By George J. Berbari, Member ASHRAE; Sleiman Shakkour, Member ASHRAE; & Fadi Hashem, Associate Member ASHRAE
making it one of the most challenging places for controlling indoor relative humidity. Around 20% of the total building cooling load and annual energy consumption is used for the treatment of the fresh air supply needed for ventilation. For those reasons, we are always challenged to look for better and more efcient ways to treat the fresh air supply.
In 1993 in a seminar held in the UAE, a cooling coil with runaround coil was presented as one possible solution. Since then the authors have helped introduce thousands of such systems into the local market and demonstrated in practice the effectiveness of this method of controlling the indoor relative humidity.1 Later, we discovered the double heat
34 ASHRAE Journal
recovery unit, which after investigating thoroughly and having been convinced of its merits, introduced one of the rst such system in the Middle East in 1999. Since then, we have promoted the benets of using this method to treat the fresh air and hundreds of units have been installed and specied in our area. The use of this system has resulted not only in improved
ashrae.org
overall efciency but also proved effective for controlling the indoor conditioned space relative humidity. The increased supply of outdoor air needed for ventilation to achieve those acceptable indoor air quality levels recommended in ANSI/ASHRAE Standard 62-1989, Ventilation for Acceptable Indoor Air Quality, signicantly increases the cooling and heating loads that the HVAC equipment needs to handle, resulting in higher initial and operating system costs. To compensate, system designers look for innovative ways to reduce the energy consumption associated with the treatment of the supply of fresh air. An analysis based on a 20-year life
About the Authors George J. Berbari is CEO at DC PRO Engineering in the UAE. Sleiman I. Shakkour is district energy specialist at FVB Energy in Woodbridge, ON, Canada. Fadi Hashem is assistant mechanical engineering manager at DC PRO Engineering in the UAE.
January 2007
cycle for six different types of supply air-handling units was made to evaluate the available system design options to compare the impact of each method of treatment on capital costs and energy costs. This was used to establish the individual system merits for use as a guide when considering options for optimizing performance. This article offers practical design guidelines based on our experience installing and maintaining fresh air makeup systems that include energy recovery.
Six Fresh Air-Handling Units
The six units use different air-to-air energy transfer technologies and are used to precondition outdoor air before it is mixed with return air from the conditioned space (Figure 1). A. Conventional fresh air-handling unit with cooling coil and supply fan. The cooling coil dehumidies the air to a constant 56F (13.3C) dew point, which is equivalent to the desired indoor condition of 76F (24.4C) dry bulb and 50% RH, without reheating it to a neutral dry-bulb temperature. B. Double wheel energy recovery unit with a total recovery wheel and a sensible heat recovery wheel. This unit has two energy transfer stages between adjacent fresh air supply duct and exhaust air duct, with air owing at opposite directions, creating a counterow heat exchange arrangement. In the rst recovery phase, total energy exchange combining both latent and sensible energy transfer is achieved by virtue of a revolving enthalpy wheel (total effectiveness = 80%) having an aluminum backbone structure with a desiccant coating and large internal
January 2007
surface area to transfer moisture and heat between the two airstreams having different temperatures, and vapor pressures as the driving force for energy transfer. During the cooling season, this precools and dehumidies the fresh air prior to entering the main cooling coil, reducing the cooling load demand. The cooling coil dehumidies the air to a constant 56F (13.3C) dew point. Leaving the cooling coil, this dehumidied fresh air enters a second sensible-only wheel (sensible effectiveness = 70%), where it absorbs heat from the exhaust airstream and is reheated to a neutral air condition of 70F (21.1C) dry bulb. During this last stage, by releasing heat to the supply airstream, exhaust air is precooled prior to entering the rst enthalpy wheel, which further enhances cooling the fresh airstream. C. Fresh air-handling unit with total energy wheel and runaround coils. In this unit, a total energy wheel is placed in series with a runaround recovery coils (sensible effectiveness = 70%) placed between supply and exhaust air ducts. A pump circulates water that is used as a sensible energy transfer medium between the airstreams. D. Fresh air-handling unit with total energy wheel and heat pipe coils. In this unit, heat pipe coils (sensible effectiveness = 63%) are placed between the supply and exhaust air ducts using refrigerant as the energy transfer medium, eliminating the need for a circulating pump. E. Fresh air-handling unit with total energy wheel only. In this unit, an enthalpy wheel (total effectiveness = 80%)
ASHRAE Journal 35
A
Fresh Air
B
2 3 Treated Fresh Air 4 Fresh Air
Purge Air 1Prelter 3Cooling Coil 2Bag Filter 4Supply Fan Exhaust Air
Cooling Coil
2 in. Filter
C
Fresh Air
D
Fresh Air Duct Fresh Air
Chilled Water 45F/55F 2 in. Bag Prelter Filter Fresh Air Duct
Exhaust Air
Purge Air
2 in. Filter
Optional Three-Way Valve
Fresh Air-Handling Unit With Total Energy Recovery Wheel and Runaround Coil
Heat Pipe
2 in. Filter
Fresh Air-Handling Unit With Total Energy Recovery Wheel and Heat Pipe
E
Fresh Air Exhaust Air
Chilled Water 45F/55F 2 in. Bag Prelter Filter Supply Air Purge Air Total Energy Recovery Wheel
Optional Variable Speed Control
F
Fresh Air Exhaust Air
Return Air
2 in. Filter
Fresh Air-Handling Unit With Total Energy Wheel And Horseshoe Heat Pipe
is added to precool and dehumidify the air entering the conventional fresh air-handling unit. Again, the cooling coil dehumidies the air to a constant 56F (13.3C) dew point, without reheating it to a neutral dry-bulb temperature. F. Fresh air-handling unit with total energy wheel and a
36 ASHRAE Journal ashrae.org
horseshoe heat pipe wrapped around the main cooling coil. In this arrangement, a precooling heat pipe coil (sensible effectiveness = 54%) is placed at the inlet to the main cooling coil to further precool the on-coil fresh air and reheat heat pipe coil is placed at the outlet to reheat fresh air to the desired condition.
January 2007
Outdoor Conditions Tdb Twb BIN F F Hours 95 94 110.4 106.6 102.1 97.2 92.3 87.5 82.6 75.0 65.7 57.6 49.1 87 Abu-Dhabi 86 76.3 76.7 77.7 78.8 79.1 77.6 73.6 67.2 60.5 54.3 44.2
Dubai
Total Energy Wheel Cooling Coil Supply Exhaust Supply Air Sensible Total Air Outlet Air Inlet Outlet Capacity Capacity Tdb Twb Tdb Twb Tdb Twb Ton Ton F F F F F F 68.6 65.5 68.4 65.2 71.5 62.4 70.8 62.5 69.9 62.8 69.0 63.1 68.1 63.2 67.1 62.8 66.2 61.8 64.7 60.3 62.9 58.9 62.3 62.3 62.3 62.3 62.3 62.3 62.3 62.3 62.3 62.3 62.3 58.5 58.5 58.5 58.5 58.5 58.5 58.5 58.5 58.5 58.5 58.5 56.3 56.3 56.3 56.3 56.3 56.3 56.3 56.3 56.3 56.3 56.3 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 11.6 11.4 14.4 13.7 12.9 12.0 11.1 10.2 9.4 8.0 6.3 25.6 24.7 16.4 16.7 17.5 18.4 18.7 17.5 14.7 10.6 6.8
Sensible Wheel Supply Exhaust Air Outlet Air Inlet Tdb Twb Tdb Twb F F F F 70 70 70 70 70 70 70 70 70 70 70 61.3 61.3 61.3 61.3 61.3 61.3 61.3 61.3 61.3 61.3 61.3 76 76 76 76 76 76 76 76 76 76 76 63.4 63.4 63.4 63.4 63.4 63.4 63.4 63.4 63.4 63.4 63.4
Exhaust Air Outlet Tdb Twb F F 62.3 62.3 62.3 62.3 62.3 62.3 62.3 62.3 62.3 62.3 62.3 58.5 58.5 58.5 58.5 58.5 58.5 58.5 58.5 58.5 58.5 58.5
Total
67,026 114,193
Table 1a: Double wheel heat recovery with total energy wheel and sensible energy wheel (10,000 cfm supply/exhaust model).
Outdoor Conditions Tdb F 95 Total Energy Wheel Supply Air Outlet Tdb Twb F F 79.6 69.0 82.6 81.9 81.0 80.1 79.1 78.2 77.3 75.8 74.0 66.2 66.2 66.5 66.8 66.9 66.5 65.5 63.9 62.8 Horseshoe Heat Pipe Cooling Coil Horseshoe Heat Pipe (Precooling) (Reheating) Exhaust Air Supply Air Supply Air Supply Air Outlet Outlet Outlet Sensible Total Outlet Tdb Twb Tdb Twb Tdb Twb Capacity Capacity Tdb Twb F F F F F F Btu/h Btu/h F F 76.0 63.4 67.1 65.3 56.3 56.1 116,640 284,800 68.7 60.3 76.0 76.0 76.0 76.0 76.0 76.0 76.0 76.0 76.0 63.4 63.4 63.4 63.4 63.4 63.4 63.4 63.4 63.4 68.5 68.1 67.6 67.2 66.7 66.3 65.6 64.5 64.6 61.3 61.3 61.8 62.4 62.7 62.6 61.5 60.2 59.5 56.3 56.3 56.3 56.3 56.3 56.3 56.3 56.3 56.3 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 56.1 131,760 127,440 122,040 117,720 112,320 108,000 100,440 88,560 89,424 151,300 151,300 169,100 186,900 195,800 195,800 160,200 120,150 97,900 70.4 70.1 69.7 69.2 68.7 68.2 68 66.8 65.8 60.8 60.8 60.4 60.2 60 59.9 60 59.5 59.2
Twb BIN F Hours 87 33 91 333 687 992 1,375 1,203 2,061 1,712 279 1 8,767
110.4 76.3 106.6 76.7 102.1 77.7 97.2 78.8 92.3 79.1 87.5 77.6 82.6 73.6 75.0 67.2 65.7 60.5 57.6 54.3 49.1 44.2 Total
Table 1b: Total energy wheel with horseshoe arrangement (10,000 cfm supply/exhaust model).
To compare these units and decide which is the most advantageous to use, it is necessary to consider the cost of the equipment and its impact on the associated chiller plant cost, and the annual energy consumption cost. For this purpose, a 10,000 cfm (4720 L/s) model was chosen for comparison, and it was assumed that the fan brings this amount of outdoor air for 24 hours/day, every day of the year. Different selections and quotations were obtained from various major manufacturers.
38 ASHRAE Journal
Based on these selections, and by computing the air conditions at different sections of each unit, the annual cooling energy and electrical energy consumption were calculated using the Abu Dhabi bin hour data that were computed using weather data covering a span of 10 years, which were provided by the Abu Dhabi Ministry of CommunicationsMeteorological Department for the period 19851994. Tables 1a and 1b show an example of a calculation for the cooling energy demand of the double-wheel energy recovery unit and
January 2007
ashrae.org
Equipment Outdoor Air Handling Unit Total Energy Recovery Only Total Energy Wheel With Horseshoe Heat Pipe Double Wheel Energy Recovery Energy Recovery With Runaround Coil (1.6 m/s Face Velocity) Energy Recovery With Runaround Coil (2.6 m/s Face Velocity) Energy Recovery With Heat Pipe Coil (1.6 m/s Face Velocity) Energy Recovery With Heat Pipe Coil (2.6 m/s Face Velocity) Double Wheel Energy Recovery (Exhaust = 90% Supply Fresh Air) Total Energy Wheel With Horseshoe Heat Pipe (Exhaust = 90% Supply Fresh Air)
9.12
80,000
7.69
67,444
5,092
152,537
Notes: Purge air is included. Fan static pressure includes pressure drop in wheels, cooling coil, runaround coils, heat pipe coils, lters and external pressure drop.
total energy wheel with horseshoe arrangement. Design conditions are shown in the rst row according to ASHRAE climatic design conditions. Air conditions are obtained at each section of the unit, and the total annual cooling energy consumption was determined in that manner. It is assumed that the unit is cycled off when the ambient temperature drops below that required for indoor comfort conditions in accordance with ANSI/ASHRAE Standard 55-1992, Thermal Environmental Conditions for Human Occupancy, at 76F (24.4C) and 50% RH. Electrical energy was calculated taking into account the power consumption of the supply fan, the exhaust fan, the runaround pump, and the total energy and sensible wheels energy. Total energy was calculated based on the operating hours for each unit. Table 2 shows a summary for the electrical energy consumption calculation. Two cases were considered for the dual energy recovery units with runaround coils and heat pipe options: 1. Face velocity through the coils 315 fpm (1.6 m/s); and 2. Face velocity through the coils 510 fpm (2.6 m/s). Because of the large size of the energy wheel, enough crosssectional area is available for the coils, which helps reduce the face velocity and consequently the energy consumption of the fan, but for the cost of a bigger coil. Thus, these two options were considered to study the feasibility of increasing the coils size for reducing energy consumed. Table 3 shows a summary of results for the cooling coil design load, annual cooling energy and electrical energy required for each unit.
January 2007
Table 4 shows a comparison between the units considered. For comparison, the cost of the air-cooled chiller plant being considered was estimated at $1,200/ton ($341/kW), including civil, mechanical, electrical, and utility connection costs. The equipment costs were obtained from manufacturers quotations. Electrical consumption was assumed to be 1.7 kW/ton (6 kW/ kW) for the total chilled water plant (including chillers, pumps and auxiliaries). The electric power cost was determined based on a at rate of $0.0543/kWh. The total capital and operating costs were calculated, for a 20-year period. The net present value was determined using an 11.75% discount rate. As shown on Table 4, the fresh air-handling unit resulted in the highest life-cycle cost. This value was reduced by 58% when the total energy wheel with the horseshoe heat pipe arrangement was used, which resulted in the lowest life-cycle cost. However, the drawback when using this unit is the difculty of controlling the temperature and moisture content of the supply air, which will vary depending on the ambient conditions. The life-cycle cost of the system with the dual energy recovery unit, compared closely with that having the lowest lifecycle cost, but having the added advantage of supplying air at constant temperature and humidity levels year-round regardless of the outdoor conditions. This results in a better control of the indoor humidity levels. The higher coil face velocity resulted in an increase of the life-cycle cost by about 8%. This lead into concluding that exceeding a coil face velocity of 400 fpm (2 m/s) is not recommended.
ASHRAE Journal 39
Design FAHU Coil Total Coil Additional Additional AHU Electric Condition Cooling Capacity Cooling Energy Cooling Effect Cooling Effect Power & Exhaust Equipment Fan Power db/wb, F Tons Ton-Hours/Year Tons Ton-Hours/Year kWh/Year Fresh Air Handling Unit Total Energy Wheel With Horseshoe Heat Pipe Double Heat Recovery AHUs Double Wheel Energy Recovery Total Energy Wheel And Runaround Coil (1.6 m/s Face Velocity) Total Energy Wheel And Runaround Coil (2.6 m/s Face Velocity) Total Energy Wheel And Heat Pipe (1.6 m/s Face Velocity) Total Energy Wheel And Heat Pipe (2.6 m/s Face Velocity) Double Wheel Energy Recovery (Exhaust = 90% Supply Fresh Air) Total Energy Wheel With Horseshoe Heat Pipe (Exhaust = 90% Supply Fresh Air) 95/87 101.0 34.6 23.7 25.6 25.3 362,139 195,220 106,243 114,193 116,385 18 18 7 5 6 150,480 150,480 64,357 45,831 54,234 90,079 125,413 146,060 155,244 150,197 Total Energy Wheel Only Recovery 95/87 95/87 95/87 95/87
95/87
26.2
124,014
63,858
182,521
95/87
24.7
111,299
44,609
152,537
7 5 6
Notes: All above AHUs have a chilled water coil for cooling and dehumidication. Additional cooling effect is measured as: 1.08cfm(76FTs,o)/12,000 where Ts,o is the supply temperature entering the space.
We noticed that Unit A (conventional fresh air-handling unit) and Unit E (fresh air-handling unit with total-energy wheel only) both dehumidify the outdoor air to the same dew point as the other systems, but they deliver it cold56.3F (13.5C) dry bulbrather than reheating it to a neutral 70F (21.1C). In these two systems, this cold air is able to offset a portion of the space sensible cooling loads. However, many designers dont take into consideration the cooling effect for sizing the secondary (local) HVAC systems nor is it used to reduce the chilling plant size. In this case, it has no impact on the capital cost. In off peak hours, when the room temperature condition is satised and the secondary system is turned off, this cool, conditioned outdoor air may overcool the space. At such time, the dehumidied outdoor air should be reheated or the local HVAC equipment needs to add heat to avoid overcooling the space. For this analysis, we decided to list the cooling energy in the tables but to ignore its impact. The reader may choose otherwise.
Recommendations
capital costs can be used (supply temperature was found to vary between 66F and 70F [18.9C to 21.1C] and RH between 59% and 67%). The recommended spacing between the heat pipe coils is 4.6 ft (1.4 m) for easier cooling coils maintenance, although this leads to having a slightly longer unit. Double energy recovery systems resulted in a better humidity control with a constant fresh air supply temperature and RH year-round regardless of fresh ambient conditions (70F [21C] and 61% RH). Although costs are higher, they are recommended for use when constant supply temperature and humidity are necessary. Of course, the results of the analysis may differ with climate, operating hours, utility costs, and installed costs.
Design Guide for Fresh Air-Handling Unit
Based on the results and assumptions of this specic analysis: When no need exists for a constant supply temperature and RH, the total energy wheel with a horseshoe heat pipe arrangement with the lowest energy consumption costs and
40 ASHRAE Journal
The following are summarized design parameters recommended based on the preceding analysis and our experience installing and maintaining these systems. Total energy or sensible wheel to have a maximum air face velocity of 600 fpm (3 m/s). This limits the pressure drop, blower power and cross leakage to modest levels. Heat pipe and runaround coil to have a maximum air face velocity of 400 fpm (2 m/s):
January 2007
ashrae.org
Equipment Outdoor AHU Total Energy Wheel Only Recovery Total Energy Wheel With Horseshoe Heat Pipe Double Wheel Energy Recovery Total Energy Wheel And Runaround Coil (1.6 m/s Face Velocity) Total Energy Wheel And Runaround Coil (2.6 m/s Face Velocity) Total Energy Wheel And Heat Pipe (1.6 m/s Face Velocity) Total Energy Wheel And Heat Pipe (2.6 m/s Face Velocity) Double Wheel Energy Recovery (Exhaust = 90% Supply Fresh Air) Total Energy Wheel With Horseshoe Heat Pipe (Exhaust = 90% Supply Fresh Air)
Outdoor Air AHU & Exhaust Fan Capital Cost $15,076 $20,000 $27,717
Double Heat Recovery AHUs 25.6 25.3 $30,720 $30,312 $26,902 $27,717 $57,622 $58,029 $18,988 $18,916 $180,493 $180,370
26.2
$31,392
$26,087
$57,479
$21,377
$196,593
24.7
$29,592
$33,424
$63,016
$18,573
$182,505
Notes: Total consumption assumed is 1.7 kW/ton. Electricity cost considered is U.S. 5.43 cents/kWh. Air cooled chiller plant is based on $1,200/ton including mechanical, electrical, civil and utility connections works. Discount rate for net present value calculation = 11.75%.
As the area dened by the wheel allows larger rectangular coil area; Heat pipe and runaround coils typically have lower effectiveness than sensible wheel at same face velocity, for runaround coil or heat pipe (typically eight rows or less); and Life-cycle analysis justies use of lower face velocity. Wheels and heat pipes should be tested and rated according to the following: ANSI/ARI Standard 1060-2001, Performance Rating of Air-to-Air Heat Exchangers for Energy Recovery Ventilation Equipment; and ANSI/ASHRAE 84-1991, Method of Testing Air-to-Air Heat Exchangers. Recommended maximum air duct velocity to be 1,200 fpm (6 m/s) and total external air static pressure drop should not exceed 1.5 in. w.g. (380 Pa) for each of the fresh air and exhaust air ductwork. It is recommended to use the static regain method for duct sizing. Recommended maintenance spacing between wheel, coils, heat pipe and fans is 1.7 ft to 2 ft (500 to 600 mm). The energy wheel edges should be protected with an epoxy coating (or equivalent) to eliminate edge corrosion. Proper ltration should be provided at the fresh air intake
of the wheel as well as the exhaust air intake for proper wheel operation and for reducing the need for frequent cleaning and maintenance. The wheel purge system should be eld adjusted to get the design purge air based on actual eld differential air pressure between fresh air and exhaust airstream. The consultant or designer should specify air pressure taps extended to the units outer panel to allow measurement of differential air pressure between upstream fresh air and upstream exhaust air of the wheel. An optional speed detector with alarm function and interface to the building management system is recommended to guard against motor or belt failure.
Controls for Fresh Air-Handling Unit
Necessary Controls
It is necessary to control the leaving air temperature from the cooling coil to a dry-bulb temperature of 56.3F (13.5C), which corresponds to the absolute humidity level of the comfort indoor condition of 76F (24.4C) and 50% RH. Fresh air fan motors start/stop, exhaust air fan start/stop , total energy wheel motor start/stop, sensible wheel motor start/stop or runaround pump start/stop with necessary
ASHRAE Journal 41
January 2007
electric protection and allowance for local as well as remote controls and communication. Ambient dew point (or grains transmitter) sensor to shut off the cooling coil motorized valve and enthalpy wheel motor when the ambient dew point is below 56F (13.3C).
Optional Control
Should the occasional need arise to control the nal leaving supply fresh air temperature (which, if the component is properly selected, should be achieved automatically), then the consultant or designer can opt to control the capacity via a variable speed drive of the sensible wheel motor, a solenoid valve for the heat pipe and a three-way bypass valve at the runaround coil. Variable speed drives for both fresh air and exhaust air can be adopted for variable occupancy applications such as ofce buildings, theaters, conference rooms, sport arenas, restaurants and others that are possible to control via CO2 sensors located in the exhaust air ducts.
Installation and Maintenance
tion to minimize leakage rate to a range of 0.05% to 0.2%. Seals require eld adjustment. Wheel media cleaning can be done annually using vacuum or pressurized air (hot water is accepted by some manufacturers). The wheel is designed for laminar ow and resists plugging and accumulation of dust particles because of the back-ushing done by the incoming and outgoing of airstreams, which help minimize the need for frequent wheel cleaning. Other wheel components requiring routine maintenance involve bearing lubrication, motor and gear reducer lubrication, verifying bearing bolt and sheave tightness, belt condition, rotor runout and atness, media tightness, etc. Coils and heat pipe require minimum maintenance such as scheduled cleaning and runaround pump maintenance.
References
1. Berbari, G.J. 1998. Fresh air treatment in hot and humid climates. ASHRAE Journal 40(10):6470.
Adjust the purge to actual site conditions. Multipass labyrinth seals or adjustable brush seals are important elements for effective and efcient wheel opera-
Bibliography
2001 ASHRAE HandbookFundamentals. Selection and Pricing Software from SEMCO Inc. Heat Pipe and SPC Inc. and Bry-Air.