Professional Documents
Culture Documents
Psychrometrics Rev
Psychrometrics Rev
J.ILANGUMARAN
s c i r t e m o r h c y s P
The Psychrometric Chart
COMFORT We air condition buildings to provide a comfortable environment for the occupants
Relative Humidity:
A minimum RH of 35% is recommended to prevent dry eyes, nose and throat. A maximum RH of 70% is recommended to prevent surface condensation and mould etc. Electrostatic charges can be generated at RH less than 45%.
Air Movement: The terminal velocity, at neck level, should be designed for approximately 0.2m/s. Air Freshness: For body odour dilution of 8l/s of fresh air per person should be introduced.
If smokers are present 16l/s of fresh air is required.
Air Cleanliness: Selection of an adequate filtration system is very important and some types
of air conditioning system permit better air cleansing than others.
Noise Levels: Careful selection of equipment and consideration of both external and internal
noise pollution is important. A certain level of noise is necessary to mask clarity of individual conversations etc.
-5
10
15
20
25
30
35
40
0.01
0.005
RELATIVE HUMIDITY
RH is actual vapour pressure compared to the vapour pressure at saturation for the same dry bulb temperature.
100% Relative Humidty (Saturation Curve) 90% 80% 70% 60% 50% 40% 30% 20% 10%
COOLING HEATING
Saturation Curve
B COOL A Moisture Content 0.01kg/kg
Dewpoint
C
A B
OL O C
Handle
If air is saturated none of the moisture on the wick will evaporate and the WB temperature will be the same as the DB. If the air is less than saturated moisture will evaporate from the wick cooling the WB thermometer. The difference between the WB and DB is called the WB depression.
25
at ur e m pe r W B Te
15 Saturation Curve 5 0 -5 10
C
20
1.32
1.3
1.28
1.26
1.24
1.22
1.2
1.18
1.16
1.14
1.12
Density kg/m3
70
75
100 95 90 85 80 75 70 65 60
10
15
20
25
30
35
40
45
50
55 50 45 -10 -5 0 5 10 15 20 25 30 35 40
0.7
1000
2000
3000
Altitude Metres
PSYCHROMETRIC DATA
1 2 3 4 5 6 7 DB Temperature = 24oC WB Temperature = 17oC RH = 50% Moisture Content = 0.0093kg/kg Total Heat Content = 48kj/kg Dewpoint = 13oC 5 Saturated Moisture Content = 0.0188kg/kg
2 3 6 4
5 1
COOLING HEATING
COOLING CURVES
Due to Cooling Coil inefficiency the air loses moisture before it reaches the saturation curve. The cooling process of a Cooling coil follows the Cooling Curves.
HUMIDIFYING
To add moisture
DEHUMIDIFYING
To remove moisture
DEHUMIDIFYING
HUMIDIFYING
SENSIBLE HEAT:
A change in DB temperature. No change in moisture content.
LATENT HEAT:
A change In moisture content . No change in DB temperature.
TOTAL HEAT
To He tal at
TOTAL COOLING
ta l o T at He
Latent Heat
Sensible Heat
Sensible Cooling
Sensible Heating
Tech
YORK Production System Brian Fossey 03/99 All rights Reserved Copyright 1999 by York International Inc.
Summer
Winter
Tech
Brian Fossey
PERIMETER ZONE
Occupants Gain Sensible & Latent CIRCULATION ZONE Miscellaneous Equipment Sensible Gain
Floor Conduction Sensible Gain Wall Solar & Conduction Sensible Gain to Ceiling Void Glass Solar &Conduction Sensible Gain to Room Infiltration Gain - Sensible & Latent to Room
PERIMETER ZONE
CIRCULATION ZONE
INTERIOR ZONE
ROOM SENSIBLE HEAT FACTOR = SENSIBLE HEAT SENSIBLE HEAT + LATENT HEAT = SENSIBLE HEAT TOTAL HEAT
Room Condition
SHF
Room Condition
RSHF - Room Sensible Heat Factor Room Sensible and Latent Heat Gains from Walls, windows, infiltration, people, lights and miscellaneous equipment
Brian Fossey
A Outside Air Louvre Filter Heating Coil B Cooling Coil Humidifier C Supply Fan D
D A B C
Outside Air Summer and A Entering Cooling Coil Condition Supply Air D Condition
Fan Gain
SUMMER
Tech
Brian Fossey
WINTER
D A B C
yH um
idi f
ier
B B
Heating Coil
Cooling Coil
Humidifier
Supply Supply Air Air Fan G F Return Air B Return Air Fan Air Conditioned Room
Outside Air
Filter
E Recirculated Air
Disharge Air
Discharge Louvre Discharge Damper
Saturation Curve
Maximum 60% RH
Saturation Curve B
SUMMER COOLING
Saturation Curve B Return Air Fan Gain Recirculated Air Condition C
A C
SUMMER COOLING
Saturation Curve B Return Air Fan Gain Recirculated Air Condition C Outside Air and Recirculated Air Mixture Condition D % Outside Air (minimum outside air) % Recirculated Air A D C Outside Air Condition Summer A
SUMMER COOLING
Saturation Curve B C Outside Air and Recirculated Air Mixture Condition D A
Cooling Coil
D C
SUMMER COOLING
Saturation Curve Apparatus Dewpoint (ADP) Cooling Coil Leaving Cooling Coil Condition E B C Outside Air and Recirculated Air Mixture Condition D A
D C
SUMMER COOLING
Supply Air Condition G B C D
Cooling Coil
D C
E G B
WINTER
Saturation Curve Supply Air Fan Gain Supply Air Condition G
Minimum 40% RH
% Recirculated Air A A D C E G B
D C
G B
D C
F G B
AIR HANDLING UNIT WITH RECIRCULATED AIR Outside Air Condition Summer 32oC DB, 19oC WB.
Supply Air Fan Gain
RSHF
Room Condition
Tech
YORK Production System Brian Fossey 03/99 All rights Reserved Copyright 1999 by York International Inc.
AIR HANDLING UNIT WITH RECIRCULATED AIR Outside Air Summer 28oC DB, 19oC WB.
Supply Air Fan Gain Room Condition Outside Air Condition Summer
RSHF
ng
Tech
Brian Fossey
TOTAL CONDITIONS
TSH = Total Sensible Heat = RSH + OASH + *Air conditioning system gains * Includes supply air and return air fan gains, duct leakage sensible losses, return air gains from lights. = Total Latent Heat = RLH + OALH + supply air duct leakage latent losses. = Grand Total Heat = TSH + TLH = TSH/GTH
EFFECTIVE CONDITIONS
ERSH = Effective Room Sensible Heat = RSH + (BF* X OASH) + **Air conditioning system gains * BF = Cooling coil bypass factor (approximately 0.1) ** Includes supply air and return air fan gains, duct leakage sensible losses, return air gains from lights. ERLH = Effective Room Latent Heat = RLH + (BF* X OALH) + **Air conditioning system gains * BF = Cooling coil bypass factor (approximately 0.1) ** Includes supply air and return air fan gains, duct leakage latent losses, return air gains from lights. = Effective Room Total Heat = ERSH + ERLH = Effective Sensible Heat Factor = ERSH / ERTH
ERTH
ESHF
PERIMETER ZONE
Occupants Gain Sensible & Latent CIRCULATION ZONE Miscellaneous Equipment Sensible Gain
Floor Transmission Sensible Gain Wall Solar & Transmission Sensible Gain to Ceiling Void Glass Solar & Transmission Sensible Gain to Room Infiltration Gain - Sensible & Latent to Room
PERIMETER ZONE
CIRCULATION ZONE
INTERIOR ZONE
9.
10. Total
SYSTEM LATENT HEAT GAINS SLH 10. Cooling required to offset supply air duct leakage to areas other than the air conditioned space. =0 11. Heat gain from minimum outside air OALH. To be calculated using Psychrometric data.
20
21oC
pe ra tu re
o
A
C
Te m W B
15
10
10
15
25
30
Tech
YORK Production System Brian Fossey 03/99 All rights Reserved Copyright 1999 by York International Inc.
= OA m3/s X (OA kj/kg - Room kj/kg) X OA kg/m3 = 4.84 X (54 - 50) X 1.19 = 23kW
Outside Air Sensible Heat (OASH) = OA air volume X specific heat X density X (OADB oC - Room DB oC) = OA m3/s X kj/kg oC X kg/m3 X (OADB oC - Room DB oC) = 4.84 X 1.02 X 1.16 X (21 - 23) = -11kW Outside Air Latent Heat (OALH) = OATH - OASH = 23 - -11
= 34kW
EFFECTIVE ROOM SENSIBLE HEAT FACTOR Effective Room Sensible Heat (ERSH) = RSH + (Bypass factor BF X OASH) + SSH
BF assume cooling coil is 10% efficient = 0.1
= 325 + (0.1 X -11) + 89 = 413kW Effective Room Latent Heat (ERLH) = RLH + (Bypass factor BF X OALH) + SLH = 44 + (0.1 X 34) + 0 = 47kW Effective Room Total Heat (ERTH) = ERSH + ERLH = 413 + 47 = 460kW Effective Room Sensible Heat Factor = ERSH/ERTH = 413/460 = 0.9
Room Condition
SHF
21oC
o
A
pe ra tu re Te m C
15
B
ESHF = 0.9 Room 23oC DB, 60% RH
10
10
15
25
30
Tech
YORK Production System Brian Fossey 03/99 All rights Reserved Copyright 1999 by York International Inc.
The ADP is at the point where the ESHF intersects the Saturation Curve.
20
21oC
o
A
pe ra tu re Te m C
15
B
ESHF = 0.9 ADP = 14.2oC DB and WB Room 23oC DB, 60% RH
10
10
15
25
30
Tech
YORK Production System Brian Fossey 03/99 All rights Reserved Copyright 1999 by York International Inc.
GRAND SENSIBLE HEAT FACTOR Total Sensible Heat (TSH) = RSH + OASH + SSH = 325 + (-11) + 89 = 403kW Total Latent Heat (TLH) = RLH + OALH + SLH = 44 + 33 + 0 = 77kW Grand Total Heat (GTH) = TSH + TLH = 403 + 77 = 480kW Grand Sensible Heat Factor
21oC
o
A
pe ra tu re Te m B C
15
GSHF = 0.84 ESHF = 0.9 B o ADP = 14.2 C DB and WB Room 23oC DB, 60% RH
10
10
15
25
30
Tech
YORK Production System Brian Fossey 03/99 All rights Reserved Copyright 1999 by York International Inc.
SUPPLY AIR VOLUME Supply Air Volume m3/s = ERSH/Specific Heat X (Room oC DB - ADP oC DB) X Supply Air Density* = 413kW/ 1.02kj/kgoC X (23 - 14.2) x 1.215kg/m3
38 m3/s
RETURN AIR SYSTEM GAINS Return Air System Heat Gain = (Return Air Fan + Lighting gain to return air) = 10+27 = 37kW Temperature rise due to return air system gain = (Return air System gain) - divided by Specific heat X Supply Air Volume X (1 - % pressurisation air remaining in the building)* X Density of room air = 37kW/ 1.02kj/kgoC X 38m3/s X (1- 0.1) X 1.19kg/m3 = 0.9oC Recirculated Air = 23 + 0.9 = 24oC * Assume that 10% of the total air remains in the space to pressurise the building to offset some of the effects of infiltration and for makeup air to toilet exhaust.
D C
F G B
20
21oC
o
A
pe ra tu re Te m B C
15
10
10
15
25
30
Tech
YORK Production System Brian Fossey 03/99 All rights Reserved Copyright 1999 by York International Inc.
D C
F G B
20
21oC
o
A
pe ra tu re Te m C
15
Mixed Air Condition D GSHF = 0.84 ESHF = 0.9 B o ADP = 14.2 C DB and WB Recirculated Air Condition Room 23oC DB, 60% RH C
10
10
15
25
30
Tech
YORK Production System Brian Fossey 03/99 All rights Reserved Copyright 1999 by York International Inc.
PERCENTAGE OUTSIDE AIR The percentage of Minimum Outside Air to Supply Air Volume = Minimum Outside Air Volume / Supply air Volume = 4.84m3/s divided by 38m3/s 4.84/38 = 12.74%
D C
F G B
21oC
C
o
A
Mixed Air Condition GSHF = 0.84 ESHF = 0.9 ADP = 14.2oC DB and WB
0% 1 0 .2 6 % 87
Te m
pe ra tu re
10
15
10
15
25
30
Tech
YORK Production System Brian Fossey 03/99 All rights Reserved Copyright 1999 by York International Inc.
BYPASS FACTOR BF
Due to the cooling coil inefficiency assume that the air bypassing the coil is 10% of the total air
D C
F G B
BYPASS FACTOR BF
20
pe ra tu re
A D
Recirculated Air Condition Room 23oC DB, 60% RH
Te m
BF Bypass Factor
15
10
10
15
25
30
Tech
YORK Production System Brian Fossey 03/99 All rights Reserved Copyright 1999 by York International Inc.
COOLING COIL
D F
Entering Cooling Coil condition = 23.8oC DB, 18.2oC WB Leaving Cooling Coil condition = 15.5oC DB, 14.8oC WB
ROOM SENSIBLE HEAT FACTOR RSHF Room Sensible Heat RSH = 325kW Room Latent Heat RLH = 44kW Room Total Heat RTH = 325 + 44 = 369kW Room Sensible Heat Factor = 325/369 = 0.88
RSHF = 0.88
D C
F G B
Te m
pe ra tu re
15
Mixed Air Condition ESHF = 0.9 GSHF = 0.88 RSHF = 0.88 B ADP = 14.2oC DB and WB
D
Recirculated Air Condition Room 23oC DB, 60% RH C
10
10
15
25
30
Tech
YORK Production System Brian Fossey 03/99 All rights Reserved Copyright 1999 by York International Inc.
SUPPLY AIR SYSTEM GAINS SYSTEM SENSIBLE HEAT GAINS SSH Supply air fan and motor. Supply air duct heat gain. Cooling required to offset supply air duct leakage to areas other than the air conditioned space. SSH = 28.59 + 23.53 = 52kW Temperature rise due to SUPPLY air system gain = Supply air System gain divided by Density of supply air X Specific heat X Supply Air Volume = 52kW 1.215kg/m3 X 1.02kj/kgoC X 38m3/s = 1.1oC Final Supply Air condition = 15.5 + 1.1 = 16.6oC DB
D C
F G B
20
Te m
pe ra tu re
15
Coil Leaving Condition Mixed Air Condition ESHF = 0.9 GSHF = 0.88 RSHF = 0.89
10
15
25
30
YORK Production System Brian Fossey 03/99 All rights Reserved Copyright 1999 by York International Inc.
SUMMARY - AIR HANDLING UNIT SUMMER CONDITIONS FANS Supply Fan Air Volume = 38m3/s Return Air Fan Air Volume = 38 X 0.9* = 34.2m3/s * 10% air remains in the air conditioned space to offset toilet exhaust and for pressurisation against infiltration. Supply Air condition = 16.6oC DB, 15.2oC WB COOLING COIL Entering Cooling Coil condition = 23.8oC DB, 18.2oC WB Leaving Cooling Coil condition = 15.5oC DB, 14.8oC WB
WINTER MIXED AIR CONDITION Outside Air DB oC = - 4 Recirculated Air DB oC = 21 + 1(Return Air Gain) = 22 Minimum Outside Air = 12.74% 0.1274 X - 4 0.8726 X 22 Mixed Air DB oC = -0.51 = 19.2 = 18.69
D C
F G B
STEAM HUMIDIFIER
20
15
Room Winter B 21oC DB, 50% RH RSHF = 0.89 Recirculated Air Condition C Mixed Air Condition with minimum Outside Air
10
Steam 5 Humidifier
20
25
D C
F G B
SPRAY HUMIDIFIER
20
15
Room Winter B 21oC DB, 50% RH RSHF = 0.89 Recirculated Air Condition C Mixed Air Condition with minimum Outside Air
10
Spray Humidifier
D
Increased Outside Air Volume D
10
15
oC
20
25
HUMIDIFIER SIZING STEAM HUMIDIFIER Increase moisture content by 0.0025kg/kg Density = 1.24 kg/m3 Steam Volume = 38m3/s X 3600 (m3/hour) X 0.0025kg/kg X 1.24kg/m3 = 424kg/Hour SPRAY HUMIDIFIER Increase moisture content by 0.0015kg/kg Density = 1.24 kg/m3
D C
F G B
15
Room Winter B 21oC DB, 50% RH RSHF = 0.89 Recirculated Air Condition C
10
F D
Steam 5 Humidifier
with high percentage 0 Outside Air of minimum Preheater Outside Air Winter
-5
-5
10
15
oC
20
25
D C
F G B
15
Room Winter B 21oC DB, 50% RH RSHF = 0.89 Recirculated Air Condition C
10
Spray Humidifier Preheater Mixed Air Condition with high percentage of D minimum Outside Air 10 15
oC
20
25
D C
REHEAT
20
15
Room Winter B 21oC DB, 50% RH RSHF = 0.89 Recirculated Air Condition C
10
G
Reheater
Spray Humidifier
10
15
oC
20
25