Earthing Calcution
PROJECT: 5 MW SOLAR POWER PLANT AT DHANK VILLAGE, GUJARAT CONTRAGTOR: MICHIGAN SAVITAR CONSORTIUM D-7 COMMERCIAL CENTRE 78, JAVJI DADAJI ROAD. TARDEO, MUMBAI- 400 034 CONSULTANAT: NITSON & AMITSU PRIVATE LIMITED 54D, HAZRA ROAD, KOLKATA-700 019
CALCULATION SHEET
REFERENCE 1 2 3 4
5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
SELECTION OF MAIN EARTHING CONDUCTOR AS PER IS 3043-1987 CLAUSE NO. 12.2.2.1 MIN. CROSS SECTIONAL AREA OF MAIN EARTH GRID AROUND AREA' E' SHALL BE DERIVED FROM THE FOLLOWING EQUATION I S WHERE, S I = = CROSS SECTIONAL AREA IN SQ.MM VALUE (ac. rms) OF FAULT CURRENT FOR A FAULT OF NEGLIGIBLE IMPEDENCE WHICH CAN FLOW THROUGH THE PROTECTIVE DEVICE( IN AMPS) t K = = OPERATING TIME OF THE DISCONNECTIONG DEVICE IN SECS. FACTOR DEPENDENT ON THE MATERIAL OF THE PROTECTIVE CONDUCTOR, THE INSULATION AND OTHER PARTS AND THE INITIAL AND FINAL TEMPERATURE THE FACTOR K IS DETERMINED BY THE FORMULA : K X 1 t
EQUATION (1)
24 25 26 27 28 29 30 31 32 33 34 35 36
K =
( B +
20 )
ln ( 1 +
20
B +
I I
EQUATION (2)
37 38 39 41 42 43
WHERE,
CALCULATION SHEET B
= RECIPROCAL OF TEMPERATURE COEFFICIENT OF RESISTIVITY AT 0 0C FOR CONDUCTOR (0 C) = ELECTRICAL RESISTIVITY OF CONDUCTOR MATERIAL AT 20 0 C (
0 = INITIAL TEMPERATURE OF CONDUCTOR ( C)
20
- MM)
THE MATERIAL CONSTANTS AS PER TABLE -5 OF IS 3045 1987 FOR STEEL ARE : B = = = = = 202 3.8 138 40
0 0
C 10 10
-3
X X C
( j / 0C mm 3 ) ( - MM)
CONSTANTS' OF IS 3043
20
-6
0 200 C
K =
3.8
X 138
10 X
-3
(
-6
202
20
10
ln ( 1 +
200 202
40 40
25 26 27 28
= =
55.7 56 ( APPROX)
29 30 31 32 33 34 35
26200 S S
56 SQRT(3)
36 37 38 39 40 41 42
810.352
THEREFORE, WE SELECT 75X 12MM GI FLAT AS EARTHING GRID AROUND TANK AREA
CALCULATION SHEET
REFERENCE 1 2 3 4 5 6
X l
log e
4 X l d
7 8 9 10 11
WHERE, l d = = = LENGTH OF ROD OR PIPE ( IN CM) DIAMETER OF pipe ( IN CM) RESISTIVITY OF THE SOIL ( - M) = = = 600 5 700 CM CM - M
12 13 14 15 16 17 18
100 2 X
700 X 600
log e
X 5
600
19 20 21 22 23 24 25 26 27 28
114.69
In order to reduce the earth resistance within permissible limit limit we have considered60nos. pipes in paralled and the resistance is than practically proportional to the reciprocal of the number employed. IF n = TOTAL NO. OF EARTH ELECTRODES THEN Req = 114.69 60 Therefore, resistance of pipe electrode is 1.912 OHM OHM = 1.912
29 30 31 32 33 34 35 36 37 38 39 41 42 43
Rs
( IS :3043-1987,Cl9.2.3)
Where Rs p l w t Therefore Rs = = = = = Resistance of strip electrode in ohm Soil resitivity in ohm-m below 1M = Length of strip in cm = depth . Of strip electrode buried in = ground in cm width of strip electrode = 700 160000 60 7.5
1.3397153
ohm
0.787749053
ohm