DUCT CONSTRUCTION CHART WITH TIE ROD REINFORCEMENT 5' COILS LENGTHS, GALVANIZED
MECHANICAL GROUP

1" PRESSURE CLASS (+/-)


REINFORCEMENT/JOINTS
GAUGE SMACNA REINF CODE REINF/ JOINT SPACING (INCHES) 59 LONG SIDE REINF/JOINT TYPE (SMACNA CODE) FLAT S (T-5) SHORT SIDE REINF/JOINT TYPE (SMACNA CODE) FLAT D (T-1) LONGITUDINAL JOINTS (SMACNA CODE)
REMARKS

DUCT SIZES
MAX LONG SIDE (IN) 14 MAX SHORT SIDE (IN) 14

24

NONE

5/8" SNAPLOCK (L-2)

SEE 2" PRESSURE CLASS CHARTS FOR SIZES LARGER THAN 14"

AS AN ALTERNATE TO FOLLOWING THE 2" PRESSURE CLASS CHART FOR DUCT DIMENSIONS GREATER THAN 14", THE FOLLOWING 1" CHART CAN BE USED.

DUCT SIZES
MAX LONG SIDE (IN) 36 36 48 54 60 72 84 96 120 OVER 120 MAX SHORT SIDE (IN) 14 18 48 54 60 72 84 96 120 OVER 120 GAUGE SMACNA REINF CODE REINF/ JOINT SPACING (INCHES)
59 56 1/4

REINFORCEMENT/JOINTS
LONG SIDE REINF/JOINT TYPE (SMACNA CODE) STANDING S (T-11) TDC (T-25A) TDC (T-25A) TDC (T-25A) TDC (T-25A) TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T SHORT SIDE REINF/JOINT TYPE (SMACNA CODE) FLAT D (T-1) TDC (T-25A) TDC (T-25A) TDC (T-25A) TDC (T-25A) TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T LONGITUDINAL JOINTS (SMACNA CODE)
REMARKS

24 22

D D

5/8" SNAPLOCK (L-2) 5/8" LARGE PITTSBURGH (L-1)

D (T-11): 1x20 GA

22 22 22 22 20 20 18 18

F F G G G H I It

56 1/4 56 1/4 56 1/4 56 1/4 56 1/4 56 1/4 56 1/4 JOINT 30" REINF 56 1/4 JOINT 30" REINF

5/8" LARGE PITTSBURGH (L-1) 5/8" LARGE PITTSBURGH (L-1) 5/8" LARGE PITTSBURGH (L-1) 5/8" LARGE PITTSBURGH (L-1) 5/8" LARGE PITTSBURGH (L-1) 5/8" LARGE PITTSBURGH (L-1) 5/8" LARGE PITTSBURGH (L-1) 5/8" LARGE PITTSBURGH (L-1)

4-CORNER STIFFENERS
4-CORNER STIFFENERS 1 MPT/ 1 JTR, 4-CORNER STIFFENERS 1 MPT/ 1 JTR, 4-CORNER STIFFENERS 2 MPT/1 JTR, 4-CORNER STIFFENERS 1 JTR/ 2x2x1/4 ANGLE AT 30" MIDSPAN WITH ENDS TIED MPT SPACED AT 5'-0" MAX SPACING WITH 2x2x1/4 ANGLE WRAP/ JTR SPACED AT 5'-0" MAX SPACING (SEE SMACNA FIGURE 2-13)

SPECIFIC NOTES TO CHART: 1. LETTER AND NUMBER IN PARENTHESIS REFERS TO SMACNA CLASSIFICATION. 2. DUCT MATERIAL SHALL BE G-90 COATED GALVANIZED STEEL PER ASTM A653, ASTM A924. 3. REINFORCEMENT SPACING REFERS TO JOINT-TO-JOINT, JOINT-TOINTERMEDIATE, OR INTERMEDIATE-TO-INTERMEDIATE. 4. THE SAME SHEET GAUGE MUST BE USED ON ALL SIDES OF DUCT. EACH DUCT DIMENSION, WIDTH, OR DEPTH, CONTROLS THE MINIMUM REINFORCEMENT REQUIREMENTS FOR THAT SIDE. 5. ALL DUCTWORK 13" WIDTH AND GREATER REGARDLESS OF LENGTH SHALL BE BEADED. 6. ALL DUCTWORK TRANSVERSE JOINTS, AND DUCT WALL PENETRATIONS SHALL BE SEALED PER SMACNA STANDARDS. SEALANT SHALL BE UNITED DUCT SEALER OR APPROVED EQUAL.

ABBREVIATIONS: FLAT D: FLAT DRIVE FLAT S: FLAT SLIP STANDING S: STANDING SLIP 3/4" T: 3/4" TIE-ROD REINFORCEMENT REQUIRED JTR: JOINT TIE ROD MPT: MID POINT TIE ROD GA: GAUGE ALT: IN SOME CASES THE FIELD MAY PREFER TO USE THE ALTERNATE JOINT CONSTRUCTION AS CONDITIONS ARISE. THESE ALTERNATES MEET OR EXCEED SMACNA STANDARDS

7. ALL TDC CONNECTIONS SHALL BE SEALED WITH 3/4" X 3/16" THICK TAPE TYPE GASKETING (BUTYLE NO. 797) W/ONE SIDE ADHESIVE BACKING AND PAINTED WITH DUCT SEALER OR CAULKING MATERIAL AT ALL CORNERS. 8. FOR SIZES NOT LISTED PLEASE CALL THE SHOP.

GENERAL NOTES: 1. DUCT CONSTRUCTION STANDARDS ARE BASED ON SMACNA 3RD EDITION- 2005 2. LETTER AND NUMBER IN PARENTHESIS REFERS TO SMACNA CLASSIFICATION.

REVISED 12.21.2009

DUCT CONSTRUCTION CHART WITH TIE ROD REINFORCEMENT 5' COIL LENGTHS, GALVANIZED
MECHANICAL GROUP

2" PRESSURE CLASS (+/-)


REINFORCEMENT/JOINTS
GAUGE SMACNA REINF CODE REINF/ JOINT SPACING (INCHES) 59 59 59 56 1/4 56 1/4 56 1/4 56 1/4 56 1/4 56 1/4 56 1/4 56 1/4 JOINT 30" REINF 56 1/4 JOINT 30" REINF LONG SIDE REINF/JOINT TYPE (SMACNA CODE) FLAT S (T-5) STANDING S (T-11) STANDING S (T-11) TDC (T-25A) TDC (T-25A) TDC (T-25A) TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T SHORT SIDE REINF/JOINT TYPE (SMACNA CODE) FLAT D (T-1) FLAT D (T-1) FLAT D (T-1) TDC (T-25A) TDC (T-25A) TDC (T-25A) TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T LONGITUDINAL JOINTS (SMACNA CODE)
REMARKS

DUCT SIZES
MAX LONG SIDE (IN) 12 26 26 42 48 54 60 72 84 96 120 MAX SHORT SIDE (IN) 12 12 14 42 48 54 60 72 84 96 120

24 24 22 20 20 20 20 18 18* 18* 18

NONE D D G G G G H I I K

5/8" SNAPLOCK (L-2) 5/8" SNAPLOCK (L-2) 5/8" SNAPLOCK (L-2) 5/8" LARGE PITTSBURGH (L-1) 5/8" LARGE PITTSBURGH (L-1)
4-CORNER STIFFENERS 5/8" LARGE PITTSBURGH (L-1) 1 JTR, 4-CORNER STIFFENERS 5/8" LARGE PITTSBURGH (L-1) 1 JTR, 4-CORNER STIFFENERS 5/8" LARGE PITTSBURGH (L-1) 2 MPT/ 1 JTR, 4-CORNER STIFFENERS 5/8" LARGE PITTSBURGH (L-1) 2 MPT/ 1 JTR, 4-CORNER STIFFENERS 5/8" LARGE PITTSBURGH (L-1) 1 JTR/ 2 1/2x2 1/2x1/4 ANGLE AT 30" MIDSPAN 5/8" LARGE PITTSBURGH (L-1) WITH ENDS TIED, 4-CORNER STIFFENERS MPT SPACED AT 5'-0" MAX SPACING WITH 5/8" LARGE PITTSBURGH (L-1) 2x2x1/4 ANGLE WRAP/ JTR SPACED AT 5'-0" MAX SPACING (SEE SMACNA FIGURE 2-13), 4CORNER STIFFENERS

D (T-11): 1x20 GA D (T-11): 1x20 GA

OVER 120

OVER 120

18

It

SPECIFIC NOTES TO CHART: 1. LETTER AND NUMBER IN PARENTHESIS REFERS TO SMACNA CLASSIFICATION. 2. DUCT MATERIAL SHALL BE G-90 COATED GALVANIZED STEEL PER ASTM A653, ASTM A924. 3. REINFORCEMENT SPACING REFERS TO JOINT-TO-JOINT, JOINT-TOINTERMEDIATE, OR INTERMEDIATE-TO-INTERMEDIATE. 4. THE SAME SHEET GAUGE MUST BE USED ON ALL SIDES OF DUCT. EACH DUCT DIMENSION, WIDTH, OR DEPTH, CONTROLS THE MINIMUM REINFORCEMENT REQUIREMENTS FOR THAT SIDE. 5. ALL DUCTWORK 13" WIDTH AND GREATER REGARDLESS OF LENGTH SHALL BE BEADED. 6. ALL DUCTWORK TRANSVERSE JOINTS, AND DUCT WALL PENETRATIONS SHALL BE SEALED PER SMACNA STANDARDS. SEALANT SHALL BE UNITED DUCT SEALER OR APPROVED EQUAL.

ABBREVIATIONS: FLAT D: FLAT DRIVE FLAT S: FLAT SLIP STANDING S: STANDING SLIP 3/4" T: 3/4" TIE-ROD REINFORCEMENT REQUIRED JTR: JOINT TIE ROD MPT: MID POINT TIE ROD GA: GAUGE

7. ALL TDC CONNECTIONS SHALL BE SEALED WITH 3/4" X 3/16" THICK TAPE TYPE GASKETING (BUTYLE NO. 797) W/ONE SIDE ADHESIVE BACKING AND PAINTED WITH DUCT SEALER OR CAULKING MATERIAL AT ALL CORNERS. 8. FOR SIZES NOT LISTED PLEASE CALL THE SHOP.

GENERAL NOTES: 1. DUCT CONSTRUCTION STANDARDS ARE BASED ON SMACNA 3RD EDITION- 2005 2. LETTER AND NUMBER IN PARENTHESIS REFERS TO SMACNA CLASSIFICATION. 3. 1/4" LARGE PITTSBURGH ON ALL RADIAL FITTINGS

REVISED: 12.21.2009

DUCT CONSTRUCTION CHART WITH TIE ROD REINFORCEMENT 5' COIL LENGTHS, GALVANIZED
MECHANICAL GROUP

3" PRESSURE CLASS (+/-)


REINFORCEMENT/JOINTS
GAUGE SMACNA REINF CODE REINF/ JOINT SPACING (INCHES) 59 59 56 1/4 56 1/4 56 1/4 56 1/4 56 1/4 56 1/4 56 1/4 56 1/4 JOINT 30" REINF 56 1/4 JOINT 30" REINF LONG SIDE REINF/JOINT TYPE (SMACNA CODE) FLAT S (T-5) STANDING S (T-11) TDC (T-25A) TDC (T-25A) TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T SHORT SIDE REINF/JOINT TYPE (SMACNA CODE) FLAT D (T-1) FLAT D (T-1) TDC (T-25A) TDC (T-25A) TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T LONGITUDINAL JOINTS (SMACNA CODE)
REMARKS

DUCT SIZES
MAX LONG MAX SHORT SIDE (IN) SIDE (IN) 12 18 30 36 42 48 60 72 96 120 OVER 120 12 12 30 36 42 48 60 72 96 120 OVER 120

22 22 22 20 20 20 20 20 18 18 18

NONE D F G H H H I J L It

5/8" SNAPLOCK (L-2) 5/8" SNAPLOCK (L- D (T-11): 1x20 GA 1) 5/8" LARGE PITTSBURGH (L-1) 5/8" LARGE PITTSBURGH (L-1) 5/8" LARGE 1 JTR PITTSBURGH (L-1)
1 MPT/ 1 JTR 5/8" LARGE PITTSBURGH (L-1) 1 MPT/ 1 JTR, 4-CORNER STIFFENERS 5/8" LARGE PITTSBURGH (L-1) 2 MPT/ 1 JTR, 4-CORNER STIFFENERS 5/8" LARGE PITTSBURGH (L-1) 2 MPT/ 1 JTR, 4-CORNER STIFFENERS 5/8" LARGE PITTSBURGH (L-1), 4-CORNER 1 JTR/ 2 1/2x2 1/2x1/4 ANGLE AT 30" MIDSPAN 5/8" LARGE PITTSBURGH (L-1) WITH ENDS TIED MPT SPACED AT 5'-0" MAX SPACING WITH 5/8" LARGE PITTSBURGH (L-1) 2x2x1/4 ANGLE WRAP/ JTR SPACED AT 5'-0" MAX SPACING (SEE SMACNA FIGURE 2-13)

SPECIFIC NOTES TO CHART: 1. LETTER AND NUMBER IN PARENTHESIS REFERS TO SMACNA CLASSIFICATION. 2. DUCT MATERIAL SHALL BE G-90 COATED GALVANIZED STEEL PER ASTM A653, ASTM A924. 3. REINFORCEMENT SPACING REFERS TO JOINT-TO-JOINT, JOINT-TOINTERMEDIATE, OR INTERMEDIATE-TO-INTERMEDIATE. 4. THE SAME SHEET GAUGE MUST BE USED ON ALL SIDES OF DUCT. EACH DUCT DIMENSION, WIDTH, OR DEPTH, CONTROLS THE MINIMUM REINFORCEMENT REQUIREMENTS FOR THAT SIDE. 5. ALL DUCTWORK 13" WIDTH AND GREATER REGARDLESS OF LENGTH SHALL BE BEADED. 6. ALL DUCTWORK TRANSVERSE JOINTS, AND DUCT WALL PENETRATIONS SHALL BE SEALED PER SMACNA STANDARDS. SEALANT SHALL BE UNITED DUCT SEALER OR APPROVED EQUAL.

ABBREVIATIONS: FLAT D: FLAT DRIVE FLAT S: FLAT SLIP STANDING S: STANDING SLIP 3/4" T: 3/4" TIE-ROD REINFORCEMENT REQUIRED JTR: JOINT TIE ROD MPT: MID POINT TIE ROD GA: GAUGE

7. ALL TDC CONNECTIONS SHALL BE SEALED WITH 3/4" X 3/16" THICK TAPE TYPE GASKETING (BUTYLE NO. 797) W/ONE SIDE ADHESIVE BACKING AND PAINTED WITH DUCT SEALER OR CAULKING MATERIAL AT ALL CORNERS. 8. FOR SIZES NOT LISTED PLEASE CALL THE SHOP.

GENERAL NOTES: 1. DUCT CONSTRUCTION STANDARDS ARE BASED ON SMACNA 3RD EDITION- 2005 2. LETTER AND NUMBER IN PARENTHESIS REFERS TO SMACNA CLASSIFICATION. 3. 1/4" LARGE PITTSBURGH ON ALL RADIAL FITTINGS

REVISED: 12.21.2009

DUCT CONSTRUCTION CHART WITH TIE ROD REINFORCEMENT COIL LENGTHS, GALVANIZED
MECHANICAL GROUP

5'

4" PRESSURE CLASS (+/-)


REINFORCEMENT/JOINTS
GAUGE SMACNA REINF CODE REINF/ JOINT SPACING (INCHES) 59 59 56 1/4 56 1/4 56 1/4 56 1/4 56 1/4 56 1/4 56 1/4 56 1/4 JOINT 30" REINF 56 1/4 JOINT 30" REINF LONG SIDE REINF/JOINT TYPE (SMACNA CODE) STANDING S (T-11) STANDING S (T-11) TDC (T-25A) TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T SHORT SIDE REINF/JOINT TYPE (SMACNA CODE) FLAT D (T-1) FLAT D (T-1) TDC (T-25A) TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T LONGITUDINAL JOINTS (SMACNA CODE)
REMARKS

DUCT SIZES
MAX LONG SIDE (IN) 12 16 28 36 48 60 72 84 96 120 MAX SHORT SIDE (IN) 12 12 28 36 48 60 72 84 96 120

20 20 20 20 20 20 20 18 18 18

NONE C F H G I I J K L

5/8" SNAPLOCK (L-2) 5/8" SNAPLOCK (L-2) 5/8" LARGE PITTSBURGH (L-1)

D (T-11): 1x20 GA D (T-11): 1x20 GA

5/8" LARGE 1 JTR PITTSBURGH (L-1) 5/8" LARGE 1 MPT/1 JTR PITTSBURGH (L-1) 5/8" LARGE 1 MPT/ 1 JTR PITTSBURGH (L-1) 4-CORNER STIFFENERS
2 MPT/ 1JTR 5/8" LARGE PITTSBURGH (L-1) 4-CORNER STIFFENERS 2 MPT/ 1JTR 5/8" LARGE PITTSBURGH (L-1) 4-CORNER STIFFENERS 2 MPT/ 1JTR 5/8" LARGE PITTSBURGH (L-1) 4-CORNER STIFFENERS 1 JTR/ 2 1/2x2 1/2x1/4 ANGLE AT 30" MIDSPAN 5/8" LARGE PITTSBURGH (L-1) WITH ENDS TIED MPT SPACED AT 5'-0" MAX SPACING WITH 2 5/8" LARGE PITTSBURGH (L-1) 1/2x2 1/2x1/4 ANGLE WRAP/ JTR SPACED AT 5'0" MAX SPACING (SEE SMACNA FIGURE 2-13)

OVER 120

OVER 120

18

Jt

SPECIFIC NOTES TO CHART: 1. LETTER AND NUMBER IN PARENTHESIS REFERS TO SMACNA CLASSIFICATION. 2. DUCT MATERIAL SHALL BE G-90 COATED GALVANIZED STEEL PER ASTM A653, ASTM A924. 3. REINFORCEMENT SPACING REFERS TO JOINT-TO-JOINT, JOINT-TOINTERMEDIATE, OR INTERMEDIATE-TO-INTERMEDIATE. 4. THE SAME SHEET GAUGE MUST BE USED ON ALL SIDES OF DUCT. EACH DUCT DIMENSION, WIDTH, OR DEPTH, CONTROLS THE MINIMUM REINFORCEMENT REQUIREMENTS FOR THAT SIDE. 5. ALL DUCTWORK 13" WIDTH AND GREATER REGARDLESS OF LENGTH SHALL BE BEADED. 6. ALL DUCTWORK SHALL BE SEALED TO SEAL CLASS 'A' PER SMACNA (ALL TRANSVERSE JOINTS, LONGITUDINAL SEAMS, AND DUCT WALL PENETRATIONS). SEALANT SHALL BE UNITED DUCT SEALER OR APPROVED EQUAL. 7. ALL TDC CONNECTIONS SHALL BE SEALED WITH 3/4" X 3/16" THICK TAPE TYPE GASKETING (BUTYLE NO. 797) W/ONE SIDE ADHESIVE BACKING AND PAINTED WITH DUCT SEALER OR CAULKING MATERIAL AT ALL CORNERS. 8. FOR SIZES NOT LISTED PLEASE CALL THE SHOP.

ABBREVIATIONS: FLAT D: FLAT DRIVE FLAT S: FLAT SLIP STANDING S: STANDING SLIP 3/4" T: 3/4" TIE-ROD REINFORCEMENT REQUIRED JTR: JOINT TIE ROD MPT: MID POINT TIE ROD GA: GAUGE

GENERAL NOTES: 1. DUCT CONSTRUCTION STANDARDS ARE BASED ON SMACNA 3RD EDITION- 2005 2. LETTER AND NUMBER IN PARENTHESIS REFERS TO SMACNA CLASSIFICATION. 3. 1/4" LARGE PITTSBURGH ON ALL RADIAL FITTINGS

REVISED: 12.21.2009

DUCT CONSTRUCTION CHART WITH TIE ROD REINFORCEMENT 5' COIL LENGTHS, GALVANIZED
MECHANICAL GROUP

6" PRESSURE CLASS (+/-)


REINFORCEMENT/JOINTS
GAUGE SMACNA REINF CODE REINF/ JOINT SPACING (INCHES) 56 1/4 56 1/4 56 1/4 56 1/4 56 1/4 56 1/4 56 1/4 56 1/4 JOINT 56 1/4 JOINT 24" REINF 56 1/4 JOINT 24" REINF LONG SIDE REINF/JOINT TYPE (SMACNA CODE) TDC (T-25A) TDC (T-25A) TDC (T-25A) TDC (T-25A) TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T SHORT SIDE REINF/JOINT TYPE (SMACNA CODE) TDC (T-25A) TDC (T-25A) TDC (T-25A) TDC (T-25A) TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T TDC (T-25A) 3/4" T LONGITUDINAL JOINTS (SMACNA CODE)
REMARKS

DUCT SIZES
MAX LONG SIDE (IN) 12 24 26 30 36 48 72 84 108* (SEE SHOP) 120* (SEE SHOP) MAX SHORT SIDE (IN) 12 24 26 30 36 48 72 84 108* (SEE SHOP) 120* (SEE SHOP)

24 22 20 18 18 20 18 18 18

C F G H H G J L J

5/8" LARGE PITTSBURGH (L-1) 5/8" LARGE PITTSBURGH (L-1) 5/8" LARGE PITTSBURGH (L-1) 5/8" LARGE PITTSBURGH (L-1)
1 JTR 5/8" LARGE PITTSBURGH (L-1)

5/8" LARGE 1 MPT/ 1 JTR PITTSBURGH (L-1) SEE SPECIFIC NOTE 9. 5/8" LARGE 1 MPT/ 1 JTR, 4 CORNER STIFFENERS PITTSBURGH (L-1) 5/8" LARGE 2 MPT/ 1 JTR, 4 CORNER STIFFENERS PITTSBURGH (L-1)
1 JTR/ 2 1/2x2 1/2x1/4 ANGLE AT 24" MIDSPAN 5/8" LARGE PITTSBURGH (L-1) WITH ENDS TIED 2 1/2x2 1/2x1/4 ANGLE AT 24" MIDSPAN WITH 5/8" LARGE PITTSBURGH (L-1) ENDS TIED/ 2 1/2x2 1/2x1/4 ANGLE AT JOINT WITH ENDS TIED MPT SPACED AT 5'-0" MAX SPACING WITH 2 5/8" LARGE PITTSBURGH (L-1) 1/2x2 1/2x1/4 ANGLE WRAP/ JTR SPACED AT 5'0" MAX SPACING (SEE SMACNA FIGURE 2-13)

18

Kt

OVER 120* (SEE SHOP)

OVER 120* (SEE SHOP)

18

Kt

56 1/4 JOINT 24" REINF

TDC (T-25A) 3/4" T

TDC (T-25A) 3/4" T

* SEE SHOP SPECIFIC NOTES TO CHART: 1. LETTER AND NUMBER IN PARENTHESIS REFERS TO SMACNA CLASSIFICATION. 2. DUCT MATERIAL SHALL BE G-90 COATED GALVANIZED STEEL PER ASTM A653, ASTM A924. 3. REINFORCEMENT SPACING REFERS TO JOINT-TO-JOINT, JOINT-TOINTERMEDIATE, OR INTERMEDIATE-TO-INTERMEDIATE. 4. THE SAME SHEET GAUGE MUST BE USED ON ALL SIDES OF DUCT. EACH DUCT DIMENSION, WIDTH, OR DEPTH, CONTROLS THE MINIMUM REINFORCEMENT REQUIREMENTS FOR THAT SIDE. 5. ALL DUCTWORK 13" WIDTH AND GREATER REGARDLESS OF LENGTH SHALL BE BEADED. 6. ALL DUCTWORK SHALL BE SEALED TO SEAL CLASS 'A' PER SMACNA (ALL TRANSVERSE JOINTS, LONGITUDINAL SEAMS, AND DUCT WALL PENETRATIONS). SEALANT SHALL BE UNITED DUCT SEALER OR APPROVED EQUAL. 7. ALL TDC CONNECTIONS SHALL BE SEALED WITH 3/4" X 3/16" THICK TAPE TYPE GASKETING (BUTYLE NO. 797) W/ONE SIDE ADHESIVE BACKING AND PAINTED WITH DUCT SEALER OR CAULKING MATERIAL AT ALL CORNERS. ABBREVIATIONS: FLAT D: FLAT DRIVE FLAT S: FLAT SLIP STANDING S: STANDING SLIP 3/4" T: 3/4" TIE-ROD REINFORCEMENT REQUIRED JTR: JOINT TIE ROD MPT: MID POINT TIE ROD GA: GAUGE

8. FOR SIZES NOT LISTED PLEASE CALL THE SHOP.

GENERAL NOTES: 1. DUCT CONSTRUCTION STANDARDS ARE BASED ON SMACNA 3RD EDITION- 2005 2. LETTER AND NUMBER IN PARENTHESIS REFERS TO SMACNA CLASSIFICATION. 3. 1/4" LARGE PITTSBURGH ON ALL RADIAL FITTINGS

REVISED: 12.21.2009

DUCT CONSTRUCTION CHART WITH TIE ROD REINFORCEMENT 5' COIL LENGTHS, ALUMINUM (ALLOY 3003-H-14) ASTM STD B209 ALLOY
MECHANICAL GROUP

2" PRESSURE CLASS (+/-)


REINFORCEMENT/JOINTS
ALUMINUM THICKNESS (GA) SMACNA REINF CODE (ALUMINUM TABLE 2-52) NONE E E F REINF/ JOINT SPACING (INCHES) 59 56 1/4 56 1/4 56 1/4 LONG SIDE REINF/JOINT TYPE (SMACNA CODE) FLAT S (T-5) TDC (T-25A) TDC (T-25A) TDC (T-25A) SHORT SIDE REINF/JOINT TYPE (SMACNA CODE) FLAT D (T-1) TDC (T-25A) TDC (T-25A) TDC (T-25A) LONGITUDINAL JOINTS (SMACNA CODE)
REMARKS

DUCT SIZES
MAX LONG MAX SHORT SIDE (IN) SIDE (IN) 12 20 28 36 12 20 28 36

0.032 (20) 0.040 (18) 0.040 (18) 0.050 (16)

3/8" LARGE PITTSBURGH (L-1) 3/8" LARGE PITTSBURGH (L-1) 3/8" LARGE 1 MPT PITTSBURGH (L-1) 3/8" LARGE 1 MPT PITTSBURGH (L-1)

SEE SHOP SEE SHOP FOR FOR ADDITIONAL ADDITIONAL SIZES SIZES SPECIFIC NOTES TO CHART: 1. LETTER AND NUMBER IN PARENTHESIS REFERS TO SMACNA CLASSIFICATION. 2. DUCT MATERIAL SHALL BE BASED ON ASTM STANDARD B209 ALLOY SHEET (ALLOY 3003-H-14). 3. REINFORCEMENT SPACING REFERS TO JOINT-TO-JOINT, JOINT-TOINTERMEDIATE, OR INTERMEDIATE-TO-INTERMEDIATE. 4. THE SAME SHEET GAUGE MUST BE USED ON ALL SIDES OF DUCT. EACH DUCT DIMENSION, WIDTH, OR DEPTH, CONTROLS THE MINIMUM REINFORCEMENT REQUIREMENTS FOR THAT SIDE. 5. ALL DUCTWORK 13" WIDTH AND GREATER REGARDLESS OF LENGTH SHALL BE BEADED. 6. ALL DUCTWORK TRANSVERSE JOINTS, AND DUCT WALL PENETRATIONS SHALL BE SEALED PER SMACNA STANDARDS. SEALANT SHALL BE SUITABLE FOR ALUMINUM MATERIAL AND APPLICATION. ABBREVIATIONS: FLAT D: FLAT DRIVE FLAT S: FLAT SLIP STANDING S: STANDING SLIP 3/4" T: 3/4" TIE-ROD REINFORCEMENT REQUIRED JTR: JOINT TIE ROD MPT: MID POINT TIE ROD GA: GAUGE

7. ALL TDC CONNECTIONS SHALL BE SEALED WITH 3/4" X 3/16" THICK TAPE TYPE GASKETING (BUTYLE NO. 797) W/ONE SIDE ADHESIVE BACKING AND PAINTED WITH DUCT SEALER OR CAULKING MATERIAL AT ALL CORNERS. SEALANT SHALL BE SUITABLE FOR APPLICATION. 8. FOR SIZES NOT LISTED PLEASE CALL THE SHOP.

GENERAL NOTES: 1. DUCT CONSTRUCTION STANDARDS ARE BASED ON SMACNA 3RD EDITION2005 2. LETTER AND NUMBER IN PARENTHESIS REFERS TO SMACNA CLASSIFICATION.

REVISED: 12.21.2009

DUCT CONSTRUCTION CHART WITH TIE ROD REINFORCEMENT 5' COIL LENGTHS, ALUMINUM (ALLOY 3003-H-14) ASTM STD B209 ALLOY
MECHANICAL GROUP

3" PRESSURE CLASS (+/-)


REINFORCEMENT/JOINTS
ALUMINUM THICKNESS (GA) SMACNA REINF CODE (ALUMINUM TABLE 2-52) E E F F REINF/ JOINT SPACING (INCHES) 56 1/4 56 1/4 56 1/4 56 1/4 LONG SIDE REINF/JOINT TYPE (SMACNA CODE) TDC (T-25A) TDC (T-25A) TDC (T-25A) TDC (T-25A) SHORT SIDE REINF/JOINT TYPE (SMACNA CODE) TDC (T-25A) TDC (T-25A) TDC (T-25A) TDC (T-25A) LONGITUDINAL JOINTS (SMACNA CODE)
REMARKS

DUCT SIZES
MAX LONG MAX SHORT SIDE (IN) SIDE (IN) 12 18 22 28 12 18 22 28

0.040 (18) 0.040 (18) 0.040 (18) 0.050 (16)

3/8" LARGE PITTSBURGH (L-1) 3/8" LARGE PITTSBURGH (L-1) 3/8" LARGE 1 MPT PITTSBURGH (L-1) 3/8" LARGE 1 MPT PITTSBURGH (L-1)

SEE SHOP SEE SHOP FOR FOR ADDITIONAL ADDITIONAL SIZES SIZES SPECIFIC NOTES TO CHART: 1. LETTER AND NUMBER IN PARENTHESIS REFERS TO SMACNA CLASSIFICATION. 2. DUCT MATERIAL SHALL BE BASED ON ASTM STANDARD B209 ALLOY SHEET (ALLOY 3003-H-14). 3. REINFORCEMENT SPACING REFERS TO JOINT-TO-JOINT, JOINT-TOINTERMEDIATE, OR INTERMEDIATE-TO-INTERMEDIATE. 4. THE SAME SHEET GAUGE MUST BE USED ON ALL SIDES OF DUCT. EACH DUCT DIMENSION, WIDTH, OR DEPTH, CONTROLS THE MINIMUM REINFORCEMENT REQUIREMENTS FOR THAT SIDE. 5. ALL DUCTWORK 13" WIDTH AND GREATER REGARDLESS OF LENGTH SHALL BE BEADED. 6. ALL DUCTWORK TRANSVERSE JOINTS, AND DUCT WALL PENETRATIONS SHALL BE SEALED PER SMACNA STANDARDS. SEALANT SHALL BE SUITABLE FOR ALUMINUM MATERIAL AND APPLICATION. ABBREVIATIONS: FLAT D: FLAT DRIVE FLAT S: FLAT SLIP STANDING S: STANDING SLIP 3/4" T: 3/4" TIE-ROD REINFORCEMENT REQUIRED JTR: JOINT TIE ROD MPT: MID POINT TIE ROD GA: GAUGE

7. ALL TDC CONNECTIONS SHALL BE SEALED WITH 3/4" X 3/16" THICK TAPE TYPE GASKETING (BUTYLE NO. 797) W/ONE SIDE ADHESIVE BACKING AND PAINTED WITH DUCT SEALER OR CAULKING MATERIAL AT ALL CORNERS. SEALANT SHALL BE SUITABLE FOR APPLICATION. 8. FOR SIZES NOT LISTED PLEASE CALL THE SHOP.

GENERAL NOTES: 1. DUCT CONSTRUCTION STANDARDS ARE BASED ON SMACNA 3RD EDITION2005 2. LETTER AND NUMBER IN PARENTHESIS REFERS TO SMACNA CLASSIFICATION.