You are on page 1of 5

Direct-On-Line Starter

Short-circuit protection device type Rated short-circuit current Iq (kA) Coordination type Rated power - 400 V - 50 Hz - AC3 (kW) Rated Current Ie - 400V - AC3 (A) Manual Motor Starter 16.0 1 0.75 1.9

Manual Motor Starter MS116-2,50 1SAM250000R1007 1

Connection kit BEA 16/116 1SBN081406R1000 1

Contactor A9-30-10 1SBL141001R8810 1

As part of its on-going improvement, ABB reserves the right to modify the characteristics or the products described in the following document. The information given is not-contractual. For further details, please contact the ABB company marketing of these products in your country.

I>

Direct-On-Line Starters Open Type Version, in Kit Form


Protected by Manual Motor Starter

MS...

MS...

BEA...

BEA...

A9 ... A26 A30 ... A110

Selection Table
Manual motor starters MS 116 MS 325 MS 450 MS 495

3-pole a.c. operated contactors A9 A12 A16 A26 A9 A12 A16 A26 A30 A40 A30 A40 A50 A63 A75 A95 A110

Connecting links BEA 16/116 BEA 26/116 BEA 16/325 BEA 26/325 BEA 40/450 BEA 50/450 BEA 75/495 BEA 110/495

Mounting plate Not required PM 26-13 Not required PM 26-13

10
1SBC101001C0202

I>

Direct-On-Line Starters Open Type Version, in Kit Form


Protected by Manual Motor Starter
Application
Direct-on-line starters for controlling three-phase asynchronous motors: up to an operational voltage of 415V - 50 or 60 Hz for a starting time of 1.5 s max. and a switching frequency of < 15 starts an hour with a load factor of 80% < 30 starts an hour with a load factor of 50% with an ambient temperature near the devices < 50C type 1 or type 2 coordination, complying with IEC 60947-4-1 / EN 60947-4-1

Coordination
1SBC5 8294 5F0301

In the event of a short-circuit, the starter is subjected to thermal stresses, in addition to very high electrodynamic stresses, proportional to short-current time. The capacity to withstand these high stresses depands upon the perfect coordination of the devices which make up the starter. The contactor and the manual motor starter control and protect motors against overload and short-circuits according to coordination types 1 and 2 defining the anticipated level of service continuity (Standard EN 60947-4-1 / IEC 60947-4-1). The tables overleaf show, for each of the two coordination types, the most usual combination between the MS manual motor starters and the contactors, according to AC-3 currents and motor powers for: coordination type 1 and type 2 at 400 V, 50 / 60 Hz, Iq = 16 kA coordination type 1 and type 2 at 400 V, 50 / 60 Hz, Iq = 50 kA.

MS 116 + BEA 16/116 + A 9-30-10

Mounting and Connection Accessory Description


The BEA.. insulated 3-pole connecting link (touch safe) is used to electrically and mechanically connect the MS.. manual motor starter and the A... serie contactor. This accessory eliminates the potential risk of wiring errors, reduces the time required to install, to test and to maintain a Direct-On-Line starter. The PM26-13 mounting plate facilitates: - the mounting and the dismounting of a A 26-30-.. up to A 40-30-.. contactor and its associated manual motor starter with the use of a BEA26/.. connecting link - the simple snap fitting of the starter onto standard 35 mm rails within the control panel, or screw fitting onto the mounting plate.

11
1SBC101001C0202

I>

Direct-On-Line Starters Open Type Version in Kit Form


Protection by Manual Motor Starter

Wiring Diagrams

1/L1

3/L2

5/L3

KM1 : 5/L3 Us 13 13 21

KM1 : 5/L3 Us 13 Q1 14 14 I KM1 14 KM1 Us N KM1 : 3/L2 A2


E3026D

Q1 14 22 Q1

I> 2/T1

I> 4/T2

I> 6/T3 O

1/L1

3/L2

5/L3

13

A1

13

2/T1

4/T2

6/T3

A2

14

A1

A2

3
Power Circuit

Remote Control

Local Control

22
1SBC101001C0202

E3027D

KM1 Us N KM1 : 3/L2

A1

U1 V1 W1

E3025D

14

KM1

KM1

13

I>

A 9 ... A 26 3-pole Contactors Protected by Manual Motor Starter


Direct-On-Line Starter

Dimensions (in mm)


85.6
45

75.5

80.1

17.5
6

4.5

70

40

10

54

62

10

25

45

35 mm EN/IEC 60715

35 mm EN/IEC 60715

43

15 10

180

177

10

180

15

E2083D

4.5

35

4.5

10

A 9, A 12, A 16 contactors + BEA 16/116 + MS 116

A 9, A 12, A 16 contactors + BEA 16/325 + MS 325


96 91

106 101

40

25

20

15

10

E2090D

44

5.5

E2084D

44

E2089D

E2082D

10

35 mm EN/IEC 60715

15
225

35 mm EN/IEC 60715

15 10

10

225

125

39.4

10

E2665D

54

7.7
E2664D

A 26 contactor + BEA 26/116 + MS 116 + PM 26-13


4.5 4 x 4.2
7.3

113

A 26 contactor + BEA 26/325 + MS 325 + PM 26-13

113

4.5

2 x 7.2

215

45

A 26 contactor + BEA.. + MS.. + PM 26-13 Drilling plan 24


1SBC101001C0202

E2660D

E2666D

107

107

10

54

E2667D

39.4
7.7

125

You might also like