
1592
1761
1930
2099
2267
2436
2605
2772
2941
3110
3279
3447
3616
3785
3952
4121
4290
4458
4626
4796
4965
5132

398
561
724
886
1049
1212
1375
1537
1700
1863
2026
2188
2351
2514
2676
2839
3002
3165
3327
3490
3653
3815
3978
4141
4303
4466
4629
4792
4954

384
541
698
854
1012
1169
1326
1482
1639
1796
1954
2110
2267
2424
2580
2738
2895
3052
3208
3365
3524
3679
3836
3993
4149
4307
4464
4621
4777

370
521
673
823
974
1126
1277
1427
1579
1731
1882
2032
2184
2335
2486
2637
2789
2940
3090
3241
3393
3544
3695
3847
3997
4149
4300
4451
4602

Page 48 of 114

Table 16: Thermal power of heating bodies Kalor 3 500/110 depending on required air temperature and
number of sections
Steam heating

tpk

= 101.5 C

T h e r m a l p o w e r Q (W) at air temperature of ti (C)


No. of sections
(n)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

452
638
823
1006
1194
1378
1564
1750
1934
2120
2304
2490
2674
2858
3046
3230
3416
3600
3786
3970
4156
4340
4526
4712
4896
5082
5266
5452
5638

418
590
762
932
1104
1274
1446
1617
1788
1960
2130
2302
2472
2644
2816
2986
3158
3328
3500
3671
3842
4013
4184
4356
4527
4698
4869
5040
5212

398
564
725
887
1051
1213
1377
1540
1702
1866
2028
2192
2354
2518
2681
2843
3007
3169
3333
3494
3658
3821
3984
4147
4310
4473
4636
4799
4963

385
543
701
858
1016
1173
1331
1489
1646
1804
1961
2119
5576
2434
2592
2749
2907
3064
3222
3378
3537
3694
3852
4010
4167
4325
4482
4640
4798

372
525
677
829
982
1133
1286
1438
1590
1743
1894
2047
2199
2351
2504
2656
2808
2950
3113
3264
3417
3569
3721
3873
4025
4178
4320
4482
4635

360
506
654
800
947
1094
1241
1388
1535
1682
1828
1976
2122
2269
2417
2563
2710
2857
3004
3150
3298
3444
3591
3739
3885
4032
4179
4326
4473

Page 49 of 114

Table 17: Thermal power of heating bodies Kalor 3 500/160 depending on required air temperature and
number of sections
Steam heating

tpk

= 101.5 C

T h e r m a l p o w e r Q (W) at air temperature of ti (C)


No. of sections
(n)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

570
803
1036
1270
1502
1735
1968
2200
2434
2667
2900
3132
3365
3599
3830
4064
4297
4531
4763
4996
5229
5461
5695
5928
6160
6393
6626
6859
7092

527
743
959
1175
1390
1606
1822
2037
2253
2769
2685
2899
3115
3331
3546
3762
3978
4194
4409
4625
4841
5055
5272
5487
5702
5918
6134
6350
6564

502
708
914
1120
1324
1530
1736
1940
2146
2352
2558
2762
2968
3174
3379
3584
3790
3996
4200
4406
4612
4817
5022
5228
5433
5638
5844
6050
6255

486
685
884
1083
1281
1480
1679
1877
2076
2275
2474
2672
2871
3070
3268
3467
3666
3865
4063
4262
4461
4659
4858
5057
5255
5454
5653
5852
6050

470
662
854
1047
1238
1430
1623
1814
2006
2199
2391
2582
2775
2967
3159
3351
3543
3736
3927
4129
4312
4503
4695
4888
5079
5271
5464
5656
5847

454
639
825
1011
1196
1381
1567
1752
1937
2123
2309
2494
2679
2865
3050
3235
3421
3607
3792
3977
4163
4348
4534
4719
4904
5090
5275
5461
5646

Page 50 of 114

Table 18: Thermal power of heating bodies Kalor 3 900/70 depending on required air temperature and
number of sections
Steam heating

tpk

= 101.5 C

T h e r m a l p o w e r Q (W) at air temperature of ti (C)


No. of sections
(n)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

548
772
997
1222
1445
1670
1895
2118
2343
2568
2792
3016
3240
3465
3689
3914
4138
4362
4587
4811
5036
5250
5484
5709
5934
6157
6382
6607
6828

505
712
919
1126
1332
1539
1746
1952
2159
2366
2574
2782
2987
3194
3399
3607
3814
4020
4227
4434
4641
4847
5054
5261
5469
5675
5882
6089
6293

470
676
873
1070
1266
1462
1659
1855
2052
2249
2445
2641
2838
3035
3230
3427
3624
3820
4016
4213
4410
4606
4837
4999
5196
5392
5589
5785
5981

463
653
843
1033
1222
1412
1602
1791
1981
2171
2361
2550
2740
2930
3119
3309
3409
3688
3878
4068
4258
4447
4637
4827
5017
5206
5396
5586
5775

447
630
813
997
1179
1362
1545
1728
1911
2094
2278
2460
2643
2827
3009
3192
3289
3558
3741
3924
4108
4290
4473
4657
4840
5022
5206
5389
5571

430
607
784
960
1136
1313
1489
1665
1841
2018
2195
2370
2547
2724
2899
3076
3253
3428
3605
3782
3958
4134
4311
4487
4664
4840
5016
5193
5367

Page 51 of 114

CAST-IRON HEATING BODIES


TERMO

Page 52 of 114

TERMO
DESCRIPTION
Cast-iron heating sections with reduced water volume and extended face transfer surface forming the front panel
area connected into heating bodies using steel nipples with external right-hand or left-hand thread G 1 are
manufactured in six models :
500/95 mm, 500/130 mm, 623/95 mm, 623/130 mm, 813/95 mm and 813/130 mm.
Heating bodies comply with CSN EN 442 1:1995 and CSN EN 442 2:1997. The material used is a grey
cast-iron corresponding to CSN EN 1561. The design of castings ensures a long life cycle of products.

500/95

500/130

623/95

623/130

813/95

813/130

Fig. 10: Heating sections of Termo type

USAGE
All heating bodies of Termo line are designed for warm-water central heating systems with gravity and forced
circulation of heating water with the highest operating temperature not exceeding 120 C and highest operating
overpressure of up to 0.6 MPa. On request we are able to supply heating bodies with higher operating
overpressure up to 0.8 MPa. All models manufactured are approved for steam central heating systems with the
highest operating overpressure o up to 0.07 MPa.

Page 53 of 114

THERMAL AND TECHNICAL PARAMETERS


Table 1: Significant thermal and technical parameters of Termo heating sections
Property

Symbol

Unit

500/95

500/130

623/95

623/130

813/95

813/130

total height
spacing
depth
width
connection
thread

H
h
B
L

(mm)
(mm)
(mm)
(mm)

560
500
95
60

560
500
130
60

683
623
95
60

683
623
130
60

873
813
95
60

873
813
130
60

"

weight
equivalent
heating area
water volume

(kg/section)

4.35

5.36

5.08

6.46

6.70

8.80

0.192

0.254

0.230

0.303

0.310

0.380

thermal power
thermal module
temperature
exponent

SL

(m / section)
3

(dm /

0.6

0.8

0.8

1.0

1.0

1.3

s
L

(W/ section)
(W/m)

73.4
1213

91
1504

88.7
1466

108.8
1499

109.3
1807

136.1
2250

(-)

1.288

1.296

1.316

1.300

1.340

1.316

All Termo models are certified by SZ Brno. Thermal and technical parameters are verified experimentally in
compliance with CSN EN 442-2 : 1997.
Tables 2 through to 25 provide values of thermal power for individual models of cast-iron heating bodies for
number of sections ranging from 2 up to 30, variable required air temperature and temperature gradient of the
heat-transfer fluid (water) equal to 90/70C, 75/65C, 55/45C and steam.

Fig. 11: Standard dimensions of Termo sections

Page 54 of 114

Basic thermal and technical parameters for the heat-transfer fluid water with the temperature gradient of
75/65 C and one-sided lateral connection (supply) of the heat-transfer fluid (water) at the top are provided in
Table 8. Individual models of heating bodies are measured without cover.

TESTING OVERPRESSURE
Units manufactured are subject to the pressure test performed in manufacturers facility using overpressure of
cold water equal to 1 MPa (1.3 MPa for maximum operating overpressure of 0.8 MPa).

ASSEMBLY
In order to achieve required thermal power of individual heating bodies it is necessary to maintain
the installation position indicated on Fig. 12. In addition to this a minimum overlap of window sill shall be
adhered to.
Window sill overlap

Window sill

Wall

Floor
Fig. 12: Installation of Termo heating bodies

Termo hearting bodies are connected to the distribution piping using roses provided with external thread G 1
with G 1/8, G 1/4, G 3/8, G 1/2 and G 3/4 bores. When facing the front panel surface the bodies are
provided on the left side with rose with right-hand thread for connection of the heat-transfer fluid (water) and on
the right side with rose with left-hand thread for outlet of the heat-transfer fluid (water) G 1. The upper plug on
the opposite side to the connection of the heat-transfer fluid (water) can be provided with bore with eccentrically
positioned thread G 1/4 or G 3/8 for the air relief valve. Automatic air relief valves are suitable for this
purpose. Prior to combining the individual units supplied into the heating body of required size it is necessary to
perform a thorough cleaning of contact surfaces of sections and individual connections shall be sealed by
Clingerite, which is normally used during production and it is suitable both for warm-water and steam systems.
The sections shall be coupled with the torque of min. 180 Nm and max. 250 Nm.
Other installation data are provided in the section of instruction manual common for all models of heating bodies
manufactured.

Page 55 of 114

THERMAL POWER TABLES


FOR INDIVIDUAL MODELS OF HEATING BODIES

Page 56 of 114

WARM-WATER HEATING

Temperature gradient to CSN EN 442 2:1997


Temperature gradients

75/65 C
90/70 C
55/45 C

Page 57 of 114

Table 2: Thermal power of heating bodies Termo 500/95 depending on required air temperature and
number of sections
Warm-water heating

t1
t2

= 75 C
= 65 C

T h e r m a l p o w e r (W) at air temperature of ti (C)


No of sections
(Ns)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

220
309
398
487
576
665
754
843
932
1021
1110
1199
1288
1377
1466
1555
1644
1732
1821
1910
1999
2088
2177
2266
2355
2444
2533
2622
2711

196
276
355
435
514
594
673
752
832
911
991
1070
1150
1229
1309
1388
1467
1547
1626
1706
1785
1865
1944
2024
2103
2182
2262
2341
2421

183
256
330
404
478
552
626
699
773
847
921
995
1069
1143
1216
1290
1364
1438
1512
1586
1660
1733
1807
1881
1955
2029
2103
2176
2250

173
244
314
384
454
524
594
665
735
805
875
945
1016
1086
1156
1226
1296
1366
1437
1507
1577
1647
1717
1787
1858
1928
1998
2068
2138

164
231
298
364
431
497
564
630
697
763
830
896
963
1029
1096
1163
1229
1296
1362
1429
1495
1562
1628
1695
1761
1828
1895
1961
2028

156
219
281
344
407
470
533
596
659
722
785
848
911
974
1037
1100
1163
1226
1289
1352
1415
1478
1541
1604
1666
1729
1792
1855
1918

Page 58 of 114

Table 3: Thermal power of heating bodies Termo 500/95 depending on required air temperature and
number of sections
Warm-water heating

t1
t2

= 90 C
= 70 C

T h e r m a l p o w e r (W) at air temperature of tr (C)


No of sections
(Ns)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

269
378
486
595
704
813
921
1030
1139
1248
1356
1465
1574
1683
1791
1900
2009
2118
2226
2335
2444
2553
2661
2770
2879
2988
3096
3205
3314

244
343
442
540
639
738
837
935
1034
1133
1232
1330
1429
1528
1627
1725
1824
1923
2022
2120
2219
2318
2417
2515
2614
2713
2812
2910
3009

229
322
415
508
601
694
787
879
972
1065
1158
1251
1344
1437
1529
1622
1715
1808
1901
1994
2087
2180
2272
2365
2458
2551
2644
2737
2830

220
309
398
487
576
665
754
843
932
1021
1110
1199
1288
1377
1466
1555
1644
1732
1821
1910
1999
2088
2177
2266
2355
2444
2533
2622
2711

210
296
381
466
551
636
721
806
891
977
1062
1147
1232
1317
1402
1487
1573
1658
1743
1828
1913
1998
2083
2168
2254
2339
2424
2509
2594

201
282
364
445
526
608
689
770
852
933
1014
1096
1177
1258
1340
1421
1502
1584
1665
1746
1828
1909
1990
2072
2153
2234
2316
2397
2478

Page 59 of 114

Table 4: Thermal power of heating bodies Termo 500/95 depending on required air temperature and
number of sections
Warm-water heating

t1
t2

= 55 C
= 45 C

T h e r m a l p o w e r (W) at air temperature of tr (C)


No of sections
(Ns)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

130
182
235
287
340
392
445
497
550
602
654
707
759
812
864
917
969
1022
1074
1127
1179
1232
1284
1337
1389
1442
1494
1547
1599

109
153
197
241
285
330
374
418
462
506
550
594
638
682
726
771
815
859
903
947
991
1035
1079
1123
1167
1212
1256
1300
1344

97
136
175
215
254
293
332
372
411
450
489
529
568
607
646
686
725
764
803
843
882
921
960
1000
1039
1078
1117
1157
1196

89
125
161
197
234
270
306
342
378
414
450
486
522
558
594
630
667
703
739
775
811
847
883
919
955
991
1027
1063
1100

82
114
147
180
213
246
279
312
345
378
411
444
477
510
543
576
609
642
675
708
741
774
807
840
873
906
939
972
1005

74
104
134
164
194
224
254
284
314
344
374
403
433
463
493
523
553
583
613
643
673
703
733
763
793
823
853
883
913

Page 60 of 114

Table 5: Thermal power of heating bodies Termo 500/130 depending on required air temperature and
number of sections
Warm-water heating

t1
t2

= 75 C
= 65 C

T h e r m a l p o w e r (W) at air temperature of tr (C)


No of sections
(Ns)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

280
394
507
621
734
848
961
1075
1188
1301
1415
1528
1642
1755
1869
1982
2096
2209
2323
2436
2550
2663
2776
2890
3003
3117
3230
3344
3457

249
349
450
551
651
752
852
953
1054
1154
1255
1356
1456
1557
1658
1758
1859
1959
2060
2161
2261
2362
2463
2563
2664
2764
2865
2966
3066

230
323
416
510
603
696
789
882
975
1068
1162
1255
1348
1441
1534
1627
1720
1814
1907
2000
2093
2186
2279
2372
2466
2559
2652
2745
2838

218
306
395
483
571
659
747
836
924
1012
1100
1189
1277
1365
1453
1542
1630
1718
1806
1895
1983
2071
2159
2248
2336
2424
2512
2600
2689

206
290
373
456
540
623
707
790
873
957
1040
1124
1207
1290
1374
1457
1541
1624
1707
1791
1874
1958
2041
2124
2208
2291
2375
2458
2542

194
273
352
430
509
588
666
745
824
902
981
1060
1138
1217
1296
1374
1453
1531
1610
1689
1767
1846
1925
2003
2082
2161
2239
2318
2397

Page 61 of 114

Table 6: Thermal power of heating bodies Termo 500/130 depending on required air temperature and
number of sections
Warm-water heating

t1
t2

= 90 C
= 70 C

T h e r m a l p o w e r (W) at air temperature of tr (C)


No of sections
(Ns)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

347
487
627
768
908
1048
1189
1329
1469
1610
1750
1890
2031
2171
2311
2452
2592
2732
2873
3013
3153
3294
3434
3574
3715
3855
3995
4136
4276

313
440
566
693
820
947
1073
1200
1327
1453
1580
1707
1833
1960
2087
2214
2340
2467
2594
2720
2847
2974
3100
3227
3354
3481
3607
3734
3861

293
412
531
649
768
887
1006
1124
1243
1362
1480
1599
1718
1837
1955
2074
2193
2311
2430
2549
2667
2786
2905
3024
3142
3261
3380
3498
3617

280
394
507
621
734
848
961
1075
1188
1301
1415
1528
1642
1755
1869
1982
2096
2209
2323
2436
2550
2663
2776
2890
3003
3117
3230
3344
3457

268
376
484
592
701
809
917
1026
1134
1242
1350
1459
1567
1675
1783
1892
2000
2108
2217
2325
2433
2541
2650
2758
2866
2974
3083
3191
3299

255
358
461
564
668
771
874
977
1080
1183
1287
1390
1493
1596
1699
1802
1906
2009
2112
2215
2318
2421
2524
2628
2731
2834
2937
3040
3143

Page 62 of 114

Table 7: Thermal power of heating bodies Termo 500/130 depending on required air temperature and
number of sections
Warm-water heating

t1
t2

= 55 C
= 45 C

T h e r m a l p o w e r (W) at air temperature of tr (C)


No of sections
(Ns)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

160
225
290
355
420
485
550
614
679
744
809
874
939
1004
1068
1133
1198
1263
1328
1393
1458
1523
1587
1652
1717
1782
1847
1912
1977

133
187
241
295
349
403
457
511
565
619
673
727
781
835
889
943
997
1051
1105
1159
1213
1266
1320
1374
1428
1482
1536
1590
1644

118
166
213
261
309
356
404
452
499
547
595
642
690
738
785
833
881
929
976
1024
1072
1119
1167
1215
1262
1310
1358
1405
1453

108
151
195
239
282
326
370
413
457
500
544
588
631
675
719
762
806
849
893
937
980
1024
1068
1111
1155
1198
1242
1286
1329

98
138
177
217
257
296
336
376
415
455
495
534
574
614
653
693
733
772
812
852
891
931
971
1010
1050
1090
1129
1169
1209

89
124
160
196
232
268
303
339
375
411
447
482
518
554
590
626
662
697
733
769
805
841
876
912
948
984
1020
1055
1091

Page 63 of 114

Table 8: Thermal power of heating bodies Termo 623/95 depending on required air temperature and
number of sections
Warm-water heating

t1
t2

= 75 C
= 65 C

T h e r m a l p o w e r (W) at air temperature of tr (C)


No of sections
(Ns)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

280
393
507
620
733
847
960
1073
1187
1300
1413
1526
1640
1753
1866
1980
2093
2206
2320
2433
2546
2660
2773
2886
2999
3113
3226
3339
3453

249
349
450
551
651
752
853
953
1054
1155
1255
1356
1456
1557
1658
1758
1859
1960
2060
2161
2262
2362
2463
2564
2664
2765
2865
2966
3067

230
324
417
510
603
697
790
883
976
1070
1163
1256
1349
1443
1536
1629
1722
1815
1909
2002
2095
2182
2282
2375
2468
2561
2655
2748
2841

218
307
395
484
572
660
749
837
926
1014
1102
1191
1279
1367
1456
1544
1633
1721
1809
1898
1986
2075
2163
2251
2340
2428
2516
2605
2693

207
290
374
457
541
625
708
792
875
959
1043
1126
1210
1293
1377
1461
1544
1628
1712
1795
1879
1962
2064
2130
2213
2297
2380
2464
2548

195
274
353
432
511
589
668
747
826
905
984
1063
1142
1221
1299
1378
1457
1536
1615
1694
1773
1852
1931
2010
2088
2167
2246
2325
2404

Page 64 of 114

Table 9: Thermal power of heating bodies Termo 623/95 depending on required air temperature and
number of sections
Warm-water heating

t1
t2

= 90 C
= 70 C

T h e r m a l p o w e r (W) at air temperature of tr (C)


No of sections
(Ns)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

345
485
625
765
905
1044
1184
1324
1464
1604
1743
1883
2023
2163
2303
2442
2582
2722
2862
3002
3141
3281
3421
3561
3701
3840
3980
4120
4260

312
439
565
691
818
944
1070
1197
1323
1450
1576
1702
1829
1955
2081
2208
2334
2461
2587
2713
2840
2966
3092
3219
3345
3471
3598
3724
3851

293
411
530
648
767
885
1004
1122
1241
1359
1478
1596
1715
1833
1952
2070
2189
2307
2426
2544
2663
2781
2900
3018
3137
3255
3374
3492
3610

280
393
507
620
733
847
960
1073
1187
1300
1413
1526
1640
1753
1866
1980
2093
2206
2320
2433
2546
2660
2773
2886
2999
3113
3226
3339
3453

267
376
484
592
700
808
917
1025
1123
1241
1349
1458
1566
1674
1782
1890
1999
2107
2215
2323
2431
2540
2648
2756
2864
2972
3080
3189
3297

255
358
461
564
667
771
874
977
1080
1183
1286
1389
1493
1596
1699
1802
1905
2008
2112
2215
2318
2421
2524
2627
2730
2834
2937
3040
3143

Page 65 of 114

Table 10: Thermal power of heating bodies Termo 623/95 depending on required air temperature and
number of sections
Warm-water heating

t1
t2

= 55 C
= 45 C

T h e r m a l p o w e r (W) at air temperature of tr (C)


No of sections
(Ns)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

161
226
292
357
422
487
552
618
683
748
813
879
944
1009
1074
1139
1205
1270
1335
1400
1465
1531
1596
1661
1726
1792
1857
1922
1987

134
189
243
297
352
406
461
515
569
624
678
732
787
841
895
950
1004
1059
1113
1167
1222
1276
1330
1385
1439
1494
1548
1602
1657

119
167
215
263
311
360
408
456
504
552
600
648
696
744
793
841
889
937
985
1033
1081
1129
1178
1226
1274
1322
1370
1418
1466

109
153
197
241
285
329
373
417
461
506
550
594
638
682
726
770
814
858
902
946
990
1034
1078
1122
1167
1211
1255
1299
1343

99
139
179
219
260
300
340
380
420
460
500
540
580
621
661
701
741
781
821
861
901
942
982
1022
1062
1102
1142
1182
1222

90
126
162
198
235
271
307
343
380
416
452
488
525
561
597
634
670
706
742
779
815
851
887
924
960
996
1032
1069
1105

Page 66 of 114

Table 11: Thermal power of heating bodies Termo 623/130 depending on required air temperature and
number of sections
Warm-water heating

t1
t2

= 75 C
= 65 C

T h e r m a l p o w e r (W) at air temperature of tr (C)


No of sections
(Ns)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

330
464
598
732
865
999
1133
1267
1400
1534
1668
1801
1935
2069
2203
2336
2470
2604
2737
2871
3005
3139
3272
3406
3540
3674
3807
3941
4075

295
414
533
652
772
891
1010
1129
1249
1368
1487
1606
1726
1845
1964
2083
2202
2322
2441
2560
2679
2799
2918
3037
3156
3276
3395
3514
3633

274
384
495
606
717
827
938
1049
1160
1270
1381
1492
1603
1713
1824
1935
2046
2156
2267
2378
2489
2599
2710
2821
2931
3042
3153
3264
3374

260
365
470
575
681
786
891
996
1101
1206
1312
1417
1522
1627
1732
1837
1942
2048
2153
2258
2363
2468
2573
2679
2784
2889
2994
3099
3204

246
346
446
545
645
745
844
944
1044
1143
1243
1342
1442
1542
1641
1741
1841
1940
2040
2140
2239
2339
2439
2538
2638
2738
2837
2937
3037

233
327
421
515
610
704
798
892
987
1081
1175
1269
1363
1458
1552
1646
1740
1835
1929
2023
2117
2211
2306
2400
2494
2588
2683
2777
2871

Page 67 of 114

Table 12: Thermal power of heating bodies Termo 623/130 depending on required air temperature and
number of sections
Warm-water heating

t1
t2

= 90 C
= 70 C

T h e r m a l p o w e r (W) at air temperature of tr (C)


No of sections
(Ns)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

405
569
733
896
1060
1224
1388
1552
1716
1879
2043
2207
2371
2535
2699
2863
3026
3190
3354
3518
3682
3846
4009
4173
4337
4501
4665
4829
4993

367
516
664
813
962
1110
1259
1407
1556
1705
1853
2002
2150
2299
2448
2596
2745
2893
3042
3191
3339
3488
3636
3785
3934
4082
4231
4379
4528

345
485
624
764
904
1043
1183
1322
1462
1602
1741
1881
2021
2160
2300
2439
2579
2719
2858
2998
3138
3277
3417
3557
3696
3836
3975
4115
4255

330
464
598
732
865
999
1133
1267
1400
1534
1668
1801
1935
2069
2203
2336
2470
2604
2737
2871
3005
3139
3272
3406
3540
3674
3807
3941
4075

316
444
572
700
828
955
1083
1211
1339
1467
1595
1723
1851
1978
2106
2234
2362
2490
2618
2746
2874
3002
3129
3257
3385
3513
3641
3769
3897

302
424
546
668
790
912
1034
1156
1279
1401
1523
1645
1767
1889
2011
2133
2255
2370
2500
2622
2744
2866
2988
3110
3232
3354
3476
3599
3721

Page 68 of 114

Table 13: Thermal power of heating bodies Termo 623/130 depending on required air temperature and
number of sections
Warm-water heating

t1
t2

= 55 C
= 45 C

T h e r m a l p o w e r (W) at air temperature of tr (C)


No of sections
(Ns)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

194
272
350
429
507
586
664
742
821
899
977
1056
1134
1213
1291
1369
1448
1526
1604
1683
1761
1839
1918
1996
2075
2153
2231
2310
2388

162
228
294
360
425
491
557
623
688
754
820
885
951
1017
1083
1148
1214
1280
1345
1411
1477
1543
1608
1674
1740
1806
1871
1937
2003

144
203
261
320
378
436
495
553
612
670
728
787
845
904
962
1020
1079
1137
1196
1254
1312
1371
1429
1488
1546
1604
1663
1721
1780

133
186
240
293
347
401
454
508
562
615
669
723
776
830
884
937
991
1044
1098
1152
1205
1259
1313
1366
1420
1474
1527
1581
1635

121
170
219
268
317
366
415
464
513
562
611
660
709
758
807
856
905
954
1003
1052
1101
1150
1199
1248
1297
1346
1395
1444
1493

110
154
199
243
287
332
376
421
465
510
554
598
643
687
732
776
821
865
909
954
998
1043
1087
1132
1176
1220
1265
1309
1354

Page 69 of 114

Table 14: Thermal power of heating bodies Termo 813/95 depending on required air temperature and
number of sections
Warm-water heating

t1
t2

= 75 C
= 65 C

T h e r m a l p o w e r (W) at air temperature of tr (C)


No of sections
(Ns)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

336
472
608
744
880
1016
1152
1288
1424
1560
1696
1832
1968
2104
2241
2377
2513
2649
2785
2921
3057
3193
3329
3465
3601
3737
3873
4009
4145

299
421
542
663
784
905
1026
1148
1269
1390
1511
1632
1753
1875
1996
2117
2238
2359
2480
2602
2723
2844
2965
3086
3207
3329
3450
3571
3692

278
390
503
615
728
840
953
1065
1178
1290
1402
1515
1627
1740
1852
1965
2077
2190
2302
2415
2527
2639
2752
2864
2977
3089
3202
3314
3427

264
371
477
584
691
797
904
1011
1118
1224
1331
1438
1545
1651
1758
1865
1972
2078
2185
2292
2399
2505
2612
2719
2826
2932
3039
3146
3253

250
351
452
553
654
755
856
958
1059
1160
1261
1362
1463
1564
1665
1766
1867
1969
2070
2171
2272
2373
2474
2575
2676
2777
2879
2980
3081

236
332
427
523
618
714
809
905
1000
1096
1191
1287
1383
1478
1574
1669
1765
1860
1956
2051
2147
2242
2338
2434
2529
2625
2720
2816
2911

Page 70 of 114

Table 15: Thermal power of heating bodies Termo 813/95 depending on required air temperature and
number of sections
Warm-water heating

t1
t2

= 90 C
= 70 C

T h e r m a l p o w e r (W) at air temperature of tr (C)


No of sections
(Ns)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

413
580
747
914
1081
1247
1414
1581
1748
1915
2082
2249
2416
2583
2750
2917
3084
3251
3418
3585
3752
3919
4086
4253
4420
4587
4754
4921
5088

374
525
677
828
979
1130
1282
1433
1584
1736
1887
2038
2190
2341
2492
2643
2795
2946
3097
3249
3400
3551
3703
3854
4005
4156
4308
4459
4610

351
493
635
777
919
1062
1204
1346
1488
1630
1772
1914
2056
2198
2340
2482
2625
2767
2909
3051
3193
3335
3477
3619
3761
3903
4045
4188
4330

336
472
608
744
880
1016
1152
1288
1424
1560
1696
1832
1968
2104
2241
2377
2513
2649
2785
2921
3057
3193
3329
3465
3601
3737
3873
4009
4145

321
451
581
711
841
971
1102
1232
1362
1492
1622
1752
1882
2012
2142
2272
2402
2532
2662
2792
2922
3052
3182
3312
3442
3572
3702
3832
3962

307
431
555
679
803
927
1051
1175
1300
1424
1548
1672
1796
1920
2044
2168
2292
2416
2441
2665
2789
2913
3037
3161
3285
3409
3533
3657
3782

Page 71 of 114

Table 16: Thermal power of heating bodies Termo 813/95 depending on required air temperature and
number of sections
Warm-water heating

t1
t2

= 55 C
= 45 C

T h e r m a l p o w e r (W) at air temperature of tr (C)


No of sections
(Ns)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

196
275
355
434
513
595
672
751
831
910
989
1069
1148
1227
1307
1386
1465
1545
1624
1703
1783
1862
1941
2021
2100
2179
2259
2338
2417

164
231
297
363
430
496
563
629
696
762
828
895
961
1028
1094
1161
1227
1293
1360
1426
1493
1559
1626
1692
1758
1825
1891
1958
2024

146
205
264
323
382
441
500
558
617
676
735
794
853
912
971
1030
1089
1148
1207
1266
1325
1384
1443
1502
1561
1620
1679
1738
1797

134
188
242
296
350
404
458
513
567
621
675
729
783
837
891
946
1000
1054
1108
1162
1216
1270
1324
1378
1433
1487
1541
1595
1649

122
171
221
270
320
369
418
468
517
566
616
665
715
764
813
863
912
961
1011
1060
1110
1159
1208
1258
1307
1356
1406
1455
1504

111
155
200
245
290
334
379
424
468
513
558
603
647
692
737
782
826
871
916
961
1005
1050
1095
1140
1184
1229
1274
1319
1363

Page 72 of 114

Table 17: Thermal power of heating bodies Termo 813/130 depending on required air temperature and
number of sections
Warm-water heating

t1
t2

= 75 C
= 65 C

T h e r m a l p o w e r (W) at air temperature of tr (C)


No of sections
(Ns)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

414
582
750
917
1085
1253
1420
1588
1756
1923
2091
2259
2426
2594
2762
2929
3097
3265
3432
3600
3768
3935
4103
4271
4438
4606
4774
4941
5109

368
517
666
816
965
1114
1263
1412
1561
1710
1859
2008
2157
2306
2455
2604
2753
2902
3051
3201
3350
3499
3648
3797
3946
4095
4244
4393
4542

341
480
618
756
894
1032
1171
1309
1447
1585
1723
1861
2000
2138
2276
2414
2552
2690
2829
2967
3105
3243
3381
3520
3658
3796
3934
4072
4210

324
455
586
717
848
979
1110
1241
1372
1503
1634
1765
1896
2027
2158
2289
2420
2552
2683
2814
2945
3076
3207
3338
3469
3600
3731
3862
3993

306
430
554
678
802
926
1050
1174
1298
1422
1546
1670
1794
1918
2042
2166
2291
2415
2539
2663
2787
2911
3035
3159
3283
3407
3531
3655
3779

289
406
523
641
758
875
992
1109
1226
1343
1460
1577
1694
1811
1928
2045
2162
2279
2397
2514
2631
2748
2865
2982
3099
3216
3333
3450
3567

Page 73 of 114

Table 18: Thermal power of heating bodies Termo 813/130 depending on required air temperature and
number of sections
Warm-water heating

t1
t2

= 90 C
= 70 C

T h e r m a l p o w e r (W) at air temperature of tr (C)


No of sections
(Ns)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

510
717
923
1130
1336
1543
1750
1956
2163
2369
2576
2782
2989
3195
3402
3608
3815
4021
4228
4434
4641
4847
5054
5260
5467
5673
5880
6087
6293

462
649
835
1022
1209
1396
1583
1770
1956
2143
2330
2517
2704
2891
3077
3264
3451
3638
3825
4012
4198
4385
4572
4759
4946
5133
5319
5506
5693

433
608
784
959
1134
1309
1485
1660
1835
2011
2186
2361
2536
2712
2887
3062
3237
3413
3588
3763
3939
4114
4289
4464
4640
4815
4990
5165
5341

414
582
750
917
1085
1253
1420
1588
1756
1923
2091
2259
2426
2594
2762
2929
3097
3265
3432
3600
3768
3935
4103
4271
4438
4606
4774
4941
5109

396
556
716
876
1036
1197
1357
1517
1677
1837
1997
2158
2318
2478
2638
2798
2958
3118
3279
3439
3599
3759
3919
4079
4240
4400
4560
4720
4880

377
530
683
836
988
1141
1294
1447
1599
1752
1905
2058
2210
2363
2516
2669
2821
2974
3127
3279
3432
3585
3738
3890
4043
4196
4349
4501
4654

Page 74 of 114

Table 19: Thermal power of heating bodies Termo 813/130 depending on required air temperature and
number of sections
Warm-water heating

t1
t2

= 55 C
= 45 C

T h e r m a l p o w e r (W) at air temperature of tr (C)


No of sections
(Ns)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

239
336
433
530
627
724
821
918
1015
1112
1209
1306
1402
1499
1596
1693
1790
1887
1984
2081
2178
2275
2372
2468
2565
2662
2759
2856
2953

200
281
362
443
524
604
685
766
847
928
1009
1090
1171
1252
1333
1414
1494
1575
1656
1737
1818
1899
1980
2061
2142
2223
2303
2384
2465

177
249
320
392
464
535
607
679
751
822
894
966
1037
1109
1181
1252
1324
1396
1467
1539
1611
1682
1754
1826
1897
1969
2041
2112
2184

162
228
294
359
425
491
556
622
688
753
819
885
951
1016
1082
1148
1213
1279
1345
1410
1476
1542
1607
1673
1739
1804
1870
1936
2001

148
208
268
327
387
447
507
567
627
686
746
806
866
926
986
1045
1105
1165
1225
1285
1345
1404
1464
1524
1584
1644
1704
1763
1823

134
188
242
296
350
404
459
513
567
621
675
729
783
837
892
946
1000
1054
1108
1162
1216
1271
1325
1379
1433
1487
1541
1595
1649

Page 75 of 114

STEAM HEATING

Steam condensation temperature

tpk = 101.5 C

Page 76 of 114

Table 20: Thermal power of heating bodies Termo 500/95 depending on required air temperature and
number of sections
Steam heating

tpk

= 101.5 C

T h e r m a l p o w e r (W) at air temperature of tr (C)


No. of sections
(Ns)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

403
566
729
892
1055
1218
1381
1544
1707
1870
2033
2196
2359
2522
2685
2848
3011
3174
3337
3500
3663
3826
3989
4151
4314
4477
4640
4803
4966

374
526
677
829
980
1132
1283
1435
1586
1738
1889
2041
2192
2344
2495
2647
2798
2950
3101
3253
3404
3556
3707
3859
4010
4162
4313
4465
4616

358
502
647
792
936
1081
1226
1370
1515
1660
1804
1949
2094
2238
2383
2528
2672
2817
2962
3107
3251
3396
3541
3685
3830
3975
4119
4264
4409

346
487
627
767
907
1047
1188
1328
1468
1608
1748
1888
2029
2169
2309
2449
2589
2730
2870
3010
3150
3290
3431
3571
3711
3851
3991
4131
4272

335
471
607
743
878
1014
1150
1285
1421
1557
1693
1828
1964
2100
2236
2371
2507
2643
2778
2914
3050
3186
3321
3457
3593
3729
3864
4000
4136

324
456
587
718
850
981
1112
1244
1375
1506
1637
1769
1900
2031
2163
2294
2425
2556
2688
2819
2950
3082
3213
3344
3476
3607
3738
3869
4001

Page 77 of 114

Table 21: Thermal power of heating bodies Termo 500/130 depending on required air temperature and
number of sections
Steam heating

tpk

= 101.5 C

T h e r m a l p o w e r (W) at air temperature of tr (C)


No. of sections
(Ns)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

531
745
960
1175
1389
1604
1819
2033
2248
2463
2677
2892
3107
3321
3536
3751
3965
4180
4395
4609
4824
5039
5253
5468
5683
5897
6112
6327
6541

491
690
888
1087
1286
1484
1683
1882
2080
2279
2478
2676
2875
3074
3272
3471
3670
3868
4067
4266
4464
4663
4862
5060
5259
5458
5656
5855
6054

468
657
846
1035
1225
1414
1603
1792
1981
2171
2360
2549
2738
2928
3117
3306
3495
3685
3874
4063
4252
4442
4631
4820
5009
5198
5388
5577
5766

452
635
818
1001
1184
1367
1550
1733
1916
2099
2282
2465
2648
2831
3014
3197
3380
3563
3746
3929
4112
4295
4478
4662
4845
5028
5211
5394
5577

437
614
791
968
1144
1321
1498
1675
1852
2029
2205
2382
2559
2736
2913
3090
3267
3443
3620
3797
3974
4151
4328
4505
4681
4858
5035
5212
5389

422
593
763
934
1105
1276
1446
1617
1788
1959
2129
2300
2471
2642
2812
2983
3154
3325
3495
3666
3837
4008
4178
4349
4520
4690
4861
5032
5203

Page 78 of 114

Table 22: Thermal power of heating bodies Termo 623/95 depending on required air temperature and
number of sections
Steam heating

tpk

= 101.5 C

T h e r m a l p o w e r (W) at air temperature of tr (C)


No. of sections
(Ns)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

526
739
952
1165
1378
1591
1804
2017
2230
2442
2655
2868
3081
3294
3507
3720
3933
4146
4359
4572
4785
4998
5210
5423
5636
5849
6062
6275
6488

487
685
882
1079
1276
1474
1671
1868
2065
2262
2460
2657
2854
3051
3249
3446
3643
3840
4037
4235
4432
4629
4826
5024
5221
5418
5615
5813
6010

465
652
840
1028
1216
1404
1592
1780
1968
2156
2344
2532
2720
2908
3096
3284
3472
3660
3848
4036
4224
4412
4600
4788
4976
5164
5352
5540
5728

449
631
813
995
1177
1359
1541
1722
1904
2086
2268
2450
2632
2814
2995
3177
3359
3541
3723
3905
4087
4268
4450
4632
4814
4996
5178
5360
5541

434
610
786
962
1138
1313
1489
1665
1841
2017
2193
2368
2544
2720
2896
3072
3247
3423
3599
3775
3951
4126
4302
4478
4654
4830
5005
5181
5357

420
589
759
929
1099
1269
1438
1608
1778
1948
2118
2288
2457
2627
2797
2967
3137
3306
3476
3646
3816
3986
4155
4325
4495
4665
4835
5004
5174

Page 79 of 114

Table 23: Thermal power of heating bodies Termo 623/130 depending on required air temperature and
number of sections
Steam heating

tpk

= 101.5 C

T h e r m a l p o w e r (W) at air temperature of tr (C)


No. of sections
(Ns)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

609
856
1103
1349
1596
1842
2089
2335
2582
2829
3075
3322
3568
3815
4062
4308
4555
4801
5048
5294
5541
5788
6034
6281
6527
6774
7021
7267
7514

566
795
1024
1253
1482
1711
1940
2169
2398
2627
2856
3085
3314
3543
3772
4001
4230
4459
4688
4917
5146
5374
5603
5832
6061
6290
6519
6748
6977

540
759
977
1196
1414
1633
1852
2070
2289
2507
2726
2944
3163
3382
3600
3819
4037
4256
4474
4693
4912
5130
5349
5567
5786
6005
6223
6442
6660

523
735
947
1158
1370
1582
1793
2005
2217
2428
2640
2852
3064
3275
3487
3699
3910
4122
4334
4546
4757
4969
5181
5392
5604
5816
6027
6239
6451

506
711
916
1121
1326
1531
1736
1940
2145
2350
2555
2760
2965
3170
3375
3580
3784
3989
4194
4399
4604
4809
5014
5219
5424
5628
5833
6038
6243

490
688
886
1084
1282
1480
1678
1876
2075
2273
2471
2669
2867
3065
3263
3461
3659
3858
4056
4254
4452
4650
4848
5046
5244
5443
5641
5839
6037

Page 80 of 114

Table 24: Thermal power of heating bodies Termo 813/130 depending on required air temperature and
number of sections
Steam heating

tpk

= 101.5 C

T h e r m a l p o w e r (W) at air temperature of tr (C)


No. of sections
(Ns)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

775
1089
1402
1716
2030
2344
2657
2971
3285
3598
3912
4226
4539
4853
5167
5480
5794
6108
6421
6735
7049
7362
7676
7990
8303
8617
8931
9244
9558

718
1009
1300
1591
1881
2172
2463
2754
3044
3335
3626
3916
4207
4498
4789
5079
5370
5661
5951
6242
6533
6824
7114
7405
7696
7987
8277
8568
8859

685
962
1239
1516
1794
2071
2348
2625
2902
3180
3457
3734
4011
4288
4565
4843
5120
5397
5674
5951
6228
6506
6783
7060
7337
7614
7892
8169
8446

663
931
1199
1468
1736
2004
2272
2541
2809
3077
3345
3614
3882
4150
4418
4686
4955
5223
5491
5759
6028
6296
6564
6832
7101
7369
7637
7905
8174

641
900
1160
1419
1678
1938
2197
2457
2716
2975
3235
3494
3754
4013
4272
4532
4791
5050
5310
5569
5829
6088
6347
6607
6866
7125
7385
7644
7904

619
870
1120
1371
1622
1872
2123
2373
2624
2875
3125
3376
3626
3877
4128
4378
4629
4879
5130
5381
5631
5882
6132
6383
6634
6884
7135
7385
7636

Page 81 of 114

Table 25: Thermal power of heating bodies Termo 813/95 depending on required air temperature and
number of sections
Steam heating

tpk

= 101.5 C

T h e r m a l p o w e r (W) at air temperature of tr (C)


No. of sections
(Ns)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

623
875
1127
1379
1631
1883
2136
2388
2640
2892
3144
3396
3648
3900
4152
4404
4656
4909
5161
5413
5665
5917
6169
6421
6673
6925
7177
7429
7682

578
812
1046
1280
1514
1748
1982
2216
2450
2684
2918
3151
3385
3619
3853
4087
4321
4555
4789
5023
5257
5491
5725
5959
6193
6427
6661
6895
7128

552
775
998
1221
1444
1668
1891
2114
2337
2561
2784
3007
3230
3453
3677
3900
4123
4346
4569
4793
5016
5239
5462
5686
5909
6132
6355
6578
6802

534
750
966
1183
1399
1615
1831
2047
2263
2479
2695
2912
3128
3344
3560
3776
3992
4208
4425
4641
4857
5073
5289
5505
5721
5937
6154
6370
6586

517
726
935
1144
1353
1562
1771
1981
2190
2399
2608
2817
3026
3235
3444
3653
3863
4072
4281
4490
4699
4908
5117
5326
5535
5744
5954
6163
6372

500
702
904
1106
1308
1510
1712
1915
2117
2319
2521
2723
2925
3127
3330
3532
3734
3936
4138
4340
4542
4745
4947
5149
5351
5553
5755
5957
6160

Page 82 of 114

CAST-IRON HEATING BODIES


BOHEMIA

Page 83 of 114

BOHEMIA
DESCRIPTION
Cast-iron heating body consisting of sections connected into heating systems using steel nipples with external
right-hand or left-hand thread G 5/4 is manufactured in the following size: 450/220 mm. Heating bodies
material complies with CSN EN 442 2:1997 (grey cast-iron to CSN EN 1561, grade 150). The design
of castings ensures a long life cycle of products.

BOHEMIA 450/220 with foot

BOHEMIA 450/220

Fig. 1: BOHEMIA type heating body

USAGE
BOHEMIA heating body is designed for warm-water central heating systems with gravity and forced circulation
of heating water with the highest operating temperature not exceeding 115 C and highest operating overpressure
of up to 0.6 MPa. With its design the body is suitable for historical buildings and stylish interiors.

Page 84 of 114

THERMAL ABD TECHNICAL PARAMETERS


BOHEMIA type is certified by SZ Brno (certificate No. B-30-00532-03). Thermal and technical parameters for
the heat-transfer fluid (water) have been verified experimentally in compliance with CSN EN 442-2 in the
Measuring laboratory of Technical University in DARMSTADT.
Basic thermal and technical parameters are provided in Table 1. Indicated thermal power applies to the
heat-transfer fluid (water) with the temperature gradient of 75/65 C and one-sided lateral connection (supply) of
the heat-transfer fluid (water) at the top. The body is measured without cover.
Environment: These heating bodies can be used in the following temperature range: +2 C up to +35 C.
Table 1: Significant thermal and technical parameters of BOHEMIA heating sections
Property

Symbol

450/220

450/220 with foot

total height
spacing
depth
width
connection
thread

H (mm)
h (mm)
B (mm)
L (mm)

540
450
225
86
5/4

634
450
225
86
5/4

11.4
1.3
110

13.2
1.3
110

weight
water volume
thermal power

G
M (kg/pc.)
V (dm3/pc.)
QN1 (W/section)

Fig. 2: Standard dimensions of BOHEMIA sections

TESTING OVERPRESSURE
Units manufactured are subject to the pressure test performed in manufacturers facility using overpressure of
cold water equal to 1 MPa.

Page 85 of 114

ASSEMBLY
In order to achieve required thermal power of heating bodies it is necessary to maintain the installation position
indicated on Fig. 3.

Wall

Floor
Fig. 3: Installation of BOHEMIA heating bodies

BOHEMIA heating bodies are connected to the distribution piping using roses provided with external thread
G 5/4 with G 3/8, G 1/2, G 3/4 and G 1 bores.
Openings of the heating body on the opposite side to connection are terminated by solid plugs provided with
external left-hand thread G 5/4. The upper plug can be provided with bore with eccentrically positioned thread
G 1/4 for the air relief valve. Automatic air relief valves are suitable for this purpose.
Prior to combining the individual units supplied it is necessary to perform a thorough cleaning of contact
surfaces of sections and connections should be sealed by TEMASIL packing, which is normally used during
production and it is suitable both for warm-water and steam systems. The sections shall be coupled with the
torque of min. 180 Nm and max. 250 Nm.
Other installation data are provided in the section of instruction manual common for all models of heating bodies
manufactured.

Page 86 of 114

THERMAL POWER TABLES


FOR INDIVIDUAL MODELS OF HEATING BODIES

Page 87 of 114

WARM-WATER HEATING

Temperature gradient to CSN EN 442 2:1997


Temperature gradients

75/65 C
90/70 C
55/45 C

Page 88 of 114

Table 2: Thermal power of heating bodies Bohemia 450/220, h = 450 mm depending on required air
temperature and number of sections for warm-water heating
tW1 = 75 C
tW2 = 65 C

T h e r m a l p o w e r Q (W) at air temperature of ti (C)


No. of
sections (Ns)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

335
471
607
743
878
1014
1150
1286
1421
1557
1693
1828
1964
2100
2236
2371
2507
2643
2779
2914
3050
3186
3322
3457
3593
3729
3864
4000
4136

297
417
538
658
778
898
1019
1139
1259
1380
1500
1620
1740
1861
1981
2101
2221
2342
2462
2582
2702
2823
2943
3063
3183
3304
3424
3544
3665

275
386
497
609
720
831
942
1054
1165
1276
1387
1498
1610
1721
1832
1943
2055
2166
2277
2388
2500
2611
2722
2833
2945
3056
3167
3278
3389

260
366
471
576
682
787
892
998
1103
1208
1314
1419
1524
1630
1735
1840
1946
2051
2156
2262
2367
2472
2578
2683
2788
2894
2999
3104
3210

246
345
445
544
644
744
843
943
1042
1142
1241
1341
1440
1540
1639
1739
1838
1938
2037
2137
2236
2336
2435
2535
2634
2734
2833
2933
3032

232
326
419
513
607
701
795
888
982
1076
1170
1264
1357
1451
1545
1639
1733
1826
1920
2014
2108
2202
2295
2389
2483
2577
2670
2764
2858

Page 89 of 114

Table 3: Thermal power of heating bodies Bohemia 450/220, h = 450 mm depending on required air
temperature and number of sections for warm-water heating
tW1 = 90 C
tW2 = 70 C

T h e r m a l p o w e r Q (W) at air temperature of ti (C)


No. of
sections (Ns)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

416
584
752
920
1088
1257
1425
1593
1761
1929
2098
2266
2434
2602
2770
2938
3107
3275
3443
3611
3779
3948
4116
4284
4452
4620
4789
4957
5125

375
527
678
830
982
1134
1285
1437
1589
1740
1892
2044
2196
2347
2499
2651
2802
2954
3106
3258
3409
3561
3713
3864
4016
4168
4320
4471
4623

351
493
635
777
919
1061
1203
1346
1488
1630
1772
1914
2056
2198
2340
2482
2624
2766
2908
3050
3192
3334
3477
3619
3761
3903
4045
4187
4329

335
471
607
743
878
1014
1150
1286
1421
1557
1693
1828
1964
2100
2236
2371
2507
2643
2779
2914
3050
3186
3322
3457
3593
3729
3864
4000
4136

320
449
579
708
838
967
1097
1226
1356
1485
1615
1744
1874
2003
2133
2262
2392
2521
2651
2780
2910
3039
3169
3298
3428
3557
3686
3816
3945

305
428
551
675
798
921
1045
1168
1291
1415
1538
1661
1784
1908
2031
2154
2278
2401
2524
2648
2771
2894
3018
3141
3264
3388
3511
3634
3758

Page 90 of 114

Table 4: Thermal power of heating bodies Bohemia 450/220, h = 450 mm depending on required air
temperature and number of sections for warm-water heating
tW1 = 55 C
tW2 = 45 C

T h e r m a l p o w e r Q (W) at air temperature of ti (C)


No. of
sections (Ns)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

191
268
345
423
500
577
654
731
809
886
963
1040
1118
1195
1272
1349
1426
1504
1581
1658
1735
1813
1890
1967
2044
2121
2199
2276
2353

158
223
287
351
415
479
543
607
672
736
800
864
928
992
1056
1121
1185
1249
1313
1377
1441
1505
1569
1634
1698
1762
1826
1890
1954

140
197
253
310
366
423
480
536
593
649
706
763
819
876
933
989
1046
1102
1159
1216
1272
1329
1386
1442
1499
1555
1612
1669
1725

128
180
231
283
335
387
438
490
542
594
645
697
749
801
853
904
956
1008
1060
1111
1163
1215
1267
1318
1370
1422
1474
1525
1577

116
163
210
257
304
351
398
445
492
539
586
633
680
727
775
822
869
916
963
1010
1057
1104
1151
1198
1245
1292
1339
1386
1433

105
147
190
232
274
317
359
402
444
487
529
571
614
656
699
741
783
826
868
911
953
996
1038
1080
1123
1165
1208
1250
1293

Page 91 of 114

STEAM HEATING

Steam condensation temperature

tpk = 101.5 C

Page 92 of 114

Table 5: Thermal power of heating bodies Bohemia 450/220, h = 450 mm depending on required air
temperature and number of sections
Steam heating

tpk

= 101.5 C

T h e r m a l p o w e r Q (W) at air temperature of ti (C)


No. of
sections (Ns)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

10

15

18

20

22

24

638
896
1154
1412
1670
1929
2187
2445
2703
2961
3219
3477
3735
3994
4252
4510
4768
5026
5284
5542
5800
6059
6317
6575
6833
7091
7349
7607
7865

590
829
1067
1306
1545
1784
2022
2261
2500
2738
2977
3216
3455
3693
3932
4171
4409
4648
4887
5126
5364
5603
5842
6081
6319
6558
6797
7035
7274

562
789
1016
1244
1471
1698
1925
2153
2380
2607
2835
3062
3289
3516
3744
3971
4198
4425
4653
4880
5107
5335
5562
5789
6016
6244
6471
6698
6926

543
763
983
1202
1422
1642
1862
2081
2301
2521
2741
2960
3180
3400
3620
3839
4059
4279
4498
4718
4938
5158
5377
5597
5817
6037
6256
6476
6696

525
737
949
1161
1374
1586
1798
2011
2223
2435
2647
2860
3072
3284
3497
3709
3921
4133
4346
4558
4770
4983
5195
5407
5619
5832
6044
6256
6469

506
711
916
1121
1326
1531
1736
1941
2145
2350
2555
2760
2965
3170
3375
3580
3785
3989
4194
4399
4604
4809
5014
5219
5424
5629
5834
6038
6243

Page 93 of 114

SUPPLEMENTARY DATA

Page 94 of 114

SUPPLEMENTARY DATA
The external surface of heating bodies shall be provided with a final paint prior to their putting into operation.
Thermal power changes if other heat-transfer fluid than the bodies were verified for (e.g. anti-free mixture) is
used. Thus, utilization of such mixtures shall be consulted with the manufacturer of radiators.
We recommend to add inhibitors to the heat carrying medium (e.g. INHICOR I, II).
All models of heating bodies may be provided with thermostatic valves.

SURFACE FINISHING
The bodies are provided with the anticorrosive protective primer at the manufacturers facility. The final paint is
performed by organization ensuring assembly based on requirements of the implementation project and/or
customers. On request we are able to secure supply of heating bodies already provided with a final paint directly
from TT Viadrus. The front contact surfaces of outlets and openings for nipples are protected by plastic closures
(caps).
BOHEMIA heating bodies are provided with a final paint in the mill, particularly WECO-FAN paint, hue 9007.

INSTALLATION INSTRUCTIONS
It the cast-iron heating bodies are used for central heating systems with forced circulation of heating water it is
advisable to perform flushing of the system (preferably three times) prior to turning the pump on. This will
ensure removal of all impurities, avoid clogging of ceramic plates of the pump and ensure long-term trouble-free
operation.

PACKAGING, TRANSPORT, STORAGE


KALOR, KALOR 3, TERMO
These heating bodies are usually delivered in sets of 10 sections, however, different size of the set can be
provided based on agreement. Products may be shipped by all suitable means of transport, e.g. railway cars,
trucks, containers, etc. The sets are placed horizontally during transport bodies with depth of 160 and 130 mm
in max. 7 layers, while bodies with depth of 110 mm and smaller in max. 10 layers. The sets shall be secured
against shifting during transport properly. The lowermost layer shall be laid on horizontal surface to avoid
slipping. Customer shall store the products in such a way to protect them against climatic effects. The same
principles apply to storage as applicable to transport.
When handling the sets it is necessary to exercise a proper care to avoid damage of sections. Sets can be carried
only in vertical position in order to prevent their deflection (applies especially to longer sets) and damage or
packing in joints.
BOHEMIA
These heating bodies are supplied in sets per customers requirement, from 3 up to 19 sections. Bodies
consisting of 3 up to 12 sections include 2 sections BOHEMIA 450/220 with foot. Maximum number of sections
is 19 and such a set includes 3 sections BOHEMIA 450/220 with foot (third section with foot is located in the
middle). The same applies also to systems consisting of 13, 15 and 17 sections (from 12 sections up only odd
numbers of sections are supplied). Heating bodies are wrapped into protective foil. Cardboard sheets are inserted
between individual sections placed on the transport pallet. These packages can be disposed of as a normal
municipal waste. Products may be shipped by all suitable means of transport, e.g. railway cars, trucks,
containers, etc. The sets shall be secured against shifting during transport properly. Customer shall store the

Page 95 of 114

products in such a way to protect them against climatic effects. The same principles apply to storage as
applicable to transport.
When handling the sets it is necessary to exercise a proper care to avoid damage of sections. Sets can be carried
only in vertical position in order to prevent their deflection (applies especially to longer sets) and damage or
packing in joints.

ORDERING
Purchase order shall include the following data:
-

type of heating body (Kalor, Kalor 3, Termo or Bohemia)

connection spacing and depth

number of sections or sets expressed in pieces, or external equivalent heating


surface in m2

As accessories customers may order brackets, holders, bolts, gudgeons, stand profile with the set and all
necessary roses and plugs according to information provided in the Installation instructions chapter.

WARRANTY
Manufacturer provides 10 years warranty covering production defects on heating systems delivered. The
warranty period starts as of the ex-works shipment date from Viadrus mill.

Page 96 of 114

DESIGNING DATA

Page 97 of 114

DESIGNING DATA
The main thermal and technical parameters for all types of heating bodies are indicated in tables. The following
formulae apply to conversion of thermal power of a heating body from basic operating mode for other
warm-water difference than stated in previous text.

= S t

s
tr
tPK
t1
t2
t

tD

= (

(-)
(W)
(W)
(C)
(C)
(C)
(C)
(C)
(C)
(C)

t
t

t =

t1 + t 2
tr
2

t = t PK t r

for warm-water heating

for steam heating

...
...
...
...
...
...
...
...
...
...

temperature exponent
thermal power
nominal thermal power (in basic operating mode)
air temperature
steam condensation temperature
inlet water temperature
outlet water temperature
temperature difference
definition temperature difference in basic operating mode
corrective factor for temperature difference

Detailed information on conversion of the heating bodys thermal power for other operating conditions
are provided in the Czech standard CSN 06 1101 or other appropriate standards applicable in individual
countries.

PRESSURE LOSSES
Pressure losses of all type of heating bodies manufactured were verified experimentally. Data provided in Table
76 apply to particular calculations of pressure losses at the water flow. These data can be used independently on
the number of cells in the system for two-point connection to the distribution piping.
Table 1: Factors for calculation of pressure losses
Pipe connection size

T ( - )

AT (m2)

DN 6

(1/8)

1.0

0.00008

DN 8

(1/4)

1.0

0.00010

DN 10 (3/8)

1.0

0.00013

DN 15 (1/2)

2.5

0.00018

DN 20 (3/4)

2.5

0.00030

DN 25 (1)

2.5

0.00046

DN 32 (5/4)

2.5

0.00091

Page 98 of 114

Formula for calculation of pressure losses p (Pa) is as follows:

w
(V )
p = T
w =
w
2
2
( AT )
T
AT
w
V
w

(-)
(m2)
(m.sec-1)
(m3.sec-1)
(kg.m-3)

drag coefficient
flow coefficient
water velocity in pipeline
volume flow of water
water density

Page 99 of 114

INTEGRATED THERMOSTATIC VALVE

Page 100 of 114

INTEGRATED THERMOSTATIC VALVE VIADRUS ITV


with adjustable valve insert V and thermostatic head
Thanks to application of thermostatic valves in heating equipment it is possible to control individually the
required room temperature and save the energy. This ensures reduction of heating costs.
Various application conditions required different sizes dimensions of thermostatic valves (DN 10 DN 20,
sizes 3/8, 1/2, 3/4).
Integrated thermostatic valve VIADRUS ITV with adjustable valve insert V and thermostatic head was
developed based on cooperation of company DB a.s., VIADRUS heating equipment mill with Honeywell
company. This valve can be used for the above specified dimension size range.
Integrated thermostatic valve VIADRUS ITV with adjustable valve insert V and thermostatic head is
supplied with a pair of heating sections coupled together using modified radiator nipples.
At the present time a version with 5/4 thread is being produced. This version can be used for heating bodies of
the following types:
!

KALOR manufactured in eight models: 350/160 mm, 500/70 mm, 500/110 mm, 500/160 mm, 500/220
mm, 600/160 mm, 900/70 mm and 900/160 mm.

KALOR 3 manufactured in five models: 350/160 mm, 500/70 mm, 500/110 mm, 500/160 mm and
900/70 mm.

Schematic representation of two connected sections with integrated thermostatic valve and adjustable valve
insert is illustrated on the following figure:
modified radiator
nipple

ADVANTAGES OF INTEGRATED
THERMOSTATIC VALVE VIADRUS ITV:

integrated
Thermostatic valve
VIADRUS ITV

adjustable
valve
insert V

More advanced heating water connection


Installation of integrated valve directly into heating body
Simpler assembly of heating bodies

modified
radiator
nipple

Integrated thermostatic valve VIADRUS ITV with adjustable valve insert V allows a different method of
heating and return water connection, which is illustrated on figures below.
Modified radiator
nipple

Thermostatic valve

Integrated thermostatic
valve VIADRUS ITV
Modified radiator
nipple

Radiator
roses

Heating water

Radiator rose

Return water

Radiator screw joint

Heating water
Radiator
screw joint

EXAMPLE OF CLASSIC INSTALLATION

Return water

EXAMPLE OF A NEW INSTALLATION WITH


INTEGRATED THERMOSTATIC VALVE

Page 101 of 114

INTEGRATED THERMOSTATIC VALVE VIADRUS ITV


With adjustable insert V
A. TECHNICAL DESCRIPTION

For warm-water central heating systems with gravity and forced circulation of heating water
For two-pipe heating systems with medium volume of heating water
With stepless pre-control (infinitely adjustable) for medium volume of heating water
20

160
V

(approx. water amount in kg/hr.)

300

Setting up using special wrench

Set-up visible also from outside


Noiseless
kv equal to 0.51
Highest operating temperature of heating water below 120 C
Maximum operating pressure 8 bar
Maximum differential pressure 2 bar
Connection of heating body with ITV to all pipe sizes DN 10 DN 20 (3/8, 1/2, 3/4)
pH value of heating water from 4 up to 9.5
Adjustable valve insert V

Page 102 of 114

B. TECHNICAL DATA

Pressure loss in Pa
(10 Pa = 1 mm v.s. = 0.1 mbar)

Pressure loss in mbar

Flow diagram for body of thermostatic valve V

5 6 7 8 9 10

5 6 7 8 9 10

Flow in kg/hr.

x = recommended application area

Pre-control
Pp = 2 K
kv (m3/h)

0.5
0.03
0.03

1
0.06
0.06

2
0.12
0.12

3
0.18
0.18

4
0.23
0.25

5
0.28
0.32

6
0.33
0.38

7
0.38
0.44

8*
0.41
0.51

* At full stroke
Example of sizing:

Specified:
To be found out:

flow rate 75 kg/hr.


set-up at required pressure loss Dp = 10 000 Pa = 100 mbar

The pressure loss looked for is obtained as a point of intersection of the flow line with selected valve
parameter, e.g. at Pp = 2 K.
Result:
kv

position 4

flow rate amount of heating fluid (heating water), which flows through the valve at given
pre-control

Pp

2nd zone of proportionality change of required value in order to ensure shifting of actuator
(valve) from one limit position to the other one.

2K

2 Kelvin temperature difference for operation of the valve (for apartments 2, for industrial
halls - 3)

Page 103 of 114

ACCESSORIES

Page 104 of 114

ACCESSORIES
As accessories customers may order brackets, holders, spacers, bolts, and stand profiles according to article
numbers specified in Installation instructions chapter. Roses, plugs and packing can be ordered using specific
names indicated on Fig. 1 Accessories.
In addition to the above it is necessary to specify, whether the rose should be provided with left-hand or righthand thread. Internal thread in the rose can be 3/8", 1/2", 3/4" or 1". Plug is a full rose.

ROSE 5/4 WITH 1/2 INTERNAL THREAD

ROSE 1 WITH 1/2 INTERNAL


THREAD

CLINGERITE PACKING FOR


ROSE 5/4

CLINGERITE PACKING FOR


ROSE 1

STEEL NIPPLE 5/4

STEEL NIPPLE 1

Fig. 1: Accessories

Page 105 of 114

We recommend to fix the heating bodies using one of the following methods
Installation of Bohemia heating bodies should be performed by their positioning on the feet of the body.

1. Utilization of special brackets with holders and spacers acc. to Fig. 2


They are used similarly to pipe brackets for fixation of heating bodies to solid walls. Their advantage consists
especially in significantly simpler and quicker installation (when drilling holes for brackets it is not necessary to
maintain accurate spacing and width of sections in sets). This allows a very simple installation of all types and
sizes of heating bodies manufactured.

BRACKET (art. No. 595)

SPACER (art. No. 514)

FIXING HOLDER (art. No. 516)

FIXING HOLDER (art. No. 554)

Fig. 2: Bracket with fixing holder and spacer

Complete kit for given fixation method includes:


-

bracket (art. No. 595)


fixing holder (art. No. 516 or art. No. 554, both are identical)
spacer (art. No. 514)
bolt 8 x 60 (art. No. 1051)
gudgeon 10 (art. No. 1071-1).

Page 106 of 114

FIXING HOLDER
BOLT (8x60) WITH
GUDGEON dia. 10

BRACKET

SPACER

Fig. 3: Fixation of heating bodies using brackets with fixing holders


Table 1: Number of brackets with fixing holders depending on dimension of sections

Dimensions of sections
(mm)
K 500/70
K 500/110, K3 500/70,
T 500/95
K 350/160, K 900/70,
K3 350/160,
K3 500/110, T 623/95
K 500/160, K 600/160,
K3 900/70, T 500/130
K3 500/160, K 500/220,
T 623/130, T 813/95
T 813/130
K 900/160

Number of sections
3 4 6 8 10 12 14 16 18 20 22
24
2
2
2
2

26
2

28
3

30
3

2
2

3
3

3
3

3
4

3
4

4
4

4
5

Page 107 of 114

2. Screw brackets with fixing holders and spacers are designed for fixation of heating
bodies into hollow walls
Proceed in compliance with Fig. 4 (indicates all items necessary to assembly including article numbers; fixing
holders can be used in the same way as in previous example). This method may be used for all types of heating
bodies manufactured.

SCREW CONSOLE (art. No. 676)

FIXING HOLDER (art. No. 516)

SPACER (art. No. 514)

FIXING HOLDER (art. No. 554)

Fig. 4: Screw bracket with fixing holder and spacer

FIXING HOLDER

SCREW BRACKET

SPACER

Fig. 5: Fixation of heating bodies into hollow walls using screw brackets

Page 108 of 114

Table 2: Number of screw brackets with fixing holders depending on dimension of sections

Dimensions of sections
(mm)
K 500/70,
K 500/110, K3 500/70,
T 500/95
K 350/160, K 900/70,
K3 350/160, K3 500/110,
T 623/95
K 500/160, K 600/160,
K3 900/70, T 500/130
K3 500/160, K 500/220,
T 623/130, T 813/95
T 813/130
K 900/160

3 4 6 8 10
2

12 14
2

Number of sections
16 18 20 22
24
3
3

26
3

28
3

30
3

2
2

3
3

3
4

4
4

4
5

4
6

5
6

5
6

5
6

3. Fixation of heating bodies to a stand


Proceed in compliance with Fig. 6 and 7. Indicated method is suitable for all models manufactured. We
recommend to use it in rooms with plasterboard partition walls or facing and in all places where it is impossible
to apply fixation according to Fig. 1 3. Foot of the stand can be fixed into the floor by screwing down or
embedding in concrete, e.g. for sizes 900/160, 900/70 and so on.
STAND PROFILE separate order
according to required length (see table 50)

STAND ACCESSORIES KIT


(art. No. 328)
PLUG

HOLDER

BRACKET

FOOT

Fig. 6: Stand with accessories kit

Page 109 of 114

Table 3: Ordering number of the stand profile

Length A(mm) 360


460
510
560
610
660
710
760
860
960
1060
1160
Ordering No. 360-1 460-1 510-1 560-1 610-1 660-1 710-1 760-1 860-1 960-1 1060-1 1160-1

PLUG

STAND PROFILE

HOLDER

BRACKET

FOOT

Fig. 7: Fixation of heating bodies using stand


Table 4: Number of stands depending on dimensions of sections

Dimensions of sections
(mm)
K 500/70
K 500/110, K3 500/70,
T 500/95
K 350/160, K 900/70,
K3 350/160, K3 500/110,
623/95
K 500/160, K 600/160,
K3 900/70, T 500/130
K3 500/160, K 500/220
623/130, T 813/95
T 813/130
K 900/160

3 4 6 8 10
2
2

12 14
2
3

Number of sections
16 18 20 22
3
3
3

24
3
3

26
3
3

28
3
4

30
3
4

2
2

3
3

3
4

4
6

5
6

5
6

5
6

4
4

Page 110 of 114

4. Using classic radiator pipe brackets and holders


These can be used for fixation of bodies on solid walls. This method is suitable for types Kalor. In case of Kalor
3 and Termo types it is necessary to use brackets instead of holders.

Kalor (all sizes)

Kalor 3 a Termo

Fig. 8: Fixation of heating sections using pipe brackets and holders

HOLDER

TYPE A BRACKET

TYPE B BRACKET

Fig. 9: Radiator pipe brackets and holder

Selection of a bracket is made based on depth of heating bodies, see Table 5. Number of brackets depending on
dimensions and number of sections is indicated in Table 6. For sets of up to 4 sections it suffices to use 1 holder.
Two holders are usually used for systems with more sections.

Page 111 of 114

Table 5: Recommended types of pipe brackets according to type of heating bodies

Bracket type
A
B

Heating body size (spacing / depth)


350/160, 500/110, 500/160, 900/160, 500/130, 623/130, 813/130
500/70, 500/95, 623/95, 813/95, 900/70

Table 6: Number of brackets depending on dimensions of sections

Dimensions of sections
(mm)
K 500/70
K 500/110, K3 500/70,
T 500/95
K 350/160, K 900/70,
K3 350/160,
K3 500/110, T 623/95
K 500/160,
K3 900/70, T 500/130
K3 500/160, T 623/130,
T 813/95
T 813/130
K 900/160

3 4 6 8 10
2
2

Number of sections
12 14 16 18 20 22 24
2
3
3
3
2
3

2
2

2
3

3
4

26

28

30

3
3

4
4

4
4

3
5

4
5

4
5

4
6

Fig. 10: Threaded screws, for top fixation of heating sections into the wall

Page 112 of 114

5. Support under KALOR heating body


This fixation method is used for KALOR and KALOR 3 heating bodies in combination with holders.

Fig. 11: Support under heating bodies KALOR and KALOR 3


Table 7: Number of brackets depending on dimensions of sections

Dimensions of sections
(mm)
KALOR 500/70
KALOR 500/110
KALOR 350/160
KALOR 900/70
KALOR 500/160,
KALOR 900/160,

3 4 6 8 10 12
2
2
2
2
2
2

Number of sections
14 16 18 20 22
3
4
3
4
3
4
3
4
3
4
3
4

24
4
4
4
4
4
4

26
4
4
4
4
4
4

28
5
5
5
5
5
5

30
5
5
5
5
5
5

Page 113 of 114

6. Using classic radiator pipe brackets


These can be used for fixation of bodies into solid walls. This type of fixation is suitable for heating body
BOHEMIA.

Fig. 12: Bracket for fixation of BOHEMIA heating bodies

Table 8: Number of brackets depending on dimensions of sections

Dimensions of sections
(mm)
Bohemia 450/220

3 4 6 8
2

Number of sections
10 12 14
16 18 20
3
4

22
5

24
5

26
5

28 30
6

Page 114 of 114