GE Series: Safety Information
GE Series: Safety Information
GE Series
INSTRUCTION MANUAL
Thank you for purchasing HANYOUNG NUX CO,.Ltd. Product. Please check whether the prouduct you purchased is the exactly same as you ordered. Before using product, please read instruction maunal carefully.
Counter / Timer
HEAD OFFICE
Safety Information
Before you use, read safety precautions carefully, and use this product properly. The precautions described in this manual contains important contents related with safety; therefore, please follow the instructions accordingly. The precautions are composed of DANGER, WARNING and CAUTION.
19. Some parts of this product have limited life span, and others are changed by their usage. 20. The warranty period for this product including parts is one year if this product is properly used. 21. When the power is on, the preparation period of contact output is required. In case of use for signals of external interlock circuit, use with a delay relay.
DANGER
Do not touch or contact the input/output terminals because they may cause electric shock.
WARNING
1. If there is a possibility of an accident caused by errors or malfunctions of this product, install external protection circuit to prevent the accident. 2. This product does not contain an electric switch or fuse, so the user needs to install a separate electric switch or fuse externally. (Fuse rating : 250 V 0.5 A) 3. To prevent defection or malfunction of this product, supply proper power voltage in accordance with the rating. 4. To prevent electric shock or devise malfunction of this product, do not supply the power until the wiring is completed. 5. Since this product is not designed with explosion-protective structure, do not use it at any place with flammable or explosive gas. 6. Do not decompose, modify, revise or repair this product. This may cause malfunction, electric shock or fire. 7. Reassemble this product while the power is off. Otherwise, it may cause malfunction or electric shock. 8. It you use the product with methods other than specified by the manufacturer, there may be bodily injuries or property damages. 9. Due to the danger of electric shock, use this product installed onto a panel while an electric current is applied.
Appearance
PRESET BATCH TOTAL (Indicator) 4 : 9999 (4 digit) 6 : 999999 (6 digit) 1 stage 2 stage A 100 V - 240 V a.c D 24 V - 60 V d.c Twin timer Support GE3,GE7:Not available
Power Supply
CAUTION
1. The contents of this manual may be changed without prior notification. 2. Before using the product you have purchased, check to make sure that it is exactly what you ordered. 3. Check to make sure that there is no damage or abnormality of the product during delivery. 4. Do not use this product at any place with corrosive(especially noxious gas or ammonia) or flammable gas. 5. Do not use this product at any place with direct vibration or impact. 6. Do not use this product at any place with liquid, oil, medical substances, dust, salt or iron contents. (Pollution level 1 or 2) 7. Do not polish this product with substances such as alcohol or benzene. 8. Do not use this product at any place with excessive induction trouble, static electricity or magnetic noise. 9. Do not use this product at any place with possible thermal accumulation due to direct sunlight or heat radiation. 10. Install this product at place under 2,000m in altitude. 11. When the product gets wet, the inspection is essential because there is danger of an electric leakage or fire. 12. If there is excessive noise from the power supply, using insulating transformer and noise filter is recommended. The noise filter must be attached to a panel grounded, and the wire between the filter output side and power supply terminal must be as short as possible. 13. If gauge cables are twisted closely, the effect on noise may occur. 14. Do not connect anything to the unused terminals. 15. After checking polarity of terminal, connect wires at the correct position. 16. When this product is connected to a panel, use a circuit breaker or switch approved with IEC847-1 or IEC947-3. 17. Install the circuit breaker or switch at near place for convenient use. 18. For the continuous and safe use of this product, the periodical maintenance is recommended. During the first 100 after power input and first 200 after power opening, it is consider as ascend and descend time of internal power and external output power. Therefore, it does not operate during unstable period in order to prevent from malfunction which is caused by unstable output operation of external sensor Supply signal only after 100 Supply power only after 200 following the power input. following the power shutdown.
GE4
GE6
Connection Diagram
NPN Input GE4-P1
GE3
Panel Cutout
a1 a2 L1 L2
GE4
GE6 66.5+0.5 0
32
+0.5 0
GE3
GE7
GE4-P2
45+0.6 0
Same as above
92 +0.5 0
45
+0.5 0
68
+0.7 0
Same as above
More than More than More than More than 130 60 90 82 Same as above More than More than Same as above 57 60
Specification
Model Power voltage Power consumption a.c d.c a.c d.c GE4 GE6 GE3 ) ) 10 10 GE7
GE6-P1
100 - 240 V a.c (50 - 60 24 - 60 V d.c / a.c (50 - 60 Max. 13.5 V a.c Max. 9 VA 11 8
FND height
10 years (Nonvolatile memory) CP1, CP2, RESET, BATCH RESET (exclude TOTAL) 4inputs [H] level 4 - 30 V d.c, [L] level 0 - 2 V d.c Internal pull up/pull down resistance connection due to NPN/PNP setup
Min input Counter External reset Min. input signal range: select among 0.1ms / 1ms / 20 ms signal External output power Timer a.c d.c 1 step 2 step 1 step 2 step Capacity 1c (OUT) START, INHIBIT, RESET Min. input signal range: select either 1ms / 20 ms 12 V d.c ( 5 %) 200 12 V d.c ( 5 %) 100 1a (OUT) 1a (OUT1), 1c (OUT2) NPN 2 points(OUT,BAT.O) NPN 2 points(OUT1,OUT2) Open collector 30 V d.c 100 Stable time: 100 Max. for every 2 Comparative cycle: repeated setup error less than 5 2000 V a.c 50 - 60 Min 100 (Power supply input terminal) (for 1 min period) double amplitude 0.5 X.Y.Z each direction for 10 minutes 100 300 (About 10G) (About 30G) 10 - 55 (for 1 min period) double amplitude 0.5 X.Y.Z each direction for 2 hours for 1 minute pulse per 16ms) 2 Max. Max. 1c (OUT)
GE6-P2
Capacity NO contact: 250V a.c. 3A resistance load, NC contact: 250V a.c. 2A resistance load
Timer operation Dielectric Strength Insulation Resistance Withstanding noise Vibration Shock Relay Life
Non-contact
GE3-P1
Malfunction 10 - 55 Durability
Maifunction
Durability Electrical Mechanical
Min. 100 thousand times (250 V a.c 2 A resistance load) Min 1 million times IP65 (Front part only) -20 ~ 65 -10 ~ 55 Max.133 g (Non freezing state) Max.203 g CE Max.203 g , 35 ~ 85 % R.H. (No freezing or decondensation) Max.138 g
If you want to modify Input and output type, plesae contact HANYOUNG sales office
GE3-P2
GE4
GE7 GE7-P1
GE7-P2
Coefficient Input 1(CP1) / Inhibit Input (INHIBIT) Terminal With using counter, it is used as coefficient input or coefficient inhibit Process time become HOLD when timer function is selected Coefficient Input 2(CP2) / Start (START) Terminal With using counter, it is used as coefficient input or coefficient inhibit With using timer, it can be used as SIGNAL ON START, SIGNAL ONE START. (Refer to output mode operation) (SIGNAL ON START: Timer operates only with the continuous input.) (SIGNAL ONE START: Timer operates only with the supply of Input 1 Pulse.) BAT. RESET This is used as BATCH, RESET during the use of counter / timer. RESET This initializes the coefficient value and current time during the use of counter / timer. OUT, OUT2 : This is used as the counter / timer comparative output. BAT.O : Batch Counter Output (1 Stage Setup Type) OUT1(BAT.O): Select between 2 Stage Setup Output and Batch Counter Output (2 Stage Setup Type)
Coefficient display (RED FND) Display coefficient value (counter), time process value (timer), batch coefficient value and setup list. Setup display (GREEN FND) Display setup value (counter), setup time (timer), batch setup value, instant output setup (batch setup is 0 in Timer) and setup contents SET1, SET2 (SET), BAT Indicates the status of coefficient section and setup section (BAT lamp corresponds to batch status.) TIM (Timer) This flashes when the timer progresses and remains lighted when the device stops from inhibit input or reset. (It is indicated in Change Mode of the device during TIM/TTWIN setup.) CNT (Counter) This is indicated during 1CNT/2CNT setup in Change Mode of the device. OUT1, OUT2(OUT), BAT.O (Output Action Indication) BAT.O lights up when the batch setup value is set. (OUT1 Output) BAT.O lights up and outputs when the device operates with the instant output where the batch setup value is 0 (timer). CP1, CP2, RST: Verification of Input Status. (Exclusively for TOTAL) LOCK:Key Lock (KEY LOCK) Action IndicationThis lights up during Lock Setup. This key is for function setup Mode Entry and Mode change. It can also be used for ending after saving when changing the setup value Setup value change Entry and Location shift UP Key RESET KEY When SET, BAT lamp light, RESET key will not operate. Batch and operation mode 1 stage and 2 stage conversion key. When BAT lamp light, it is batch mode and keep operate. Push both of keys together, It operate same as key. DOWN Key TOTAL Model does not have Setup Indication Section, SET1, SET2 and BAT Lamp. OUT1, OUT2, BAT.O change their use as CP1, CP2, RST Input Status Check Lamp. 1 Stage Setup Model does not have SET1 and OUT1 Lamp, and SET2 is displayed as SET and OUT2 is displayed as OUT.
GE6
Convert Operation Mode to Function Mode -> Press MD key for 2 seconds Contents Initial value
1 Stage setup counter 2 Stage setup counter CP1,CP2 Dual inputs UP mode operatio CP1,CP2 Dual inputs down mode operation Refer to Input operation Mode (Counter) Refer to Output operation Mode (Counter) One short delay time One short time setup No display for level 1 product Set Batch output port Relay or Transistor is set when contact is used with maxmum input speed When using encoder (incremental method). Please use Noice) The input Login of above list is PNP. (D setup is self-maintenance output)
Initial Value set up to 5 decimal points and possible to move up to 4 decimal points Setup decimal point in display and possible to move up to the third decimal point Minimum signal width of external reset signal input Coefficient value is saved when POWER become OFF Coefficient value is initialized when POWER become OFF Vary depends on internal switch conversion Key Lock Cancel Key Lock Do not use any keys (except Do not use , , , key key Do not use front side key)
Flashing Flashing
DOWN
UP/DOWN A,B,C
Key Lock
Set value is first to decrease within Down Mode 6 digits: if -99999(-999), it flashes and does not get counted Within UP MODE, it increases to the maximum display value, initializes to 0 and increases again
Pressing key will return to operation mode without saving. Return to operation mode if there is no key input more than 60 seconds. With function setup mode, it ignores external signal input and maintains output in OFF state. TOTAL product does not display setup lists such as output mode, OUT2 output time, OUT1 output time, BATCH output and etc Level 1 setup product does not display OUT1 output time setup list. Selecting for BATCH output setup will restrict setup function and display function.
As for 1 Stage Counter (OUT), it is the same as 2ND Output (OUT2) Action.
Select One Shot Output between 0.01ms~99.99ms One Shot Time Delay Self-Maintenance Output Self-Maintenance Output One Shot Output of OUT2 Output
Coefficient value indication is continuously processed and setting up HOLD (0) leads to self-maintenance output. Also, setting up time leads to OUT2 output after one shot delay setup. OUT1 and OUT2 become OFF when reset and return to Start
Coefficient value indication is continuously processed during START state and OUT2 yields One Shot Output. Self-maintenance output of OUT1 is turned off when OUT2 is turned OFF
Coefficient value indication is maintained during One Shot Time, and then resets. (Repetitive Action)
Coefficient value indication is continuously processed. OUT2 yields one shot output. Self-maintenance output of OUT1 is turned off after one shot time of out2
When coefficient value returns to initial state, then coefficient value indication is maintained for one shot time. After processing one shot time, it displays processed coefficient value.
Coefficient value increases and OUT2 yields One Shot Output. The device is reset after the One Shot Output. (Repetitive Action) Coefficient value is maintained and OUT2 yields one shot output. OUT1 and OUT2 are independent from each other. If #OUT1 is same as setup value of SET1, it leads to one shot output or self-maintenance output. (In case of Level 1 setup type, OUT1 and OUT2 are same each other) # Reset refers to OUT1 and OUT2 become OFF and coefficient value being initialized.
Input Connection
NPN (Non-Voltage Input) Input Logic Selection
Operate the conversion switch after confirming NPN/PNP indication which is displayed on the top Input Method H Non-Contact Sensor Connection Method Contact Sensor Connection Method L NPN Setup Voltage Input PNP O.C PNP Setup Voltage Input PNP O.C
Input Method H L
For receiving Open Collector Input, Input Logic (PNP/NPN) Conversion Switch is embedded internally to Pull up / Pull down the resistance of 4.7 (NPN Setup during shipment) Non-Contact Sensor Connection Method Contact Sensor Connection Method
Input Logic Setup Status can be verified in Function Setup Mode. Internal Impedance is 4.7 , and switches over to Pull Up or Pull Down from NPN/PNP Selection. (Refer to Input Connection) To prevent chattering during the use of Contact Input Counter, setup the coefficient speed at 1 or 30 cps in Function Setup Mode.
Output Connection
Example of Non-Contact Output
Connect surge observer (diode,varistor) on the both ends of the load when using inductive load (relay etc.),and must use with GND since the internal circuit and non-contact output are isolated from one another. Calculate power load and load to prevent the non-contact output from exceeding the maximum of 30 V 100
Avoid the flow of excessive current since it is 250 V a.c NO 3 A (loadresistance) NC 2 A (load resistance), and theconnection must correspond to standard connection method.
Signal RUN / ON delay Signal RUN / OFF delay Interval / Signal RUN Interval / Signal START Flicker / Signal START Flicker (Counter 0.01sec ~ 999999(9999)h UP/DOWN selectable Flicker (Counter Flicker (Counter Signal Addition Mode) Mode) Mode)
10 (Decimal) / 60 (Sexagesimal)system
CP1/INHIBIT function stops the time. [S.---] is activated when CP2 (START) is ON [S ---] is activated when CP2 is maintained ON, and resets when OFF. [P ---] activates with POWER ON Setup as in order to compensate for interruption of electric power during POWER OFF (Indicates the Memorized Value when electric power is inputted again.)
Output time BATCH Output Input time Memory for power failure Input logic Key Lock
* No display for Total and TWIN TIMER mode Set Batch output port :Relay : Transistor) Minimum input time selection 1 /20 (INHIBIT), (START), RESET Current time and Batch count value are saved when power failure Remove a data when power failure
Timer[TIM]Output Operation
1 Stage Setup Type Output is OUT. INHIBIT (CP1) temporarily stops the time.
Convertible by dip switch It is not available to change setup in power input menu. Key Lock No use for all keys ( key exception) No use keys
, No use
, keys
Total(Indicator) type of product does not have setup mode for output time and Batch One stage output mode does not have twin timer function
Runs when POWER ON When Reset signal is authorized, process value initializes and runs.
Run when START (CP2) is ON within the initial setup value When setup time exceeds, display value will maintain and output (one short output with setting).
Runs when START (CP2) is ON. Output is ON during the set time, and the indicated value is initialized and output is OFF when the set time elapses.
Signal START / ON delay (Counter F output mode operation) - RUN when initial setup value of START (CP2) is ON - When setup time exceeds, display value will increase and put out the output (one short output with Setting
Run when CP2 (START) is ON within the initial setup value and when OFF, it RESET When setup time exceeds, it maintains display value and output time
[HOLD] Setup (when output time [OUTT] is set at 0[HOLD]) Setup Set Time in Run Mode Maintains the indication of initial value when Power is ON Runs when becomes START (CP2). ON/OFF Repetitious Action of control output after reaching the Set Time. Initializes and stops when Reset is ON ONE SHOT TIME Setup (when output time [OUTT] is set at more than 1) Setup Set2 Time in Run Mode. Maintains the indication of initial value when Power is ON Runs when Power is ON One Shot Output after reaching the Set Time. Initializes and stops when Reset is ON Flicker / Signal START Same operation as counter output mode
Signal Addition
When START (CP2) is ON then output become ON and time will display initial value. Time activates the initial value to run when START (CP2) is OFF. The initial value is initialized and output is OFF when the set time elapses.
Signal RUN
Runs when START (CP2) is ON, and resets when START (CP2) is OFF Set Time is first to be reduced during Down Mode Setup.
Batch Counter
setting
Power RUN
Runs after initializing the process value upon the authorization of Run Reset Signal when Power is ON Set Time is first to be reduced during Down Mode Setup.