You are on page 1of 266

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.

D)

Product Description
Issue Date 03 2013-01-15

HUAWEI TECHNOLOGIES CO., LTD.

Copyright Huawei Technologies Co., Ltd. 2013. All rights reserved. No part of this document may be reproduced or transmitted in any form or by any means without prior written consent of Huawei Technologies Co., Ltd.

Trademarks and Permissions


and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd. All other trademarks and trade names mentioned in this document are the property of their respective holders.

Notice
The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS" without warranties, guarantees or representations of any kind, either express or implied. The information in this document is subject to change without notice. Every effort has been made in the preparation of this document to ensure accuracy of the contents, but all statements, information, and recommendations in this document do not constitute a warranty of any kind, express or implied.

Huawei Technologies Co., Ltd.


Address: Huawei Industrial Base Bantian, Longgang Shenzhen 518129 People's Republic of China http://www.huawei.com support@huawei.com

Website: Email:

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

About This Document

About This Document


Overview
This document presents the exteriors and describes the functions, technical specifications, application scenarios, structure, components, and cable connections of the APM30H (Ver.D), TMC11H (Ver.D), IBBS200D (Ver.D), and IBBS200T (Ver.D). It also describes the configurations, functions, and specifications of the modules and boards, and details such as cable types, cable connections, and connector specifications. l l l l APM30H is short for advanced power module with heat exchanger. TMC11H is short for transmission cabinet of 11 U high with heat exchanger. IBBS200D is short for integrated battery backup system with direct cooling. IBBS200T is short for integrated battery backup system with thermal electric cooling.

Product Version
Product Name APM30H Ver.D (APM30H for short) TMC11H Ver.D (TMC11H for short) IBBS200D Ver.D (IBBS200D for short) IBBS200T Ver.D (IBBS200T for short) Product Version V300R003C00

Intended Audience
l l l Base station installation personnel System engineers Site maintenance personnel

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

ii

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

Contents

Contents
About This Document.....................................................................................................................ii 1 Changes in APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description ..............................................................................................................................................................1 2 APM30H Cabinet...........................................................................................................................3
2.1 Cabinet Exterior..................................................................................................................................................4 2.2 Cabinet Engineering Specifications....................................................................................................................4 2.3 Engineering Specifications of Customer Equipment in APM or TMC Series Cabinets....................................8 2.4 Cabinet Application Scenarios.........................................................................................................................11 2.5 Cabinet Interior.................................................................................................................................................13 2.6 Components in an APM30H.............................................................................................................................15 2.6.1 EPU05A...................................................................................................................................................15 2.6.2 Junction Box............................................................................................................................................33 2.6.3 FAN 02D.................................................................................................................................................35 2.6.4 ELU.........................................................................................................................................................36 2.6.5 Door Status Sensor..................................................................................................................................41 2.6.6 Filler Module...........................................................................................................................................44 2.6.7 AC Heater................................................................................................................................................45 2.6.8 SOU.........................................................................................................................................................45 2.7 APM30H Cables...............................................................................................................................................47 2.7.1 Cable List.................................................................................................................................................47 2.7.2 Cable Connections...................................................................................................................................49 2.7.3 PGND Cable............................................................................................................................................52 2.7.4 Equipotential Cable.................................................................................................................................58 2.7.5 Power Cables...........................................................................................................................................63 2.7.6 Signal Cables...........................................................................................................................................75

3 TMC11H Cabinet.........................................................................................................................83
3.1 Cabinet Exterior................................................................................................................................................84 3.2 Cabinet Engineering Specifications..................................................................................................................84 3.3 Cabinet Application Scenarios.........................................................................................................................88 3.4 Cabinet Interior.................................................................................................................................................89 3.5 TMC11H Components.....................................................................................................................................92 3.5.1 DCDU-12B..............................................................................................................................................92 Issue 03 (2013-01-15) Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd. iii

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

Contents

3.5.2 DCDU-12C..............................................................................................................................................98 3.5.3 FAN 02D...............................................................................................................................................102 3.5.4 Filler Module.........................................................................................................................................102 3.5.5 Junction Box..........................................................................................................................................103 3.5.6 ELU.......................................................................................................................................................105 3.5.7 Door Status Sensor................................................................................................................................111 3.5.8 AC Heater..............................................................................................................................................114 3.5.9 SOU.......................................................................................................................................................115 3.6 TMC11H Cables.............................................................................................................................................116 3.6.1 Cable List...............................................................................................................................................116 3.6.2 Cable Connections.................................................................................................................................119 3.6.3 PGND Cable..........................................................................................................................................120 3.6.4 Equipotential Cable...............................................................................................................................126 3.6.5 Power Cables.........................................................................................................................................131 3.6.6 Signal Cables.........................................................................................................................................144

4 IBBS200D Cabinet.....................................................................................................................151
4.1 Cabinet Exterior..............................................................................................................................................152 4.2 Cabinet Engineering Specifications................................................................................................................152 4.3 Cabinet Interior...............................................................................................................................................154 4.4 IBBS200D Components.................................................................................................................................155 4.4.1 Fan Mounting Frame.............................................................................................................................155 4.4.2 CMUEA.................................................................................................................................................159 4.4.3 Power Distribution Box.........................................................................................................................162 4.4.4 Storage Battery......................................................................................................................................164 4.4.5 ELU.......................................................................................................................................................165 4.4.6 Heating Film..........................................................................................................................................171 4.4.7 Door Status Sensor................................................................................................................................172 4.4.8 Temperature Sensor...............................................................................................................................175 4.5 IBBS200D Cables...........................................................................................................................................180 4.5.1 Cable List...............................................................................................................................................180 4.5.2 Cable Connections.................................................................................................................................182 4.5.3 PGND Cable..........................................................................................................................................184 4.5.4 Equipotential Cable...............................................................................................................................190 4.5.5 Power Cables.........................................................................................................................................195 4.5.6 Signal Cables.........................................................................................................................................202

5 IBBS200T Cabinet......................................................................................................................208
5.1 Cabinet Exterior..............................................................................................................................................209 5.2 Cabinet Engineering Specifications................................................................................................................209 5.3 Cabinet Interior...............................................................................................................................................211 5.4 IBBS200T Components..................................................................................................................................213 5.4.1 TEC........................................................................................................................................................213 5.4.2 CMUEA.................................................................................................................................................214 Issue 03 (2013-01-15) Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd. iv

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

Contents

5.4.3 Power Distribution Box.........................................................................................................................218 5.4.4 Storage Battery......................................................................................................................................220 5.4.5 ELU.......................................................................................................................................................221 5.4.6 Door Status Sensor................................................................................................................................227 5.4.7 Temperature Sensor...............................................................................................................................230 5.5 IBBS200T Cables...........................................................................................................................................235 5.5.1 Cable List...............................................................................................................................................235 5.5.2 Cable Connections.................................................................................................................................237 5.5.3 PGND Cable..........................................................................................................................................239 5.5.4 Equipotential Cable...............................................................................................................................244 5.5.5 Power Cables.........................................................................................................................................249 5.5.6 Signal Cables.........................................................................................................................................255

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

1 Changes in APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description


This chapter describes the changes in the APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description.

Changes in

03 (2013-01-15)
This is the third commercial release. Compared with 02 (2012-12-30), no information is added. Compared with 02 (2012-12-30), this issue incorporates the following changes. Topic l EPU05A-02 or EPU05A-04 Power Cable l Power Cable for the EPU05A-03 or EPU05A-05 l 3.5.1 DCDU-12B l 3.5.2 DCDU-12C l 2.6.1 EPU05A l 2.6.3 FAN 02D l PMU 11A l PSU (R4850G2) Change Description Changed the input power cable for the APM30H to the EPU05A-02 or EPU05A-04 power cable and the EPU05A-03 or EPU05A-05 power cable.

Changed the input power cable for the TMC11H to the DCDU-12B power cable and the DCDU-12C power cable. Specified the models of the EPU, fan assembly, PMU, and PSU.Specified the models of the EPU, fan assembly, PMU, and PSU.

Compared with 02 (2012-12-30), no information is deleted.

02 (2012-12-30)
This is the second commercial release.
Issue 03 (2013-01-15) Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd. 1

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

1 Changes in APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

Compared with 01 (2012-11-10), no information is added. Compared with 01 (2012-11-10), this issue incorporates the following changes. Topic Power Cables for a Fan Assembly Input Power Cable for a TMC11H Power Cables for the Fan in an IBBS200D TEC Power Cables Power Cables in a Battery Cabinet DCDU-12B Input Power Cable Technical Specifications of an APM30H Modified the input protection. Change Description Added the description of the cables complying with British Standards (BS).

Compared with 01 (2012-11-10), no information is deleted.

01 (2012-11-10)
This is the first commercial release. Compared with draft A (2012-09-15), no information is added or deleted. Compared with draft A (2012-09-15), some descriptions are optimized, and changed the APM30H (Ver.D2) and TMC11H (Ver.D2) cabinets to APM30H (Ver.D) and TMC11H (Ver.D), respectively. Compared with draft A (2012-09-15), all information about the APM30H (Ver.D1) and TMC11H (Ver.D1) is deleted from this issue.

Draft A (2012-09-15)
This is a draft.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

2
About This Chapter

APM30H Cabinet

This chapter describes the APM30H cabinet exterior, engineering specifications, application scenarios, as well as boards, modules, and cables in the APM30H cabinet. 2.1 Cabinet Exterior The advanced power module with heat exchanger (APM30H) is used for Huawei wireless products outdoors. It is small and easy to transport. 2.2 Cabinet Engineering Specifications This section describes the engineering specifications of the APM30H, including the power specifications, equipment specifications, surge protection specifications, and environment specifications. 2.3 Engineering Specifications of Customer Equipment in APM or TMC Series Cabinets The customer equipment to be installed in APM or TMC series cabinets must meet the requirements for engineering specifications. 2.4 Cabinet Application Scenarios The APM30H can apply to a distributed base station or a separated macro base station. 2.5 Cabinet Interior The APM30H supplies DC power to the distributed or separated macro base station in outdoor scenarios. It provides space for both the BBU and transmission equipment. If an AC heater or an SOU is not configured in the APM30H and one BBU is installed, 5 U space is provided for the customer equipment. 2.6 Components in an APM30H This section describes the mandatory and optional components in an APM30H. 2.7 APM30H Cables The APM30H cables consist of the power cables, equipotential cables, PGND cables, and signal cables.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

2.1 Cabinet Exterior


The advanced power module with heat exchanger (APM30H) is used for Huawei wireless products outdoors. It is small and easy to transport. The following figure shows the exterior of the APM30H. Figure 2-1 Exterior of the APM30H

2.2 Cabinet Engineering Specifications


This section describes the engineering specifications of the APM30H, including the power specifications, equipment specifications, surge protection specifications, and environment specifications.

Power Specifications
The APM30H supports the input power of 220 V AC single-phase, 220/380 V AC three-phase, 110 V AC dual-live-wire, 120 V AC dual-live-wire, and the output power of -48 V DC. When AC power is used, the base station converts AC power into -48 V DC power. The following table lists the AC input voltage range supported by the APM30H.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Table 2-1 AC input specifications Power Supply 220 V AC single-phase 220/380 V AC threephase 110 V AC dual-livewire 120 V AC dual-livewire Rated Voltage 200 V AC to 240 V AC 200/346 V AC to 240/415 V AC 100/200 V AC to 120/240 V AC 120/208 V AC to 127/220 V AC Operating Voltage 176 V AC to 290 V AC 176/304 V AC to 290/500 V AC 90/180 V AC to 135/270 V AC 105/176 V AC to 150/260 V AC Rated Input Current 80 A 32 A Input Voltage Frequency 45 Hz to 65 Hz Input Protection l Overvolt age protectio n: The system generates an alarm when the input voltage exceeds the AC overvolta ge alarm threshold (301 V by default). l Undervol tage protectio n: The system generates an alarm when the input voltage is lower than the AC undervolt age alarm threshold (74 V by default).

80 A

80 A

Heat consumption in the APM30H: 1500 W (heat dissipation capability at the ambient temperature of 50oC or 122oF) (including the BBU, power system, and transmission equipment)

Equipment Specifications
The following table lists the equipment specifications of the APM30H.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Table 2-2 Equipment specifications Item Dimensions (H x W x D) Specifications Cabinet (without the base): 700 mm x 600 mm x 480 mm (27.56 in. x 23.62 in. x 18.90 in.) Base: 200 mm x 600 mm x 434 mm (7.87 in. x 23.62 in. x 17.09 in.) Space for the customer equipment (H x W x D) Configured with one BBU: 5 U x 19 in. x 380 mm Configured with two BBUs: 3U x 19 in. x 380 mm 68 kg (149.94 lb) Total weight of the equipment l Including the cabinet frame, inner air circulation fan, outer air circulation fan, core of the heat exchanger, EPU subrack, and cables l Excluding the BBU, customer transmission equipment, PMU, and PSUs 87 kg (191.84 lb) Weight with full configuration l Including the total weight of the equipment, one PMU, five PSUs, and one BBU l Excluding the customer transmission equipment Cabling and maintenance space at the front 70 mm (2.76 in.) The depth includes 280 mm (11.02 in.) away from the rear of the subrack mounting ears and 100 mm (3.94 in.) away from the front. Remarks -

Cabinet weight

Surge Protection Specifications


The following table lists the surge protection specifications of the APM30H. Table 2-3 Surge protection specifications Item Surge protection for AC input ports Specifications In differential mode: l Rated through-current capacity (8/20 us): 30 kA l Maximum through-current capacity (8/20 us): 60 kA

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Item

Specifications In common mode: l Rated through-current capacity (8/20 us): 30 kA l Maximum through-current capacity (8/20 us): 60 kA

Surge protection for DC output ports

l In differential mode (8/20 us): 10 kA l In common mode (8/20 us): 20 kA The DC output corresponds to the secondary load.
NOTE The surge protection capacity of the shield layer in an RRU power cable is 40 kA.

Surge protection for signal ports

E1/T1 port: l In differential mode (8/20 us): 3 kA l In common mode (8/20 us): 5 kA FE port: l In differential mode (8/20 us): 3 kA l In common mode (8/20 us): 5 kA

Environment Specifications
The APM30H can be used outdoors. The following table lists the environment specifications of the APM30H. Table 2-4 Environment specifications Item Operating temperatur e Specifications -40oC to +50oC (-40oF to +122oF) Remarks A heater is required when the temperature is lower than -20oC (-4oF). A sun shield is required when the temperature is higher than 50oC (122oF).
NOTE The temperature at which the heater is required is specified as the local average lowest temperature of each day in the coldest month of the year.

Relative humidity Altitude

5% RH to 100% RH -60 m to +4000 m (-196.85 ft to +13123.2 ft)

From the altitude of 1800 m (5905.44 ft), the maximum operating temperature drops by 1oC (33.8oF) each time the altitude increases by 220 m (721.78 ft).

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Item Wind speed Storage temperatur e Dustproof and waterproof Noise

Specifications 67 m/s -40oC to +70oC (-40oF to +158oF)

Remarks -

IP55

When the heat consumption of the cabinet is equal to or less than 700 W, the noise is equal to or less than 61 dBA at the temperature of 25oC (77oF) and equal to or less than 67 dBA at the temperature of 45oC (113oF). When the heat consumption of the cabinet is equal to 1050 W or between 700 W and 1050 W, the noise is equal to or less than 66 dBA at the temperature of 25oC (77oF) and equal to or less than 76 dBA at the temperature of 45oC (113oF).

Meeting the ETS 300 753 4.1E standard (rural area)

Meeting the ETS 300 753 4.1E standard (urban area)

2.3 Engineering Specifications of Customer Equipment in APM or TMC Series Cabinets


The customer equipment to be installed in APM or TMC series cabinets must meet the requirements for engineering specifications. The customer equipment to be installed in the APM30H (Ver.B), APM30H (Ver.C), APM30H (Ver.D), TMC11H (Ver.B), TMC11H (Ver.C), or TMC11H (Ver.D) must meet the following requirements: l Dimension requirements The dimension requirements are shown in Figure 2-2. The width is 19 inch. The depth of the customer equipment which uses natural ventilation or supports heat dissipation from left to right is less than or equal to 280 mm (11.02 in.). The depth of the customer equipment which supports heat dissipation from front to rear is less than 250 mm (9.84 in.). The cabling space in front of the front panel is less than or equal to 100 mm (3.94 in.). l Heat dissipation requirements

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

If the customer equipment has built-in fans, the fans must dissipate heat out from left to right or from front to rear. If the customer equipment does not have built-in fans but uses natural ventilation, a minimum of 1 U space must be reserved above and below the customer equipment to ensure heat dissipation. l Temperature requirements The following table lists the temperature requirements. Table 2-5 Temperature requirements for the customer equipment Highest Environmental Temperature Equal to or lower than 40 C (104F) Higher than 40C (104F) Lowest Operating Temperature for the Customer Equipment Highest Operating Temperature for the Customer Equipment

Equal to or lower than -10 Equal to or higher than 55 C (14F) C (131F) Equal to or lower than -10 Equal to or higher than 60 C (14F) C (140F)

Figure 2-2 Dimension requirements and heat dissipation requirements

(1) Equipment using natural ventilation

(2) Equipment dissipating heat out (3) Equipment dissipating heat out from left to right from front to rear

The customer equipment to be installed in the APM30, APM30H (Ver.A), TMC, or TMC11H (Ver.A) must meet the following requirements: l Dimension requirements The dimension requirements are shown in Figure 2-3.
Issue 03 (2013-01-15) Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd. 9

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

The width is 19 inch. The depth of the customer equipment which uses natural ventilation or supports heat dissipation from left to right is less than or equal to 310 mm (12.20 in.). The depth of the customer equipment which supports heat dissipation from front to rear is less than 280 mm (11.02 in.). The cabling space in front of the front panel is less than or equal to 70 mm (2.76 in.). l Heat dissipation requirements If the customer equipment has built-in fans, the fans must dissipate heat out from left to right or from front to rear. If the customer equipment does not have built-in fans but uses natural ventilation, a minimum of 1 U space must be reserved above and below the customer equipment to ensure heat dissipation. l Temperature requirements The following table lists the temperature requirements. Table 2-6 Temperature requirements for the customer equipment Highest Environmental Temperature Equal to or lower than 40 C (104F) Higher than 40C (104F) Lowest Operating Temperature for the Customer Equipment Highest Operating Temperature for the Customer Equipment

Equal to or lower than -10 Equal to or higher than 55 C (14F) C (131F) Equal to or lower than -10 Equal to or higher than 60 C (14F) C (140F)

Figure 2-3 Dimension requirements and heat dissipation requirements

(1) Equipment using natural ventilation

(2) Equipment dissipating heat out (3) Equipment dissipating heat out from left to right from front to rear

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

10

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

2.4 Cabinet Application Scenarios


The APM30H can apply to a distributed base station or a separated macro base station.

Distributed Base Stations Configured with an APM30H


NOTE

Distributed or separated base stations configured with an IBBS200D and with an IBBS200T are the same in scenarios configured with an APM30H. This section uses the IBBS200D as an example.

The following figure shows the distributed base station where an APM30H is stacked on a battery cabinet. Figure 2-4 Distributed base station where an APM30H is stacked on a battery cabinet

In a distributed base station, an APM30H is configured as follows:

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

11

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

The APM30H provides 5 U space for transmission equipment and uses an embedded power system to feed -48 V DC power into the distributed base station, transmission equipment, and storage battery groups in the battery cabinet. When the mains power supply is unavailable, storage battery groups feed -48 V DC power into the distributed base station and transmission equipment.

Separated Macro Base Stations Configured with an APM30H


The following figure shows the separated macro base station configured with an APM30H. Figure 2-5 Separated macro base station configured with an APM30H

In a separated macro base station, an APM30H is configured as follows: l The APM30H provides 5 U space for transmission equipment and uses an embedded power system to feed -48 V DC power into the BBU, RFUs, transmission equipment, and storage battery groups in the battery cabinet. When the mains power supply is unavailable, storage battery groups feed -48 V DC power into the BBU, RFUs, and transmission equipment. The APM30H reports alarms from the fans of the RFC, door status sensor, DCDU, and battery cabinet.
Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd. 12

l l

Issue 03 (2013-01-15)

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

2.5 Cabinet Interior


The APM30H supplies DC power to the distributed or separated macro base station in outdoor scenarios. It provides space for both the BBU and transmission equipment. If an AC heater or an SOU is not configured in the APM30H and one BBU is installed, 5 U space is provided for the customer equipment. The following figure shows the interior of the APM30H. The following figure uses an APM30H in the separated macro base station as an example. For more details about the interior of the APM30H in a distributed base station, see DBS3900 Hardware Description. Figure 2-6 Interior of the APM30H

The following table describes the components in the APM30H.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

13

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Table 2-7 Components in the APM30H N o. Compone nt Op tio nal or Ma nd ato ry Ma xim um Qu anti ty in a Sin gle Cab inet 1 Remarks

Outer air circulation assembly Junction box

Ma nda tor y Ma nda tor y Ma nda tor y Ma nda tor y

The assembly is installed on the front door, providing inner and outer air circulation and dissipating heat from the cabinet. The junction box converts one AC input to four AC outputs and is used in the scenario where a service outlet unit (SOU) and multiple heating films or heaters are configured. The fan assembly is configured with fans and central monitoring unit type EA (CMUEA), dissipating heat from the cabinet. l To provide protection for trunk signals, a signal lightning protection unit (SLPU) is mandatory and installed in the top 1 U space of the cabinet. It is configured with the universal E1/T1 lightning protection unit (UELP) or universal FE lightning protection unit (UFLP). l To provide protection for monitoring signals, an SLPU is optional and installed in the 1 U space below the BBU. It is configured with two universal signal lightning protection unit 2 (USLP2) boards.

FAN 02D

SLPU

Door status sensor

Ma nda tor y Ma nda tor y Ma nda tor y

The door status sensor monitors the status (open or closed) of the cabinet door.

ELU

The electronic label unit (ELU) reports the cabinet type automatically to facilitate troubleshooting.

EPU05A

The EPU converts AC input power to DC output power and distributes the DC power to all the components in the cabinet. The EPU consists of the EPU subrack, PMU, and PSUs.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

14

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

N o.

Compone nt

Op tio nal or Ma nd ato ry

Ma xim um Qu anti ty in a Sin gle Cab inet 2

Remarks

BBU3900

Opt ion al

A maximum of two BBU3900s can be configured in an APM30H. l The BBU3900 provides physical ports for communication between the BBU3900 and the BSC or RNC, and enables interaction between the base station and the BSC or RNC. l The BBU3900 provides CPRI ports for communication between the BBU and RF modules. l The BBU3900 processes uplink and downlink data.

EMUA

Opt ion al Ma nda tor y Opt ion al

The environment monitoring unit type A (EMUA) monitors environment of the equipment. A filler module is a 1 U high plastic component, which prevents the heat reflux in the empty space below the BBU.

10

Filler module

11

AC heater

The AC heater ensures that components in the cabinet work within the acceptable temperature range when the surrounding temperature is low. It can be installed in the 1 U space at the bottom of the cabinet. If both an AC heater and an SOU are configured, the heater is installed in the 1 U space above the SOU. The service outlet unit (SOU) transfers AC power supply to the customer equipment. It can be installed in the 1 U space at the bottom of the cabinet.

12

SOU

Opt ion al

2.6 Components in an APM30H


This section describes the mandatory and optional components in an APM30H.

2.6.1 EPU05A
An EPU05A converts AC power into DC power and distributes power.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

15

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Components of an EPU05A-02 or EPU05A-04


An EPU05A-02 or EPU05A-04 consists of an EPU05A-02 or EPU05A-04 subrack, a PMU 11A, and PSUs (R4850G2). The following figure shows the components of an EPU05A-02 or EPU05A-04. Figure 2-7 Components of an EPU05A-02 or EPU05A-04

(1) PMU 11A

(2) PSU (R4850G2)

(3) Filler panel

(4) EPU05A-02 or EPU05A-04 Subrack

The following table describes the components of an EPU05A-02 or EPU05A-04. Table 2-8 Components of an EPU05A-02 or EPU05A-04 Module PMU 11A PSU (R4850G2) Description It is installed in slot 0. A minimum of two PSUs must be configured. The PSUs must be installed in adjacent slots in the sequence of slot 1 to slot 5. A filler panel must be installed in a slot not configured with a PSU (R4850G2). Figure 2-7 shows how slots are numbered in an EPU05A-02 or EPU05A-04 subrack.

Filler panel EPU05A-02 or EPU05A-04 subrack

Components of an EPU05A-03 or EPU05A-05


An EPU05A-03 or EPU05A-05 consists of an EPU05A-03 or EPU05A-05 subrack, a PMU 11A, and PSUs (R4850G2).
Issue 03 (2013-01-15) Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd. 16

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

The following figure shows the components of the EPU05A-03 or EPU05A-05. Figure 2-8 Components of the EPU05A-03 or EPU05A-05

(1) PMU 11A

(2) PSU (R4850G2)

(3) Filler panel

(4) EPU05A-03 or EPU05A-05 Subrack

The following table describes the components of the EPU05A-03 or EPU05A-05. Table 2-9 Components of the EPU05A-03 or EPU05A-05 Module PMU 11A PSU (R4850G2) Description It is installed in slot 0. A minimum of two PSUs must be configured. The PSUs must be installed in adjacent slots sequentially from slot 1 to slot 5. A maximum of five PSUs can be configured in the APM30H (Ver.D). Filler panels must be installed in vacant slots. Figure 2-8 shows how slots are numbered in the EPU05A-03 or EPU05A-05 subrack.

Filler panel

EPU05A-03 or EPU05A-05 subrack

EPU05A-02 or EPU05A-04 Subrack


An EPU05A-02 or EPU05A-04 subrack houses the PMU 11A and PSUs (R4850G2). It also distributes AC input power and DC output power. An EPU05A-02 or EPU05A-04 applies to a separated macro base station.
Issue 03 (2013-01-15) Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd. 17

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Application of an EPU05A-02 or EPU05A-04 Subrack


The following table describes the application of an EPU05A-02 or EPU05A-04 subrack. Table 2-10 Application of an EPU05A-02 or EPU05A-04 subrack Type Description It is a 5 U subrack and houses a maximum of five PSUs (R4850G2) and one PMU. It distributes large- and smallcapacity DC power. It is a 5 U subrack and houses a maximum of five PSUs (R4850G2) and one PMU. It distributes large- and smallcapacity DC power. Application

EPU05A -02

Separated macro base station with external 220 V AC input

EPU05A -04

Separated macro base station with external 110 V AC input

Exterior
Figure 2-9 and Figure 2-10 show the exteriors of EPU05A-02 and EPU05A-04 subracks, respectively.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

18

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Figure 2-9 Exterior of an EPU05A-02 subrack

(1) AC surge protector

(2) PSU1/4 circuit breaker, (3) AC OUTPUT circuit PSU2/5 circuit breaker, and breaker PSU3 circuit breaker (6) Circuit breaker for RFC2 (10) LOAD0 to LOAD8 output ports (14) AC OUTPUT (7) Output port for the storage battery (11) Spare fuse box -

(4) BAT circuit breaker

(5) Circuit breaker for RFC1 (9) RFC2 output port (13) AC INPUT
NOTE

(8) RFC1 output port (12) Short-circuiting bar(1) -

When a short-circuiting bar is installed on the AC INPUT wiring terminal to connect the L1, L2, and L3 terminals, the EPU subrack supplies 220 V AC single-phase power. When the short-circuiting bar is not installed on the AC INPUT wiring terminal, the EPU subrack supplies 220 V AC three-phase power.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

19

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Figure 2-10 Exterior of an EPU05A-04 subrack

(1) AC surge protector (5) Circuit breaker for RFC1 (9) RFC2 output port (13) AC OUTPUT

(2) PSU circuit breaker (6) Circuit breaker for RFC2

(3) AC OUTPUT1/AC OUTPUT2 circuit breaker

(4) BAT circuit breaker

(7) Output port for the storage (8) RFC1 output port battery (12) AC INPUT -

(10) LOAD0 to LOAD8 (11) Spare fuse box output ports -

Function
An EPU05A-02 or EPU05A-04 subrack distributes AC and DC power. l An EPU05A-02 or EPU05A-04 subrack performs the following AC power distribution functions: Provides two AC outputs. One is used for the service outlet unit (SOU). The other one is connected to the AC junction box on the left of the cabinet, and divided into four AC power outputs, which are then provided for the heater or heating film. Reports AC input surge protection alarms. l An EPU05A-02 or EPU05A-04 subrack provides 12 DC outputs for a separated macro base station.

Port
The following figure shows the power input and output ports on an EPU05A-02 or EPU05A-04 subrack. Table 2-11 and Table 2-12 list the ports in detail.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

20

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Figure 2-11 Power input and output ports on an EPU05A-02 or EPU05A-04 subrack

Table 2-11 AC input and output ports on an EPU05A-02 or EPU05A-04 subrack AC Input/Output Terminal AC INPUT AC OUTPUT Wiring Terminal L1, L2, L3, N L1, N1, L2, N2 Connector OT terminal (M6)

Table 2-12 DC input and output ports and terminals on an EPU05A-02 or EPU05A-04 subrack DC output ports LOAD0 and LOAD1 LOAD2 LOAD3 LOAD4 LOAD5 LOAD6 LOAD7 LOAD8 DC Power Supply Unit BBU FAN TM_0(1) TM_1 TM_2 or EMUA TM_3 or BBU TMC IBBS(2) Protector Fuse(3) Protector Specification 2x30 A 1x30 A Connector EPC4 or EPC6

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

21

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

DC output ports RFC1 RFC2 BAT

DC Power Supply Unit RFC1 RFC2 BAT

Protector Breaker

Protector Specification 1x125 A

Connector OT terminal (M6) OT terminal (M8)

1x250 A

NOTE

(1) TM is the customer transmission equipment. LOAD3, LOAD4, LOAD5, and LOAD6 are DC output terminals for the transmission equipment, supporting four DC outputs. (2) When the IBBS200D is configured, LOAD8 is the DC output port for the IBBS200D fan power cable. When IBBS200T is configured, LOAD8 is the DC output port for the IBBS200T TEC power cable. (3) The spare fuse box contains five 5 A fuses and three 30 A fuses for onsite replacement.

Circuit Breaker
There are several circuit breakers on the EPU05A-02 or EPU05A-04 subrack panel to control the DC outputs. The following figure shows the positions of circuit breakers and the following table describes the specifications of circuit breakers. Figure 2-12 Circuit breakers on an EPU05A-02 or EPU05A-04 subrack

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

22

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Table 2-13 Circuit breakers on an EPU05A-02 or EPU05A-04 subrack Circuit Breaker PSU circuit breakers (EPU05A-02) Silkscreen on the Panel PSU1/4 PSU2/5 PSU3 PSU circuit breakers (EPU05A-04) AC output circuit breaker (EPU05A-02) AC output circuit breaker (EPU05A-04) Storage battery circuit breaker RFC circuit breaker PSU AC OUTPUT AC OUTPUT1 and AC OUTPUT2 BAT RFC 1 and RFC 2 Requirement for the Circuit Breaker 1x40 A/1 P 1x40 A/1 P 1x25 A/1 P 1x100 A/2 P 1x16 A/2 P 2x16 A/1 P 1x125 A/2 P 2x125 A/1 P

Technical Specifications
The following table describes the technical specifications of an EPU05A-02 or EPU05A-04 subrack. Table 2-14 Technical specifications of an EPU05A-02 or EPU05A-04 subrack Component Output voltage Rated voltage Output current Specifications -44 V DC to -58 V DC -53.5 V DC 0 A to 250 A

EPU05A-03 or EPU05A-05 Subrack


An EPU05A-03 or EPU05A-05 subrack houses the PMU 11A and PSUs (R4850G2). It also distributes AC and DC power. The EPU05A-03 and EPU05A-05 subrack applies to a distributed base station.

Applications of an EPU05A-03 or EPU05A-05 Subrack


The following table describes the applications of an EPU05A-03 or EPU05A-05 subrack.
Issue 03 (2013-01-15) Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd. 23

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Table 2-15 Applications of the EPU05A-03 or EPU05A-05 subrack Type Description It is a 5 U subrack and houses a maximum of five PSUs (R4850G2) and one PMU 11A. It distributes large- and small-capacity DC power. It is a 5 U subrack and houses a maximum of five PSUs (R4850G2) and one PMU 11A. It distributes large- and small-capacity DC power. Application

EPU05A -03

Distributed base station supplied with 220 V AC power

EPU05A -05

Distributed base station supplied with 110 V AC power

Exteriors
Figure 2-13 and Figure 2-14 show the exteriors of the EPU05A-03 and EPU05A-05 subracks, respectively. Figure 2-13 Exterior of the EPU05A-03 subrack

(1) AC surge protector

(2) PSU1/4 circuit (3) AC OUTPUT circuit breaker, PSU2/5 circuit breaker breaker, and PSU3 circuit breaker

(4) BAT circuit breaker

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

24

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description


(5) Circuit breaker for RFC (6) Output terminal for 1 storage batteries (9) Output terminals for RRU 0 to RRU 5 (13) AC OUTPUT
NOTE

2 APM30H Cabinet
(7) Output terminal for RFC 1 (8) Output terminals for LOAD 0 to LOAD 8

(10) Spare fuse box -

(11) Short-circuiting bar(1) (12) AC INPUT -

When a short-circuiting bar is installed on the AC INPUT wiring terminal to connect the L1, L2, and L3 terminals, the EPU subrack supports 220 V AC single-phase power. When no short-circuiting bar is installed on the AC INPUT wiring terminal, the EPU subrack supports 220 V AC three-phase power.

Figure 2-14 Exterior of the EPU05A-05 subrack

(1) AC surge protector

(2) PSU circuit breaker

(3) AC OUTPUT 1 or AC (4) BAT circuit breaker OUTPUT 2 circuit breaker (7) Output terminal for RFC 1 (11) AC INPUT (8) LOAD 0 to LOAD 8 output terminals (12) AC OUTPUT

(5) Circuit breaker for RFC (6) Output terminal for 1 storage batteries (9) Output terminals for RRU 0 to RRU 5 (10) Spare fuse box

Function
An EPU05A-03 or EPU05A-05 distributes AC and DC power. l An EPU05A-03 or EPU05A-05 subrack performs the following AC power distribution functions: Provides two AC outputs. One is used for the service outlet unit (SOU). The other one is connected to the junction box on the left side of the cabinet interior, and divided into four AC power outputs, which are then provided to the heater or heating film. Reports AC input surge protection alarms.
Issue 03 (2013-01-15) Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd. 25

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

An EPU05A-03 or EPU05A-05 subrack provides 17 DC outputs for a distributed base station.

Terminals
The following figure shows the power input and output terminals on the EPU05A-03 or EPU05A-05 subrack, as shown in Table 2-16, Table 2-17. Figure 2-15 Power input and output terminals on the EPU05A-03 or EPU05A-05 subrack

Table 2-16 AC input and output terminals on the EPU05A-03 or EPU05A-05 subrack AC Input/Output Terminal AC INPUT AC OUTPUT Wiring Terminal L1, L2, L3, N L1, N1, L2, N2 Connector OT terminal (M6)

Table 2-17 DC input and output terminals on the EPU05A-03 or EPU05A-05 subrack DC Output Terminal LOAD 0 and LOAD 1 LOAD 2
Issue 03 (2013-01-15)

DC Power Supply Unit BBU FAN

Protector Fuse(3)

Protector Specification 2x30 A 1x30 A

Connector EPC 4 or EPC 6

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

26

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

DC Output Terminal LOAD 3 LOAD 4 LOAD 5 LOAD 6 LOAD 7 LOAD 8 RRU 0 to RRU 5 RFC 1 BAT

DC Power Supply Unit TM_0(1) TM_1 TM_2 or EMUA TM_3 or BBU TMC IBBS(2) RRU RFC BAT

Protector

Protector Specification

Connector

EPC 5 Breaker 1x125 A 1x250 A OT terminal (M6) OT terminal (M8)

NOTE

(1) TM is the customer transmission equipment. LOAD3, LOAD4, LOAD5, and LOAD6 are DC output terminals for the transmission equipment, supporting four DC outputs. (2) When the IBBS200D is configured, LOAD8 is the DC output terminal connecting to the IBBS200D fan power cable. When IBBS200T is configured, LOAD8 is the DC output terminal connecting to the IBBS200T TEC power cable. (3) The spare fuse box can provide five 5 A fuses and three 30 A fuses, which can be used to replace broken ones onsite.

Circuit Breakers
There are several circuit breakers on the EPU05A-03 or EPU05A-05 subrack panel to control the DC outputs. The following figure shows the positions of the circuit breakers and the following table describes the specifications of the circuit breakers.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

27

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Figure 2-16 Circuit breakers on the EPU05A-03 or EPU05A-05 subrack

Table 2-18 Specifications of the circuit breakers on the EPU05A-03 or EPU05A-05 subrack Circuit Breaker PSU circuit breakers (EPU05A-03) Silkscreen PSU1/4 PSU2/5 PSU3 PSU circuit breaker (EPU05A-05) AC output circuit breaker (EPU05A-03) AC output circuit breakers (EPU05A-05) PSU AC OUTPUT AC OUTPUT1 and AC OUTPUT2 Requirement for the Circuit Breaker 1x40 A/1 P 1x40 A/1 P 1x25 A/1 P 1x100 A/2 P 1x16 A/2 P 2x16 A/1 P

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

28

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Circuit Breaker Circuit breaker for storage batteries RFC circuit breaker

Silkscreen BAT RFC1

Requirement for the Circuit Breaker 1x125 A/2 P 1x125 A/1 P

Technical Specifications
The following table describes the technical specifications of the EPU05A-03 or EPU05A-05 subrack. Table 2-19 Technical specifications of the EPU05A-03 or EPU05A-05 subrack Component Output voltage Rated voltage Output current Specifications -44 V DC to -58 V DC -53.5 V DC 0 A to 250 A

PMU 11A
A power monitoring unit 11A (PMU 11A) manages the power system and battery, monitors power distribution, and reports alarms.

Exterior
The following figure shows the exterior of a PMU 11A. Figure 2-17 Exterior of a PMU 11A

Function
A PMU 11A performs the following functions:
Issue 03 (2013-01-15) Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd. 29

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

l l l l l

Communicates with the upper-level device through an RS485 port. Manages the power system and the charge and discharge of storage batteries. Monitors the door status and the temperature of storage batteries. Monitors power distribution and reports alarms. Communicates with the battery cabinet through an RS485 port.

Port
The following figure shows the ports on a PMU 11A. Figure 2-18 Ports on a PMU 11A

The following table describes the ports on a PMU 11A. Table 2-20 Ports on a PMU 11A No. 1 2 3 4 5 Silkscreen GATE TEM_BAT COM_IN COM_OUT COM_485 Connector 2-pin connector 2-pin connector RJ45 connector RJ45 connector RJ45 connector Description Connects to a door status sensor. Connects to a battery temperature sensor. Connects to the BBU or communicates with the upper-level monitoring board. Communicates with the lower-level monitoring board. Connects to the monitoring board in the battery cabinet, and receives monitoring signals from the battery cabinet.

Indicator
The following table describes the indicators on a PMU 11A.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

30

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Table 2-21 Indicators on a PMU 11A Silksc reen RUN Meanin g Running indicator Color Green State Steady on Blinking (on for 1s and off for 1s) Description The module is performing startup, selfcheck, loading, and activation. The PMU 11A is functional and communicating with the main control board in the BBU properly. (This status does not necessarily mean that the PMU 11A has been configured.) The PMU 11A is functional but unable to communicate properly. The module is faulty or there is no DC power supply. Alarms are generated, and the module must be replaced. No alarm is generated. An alarm is generated and you need to locate the fault before determining whether to replace the module.

Blinking (on for 0.125s and off for 0.125s) Steady off ALM Alarm indicator Red Steady on Steady off Blinking (on for 1s and off for 1s)

DIP Switch
There is a DIP switch on the left panel of the PMU 11A. The DIP switch has eight bits, where the four least significant bits 1, 2, 3, and 4 define the monitoring address of the PMU 11A, and the four most significant bits 5, 6, 7, and 8 are not defined but reserved for future use. ON is indicated by 1, and OFF is indicated by 0. The monitoring address of the PMU 11A is set to 3 by default before delivery, as shown in the following figure. Figure 2-19 DIP switch on the left panel of the PMU 11A

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

31

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description


NOTE

2 APM30H Cabinet

At a site configured with two or more APM30Hs, if two PMU units are connected to one RS485 bus for the BBU, the monitoring address of the other PMU is set to 4. That is, the lower four bits of the DIP switch are set to 0010.

PSU (R4850G2)
A power supply unit (PSU) (R4850G2) converts 110 V AC or 220 V AC power into -48 V DC.

Exterior
The following figure shows the exterior of a PSU (R4850G2). Figure 2-20 Exterior of a PSU (R4850G2)

Function
A PSU (R4850G2) performs the following functions: l l l Converts 110 V AC or 220 V AC power into -48 V DC and adjusts the output voltage. Provides protection against overcurrent, overvoltage, and overtemperature for its DC outputs. Dissipates heat using its built-in fans.

Indicator
The following figure shows the indicators on a PSU (R4850G2). Figure 2-21 Indicators on a PSU (R4850G2)

The following table describes the indicators on a PSU (R4850G2).


Issue 03 (2013-01-15) Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd. 32

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Table 2-22 Indicators on a PSU (R4850G2) Silkscree n (1) Power indicator Color Green State Steady on Blinking (on for 0.125s and off for 0.125s) Steady off (2) Protection indicator Yello w Steady off Steady on Blinking (on for 1s and off for 1s) (3) Fault indicator Red Steady off Steady on Description The board is functional. The PSU is loading software online. The mains supply or the module is faulty. Yes An alarm triggered by an external factor is generated. The communication between the module and the PMU is interrupted. Yes The module is faulty or is shut down in an emergency. Locate the fault and replace the module.

2.6.2 Junction Box


The junction box is configured in the BTS3900AL, APM30H, TMC11H, IBBS700D, or IBBS700T cabinet. When a heater or a heating film is configured, the junction box feeds power to the heater or the heating film.

Exterior
A junction box is installed on the left inner side of the APM30H, TMC11H, IBBS700D, or IBBS700T. In the BTS3900AL, the junction box is installed on the right inner side of the cabinet. The following figure shows the position and exterior of the junction box in the APM30H.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

33

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Figure 2-22 Exterior of the junction box

Functions
The junction box used in the BTS3900AL, APM30H, TMC11H, IBBS700D and IBBS700T performs the following functions: l l The PDU05A-01 feeds power to the junction box in the BTS3900AL. The power is divided into four AC power outputs, which are then provided for the heater in the cabinet. The EPU subrack feeds power into the junction box in the APM30H. The power is divided into four AC power outputs, which are then provided for the heater in the cabinet or heating film in the IBBS200D. The junction box in the APM30H feeds power into the junction box in the TMC11H. The power is divided into four AC power outputs, which are then provided for the heater or service outlet unit (SOU) in the cabinet. The junction box in the primary cabinet (BTS3900A, BTS3900AL, or TP48600A-H17B1) feeds power into the junction box in the IBBS700D or IBBS700T. The power is divided into four AC power outputs, which are then provided for the heater in the cabinet.

Interior
The following figure shows the interior of an AC junction box.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

34

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Figure 2-23 Interior of an AC junction box

(1) Four AC output L wiring terminals (4) Cable holes

(2) Four AC output N wiring terminals (5) AC input N wiring terminal

(3) Four AC output PE wiring terminals (6) AC input L wiring terminal

2.6.3 FAN 02D


A FAN 02C dissipates heat and detects temperature for an APM30H (Ver.D) or TMC11H (Ver.D).

Exterior
A FAN 02D consists of the fan subrack, fans, and CMUEA. The following figure shows the exterior of a FAN 02D. Figure 2-24 Exterior of a FAN 02D

(1) Fan subrack

(2) Fans

(3) CMUEA

For details about the ports and indicators on the CMUEA, see CMUEA.
Issue 03 (2013-01-15) Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd. 35

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

2.6.4 ELU
An electronic label unit (ELU) reports the cabinet type automatically to facilitate troubleshooting.

Exterior
The following figure shows the exterior of an ELU. Figure 2-25 Exterior of an ELU

(1) Shell

(2) RJ45 port

NOTE

The ELU in a BTS3900 or BTS3900L has no shell.

The board collecting information from the ELU varies according to the cabinet, as listed in the following table. Table 2-23 Monitoring boards to which an ELU reports information Base Station Type BTS3900 (Ver.B) and BTS3900L (Ver.B) BTS3900 (Ver.C) and BTS3900L (Ver.C) BTS3900 (Ver.D) and BTS3900L (Ver.D)
Issue 03 (2013-01-15)

Cabinet

Board Collecting Information from the ELU FMUC

BTS3900 (Ver.B) and BTS3900L (Ver.B)

BTS3900 (Ver.C) and BTS3900L (Ver.C)

FMUE

BTS3900 (Ver.D) and BTS3900L (Ver.D)

FMUEA

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

36

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Base Station Type BTS3900A (Ver.B) BTS3900A (Ver.C) BTS3900A (Ver.D)

Cabinet

Board Collecting Information from the ELU CMUA

APM30H (Ver.B), TMC11H (Ver.B), RFC (Ver.B), IBBS200D (Ver.B), and IBBS200T (Ver.B) APM30H (Ver.C), TMC11H (Ver.C), RFC (Ver.C), IBBS200D (Ver.C), and IBBS200T (Ver.C) APM30H (Ver.D), TMC11H(Ver.D), RFC (Ver.D), IBBS200D(Ver.D), IBBS200T (Ver.D), and IBBS700D IBBS700T

CMUE

CMUEA

CMUF HEUB CCU

BTS3900C (Ver.C) BTS3900AL (Ver.A)

OMB (Ver.C) BTS3900AL (Ver.A), IBBS700D, IBBS700T

Installation Position
Positions of ELUs vary in different cabinets. The following figure shows their positions. Figure 2-26 Position of the ELU in a BTS3900 cabinet

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

37

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Figure 2-27 Position of the ELU in a BTS3900L cabinet

Figure 2-28 Position of the ELU in an APM30H or IBBS200D cabinet

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

38

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description


NOTE

2 APM30H Cabinet

An ELU is located on the right inner wall of the APM30H, TMC11H, or RFC, or on the left inner wall of the IBBS200D or IBBS200T. The preceding figure shows an APM30H and an IBBS200D as an example.

Figure 2-29 Position of the ELU in an OMB

Figure 2-30 Position of the ELU in a BTS3900AL cabinet

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

39

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Figure 2-31 Position of the ELU in a IBBS700D cabinet

NOTE

In the IBBS700D, when the cabinet is configured with a CCU, the ELU is above the CCU. When the cabinet is not configured with a CCU, the ELU is on the right of the CMUEA.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

40

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Figure 2-32 Position of the ELU in a IBBS700T cabinet

NOTE

In the IBBS700T, when the cabinet is configured with a CCU, the ELU is above the CCU. When the cabinet is not configured with a CCU, the ELU is on the left of the CMUF.

2.6.5 Door Status Sensor


A door status sensor reports the status (open or closed) of a door. It is installed in any of the following cabinets: BTS3900AL, OMB, OMB (Ver.C), APM30H, RFC, TMC11H, IBBS200D, IBBS200T, IBBS700D, and IBBS700T.

Exterior
A door status sensor consists of a magnet and a switch. The following figures show the exteriors of them.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

41

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Figure 2-33 Exterior of the magnet of a door status sensor

(1) Magnetic shell

(2) Magnet

The following figure shows the exterior of the switch of a door status sensor. Figure 2-34 Exterior of the switch of a door status sensor

Installation Position
Positions of door status sensors vary in different cabinets. The following figure shows their positions.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

42

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description


NOTE

2 APM30H Cabinet

l A door status sensor is installed at the same position in the BTS3900AL (Ver.A), IBBS700D, and IBBS700T. Figure 2-35 uses the BTS3900AL (Ver.A) as an example. l A door status sensor is installed at the same position in the OMB and OMB (Ver.C). Figure 2-36 uses the OMB (Ver.C) as an example. l A door status sensor is installed at the same position in the following cabinets: APM30H (Ver.B), APM30H (Ver.C), APM30H (Ver.D), RFC (Ver.B), RFC (Ver.C), RFC (Ver.D), TMC11H (Ver.B), TMC11H (Ver.C), TMC11H (Ver.D), IBBS200D (Ver.B), IBBS200D (Ver.C), IBBS200D (Ver.D), IBBS200T (Ver.B), IBBS200T (Ver.C), and IBBS200T (Ver.D). Figure 2-37 uses the APM30H (Ver.D) as an example.

Figure 2-35 Position of a door status sensor in the BTS3900AL (Ver.A)

Figure 2-36 Position of a door status sensor in the OMB (Ver.C)

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

43

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Figure 2-37 Position of a door status sensor in the APM30H (Ver.D)

2.6.6 Filler Module


A filler module is a standard plastic component, which prevents heat reflux in the empty space below the BBU and improves the heat dissipation in the cabinet. Filler modules are installed in the customer space of an APM30H or TMC11H.

Exterior
A filler module is 1 U high. The following figure shows the exterior of a filler module. Figure 2-38 Exterior of a filler module

Function
A filler module is installed in the customer space below the BBU to prevent heat reflux in the empty space below the BBU.
NOTE

In an APM30H or TMC11H, the filler module is configured in the customer space by default. Before installing other modules, first remove the filler module. For details about removing a filler module, see chapter "Installing Optional Modules and Cables" in the "Installation Guide".

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

44

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

2.6.7 AC Heater
An AC heater is optionally installed in the customer space in an APM30H or TMC11H. It ensures that the customer equipment in a cabinet works within the acceptable temperature range.

Exterior
The following figure shows the exterior of an AC heater. Figure 2-39 Exterior of an AC heater

Technical Specifications
The following table lists the technical specifications of an AC heater. Table 2-24 Technical specifications of an AC heater Counter Temperature range in the cabinet when the AC heater starts working Temperature range in the cabinet when the AC heater stops working Rated heating power Specification < 1oC (6oC) > 15oC (3oC) 330 W

2.6.8 SOU
A service outlet unit (SOU) transfers AC power to the customer equipment. An SOU is optionally installed in the customer space in an APM30H or TMC11H.

Exterior
An SOU is 1 U high. The following figure shows the exterior of an SOU.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

45

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Figure 2-40 Exterior of an SOU

(1) Input power port

(2) Breaker

(3) Socket (European standard)

An SOU applies to the four types of sockets meeting the following standards: North American standard, European standard, Universal standard, and British standard. The following figure shows the exteriors of the four types of sockets. Figure 2-41 Exteriors of different types of sockets

Technical Specifications
The following table lists the technical specifications of an SOU. Table 2-25 Technical specifications of an SOU Counter Dimensions (H x W x D) Weight Input voltage range Maximum input current Output voltage range Maximum output current Frequency band
Issue 03 (2013-01-15)

Specification 482.6 mm x 91 mm x 55 mm (7.87 in. x 23.62 in. x 17.09 in.) 1.5 kg (3.31 lb) 200 V AC to 240 V AC 10 A 200 V AC to 240 V AC 10 A 50 Hz or 60 Hz
46

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Counter Operating temperature Altitude

Specification -40oC to +55oC 4,000m


NOTE Above the altitude of 3000 m (9842.52 ft), the maximum operating temperature drops by 1oC (33.8oF) as the altitude increases by 100 m (328.08 ft).

Protection class

IP20

2.7 APM30H Cables


The APM30H cables consist of the power cables, equipotential cables, PGND cables, and signal cables.

2.7.1 Cable List


APM30H cables mainly consist of the PGND cables, equipotential cables, power cables, and signal cables.

Power Cables, PGND Cables, and Equipotential Cables


The following table lists the power cables, PGND cables, and equipotential cables. Table 2-26 Power cables, PGND cables, and equipotential cables Classif ication Cable One End Connector BTS3900A DBS3900 OT terminal Installation Position L and N terminals on the AC INPUT terminal block on the EPU Ground bar in the APM30H Ground bar in the APM30H The Other End Connector Depending on external power equipment Installation Position External power equipment

Cables to be installe d onsite

2.7.3 PGND Cable 2.7.4 Equipotential Cable

OT terminal

OT terminal

Ground busbar outside the cabinet Ground bar in the lower cabinet

OT terminal

OT terminal

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

47

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Classif ication

Cable

One End Connector Installation Position RFC1 output port on the EPU in the APM30H

The Other End Connector OT terminal Installation Position RTN(+) and NEG(-) terminals on the INPUT terminal block on the DCDU-12B PWR port on the fan assembly in the APM30H Input power port on the AC heater

DCDU-12B Power Cable

OT terminal

Cables installe d before deliver y

FAN 02D Power Cable

EPC4 or EPC6 connector OT terminal

LOAD5 port on the EPU in the APM30H L0 and N0 terminals on the AC junction box in the APM30H and the cabinet ground bar M4 ground screw, L2 terminal, and N2 terminal on the AC OUTPUT terminal block on the EPU M4 ground screw, L1 terminal, and N1 terminal on the AC OUTPUT terminal block on the EPU

3V3 connector

Power Cable for an AC Heater (in the APM30H)

C13 connector

SOU Power Cable

OT terminal

C13 connector

INPUT port on the SOU

Power Cable for an AC Junction Box (in the APM30H)

OT terminal

OT terminal

L and N terminals on the AC junction box in the APM30H and the cabinet ground bar

NOTE

The connection of power cables for optional components depends on the delivery mode. Table 2-26 describes the power cables in a macro base station.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

48

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Signal Cables
The following table describes the signal cables. Table 2-27 Signal cables Classi ficati on Cables to be install ed onsite Cables install ed before deliver y Cable One End Connecto r Installation Position The Other End Connect or Installation Position -

PMU 11ACMUEA Monitoring Signal Cable ELU Signal Cable Monitoring Signal Cable for the Door Status Sensor Monitoring Signal Transfer Cable for the Fan in the Front Door

RJ45 connector

COM_IN port on the PMU

RJ45 connector

COM_OUT port on the CMUEA on the fan assembly in the APM30H ELU port on the CMUEA Door status sensor

RJ45 connector 2-pin connector

ELU GATE port on the PMU

RJ45 connector Bare wire

Interconne ction terminal

Transfer terminal on the front door of the APM30H

4-pin connector

FAN_EXT port on the CMUEA

2.7.2 Cable Connections


This section describes the principles for connecting power cables and signal cables in the APM30H.

Power Cable Connections


This section describes the power cable connections in the APM30H.

Cable Connections in a Distributed Base Station


The following figure shows the APM30H power cable connections in a distributed base station.
Issue 03 (2013-01-15) Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd. 49

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Figure 2-42 Power cable connections in a distributed base station

(1) Power Cable for an AC Junction Box (4) DCDU-12B Power Cable

(2) FAN 02D Power Cable (3) Storage Battery Power Cable (5) SOU Power Cable (6) Power Cable for an AC Heater

Cable Connections in a Separated Macro Base Station


The following figure shows the APM30H power cable connections in a separated macro base station.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

50

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Figure 2-43 Power cable connections in a separated macro base station

(1) Power Cable for an AC Junction (2) FAN 02D Power Cable Box

(3) Storage Battery Power Cable

(4) Power Cable for the DC Junction (5) Power Cable for the DC Junction (6) SOU Power Cable Box in an RFC Box in an RFC (7) Power Cable for an AC Heater -

Monitoring Signal Cable Connections


This section provides reference for onsite installation of monitoring signal cables. The following figure shows the monitoring signal cable connections in the APM30H.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

51

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Figure 2-44 Monitoring signal cable connections in the APM30H

(1) Monitoring signal cable for the fans on the front door (3) PMU-CMUEA monitoring signal cable (5) ELU signal cable

(2) Monitoring signal transfer cable for the fans on the front door (4) Monitoring signal cable for the door status sensor in the APM30H -

2.7.3 PGND Cable


PGND cables ensure that cabinets and internal components are properly grounded and that base stations run properly. PGND cables include classified into PGND cables for cabinets and PGND cables for components.

Exterior
The following figure shows the exterior of a PGND cable.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

52

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Figure 2-45 Exterior of a PGND cable

(1) One-hole OT terminal

(2) Two-hole OT terminal

NOTE

In most cases, the PGND cable is a yellow and green colored cable. When 110 V dual-live-wire power is supplied for BTS3900A (Ver.C) and BTS3900A (Ver.D) cabinets, the PGND cables are green.

Description
The cross-sectional areas and maximum lengths of PGND cables vary according to the types of cabinets. Table 2-28 and Table 2-29 describe PGND cables. Table 2-28 PGND cables for cabinets Base Station Type BTS3900 (Ver.B) and BTS3900L (Ver.B) BTS3900 (Ver.C) and BTS3900L (Ver.C) BTS3900 (Ver.D) and BTS3900L (Ver.D) Cabinet Maximum Length CrossSection al Area 25 mm2 (0.039 in.2) Connect or One-hole OT terminal (M8) Exterior

BTS3900 (Ver.B) 15 m (49.21 and BTS3900L ft) (Ver.B) BTS3900 (Ver.C) and BTS3900L (Ver.C) BTS3900 (Ver.D) and BTS3900L (Ver.D)

The exterior is shown by illustration 1 in the preceding figure.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

53

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Base Station Type BTS3900A (Ver.B)

Cabinet

Maximum Length 8 m (26.25 ft)

CrossSection al Area 16 mm2 (0.025 in.2)

Connect or One-hole OT terminal (M6)

Exterior

RFC (Ver.B)

The exterior is shown by illustration 1 in the preceding figure. The exterior is shown by illustration 1 in the preceding figure. The exterior is shown by illustration 1 in the preceding figure. The exterior is shown by illustration 1 in the preceding figure.

BTS3900A (Ver.C)

RFC (Ver.C)

8 m (26.25 ft)

25 mm2 (0.039 in.2)

One-hole OT terminal (M6)

BTS3900A (Ver.D)

RFC (Ver.D)

8 m (26.25 ft)

16 mm2 (0.025 in.2)

One-hole OT terminal (M6)

BTS3900A (Ver.D)

IBBS700D and IBBS700T

5 m (16.4 ft)

35 mm2 (0.054 in.2)

The cable has a onehole OT terminal (M6) on the cabinet side and a one-hole OT terminal (M8) on the ground bar side.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

54

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Base Station Type BTS3900AL (Ver.A)

Cabinet

Maximum Length 8 m (26.25 ft)

CrossSection al Area 35 mm2 (0.054 in.2)

Connect or Select one of the followin g specificat ions based on the onsite situation: l The cable has a twohole OT termi nal (M6) at each end, and the distan ce betwe en the two holes of each twohole OT termi nal is 15.8 mm (0.62 in.). l The cable has a twohole OT termi

Exterior

BTS3900AL (Ver.A)

The exterior is shown by illustration 2 or 3 in the preceding figure.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

55

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Base Station Type

Cabinet

Maximum Length

CrossSection al Area

Connect or nal (M6) on the cabin et side and a onehole OT termi nal (M6) on the groun d bar side. The distan ce betwe en the two holes of the twohole OT termi nal is 15.8 mm (0.62 in.).

Exterior

IBBS700D and IBBS700T

5 m (16.4 ft)

35 mm2 (0.054 in.2)

The cable has a onehole OT terminal (M6) on the cabinet side and a one-hole OT terminal (M8) on the ground bar side.

The exterior is shown by illustration 1 in the preceding figure.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

56

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Base Station Type BTS3900C (Ver.C)

Cabinet

Maximum Length 15 m (49.21 ft)

CrossSection al Area 16 mm2 (0.025 in.2)

Connect or One-hole OT terminal (M6)

Exterior

OMB (Ver.C)

The exterior is shown by illustration 1 in the preceding figure. The exterior is shown by illustration 1 in the preceding figure. The exterior is shown by illustration 1 in the preceding figure. The exterior is shown by illustration 1 in the preceding figure.

DBS3900

APM30H (Ver.B) series cabinets

8 m (26.25 ft)

16 mm2 (0.025 in.2)

One-hole OT terminal (M6)

APM30H (Ver.C) series cabinets

8 m (26.25 ft)

25 mm2 (0.039 in.2)

One-hole OT terminal (M6)

APM30H (Ver.D) series cabinets

8 m (26.25 ft)

16 mm2 (0.025 in.2)

One-hole OT terminal (M6)

Table 2-29 PGND cables for components Base Station Type BTS3900 (Ver.B) and BTS3900L (Ver.B) BTS3900 (Ver.C) and BTS3900L (Ver.C) BTS3900 (Ver.D) and BTS3900L (Ver.D) Cabinet Maximum Length 15 m (49.21 ft) CrossSection al Area 6 mm2 (0.009 in.2) Connect or One-hole OT terminal (M4) Exterior

BTS3900 (Ver.B) and BTS3900L (Ver.B) BTS3900 (Ver.C) and BTS3900L (Ver.C) BTS3900 (Ver.D) and BTS3900L (Ver.D)

The exterior is shown by illustratio n 1 in the preceding figure.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

57

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Base Station Type BTS3900A (Ver.B)

Cabinet

Maximum Length 15 m (49.21 ft)

CrossSection al Area 6 mm2 (0.009 in.2)

Connect or One-hole OT terminal (M4)

Exterior

APM30H (Ver.B) IBBS200D (Ver.B) IBBS200T (Ver.B)

The exterior is shown by illustratio n 1 in the preceding figure. The exterior is shown by illustratio n 1 in the preceding figure. The exterior is shown by illustratio n 1 in the preceding figure.

BTS3900C (Ver.C)

OMB (Ver.C)

15 m (49.21 ft)

6 mm2 (0.009 in.2)

One-hole OT terminal (M6)

BTS3900AL (Ver.A)

BTS3900AL

15 m (49.21 ft)

6 mm2 (0.009 in.2)

One-hole OT terminal (M6)

2.7.4 Equipotential Cable


An equipotential cable connects the PGND terminals of two cabinets. It ensures equipotential bonding between cabinets and safe operation of base stations.

Exterior
The following figure shows the exterior of an equipotential cable.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

58

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Figure 2-46 Exterior of an equipotential cable

(1) One-hole OT terminal

(2) Two-hole OT terminal

NOTE

In most cases, the equipotential cable is a green and yellow cable. When 110 V dual-live-wire power is supplied for the cabinets used by the BTS3900A (Ver.C) or BTS3900A (Ver.D), the equipotential cable is green.

Description
The following table describes equipotential cables. Table 2-30 Equipotential cables Base Station Type BTS3900 (Ver.B) BTS3900 (Ver.C) BTS3900 (Ver.D) BTS3900A (Ver.B) 16 mm2 (0.025 in.2) Cross-Sectional Area Connect or One-hole OT terminal (M6) at each end Exterior

16 mm2 (0.025 in.2)

The exterior is shown by illustration 1 in the preceding figure.

One-hole OT terminal (M6) at each end

The exterior is shown by illustration 2 in the preceding figure.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

59

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Base Station Type BTS3900A (Ver.C)

Cross-Sectional Area

Connect or One-hole OT terminal (M6) at each end

Exterior

The cross-sectional areas of cables vary according to the way that cabinets are combined. l 16 mm2 (0.025 in.2) for stacked cabinets l 25 mm2 (0.039 in.2) for side-by-side cabinets

The exterior is shown by illustration 1 in the preceding figure.

BTS3900A (Ver.D)

16 mm2 (0.025 in.2)

One-hole OT terminal (M6) at each end

The exterior is shown by illustration 1 in the preceding figure.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

60

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Base Station Type BTS3900AL (Ver.A)

Cross-Sectional Area

Connect or l When a BTS39 00AL AC cabinet is combi ned with a BTS39 00AL DC cabinet or an IBBS7 00D/ IBBS7 00T, each end of the cable has a twohole OT termin al (M6), and the distanc e betwee n the two holes of each twohole termin al is 15.8 mm (0.62 in.). l When a

Exterior

The cross-sectional areas of cables vary according to the way that cabinets are combined. l When a BTS3900AL AC cabinet is combined with a BTS3900AL DC cabinet or an IBBS700D/ IBBS700T, the crosssectional area of the cable is 35 mm2 (0.054 in.2) l When a BTS3900AL AC cabinet is combined with a TMC11H (Ver.C), the cross-sectional area of the cable is 25 mm2 (0.039in. 2).

The exterior is shown by illustration 2 or 3 in the preceding figure.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

61

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Base Station Type

Cross-Sectional Area

Connect or BTS39 00AL AC cabinet is combi ned with a TMC1 1H (Ver.C ), the cable has a twohole OT termin al (M6) on the BTS39 00AL AC cabinet side and a onehole OT termin al (M6) on the TMC1 1H (Ver.C ) side. The distanc e betwee n the two holes of each twohole

Exterior

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

62

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Base Station Type

Cross-Sectional Area

Connect or termin al is 15.8 mm (0.62 in.).

Exterior

2.7.5 Power Cables


This section describes the exteriors, functions, and pin assignments of the power cables in the APM30H.

EPU05A-02 or EPU05A-04 Power Cable


An EPU05A-02 or EPU05A-04 power cable feeds external AC power into the power system of an APM30H (Ver.D). An APM30H can be supplied with 220 V AC single-phase, 220 V AC three-phase, and 110 V or 120 V AC dual-live-wire power.

Exterior
The number of core wires contained in an EPU05A-02 or EPU05A-04 power cable depends on the power system where the EPU05A-02 or EPU05A-04 is used. The following figure shows the exteriors of EPU05A-02 or EPU05A-04 power cables in the 220 V AC single-phase scenario. Figure 2-47 Exteriors of EPU05A-02 or EPU05A-04 power cables in the 220 V AC singlephase scenario

(1) OT terminal

Description
The following table describes EPU05A-02 or EPU05A-04 power cables.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

63

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Table 2-31 EPU05A-02 or EPU05A-04 power cables Cable 220 V AC three-phase power cable Wire L1 L2 L3 N 220 V AC singlephase power cable 110 V AC dual-livewire L N L1 L2 N Color Brown Black Gray Blue Brown Blue Black Red White 25 mm2 (0.039 in.2) 25 mm2 (0.039 in.2) Cross-Sectional Area 6 mm2 (0.009 in.2)

NOTE

The colors and structures of cables vary according to countries and regions. If cables are purchased locally, the cables must comply with local rules and regulations.

Power Cable for the EPU05A-03 or EPU05A-05


The power cable for the EPU05A-03 or EPU05A-05 feeds the external AC power into the power system in the APM30H. The APM30H supports the power supplies of 220 V AC single-phase, 220 V AC three-phase, and 110 V AC or 120 V AC dual-live-wire.

Exterior
The number of core wires contained in the power cable for the EPU05A-03 or EPU05A-05 varies according to the power systems. The following figure shows the exterior of the power cable for the EPU05A-03 or EPU05A-05 used in 220 V AC single-phase scenario. Figure 2-48 Exterior of the power cable for the EPU05A-03 or EPU05A-05 (in 220 V AC singlephase scenario)

(1) OT terminal (M6)

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

64

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Description
The following table lists the power cables for the EPU05A-03 or EPU05A-05. Table 2-32 Power cables for the EPU05A-03 or EPU05A-05 Cable 220 V AC threephase power cable Wire L1 wire L2 wire L3 wire N wire 220 V AC singlephase power cable 110 V AC or 120 V AC dual-live-wire L wire N wire L1 wire L2 wire N wire Color Brown Black Gray Blue Brown Blue Black Red White 25 mm2 (0.039 in.2) 25 mm2 (0.039 in.2) Cross-Sectional Area 6 mm2 (0.009 in.2)

NOTE

The colors and structures of cables delivered by Huawei vary according to countries and areas. If cables are purchased locally, the cables must comply with local rules and regulations.

DCDU-12B Power Cable


A DCDU-12B power cable feeds DC power into a DCDU-12B.

Exterior
The types of DCDU-12B power cables vary according to power supply scenarios. The following figure shows the exteriors of DCDU-12B power cables.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

65

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Figure 2-49 Exteriors of DCDU-12B power cables

(1) OT terminal (M6)

Description
The following table describes DCDU-12B power cables.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

66

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Table 2-33 DCDU-12B power cables Base Station Type BTS3900 (Ver.D) Applicatio n Scenario Power Equipme nt External power equipment Cross-Sectional Area Maxi mum Leng th 10 m (32.8 1 ft) Exterior Functi on

In DC scenarios, a DCDU-12B is installed in a BTS3900 (Ver.D) cabinet.

BTS3900 L (Ver.D)

In DC scenarios, a DCDU-12B is installed in a BTS3900L (Ver.D) cabinet.

External power equipment

l One group of cables with a crosssectional area of 35 mm2 (0.054 in.2) is required when one 160 A upper-level circuit breaker is used. l Two groups of cables with a crosssectional area of 16 mm2 (0.025 in.2) are required when two 80 A upper-level circuit breakers are used.

The exterior is shown by illustratio n 1 in the preceding figure. In most regions, the RTN (+) wire is black and the NEG (-) wire is blue. In UK, the RTN(+) wire is blue and the NEG (-) wire is gray. The exterior is shown by illustratio n 1 in the preceding figure. In most regions, the RTN (+) wire is black and the NEG (-) wire is blue. In UK, the RTN(+) wire is blue and the NEG (-) wire is gray.

When the base station is configu red with RFUs and RRUs, a DCDU -12B power cable feeds DC power into the DCDU -12B, and then the DCDU -12B supplie s the power to the RRUs.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

67

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Base Station Type BTS3900 A (Ver.D)

Applicatio n Scenario

Power Equipme nt l Extern al power equip ment in DC scenari os l EPU05 A-02 or EPU05 A-04 in an APM3 0H in AC scenari os

Cross-Sectional Area

Maxi mum Leng th 1.5 m (4.92 ft)

Exterior

Functi on

A DCDU-12B is installed in an RFC (Ver.D).

l One group of cables with a crosssectional area of 25 mm2 (0.039 in.2) in DC scenarios l One group of cables with a crosssectional area of 35 mm2 (0.054 in.2) or two groups of cables with a crosssectional area of 16 mm2 (0.025 in.2) in AC scenarios

The exterior is shown by illustratio n 2 in the preceding figure. In most regions, the RTN (+) wire is black and the NEG (-) wire is blue. In UK, the RTN(+) wire is blue and the NEG (-) wire is gray.

DBS3900

In DC scenarios, a second DCDU-12B is installed in a TMC11H (Ver.D) configured for the DBS3900.

External power equipment

l One group of cables with a crosssectional area of 35 mm2 (0.054 in.2) is required when one 160 A upper-level circuit breaker is used. l Two groups of cables with a crosssectional area of 16 mm2 (0.025 in.2) are required when two 80 A upper-level circuit breakers are used.

15 m (49.2 1 ft)

The exterior is shown by illustratio n 1 in the preceding figure. In most regions, the RTN (+) wire is black and the NEG (-) wire is blue. In UK, the RTN(+) wire is blue and the NEG (-) wire is gray.

When the base station is configu red with RFUs and RRUs, a DCDU -12B power cable feeds DC power into the DCDU -12B, and then

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

68

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Base Station Type

Applicatio n Scenario

Power Equipme nt EPU05A03 or EPU05A05 in the APM30H

Cross-Sectional Area

Maxi mum Leng th 1.5 m (4.92 ft)

Exterior

Functi on

In AC scenarios where the DBS3900 uses the APM30H (Ver.D) and is configured with 7 to 12 RRUs, the DCDU-12B is installed in the APM30H (Ver.D).

One group of cables with a cross-sectional area of 25 mm2 (0.039 in.2)

The exterior is shown by illustratio n 2 in the preceding figure. In most regions, the RTN (+) wire is black and the NEG (-) wire is blue. In UK, the RTN(+) wire is blue and the NEG (-) wire is gray.

the DCDU -12B supplie s the power to RFUs, RRUs, and transmi ssion equipm ent.

DBS3900 where the BBU is installed on a wall, 19inch rack, or IMB03.

External power equipment One group of cables with a crosssectional area of 25 mm2 (0.039 in. 2)

One group of cables with a cross-sectional area of 16 mm2 (0.023 in.2)

15 m (49.2 1 ft)

The exterior is shown by illustratio n 1 in the preceding figure. In most regions, the RTN (+) wire is black and the NEG (-) wire is blue. In UK, the RTN(+) wire is blue and the NEG (-) wire is gray.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

69

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

SOU Power Cable


The power cable for a service outlet unit (SOU) feeds AC power into the SOU from the AC OUTPUT port on the EPU or EPS.

Exterior
The following figure shows the exterior of an SOU power cable. Figure 2-50 Exterior of an SOU power cable

(1) C13 connector

(2) OT terminal (M4)

Description
The following table describes an SOU power cable. Table 2-34 SOU power cable Wire W1 W2 W3 Color Brown Green and yellow Blue Silkscreen L PE N Cross-Sectional Area 2.5 mm2 (0.004 in.2)

NOTE

The colors and structures of cables delivered by Huawei vary according to countries and regions. If cables are purchased locally, the cables must comply with local rules and regulations.

Power Cable for an AC Heater


The power cable for an AC heater feeds power into an AC junction box from the AC OUTPUT port on an EPU or EPS. Then the AC junction box distributes power to the AC heater. If an AC
Issue 03 (2013-01-15) Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd. 70

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

heater is configured in the -48 V DC input scenario, one more AC power input must be added for the heater. In this case, the maximum length of the power cable for the AC heater is 15 m (49.21 ft).

Exterior
The following figure shows the exterior of a power cable for an AC heater. Figure 2-51 Exterior of a power cable for an AC heater

(1) C13 connector

(2) OT terminal (M4)

Description
The following table describes the power cable for an AC heater. Table 2-35 Power cable for an AC heater Wire W1 W2 W3 Color Brown Green and yellow Blue Silkscreen L PE N Cross-Sectional Area 1.5 mm2 (0.002 in.2)

NOTE

The colors and structures of cables delivered by Huawei vary according to countries and regions. If cables are purchased locally, the cables must comply with local rules and regulations.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

71

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

FAN 02D Power Cable


A FAN 02D power cable feeds -48 V DC power into the FAN 02D in an APM30H or TMC11H (Ver.D).

Exterior
Figure 2-52 and Figure 2-53 show the exterior of a FAN 02D power cable. Figure 2-52 Exterior of a FAN 02D power cable in most regions

(1) 3V3 connector

(2) EPC4 or EPC6 connector

Figure 2-53 Exterior of a FAN 02D power cable in UK

(1) 3V3 connector

(2) EPC4 or EPC6 connector

Description
The following table describes a FAN 02D power cable. Table 2-36 FAN 02D power cable Cable FAN 02D power cable
Issue 03 (2013-01-15)

Wire RTN(+)

Wire Color in Most Regions Black

Wire Color in Other Regions (UK) Blue

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

72

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Cable

Wire NEG(-)

Wire Color in Most Regions Black

Wire Color in Other Regions (UK) Gray

Power Cable for an AC Junction Box


A power cable for the AC junction box feeds AC power from the power devise into the AC junction box. The power is divided into four AC outputs, which are then provided to other components, such as the heater or heating film.

Exterior
The following figure shows the exterior of a power cable for an AC junction box. Figure 2-54 Power cable for an AC junction box

(1) OT terminal

(2) Cord end terminal

NOTE

The colors and structures of cables delivered by Huawei vary according to countries and regions. If cables are purchased locally, the cables must comply with local rules and regulations.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

73

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Description
The following table describes a power cable for an AC junction box. Table 2-37 Power cable for an AC junction box Base Stati on Type BTS3 900A Cabinet Power Equipme nt EPU or EPS subrack EPU or EPS subrack, and transfered by AC junction box in APM30H EPU subrack, and transfered by AC junction box in APM30H PDU05A-0 1 Wire Color CrossSectional Area 1.5 mm2 (0.002 in.2) 1.5 mm2 (0.002 in.2) Exterior

APM30H

L N L N

Brown Blue Brown Blue

TMC11H

The exterior is shown by illustration 1 in the preceding figure.

IBBS700 D/ IBBS700 T

L N

Brown Blue

1.5 mm2 (0.002 in.2)

BTS3 900A L

BTS3900 AL AC

L N

Brown Blue

2.5 mm2 (0.004 in.2)

The exterior is shown by illustration 2 in the preceding figure. The exterior is shown by illustration 3 in the preceding figure.

BTS3900 AL DC

PDU05A-0 1, and transfered by AC junction box in BTS3900A L AC PDU05A-0 1, and transfered by AC junction box in

L N

Brown Blue

2.5 mm2 (0.004 in.2)

IBBS700 D/ IBBS700 T

Brown

2.5 mm2 (0.004 in.2)

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

74

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Base Stati on Type

Cabinet

Power Equipme nt BTS3900A L AC

Wire

Color

CrossSectional Area

Exterior

Blue

2.7.6 Signal Cables


This section describes the exteriors, functions, and pin assignments of the signal cables in the APM30H.

ELU Signal Cable


An electronic label unit (ELU) signal cable transmits the cabinet type to a monitoring board in the cabinet.

Exterior
The following figure shows the exterior of an ELU signal cable. Figure 2-55 Exterior of an ELU signal cable

(1) RJ45 connector

Description
The following table describes an ELU signal cable. Table 2-38 ELU signal cable X1 End X1.1
Issue 03 (2013-01-15)

X2 End X2.1

Color White

Wire Type Twisted pair


75

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

X1 End X1.2 X1.3 X1.6 X1.5 X1.4 X1.7 X1.8

X2 End X2.2 X2.3 X2.6 X2.5 X2.4 X2.7 X2.8

Color Orange White Green White Blue White Brown

Wire Type

Twisted pair

Twisted pair

Twisted pair

Monitoring Signal Cable for the Door Status Sensor


A monitoring signal cable for the door status sensor is used to inform the monitoring board of the door status that is obtained from the door status sensor. Cabinets configured with door status sensors are as follows: APM30H, TMC11H, RFC, IBBS200D, IBBS200T, BTS3900AL, OMB, IBBS700D and IBBS700T.

Exterior
Monitoring signal cables for door status sensors are classified into three types according to the cabinets being monitored. Figure 2-56, Figure 2-57, and Figure 2-58 show their exteriors. Figure 2-56 Exterior of a monitoring signal cable for the door status sensor (1)

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

76

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Figure 2-57 Exterior of a monitoring signal cable for the door status sensor (2)

NOTE

l Cable 1 has a 2-pin straight socket at one end, which is connected to the HPMI. Cable 1 has a bare wire and a cord end terminal at the other end, which are connected to a door status sensor and a cable terminal block, respectively. l Cable 2 has a bare wire at one end, which is connected to a door status sensor. Cable 2 has a cord end terminal at the other end, which is connected to a cable terminal block. l Cable 3 has a cord end terminal at each end. The two cord end terminals are connected to the two ports on one side of the cable terminal block.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

77

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Figure 2-58 Exterior of a monitoring signal cable for the door status sensor (3)

NOTE

l Cable 1 has a 2-pin straight socket at one end, which is connected to the GATE port on the PMU. Cable 1 has a bare wire and a cord end terminal at the other end, which are connected to a door status sensor and a cable terminal block, respectively. l Cable 2 has a bare wire at one end, which is connected to a door status sensor. Cable 2 has a cord end terminal at the other end, which is connected to a cable terminal block. l Cable 3 has a cord end terminal at each end. The two cord end terminals are connected to the two ports on one side of the cable terminal block.

Description
Monitoring signal cables for door status sensors are classified into different types according to the monitoring boards to which the door status is reported. The following table lists the monitoring signal cables for door status sensors.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

78

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Table 2-39 Types of monitoring signal cables for door status sensors Base Station Type BTS3900A (Ver.B) Cabinet Monitoring Board to Which the Door Status Is Reported CMUA Exterior

l RFC (Ver.B) l TMC11H (Ver.B) l IBBS200D (Ver.B) or IBBS200T (Ver.B)

The exterior is shown in Figure 2-56.

BTS3900A (Ver.C)

l RFC (Ver.C) l TMC11H (Ver.C) l IBBS200D (Ver.C) or IBBS200T (Ver.C)

CMUE

BTS3900A (Ver.D)

l RFC (Ver.D) l TMC11H (Ver.D) l IBBS200D (Ver.D) or IBBS200T (Ver.D) l IBBS700D IBBS700T

CMUEA

CMUF CMUA

DBS3900

l TMC11H (Ver.B) l IBBS200D (Ver.B) or IBBS200T (Ver.B) l TMC11H (Ver.C) l IBBS200D (Ver.C) or IBBS200T (Ver.C) l TMC11H (Ver.D) l IBBS200D (Ver.D) or IBBS200T (Ver.D)

CMUE

CMUEA

l BTS3900C l DBS3900 l BTS3900C (Ver.C) l DBS3900 (Ver.C)

OMB

HEUA

OMB (Ver.C)

HEUB

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

79

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Base Station Type BTS3900AL (Ver.A)

Cabinet

Monitoring Board to Which the Door Status Is Reported CCU

Exterior

l BTS3900AL (Ver.A) l IBBS700D l IBBS700T

l BTS3900A (Ver.B) l DBS3900 l BTS3900A (Ver.C) l DBS3900 l BTS3900A (Ver.D) l DBS3900

APM30H (Ver.B)

HPMI

The exterior is shown in Figure 2-57.

APM30H (Ver.C)

HPMI

APM30H (Ver.D)

PMU

The exterior is shown in Figure 2-58.

Monitoring Signal Transfer Cable for the Fan in the Front Door
A monitoring signal transfer cable for the fan in the front door feeds power into the fan in the front door of the APM30H or TMC11H. It also transmits fan monitoring signals to a monitoring board in the cabinet.

Cable Type
The following table lists the types of monitoring boards to which the monitoring signals are reported. Monitoring signal cables vary according to the boards. Table 2-40 Cable type Cable Cabinet Monitoring Board to Which the Monitoring Signals Are Reported CMUA CMUE CMUEA Exterior

Monitoring signal transfer cable for the fan in the front door

APM30H (Ver.B) or TMC11H (Ver.B) APM30H (Ver.C) or TMC11H (Ver.C) APM30H (Ver.D) or TMC11H (Ver.D)

The exterior is shown by illustration 1 in the following figure.

The exterior is shown by illustration 2 in the following figure.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

80

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Exterior
The following figure shows the exteriors of monitoring signal transfer cables for fans in the front doors. Figure 2-59 Exteriors of monitoring signal transfer cables for fans in the front doors

(1) 4-pin connector

(2) Interconnection terminal

Description
The following table describes a monitoring signal transfer cable for the fan in the front door. Table 2-41 Monitoring signal transfer cable for the fan in the front door Wire W1 W2 W3 W4 X1 End X1.1 X1.2 X1.3 X1.4 X2 End X2.1 X2.2 X2.3 X2.4 Color Black Black Black Black

PMU 11A-CMUEA Monitoring Signal Cable


The PMU 11A-CMUEA monitoring signal cable connects the PMU and the CMUEA in the FAN 02D. It transmits the RS485 signals collected by the PMU to the BBU through the CMUEA. This monitoring signal cable is 1.1 m (3.61 ft) long.

Exterior
The following figure shows the exterior of a PMU 11A-CMUEA monitoring signal cable.
Issue 03 (2013-01-15) Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd. 81

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

2 APM30H Cabinet

Figure 2-60 Exterior of a PMU 11A-CMUEA monitoring signal cable

(1) RJ45 connector

Description
The following table describes a PMU 11A-CMUEA monitoring signal cable. Table 2-42 PMU 11A-CMUEA monitoring signal cable X1 End X1.1 X1.2 X1.3 X1.6 X1.4 X1.5 X1.7 X1.8 X2 End X2.1 X2.2 X2.3 X2.6 X2.4 X2.5 X2.7 X2.8 Twisted pair Twisted pair Twisted pair Wire Type Twisted pair

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

82

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

3
About This Chapter

TMC11H Cabinet

This chapter describes the TMC11H cabinet exterior, engineering specifications, application scenarios, as well as boards, modules, and cables in the TMC11H cabinet. 3.1 Cabinet Exterior The transmission cabinet of 11 U high with heat exchanger (TMC11H) is used for Huawei wireless products outdoors. It supplies DC power to the distributed or separated macro base station in outdoor scenarios. 3.2 Cabinet Engineering Specifications This section describes the engineering specifications of the TMC11H, including the electrical specifications, equipment specifications, surge protection specifications, and environment specifications. 3.3 Cabinet Application Scenarios The TMC11H can apply to a distributed base station or a separated macro base station. 3.4 Cabinet Interior This section describes the components and boards in the TMC11H. If a filler module or an AC heater is not configured, 11 U space is provided for customer equipment. 3.5 TMC11H Components This section describes the mandatory and optional components in a TMC11H. 3.6 TMC11H Cables The TMC11H cables consist of the power cables, equipotential cables, PGND cables, and signal cables.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

83

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

3.1 Cabinet Exterior


The transmission cabinet of 11 U high with heat exchanger (TMC11H) is used for Huawei wireless products outdoors. It supplies DC power to the distributed or separated macro base station in outdoor scenarios. The exterior of the TMC11H is the same as that of the APM30H, but their inner modules are different. The following figure shows the exterior of the TMC11H. Figure 3-1 Exterior of the TMC11H

3.2 Cabinet Engineering Specifications


This section describes the engineering specifications of the TMC11H, including the electrical specifications, equipment specifications, surge protection specifications, and environment specifications.

Electrical Specifications
The following table lists the electrical specifications of the TMC11H. Table 3-1 Electrical specifications Parameter Characteristi cs of DC input Input voltage range Typical input voltage Specifications -38.4 V DC to -57 V DC -48 V DC

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

84

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Parameter Maximum input current

Specifications The maximum input current depends on the application scenario. l In a distributed base station: 160 A l In a separated macro base station: 30 A (When the TMC11H is configured together with the APM30H, the APM30H supplies power to the TMC11H.) Input mode -48 V DC power input, supporting the one-hole M6 OT terminal Ten -48 V DC outputs: LOAD0 to LOAD9, used to supply power to the customer equipment -48 V DC Providing overcurrent protection and short-circuit protection for the DC power 1500 W (heat dissipation capability at the ambient temperature of 50oC or 122oF)

Characteristi cs of DC output

DC distribution Typical output voltage

Protection Heat consumption of the cabinet

Equipment Specifications
The following table lists the equipment specifications of the TMC11H. Table 3-2 Equipment specifications Parameter Dimensions (H x W x D) Specifications Cabinet (without the base): 700 mm x 600 mm x 480 mm (27.56 in. x 23.62 in. x 18.90 in.) Base: 200 mm x 600 mm x 434 mm (7.87 in. x 23.62 in. x 17.09 in.) Space for the customer equipment (H x W x D) Cabling and maintenance space at the front 11 U x 19 in. x 380 mm The depth includes 100 mm (3.94 in.) in front of the columns and 280 mm (11.02 in.) between the columns and the rear of the cabinet. Remarks The TMC11H and APM30H have the same exterior and base.

70 mm (2.76 in.)

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

85

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Parameter Cabinet weight

Specifications 47 kg (103.64 lb)

Remarks Total weight of the equipment l Including the cabinet frame, outer air circulation assembly (heat dissipation core and outer air circulation fan), inner air circulation fan assembly, DCDU, and cables l Excluding the customer transmission equipment

Method of installation

It can be installed on the ground, pole, or wall. It can also be installed on an RFC, IBBS200D, or IBBS200T in stack mode.

In stack mode, the TMC11H must be installed on the top of the RFC, IBBS200D, or IBBS200T.

Surge Protection Specifications


The following table lists the surge protection specifications of the TMC11H. Table 3-3 Surge protection specifications Item Surge protection for DC input ports Surge protection for DC output ports Specifications l In differential mode (8/20 us): 3 kA l In common mode (8/20 us): 5 kA l In differential mode (8/20 us): 10 kA l In common mode (8/20 us): 20 kA The DC output corresponds to the secondary load.
NOTE The surge protection capacity of the shield layer in an RRU power cable is 40 kA.

Environment Specifications
The TMC11H can be used outdoors. The following table lists the environment specifications of the TMC11H.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

86

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Table 3-4 Environment specifications Paramete r Operating temperatur e Specifications -40oC to +50oC (-40oF to +122oF) Remarks A heater is required when the temperature is lower than -20oC (-4oF). A sun shield is required when the temperature is higher than 50oC (122oF).
NOTE The temperature at which the heater is required is specified as the local average lowest temperature of each day in the coldest month of the year.

Relative humidity Altitude

5% RH to 100% RH -60 m to +4000 m (-196.85 ft to +13123.2 ft)

From the altitude of 1800 m (5905.44 ft), the maximum operating temperature drops by 1oC (33.8oF) each time the altitude increases by 220 m (721.78 ft). -

Wind speed Storage temperatur e Dustproof and waterproof Noise

67 m/s -40oC to +70oC (-40oF to +158oF) IP55

When the heat consumption of the cabinet is equal to or less than 700 W, the noise is equal to or less than 61 dBA at the temperature of 25oC (77oF) and equal to or less than 67 dBA at the temperature of 45oC (113oF). When the heat consumption of the cabinet is equal to 1500 W or between 700 W and 1500 W, the noise is equal to or less than 66 dBA at the temperature of 25oC (77oF) and equal to or less than 76 dBA at the temperature of 45oC (113oF).

Meeting the ETS 300 753 4.1E standard (rural area)

Meeting the ETS 300 753 4.1E standard (urban area)

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

87

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

3.3 Cabinet Application Scenarios


The TMC11H can apply to a distributed base station or a separated macro base station.

Distributed Base Stations Configured with a TMC11H


The following figure shows the distributed base station configured with a TMC11H. Figure 3-2 Distributed base station configured with a TMC11H

In a distributed base station, a TMC11H is configured as follows: l l l Supplied with -48 V DC power. Combined with RRUs. Configured with a DCDU-12B, which distributes power into RRUs and the BBU, fan assembly, and transmission equipment in the TMC11H.

Separated Macro Base Stations Configured with a TMC11H


The following figure shows the separated macro base station configured with a TMC11H.
Issue 03 (2013-01-15) Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd. 88

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Figure 3-3 Separated macro base station configured with a TMC11H

In a separated macro base station, a TMC11H is configured as follows: l l l Supplied with -48 V DC power. Stacked on the RFC. External -48 V DC power is supplied to the DC junction box on the left wall of the RFC interior, and then distributed to the DCDUs in the RFC and TMC11H.

3.4 Cabinet Interior


This section describes the components and boards in the TMC11H. If a filler module or an AC heater is not configured, 11 U space is provided for customer equipment. The following figure shows the interior of the TMC11H.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

89

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Figure 3-4 Interior of the TMC11H

The following table describes the components in the TMC11H. Table 3-5 Components in the TMC11H N o. Compon ent Op tio nal or Ma nd ato ry Ma xi mu m Qu ant ity in a Sin gle Ca bin et Remarks

Outer air circulatio n assembly Junction box

Ma nda tory Ma nda tory

The assembly is installed on the front door of the cabinet, dissipating heat from the cabinet. The junction box converts one AC input to four AC outputs and is used in the scenario where a service outlet unit (SOU) and multiple heating films or heaters are configured.
90

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

N o.

Compon ent

Op tio nal or Ma nd ato ry

Ma xi mu m Qu ant ity in a Sin gle Ca bin et 1

Remarks

Ma FAN 02D nda tory

The fan assembly is configured with fans and central monitoring unit type EA (CMUEA), dissipating heat from the cabinet. l To provide protection for trunk signals, a signal lightning protection unit (SLPU) is mandatory and installed in the top 1 U space of the cabinet. It is configured with the universal E1/T1 lightning protection unit (UELP) or universal FE lightning protection unit (UFLP). l To provide protection for monitoring signals, an SLPU is optional and installed in the 1 U space below the BBU. It is configured with two universal signal lightning protection unit 2 (USLP2) boards.

SLPU

Ma nda tory

Door status sensor ELU

Ma nda tory Ma nda tory Ma nda tory

The door status sensor monitors the status (open or closed) of the cabinet door. The electronic label unit (ELU) reports the cabinet type automatically to facilitate troubleshooting. The direct current distribution unit-12B (DCDU-12B) or direct current distribution unit-12C (DCDU-12C) in the TMC11H distributes DC power to all the components in the TMC11H. A DCDU-12B or DCDU-12C is 1 U high. The DCDU varies with the installation scenarios. A maximum of two BBU3900s can be configured in a TMC11H.

DCDU-1 2B or DCDU-1 2C

8 Opt ion al

BBU390 0

l The BBU3900 provides physical ports for communication between the BBU3900 and the BSC or RNC, and enables interaction between the base station and the BSC or RNC. l The BBU3900 provides CPRI ports for communication between the BBU and RF modules. l The BBU3900 processes uplink and downlink data.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

91

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

N o.

Compon ent

Op tio nal or Ma nd ato ry

Ma xi mu m Qu ant ity in a Sin gle Ca bin et 1

Remarks

9 EMUA 10

Opt ion al Opt ion al Opt ion al

The environment monitoring unit type A (EMUA) monitors environment of the equipment. A filler module is a plastic component with a height of 1 U in the cabinet, preventing the heat reflux in the empty space below the BBU. The AC heater ensures that components in the cabinet work within the acceptable temperature range when the surrounding temperature is low. It can be preferentially installed in the 1 U space at the bottom of the cabinet.

Filler module

11 AC heater

3.5 TMC11H Components


This section describes the mandatory and optional components in a TMC11H.

3.5.1 DCDU-12B
A direct current distribution unit-12B (DCDU-12B) is 1 U high and provides -48 V DC power for other components.

Exterior
The following figure shows the front and rear of the DCDU-12B.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

92

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Figure 3-5 Front and rear of the DCDU-12B

(1) Equipotential ground points

(2) Ground points

NOTE

A DCDU-12B uses the equipotential connection point and ground point in the following scenarios: l Scenario 1: The DCDU-12B is installed on an open rack. In this scenario, an equipotential cable connects the equipotential ground point near the mounting ear on the DCDU-12B to the ground bar on the open rack. l Scenario 2: The DCDU-12B is installed on a wall as a standalone power distribution device. In this scenario, the ground point at the rear of the DCDU-12B is connected to the ground bar in the equipment room.

Function
The DCDU-12B provides ten -48 V DC outputs using the same fuse configurations to meet the power distribution requirements of indoor and outdoor macro base stations, micro base stations, and distributed base stations.

Port
The following figure shows the ports on the DCDU-12B panel.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

93

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Figure 3-6 Ports on the DCDU-12B panel

The following table describes the ports on the DCDU-12B panel. Table 3-6 Ports on the DCDU-12B panel N o. (1) Port DC input terminals Silkscreen NEG(-) RTN(+) Matched Terminal and Cable Two one-hole OT terminals (M6). If one group of power cables are used, the maximum crosssectional area of each power cable is 35 mm2 (0.054 in.2). If two groups of power cables are used, the maximum crosssectional area of each power cable is 25 mm2 (0.039 in.2). Description It is a negative power input wiring terminal. It is a positive power input wiring terminal.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

94

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

N o. (2)

Port Fuse blocks

Silkscreen LOAD0 to LOAD9

Matched Terminal and Cable -

Description The fuse blocks control the LOAD0 to LOAD9 ports, and therefore control the power supplies to the BBU, fan assemblies, and transmission equipment. The indicator on the fuse block indicates the status of the fuse. l When the indicator is steady on, the fuse is faulty and needs to be replaced. l When the indicator is steady off, the fuse is working properly.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

95

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

N o. (3)

Port DC output ports

Silkscreen LOAD0 to LOAD9

Matched Terminal and Cable

Description

l Figure 3-7 shows For the specifications of the DC output, see Table 3-7. an EPC5 connector, which applies to any of the LOAD0 to LOAD5 ports. The maximum cross-sectional area of the cable supported is 6 mm2 (0.009 in.2) to 10 mm2 (0.016 in.2). l Figure 3-8 shows an EPC4 or EPC6 connector, which applies to any of the LOAD6 to LOAD9 ports. The maximum cross-sectional area of the cable supported is 3.3 mm2 (0.005 in.2) to 4 mm2 (0.006 in.2).
NOTE Figure 3-8 shows an EPC4 or EPC6 connector. An EPC4 connector must be connected to a cable onsite, whereas an EPC6 connector has been connected to a cable before delivery. An EPC5 connector must also be connected to a cable onsite.

NOTE

A fuse block and a DC output port are jointly called a fuse terminal block.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

96

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Figure 3-7 Exterior of an EPC5 connector

Figure 3-8 Exterior of an EPC4 or EPC6 connector

The following table describes the power distribution of the DC output ports on a DCDU-12B. Table 3-7 Power distribution of the DC output ports on a DCDU-12B Base Station Type Application Scenario l DBS3900 configured with a power cabinet TMC11H (Ver.D) l DBS3900 where the BBU is installed on a wall, 19-inch rack, or IMB03 DC Output Port LOAD0 to LOAD5 LOAD6 and LOAD7 LOAD8 LOAD9 BTS3900AL (Ver.A) BTS3900AL (Ver.A) configured with RFUs and RRUs LOAD0 to LOAD5 LOAD6 to LOAD9 LOAD0 to LOAD8 PowerConsumin g Device RRU Transmissio n equipment or BBU Transmissio n equipment FAN 02D RRU 0 to RRU 5 Reserved RRU 0 to RRU 9 10x30 A 10x30 A Fuse Specif ication 10x30 A

DBS3900

l BTS3900A (Ver.D) l BTS3900 (Ver.D) l BTS3900L (Ver.D)

l BTS3900A (Ver.D) configured with an RFC (Ver.D) cabinet and

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

97

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Base Station Type

Application Scenario configured with RFUs and RRUs l BTS3900 (Ver.D) configured with RFUs and RRUs l BTS3900L (Ver.D) configured with RFUs and RRUs

DC Output Port LOAD9

PowerConsumin g Device Reserved

Fuse Specif ication

Technical Specifications
The following table lists the technical specifications of a DCDU-12B. Table 3-8 Technical specifications of a DCDU-12B Parameter Dimensions (H x W x D) Specifications A DCDU-12B is 1 U high and can be installed in a 19-inch cabinet or rack. Its dimensions are as follows: l 42 mm x 442 mm x 65 mm (1.65 in. x 17.4 in. x 2.56 in.) (without mounting ears) l 42 mm x 482.6 mm x 65 mm (1.65 in. x 19 in. x 2.56 in.) (with mounting ears) Surge protection specifications -48 V DC power port, 10 kA (8/20 s) differential mode -48 V DC power port, 20 kA (8/20 s) common mode

3.5.2 DCDU-12C
A direct current distribution unit-12C (DCDU-12C) is 1 U high and provides -48 V DC power for other components.

Exterior
The following figure shows the front and rear of the DCDU-12C.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

98

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Figure 3-9 Front and rear of the DCDU-12C

(1) Equipotential ground points

(2) Ground points

NOTE

The DCDU-12C has no equipotential connection point and ground point.

Function
The DCDU-12C provides ten -48 V DC outputs using same fuse configurations to meet the power distribution requirements of distributed and outdoor macro base stations.

Port
The following table describes the ports and terminals on a DCDU-12C panel. Figure 3-10 Ports on the DCDU-12C panel

The following table describes the ports on the DCDU-12C panel.


Issue 03 (2013-01-15) Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd. 99

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Table 3-9 Ports on the DCDU-12C panel N o. (1) Port DC input terminals Silkscreen NEG(-) RTN(+) Matched Terminal and Cable Two one-hole OT terminals (M6). The cross-sectional area of the cable is 16 mm2 (0.025 in.2) by default. Description It is a negative power input wiring terminal. It is a positive power input wiring terminal.

(2)

Fuse blocks

LOAD0 to LOAD9

The fuse blocks control the LOAD0 to LOAD9 ports, and therefore control the power supplies to the BBU, fan assemblies, and transmission equipment. The indicator on the fuse block indicates the status of the fuse. l When the indicator is steady on, the fuse is faulty and needs to be replaced. l When the indicator is steady off, the fuse is working properly.

(3)

DC output ports

LOAD0 to LOAD9

Figure 3-11 shows For the specifications of the DC an EPC4 or EPC6 output, see Table 3-10. connector, which applies to any of the LOAD0 to LOAD9 ports. The maximum cross-sectional area of the cable supported is 3.3 mm2 (0.005 in.2) to 4 mm2 (0.006 in.2).

NOTE

A fuse block and a DC output port are jointly called a fuse terminal block.

Figure 3-11 Exterior of an EPC4 or EPC6 connector

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

100

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

The following table describes the power distribution of the DC output ports on a DCDU-12C. Table 3-10 Power distribution of the DC output ports on a DCDU-12C Base Station Type l BTS3900 A (Ver.D) l DBS3900 Application Scenario DC Output Port LOAD0 to LOAD5 and LOAD8 LOAD6 and LOAD7 LOAD9 PowerConsuming Device Transmission equipment Transmission equipment or BBU FAN 02D Fuse Specif ication 10x30 A

l BTS3900A (Ver.D) configured with a power cabinet TMC11H (Ver.D) l BTS3900A (Ver.D) configured with a transmission cabinet TMC11H (Ver.D) l DBS3900 configured with an APM30H (Ver.D) and a transmission cabinet TMC11H (Ver.D) Equipment compartment of the BTS3900AL (Ver.A) cabinet

BTS3900AL (Ver.A)

LOAD0 LOAD1 LOAD2 and LOAD3 LOAD4 LOAD5 to LOAD8 LOAD9

CCU Reserved Transmission equipment Battery cabinet BBU Heat exchanger RFUs FAU

10x30 A

RF compartment of the BTS3900AL (Ver.A) cabinet

LOAD0 to LOAD8 LOAD9

10x30 A

Technical Specifications
The following table lists the technical specifications of a DCDU-12C.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

101

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Table 3-11 Technical specifications of a DCDU-12C Parameter Dimensions (H x W x D) Specifications The DCDU-12C is 1 U (44.45 mm or 1.75 in.) high and can be installed in a 19-inch cabinet or rack. Its dimensions are as follows: l 42 mm x 442 mm x 65 mm (1.65 in. x 17.4 in. x 2.56 in.) (without mounting ears) l 42 mm x 482.6 mm x 65 mm (1.65 in. x 19 in. x 2.56 in.) (with mounting ears) Surge protection specifications -48 V DC power port, 10 kA (8/20 s) differential mode -48 V DC power port, 20 kA (8/20 s) common mode

3.5.3 FAN 02D


A FAN 02C dissipates heat and detects temperature for an APM30H (Ver.D) or TMC11H (Ver.D).

Exterior
A FAN 02D consists of the fan subrack, fans, and CMUEA. The following figure shows the exterior of a FAN 02D. Figure 3-12 Exterior of a FAN 02D

(1) Fan subrack

(2) Fans

(3) CMUEA

For details about the ports and indicators on the CMUEA, see CMUEA.

3.5.4 Filler Module


A filler module is a standard plastic component, which prevents heat reflux in the empty space below the BBU and improves the heat dissipation in the cabinet. Filler modules are installed in the customer space of an APM30H or TMC11H.
Issue 03 (2013-01-15) Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd. 102

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Exterior
A filler module is 1 U high. The following figure shows the exterior of a filler module. Figure 3-13 Exterior of a filler module

Function
A filler module is installed in the customer space below the BBU to prevent heat reflux in the empty space below the BBU.
NOTE

In an APM30H or TMC11H, the filler module is configured in the customer space by default. Before installing other modules, first remove the filler module. For details about removing a filler module, see chapter "Installing Optional Modules and Cables" in the "Installation Guide".

3.5.5 Junction Box


The junction box is configured in the BTS3900AL, APM30H, TMC11H, IBBS700D, or IBBS700T cabinet. When a heater or a heating film is configured, the junction box feeds power to the heater or the heating film.

Exterior
A junction box is installed on the left inner side of the APM30H, TMC11H, IBBS700D, or IBBS700T. In the BTS3900AL, the junction box is installed on the right inner side of the cabinet. The following figure shows the position and exterior of the junction box in the APM30H.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

103

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Figure 3-14 Exterior of the junction box

Functions
The junction box used in the BTS3900AL, APM30H, TMC11H, IBBS700D and IBBS700T performs the following functions: l l The PDU05A-01 feeds power to the junction box in the BTS3900AL. The power is divided into four AC power outputs, which are then provided for the heater in the cabinet. The EPU subrack feeds power into the junction box in the APM30H. The power is divided into four AC power outputs, which are then provided for the heater in the cabinet or heating film in the IBBS200D. The junction box in the APM30H feeds power into the junction box in the TMC11H. The power is divided into four AC power outputs, which are then provided for the heater or service outlet unit (SOU) in the cabinet. The junction box in the primary cabinet (BTS3900A, BTS3900AL, or TP48600A-H17B1) feeds power into the junction box in the IBBS700D or IBBS700T. The power is divided into four AC power outputs, which are then provided for the heater in the cabinet.

Interior
The following figure shows the interior of an AC junction box.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

104

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Figure 3-15 Interior of an AC junction box

(1) Four AC output L wiring terminals (4) Cable holes

(2) Four AC output N wiring terminals (5) AC input N wiring terminal

(3) Four AC output PE wiring terminals (6) AC input L wiring terminal

3.5.6 ELU
An electronic label unit (ELU) reports the cabinet type automatically to facilitate troubleshooting.

Exterior
The following figure shows the exterior of an ELU.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

105

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Figure 3-16 Exterior of an ELU

(1) Shell

(2) RJ45 port

NOTE

The ELU in a BTS3900 or BTS3900L has no shell.

The board collecting information from the ELU varies according to the cabinet, as listed in the following table. Table 3-12 Monitoring boards to which an ELU reports information Base Station Type BTS3900 (Ver.B) and BTS3900L (Ver.B) BTS3900 (Ver.C) and BTS3900L (Ver.C) BTS3900 (Ver.D) and BTS3900L (Ver.D) BTS3900A (Ver.B) BTS3900A (Ver.C) Cabinet Board Collecting Information from the ELU FMUC

BTS3900 (Ver.B) and BTS3900L (Ver.B)

BTS3900 (Ver.C) and BTS3900L (Ver.C)

FMUE

BTS3900 (Ver.D) and BTS3900L (Ver.D)

FMUEA

APM30H (Ver.B), TMC11H (Ver.B), RFC (Ver.B), IBBS200D (Ver.B), and IBBS200T (Ver.B) APM30H (Ver.C), TMC11H (Ver.C), RFC (Ver.C), IBBS200D (Ver.C), and IBBS200T (Ver.C)

CMUA

CMUE

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

106

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Base Station Type BTS3900A (Ver.D)

Cabinet

Board Collecting Information from the ELU CMUEA

APM30H (Ver.D), TMC11H(Ver.D), RFC (Ver.D), IBBS200D(Ver.D), IBBS200T (Ver.D), and IBBS700D IBBS700T

CMUF HEUB CCU

BTS3900C (Ver.C) BTS3900AL (Ver.A)

OMB (Ver.C) BTS3900AL (Ver.A), IBBS700D, IBBS700T

Installation Position
Positions of ELUs vary in different cabinets. The following figure shows their positions. Figure 3-17 Position of the ELU in a BTS3900 cabinet

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

107

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Figure 3-18 Position of the ELU in a BTS3900L cabinet

Figure 3-19 Position of the ELU in an APM30H or IBBS200D cabinet

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

108

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description


NOTE

3 TMC11H Cabinet

An ELU is located on the right inner wall of the APM30H, TMC11H, or RFC, or on the left inner wall of the IBBS200D or IBBS200T. The preceding figure shows an APM30H and an IBBS200D as an example.

Figure 3-20 Position of the ELU in an OMB

Figure 3-21 Position of the ELU in a BTS3900AL cabinet

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

109

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Figure 3-22 Position of the ELU in a IBBS700D cabinet

NOTE

In the IBBS700D, when the cabinet is configured with a CCU, the ELU is above the CCU. When the cabinet is not configured with a CCU, the ELU is on the right of the CMUEA.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

110

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Figure 3-23 Position of the ELU in a IBBS700T cabinet

NOTE

In the IBBS700T, when the cabinet is configured with a CCU, the ELU is above the CCU. When the cabinet is not configured with a CCU, the ELU is on the left of the CMUF.

3.5.7 Door Status Sensor


A door status sensor reports the status (open or closed) of a door. It is installed in any of the following cabinets: BTS3900AL, OMB, OMB (Ver.C), APM30H, RFC, TMC11H, IBBS200D, IBBS200T, IBBS700D, and IBBS700T.

Exterior
A door status sensor consists of a magnet and a switch. The following figures show the exteriors of them.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

111

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Figure 3-24 Exterior of the magnet of a door status sensor

(1) Magnetic shell

(2) Magnet

The following figure shows the exterior of the switch of a door status sensor. Figure 3-25 Exterior of the switch of a door status sensor

Installation Position
Positions of door status sensors vary in different cabinets. The following figure shows their positions.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

112

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description


NOTE

3 TMC11H Cabinet

l A door status sensor is installed at the same position in the BTS3900AL (Ver.A), IBBS700D, and IBBS700T. Figure 3-26 uses the BTS3900AL (Ver.A) as an example. l A door status sensor is installed at the same position in the OMB and OMB (Ver.C). Figure 3-27 uses the OMB (Ver.C) as an example. l A door status sensor is installed at the same position in the following cabinets: APM30H (Ver.B), APM30H (Ver.C), APM30H (Ver.D), RFC (Ver.B), RFC (Ver.C), RFC (Ver.D), TMC11H (Ver.B), TMC11H (Ver.C), TMC11H (Ver.D), IBBS200D (Ver.B), IBBS200D (Ver.C), IBBS200D (Ver.D), IBBS200T (Ver.B), IBBS200T (Ver.C), and IBBS200T (Ver.D). Figure 3-28 uses the APM30H (Ver.D) as an example.

Figure 3-26 Position of a door status sensor in the BTS3900AL (Ver.A)

Figure 3-27 Position of a door status sensor in the OMB (Ver.C)

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

113

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Figure 3-28 Position of a door status sensor in the APM30H (Ver.D)

3.5.8 AC Heater
An AC heater is optionally installed in the customer space in an APM30H or TMC11H. It ensures that the customer equipment in a cabinet works within the acceptable temperature range.

Exterior
The following figure shows the exterior of an AC heater. Figure 3-29 Exterior of an AC heater

Technical Specifications
The following table lists the technical specifications of an AC heater. Table 3-13 Technical specifications of an AC heater Counter Temperature range in the cabinet when the AC heater starts working
Issue 03 (2013-01-15)

Specification < 1oC (6oC)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

114

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Counter Temperature range in the cabinet when the AC heater stops working Rated heating power

Specification > 15oC (3oC) 330 W

3.5.9 SOU
A service outlet unit (SOU) transfers AC power to the customer equipment. An SOU is optionally installed in the customer space in an APM30H or TMC11H.

Exterior
An SOU is 1 U high. The following figure shows the exterior of an SOU. Figure 3-30 Exterior of an SOU

(1) Input power port

(2) Breaker

(3) Socket (European standard)

An SOU applies to the four types of sockets meeting the following standards: North American standard, European standard, Universal standard, and British standard. The following figure shows the exteriors of the four types of sockets. Figure 3-31 Exteriors of different types of sockets

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

115

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Technical Specifications
The following table lists the technical specifications of an SOU. Table 3-14 Technical specifications of an SOU Counter Dimensions (H x W x D) Weight Input voltage range Maximum input current Output voltage range Maximum output current Frequency band Operating temperature Altitude Specification 482.6 mm x 91 mm x 55 mm (7.87 in. x 23.62 in. x 17.09 in.) 1.5 kg (3.31 lb) 200 V AC to 240 V AC 10 A 200 V AC to 240 V AC 10 A 50 Hz or 60 Hz -40oC to +55oC 4,000m
NOTE Above the altitude of 3000 m (9842.52 ft), the maximum operating temperature drops by 1oC (33.8oF) as the altitude increases by 100 m (328.08 ft).

Protection class

IP20

3.6 TMC11H Cables


The TMC11H cables consist of the power cables, equipotential cables, PGND cables, and signal cables.

3.6.1 Cable List


TMC11H cables mainly consist of the equipotential cables, power cables, and signal cables.

Equipotential Cables and Power Cables


The following table describes the equipotential cables and power cables.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

116

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Table 3-15 Equipotential cables and power cables Classi ficati on Cables to be install ed onsite Cable One End Connector DCDU-12C Power Cable (AC scenario) EPC4 or EPC6 connector Installation Position LOAD7 port on the EPU The Other End Connector OT terminal Installation Position RTN(+) and NEG(-) terminals on the INPUT terminal block on the DCDU-12C L and N terminals on the AC junction box in the TMC11H External power equipment Ground bar in the lower cabinet External power equipment

Power Cable for an AC Junction Box (in the TMC11H) Power Cable for an AC Heater (-48 V DC scenario) 2.7.4 Equipotential Cable DCDU-12B Power Cable

OT terminal

L3 and N3 terminals on the AC junction box in the APM30H Input power port on the AC heater Ground bar in the upper cabinet RTN(+) and NEG(-) terminals on the INPUT terminal block on the DCDU-12B LOAD9 port on the DCDU-12C L0 and N0 terminals on the AC junction box in the TMC11H and the cabinet ground bar

OT terminal

C13 connector

Depending on external power equipment OT terminal

OT terminal

OT terminal

Depending on external power equipment

Cables install ed before deliver y

FAN 02D Power Cable

EPC4 or EPC6 connector OT terminal

3V3 connector

PWR port on the fan assembly in the TMC11H Input power port on the AC heater

Power Cable for an AC Heater

C13 connector

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

117

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Classi ficati on

Cable

One End Connector Installation Position DC junction box in the RFC

The Other End Connector OT terminal Installation Position RTN(+) and NEG(-) terminals on the INPUT terminal block on the DCDU-12B

DCDU-12B Power Cable (-48 V DC scenario)

OT terminal

NOTE

The connection of power cables for optional components depends on the delivery mode. Table 3-15 describes the power cables in a macro base station.

Signal Cables
The following table describes the signal cables. Table 3-16 Signal cables Classi ficati on Cables to be install ed onsite Cables install ed before deliver y Cable One End Connecto r Installation Position The Other End Connect or Installation Position -

ELU Signal Cable Monitoring Signal Cable for the Door Status Sensor Monitoring Signal Transfer Cable for the Fan in the Front Door

RJ45 connector Bare wire

ELU GATE port on the CMUEA

RJ45 connector Bare wire

ELU port on the CMUEA Door status sensor

Interconne ction terminal

Interconnection terminal on the front door of the TMC11H

4-pin connector

FAN_EXT port on the CMUEA

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

118

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

3.6.2 Cable Connections


This section describes the principles for connecting power cables and signal cables in the TMC11H.

Power Cable Connections


This section describes the power cable connections in the TMC11H. The following figure shows the power cable connections in the TMC11H. Figure 3-32 Power cable connections in the TMC11H

(1) FAN 02D Power Cable (2) Power Cable for an AC Heater (3) DCDU-12B Power Cable or DCDU-12C Power Cable

Monitoring Signal Cable Connections


This section provides reference for onsite installation of monitoring signal cables. Figure 3-33 shows the monitoring signal cable connections in the TMC11H.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

119

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Figure 3-33 Monitoring signal cable connections in the TMC11H

(1) Monitoring signal cable for the fans on the front door (3) ELU signal cable

(2) Monitoring signal transfer cable for the fans on the front door (4) Monitoring signal cable for the door status sensor

3.6.3 PGND Cable


PGND cables ensure that cabinets and internal components are properly grounded and that base stations run properly. PGND cables include classified into PGND cables for cabinets and PGND cables for components.

Exterior
The following figure shows the exterior of a PGND cable.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

120

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Figure 3-34 Exterior of a PGND cable

(1) One-hole OT terminal

(2) Two-hole OT terminal

NOTE

In most cases, the PGND cable is a yellow and green colored cable. When 110 V dual-live-wire power is supplied for BTS3900A (Ver.C) and BTS3900A (Ver.D) cabinets, the PGND cables are green.

Description
The cross-sectional areas and maximum lengths of PGND cables vary according to the types of cabinets. Table 3-17 and Table 3-18 describe PGND cables. Table 3-17 PGND cables for cabinets Base Station Type BTS3900 (Ver.B) and BTS3900L (Ver.B) BTS3900 (Ver.C) and BTS3900L (Ver.C) BTS3900 (Ver.D) and BTS3900L (Ver.D) Cabinet Maximum Length CrossSection al Area 25 mm2 (0.039 in.2) Connect or One-hole OT terminal (M8) Exterior

BTS3900 (Ver.B) 15 m (49.21 and BTS3900L ft) (Ver.B) BTS3900 (Ver.C) and BTS3900L (Ver.C) BTS3900 (Ver.D) and BTS3900L (Ver.D)

The exterior is shown by illustration 1 in the preceding figure.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

121

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Base Station Type BTS3900A (Ver.B)

Cabinet

Maximum Length 8 m (26.25 ft)

CrossSection al Area 16 mm2 (0.025 in.2)

Connect or One-hole OT terminal (M6)

Exterior

RFC (Ver.B)

The exterior is shown by illustration 1 in the preceding figure. The exterior is shown by illustration 1 in the preceding figure. The exterior is shown by illustration 1 in the preceding figure. The exterior is shown by illustration 1 in the preceding figure.

BTS3900A (Ver.C)

RFC (Ver.C)

8 m (26.25 ft)

25 mm2 (0.039 in.2)

One-hole OT terminal (M6)

BTS3900A (Ver.D)

RFC (Ver.D)

8 m (26.25 ft)

16 mm2 (0.025 in.2)

One-hole OT terminal (M6)

BTS3900A (Ver.D)

IBBS700D and IBBS700T

5 m (16.4 ft)

35 mm2 (0.054 in.2)

The cable has a onehole OT terminal (M6) on the cabinet side and a one-hole OT terminal (M8) on the ground bar side.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

122

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Base Station Type BTS3900AL (Ver.A)

Cabinet

Maximum Length 8 m (26.25 ft)

CrossSection al Area 35 mm2 (0.054 in.2)

Connect or Select one of the followin g specificat ions based on the onsite situation: l The cable has a twohole OT termi nal (M6) at each end, and the distan ce betwe en the two holes of each twohole OT termi nal is 15.8 mm (0.62 in.). l The cable has a twohole OT termi

Exterior

BTS3900AL (Ver.A)

The exterior is shown by illustration 2 or 3 in the preceding figure.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

123

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Base Station Type

Cabinet

Maximum Length

CrossSection al Area

Connect or nal (M6) on the cabin et side and a onehole OT termi nal (M6) on the groun d bar side. The distan ce betwe en the two holes of the twohole OT termi nal is 15.8 mm (0.62 in.).

Exterior

IBBS700D and IBBS700T

5 m (16.4 ft)

35 mm2 (0.054 in.2)

The cable has a onehole OT terminal (M6) on the cabinet side and a one-hole OT terminal (M8) on the ground bar side.

The exterior is shown by illustration 1 in the preceding figure.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

124

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Base Station Type BTS3900C (Ver.C)

Cabinet

Maximum Length 15 m (49.21 ft)

CrossSection al Area 16 mm2 (0.025 in.2)

Connect or One-hole OT terminal (M6)

Exterior

OMB (Ver.C)

The exterior is shown by illustration 1 in the preceding figure. The exterior is shown by illustration 1 in the preceding figure. The exterior is shown by illustration 1 in the preceding figure. The exterior is shown by illustration 1 in the preceding figure.

DBS3900

APM30H (Ver.B) series cabinets

8 m (26.25 ft)

16 mm2 (0.025 in.2)

One-hole OT terminal (M6)

APM30H (Ver.C) series cabinets

8 m (26.25 ft)

25 mm2 (0.039 in.2)

One-hole OT terminal (M6)

APM30H (Ver.D) series cabinets

8 m (26.25 ft)

16 mm2 (0.025 in.2)

One-hole OT terminal (M6)

Table 3-18 PGND cables for components Base Station Type BTS3900 (Ver.B) and BTS3900L (Ver.B) BTS3900 (Ver.C) and BTS3900L (Ver.C) BTS3900 (Ver.D) and BTS3900L (Ver.D) Cabinet Maximum Length 15 m (49.21 ft) CrossSection al Area 6 mm2 (0.009 in.2) Connect or One-hole OT terminal (M4) Exterior

BTS3900 (Ver.B) and BTS3900L (Ver.B) BTS3900 (Ver.C) and BTS3900L (Ver.C) BTS3900 (Ver.D) and BTS3900L (Ver.D)

The exterior is shown by illustratio n 1 in the preceding figure.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

125

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Base Station Type BTS3900A (Ver.B)

Cabinet

Maximum Length 15 m (49.21 ft)

CrossSection al Area 6 mm2 (0.009 in.2)

Connect or One-hole OT terminal (M4)

Exterior

APM30H (Ver.B) IBBS200D (Ver.B) IBBS200T (Ver.B)

The exterior is shown by illustratio n 1 in the preceding figure. The exterior is shown by illustratio n 1 in the preceding figure. The exterior is shown by illustratio n 1 in the preceding figure.

BTS3900C (Ver.C)

OMB (Ver.C)

15 m (49.21 ft)

6 mm2 (0.009 in.2)

One-hole OT terminal (M6)

BTS3900AL (Ver.A)

BTS3900AL

15 m (49.21 ft)

6 mm2 (0.009 in.2)

One-hole OT terminal (M6)

3.6.4 Equipotential Cable


An equipotential cable connects the PGND terminals of two cabinets. It ensures equipotential bonding between cabinets and safe operation of base stations.

Exterior
The following figure shows the exterior of an equipotential cable.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

126

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Figure 3-35 Exterior of an equipotential cable

(1) One-hole OT terminal

(2) Two-hole OT terminal

NOTE

In most cases, the equipotential cable is a green and yellow cable. When 110 V dual-live-wire power is supplied for the cabinets used by the BTS3900A (Ver.C) or BTS3900A (Ver.D), the equipotential cable is green.

Description
The following table describes equipotential cables. Table 3-19 Equipotential cables Base Station Type BTS3900 (Ver.B) BTS3900 (Ver.C) BTS3900 (Ver.D) BTS3900A (Ver.B) 16 mm2 (0.025 in.2) Cross-Sectional Area Connect or One-hole OT terminal (M6) at each end Exterior

16 mm2 (0.025 in.2)

The exterior is shown by illustration 1 in the preceding figure.

One-hole OT terminal (M6) at each end

The exterior is shown by illustration 2 in the preceding figure.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

127

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Base Station Type BTS3900A (Ver.C)

Cross-Sectional Area

Connect or One-hole OT terminal (M6) at each end

Exterior

The cross-sectional areas of cables vary according to the way that cabinets are combined. l 16 mm2 (0.025 in.2) for stacked cabinets l 25 mm2 (0.039 in.2) for side-by-side cabinets

The exterior is shown by illustration 1 in the preceding figure.

BTS3900A (Ver.D)

16 mm2 (0.025 in.2)

One-hole OT terminal (M6) at each end

The exterior is shown by illustration 1 in the preceding figure.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

128

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Base Station Type BTS3900AL (Ver.A)

Cross-Sectional Area

Connect or l When a BTS39 00AL AC cabinet is combi ned with a BTS39 00AL DC cabinet or an IBBS7 00D/ IBBS7 00T, each end of the cable has a twohole OT termin al (M6), and the distanc e betwee n the two holes of each twohole termin al is 15.8 mm (0.62 in.). l When a

Exterior

The cross-sectional areas of cables vary according to the way that cabinets are combined. l When a BTS3900AL AC cabinet is combined with a BTS3900AL DC cabinet or an IBBS700D/ IBBS700T, the crosssectional area of the cable is 35 mm2 (0.054 in.2) l When a BTS3900AL AC cabinet is combined with a TMC11H (Ver.C), the cross-sectional area of the cable is 25 mm2 (0.039in. 2).

The exterior is shown by illustration 2 or 3 in the preceding figure.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

129

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Base Station Type

Cross-Sectional Area

Connect or BTS39 00AL AC cabinet is combi ned with a TMC1 1H (Ver.C ), the cable has a twohole OT termin al (M6) on the BTS39 00AL AC cabinet side and a onehole OT termin al (M6) on the TMC1 1H (Ver.C ) side. The distanc e betwee n the two holes of each twohole

Exterior

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

130

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Base Station Type

Cross-Sectional Area

Connect or termin al is 15.8 mm (0.62 in.).

Exterior

3.6.5 Power Cables


This section describes the exteriors, functions, and pin assignments of the power cables in the TMC11H.

DCDU-12B Power Cable


A DCDU-12B power cable feeds DC power into a DCDU-12B.

Exterior
The types of DCDU-12B power cables vary according to power supply scenarios. The following figure shows the exteriors of DCDU-12B power cables. Figure 3-36 Exteriors of DCDU-12B power cables

(1) OT terminal (M6)

Description
The following table describes DCDU-12B power cables.
Issue 03 (2013-01-15) Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd. 131

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Table 3-20 DCDU-12B power cables Base Station Type BTS3900 (Ver.D) Applicatio n Scenario Power Equipme nt External power equipment Cross-Sectional Area Maxi mum Leng th 10 m (32.8 1 ft) Exterior Functi on

In DC scenarios, a DCDU-12B is installed in a BTS3900 (Ver.D) cabinet.

BTS3900 L (Ver.D)

In DC scenarios, a DCDU-12B is installed in a BTS3900L (Ver.D) cabinet.

External power equipment

l One group of cables with a crosssectional area of 35 mm2 (0.054 in.2) is required when one 160 A upper-level circuit breaker is used. l Two groups of cables with a crosssectional area of 16 mm2 (0.025 in.2) are required when two 80 A upper-level circuit breakers are used.

The exterior is shown by illustratio n 1 in the preceding figure. In most regions, the RTN (+) wire is black and the NEG (-) wire is blue. In UK, the RTN(+) wire is blue and the NEG (-) wire is gray. The exterior is shown by illustratio n 1 in the preceding figure. In most regions, the RTN (+) wire is black and the NEG (-) wire is blue. In UK, the RTN(+) wire is blue and the NEG (-) wire is gray.

When the base station is configu red with RFUs and RRUs, a DCDU -12B power cable feeds DC power into the DCDU -12B, and then the DCDU -12B supplie s the power to the RRUs.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

132

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Base Station Type BTS3900 A (Ver.D)

Applicatio n Scenario

Power Equipme nt l Extern al power equip ment in DC scenari os l EPU05 A-02 or EPU05 A-04 in an APM3 0H in AC scenari os

Cross-Sectional Area

Maxi mum Leng th 1.5 m (4.92 ft)

Exterior

Functi on

A DCDU-12B is installed in an RFC (Ver.D).

l One group of cables with a crosssectional area of 25 mm2 (0.039 in.2) in DC scenarios l One group of cables with a crosssectional area of 35 mm2 (0.054 in.2) or two groups of cables with a crosssectional area of 16 mm2 (0.025 in.2) in AC scenarios

The exterior is shown by illustratio n 2 in the preceding figure. In most regions, the RTN (+) wire is black and the NEG (-) wire is blue. In UK, the RTN(+) wire is blue and the NEG (-) wire is gray.

DBS3900

In DC scenarios, a second DCDU-12B is installed in a TMC11H (Ver.D) configured for the DBS3900.

External power equipment

l One group of cables with a crosssectional area of 35 mm2 (0.054 in.2) is required when one 160 A upper-level circuit breaker is used. l Two groups of cables with a crosssectional area of 16 mm2 (0.025 in.2) are required when two 80 A upper-level circuit breakers are used.

15 m (49.2 1 ft)

The exterior is shown by illustratio n 1 in the preceding figure. In most regions, the RTN (+) wire is black and the NEG (-) wire is blue. In UK, the RTN(+) wire is blue and the NEG (-) wire is gray.

When the base station is configu red with RFUs and RRUs, a DCDU -12B power cable feeds DC power into the DCDU -12B, and then

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

133

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Base Station Type

Applicatio n Scenario

Power Equipme nt EPU05A03 or EPU05A05 in the APM30H

Cross-Sectional Area

Maxi mum Leng th 1.5 m (4.92 ft)

Exterior

Functi on

In AC scenarios where the DBS3900 uses the APM30H (Ver.D) and is configured with 7 to 12 RRUs, the DCDU-12B is installed in the APM30H (Ver.D).

One group of cables with a cross-sectional area of 25 mm2 (0.039 in.2)

The exterior is shown by illustratio n 2 in the preceding figure. In most regions, the RTN (+) wire is black and the NEG (-) wire is blue. In UK, the RTN(+) wire is blue and the NEG (-) wire is gray.

the DCDU -12B supplie s the power to RFUs, RRUs, and transmi ssion equipm ent.

DBS3900 where the BBU is installed on a wall, 19inch rack, or IMB03.

External power equipment One group of cables with a crosssectional area of 25 mm2 (0.039 in. 2)

One group of cables with a cross-sectional area of 16 mm2 (0.023 in.2)

15 m (49.2 1 ft)

The exterior is shown by illustratio n 1 in the preceding figure. In most regions, the RTN (+) wire is black and the NEG (-) wire is blue. In UK, the RTN(+) wire is blue and the NEG (-) wire is gray.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

134

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

DCDU-12C Power Cable


A DCDU-12C power cable feeds DC power into a DCDU-12C.

Exterior
The types of DCDU-12C power cables vary according to power supply scenarios. The following figure shows the exteriors of DCDU-12C power cables. Figure 3-37 Exteriors of DCDU-12C power cables

(1) EPC4 or EPC6 connector

(2) OT terminal (M6)

NOTE

In most regions, the RTN(+) wire is black and the NEG(-) wire is blue. In UK, the RTN(+) wire is blue and the NEG(-) wire is gray.

Description
The following table describes DCDU-12C power cables.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

135

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Table 3-21 DCDU-12C power cables Base Station Type Applicati on Scenario Power Equipme nt CrossSectional Area Maxi mu m Leng th Exterior Functio n

BTS3900 A (Ver.D)

In AC scenarios, a DCDU-12 C is installed in a TMC11H (Ver.D), which serves as a transmissi on cabinet.

EPU05A02 or EPU05A04 in the APM30H

One group of cables with a cross-sectional area of 4 mm2 (0.006 in.2)

The exterior is shown by illustration 1 in the preceding figure.

A DCDU-1 2C power cable feeds DC power into a DCDU-1 2C. A DCDU-1 2C distribute s power to each compone nt in the cabinet.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

136

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Base Station Type

Applicati on Scenario

Power Equipme nt

CrossSectional Area

Maxi mu m Leng th 15 m (59.2 1 ft) when the TMC 11H serve s as a trans missi on cabin et

Exterior

Functio n

In DC scenarios, a DCDU-12 C is installed in a TMC11H (Ver.D), which serves as a transmissi on cabinet or the power cabinet.

l DC junctio n box in the RFC when the TMC1 1H serves as the power cabinet l Extern al power equipm ent when the TMC1 1H serves as a transmi ssion cabinet

l One group of cables with a crosssectional area of 25 mm2 (0.039 in.2) when the TMC11H serves as the power cabinet l One group of power cables with a crosssectional area of 4 mm2 (0.006 in.2) when the TMC11H serves as a transmission cabinet

l The exterior is shown by illustrati on 3 in the precedi ng figure when the TMC11 H serves as the power cabinet. l The exterior is shown by illustrati on 2 in the precedi ng figure when the TMC11 H serves as a transmis sion cabinet.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

137

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Base Station Type

Applicati on Scenario

Power Equipme nt

CrossSectional Area

Maxi mu m Leng th -

Exterior

Functio n

DBS3900

In AC scenarios, a DCDU-12 C is installed in a TMC11H (Ver.D), which serves as a transmissi on cabinet. In DC scenarios, a DCDU-12 C is installed in a TMC11H (Ver.D), which serves as a transmissi on cabinet.

EPU05A03 or EPU05A05 in the APM30H

One group of cables with a cross-sectional area of 25 mm2 (0.039 in.2)

The exterior is shown by illustration 1 in the preceding figure.

External power equipment

One group of cables with a cross-sectional area of 4 mm2 (0.006 in.2)

10 m (32.8 1 ft)

The exterior is shown by illustration 2 in the preceding figure.

BTS3900 AL (Ver.A)

A DCDU-12 C is installed in a BTS3900 AL (Ver.A).

l PDU03 D-01 in the BTS39 00AL (Ver.A ) in DC scenari os l ETP48 400 in the BTS39 00AL (Ver.A ) in AC scenari os

One group of cables with a cross-sectional area of 16 mm2 (0.025 in2)

The exterior is shown by illustration 3 in the preceding figure.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

138

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

SOU Power Cable


The power cable for a service outlet unit (SOU) feeds AC power into the SOU from the AC OUTPUT port on the EPU or EPS.

Exterior
The following figure shows the exterior of an SOU power cable. Figure 3-38 Exterior of an SOU power cable

(1) C13 connector

(2) OT terminal (M4)

Description
The following table describes an SOU power cable. Table 3-22 SOU power cable Wire W1 W2 W3 Color Brown Green and yellow Blue Silkscreen L PE N Cross-Sectional Area 2.5 mm2 (0.004 in.2)

NOTE

The colors and structures of cables delivered by Huawei vary according to countries and regions. If cables are purchased locally, the cables must comply with local rules and regulations.

Power Cable for an AC Heater


The power cable for an AC heater feeds power into an AC junction box from the AC OUTPUT port on an EPU or EPS. Then the AC junction box distributes power to the AC heater. If an AC
Issue 03 (2013-01-15) Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd. 139

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

heater is configured in the -48 V DC input scenario, one more AC power input must be added for the heater. In this case, the maximum length of the power cable for the AC heater is 15 m (49.21 ft).

Exterior
The following figure shows the exterior of a power cable for an AC heater. Figure 3-39 Exterior of a power cable for an AC heater

(1) C13 connector

(2) OT terminal (M4)

Description
The following table describes the power cable for an AC heater. Table 3-23 Power cable for an AC heater Wire W1 W2 W3 Color Brown Green and yellow Blue Silkscreen L PE N Cross-Sectional Area 1.5 mm2 (0.002 in.2)

NOTE

The colors and structures of cables delivered by Huawei vary according to countries and regions. If cables are purchased locally, the cables must comply with local rules and regulations.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

140

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

FAN 02D Power Cable


A FAN 02D power cable feeds -48 V DC power into the FAN 02D in an APM30H or TMC11H (Ver.D).

Exterior
Figure 3-40 and Figure 3-41 show the exterior of a FAN 02D power cable. Figure 3-40 Exterior of a FAN 02D power cable in most regions

(1) 3V3 connector

(2) EPC4 or EPC6 connector

Figure 3-41 Exterior of a FAN 02D power cable in UK

(1) 3V3 connector

(2) EPC4 or EPC6 connector

Description
The following table describes a FAN 02D power cable. Table 3-24 FAN 02D power cable Cable FAN 02D power cable
Issue 03 (2013-01-15)

Wire RTN(+)

Wire Color in Most Regions Black

Wire Color in Other Regions (UK) Blue

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

141

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Cable

Wire NEG(-)

Wire Color in Most Regions Black

Wire Color in Other Regions (UK) Gray

Power Cable for an AC Junction Box


A power cable for the AC junction box feeds AC power from the power devise into the AC junction box. The power is divided into four AC outputs, which are then provided to other components, such as the heater or heating film.

Exterior
The following figure shows the exterior of a power cable for an AC junction box. Figure 3-42 Power cable for an AC junction box

(1) OT terminal

(2) Cord end terminal

NOTE

The colors and structures of cables delivered by Huawei vary according to countries and regions. If cables are purchased locally, the cables must comply with local rules and regulations.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

142

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Description
The following table describes a power cable for an AC junction box. Table 3-25 Power cable for an AC junction box Base Stati on Type BTS3 900A Cabinet Power Equipme nt EPU or EPS subrack EPU or EPS subrack, and transfered by AC junction box in APM30H EPU subrack, and transfered by AC junction box in APM30H PDU05A-0 1 Wire Color CrossSectional Area 1.5 mm2 (0.002 in.2) 1.5 mm2 (0.002 in.2) Exterior

APM30H

L N L N

Brown Blue Brown Blue

TMC11H

The exterior is shown by illustration 1 in the preceding figure.

IBBS700 D/ IBBS700 T

L N

Brown Blue

1.5 mm2 (0.002 in.2)

BTS3 900A L

BTS3900 AL AC

L N

Brown Blue

2.5 mm2 (0.004 in.2)

The exterior is shown by illustration 2 in the preceding figure. The exterior is shown by illustration 3 in the preceding figure.

BTS3900 AL DC

PDU05A-0 1, and transfered by AC junction box in BTS3900A L AC PDU05A-0 1, and transfered by AC junction box in

L N

Brown Blue

2.5 mm2 (0.004 in.2)

IBBS700 D/ IBBS700 T

Brown

2.5 mm2 (0.004 in.2)

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

143

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Base Stati on Type

Cabinet

Power Equipme nt BTS3900A L AC

Wire

Color

CrossSectional Area

Exterior

Blue

3.6.6 Signal Cables


This section describes the exteriors, functions, and pin assignments of the signal cables in the TMC11H.

ELU Signal Cable


An electronic label unit (ELU) signal cable transmits the cabinet type to a monitoring board in the cabinet.

Exterior
The following figure shows the exterior of an ELU signal cable. Figure 3-43 Exterior of an ELU signal cable

(1) RJ45 connector

Description
The following table describes an ELU signal cable. Table 3-26 ELU signal cable X1 End X1.1
Issue 03 (2013-01-15)

X2 End X2.1

Color White

Wire Type Twisted pair


144

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

X1 End X1.2 X1.3 X1.6 X1.5 X1.4 X1.7 X1.8

X2 End X2.2 X2.3 X2.6 X2.5 X2.4 X2.7 X2.8

Color Orange White Green White Blue White Brown

Wire Type

Twisted pair

Twisted pair

Twisted pair

Monitoring Signal Cable for the Door Status Sensor


A monitoring signal cable for the door status sensor is used to inform the monitoring board of the door status that is obtained from the door status sensor. Cabinets configured with door status sensors are as follows: APM30H, TMC11H, RFC, IBBS200D, IBBS200T, BTS3900AL, OMB, IBBS700D and IBBS700T.

Exterior
Monitoring signal cables for door status sensors are classified into three types according to the cabinets being monitored. Figure 3-44, Figure 3-45, and Figure 3-46 show their exteriors. Figure 3-44 Exterior of a monitoring signal cable for the door status sensor (1)

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

145

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Figure 3-45 Exterior of a monitoring signal cable for the door status sensor (2)

NOTE

l Cable 1 has a 2-pin straight socket at one end, which is connected to the HPMI. Cable 1 has a bare wire and a cord end terminal at the other end, which are connected to a door status sensor and a cable terminal block, respectively. l Cable 2 has a bare wire at one end, which is connected to a door status sensor. Cable 2 has a cord end terminal at the other end, which is connected to a cable terminal block. l Cable 3 has a cord end terminal at each end. The two cord end terminals are connected to the two ports on one side of the cable terminal block.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

146

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Figure 3-46 Exterior of a monitoring signal cable for the door status sensor (3)

NOTE

l Cable 1 has a 2-pin straight socket at one end, which is connected to the GATE port on the PMU. Cable 1 has a bare wire and a cord end terminal at the other end, which are connected to a door status sensor and a cable terminal block, respectively. l Cable 2 has a bare wire at one end, which is connected to a door status sensor. Cable 2 has a cord end terminal at the other end, which is connected to a cable terminal block. l Cable 3 has a cord end terminal at each end. The two cord end terminals are connected to the two ports on one side of the cable terminal block.

Description
Monitoring signal cables for door status sensors are classified into different types according to the monitoring boards to which the door status is reported. The following table lists the monitoring signal cables for door status sensors.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

147

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Table 3-27 Types of monitoring signal cables for door status sensors Base Station Type BTS3900A (Ver.B) Cabinet Monitoring Board to Which the Door Status Is Reported CMUA Exterior

l RFC (Ver.B) l TMC11H (Ver.B) l IBBS200D (Ver.B) or IBBS200T (Ver.B)

The exterior is shown in Figure 3-44.

BTS3900A (Ver.C)

l RFC (Ver.C) l TMC11H (Ver.C) l IBBS200D (Ver.C) or IBBS200T (Ver.C)

CMUE

BTS3900A (Ver.D)

l RFC (Ver.D) l TMC11H (Ver.D) l IBBS200D (Ver.D) or IBBS200T (Ver.D) l IBBS700D IBBS700T

CMUEA

CMUF CMUA

DBS3900

l TMC11H (Ver.B) l IBBS200D (Ver.B) or IBBS200T (Ver.B) l TMC11H (Ver.C) l IBBS200D (Ver.C) or IBBS200T (Ver.C) l TMC11H (Ver.D) l IBBS200D (Ver.D) or IBBS200T (Ver.D)

CMUE

CMUEA

l BTS3900C l DBS3900 l BTS3900C (Ver.C) l DBS3900 (Ver.C)

OMB

HEUA

OMB (Ver.C)

HEUB

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

148

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Base Station Type BTS3900AL (Ver.A)

Cabinet

Monitoring Board to Which the Door Status Is Reported CCU

Exterior

l BTS3900AL (Ver.A) l IBBS700D l IBBS700T

l BTS3900A (Ver.B) l DBS3900 l BTS3900A (Ver.C) l DBS3900 l BTS3900A (Ver.D) l DBS3900

APM30H (Ver.B)

HPMI

The exterior is shown in Figure 3-45.

APM30H (Ver.C)

HPMI

APM30H (Ver.D)

PMU

The exterior is shown in Figure 3-46.

Monitoring Signal Transfer Cable for the Fan in the Front Door
A monitoring signal transfer cable for the fan in the front door feeds power into the fan in the front door of the APM30H or TMC11H. It also transmits fan monitoring signals to a monitoring board in the cabinet.

Cable Type
The following table lists the types of monitoring boards to which the monitoring signals are reported. Monitoring signal cables vary according to the boards. Table 3-28 Cable type Cable Cabinet Monitoring Board to Which the Monitoring Signals Are Reported CMUA CMUE CMUEA Exterior

Monitoring signal transfer cable for the fan in the front door

APM30H (Ver.B) or TMC11H (Ver.B) APM30H (Ver.C) or TMC11H (Ver.C) APM30H (Ver.D) or TMC11H (Ver.D)

The exterior is shown by illustration 1 in the following figure.

The exterior is shown by illustration 2 in the following figure.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

149

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

3 TMC11H Cabinet

Exterior
The following figure shows the exteriors of monitoring signal transfer cables for fans in the front doors. Figure 3-47 Exteriors of monitoring signal transfer cables for fans in the front doors

(1) 4-pin connector

(2) Interconnection terminal

Description
The following table describes a monitoring signal transfer cable for the fan in the front door. Table 3-29 Monitoring signal transfer cable for the fan in the front door Wire W1 W2 W3 W4 X1 End X1.1 X1.2 X1.3 X1.4 X2 End X2.1 X2.2 X2.3 X2.4 Color Black Black Black Black

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

150

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

4
About This Chapter

IBBS200D Cabinet

This chapter describes the IBBS200D cabinet exterior, engineering specifications, application scenarios, as well as boards, modules, and cables in the IBBS200D cabinet. 4.1 Cabinet Exterior The integrated battery backup system with direct cooling (IBBS200D) uses fans to dissipate heat from the cabinet and can provide backup power to the APM30H. 4.2 Cabinet Engineering Specifications This section describes the engineering specifications of the IBBS200D, including the electrical specifications, equipment specifications, and environment specifications. 4.3 Cabinet Interior This section describes the components and boards in the IBBS200D. The power distribution equipment is installed on the upper right wall of the cabinet interior, and the monitoring equipment is installed inside the cabinet door. 4.4 IBBS200D Components This section describes the mandatory and optional components in an IBBS200D. 4.5 IBBS200D Cables The IBBS200D cables consist of the power cables, equipotential cables, PGND cables, and signal cables.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

151

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

4.1 Cabinet Exterior


The integrated battery backup system with direct cooling (IBBS200D) uses fans to dissipate heat from the cabinet and can provide backup power to the APM30H. The following figure shows the exterior of the IBBS200D. Figure 4-1 Exterior of the IBBS200D

4.2 Cabinet Engineering Specifications


This section describes the engineering specifications of the IBBS200D, including the electrical specifications, equipment specifications, and environment specifications.

Electrical Specifications
The following table lists the electrical specifications of the IBBS200D. Table 4-1 Electrical specifications Item Input voltage range Maximum capacity of the storage batteries Heat dissipation in the cabinet Specifications -38.4 V DC to -57 V DC 48 V, 184 Ah The difference between the temperature in the battery cabinet and the ambient temperature must be less than 5oC (41oF).

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

152

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

Equipment Specifications
The following table lists the equipment specifications of the IBBS200D. Table 4-2 Equipment specifications Item Dimensions (H x W x D) Specifications Cabinet (without the base): 700 mm x 600 mm x 480 mm (27.56 in. x 23.62 in. x 18.90 in.) Base: 200 mm x 600 mm x 434 mm (7.87 in. x 23.62 in. x 17.09 in.) Cabinet weight 40 kg (88.2 lb) The cabinet is configured only with monitoring boards, power distribution box, and cables. The total capacity can expand to 48 V 184 Ah (two 48 V 92 Ah battery packs). Remarks -

Weight of storage batteries

12 V 92 Ah storage battery: 33.5 kg (73.87 lb)


NOTE Storage batteries from different manufacturers have different specifications. The specifications listed above are for the commonly used storage batteries.

Method of installation

It can be installed on the ground. It can be also installed on the TMC11H or APM30H in stack mode.

In stack mode, the IBBS200D must be installed under the TMC11H or APM30H.

Environment Specifications
The IBBS200D can be used outdoors. The following table lists the environment specifications of the IBBS200D. Table 4-3 Environment specifications Item Operating temperatur e Relative humidity Altitude Specifications -40oC to +40oC (-40oF +104oF) Remarks Heating films must be used in cold areas. From the altitude of 1800 m (5905.44 ft), the maximum operating temperature drops by 1oC (33.8oF) each time the altitude increases by 220 m (721.78 ft).
153

5% RH to 100% RH -60 m to +4000 m (-196.85 ft to +13123.2 ft)

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

Item Wind speed Storage temperatur e Dustproof and waterproof Noise

Specifications 67 m/s -40oC to +70oC (-40oF to +158oF)

Remarks -

IP34

Meeting the ETS 300 753 4.1E standard (rural area)

4.3 Cabinet Interior


This section describes the components and boards in the IBBS200D. The power distribution equipment is installed on the upper right wall of the cabinet interior, and the monitoring equipment is installed inside the cabinet door. The following figure shows the interior of the IBBS200D. Figure 4-2 Interior of the IBBS200D

The following table describes the components in the IBBS200D.\

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

154

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

Table 4-4 Components in the IBBS200D No . Component Option al or Manda tory Max imu m Qua ntit y in a Sin gle Cab inet 1 1 Remarks

1 2

Fan mounting frame CMUEA

Mandat ory Mandat ory Mandat ory Mandat ory Mandat ory

The fan mounting frame is installed on the front door of the cabinet, and configured with a fan. The central monitoring unit type EA (CMUEA) controls temperature, detects Boolean alarm, and identifies the ELU. The electronic label unit (ELU) reports the cabinet type automatically to facilitate troubleshooting. The storage batteries provide long-duration backup power for base stations. The power distribution box is installed on the upper right wall of the cabinet interior. It transfers and distributes input power to the TEC or fan and storage batteries. The door status sensor monitors the status (open or closed) of the cabinet door. The IBBS200D must be configured with a heating film in cold areas. The heating film is not required in general areas. The junction terminal provides the input power port for the heating film.

3 4 5

ELU Storage battery Power distribution box Door status sensor Heating film

1 8 1

6 7

Mandat ory Optiona l Mandat ory

1 2

Junction terminal for the input power cable of the heating film

4.4 IBBS200D Components


This section describes the mandatory and optional components in an IBBS200D.

4.4.1 Fan Mounting Frame


In an IBBS200D, the fan mounting frame is configured with a fan and is installed on the front door of the cabinet. The fan promotes the inner and outer air circulation of the cabinet to ensure
Issue 03 (2013-01-15) Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd. 155

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

that the cabinet work within an acceptable temperature range. This allows the batteries to work properly.

Exterior
The following figure shows the exterior of the fan mounting frame in an IBBS200D (Ver.B). Figure 4-3 Exterior of the fan mounting frame in an IBBS200D (Ver.B)

(1) Fan

(2) CMUA

The following figure shows the exterior of the fan mounting frame in an IBBS200D (Ver.C).

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

156

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

Figure 4-4 Exterior of the fan mounting frame in an IBBS200D (Ver.C)

(1) Fan

(2) CMUE

The following figure shows the exterior of the fan mounting frame in an IBBS200D (Ver.D). Figure 4-5 Exterior of the fan mounting frame in an IBBS200D (Ver.D)

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

157

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

Functions
A fan mounting frame performs the following functions: l l The fan promotes the inner and outer air circulation of the cabinet to ensure that the cabinet work within an acceptable temperature range. This allows the batteries to work properly. The monitoring board installed in the fan mounting frame collects the alarm signals from the door status sensor, battery temperature sensor, fans, and smoke sensor in the cabinet, and it reports these alarm signals to the PMU through an RS485 signal cable.

The types of monitoring boards installed in the fan mounting frames vary with the versions of cabinets. The following table lists the types of monitoring boards. Table 4-5 Types of monitoring boards installed in the fan mounting frames Cabinet IBBS200D (Ver.B) IBBS200D (Ver.C) IBBS200D (Ver.D) Monitoring Board CMUA CMUE CMUEA

Signal Cable Delivered with a Fan


Exterior IBBS200D (Ver.B), IBBS200D (Ver.C), and IBBS200D (Ver.D) have signal cables delivered along with them. The following figure shows the exterior of such a signal cable. Figure 4-6 Exterior of a signal cable delivered with a fan

NOTE

The signal cable delivered with a fan feeds power into the fan and transmits signals to a monitoring board.

Description The following table describes a signal cable delivered with the fan. Table 4-6 Description Wire W1 W2 A End A.1 A.2 Color Red Yello w Description Connects to the positive pole of the power supply. Imports PWM speed-adjusting signals.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

158

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

Wire W3 W4

A End A.3 A.4

Color Blue Black

Description Exports alarm or speed signals. Connects to the negative pole of the power supply.

NOTE

The color of the signal cable delivered with a fan depends on the manufacturer.

4.4.2 CMUEA
The central monitoring unit type EA (CMUEA) monitors the fans, Heater Assembly Unit, and cabinet temperature. A CMUEA can be used in the AMP30H, RFC, TMC11H, IBBS200D, IBBS200T, or IBBS700D cabinet.

Exterior
The following figure shows the exterior of a CMUEA. Figure 4-7 Exterior of a CMUEA

Ports
The following figure shows the ports on a CMUEA. Figure 4-8 Ports on a CMUEA

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

159

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

The following table lists information about ports on a CMUEA. Table 4-7 Ports on a CMUEA No . (1) (2) (3) (4) (5) (6) (7) (8) Silkscreen on the Panel TEMP2 WATER IFAN4 IFAN3 IFAN2 IFAN1 TEC TEMP1 Connected to the TEC cooler to receive alarms related to the TEC cooler. l In an RFC, this port is connected to the temperature sensor at the air intake vent of the cabinet to receive temperature alarms about the RFC. l In an IBBS200D, IBBS200T, IBBS700D, or IBBS700T, this port is connected to the battery temperature sensor to receive alarm signals about the battery temperature. (9) COM_OUT It is an RS485 signal port, which communicates with lower-level cascading ports and reports monitoring information. l In the APM30H, this port is connected to the PMU. l In an RFC, TMC11H, IBBS200D, IBBS200T, IBBS700D, or IBBS700T, this port is connected to a lower-level CMUEA. (10 ) COM_IN RS485 signal port for communicating with upper-level cascading ports and reporting monitoring information. l In the APM30H, this port is connected to the BBU. l In the RFC or TMC11H, this port is connected to the BBU or an upper-level CMUEA. l In an IBBS200D, IBBS200T, IBBS700D, or IBBS700T, this port is connected to the PMU or an upper-level CMUEA. (11 ) (12 ) (13 ) ELU GATE IN0, IN1, and IN2 Port for connecting the ELU to report the cabinet type. Boolean signal port, which is connected to the door status sensor. Boolean signal port. l In the APM30H, RFC, TMC11H, IBBS200D, or IBBS200T, these ports are reserved. l In the IBBS700D or IBBS700T, IN0 is connected to the heater, and IN1 and IN2 are reserved.
Issue 03 (2013-01-15) Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd. 160

Description

Reserved port, connected to the temperature sensor. Connected to the water sensor. Connected to the inner air circulation to receive alarms related to the inner air circulation.

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

No . (14 )

Silkscreen on the Panel SMOKE

Description

Boolean signal port. l In the APM30H, RFC, TMC11H, IBBS200D, or IBBS200T, this port is connected to the smoke sensor. l In the IBBS700D or IBBS700T, this port is not involved.

(15 ) (16 ) (17 )

EFAN1 EFAN2 PWR

Connected to the outer air circulation fan to receive its alarm signals.

Power input port providing DC power input for the board.

Indicators
The two indicators on the CMUEA panel indicate the status of the CMUEA. The following table describes their meanings. Table 4-8 Indicators on the CMUEA panel Silkscr een RUN Color Green State Blinking (on for 1s and off for 1s) Blinking (on for 0.125s and off for 0.125s) Steady on Steady off ALM Red Steady off Steady on Blinking (on for 1s and off for 1s) Meaning The board is functional and communicating with the BBU properly. The board is functional but fails to communicate with the BBU or the board is not registered. The board is in the power-on self-check status. There is no power supply, or the board is faulty. No alarm is reported. An alarm is generated, and the board must be replaced. An alarm is generated, and the alarm may be caused by an associated board or port fault. Therefore, you need to locate the fault before determining whether to replace the board.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

161

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

DIP Switch
On the CMUEA, there is a DIP switch J18, which is used to set the working mode of the CMUEA according to the cabinet type. Figure 4-9 shows the position of the DIP switch on the CMUEA. Figure 4-9 Position of DIP switch on a CMUEA

In different types of cabinets, DIP switches on the CMUEA are set in different ways, as shown in Figure 4-10.
NOTE

The white boxes indicate the positions of all bits in the DIP switch.

Figure 4-10 DIP switch setting on the CMUEA in different cabinets

4.4.3 Power Distribution Box


The power distribution box is installed on the upper right inner wall of the cabinet, which controls the two storage battery groups separately and the DC power supply to the fan or TEC.
Issue 03 (2013-01-15) Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd. 162

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

Exterior
The following figure shows the exterior of a power distribution box. Figure 4-11 Exterior of a power distribution box

Port
The following table describes the ports on a power distribution box. Table 4-9 Ports on the power distribution box No. (1) Silkscreen BAT Meaning Input power cable port for storage batteries Circuit breaker for the upper storage batteries Power output port for a fan or TEC Circuit breaker for the lower storage batteries Input power cable port for storage batteries Power input port for a fan or TEC Description It supports a one-hole OT terminal (M8) installed on a cable with a cross-sectional area of 35 mm2 (0.054 in.2). It controls the power supply to upper storage batteries in the cabinet. The circuit breaker requires 250 A current. It supports EPC4 connectors and requires 30 A current. It controls the power supply to lower storage batteries in the cabinet. The circuit breaker requires 250 A current. It supports a one-hole OT terminal (M8) installed on a cable with a cross-sectional area of 35 mm2 (0.054 in.2). It supports EPC4 connectors and requires 30 A current.

(2)

BAT_SW0

(3)

FAN/ TEC_OUTPU T BAT_SW1

(4)

(5)

BAT

(6)

FAN/ TEC_INPUT

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

163

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

Wire
The following figure shows the input and output power cables for a power distribution box. Figure 4-12 Cables for a power distribution box

(1) RTN(+) cable for upper storage (2) Power transfer cable for a TEC or (3) NEG(-) wire for lower storage batteries fan assembly batteries (4) NEG(-) wire for upper storage batteries (5) RTN(+) wire for lower storage batteries -

4.4.4 Storage Battery


Storage batteries is the store power equipment.
NOTE

Storage batteries from different manufacturers differ in exteriors and technical specifications. In this section, a 12 V 92 Ah storage battery is described as an example.

Exterior
The following figure shows the exterior of a 12 V 92 Ah storage battery.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

164

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

Figure 4-13 Exterior of a 12 V 92 Ah storage battery

Configuration
The IBBS200T and IBBS200D support two types of storage battery groups: 48 V 92 Ah and 48 V 184 Ah. l l Two 48 V 92 Ah storage battery groups are connected in parallel and serve as a 48 V 184 Ah storage battery group. Each group consists of four storage batteries.

Technical Specifications
The following table describes the technical specifications of a 12 V 92 Ah storage battery. Table 4-10 Technical specifications of a 12 V 92 Ah storage battery Storage Battery Type 12 V, 92 Ah Dimensions (H x W x D) 105 mm x 287 mm x 390 mm (11.30 in. x 4.13 in. x 15.35 in.) 108 mm x 287 mm x 393 mm (11.30 in. x 4.25 in. x 15.47 in.) Weight 33.5 kg (73.85 lb)

35 kg (77.16 lb)

4.4.5 ELU
An electronic label unit (ELU) reports the cabinet type automatically to facilitate troubleshooting.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

165

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

Exterior
The following figure shows the exterior of an ELU. Figure 4-14 Exterior of an ELU

(1) Shell

(2) RJ45 port

NOTE

The ELU in a BTS3900 or BTS3900L has no shell.

The board collecting information from the ELU varies according to the cabinet, as listed in the following table. Table 4-11 Monitoring boards to which an ELU reports information Base Station Type BTS3900 (Ver.B) and BTS3900L (Ver.B) BTS3900 (Ver.C) and BTS3900L (Ver.C) BTS3900 (Ver.D) and BTS3900L (Ver.D) BTS3900A (Ver.B) Cabinet Board Collecting Information from the ELU FMUC

BTS3900 (Ver.B) and BTS3900L (Ver.B)

BTS3900 (Ver.C) and BTS3900L (Ver.C)

FMUE

BTS3900 (Ver.D) and BTS3900L (Ver.D)

FMUEA

APM30H (Ver.B), TMC11H (Ver.B), RFC (Ver.B), IBBS200D (Ver.B), and IBBS200T (Ver.B)

CMUA

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

166

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

Base Station Type BTS3900A (Ver.C) BTS3900A (Ver.D)

Cabinet

Board Collecting Information from the ELU CMUE

APM30H (Ver.C), TMC11H (Ver.C), RFC (Ver.C), IBBS200D (Ver.C), and IBBS200T (Ver.C) APM30H (Ver.D), TMC11H(Ver.D), RFC (Ver.D), IBBS200D(Ver.D), IBBS200T (Ver.D), and IBBS700D IBBS700T

CMUEA

CMUF HEUB CCU

BTS3900C (Ver.C) BTS3900AL (Ver.A)

OMB (Ver.C) BTS3900AL (Ver.A), IBBS700D, IBBS700T

Installation Position
Positions of ELUs vary in different cabinets. The following figure shows their positions. Figure 4-15 Position of the ELU in a BTS3900 cabinet

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

167

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

Figure 4-16 Position of the ELU in a BTS3900L cabinet

Figure 4-17 Position of the ELU in an APM30H or IBBS200D cabinet

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

168

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description


NOTE

4 IBBS200D Cabinet

An ELU is located on the right inner wall of the APM30H, TMC11H, or RFC, or on the left inner wall of the IBBS200D or IBBS200T. The preceding figure shows an APM30H and an IBBS200D as an example.

Figure 4-18 Position of the ELU in an OMB

Figure 4-19 Position of the ELU in a BTS3900AL cabinet

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

169

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

Figure 4-20 Position of the ELU in a IBBS700D cabinet

NOTE

In the IBBS700D, when the cabinet is configured with a CCU, the ELU is above the CCU. When the cabinet is not configured with a CCU, the ELU is on the right of the CMUEA.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

170

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

Figure 4-21 Position of the ELU in a IBBS700T cabinet

NOTE

In the IBBS700T, when the cabinet is configured with a CCU, the ELU is above the CCU. When the cabinet is not configured with a CCU, the ELU is on the left of the CMUF.

4.4.6 Heating Film


The heating film functions in the low-temperature environment to provide the suitable storage and operating temperature for the storage batteries. When the operating temperature is lower than the temperature specification of the storage batteries, the battery capacity declines. Therefore, the heating film is installed to ensure that the storage batteries work in a proper temperature range. The heating film is optional.
NOTE

An IBBS200D has two heating films, which are installed on the upper and lower pallets, respectively.

Exterior
The following figure shows the exterior of a heating film.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

171

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

Figure 4-22 Exterior of a heating film

Technical Specifications
The technical specifications of a heating film are as follows: Table 4-12 Technical specifications of a heating film Counter Temperature range in the cabinet when the heating film starts working Temperature range in the cabinet when the heating film stops working Rated heating power Rated operating voltage Specification < 1oC (6oC) or 33.8oF (42.8oF) > 15oC (3oC) or 59 oF (37.4oF) 100 W 220 V AC

4.4.7 Door Status Sensor


A door status sensor reports the status (open or closed) of a door. It is installed in any of the following cabinets: BTS3900AL, OMB, OMB (Ver.C), APM30H, RFC, TMC11H, IBBS200D, IBBS200T, IBBS700D, and IBBS700T.

Exterior
A door status sensor consists of a magnet and a switch. The following figures show the exteriors of them.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

172

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

Figure 4-23 Exterior of the magnet of a door status sensor

(1) Magnetic shell

(2) Magnet

The following figure shows the exterior of the switch of a door status sensor. Figure 4-24 Exterior of the switch of a door status sensor

Installation Position
Positions of door status sensors vary in different cabinets. The following figure shows their positions.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

173

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description


NOTE

4 IBBS200D Cabinet

l A door status sensor is installed at the same position in the BTS3900AL (Ver.A), IBBS700D, and IBBS700T. Figure 4-25 uses the BTS3900AL (Ver.A) as an example. l A door status sensor is installed at the same position in the OMB and OMB (Ver.C). Figure 4-26 uses the OMB (Ver.C) as an example. l A door status sensor is installed at the same position in the following cabinets: APM30H (Ver.B), APM30H (Ver.C), APM30H (Ver.D), RFC (Ver.B), RFC (Ver.C), RFC (Ver.D), TMC11H (Ver.B), TMC11H (Ver.C), TMC11H (Ver.D), IBBS200D (Ver.B), IBBS200D (Ver.C), IBBS200D (Ver.D), IBBS200T (Ver.B), IBBS200T (Ver.C), and IBBS200T (Ver.D). Figure 4-27 uses the APM30H (Ver.D) as an example.

Figure 4-25 Position of a door status sensor in the BTS3900AL (Ver.A)

Figure 4-26 Position of a door status sensor in the OMB (Ver.C)

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

174

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

Figure 4-27 Position of a door status sensor in the APM30H (Ver.D)

4.4.8 Temperature Sensor


The temperature sensor monitors the temperature in the cabinet. It is installed in the following cabinets: BTS3900AL, RFC, IBBS200T, IBBS200D, OMB, IBBS700T, and IBBS700D.

Exterior
The following figure shows the exterior of a temperature sensor. Figure 4-28 Exterior of a temperature sensor

(1) Temperature sensor

(2) 4-pin connector

Installation Position
Positions of temperature sensors vary in different cabinets. The following figure shows their positions.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

175

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description


NOTE

4 IBBS200D Cabinet

l A temperature sensor is installed at the same position in the RFC (Ver.B), RFC (Ver.C), and RFC (Ver.D). Figure 4-30 uses the RFC (Ver.D) as an example. l A temperature sensor is installed at the same position in the IBBS200T (Ver.B), IBBS200T (Ver.C), and IBBS200T (Ver.D). Figure 4-31 uses the IBBS200T (Ver.D) as an example. l A temperature sensor is installed at the same position in the IBBS200D (Ver.B), IBBS200D (Ver.C), and IBBS200D (Ver.D). Figure 4-32 uses the IBBS200D (Ver.D) as an example. l A temperature sensor is installed at the same position in the OMB (Ver.C), and OMB. Figure 4-33 uses the OMB (Ver.C) as an example.

Figure 4-29 Position of the temperature sensor in a BTS3900AL (Ver.A) cabinet

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

176

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

Figure 4-30 Position of the temperature sensor in an RFC (Ver.D)

Figure 4-31 Position of the temperature sensor in an IBBS200T (Ver.D)

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

177

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

Figure 4-32 Position of the temperature sensor in an IBBS200D (Ver.D)

Figure 4-33 Position of the temperature sensor in an OMB (Ver.C)

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

178

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

Figure 4-34 Position of the temperature sensor in an IBBS700D

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

179

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

Figure 4-35 Position of the temperature sensor in an IBBS700T

Technical Specifications
The following table lists the technical specifications of a temperature sensor. Table 4-13 Technical specifications of a temperature sensor Counter Operating voltage Temperature measurement range Temperature measurement error Specification 3.0 V DC to 5.5 V DC -55C to +125C (-131 F to +257 F) 2C (35.6F)

4.5 IBBS200D Cables


The IBBS200D cables consist of the power cables, equipotential cables, PGND cables, and signal cables.

4.5.1 Cable List


IBBS200D cables consist of the PGND cables, equipotential cables, power cables, and signal cables.
Issue 03 (2013-01-15) Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd. 180

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

Power Cables, PGND Cables, and Equipotential Cables


The following table lists the power cables, PGND cables, and equipotential cables. Table 4-14 Power cables, PGND cables, and equipotential cables Classi ficati on Cables to be install ed onsite Cable One End Connector Power Cable for a Power Distribution Box OT terminal Installation Position RTN(+) and NEG(-) terminals on the BAT terminal block on the EPU The Other End Connector OT terminal Installation Position RTN(+) and NEG(-) terminals on the BAT terminal block on the power distribution box in the IBBS200D Storage battery

Storage Battery Power Cable Power Cable for the Fan in an IBBS200D

OT terminal

Copper bar on the power distribution box LOAD8 port on the EPU

OT terminal

EPC4 or EPC6 connector

EPC4 or EPC6 connector

FAN/ TEC_INPUT port on the power distribution box in the IBBS200D L and N terminals on the junction terminal for the input power cable for the heating film in the IBBS200D Ground busbar outside the cabinet Ground bar in the lower cabinet

Power Cable for the Heating Film

OT terminal

L1 and N1 or L2 and N2 terminals on the AC junction box in the APM30H

OT terminal

2.7.3 PGND Cable 2.7.4 Equipotential Cable

OT terminal

Ground bar in the cabinet Ground bar in the upper cabinet

OT terminal

OT terminal

OT terminal

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

181

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

Classi ficati on Cables install ed before deliver y

Cable

One End Connector Installation Position -

The Other End Connector Installation Position -

Signal Cables
The following table describes the signal cables. Table 4-15 Signal cables Classi ficati on Cables to be install ed onsite Cables install ed before deliver y Cable One End Connecto r Monitoring Signal Cable for the Battery Cabinet ELU Signal Cable Monitoring Signal Cable for the Door Status Sensor RJ45 connector Installation Position COM_IN port on the CMUEA in the IBBS200D or IBBS200T ELU GATE port on the CMUEA The Other End Connect or RJ45 connector Installation Position COM_485 port on the PMU

RJ45 connector Bare wire

RJ45 connector Bare wire

ELU port on the CMUEA Door status sensor

4.5.2 Cable Connections


This section describes the principles for connecting power cables and signal cables in the IBBS200D.

Power Cable Connections


This section describes the power cable connections in the IBBS200D. The following figure shows the power cable connections in the IBBS200D.
Issue 03 (2013-01-15) Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd. 182

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

Figure 4-36 Power cable connections in the IBBS200D

(1) Cable between the battery pack (2) Power Cable for the Fan in an and the short-circuiting copper bar IBBS200D

(3) Storage Battery Power Cable

(4) Cable between the battery pack (5) Power Cable for the Heating Film (6) Power Transfer Cable for the Fan and the short-circuiting copper bar in the IBBS200D

Monitoring Signal Cable Connections


This section provides reference for onsite installation of monitoring signal cables. Figure 4-37 shows the monitoring signal cable connections in the IBBS200D.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

183

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

Figure 4-37 Monitoring signal cable connections in the IBBS200D

(1) Monitoring signal cable for the door status sensor

(2) ELU signal cable (3) Monitoring signal cable for the battery cabinet

4.5.3 PGND Cable


PGND cables ensure that cabinets and internal components are properly grounded and that base stations run properly. PGND cables include classified into PGND cables for cabinets and PGND cables for components.

Exterior
The following figure shows the exterior of a PGND cable.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

184

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

Figure 4-38 Exterior of a PGND cable

(1) One-hole OT terminal

(2) Two-hole OT terminal

NOTE

In most cases, the PGND cable is a yellow and green colored cable. When 110 V dual-live-wire power is supplied for BTS3900A (Ver.C) and BTS3900A (Ver.D) cabinets, the PGND cables are green.

Description
The cross-sectional areas and maximum lengths of PGND cables vary according to the types of cabinets. Table 4-16 and Table 4-17 describe PGND cables. Table 4-16 PGND cables for cabinets Base Station Type BTS3900 (Ver.B) and BTS3900L (Ver.B) BTS3900 (Ver.C) and BTS3900L (Ver.C) BTS3900 (Ver.D) and BTS3900L (Ver.D) Cabinet Maximum Length CrossSection al Area 25 mm2 (0.039 in.2) Connect or One-hole OT terminal (M8) Exterior

BTS3900 (Ver.B) 15 m (49.21 and BTS3900L ft) (Ver.B) BTS3900 (Ver.C) and BTS3900L (Ver.C) BTS3900 (Ver.D) and BTS3900L (Ver.D)

The exterior is shown by illustration 1 in the preceding figure.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

185

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

Base Station Type BTS3900A (Ver.B)

Cabinet

Maximum Length 8 m (26.25 ft)

CrossSection al Area 16 mm2 (0.025 in.2)

Connect or One-hole OT terminal (M6)

Exterior

RFC (Ver.B)

The exterior is shown by illustration 1 in the preceding figure. The exterior is shown by illustration 1 in the preceding figure. The exterior is shown by illustration 1 in the preceding figure. The exterior is shown by illustration 1 in the preceding figure.

BTS3900A (Ver.C)

RFC (Ver.C)

8 m (26.25 ft)

25 mm2 (0.039 in.2)

One-hole OT terminal (M6)

BTS3900A (Ver.D)

RFC (Ver.D)

8 m (26.25 ft)

16 mm2 (0.025 in.2)

One-hole OT terminal (M6)

BTS3900A (Ver.D)

IBBS700D and IBBS700T

5 m (16.4 ft)

35 mm2 (0.054 in.2)

The cable has a onehole OT terminal (M6) on the cabinet side and a one-hole OT terminal (M8) on the ground bar side.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

186

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

Base Station Type BTS3900AL (Ver.A)

Cabinet

Maximum Length 8 m (26.25 ft)

CrossSection al Area 35 mm2 (0.054 in.2)

Connect or Select one of the followin g specificat ions based on the onsite situation: l The cable has a twohole OT termi nal (M6) at each end, and the distan ce betwe en the two holes of each twohole OT termi nal is 15.8 mm (0.62 in.). l The cable has a twohole OT termi

Exterior

BTS3900AL (Ver.A)

The exterior is shown by illustration 2 or 3 in the preceding figure.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

187

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

Base Station Type

Cabinet

Maximum Length

CrossSection al Area

Connect or nal (M6) on the cabin et side and a onehole OT termi nal (M6) on the groun d bar side. The distan ce betwe en the two holes of the twohole OT termi nal is 15.8 mm (0.62 in.).

Exterior

IBBS700D and IBBS700T

5 m (16.4 ft)

35 mm2 (0.054 in.2)

The cable has a onehole OT terminal (M6) on the cabinet side and a one-hole OT terminal (M8) on the ground bar side.

The exterior is shown by illustration 1 in the preceding figure.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

188

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

Base Station Type BTS3900C (Ver.C)

Cabinet

Maximum Length 15 m (49.21 ft)

CrossSection al Area 16 mm2 (0.025 in.2)

Connect or One-hole OT terminal (M6)

Exterior

OMB (Ver.C)

The exterior is shown by illustration 1 in the preceding figure. The exterior is shown by illustration 1 in the preceding figure. The exterior is shown by illustration 1 in the preceding figure. The exterior is shown by illustration 1 in the preceding figure.

DBS3900

APM30H (Ver.B) series cabinets

8 m (26.25 ft)

16 mm2 (0.025 in.2)

One-hole OT terminal (M6)

APM30H (Ver.C) series cabinets

8 m (26.25 ft)

25 mm2 (0.039 in.2)

One-hole OT terminal (M6)

APM30H (Ver.D) series cabinets

8 m (26.25 ft)

16 mm2 (0.025 in.2)

One-hole OT terminal (M6)

Table 4-17 PGND cables for components Base Station Type BTS3900 (Ver.B) and BTS3900L (Ver.B) BTS3900 (Ver.C) and BTS3900L (Ver.C) BTS3900 (Ver.D) and BTS3900L (Ver.D) Cabinet Maximum Length 15 m (49.21 ft) CrossSection al Area 6 mm2 (0.009 in.2) Connect or One-hole OT terminal (M4) Exterior

BTS3900 (Ver.B) and BTS3900L (Ver.B) BTS3900 (Ver.C) and BTS3900L (Ver.C) BTS3900 (Ver.D) and BTS3900L (Ver.D)

The exterior is shown by illustratio n 1 in the preceding figure.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

189

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

Base Station Type BTS3900A (Ver.B)

Cabinet

Maximum Length 15 m (49.21 ft)

CrossSection al Area 6 mm2 (0.009 in.2)

Connect or One-hole OT terminal (M4)

Exterior

APM30H (Ver.B) IBBS200D (Ver.B) IBBS200T (Ver.B)

The exterior is shown by illustratio n 1 in the preceding figure. The exterior is shown by illustratio n 1 in the preceding figure. The exterior is shown by illustratio n 1 in the preceding figure.

BTS3900C (Ver.C)

OMB (Ver.C)

15 m (49.21 ft)

6 mm2 (0.009 in.2)

One-hole OT terminal (M6)

BTS3900AL (Ver.A)

BTS3900AL

15 m (49.21 ft)

6 mm2 (0.009 in.2)

One-hole OT terminal (M6)

4.5.4 Equipotential Cable


An equipotential cable connects the PGND terminals of two cabinets. It ensures equipotential bonding between cabinets and safe operation of base stations.

Exterior
The following figure shows the exterior of an equipotential cable.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

190

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

Figure 4-39 Exterior of an equipotential cable

(1) One-hole OT terminal

(2) Two-hole OT terminal

NOTE

In most cases, the equipotential cable is a green and yellow cable. When 110 V dual-live-wire power is supplied for the cabinets used by the BTS3900A (Ver.C) or BTS3900A (Ver.D), the equipotential cable is green.

Description
The following table describes equipotential cables. Table 4-18 Equipotential cables Base Station Type BTS3900 (Ver.B) BTS3900 (Ver.C) BTS3900 (Ver.D) BTS3900A (Ver.B) 16 mm2 (0.025 in.2) Cross-Sectional Area Connect or One-hole OT terminal (M6) at each end Exterior

16 mm2 (0.025 in.2)

The exterior is shown by illustration 1 in the preceding figure.

One-hole OT terminal (M6) at each end

The exterior is shown by illustration 2 in the preceding figure.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

191

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

Base Station Type BTS3900A (Ver.C)

Cross-Sectional Area

Connect or One-hole OT terminal (M6) at each end

Exterior

The cross-sectional areas of cables vary according to the way that cabinets are combined. l 16 mm2 (0.025 in.2) for stacked cabinets l 25 mm2 (0.039 in.2) for side-by-side cabinets

The exterior is shown by illustration 1 in the preceding figure.

BTS3900A (Ver.D)

16 mm2 (0.025 in.2)

One-hole OT terminal (M6) at each end

The exterior is shown by illustration 1 in the preceding figure.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

192

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

Base Station Type BTS3900AL (Ver.A)

Cross-Sectional Area

Connect or l When a BTS39 00AL AC cabinet is combi ned with a BTS39 00AL DC cabinet or an IBBS7 00D/ IBBS7 00T, each end of the cable has a twohole OT termin al (M6), and the distanc e betwee n the two holes of each twohole termin al is 15.8 mm (0.62 in.). l When a

Exterior

The cross-sectional areas of cables vary according to the way that cabinets are combined. l When a BTS3900AL AC cabinet is combined with a BTS3900AL DC cabinet or an IBBS700D/ IBBS700T, the crosssectional area of the cable is 35 mm2 (0.054 in.2) l When a BTS3900AL AC cabinet is combined with a TMC11H (Ver.C), the cross-sectional area of the cable is 25 mm2 (0.039in. 2).

The exterior is shown by illustration 2 or 3 in the preceding figure.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

193

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

Base Station Type

Cross-Sectional Area

Connect or BTS39 00AL AC cabinet is combi ned with a TMC1 1H (Ver.C ), the cable has a twohole OT termin al (M6) on the BTS39 00AL AC cabinet side and a onehole OT termin al (M6) on the TMC1 1H (Ver.C ) side. The distanc e betwee n the two holes of each twohole

Exterior

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

194

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

Base Station Type

Cross-Sectional Area

Connect or termin al is 15.8 mm (0.62 in.).

Exterior

4.5.5 Power Cables


This section describes the exteriors, functions, and pin assignments of the power cables in the IBBS200D.

Storage Battery Power Cable


Storage battery power cables connect storage batteries and the power distribution boxes in battery cabinets. The power cables include groups to wiring copper bars and connect the copper bars between storage batteries.

Storage Battery Power Cables Between Battery Groups and Wiring Copper Bars
The following figure shows the exteriors of the power cables. Figure 4-40 Exteriors of storage battery power cables between battery groups and wiring copper bars

(1) OT terminal (M8)

(2) OT terminal (M6)

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

195

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

The following table describes the storage battery power cables between battery groups and wiring copper bars. Table 4-19 Storage battery power cables between battery groups and wiring copper bars Power Equipment EPU03A-02 or EPU03A-04, EPU05A-02 or EPU05A-04, and ETP48400 Wire RTN (+) NEG (-) Color Red Black Cross-Sectional Area 35 mm2 (0.054 in. 2) Exterior The exterior is shown by illustration 1 in the preceding figure. When the power equipment is EPU05A-02, EPU05A-04, or ETP48400 in UK, the RTN(+) wire is blue and the NEG(-) wire is gray. The exterior is shown by illustration 2 in the preceding figure.

EPS01A or EPS01C

RTN (+) NEG (-)

Red Black

16 mm2 (0.025 in. 2)

Copper Bars Between Storage Batteries


Copper bars are delivered with the storage batteries. The following figure shows the exterior of a copper bar. Figure 4-41 Exterior of a copper bar between storage batteries

Power Cable for a Power Distribution Box


A power cable for a power distribution box connects the power system to the power distribution box in a battery cabinets, which are IBBS200D, IBBS200T, IBBS700D, and IBBS700T, and provide input power to batteries in these cabinets.

Exterior
Power cables for power distribution boxes vary according to the power equipment. The following figure shows the exteriors of the power cables.
Issue 03 (2013-01-15) Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd. 196

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

Figure 4-42 Exteriors of power cables for power distribution boxes

(1) Power series 120 connector (2) OT terminal (M6) (3) Power series 175 connector (4) OT terminal (M8)

Description
The following table describes the power cables for power distribution boxes. Table 4-20 Power cables for power distribution boxes Cabinet Power Equipmen t Wiring Termi nal Color In Most Regio ns Red Black UK Cross-Sectional Area Exterior

IBBS200D (Ver.B)/ IBBS200T (Ver.B)

EPS01A, EPS01B, EPS01C, or EPS01D

RTN(+) NEG(-)

16 mm2 (0.025 in. 2)

The exterior is shown by illustratio n 1 in the preceding figure. The exterior is shown by illustratio
197

IBBS200D (Ver.C)/ IBBS200T (Ver.C)


Issue 03 (2013-01-15)

EPU03A-02 , EPU03A-03 ,

RTN(+)

Red

35 mm2 (0.054 in. 2)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

Cabinet

Power Equipmen t

Wiring Termi nal

Color In Most Regio ns Black UK

Cross-Sectional Area

Exterior

EPU03A-04 , or EPU03A-05

NEG(-)

n 2 in the preceding figure.

IBBS200D (Ver.D)/ IBBS200T (Ver.D)

EPU05A-02 , EPU05A-03 , EPU05A-04 , or EPU05A-05 ETP48400

RTN(+) NEG(-)

Red Black

Blue Gray

35 mm2 (0.054 in. 2), UL3436

The exterior is shown by illustratio n 3 in the preceding figure. The exterior is shown by illustratio n 3 in the preceding figure.

IBBS700D/ IBBS700T

RTN(+) NEG(-)

Red Black

Blue Gray

35 mm2 (0.054 in. 2), UL3436

Power Cable for the Fan in an IBBS200D


The power cables feed power into the fans in an IBBS200D. The power cables include input power cables and power transfer cables.

Input Power Cable for the Fan in an IBBS200D


Exterior The input power cables vary according to the types of IBBS200Ds where the fan mounting frames are installed. The following figure shows the exteriors of the input power cables.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

198

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

Figure 4-43 Exteriors of input power cables for the fan in an IBBS200D

(1) Tool-less female connector (pressfit type)

(2) OT terminal (M4)

(3) EPC4 or EPC6 connector

Description The following table describes the input power cables. Table 4-21 Input power cable for the fan in an IBBS200D Base Station Type Cabinet Wirin g Termi nal RTN (+) NEG(-) BTS3900 A (Ver.C) IBBS200D (Ver.C) RTN (+) NEG(-) BTS3900 A (Ver.D) IBBS200D (Ver.D) RTN (+) NEG(-) Color Most Region s Black Blue Black Blue Black Blue UK CrossSectional Area Exterior

BTS3900 A (Ver.B)

IBBS200D (Ver.B)

Blue Gray Blue Gray

2.5 mm2 (0.004 in.2)

The exterior is shown by illustration 1 in the preceding figure. The exterior is shown by illustration 1 in the preceding figure. The exterior is shown by illustration 2 in the preceding figure.
199

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

Power Transfer Cable for the Fan in an IBBS200D


Exterior Power transfer cables vary according to the types of cabinets where the fan mounting frames are installed. The following figures show the exteriors of power transfer cables. Figure 4-44 Exterior of a power transfer cable for the fan in an IBBS200D

(1) 3V3 connector

(2) OT terminal (M6)

(3) OT terminal (M4)

Description The following table describes the power transfer cables. Table 4-22 Power transfer cables for the fans in IBBS200Ds Base Station Type Cabinet Wire Color Most Regio ns IBBS200D (Ver.B) IBBS200D (Ver.C) RTN (+) Black UK CrossSectional Area Exterior

BTS3900 A (Ver.B) BTS3900 A (Ver.C)


Issue 03 (2013-01-15)

Blue

l OT terminal (M4), 1.5 mm2 (0.002 in. 2)

The exterior is shown in illustration 1 in the above figure.

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

200

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

Base Station Type

Cabinet

Wire

Color Most Regio ns UK

CrossSectional Area

Exterior

NEG (-)

Blue

Gray

l OT terminal (M6), 6 mm2 (0.009 in. 2)

BTS3900 A (Ver.D)

IBBS200D (Ver.D)

RTN (+) NEG (-)

Black Blue

Blue Gray

2.5 mm2 (0.004 in.2)

The exterior is shown in illustration 2 in the above figure.

Power Cable for the Heating Film


A power cable for the heating film connects the AC junction box in an APM30H to the AC junction box for the heating film in an IBBS200D. Then the AC junction box distributes power to the heating film.

Exterior
The following figure shows the exterior of a power cable for the heating film. Figure 4-45 Exterior of a power cable for the heating film

(1) OT terminal (M4) on the APM30H side

(2) OT terminal (M4) on the IBBS200D side

Description
The power cable for the heating film, whose cross-sectional area is 1.5 mm2 (0.002 in.2), is wrapped in a black jacket and has a blue wire and a brown wire.
Issue 03 (2013-01-15) Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd. 201

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description


NOTE

4 IBBS200D Cabinet

The colors and structures of cables delivered by Huawei vary according to countries and regions. If cables are purchased locally, the cables must comply with local rules and regulations.

4.5.6 Signal Cables


This section describes the exteriors, functions, pin assignment of all signal cables in the IBBS200D.

ELU Signal Cable


An electronic label unit (ELU) signal cable transmits the cabinet type to a monitoring board in the cabinet.

Exterior
The following figure shows the exterior of an ELU signal cable. Figure 4-46 Exterior of an ELU signal cable

(1) RJ45 connector

Description
The following table describes an ELU signal cable. Table 4-23 ELU signal cable X1 End X1.1 X1.2 X1.3 X1.6 X1.5 X1.4 X1.7 X1.8
Issue 03 (2013-01-15)

X2 End X2.1 X2.2 X2.3 X2.6 X2.5 X2.4 X2.7 X2.8

Color White Orange White Green White Blue White Brown

Wire Type Twisted pair

Twisted pair

Twisted pair

Twisted pair

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

202

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

Monitoring Signal Cable for the Door Status Sensor


A monitoring signal cable for the door status sensor is used to inform the monitoring board of the door status that is obtained from the door status sensor. Cabinets configured with door status sensors are as follows: APM30H, TMC11H, RFC, IBBS200D, IBBS200T, BTS3900AL, OMB, IBBS700D and IBBS700T.

Exterior
Monitoring signal cables for door status sensors are classified into three types according to the cabinets being monitored. Figure 4-47, Figure 4-48, and Figure 4-49 show their exteriors. Figure 4-47 Exterior of a monitoring signal cable for the door status sensor (1)

Figure 4-48 Exterior of a monitoring signal cable for the door status sensor (2)

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

203

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description


NOTE

4 IBBS200D Cabinet

l Cable 1 has a 2-pin straight socket at one end, which is connected to the HPMI. Cable 1 has a bare wire and a cord end terminal at the other end, which are connected to a door status sensor and a cable terminal block, respectively. l Cable 2 has a bare wire at one end, which is connected to a door status sensor. Cable 2 has a cord end terminal at the other end, which is connected to a cable terminal block. l Cable 3 has a cord end terminal at each end. The two cord end terminals are connected to the two ports on one side of the cable terminal block.

Figure 4-49 Exterior of a monitoring signal cable for the door status sensor (3)

NOTE

l Cable 1 has a 2-pin straight socket at one end, which is connected to the GATE port on the PMU. Cable 1 has a bare wire and a cord end terminal at the other end, which are connected to a door status sensor and a cable terminal block, respectively. l Cable 2 has a bare wire at one end, which is connected to a door status sensor. Cable 2 has a cord end terminal at the other end, which is connected to a cable terminal block. l Cable 3 has a cord end terminal at each end. The two cord end terminals are connected to the two ports on one side of the cable terminal block.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

204

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

Description
Monitoring signal cables for door status sensors are classified into different types according to the monitoring boards to which the door status is reported. The following table lists the monitoring signal cables for door status sensors. Table 4-24 Types of monitoring signal cables for door status sensors Base Station Type BTS3900A (Ver.B) Cabinet Monitoring Board to Which the Door Status Is Reported CMUA Exterior

l RFC (Ver.B) l TMC11H (Ver.B) l IBBS200D (Ver.B) or IBBS200T (Ver.B)

The exterior is shown in Figure 4-47.

BTS3900A (Ver.C)

l RFC (Ver.C) l TMC11H (Ver.C) l IBBS200D (Ver.C) or IBBS200T (Ver.C)

CMUE

BTS3900A (Ver.D)

l RFC (Ver.D) l TMC11H (Ver.D) l IBBS200D (Ver.D) or IBBS200T (Ver.D) l IBBS700D IBBS700T

CMUEA

CMUF CMUA

DBS3900

l TMC11H (Ver.B) l IBBS200D (Ver.B) or IBBS200T (Ver.B) l TMC11H (Ver.C) l IBBS200D (Ver.C) or IBBS200T (Ver.C) l TMC11H (Ver.D) l IBBS200D (Ver.D) or IBBS200T (Ver.D)

CMUE

CMUEA

l BTS3900C l DBS3900
Issue 03 (2013-01-15)

OMB

HEUA

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

205

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

Base Station Type l BTS3900C (Ver.C) l DBS3900 (Ver.C) BTS3900AL (Ver.A)

Cabinet

Monitoring Board to Which the Door Status Is Reported HEUB

Exterior

OMB (Ver.C)

l BTS3900AL (Ver.A) l IBBS700D l IBBS700T

CCU

l BTS3900A (Ver.B) l DBS3900 l BTS3900A (Ver.C) l DBS3900 l BTS3900A (Ver.D) l DBS3900

APM30H (Ver.B)

HPMI

The exterior is shown in Figure 4-48.

APM30H (Ver.C)

HPMI

APM30H (Ver.D)

PMU

The exterior is shown in Figure 4-49.

Monitoring Signal Cable for the Battery Cabinet


A monitoring signal cable for the battery cabinet reports the monitoring signals to the PMU.

Exterior
The following figure shows the exterior of a monitoring signal cable for the battery cabinet. Figure 4-50 Exterior of a monitoring signal cable for the battery cabinet

(1) RJ45 connector

Description
The following table describes a monitoring signal cable for the battery cabinet.
Issue 03 (2013-01-15) Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd. 206

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

4 IBBS200D Cabinet

Table 4-25 Monitoring signal cable for the battery cabinet X1 End X1.1 X1.2 X1.3 X1.6 X1.5 X1.4 X1.7 X1.8 X2 End X2.1 X2.2 X2.3 X2.6 X2.5 X2.4 X2.7 X2.8 Color White Orange White Green White Blue White Brown Twisted pair Twisted pair Twisted pair Wire Type Twisted pair

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

207

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

5
About This Chapter

IBBS200T Cabinet

This chapter describes the IBBS200T cabinet exterior, engineering specifications, application scenarios, as well as boards, modules, and cables in the IBBS200T cabinet. 5.1 Cabinet Exterior The IBBS200T is an outdoor battery cabinet with a TEC. The IBBS200T can provide backup power for the APM30H. 5.2 Cabinet Engineering Specifications This section describes the engineering specifications of the IBBS200T, including the electrical specifications, equipment specifications, and environment specifications. 5.3 Cabinet Interior This section describes the components and boards in the IBBS200T. The power distribution equipment is installed on the upper right wall of the cabinet interior, and the monitoring equipment is installed inside the cabinet door. 5.4 IBBS200T Components This section describes the mandatory and optional components in an IBBS200T. 5.5 IBBS200T Cables The IBBS200T cables consist of the power cables, equipotential cables, PGND cables, and signal cables.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

208

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

5.1 Cabinet Exterior


The IBBS200T is an outdoor battery cabinet with a TEC. The IBBS200T can provide backup power for the APM30H. The housing material of the IBBS200T uses aluminum board. The surface is covered with acrylic orange-figured paint to protect the IBBS200T from the damage caused by the solar radiation, corrosion, moist heat, and mold. The following figure shows the exterior of the IBBS200T. Figure 5-1 Exterior of the IBBS200T

5.2 Cabinet Engineering Specifications


This section describes the engineering specifications of the IBBS200T, including the electrical specifications, equipment specifications, and environment specifications.

Electrical Specifications
The following table lists the electrical specifications of the IBBS200T. Table 5-1 Electrical specifications Item Input voltage range Maximum capacity of the storage batteries Specifications -38.4 V DC to -57 V DC 48 V, 184 Ah

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

209

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

Item Cooling capability

Specifications l When the ambient temperature is equal to or less than 45oC (113oF), the temperature at the air return vent for inner circulation of the cabinet is equal to or less than 35oC (95oF). l When the ambient temperature is equal to 50oC (122oF) or between 45oC (113oF) and 50oC (122oF), the temperature at the air return vent for inner circulation of the cabinet is equal to or less than 45oC (113oF).

Equipment Specifications
The following table lists the equipment specifications of the IBBS200T. Table 5-2 Equipment specifications Item Dimensions (H x W x D) Specifications Cabinet (without the base): 700 mm x 600 mm x 480 mm (27.56 in. x 23.62 in. x 18.90 in.) Base: 200 mm x 600 mm x 434 mm (7.87 in. x 23.62 in. x 17.09 in.) Cabinet weight 45 kg (99.23 lb) The cabinet is configured only with monitoring boards, power distribution box, and cables. The total capacity can expand to 48 V 184 Ah (two 48 V 92 Ah battery packs). Remarks -

Weight of storage batteries

12 V 92 Ah storage battery: 33.5 kg (73.87 lb)


NOTE Storage batteries from different manufacturers have different specifications. The specifications listed above are for the commonly used storage batteries.

Method of installation

It can be installed on the ground. It can be also installed on the TMC11H or APM30H in stack mode.

In stack mode, the IBBS200T must be installed under the TMC11H or APM30H.

Environment Specifications
The IBBS200T can be used outdoors. The following table lists the environment specifications of the IBBS200T.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

210

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

Table 5-3 Environment specifications Paramete r Operating temperatur e Relative humidity Altitude Specifications -20oC to +50oC (-4oF to +122oF) Remarks When the temperature is higher than 50oC (122oF), a sun shield is required. From the altitude of 1800 m (5905.44 ft), the maximum operating temperature drops by 1oC (33.8oF) each time the altitude increases by 220 m (721.78 ft). -

5% RH to 100% RH -60 m to +4000 m (-196.85 ft to +13123.2 ft)

Wind speed Storage temperatur e Dustproof and waterproof Noise

67 m/s -40oC to +70oC (-40oF to +158oF)

IP55

Meeting the ETS 300 753 4.1E standard (rural area)

5.3 Cabinet Interior


This section describes the components and boards in the IBBS200T. The power distribution equipment is installed on the upper right wall of the cabinet interior, and the monitoring equipment is installed inside the cabinet door. To improve the cooling efficiency of the TEC, the coverage of the heat insulation foam must be greater than 75% on the inner side of the IBBS200T. The following figure shows the interior of the IBBS200T.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

211

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

Figure 5-2 Interior of the IBBS200T

The following table describes the components in the IBBS200D. Table 5-4 Components in the IBBS200T N o. Compone nt Option al or Manda tory Max imu m Qua ntit y in a Sin gle Cab inet 1 Remarks

TEC

Mandat ory Mandat ory Mandat ory

The TEC ensures the normal operation of the IBBS200T in high-temperature areas and dissipates heat from the storage batteries. The central monitoring unit type EA (CMUEA) controls temperature, detects Boolean alarm, and identifies the ELU. The electronic label unit (ELU) reports the cabinet type automatically to facilitate troubleshooting.

CMUEA

ELU

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

212

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

N o.

Compone nt

Option al or Manda tory

Max imu m Qua ntit y in a Sin gle Cab inet 8 1

Remarks

4 5

Storage battery Power distributio n box Door status sensor

Mandat ory Mandat ory

The storage batteries provide long-duration backup power for base stations. The power distribution box is installed on the upper right wall of the cabinet interior. It transfers and distributes power to the fan or TEC and storage batteries. The door status sensor monitors the status (open or closed) of the cabinet door.

Mandat ory

NOTE

For the position of the temperature sensor for the storage batteries, see section "Temperature Sensor for the Storage Batteries" in BTS3900A Hardware Description.

5.4 IBBS200T Components


This section describes the mandatory and optional components in an IBBS200T.

5.4.1 TEC
A TEC dissipates heat for the storage batteries and ensures the normal operation of an IBBS200T in high-temperature areas.

Exterior
The following figure shows the exterior of a TEC.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

213

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

Figure 5-3 Exterior of a TEC

(1) Outer air circulation fan

(2) Inner air circulation fan

Function
A TEC performs the following functions: l If there is a sun shield, and the ambient temperature is 500oC (122oF) without solar radiation, the TEC ensures that the temperature is equal to or less than 40oC (104oF) in the cabinet when storage batteries are in float charge and equal to or less than 45oC (113oF) when the storage batteries are in boost charge. If there is no sun shield, and the ambient temperature is 50oC (122oF) with solar radiation of 1120 W/m2, the TEC ensures that the temperature in the cabinet is equal to or less than 45oC (113oF) when storage batteries are in float charge and equal to or less than 50oC (122oF) when the storage batteries are in boost charge. If the ambient temperature is 32oC (89.6oF) and there is no temperature difference between the air intake vent at the hot and cold sides of the TEC, the refrigeration power of the TEC is equal to or more than 190 W10% and the COP is equal to or more than 0.5.

5.4.2 CMUEA
The central monitoring unit type EA (CMUEA) monitors the fans, Heater Assembly Unit, and cabinet temperature. A CMUEA can be used in the AMP30H, RFC, TMC11H, IBBS200D, IBBS200T, or IBBS700D cabinet.

Exterior
The following figure shows the exterior of a CMUEA.
Issue 03 (2013-01-15) Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd. 214

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

Figure 5-4 Exterior of a CMUEA

Ports
The following figure shows the ports on a CMUEA. Figure 5-5 Ports on a CMUEA

The following table lists information about ports on a CMUEA. Table 5-5 Ports on a CMUEA No . (1) (2) (3) (4) (5) (6) (7) Silkscreen on the Panel TEMP2 WATER IFAN4 IFAN3 IFAN2 IFAN1 TEC Connected to the TEC cooler to receive alarms related to the TEC cooler. Description

Reserved port, connected to the temperature sensor. Connected to the water sensor. Connected to the inner air circulation to receive alarms related to the inner air circulation.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

215

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

No . (8)

Silkscreen on the Panel TEMP1

Description

l In an RFC, this port is connected to the temperature sensor at the air intake vent of the cabinet to receive temperature alarms about the RFC. l In an IBBS200D, IBBS200T, IBBS700D, or IBBS700T, this port is connected to the battery temperature sensor to receive alarm signals about the battery temperature.

(9)

COM_OUT

It is an RS485 signal port, which communicates with lower-level cascading ports and reports monitoring information. l In the APM30H, this port is connected to the PMU. l In an RFC, TMC11H, IBBS200D, IBBS200T, IBBS700D, or IBBS700T, this port is connected to a lower-level CMUEA.

(10 )

COM_IN

RS485 signal port for communicating with upper-level cascading ports and reporting monitoring information. l In the APM30H, this port is connected to the BBU. l In the RFC or TMC11H, this port is connected to the BBU or an upper-level CMUEA. l In an IBBS200D, IBBS200T, IBBS700D, or IBBS700T, this port is connected to the PMU or an upper-level CMUEA.

(11 ) (12 ) (13 )

ELU GATE IN0, IN1, and IN2

Port for connecting the ELU to report the cabinet type. Boolean signal port, which is connected to the door status sensor. Boolean signal port. l In the APM30H, RFC, TMC11H, IBBS200D, or IBBS200T, these ports are reserved. l In the IBBS700D or IBBS700T, IN0 is connected to the heater, and IN1 and IN2 are reserved.

(14 )

SMOKE

Boolean signal port. l In the APM30H, RFC, TMC11H, IBBS200D, or IBBS200T, this port is connected to the smoke sensor. l In the IBBS700D or IBBS700T, this port is not involved.

(15 ) (16 ) (17 )

EFAN1 EFAN2 PWR

Connected to the outer air circulation fan to receive its alarm signals.

Power input port providing DC power input for the board.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

216

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

Indicators
The two indicators on the CMUEA panel indicate the status of the CMUEA. The following table describes their meanings. Table 5-6 Indicators on the CMUEA panel Silkscr een RUN Color Green State Blinking (on for 1s and off for 1s) Blinking (on for 0.125s and off for 0.125s) Steady on Steady off ALM Red Steady off Steady on Blinking (on for 1s and off for 1s) Meaning The board is functional and communicating with the BBU properly. The board is functional but fails to communicate with the BBU or the board is not registered. The board is in the power-on self-check status. There is no power supply, or the board is faulty. No alarm is reported. An alarm is generated, and the board must be replaced. An alarm is generated, and the alarm may be caused by an associated board or port fault. Therefore, you need to locate the fault before determining whether to replace the board.

DIP Switch
On the CMUEA, there is a DIP switch J18, which is used to set the working mode of the CMUEA according to the cabinet type. Figure 5-6 shows the position of the DIP switch on the CMUEA. Figure 5-6 Position of DIP switch on a CMUEA

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

217

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

In different types of cabinets, DIP switches on the CMUEA are set in different ways, as shown in Figure 5-7.
NOTE

The white boxes indicate the positions of all bits in the DIP switch.

Figure 5-7 DIP switch setting on the CMUEA in different cabinets

5.4.3 Power Distribution Box


The power distribution box is installed on the upper right inner wall of the cabinet, which controls the two storage battery groups separately and the DC power supply to the fan or TEC.

Exterior
The following figure shows the exterior of a power distribution box. Figure 5-8 Exterior of a power distribution box

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

218

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

Port
The following table describes the ports on a power distribution box. Table 5-7 Ports on the power distribution box No. (1) Silkscreen BAT Meaning Input power cable port for storage batteries Circuit breaker for the upper storage batteries Power output port for a fan or TEC Circuit breaker for the lower storage batteries Input power cable port for storage batteries Power input port for a fan or TEC Description It supports a one-hole OT terminal (M8) installed on a cable with a cross-sectional area of 35 mm2 (0.054 in.2). It controls the power supply to upper storage batteries in the cabinet. The circuit breaker requires 250 A current. It supports EPC4 connectors and requires 30 A current. It controls the power supply to lower storage batteries in the cabinet. The circuit breaker requires 250 A current. It supports a one-hole OT terminal (M8) installed on a cable with a cross-sectional area of 35 mm2 (0.054 in.2). It supports EPC4 connectors and requires 30 A current.

(2)

BAT_SW0

(3)

FAN/ TEC_OUTPU T BAT_SW1

(4)

(5)

BAT

(6)

FAN/ TEC_INPUT

Wire
The following figure shows the input and output power cables for a power distribution box.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

219

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

Figure 5-9 Cables for a power distribution box

(1) RTN(+) cable for upper storage (2) Power transfer cable for a TEC or (3) NEG(-) wire for lower storage batteries fan assembly batteries (4) NEG(-) wire for upper storage batteries (5) RTN(+) wire for lower storage batteries -

5.4.4 Storage Battery


Storage batteries is the store power equipment.
NOTE

Storage batteries from different manufacturers differ in exteriors and technical specifications. In this section, a 12 V 92 Ah storage battery is described as an example.

Exterior
The following figure shows the exterior of a 12 V 92 Ah storage battery.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

220

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

Figure 5-10 Exterior of a 12 V 92 Ah storage battery

Configuration
The IBBS200T and IBBS200D support two types of storage battery groups: 48 V 92 Ah and 48 V 184 Ah. l l Two 48 V 92 Ah storage battery groups are connected in parallel and serve as a 48 V 184 Ah storage battery group. Each group consists of four storage batteries.

Technical Specifications
The following table describes the technical specifications of a 12 V 92 Ah storage battery. Table 5-8 Technical specifications of a 12 V 92 Ah storage battery Storage Battery Type 12 V, 92 Ah Dimensions (H x W x D) 105 mm x 287 mm x 390 mm (11.30 in. x 4.13 in. x 15.35 in.) 108 mm x 287 mm x 393 mm (11.30 in. x 4.25 in. x 15.47 in.) Weight 33.5 kg (73.85 lb)

35 kg (77.16 lb)

5.4.5 ELU
An electronic label unit (ELU) reports the cabinet type automatically to facilitate troubleshooting.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

221

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

Exterior
The following figure shows the exterior of an ELU. Figure 5-11 Exterior of an ELU

(1) Shell

(2) RJ45 port

NOTE

The ELU in a BTS3900 or BTS3900L has no shell.

The board collecting information from the ELU varies according to the cabinet, as listed in the following table. Table 5-9 Monitoring boards to which an ELU reports information Base Station Type BTS3900 (Ver.B) and BTS3900L (Ver.B) BTS3900 (Ver.C) and BTS3900L (Ver.C) BTS3900 (Ver.D) and BTS3900L (Ver.D) BTS3900A (Ver.B) Cabinet Board Collecting Information from the ELU FMUC

BTS3900 (Ver.B) and BTS3900L (Ver.B)

BTS3900 (Ver.C) and BTS3900L (Ver.C)

FMUE

BTS3900 (Ver.D) and BTS3900L (Ver.D)

FMUEA

APM30H (Ver.B), TMC11H (Ver.B), RFC (Ver.B), IBBS200D (Ver.B), and IBBS200T (Ver.B)

CMUA

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

222

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

Base Station Type BTS3900A (Ver.C) BTS3900A (Ver.D)

Cabinet

Board Collecting Information from the ELU CMUE

APM30H (Ver.C), TMC11H (Ver.C), RFC (Ver.C), IBBS200D (Ver.C), and IBBS200T (Ver.C) APM30H (Ver.D), TMC11H(Ver.D), RFC (Ver.D), IBBS200D(Ver.D), IBBS200T (Ver.D), and IBBS700D IBBS700T

CMUEA

CMUF HEUB CCU

BTS3900C (Ver.C) BTS3900AL (Ver.A)

OMB (Ver.C) BTS3900AL (Ver.A), IBBS700D, IBBS700T

Installation Position
Positions of ELUs vary in different cabinets. The following figure shows their positions. Figure 5-12 Position of the ELU in a BTS3900 cabinet

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

223

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

Figure 5-13 Position of the ELU in a BTS3900L cabinet

Figure 5-14 Position of the ELU in an APM30H or IBBS200D cabinet

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

224

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description


NOTE

5 IBBS200T Cabinet

An ELU is located on the right inner wall of the APM30H, TMC11H, or RFC, or on the left inner wall of the IBBS200D or IBBS200T. The preceding figure shows an APM30H and an IBBS200D as an example.

Figure 5-15 Position of the ELU in an OMB

Figure 5-16 Position of the ELU in a BTS3900AL cabinet

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

225

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

Figure 5-17 Position of the ELU in a IBBS700D cabinet

NOTE

In the IBBS700D, when the cabinet is configured with a CCU, the ELU is above the CCU. When the cabinet is not configured with a CCU, the ELU is on the right of the CMUEA.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

226

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

Figure 5-18 Position of the ELU in a IBBS700T cabinet

NOTE

In the IBBS700T, when the cabinet is configured with a CCU, the ELU is above the CCU. When the cabinet is not configured with a CCU, the ELU is on the left of the CMUF.

5.4.6 Door Status Sensor


A door status sensor reports the status (open or closed) of a door. It is installed in any of the following cabinets: BTS3900AL, OMB, OMB (Ver.C), APM30H, RFC, TMC11H, IBBS200D, IBBS200T, IBBS700D, and IBBS700T.

Exterior
A door status sensor consists of a magnet and a switch. The following figures show the exteriors of them.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

227

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

Figure 5-19 Exterior of the magnet of a door status sensor

(1) Magnetic shell

(2) Magnet

The following figure shows the exterior of the switch of a door status sensor. Figure 5-20 Exterior of the switch of a door status sensor

Installation Position
Positions of door status sensors vary in different cabinets. The following figure shows their positions.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

228

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description


NOTE

5 IBBS200T Cabinet

l A door status sensor is installed at the same position in the BTS3900AL (Ver.A), IBBS700D, and IBBS700T. Figure 5-21 uses the BTS3900AL (Ver.A) as an example. l A door status sensor is installed at the same position in the OMB and OMB (Ver.C). Figure 5-22 uses the OMB (Ver.C) as an example. l A door status sensor is installed at the same position in the following cabinets: APM30H (Ver.B), APM30H (Ver.C), APM30H (Ver.D), RFC (Ver.B), RFC (Ver.C), RFC (Ver.D), TMC11H (Ver.B), TMC11H (Ver.C), TMC11H (Ver.D), IBBS200D (Ver.B), IBBS200D (Ver.C), IBBS200D (Ver.D), IBBS200T (Ver.B), IBBS200T (Ver.C), and IBBS200T (Ver.D). Figure 5-23 uses the APM30H (Ver.D) as an example.

Figure 5-21 Position of a door status sensor in the BTS3900AL (Ver.A)

Figure 5-22 Position of a door status sensor in the OMB (Ver.C)

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

229

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

Figure 5-23 Position of a door status sensor in the APM30H (Ver.D)

5.4.7 Temperature Sensor


The temperature sensor monitors the temperature in the cabinet. It is installed in the following cabinets: BTS3900AL, RFC, IBBS200T, IBBS200D, OMB, IBBS700T, and IBBS700D.

Exterior
The following figure shows the exterior of a temperature sensor. Figure 5-24 Exterior of a temperature sensor

(1) Temperature sensor

(2) 4-pin connector

Installation Position
Positions of temperature sensors vary in different cabinets. The following figure shows their positions.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

230

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description


NOTE

5 IBBS200T Cabinet

l A temperature sensor is installed at the same position in the RFC (Ver.B), RFC (Ver.C), and RFC (Ver.D). Figure 5-26 uses the RFC (Ver.D) as an example. l A temperature sensor is installed at the same position in the IBBS200T (Ver.B), IBBS200T (Ver.C), and IBBS200T (Ver.D). Figure 5-27 uses the IBBS200T (Ver.D) as an example. l A temperature sensor is installed at the same position in the IBBS200D (Ver.B), IBBS200D (Ver.C), and IBBS200D (Ver.D). Figure 5-28 uses the IBBS200D (Ver.D) as an example. l A temperature sensor is installed at the same position in the OMB (Ver.C), and OMB. Figure 5-29 uses the OMB (Ver.C) as an example.

Figure 5-25 Position of the temperature sensor in a BTS3900AL (Ver.A) cabinet

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

231

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

Figure 5-26 Position of the temperature sensor in an RFC (Ver.D)

Figure 5-27 Position of the temperature sensor in an IBBS200T (Ver.D)

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

232

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

Figure 5-28 Position of the temperature sensor in an IBBS200D (Ver.D)

Figure 5-29 Position of the temperature sensor in an OMB (Ver.C)

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

233

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

Figure 5-30 Position of the temperature sensor in an IBBS700D

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

234

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

Figure 5-31 Position of the temperature sensor in an IBBS700T

Technical Specifications
The following table lists the technical specifications of a temperature sensor. Table 5-10 Technical specifications of a temperature sensor Counter Operating voltage Temperature measurement range Temperature measurement error Specification 3.0 V DC to 5.5 V DC -55C to +125C (-131 F to +257 F) 2C (35.6F)

5.5 IBBS200T Cables


The IBBS200T cables consist of the power cables, equipotential cables, PGND cables, and signal cables.

5.5.1 Cable List


IBBS200T cables consist of the PGND cables, equipotential cables, power cables, and signal cables.
Issue 03 (2013-01-15) Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd. 235

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

Power Cables, PGND Cables, and Equipotential Cables


Table 5-11 lists the power cables, PGND cables, and equipotential cables. Table 5-11 Power cables, PGND cables, and equipotential cables Classi ficati on Cables to be install ed onsite Cable One End Connector Power Cable for a Power Distribution Box OT terminal Installation Position RTN(+) and NEG(-) terminals on the terminal block for storage batteries on the EPU Copper bar on the power distribution box LOAD8 port on the EPU The Other End Connector OT terminal Installation Position RTN(+) and NEG(-) terminals on the BAT terminal block on the power distribution box in the IBBS200T Storage battery

Storage Battery Power Cable TEC Power Cable

OT terminal

OT terminal

EPC4 or EPC6 connector

EPC4 or EPC6 connector

FAN/ TEC_INPUT port on the power distribution box in the IBBS200T Ground busbar outside the cabinet Ground bar in the lower cabinet -

2.7.3 PGND Cable 2.7.4 Equipotential Cable Cables install ed before deliver y -

OT terminal

Ground bar in the cabinet Ground bar in the upper cabinet -

OT terminal

OT terminal

OT terminal

NOTE

(1) If there are two IBBS200Ts, connects the power cable for the TEC in the second IBBS200T to the power distribution box in the first IBBS200T.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

236

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

Signal Cables
Table 5-12 describes signal cables. Table 5-12 Signal cables Classi ficati on Cables to be install ed onsite Cables install ed before deliver y Cable One End Connecto r Monitoring Signal Cable for the Battery Cabinet ELU Signal Cable Monitoring Signal Cable for the Door Status Sensor RJ45 connector Installation Position COM_IN port on the CMUEA in the IBBS200D or IBBS200T ELU GATE port on the CMUEA The Other End Connect or RJ45 connector Installation Position COM_485 port on the PMU

RJ45 connector 2-pin connector

RJ45 connector Bare wire

ELU port on the CMUEA Door status sensor

5.5.2 Cable Connections


This section describes the principles for connecting power cables and signal cables in the IBBS200T.

Power Cable Connections


This section describes the power cable connections in the IBBS200T. The following figure shows the power cable connections in the IBBS200T.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

237

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

Figure 5-32 Power cable connections in the IBBS200T

(1) Cable between the battery pack and the shortcircuiting copper bar (4) Cable between the battery pack and the shortcircuiting copper bar

(2) TEC Power Cable (3) Storage Battery Power Cable (5) TEC Power Cable -

Monitoring Signal Cable Connections


This section provides reference for onsite installation of monitoring signal cables. Figure 5-33 shows the monitoring signal cable connections in the IBBS200T. Figure 5-33 Monitoring signal cable connections in the IBBS200T

(1) Monitoring signal cable for the battery (2) ELU signal cable (3) Monitoring signal cable for the door cabinet status sensor

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

238

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

5.5.3 PGND Cable


PGND cables ensure that cabinets and internal components are properly grounded and that base stations run properly. PGND cables include classified into PGND cables for cabinets and PGND cables for components.

Exterior
The following figure shows the exterior of a PGND cable. Figure 5-34 Exterior of a PGND cable

(1) One-hole OT terminal

(2) Two-hole OT terminal

NOTE

In most cases, the PGND cable is a yellow and green colored cable. When 110 V dual-live-wire power is supplied for BTS3900A (Ver.C) and BTS3900A (Ver.D) cabinets, the PGND cables are green.

Description
The cross-sectional areas and maximum lengths of PGND cables vary according to the types of cabinets. Table 5-13 and Table 5-14 describe PGND cables.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

239

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

Table 5-13 PGND cables for cabinets Base Station Type BTS3900 (Ver.B) and BTS3900L (Ver.B) BTS3900 (Ver.C) and BTS3900L (Ver.C) BTS3900 (Ver.D) and BTS3900L (Ver.D) BTS3900A (Ver.B) Cabinet Maximum Length CrossSection al Area 25 mm2 (0.039 in.2) Connect or One-hole OT terminal (M8) Exterior

BTS3900 (Ver.B) 15 m (49.21 and BTS3900L ft) (Ver.B) BTS3900 (Ver.C) and BTS3900L (Ver.C) BTS3900 (Ver.D) and BTS3900L (Ver.D) RFC (Ver.B) 8 m (26.25 ft)

The exterior is shown by illustration 1 in the preceding figure.

16 mm2 (0.025 in.2)

One-hole OT terminal (M6)

The exterior is shown by illustration 1 in the preceding figure. The exterior is shown by illustration 1 in the preceding figure. The exterior is shown by illustration 1 in the preceding figure. The exterior is shown by illustration 1 in the preceding figure.

BTS3900A (Ver.C)

RFC (Ver.C)

8 m (26.25 ft)

25 mm2 (0.039 in.2)

One-hole OT terminal (M6)

BTS3900A (Ver.D)

RFC (Ver.D)

8 m (26.25 ft)

16 mm2 (0.025 in.2)

One-hole OT terminal (M6)

BTS3900A (Ver.D)

IBBS700D and IBBS700T

5 m (16.4 ft)

35 mm2 (0.054 in.2)

The cable has a onehole OT terminal (M6) on the cabinet side and a one-hole OT terminal (M8) on the ground bar side.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

240

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

Base Station Type BTS3900AL (Ver.A)

Cabinet

Maximum Length 8 m (26.25 ft)

CrossSection al Area 35 mm2 (0.054 in.2)

Connect or Select one of the followin g specificat ions based on the onsite situation: l The cable has a twohole OT termi nal (M6) at each end, and the distan ce betwe en the two holes of each twohole OT termi nal is 15.8 mm (0.62 in.). l The cable has a twohole OT termi

Exterior

BTS3900AL (Ver.A)

The exterior is shown by illustration 2 or 3 in the preceding figure.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

241

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

Base Station Type

Cabinet

Maximum Length

CrossSection al Area

Connect or nal (M6) on the cabin et side and a onehole OT termi nal (M6) on the groun d bar side. The distan ce betwe en the two holes of the twohole OT termi nal is 15.8 mm (0.62 in.).

Exterior

IBBS700D and IBBS700T

5 m (16.4 ft)

35 mm2 (0.054 in.2)

The cable has a onehole OT terminal (M6) on the cabinet side and a one-hole OT terminal (M8) on the ground bar side.

The exterior is shown by illustration 1 in the preceding figure.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

242

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

Base Station Type BTS3900C (Ver.C)

Cabinet

Maximum Length 15 m (49.21 ft)

CrossSection al Area 16 mm2 (0.025 in.2)

Connect or One-hole OT terminal (M6)

Exterior

OMB (Ver.C)

The exterior is shown by illustration 1 in the preceding figure. The exterior is shown by illustration 1 in the preceding figure. The exterior is shown by illustration 1 in the preceding figure. The exterior is shown by illustration 1 in the preceding figure.

DBS3900

APM30H (Ver.B) series cabinets

8 m (26.25 ft)

16 mm2 (0.025 in.2)

One-hole OT terminal (M6)

APM30H (Ver.C) series cabinets

8 m (26.25 ft)

25 mm2 (0.039 in.2)

One-hole OT terminal (M6)

APM30H (Ver.D) series cabinets

8 m (26.25 ft)

16 mm2 (0.025 in.2)

One-hole OT terminal (M6)

Table 5-14 PGND cables for components Base Station Type BTS3900 (Ver.B) and BTS3900L (Ver.B) BTS3900 (Ver.C) and BTS3900L (Ver.C) BTS3900 (Ver.D) and BTS3900L (Ver.D) Cabinet Maximum Length 15 m (49.21 ft) CrossSection al Area 6 mm2 (0.009 in.2) Connect or One-hole OT terminal (M4) Exterior

BTS3900 (Ver.B) and BTS3900L (Ver.B) BTS3900 (Ver.C) and BTS3900L (Ver.C) BTS3900 (Ver.D) and BTS3900L (Ver.D)

The exterior is shown by illustratio n 1 in the preceding figure.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

243

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

Base Station Type BTS3900A (Ver.B)

Cabinet

Maximum Length 15 m (49.21 ft)

CrossSection al Area 6 mm2 (0.009 in.2)

Connect or One-hole OT terminal (M4)

Exterior

APM30H (Ver.B) IBBS200D (Ver.B) IBBS200T (Ver.B)

The exterior is shown by illustratio n 1 in the preceding figure. The exterior is shown by illustratio n 1 in the preceding figure. The exterior is shown by illustratio n 1 in the preceding figure.

BTS3900C (Ver.C)

OMB (Ver.C)

15 m (49.21 ft)

6 mm2 (0.009 in.2)

One-hole OT terminal (M6)

BTS3900AL (Ver.A)

BTS3900AL

15 m (49.21 ft)

6 mm2 (0.009 in.2)

One-hole OT terminal (M6)

5.5.4 Equipotential Cable


An equipotential cable connects the PGND terminals of two cabinets. It ensures equipotential bonding between cabinets and safe operation of base stations.

Exterior
The following figure shows the exterior of an equipotential cable.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

244

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

Figure 5-35 Exterior of an equipotential cable

(1) One-hole OT terminal

(2) Two-hole OT terminal

NOTE

In most cases, the equipotential cable is a green and yellow cable. When 110 V dual-live-wire power is supplied for the cabinets used by the BTS3900A (Ver.C) or BTS3900A (Ver.D), the equipotential cable is green.

Description
The following table describes equipotential cables. Table 5-15 Equipotential cables Base Station Type BTS3900 (Ver.B) BTS3900 (Ver.C) BTS3900 (Ver.D) BTS3900A (Ver.B) 16 mm2 (0.025 in.2) Cross-Sectional Area Connect or One-hole OT terminal (M6) at each end Exterior

16 mm2 (0.025 in.2)

The exterior is shown by illustration 1 in the preceding figure.

One-hole OT terminal (M6) at each end

The exterior is shown by illustration 2 in the preceding figure.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

245

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

Base Station Type BTS3900A (Ver.C)

Cross-Sectional Area

Connect or One-hole OT terminal (M6) at each end

Exterior

The cross-sectional areas of cables vary according to the way that cabinets are combined. l 16 mm2 (0.025 in.2) for stacked cabinets l 25 mm2 (0.039 in.2) for side-by-side cabinets

The exterior is shown by illustration 1 in the preceding figure.

BTS3900A (Ver.D)

16 mm2 (0.025 in.2)

One-hole OT terminal (M6) at each end

The exterior is shown by illustration 1 in the preceding figure.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

246

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

Base Station Type BTS3900AL (Ver.A)

Cross-Sectional Area

Connect or l When a BTS39 00AL AC cabinet is combi ned with a BTS39 00AL DC cabinet or an IBBS7 00D/ IBBS7 00T, each end of the cable has a twohole OT termin al (M6), and the distanc e betwee n the two holes of each twohole termin al is 15.8 mm (0.62 in.). l When a

Exterior

The cross-sectional areas of cables vary according to the way that cabinets are combined. l When a BTS3900AL AC cabinet is combined with a BTS3900AL DC cabinet or an IBBS700D/ IBBS700T, the crosssectional area of the cable is 35 mm2 (0.054 in.2) l When a BTS3900AL AC cabinet is combined with a TMC11H (Ver.C), the cross-sectional area of the cable is 25 mm2 (0.039in. 2).

The exterior is shown by illustration 2 or 3 in the preceding figure.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

247

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

Base Station Type

Cross-Sectional Area

Connect or BTS39 00AL AC cabinet is combi ned with a TMC1 1H (Ver.C ), the cable has a twohole OT termin al (M6) on the BTS39 00AL AC cabinet side and a onehole OT termin al (M6) on the TMC1 1H (Ver.C ) side. The distanc e betwee n the two holes of each twohole

Exterior

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

248

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

Base Station Type

Cross-Sectional Area

Connect or termin al is 15.8 mm (0.62 in.).

Exterior

5.5.5 Power Cables


This section describes the exteriors, functions, and pin assignments of the power cables in the IBBS200T.

Storage Battery Power Cable


Storage battery power cables connect storage batteries and the power distribution boxes in battery cabinets. The power cables include groups to wiring copper bars and connect the copper bars between storage batteries.

Storage Battery Power Cables Between Battery Groups and Wiring Copper Bars
The following figure shows the exteriors of the power cables. Figure 5-36 Exteriors of storage battery power cables between battery groups and wiring copper bars

(1) OT terminal (M8)

(2) OT terminal (M6)

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

249

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

The following table describes the storage battery power cables between battery groups and wiring copper bars. Table 5-16 Storage battery power cables between battery groups and wiring copper bars Power Equipment EPU03A-02 or EPU03A-04, EPU05A-02 or EPU05A-04, and ETP48400 Wire RTN (+) NEG (-) Color Red Black Cross-Sectional Area 35 mm2 (0.054 in. 2) Exterior The exterior is shown by illustration 1 in the preceding figure. When the power equipment is EPU05A-02, EPU05A-04, or ETP48400 in UK, the RTN(+) wire is blue and the NEG(-) wire is gray. The exterior is shown by illustration 2 in the preceding figure.

EPS01A or EPS01C

RTN (+) NEG (-)

Red Black

16 mm2 (0.025 in. 2)

Copper Bars Between Storage Batteries


Copper bars are delivered with the storage batteries. The following figure shows the exterior of a copper bar. Figure 5-37 Exterior of a copper bar between storage batteries

Power Cable for a Power Distribution Box


A power cable for a power distribution box connects the power system to the power distribution box in a battery cabinets, which are IBBS200D, IBBS200T, IBBS700D, and IBBS700T, and provide input power to batteries in these cabinets.

Exterior
Power cables for power distribution boxes vary according to the power equipment. The following figure shows the exteriors of the power cables.
Issue 03 (2013-01-15) Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd. 250

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

Figure 5-38 Exteriors of power cables for power distribution boxes

(1) Power series 120 connector (2) OT terminal (M6) (3) Power series 175 connector (4) OT terminal (M8)

Description
The following table describes the power cables for power distribution boxes. Table 5-17 Power cables for power distribution boxes Cabinet Power Equipmen t Wiring Termi nal Color In Most Regio ns Red Black UK Cross-Sectional Area Exterior

IBBS200D (Ver.B)/ IBBS200T (Ver.B)

EPS01A, EPS01B, EPS01C, or EPS01D

RTN(+) NEG(-)

16 mm2 (0.025 in. 2)

The exterior is shown by illustratio n 1 in the preceding figure. The exterior is shown by illustratio
251

IBBS200D (Ver.C)/ IBBS200T (Ver.C)


Issue 03 (2013-01-15)

EPU03A-02 , EPU03A-03 ,

RTN(+)

Red

35 mm2 (0.054 in. 2)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

Cabinet

Power Equipmen t

Wiring Termi nal

Color In Most Regio ns Black UK

Cross-Sectional Area

Exterior

EPU03A-04 , or EPU03A-05

NEG(-)

n 2 in the preceding figure.

IBBS200D (Ver.D)/ IBBS200T (Ver.D)

EPU05A-02 , EPU05A-03 , EPU05A-04 , or EPU05A-05 ETP48400

RTN(+) NEG(-)

Red Black

Blue Gray

35 mm2 (0.054 in. 2), UL3436

The exterior is shown by illustratio n 3 in the preceding figure. The exterior is shown by illustratio n 3 in the preceding figure.

IBBS700D/ IBBS700T

RTN(+) NEG(-)

Red Black

Blue Gray

35 mm2 (0.054 in. 2), UL3436

TEC Power Cable


A thermoelectric cooler (TEC) power cable feeds power into a TEC.

TEC Power Cable


Exterior The following figure shows two types of TEC power cables classified by the power equipment.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

252

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

Figure 5-39 Exteriors of TEC power cables

(1) Tool-less female connector (pressfit type)

(2) OT terminal (M4)

(3) EPC4 or EPC6 connector

Description The following table describes TEC power cables. Table 5-18 TEC power cables Power Equipment Wire Color Most Region s RTN(+) NEG(-) RTN(+) NEG(-) Black Blue Black Blue UK CrossSectional Area Exterior

EPS01A or EPS01C and EPU03A-02 or EPU03A-04 EPU05A-02 or EPU05A-04

Blue Gray Blue Gray

2.5 mm2 (0.004 in.2)

The exterior is shown by illustration 1 in the preceding figure. The exterior is shown by illustration 2 in the preceding figure.

TEC Power Transfer Cable


Exterior The following figure shows two types of TEC power transfer cables classified by the power equipment.
Issue 03 (2013-01-15) Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd. 253

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

Figure 5-40 Exteriors of TEC power transfer cables

(1) 3V3 connector

(2) OT terminal (M6)

(3) OT terminal (M4)

Description The following table describes TEC power transfer cables. Table 5-19 TEC power transfer cables Power Equipment Wire Color Most Region s RTN (+) NEG (-) Black Blue UK CrossSectional Area Exterior

EPS 01A or EPS 01C and EPU03A-02 or EPU03A-04

Blue Gray

l OT terminal (M4), 1.5 mm2 (0.002 in.2) l OT terminal (M6), 6 mm2 (0.009 in.2) 2.5 mm2 (0.004 in.2)

The exterior is shown by illustration 1 in the preceding figure.

EPU05A-02 or EPU05A-04

RTN (+) NEG (-)

Black Blue

Blue Gray

The exterior is shown by illustration 2 in the preceding figure.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

254

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

5.5.6 Signal Cables


This section describes the exteriors, functions, pin assignment of all signal cables in the IBBS200T.

ELU Signal Cable


An electronic label unit (ELU) signal cable transmits the cabinet type to a monitoring board in the cabinet.

Exterior
The following figure shows the exterior of an ELU signal cable. Figure 5-41 Exterior of an ELU signal cable

(1) RJ45 connector

Description
The following table describes an ELU signal cable. Table 5-20 ELU signal cable X1 End X1.1 X1.2 X1.3 X1.6 X1.5 X1.4 X1.7 X1.8 X2 End X2.1 X2.2 X2.3 X2.6 X2.5 X2.4 X2.7 X2.8 Color White Orange White Green White Blue White Brown Twisted pair Twisted pair Twisted pair Wire Type Twisted pair

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

255

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

Monitoring Signal Cable for the Door Status Sensor


A monitoring signal cable for the door status sensor is used to inform the monitoring board of the door status that is obtained from the door status sensor. Cabinets configured with door status sensors are as follows: APM30H, TMC11H, RFC, IBBS200D, IBBS200T, BTS3900AL, OMB, IBBS700D and IBBS700T.

Exterior
Monitoring signal cables for door status sensors are classified into three types according to the cabinets being monitored. Figure 5-42, Figure 5-43, and Figure 5-44 show their exteriors. Figure 5-42 Exterior of a monitoring signal cable for the door status sensor (1)

Figure 5-43 Exterior of a monitoring signal cable for the door status sensor (2)

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

256

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description


NOTE

5 IBBS200T Cabinet

l Cable 1 has a 2-pin straight socket at one end, which is connected to the HPMI. Cable 1 has a bare wire and a cord end terminal at the other end, which are connected to a door status sensor and a cable terminal block, respectively. l Cable 2 has a bare wire at one end, which is connected to a door status sensor. Cable 2 has a cord end terminal at the other end, which is connected to a cable terminal block. l Cable 3 has a cord end terminal at each end. The two cord end terminals are connected to the two ports on one side of the cable terminal block.

Figure 5-44 Exterior of a monitoring signal cable for the door status sensor (3)

NOTE

l Cable 1 has a 2-pin straight socket at one end, which is connected to the GATE port on the PMU. Cable 1 has a bare wire and a cord end terminal at the other end, which are connected to a door status sensor and a cable terminal block, respectively. l Cable 2 has a bare wire at one end, which is connected to a door status sensor. Cable 2 has a cord end terminal at the other end, which is connected to a cable terminal block. l Cable 3 has a cord end terminal at each end. The two cord end terminals are connected to the two ports on one side of the cable terminal block.

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

257

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

Description
Monitoring signal cables for door status sensors are classified into different types according to the monitoring boards to which the door status is reported. The following table lists the monitoring signal cables for door status sensors. Table 5-21 Types of monitoring signal cables for door status sensors Base Station Type BTS3900A (Ver.B) Cabinet Monitoring Board to Which the Door Status Is Reported CMUA Exterior

l RFC (Ver.B) l TMC11H (Ver.B) l IBBS200D (Ver.B) or IBBS200T (Ver.B)

The exterior is shown in Figure 5-42.

BTS3900A (Ver.C)

l RFC (Ver.C) l TMC11H (Ver.C) l IBBS200D (Ver.C) or IBBS200T (Ver.C)

CMUE

BTS3900A (Ver.D)

l RFC (Ver.D) l TMC11H (Ver.D) l IBBS200D (Ver.D) or IBBS200T (Ver.D) l IBBS700D IBBS700T

CMUEA

CMUF CMUA

DBS3900

l TMC11H (Ver.B) l IBBS200D (Ver.B) or IBBS200T (Ver.B) l TMC11H (Ver.C) l IBBS200D (Ver.C) or IBBS200T (Ver.C) l TMC11H (Ver.D) l IBBS200D (Ver.D) or IBBS200T (Ver.D)

CMUE

CMUEA

l BTS3900C l DBS3900
Issue 03 (2013-01-15)

OMB

HEUA

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

258

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

Base Station Type l BTS3900C (Ver.C) l DBS3900 (Ver.C) BTS3900AL (Ver.A)

Cabinet

Monitoring Board to Which the Door Status Is Reported HEUB

Exterior

OMB (Ver.C)

l BTS3900AL (Ver.A) l IBBS700D l IBBS700T

CCU

l BTS3900A (Ver.B) l DBS3900 l BTS3900A (Ver.C) l DBS3900 l BTS3900A (Ver.D) l DBS3900

APM30H (Ver.B)

HPMI

The exterior is shown in Figure 5-43.

APM30H (Ver.C)

HPMI

APM30H (Ver.D)

PMU

The exterior is shown in Figure 5-44.

Monitoring Signal Cable for the Battery Cabinet


A monitoring signal cable for the battery cabinet reports the monitoring signals to the PMU.

Exterior
The following figure shows the exterior of a monitoring signal cable for the battery cabinet. Figure 5-45 Exterior of a monitoring signal cable for the battery cabinet

(1) RJ45 connector

Description
The following table describes a monitoring signal cable for the battery cabinet.
Issue 03 (2013-01-15) Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd. 259

APM30H&TMC11H&IBBS200D&IBBS200T (Ver.D) Product Description

5 IBBS200T Cabinet

Table 5-22 Monitoring signal cable for the battery cabinet X1 End X1.1 X1.2 X1.3 X1.6 X1.5 X1.4 X1.7 X1.8 X2 End X2.1 X2.2 X2.3 X2.6 X2.5 X2.4 X2.7 X2.8 Color White Orange White Green White Blue White Brown Twisted pair Twisted pair Twisted pair Wire Type Twisted pair

Issue 03 (2013-01-15)

Huawei Proprietary and Confidential Copyright Huawei Technologies Co., Ltd.

260