Index

Introduction
Manufacturing Process ..............................................................................................................
Manufacturing of Cables.............................................................................................................
Advantages................................................................................................................................
Cable ranges at a glance............................................................................................................

1
2
3
4,5

Technical detail for


1.1 kV Single Core, PVC Insulated, Un-armoured Cables...........................................................
1.1 kV Two Core, PVC Insulated, Un-armoured Cables..............................................................
1.1 kV Three Core, PVC Insulated, Un-armoured Cables............................................................
1.1 kV Three & Half Core, PVC Insulated, Un-armoured Cables..................................................
1.1 kV Four Core, PVC Insulated, Un-armoured Cables.............................................................

6
7
8
9
10

Technical detail for


1.1 kV Single Core, PVC Insulated, Armoured Cables................................................................
1.1 kV Two Core, PVC Insulated, Armoured Cables....................................................................
1.1 kV Three Core, PVC Insulated, Armoured Cables.................................................................
1.1 kV Three & Half Core, PVC Insulated, Armoured Cables.......................................................
1.1 kV Four Core, PVC Insulated, Armoured Cables...................................................................

11
12
13
14
15

Technical detail for


1.1 kV 1.5 sq. mm Copper Cond. PVC Insulated, Armoured Cables...........................................
1.1 kV 2.5 sq. mm Copper Cond. PVC Insulated, Armoured Cables...........................................

16
17

Technical detail for


1.1 kV Single Core, XLPE Insulated, Un-armoured Cables ........................................................
1.1 kV Two Core, XLPE Insulated, Un-armoured Cables ............................................................
1.1 kV Three Core, XLPE Insulated, Un-armoured Cables .........................................................
1.1 kV Three & Half Core, XLPE Insulated, Un-armoured Cables ...............................................
1.1 kV Four Core, XLPE Insulated, Un-armoured Cables ...........................................................

18
19
20
21
22

Technical detail for


1.1 kV Single Core, XLPE Insulated, Armoured Cables ..............................................................
1.1 kV Two Core, XLPE Insulated, Armoured Cables .................................................................
1.1 kV Three Core, XLPE Insulated,Armoured Cables................................................................
1.1 kV Three & Half Core, XLPE Insulated,Armoured Cables......................................................
1.1 kV Four Core, XLPE Insulated, Armoured Cables .................................................................

23
24
25
26
27

Technical detail for


3.3 kV Single Core, XLPE Insulated, Armoured Cables ..............................................................
3.3 kV Three Core, XLPE Insulated, Armoured Cables ...............................................................

28
29

Technical detail for


3.8/6.6 kV Single Core, XLPE Insulated, Armoured Cables ........................................................
3.8/6.6 kV Three Core, XLPE Insulated, Armoured Cables .........................................................

30
31

Technical detail for


6.6/6.6 kV& 6.35/11Kv Single Core, XLPE Insulated, Armoured Cables .....................................
6.6/6.6 kV& 6.35/11Kv Three Core, XLPE Insulated, Armoured Cables ......................................

32
33

Technical detail for


11/11kV Single Core, XLPE Insulated, Armoured Cables ...........................................................
11/11kV Three Core, XLPE Insulated, Armoured Cables ............................................................

34
35

Technical detail for


12.7/22 kV Single Core, XLPE Insulated, Armoured Cables .......................................................
12.7/22 kV Three Core, XLPE Insulated, Armoured Cables ........................................................

36
37

Technical detail for


19/33 kV Single Core, XLPE Insulated, Armoured Cables ..........................................................
19/33 kV Three Core, XLPE Insulated, Armoured Cables ...........................................................

38
39

Basic assumption for current ratings & rating factors .................................................................. 40,41
Selection criteria of M/VHV cable size for primary distribution ..................................................... 42
Standard Drum lengths of Cables ............................................................................................... 43
Quality Control & Test ................................................................................................................
44
Selection Guide .........................................................................................................................
45
Handling & Storage ....................................................................................................................
46

ISI & CM/L Nos.


IS:1554 (Part-1), 1988
CM/L No.: 81579 82
IS:1554 (Part-2), 1988
CM/L No.: 82594 85
IS:7098 (Part-1), 1988
CM/L No.: 81896 92
IS:7098 (Part-2), 1985
CM/L No.: 83683 89

Introduction

Havells India Ltd, a US 1bn company, and one the largest & India s fastest growing

electrical and power distribution equipment company, manufacturing products


ranging from Building Circuit Protection, Industrial & Domestic Switchgear, Cables
&

ires, Energy Meters, Fans, CFL Lamps, Luminaires for domestic, commercial &

Industrial application, Capacitors and Modular Switches.


Havells owns some of the prestigious global brands like Crabtree, Sylvania,
Concord martin, Lumiance, Claude, Sylvania Linolite, SLI Lighting & enith.
ith 94 branch / representative office and over 8,000 professionals spread over
50 countries across the globe, the group has achieved rapid success in the past few
years. Its 18 state-of-the-art manufacturing plants spread over India, Europe, Latin
America & Africa churns out globally acclaimed products like switchgear,
luminaires, CFLs. etc. Havells India Ltd. is a name synonymous with e cellence and
e pertise in the electrical industry. Its 20,000 strong global distribution network is
always ready to service its clients.
The company has acquired a number of International certifications, like CSA,
KEMA, CB, CE, ASTA, CPA, SEMK , SI IUM Malaysia , SP I G Singapore ,
TSE Turkey , S I Indonesia and EDD Bahrain for various products. Today
Havells and its brands has emerged as the preferred choice for a discerning range of
individual and industrial consumers both in India and abroad.
The essence of its success lies in the e pertise of a fine team of professionals,
strong relationship with associate, the ability to adapt quickly and efficiently and ably
supported with the vision to think ahead.

Manufacturing Process
Copper or
Aluminium Rods
ire to be drawn for required size

Annealing

Drawn Copper wires are annealed

Stranding

equired conductor size to be


manufactured with specified design

Conductor Screening

Stranded conductors are screened with e truded


semiconducting compound Applicable for H.T.
Screened cable only

Insulation

Conductor to be Insulated with PVC /


XLPE as per required specification.

Insulation Screening

Insulated cores are screened with e truded


semiconducting compound Applicable for H.T.
Screened cables only

on metallic part

Core

ewinding & Curing

Insulation Screening
Metallic Part

L.T. Unscreened Cables

H.T. Screened Cables

ire Drawing

Cores to be rewound & cured with specified requirement


for P.V.C. Cables curing not required .
Copper tape shall be applied hellically with 100
coverage over screened cores Applicable for H.T.
Screend core only

Laying Up

All rewound cores to be arranged together to from a Cable


with Specified design.

Inner Sheathing

To be done with required specification

Armouring

To be done with required specification.

uter Sheath

To be done with required specification.

ewinding & Testing

All cables are rewound on wooden Drums & tests Carriedout as per required specification

Packing

All tested and passed cables are packed in required sized


drums prior to despatch.

Manufacturing of Cables
Cables with Aluminium and Copper conductor and polymer insulation are manufactured at Havells India Ltd. Cable orks Alwar.
Essentially cables comprise of conductors, insulation, inner-sheath, armour and outersheath. The brief description of the process is
mentioned as under
CONDUCTOR
Havells Cables are available with both aluminum and copper
conductors. It is manufactured with solid/Stranded Circular/
Shaped Aluminium / Copper Conductor. Stranding makes
Cables fle ible and easy to handle while shaping makes them
compact.
Compaction is provided to all stranded conductor constructions
as under
1.

Circular Conductor :

ith one wire in the centre

conductor contains 6, 12, 18, 24, 30.... wire layers in either


unilay or opposite helical directions. The conductor is sized
upto 92
2.

compaction.

Shaped Conductors : In all multicore cables from


16 Sq. mm size, conductors are shaped . Compaction
degree in multicore power cables is upto 92 .

3.

Segmental Conductor : As a special case Havells cables


of 1600 sq. mm are made up of segmental conductors.

The conductor is manufactured in equal segments and

stabilizers and traces of aromatic polynuclear hydrocarbon.


Thus improving electrical treeing characteristics and
mechanical strength of insulation.
Havells cables are friendly during continuous, emergency and
short circuit conditions.
Though there is no change in basic design of Havells cables yet
the latest manufacturing process gives improved reliability and
compactness to cables. The relative thermal e pansion during
short circuit between dielectric and conductor is therefore limited
to minimum both in PVC & XLPE, thus limiting displacement of
cores in cables during short circuit.
Insulation for Havells Cables are strictly manufactured and
applied over conductor in accordance with ational and
International specifications
ational Specification
International Specifications

IS 5831/IS 7098
BS 6746/BS 5467/IEC 60502

SCREENING
XLPE Cables with rated voltage over 3300V shall be provided

compacted, then laid together. This reduces A.C. losses in the

with conductor and insulation screening as follows

large sized conductor, which are due to skin and pro imity

Conductor Conductor shall be screened with e truded

effects.

Screen

Semiconducting compound as per is 7098 part 2.

Havells has special construction of conductor to suggest to its

Insulation

Insulation screening shall consist of non-metalic

Screen

Part in combination with metalic part. on metalic

customer for meeting their specific need.


Havells copper conductor cables are of the same construction

part shall consist of either semi conducting

that of cables with Aluminium conductor e cept for high tensile

compound tape applied hellically or e truded

strength, superior conductivity, better fle ibility and ease of

layer of semi conducting compound, applied

ointing, copper cables are used in control, instrumentation,

directly over insulation.

winding, submarine, mining and ship wiring etc. etc applications.

overlap as per IS 7098 part 2.

All conductors for Havells cables are manufactured strictly in


accordance with ational and International specifications.
ational specifications

IS 8130

screen, insulation and insulation screen non-metalic part in


one operation through tripple e trusion.

DIELECTRIC INSULATION
ational and

Havells cables are designed and manufactured with polymer


dielectrics to bear thermal and thermomechanical stresses
safely at continuous normal and short circuit temperature
conditions.
Havells cables are available with both thermoplastic & thermo
setting insulations.
- PVC Cables

Thermoplastic dielectric

- XLPE Cables

Thermo setting dielectric

To avoid the cavities and voids formation in dielectric particularly


on bending operation of cable, perfect bonding of insulation and
screening is required. To ensure this Havells applying conductor

International specification IEC 60228 / BS 6360

Insulation for Havells cables is strictly as per


International specifications.

ver this, metalic part

copper tape shall be applied hellically with

Havells PVC cables use PVC compounds that take care of over
load and short circuit current with both coarse & fine protection
systems.
Havells XLPE cables use XLPE compound with anti o idant

LAYING UP
Cores are tested on line during production both for physical and
electrical characteristics. Control is observed within tight
tolerance limits for dimensions in case pf PVC/XLPE insulation.
For multicore cables cores are laid up on our latest laying up
machine equipped with sector correction equipment. In case of
XLPE insulated cores the same are cured so as to impart the
requisite characteristics both electrical and mechanical and then
are laid up.
INNERSHEATH
Laid up cables are provided with inner sheath with high quality of
PVC which acts as bedding for steel wire / strip armouring.
herever required, filler cords are provided to maintain the
circularity to laid up cables.
2

Advantages
In Havells Cable-polymers used for inner sheath are softer than
insulation or outer sheath & are compatible with temperature
ratings of cables & do not have deleteriocus effect on any other
component of cable.
Inner sheath is applied either with e trusion or by wrapping.
In Havells Cables though the inner sheath is closely applied on
the laid up cores, same can be stripped with ease without
damaging insulation.
The inner sheath dimensions are maintained strictly in
accordance with laid down specification .
Specification

For PVC Cables

IS 1554 Part-I & II

For XLPE Cables IS 7098 Part-I & II


Armouring
Mechanical protection to the cable is provided with armouring.
Havells single core cables are armoured with Aluminium or
Aluminium alloy wire/strips, thus avoiding magnetic hysteresis
losses on A. C. System.
Multicore cables are provided with galvanised steel wire/strips.
Havells cables are provided with galvanised wire armouring,
where cables are to run vertically and are sub ected to stresses.
Havells Mining cables are armoured with steel wire and tinned
copper wires, so as to provide conductivity of armour more than
75 of main conductor of cable.
Havells cables armour wires/strips are of low resistivity material
and meet the requirements of IS 3975.
Havells armoured cables are with almost 95

armour coverage.

Outer Sheath
All Havells Cables are provided with PVC/polymer outer sheath.
Havells Cables are manufactured with various characteristics of
sheathing compounds.
General purpose sheathing Compound
Fire etardant Low

IEC 754 Part I

Smoke Compound

IEC 60332 Part I& III


IEEE-383
ASTM-2843
ASTM-2863

Flame etartant Compound F

Each Havells Cable is tested for all applicable outine Tests.


From a lot of Cable one cable of each type is tested for Type
tests, as per relevant specifications.
Havells conduct its testing at Havell s India Ltd. cable plant at
Alwar for acceptance test as per specification.
Testing of Havells Cables are carried out as per Havells
Standards for testing, besides applicable standards.

to EIL Specn.

Ultra Voilet adiations esistance Compound to ASTM G-53.

ork

Advantages of PVC Cables


1.

A non-hygroscopic insulation almost unaffected by


moisture.

2.

on-migration of compound permitting vertical installation.

3.

Complete protection against most forms of electrolytic and


chemical corrosion.

4.

A tough and resilient sheath with e cellent fire - resisting


qualities.

5.

Good ageing characterstics.

6.

ot affected by vibration.

Advantages of XLPE Cables


1.

Higher Current ating.

2.

Higher Short Circuit ating.

3.

Longer Service Life.

4.

For a short time it can withstand ma imum 130oC and is


favourable to endure short circuit stresses.

5.

It is less sensitive to the setting of the network protection.

6.

Because of the thermosetting process taking place due the


effect of cross linking, the crack resistance is increased.

7.

Due to the chemical cross-linking internal stresses are


reduced. Consequently the material is less sensitive
during manufacturing process to the setting of the cooling
gradient.

8.

The thermal resistivity of cross-linked material is


favourably low, compared to thermoplastic material.

9.

The low dielectric loss is a significant advantage.

ST1

Heat resistant Compound for sheath H. . ST2

F LS

Final Testing

10. The e cellent mechanical features of the insulation


improves the protection against e ternal effects.
11. The resistance of the XLPE to acids, alkalies is outstanding
and is often compensating the adverse environmental
influences.

Anti odent and Anti Termite Compound.


PVC compounds used for Havells Cables are of various grades
to meet specifications IS 5831.
In order to be identified, Havells Cables have their name
embossed/printed/indented on outersheath at regular intervals
on the outer sheath of Havells Cables, Voltage Grade, cable
size, trade name & year of manufacture are embossed, as
desired.
Cables are sequentially marked for length at every metre
throughout its length.
3

Cable ranges at a glance


Application
Cables for Power
Supply to Residential,
Commercial &
Industrial units

Heavy Duty XLPE


Power cables for
Power Generation
Distribution

Heavy Duty copper


cables for Coal Mines

Arial Bunched /
Bundled required
for over head power
distribution

Copper Control
Cables for Power
Switch yard Control /
Relay Equipment

Railway Signaling
Cables

Telecom / Switch
board cables for
Indoor Telephones

Coaxial cables for


Telcom / Microwave /
CATV / MATV
industry

Flat cables for


Submersible
Pumps & Motors

Type & Size


PVC/XLPE Power cables for 1.1
& 3.3 kv for Electrical Substations
as per IS 1554 - I & 2
Sizes:
Single Core 10-1000 sq. mm
Multicore 6-630 sq. mm

Options

Cross Sectional View

Conductor - Stranded / Solid, Circular /


Shaped Aluminium / Copper
Insulation - PVC / H PVC
Inner Sheath - PVC / H PVC / F LS / PVC
Unarmoured / Armoured - G.S. ound
Flat Strip or Aluminum ire / Flat Strip
Outer Sheath - PVC/ H PVC/ F LS PVC

ire/

XLPE Power cables


upto 19/33 kv grade 33 kv E
as per IS 7098 - I & II
Sizes :
Single Core : 25 - 1000 sq. mm
Multicore : 25 - 400 sq. mm

Conductor - Circular/Shaped - Aluminum/Copper


Insulation - XLPE
Innersheath - PVC / H PVC / F LS
Unarmoured / Armoured - G.S ound ire /
Flat Strip or Aluminum
ire / Flat Strip
Outersheath - PVC / H PVC / F LS

Stranded bright annnealed


electrolytic copper conductor, PVC/
XLPE insulated / PVC sheathed
upto and including 3.3 kv as per
IS 1554 - I&II / IS 7098 - I & II
Sizes :
Multicore 25 to 400 sq. mm

Conductor - Circular / Shaped


Insulaton - PVC / XLPE
Innersheath- PVC / H PVC / F LS
Unarmoured/Armoured- ound ire/Flat Strip
with conductivity not less than 75 of the phase
Conductor
Outer Sheath - PVC/ H PVC / F LS

PE/XLPE insulated 1.1 kv to 33 kv


as per IS 14255 & IS 7098-II

Conductor - Stranded Circular compacted


Aluminium
Insulation - PE/XLPE
Messenger conductor - All Aluminium Alloy-Bare/
Insulated
Street Light Cond. - Stranded Circular
Compacted Aluminium, Bare/Insulated

Annealed electrolytic copper


conductor, PVC/XLPE insulated,
PVC sheathed 650/ 1100V
grade as per IS 1554-I & IS 7098-I
Sizes :
1.5 / 2.5 sq. mm upto 61 core
4 & 6 Sq. mm upto 4 core

Conductor - Solid/Stranded, Plain /Tinned


Insulation - PVC/H PVC/XLPE
Innersheath - PVC/H PVC/F LS/ ero Halogen
Unarmoured / Armoured - G.S. ound ire/
Flat Strip
Outersheath - PVC/H PVC/F LS/ ero Halogen
Additional Option :
verall shielding with
Aluminum mylar tape with 100 coverage & 25
overlap on laid up cores for static noise re ection.

Annealed Bare Copper conductor,


PVC insulated cores laid up PVC
sheath as per I S-S-63/89 DS
& related specifications
Sizes :
1.5 & 2.5 sq. mm upto 61 core
4 & 6 sq. mm upto 4 core

Screened/Unscreened - Aluminum mylar tape


Unarmoured/Armoured - G.S. ound ire /
Flat Strip/Galvanised Tape
Additional Option :
Insulation/Inner/Outer Sheath - PVC
Inner/Outer sheath - PVC

Annealed Copper conductor,


PVC Insulated as per D T TEC
Spec o G/ I -06/02
Sizes :
0.4 / 0.5 / 0.6 / 0.7 / 0.9 mm

Conductor - Tinned / Plain


Insulation - PVC / H PVC / ylon
Innersheath - PVC/ H PVC/ F LS ero Halogen
Unarmoured / Armoured - G.S. round wire /
Flat Strip
Outer sheath - PVC/H PVC/F LS
AdditIonal Option - Individual / verall pair/
Shielding / Screening

Available in specified G
& U Series as per MIL-C-17 /
BS 2316 / IS 5608 / IS 11967
Sizes :
Suitable for Impedance
of 50 / 75 / 100 / 125 ohms

Conductor - Plain / Tinned / Copper Clad Steel /


Silver Plated
Insulation - Solid / Foam / Semi air spaced
Screen - Single / Double braid
Sheath - PVC / H PVC / F LS / P.E

Stranded Plain copper, PVC


insulated & PVC sheathed of
1.1kV grade as per IS 694
Sizes :
3 core - 1.5 to 50 sq. mm

Insulation - PVC / H PVC


Sheathing - PVC / H PVC

uter-Sheath
Armouring
Inner-Sheath
Insulation
Aluminium /
Copper Conductor

PVC

uter-Sheath

Armouring
PVC Inner-Sheath
Filler
Stranded Conductor
Conductor Screening
XLPE Insulation
Insulation Screening
Metallic Screening

uter-sheath
Armour outer layer
Seprator PVC tape
Armour inner layer
Inner-Sheath
Insulation
Conductor

uter Sheath
Cu Tape Screening
Insulation Screening
XLPE Insulation
Conductor Screening
Conductor
AAA
Messenger
Conductor

uter Sheath
Armour
Inner Sheath
Conductor
Insulation

uter Sheath
Armour
Inner Sheath
Conductor
Insulation

uter Sheath
Armour
Inner Sheath
Bedding Tape
Conductor
Insulation
Twisted Pair
Filler

P.E. Insulation

Sheath

Braid

Insulation
Conductor
Sheath

Cable ranges at a glance


Application

Type & Size

Options

Cross Sectional View

Instrumentation
Signal Cables for
Process control &
Instrumentation

PVC Sheathed 225/650/


1100 V grade cables as per
BS 5308 / DI VDE 0815 &
816 / IS 1554 / IEC 189
Sizes :
0.5/0.75/1.0/1.5 sq. mm

Conductor - Standed / Solid, plain / tinned


Drain ire
Insulation - PVC / H PVC / P.E / ero Halogen
uter Sheath
Armour
Shielding - Individual Pair / over all pairs
Inner Sheath
D r a i n w i r e - S o l i d S t r a n d e dDrain ire
Innersheath - PVC / H PVC
Individual Pair Shield
Conductor
Zero Halogen
Insulation
ound
ire, Flat
Unarmoured/Armoured-G.S.
Strip Outersheath - PVC / H PVC/ F LS /
ero Halogen

Flexible & Cord


Cables for
appliances, Machine
Tools & Equipment
Wiring

Multistrand, fle ible, bright


annealed electrolytic copper
conductor, PVC insulated and
sheathed upto 1100V as per IS 694
Sizes :
Single, Two, Three or
Four core upto 25 sq. mm

Insulation - PVC / H PVC / F LS /


ero Halogen
Unsheathed /Sheathed - PVC / H PVC /
F LS / ero Halogen

Wiring Cables for


electrical industry

Multistrand Fle ible, upto 1100V


grade PVC Cables as per IS 694
Sizes :
Single core 1.0 - 630 sq. mm

Conductor - Bright Annealed Copper


Insulation - PVC/ H PVC/ F LS PVC /
ero Halogen

Energy Cables
for Power Supply to
Telephone
Exchanges / UPS /
Battery Backup /
Equipments

PVC Fle ible Cables upto 1.1kv


grade as per IS 694
Sizes :
1.0 upto 240 sq. mm
Single / Multi Core

Conductor - Stranded / Solid bright


annealed Copper
Insulation - PVC / H PVC / F LS /
ero Halogen

Air Field Lighting


Cables

Stranded plain annealed copper,


PVC insulated & PVC
sheathed of 5 kV grade
Sizes :
Single core 6 /16 sq.mm
and 2 x 6, 16 & 25

Insulation - PVC / XLPE

Conductor
Insulation
Filler
Sheath

Insulation

Conductor

Color Skin
atural PVC
Multistrand Fle ible
Copper Conductor

Insulation
Conductor
Sheath

Inside View - Cable Factory


5

TABLE - 1

TECHNICAL DETAIL FOR HAVELLS 1.1 KV SINGLE CORE,


AL/COPPER COND., PVC INSULATED, UN-ARMOURED CABLES
Cable Code A /
EF SPEC IS 1554PA T-1
PHYSICAL PARAMETERS
SI E
cross-sectional
area Sq MM

4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
C

SS-SECTI

Minimum
o of Strand in
Conductor
Al
Cu

ominal
Thickness of
Insulation
mm

1/7
1/7
6
6
6
6
6
12
15
18
18
30
34
34
53
53
53
53
53

1
1
6
6
6
6
12
15
15
15
30
30
30
53
53
53
53
53
AL VIE

1.0
1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4
2.6
3.0
3.4
3.4
3.4

ominal
Thickness of
outer sheath
mm

Appro .
veral
Diameter
mm

1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
2.0
2.0
2.0
2.0
2.0
2.2
2.2
2.4
2.4
2.6

Appro .

eight of cable in kg /km

ith Al Conductor
A

8
9
10
11
13
14
16
17
19
21
23
25
28
30
35
38
43
48
52

ith Cooper conductor

80
100
120
160
210
250
300
400
500
600
750
900
1100
1350
1700
2150
2750
3300
4100

105
135
180
260
365
460
610
830
1100
1350
1680
2050
2600
3200
4200
5250
6650
8250
10300

C
DUCT
Material - Aluminium /Copper
Shape AL . Cond - 6 & 10 SQMM -Solid circular, 16 sq.mm & above Stranded compacted circular
Copper. Cond - 4 & 6 sq. mm-solid/ stranded non compacted circular, 10 sq. mm & above Stranded compacted circular

I SULATI
PVC Type A of IS 5831 / PTI
H PVC Type-C of IS-5831 , Colour Black
UTE SHEATH PVC T PE ST-1 F IS 5831
PTI
S PVC Type ST-2 of IS 5831/ F T PE/F LS T PE

C L U

F UTE SHEATH BLACK . PTI

S any other colour as per requirement.

- Tabulated appro . net wt. of cables are only guidelines for transportation, loading & unloading purpose..
- Please ref page no 43 for normal delivery lengths & packing details.

ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM

4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000

Ma . Cond. D.C. Appro . Cond. A.C. App. eactance App. Capecitance


ormal Current ating in Amps
esistance at
esistance at
at 50H
of cable
ith Aluminium cond.
ith Copper cond.
o
o
20 Cin hm/km 70 C in hm/km
in ohms/km
in microF/KM
Ground Duct
Air
Ground Duct
Air
Al
Cu
Al
Cu

4.61
3.08
1.91
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
0.0367
0.0291

4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
0.0221
0.0176

5.53
3.70
2.29
1.44
1.04
0.769
0.532
0.384
0.304
0.247
0.197
0.151
0.122
0.0961
0.0759
0.0610
0.0503
0.0422

5.53
3.70
2.20
1.38
0.87
0.63
0.464
0.322
0.232
0.184
0.1488
0.1189
0.0912
0.0733
0.0580
0.0459
0.0368
0.0303
0.0255

0.140
0.127
0.118
0.110
0.105
0.100
0.098
0.091
0.088
0.086
0.085
0.084
0.082
0.080
0.080
0.079
0.077
0.077
0.076

0.58
0.68
0.83
1.01
1.05
1.22
1.22
1.43
1.47
1.62
1.62
1.62
1.72
1.74
1.81
1.86
1.87
1.98
2.20

39
51
66
86
100
120
140
175
195
220
240
270
295
325
345
390
450
500

37
51
65
84
100
115
135
155
170
190
210
225
245
275
295
320
380
415

35
47
64
84
105
130
155
190
220
250
290
335
380
435
480
550
610
680

39
49
65
85
110
130
155
190
220
250
280
305
345
375
400
425
470
530
590

38
48
64
83
110
125
150
175
200
220
245
260
285
310
335
355
375
425
740

35
44
60
82
110
130
165
205
245
280
320
370
425
475
550
590
660
725
870

Short Circuit Current


ating for 1Sec.duration

in K. Amps
Al
Cu

0.304
0.456
0.760
1.220
1.900
2.660
3.800
5.320
7.220
9.120
11.40
14.10
18.20
22.80
30.40
38.00
47.90
60.80
76.00

0.460
0.690
1.150
1.84
2.88
4.03
5.75
8.05
10.90
13.80
17.30
21.30
27.30
34.50
46.00
57.50
72.50
92.00
115.00

ote
ormal current ratings are given in standard conditions as given in page no 40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42

TABLE - 2

TECHNICAL DETAIL FOR HAVELLS 1.1 KV TWO CORES,


AL/ COPPER COND., PVC INSULATED, UN-ARMOURED CABLES
Cable Code A /
ef Specification IS 1554 PA T -1
PHYSICAL PARAMETERS
SI E Cross-sectional
area
sqmm
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
C

SS- SECTI

Minimum o of
Strands in
Conductor
Al
Cu

AL VIE

2
3
4

Minimum
thickness of
inner Sh.
mm

ominal thick.
of UTE
Sheath
mm

Appro .
verall
Diameter
mm

1.0
1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4
2.6
3.0
3.4

0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.40
0.40
0.40
0.50
0.50
0.60
0.70
0.70
0.70

1.80
1.80
1.80
1.80
2.00
2.00
2.00
2.00
2.20
2.20
2.40
2.40
2.60
2.80
3.20
3.40
3.80

14
17
18
17
19
21
24
26
30
32
34
38
42
46
52
54
65

1/7
1/7
6
6
6
6
6
12
15
18
18
30
34
34
53
53
53

1
1
6
6
6
6
12
15
15
15
30
30
30
53
53
53
1

ominal
Thickness of
Insulation
mm

Appro . et t
of cable Kg/KM
ith Al cond
ith Cu Cond.
A
240
300
400
430
450
550
700
850
1150
1300
1600
2000
2500
3000
3800
4800
6000

290
370
520
630
750
980
1300
1700
2300
2800
3450
4300
5500
6700
8750
11000
13800

C
DUCT
Material - Aluminium /Copper
Shape AL . Cond - 6 & 10 SQMM -Solid circular, 16 sqmm & above Stranded compacted shaped

Copper. Cond - 4 & 6sqmm -solid/ stranded non compacted circular, 10sqmm Stranded compacted circular,16sqmm & above Stranded compacted
shaped

I SULATI
PVC Type A of IS 5831/ PTI
H PVC Type -C of IS -5831 , Colour ed & Black
I E SHEATH PVC as per IS 1554PT-1
UTE SHEATH PVC T PE ST-1 F IS 5831
PTI
S PVC T PE ST-2 F IS 5831/ F T PE/ F LS T PE
C L U
F UTE SHEATH BLACK . PTI
S any other colour as per requirement.

Tabulated appro . net wt. of cables are only guidelines for transportation, loading &unloading purpose.
Please ref page no 43 for normal delivery lengths & packing details.

ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM

4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630

Ma . Cond. D.C. Appro . Cond. A.C. App. eactance App.Capecitance


ormal Current ating in Amps
esistance at
esistance at
of cable at 50H
of cable
ith Aluminium cond.
ith Copper cond.
20oC in hm/km 70oC in hm/km
in ohms/km
in microF/KM
Ground Duct
Air
Ground Duct
Air
Al
Cu
Al
Cu

4.61
3.08
1.91
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469

4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283

5.53
3.70
2.29
1.44
1.04
0.769
0.532
0.384
0.304
0.247
0.197
0.151
0.122
0.0961
0.0759
0.0610

5.53
3.70
2.20
1.38
0.87
0.63
0.464
0.322
0.232
0.184
0.1488
0.1189
0.0912
0.0733
0.0580
0.0459
0.0368

0.098
0.096
0.091
0.085
0.083
0.082
0.082
0.076
0.076
0.075
0.074
0.074
0.073
0.073
0.072
0.072
0.072

0.23
0.28
0.34
0.40
0.42
0.48
0.49
0.56
0.58
0.63
0.63
0.64
0.67
0.68
0.70
0.70
0.70

32
40
55
70
90
110
135
160
190
210
240
275
320
355
385
425
465

27
34
45
58
76
92
115
140
170
190
210
240
275
305
345
380
415

27
35
47
59
78
99
125
150
185
210
240
275
325
365
420
475
540

41
50
70
90
115
140
165
205
240
275
310
350
405
450
490
540
640

35
44
58
75
97
120
145
180
215
235
270
300
345
385
485
460
550

35
45
60
78
105
125
155
195
230
265
305
350
410
465
530
605
785

Short Circuit Current


ating for 1Sec.duration

in K. Amps
Al
Cu

0.304
0.456
0.760
1.220
1.900
2.660
3.800
5.320
7.220
9.120
11.40
14.10
18.20
22.80
30.40
38.00
47.90

0.460
0.690
1.150
1.840
2.880
4.030
5.750
8.050
10.90
13.80
17.300
21.280
27.600
34.500
46.000
57.500
72.550

ote
ormal current ratings are given in standard conditions as given in page no 40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42

TABLE - 3

TECHNICAL DETAIL FOR HAVELLS 1.1 KV


THREE CORES, AL/COPPER COND., PVC INSULATED, UN-ARMOURED CABLES
Cable Code A /
ef Specification IS 1554PA T -1
PHYSICAL PARAMETERS
SI E Cross-sectional
area
sqmm
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
C

SS-SECTI

Minimum o of
Strands in
Conductor
Al
Cu
1
1
6
6
6
6
12
15
15
15
30
30
30
53
53
53

AL VIE
1

2
3
4

ominal thick.
Thickness of
Insulation
mm

1/7
1/7
6
6
6
6
6
12
15
18
18
30
34
34
53
53
53

Minimum
thickness of
inner Sh.
mm

1.0
1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4
2.6
3.0
3.4

ominal thick.
of outer
Sheath
mm

0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.40
0.40
0.40
0.50
0.50
0.60
0.60
0.70
0.70
0.70

Appro .
verall
Diameter
mm

1.80
1.80
1.80
1.80
2.00
2.00
2.00
2.20
2.20
2.20
2.40
2.60
2.80
3.00
3.40
3.60
4.00

Appro . et t
of cable Kg/KM
ith Al cond
ith Cu Cond.
A

16
18
19
19
22
24
27
30
34
37
40
44
50
55
62
69
77

270
360
440
460
620
740
940
1200
1600
1900
2300
2750
3500
4300
5450
6900
8700

340
470
650
730
1080
1400
1870
2500
3350
4100
5100
6200
7950
9900
12800
16200
20400

C
DUCT
Material - Aluminium /Copper
Shape AL . Cond - 6 & 10 sqmm - Solid circular, 16 sqmm & above Stranded compacted shaped

Copper . Cond - 4 & 6 sqmm-solid/ stranded non compacted circular, 10 sqmm Stranded compacted circular,16sqmm & above Stranded compacted
shaped

I SULATI
PVC Type A of IS 5831/ PTI
H PVC Type -C of IS -5831 , Colour ed, ellow & Blue
I E SHEATH PVC as per IS 1554PT-1
UTE SHEATH PVC T PE ST-1 F IS 5831
PTI
S PVC T PE ST-2 F IS 5831/ F T PE/ F LS T PE
C L U
F UTE SHEATH BLACK. PTI
S any other colour as per requirement.

Tabulated appro . net wt. of cables are only guidelines for transportation, loading &unloading purpose.
Please ref page no 43 for normal delivery lengths & packing details.

ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM

4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630

Ma . Cond. D.C. Appro . Cond. A.C. pp.. eactance App. Capecitance


ormal Current ating in Amps
esistance at
esistance at
at 50H
of cable
ith Aluminium cond.
ith Copper cond.
20oC in hm/km 70oC in hm/km
in ohms/km
in microF/KM
Ground Duct
Air
Ground Duct
Air
Al
Cu
Al
Cu

4.61
3.08
1.91
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469

4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283

5.53
3.70
2.29
1.44
1.04
0.769
0.532
0.384
0.304
0.247
0.197
0.151
0.122
0.0961
0.759
0.0610

5.53
3.70
2.20
1.38
0.87
0.63
0.464
0.322
0.232
0.184
0.1488
0.1189
0.0912
0.0733
0.0580
0.0459
0.0368

0.098
0.096
0.091
0.085
0.083
0.082
0.082
0.076
0.076
0.075
0.074
0.074
0.073
0.073
0.072
0.072
0.072

0.23
0.28
0.34
0.40
0.42
0.48
0.49
0.56
0.58
0.63
0.63
0.64
0.67
0.68
0.70
0.70
0.70

28
35
46
60
76
92
110
135
165
185
210
235
275
305
335
370
405

23
30
39
50
63
77
95
115
140
155
175
200
235
260
290
320
350

23
30
40
51
70
86
105
130
155
180
205
240
280
315
375
425
480

36
45
60
77
99
120
145
175
210
240
270
300
345
385
425
470
555

30
38
50
64
81
99
125
150
175
195
225
255
295
335
360
390
470

30
39
52
66
90
110
135
165
200
230
265
305
355
400
435
520
675

Short Circuit Current


ating for 1Sec.duration

in K. Amps
Al
Cu

0.304
0.456
0.760
1.220
1.900
2.660
3.800
5.320
7.220
9.120
11.40
14.10
18.20
22.80
30.40
38.00
47.90

0.460
0.690
1.150
1.840
2.880
4.030
5.750
8.050
10.900
13.800
17.300
21.300
27.600
34.500
46.000
57.500
72.500

ote
ormal current ratings are given in standard conditions as given in page no- 40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42

TABLE - 4

TECHNICAL DETAIL FOR HAVELLS 1.1 KV


THREE & HALF CORES, AL/COPPER COND., PVC INSULATED, UN-ARMOURED CABLES
Cable Code A /
ef Specification IS 1554PA T -1
PHYSICAL PARAMETERS
SI E
cross-sectional
area Sq MM

3X25 16
3X35 16
3X50 25
3X70 35
3X95 50
3X120 70
3X150 70
3X185 95
3X240 120
3X300 150
3X400 185
3X500 240
3X630 300
C

SS-SECTI

Minimum nos of
Strands in conductor
Phase
eutral
Al
Cu

6/6
6/6
6/6
12/6
15/6
15/12
15/12
30/15
30/15
30/15
53/30
53/30
53/30

AL VIE
1

2
3
4

6/6
6/6
6/6
12/6
15/6
18/12
18/12
30/15
34/18
34/18
53/30
53/34
53/34

ominal
Thickness of
Insulation mm
Phase / eutral

1.20/1.00
1.20/1.00
1.40/1.20
1.40/1.20
1.60/1.40
1.60/1.40
1.80/1.40
2.00/1.60
2.20/1.60
2.40/1.80
2.60/2.00
3.00/2.20
3.40/2.40

Minimum
Thickness of
inner sheath
mm

0.30
0.30
0.30
0.40
0.40
0.50
0.50
0.50
0.60
0.60
0.70
0.70
0.70

ominal
thickness of
outer sheath
mm

2.00
2.00
2.00
2.20
2.20
2.40
2.40
2.60
3.00
3.20
3.40
3.80
4.00

Appro .
veral
Diameter
mm

24
26
29
32
36
40
44
48
54
62
68
77
87

Appro . et t.
of cable Kg/KM
ith Al Conductor
ith Cu conductor
A

700
850
1050
1400
1800
2200
2600
3200
4100
5000
6300
8000
10000

1264
1600
2100
2900
3900
4850
5800
7200
9300
11500
15000
18500
23500

C
DUCT
Material - Aluminium /Copper
Shape AL . Cond - 6 & 10 sq mm -Solid circular, 16sqmm & above Stranded compacted shaped

Copper . Cond - 4 & 6sqmm -solid/ stranded non compacted circular , 10sqmm Stranded compacted circular,16sqmm & above Stranded compacted
shaped

I SULATI
PVC Type A of IS 5831/ PTI
H PVC Type -C of IS -5831 , Colour ed, ellow, Blue, Black
I E SHEATH PVC as per IS 1554PT-1
UTE SHEATH PVC T PE ST-1 F IS 5831
PTI
S PVC T PE ST-2 F IS 5831/ F T PE/ F LS T PE
C L U
F UTE SHEATH BLACK . PTI
S any other colour as per requirement.

Tabulated appro . net wt. of cables are only guidelines for transportation, loading &unloading purpose ..
Please ref page no 43 for normal delivery lengths & packing details.

ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM

3X25
3X35
3X50
3X70
3X95
3X120
3X150
3X185
3X240
3X300
3X400
3X500
3X630

16
16
25
35
50
70
70
95
120
150
185
240
300

Ma . Cond. D.C. Appro . Cond. A.C. App. eactance App. Capecitance


ormal Current ating in Amps
esistance at
esistance at
of cable at 50H
of cable
ith Aluminium cond.
ith Copper cond.
o
o
20 C in hm/km 70 C in hm/km
in ohms/km
in microF/KM
Ground Duct
Air
Ground Duct
Air
Al
Cu
Al
Cu

1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469

0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283

1.44
1.04
0.769
0.532
0.384
0.304
0.247
0.197
0.151
0.122
0.0961
0.0759
0.0610

0.87
0.63
0.464
0.322
0.232
0.184
0.1488
0.1189
0.0912
0.0733
0.0580
0.0459
0.0368

0.083
0.082
0.082
0.076
0.076
0.075
0.074
0.074
0.073
0.073
0.072
0.072
0.072

0.42
0.48
0.49
0.56
0.58
0.63
0.63
0.64
0.67
0.68
0.70
0.70
0.70

76
92
110
135
165
185
210
235
275
305
335
370
405

63
77
95
115
140
155
175
200
235
260
290
320
350

70
86
105
130
155
180
205
240
280
315
375
425
480

99
120
145
175
210
240
270
300
345
385
425
470
555

81
99
125
150
175
195
225
255
295
335
360
390
470

90
110
135
165
200
230
265
305
355
400
435
520
675

Short Circuit Current


ating for 1Sec.duration

in K. Amps
Al
Cu

1.90
2.66
3.80
5.32
7.22
9.12
11.40
14.10
18.20
22.80
30.40
38.00
47.90

2.88
4.03
5.75
8.05
10.90
13.80
17.30
21.30
27.60
34.50
46.00
57.50
72.50

ote
ormal current ratings are given in standard conditions as given in page no- 40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42

Inner view - Cable Factory

TABLE - 5

TECHNICAL DETAIL FOR HAVELLS 1.1 KV


FOUR CORES, AL/COPPER COND., PVC INSULATED, UN-ARMOURED CABLES
Cable Code A /
ef Specification IS 1554PA T -1
PHYSICAL PARAMETERS
SI E
cross-sectional
area
sq mm

4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
SS- SECTI

Minimum
o of Strand in
Conductor
Cu

Al

1
1
6
6
6
6
12
15
15
15
30
30
30
53
53
53
AL VIE
1

2
3
4

ominal
Thickness of
Insulation
mm

1/7
1/7
6
6
6
6
6
12
15
18
18
30
34
34
53
53
53

1.0
1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4
2.6
3.0
3.4

Minimum
Thickness of
inner sheath
mm

0.30
0.30
0.30
0.30
0.30
0.30
0.40
0.40
0.40
0.50
0.50
0.60
0.60
0.70
0.70
0.70
0.70

ominal
thickness of
outer sheath
mm

1.80
1.80
1.80
2.00
2.00
2.00
2.20
2.20
2.40
2.40
2.60
2.80
3.00
3.40
3.60
4.00
4.00

Appro .
veral
Diameter
mm

16
18
20
23
26
30
34
38
43
46
51
55
60
66
73
82
92

Appro . et t.
of cable Kg/KM
ith Al Conductor
A

300
390
540
560
750
940
1250
1550
2050
2400
2950
3650
4600
5500
6800
8600
11000

ith Cu

400
540
788
950
1370
1800
2500
3300
4400
5380
6670
8250
10550
12950
16720
21000
26000

C
DUCT
Material - Aluminium /Copper
Shape AL . Cond - 6 & 10SQMM -Solid circular, 16sqmm & above Stranded compacted shaped

Copper . Cond - 4 & 6sqmm -solid/ stranded non compacted circular, 10sqmm Stranded compacted circular,16sqmm & above Stranded compacted
shaped

I SULATI
PVC Type A of IS 5831/ PTI
H PVC Type -C of IS -5831 , Colour ed, ellow, Blue, Black
I E SHEATH PVC as per IS 1554PT-1
UTE SHEATH PVC T PE ST-1 F IS 5831
PTI
S PVC T PE ST-2 F IS 5831/ F T PE/ F LS T PE
C L U
F UTE SHEATH BLACK . PTI
S any other colour as per requirement.

Tabulated appro . net wt. of cables are only guidelines for transportation, loading &unloading purpose ..
Please ref page no 43 for normal delivery lengths & packing details.

ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM

4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630

Ma . Cond. D.C. Appro . Cond. A.C. App. eactance App. Capecitance


ormal Current ating in Amps
esistance at
esistance at
of cable at 50H
of cable
ith Aluminium cond.
ith Copper cond.
20oC in hm/km 70oC in hm/km
in ohms/km
in microF/KM
Ground Duct
Air
Ground Duct
Air
Al
Cu
Al
Cu

4.61
3.08
1.91
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469

4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283

5.53
3.70
2.29
1.44
1.04
0.769
0.532
0.384
0.304
0.247
0.197
0.151
0.122
0.0961
0.0759
0.0610

5.53
3.70
2.20
1.38
0.87
0.63
0.464
0.322
0.232
0.184
0.1488
0.1189
0.0912
0.0733
0.0580
0.0459
0.0368

0.098
0.096
0.091
0.085
0.083
0.082
0.082
0.076
0.076
0.075
0.074
0.074
0.073
0.073
0.072
0.072
0.072

0.23
0.28
0.34
0.40
0.42
0.48
0.49
0.56
0.58
0.63
0.63
0.64
0.67
0.68
0.70
0.70
0.70

28
35
46
60
76
92
110
135
165
185
210
235
275
305
335
370
405

23
30
39
50
63
77
95
115
140
155
175
200
235
260
290
320
350

23
30
40
51
70
86
105
130
155
180
205
240
280
315
375
425
480

36
45
60
77
99
120
145
175
210
240
270
300
345
385
425
470
555

30
38
50
64
81
99
125
150
175
195
225
255
295
335
360
390
470

30
39
52
66
90
110
135
165
200
230
265
305
355
400
435
520
675

Short Circuit Current


ating for 1Sec.duration

in K. Amps
Al
Cu

0.304
0.456
0.760
1.220
1.900
2.660
3.800
5.320
7.220
9.120
11.400
14.100
18.200
22.800
30.400
38.000
47.900

0.460
0.690
1.150
1.840
2.880
4.030
5.750
8.050
10.900
13.800
17.300
21.300
27.600
34.500
46.000
57.500
72.500

ote
ormal current ratings are given in standard conditions as given in page no 40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42

10

TABLE - 6

TECHNICAL DETAIL FOR HAVELLS 1.1 KV


SINGLE CORE, AL/COPPER COND., PVC INSULATED, AL WIRE/STRIP ARMOURED CABLES
Cable Code A Fa / Fa , A
a /
a
ef Specification IS 1554PA T -1
PHYSICAL PARAMETERS
SI E
Cross-sectional
area
sqmm

4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000

Minimum
o of
Strands in
Conductor
Al
Cu

1
1
6
6
6
6
12
15
15
15
30
30
30
53
53
53
53
53

SS- SECTI

ominal

Thickness of
Insulation
mm

1/7
1/7
6
6
6
6
6
12
15
18
18
30
34
34
53
53
53
53
53

1.3
1.3
1.3
1.3
1.5
1.5
1.7
1.7
1.9
1.9
2.1
2.3
2.5
2.7
3.0
3.4
3.9
3.9
3.9

AL VIE
1

2
3
4
5

A M U I G ITH FLAT ST IP A Fa / Fa
A M U I G ITH
U D I ES A
a /
a
ominal
Minimum
Appro .
Appro . et t
ominal
Minimum
Appro .
Appro . et t
Thickness Thickness of
verall
of cable Kg/KM
Diameter Thickness of
verall
of cable Kg/KM
ith Al cond ith Cu Cond. of wire
outer sheath Diameter ith Al cond ith Cu Cond.
of armour
outer sheath Diameter
mm
mm
mm
A Fa
Fa
mm
mm
mm
A
a
a

/A
/A
/A
/A
/A
/A
/A
/A
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80

/A
/A
/A
/A
/A
/A
/A
/A
1.40
1.40
1.40
1.40
1.40
1.56
1.56
1.56
1.72
1.88
2.04

/A
/A
/A
/A
/A
/A
/A
/A
21
23
24
27
30
32
37
40
45
49
55

/A
/A
/A
/A
/A
/A
/A
/A
650
750
900
1050
1300
1600
1950
2400
3100
3700
4600

/A
/A
/A
/A
/A
/A
/A
/A
1230
1500
1830
2200
2800
3450
4400
5500
7000
8650
10800

1.40
1.40
1.40
1.40
1.40
1.40
1.40
1.40
1.60
1.60
1.60
1.60
1.60
1.60
2.00
2.00
2.00
2.00
2.50

1.24
1.24
1.24
1.24
1.24
1.24
1.24
1.40
1.40
1.40
1.40
1.40
1.56
1.56
1.56
1.72
1.88
1.88
2.04

11
12
13
14
15
16
18
20
22
24
26
29
32
33
39
42
48
52
59

150
180
200
250
300
350
450
550
700
800
950
1100
1400
1650
2100
2700
3300
4000
4900

180
210
260
350
450
560
750
980
1300
1550
1880
2250
2900
3500
4580
5800
7200
8950
11000

C
DUCT
Material - Aluminium /Copper
Shape AL . Cond - 6 & 10 sqmm - Solid circular, 16 sqmm & above Stranded compacted shaped

Copper . Cond - 4 & 6sqmm -solid/ stranded non compacted circular, 10sqmm Stranded compacted circular,16sqmm & above Stranded compacted
shaped

I SULATI
PVC Type A of IS 5831/ PTI
H PVC Type -C of IS -5831 , Colour Black
I E SHEATH PVC as per IS 1554PT-1
A M U I G Single layer of Aluminium ound wires / Flat Strips
UTE SHEATH PVC T PE ST-1 F IS 5831
PTI
S PVC T PE ST-2 F IS 5831/ F T PE/ F LS T PE
C L U
F UTE SHEATH BLACK. PTI
S any other colour as per requirement.

Tabulated appro . net wt. of cables are only guidelines for transportation, loading &unloading purpose.
Please ref page no 43 for normal delivery lengths & packing details.

ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM

4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000

Ma . Cond. D.C. Appro . Cond. A.C. App. eactance App. Capecitance


ormal Current ating in Amps
esistance at
esistance at
of cable
of cable
ith Aluminium cond.
ith Copper cond.
20oC in hm/km 70oC in hm/km
in at 50H
in microF/KM
Ground Duct
Air
Ground Duct
Air
Al
Cu
Al
Cu
ohms/km

7.41
4.61
3.08
1.91
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
0.0367
0.0291

4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
0.0221
0.0176

8.89
5.53
3.70
2.29
1.44
1.04
0.769
0.532
0.384
0.304
0.247
0.197
0.151
0.122
0.0961
0.076
0.0610
0.0503
0.0422

5.53
3.70
2.20
1.38
0.87
0.63
0.464
0.322
0.232
0.184
0.1488
0.1189
0.0912
0.0733
0.0580
0.0459
0.0368
0.0303
0.0255

0.157
0.148
0.138
0.128
0.120
0.114
0.110
0.103
0.101
0.096
0.094
0.092
0.090
0.088
0.088
0.087
0.086
0.083
0.082

0.48
0.56
0.67
0.81
0.87
1.00
1.03
1.21
1.27
1.42
1.42
1.44
1.53
1.56
1.59
1.67
1.67
1.75
1.94

31
39
51
66
86
100
120
140
175
195
220
240
270
295
325
345
390
450
500

30
37
51
65
84
100
115
135
155
170
190
210
225
245
275
295
320
380
414

27
35
47
64
84
105
130
155
190
220
250
290
335
380
435
480
550
610
680

39
49
65
85
110
130
155
190
220
250
280
305
345
375
400
425
470
530
590

38
48
64
83
110
125
150
175
200
220
245
260
285
310
335
355
375
423
471

35
44
60
82
110
130
165
205
245
280
320
370
425
475
550
590
660
725
870

Short Circuit Current


ating for 1Sec.duration

in K. Amps
Al
Cu

0.304
0.460
0.456
0.690
0.760
1.150
1.220
1.840
1.900
2.880
2.660
4.030
3.800
5.750
5.320
8.050
7.220 10.90
9.120 13.80
11.400 17.30
14.100 21.30
18.200 27.60
22.800 34.50
30.400 46.00
38.000 57.50
47.880 72.50
60.800 92.00
76.000 115.00

ote
ormal current ratings are given in standard conditions as given in page no - 40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42
11

TABLE - 7

TECHNICAL DETAIL FOR HAVELLS 1.1 KV


TWO CORES, AL/COPPER COND., PVC INSULATED, GALVANIZED STEEL WIRE/STRIP ARMOURED CABLES
Cable Code A F / F , A
/
ef Specification IS 1554 PA T -1
PHYSICAL PARAMETERS
SI E
Cross-sectional
area
sqmm

4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630

Minimum
ominal Minimum
A M U I G ITH FLAT ST IP A F / F
A M U I G ITH
U D I ES A
/
o of
Thickness Thickness
ominal
Minimum
Appro .
Appro . et t
ominal
Minimum
Appro .
Appro . et t
Strands in
of
Thickness Thickness of
verall
of cable Kg/KM
Diameter Thickness of
verall of cable Kg/KM
of
Conductor Insulation inner Sh. of armour outer sheath Diameter ith Al cond ith Cu Cond. of armour outer sheath Diameter ith Al cond ith Cu Cond.
Al
Cu
mm
mm
mm
mm
A F
F
mm
mm
mm
A
mm

1
1
6
6
6
6
12
15
15
15
30
30
30
53
53
53

SS- SECTI

1/7
1/7
6
6
6
6
6
12
15
18
18
30
34
34
53
53
53

1.0
1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4
2.6
3.0
3.4

AL VIE
1

0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.40
0.40
0.40
0.50
0.50
0.60
0.70
0.70
0.70

/A
/A
/A
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80

/A
/A
/A
1.40
1.40
1.40
1.40
1.56
1.56
1.56
1.72
1.88
2.04
2.20
2.36
2.68
2.84

/A
/A
/A
18
20
22
25
27
30
32
35
38
43
48
53
56
66

/A
/A
/A
580
700
800
1000
1200
1550
1800
2100
2500
3100
3700
4500
5600
6900

/A
/A
/A
780
1000
1230
1620
2050
2720
3290
3970
4800
6080
7400
9450
11800
14700

1.40
1.40
1.40
1.60
1.60
1.60
1.60
1.60
2.00
2.00
2.00
2.00
2.50
2.50
3.15
3.15
4.00

1.24
1.24
1.24
1.40
1.40
1.40
1.56
1.56
1.56
1.72
1.72
1.88
2.04
2.20
2.52
2.84
3.00

18
19
20
20
22
23
26
29
33
35
37
41
47
50
58
64
72

600
660
750
750
900
1030
1300
1500
2050
2400
2760
3200
4200
5000
6600
8000
11000

650
730
870
950
1200
1450
1900
2350
3200
3900
4600
5500
7200
8700
11500
14000
18800

C
DUCT
Material - Aluminium /Copper
Shape AL . Cond - 6 & 10SQMM -Solid circular, 16sqmm & above Stranded compacted shaped

Copper. Cond - 4 & 6 sqmm-solid/ stranded non compacted circular, 10sqmm Stranded compacted circular,16sqmm & above Stranded compacted
shaped

2
3
4
5

I SULATI
PVC Type A of IS 5831/ PTI
H PVC Type -C of IS -5831 , Colour ed & Black
I E SHEATH PVC as per IS 1554PT-1
A M U I G Single layer of Galvanized steel ound wires / Flat Strips
UTE SHEATH PVC T PE ST-1 F IS 5831
PTI
S PVC T PE ST-2 F IS 5831/ F T PE/ F LS T PE
C L U
F UTE SHEATH BLACK . PTI
S any other colour as per requirement.

Tabulated appro . net wt. of cables are only guidelines for transportation, loading &unloading purpose.
Please ref page no 43 for normal delivery lengths & packing details.

ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM

Ma . Cond. D.C. Appro . Cond. A.C. App. eactance App. Capecitance


ormal Current ating in Amps
esistance at
esistance at
of cable at 50H
of cable
ith Aluminium cond.
ith Copper cond.
20oC in hm/km 70oC in hm/km
in ohms/km
in microF/KM
Ground Duct
Air
Ground Duct
Air
Al
Cu
Al
Cu

4
--4.61
--5.53
0.098
0.23
6
4.61
3.08
5.53
3.70
0.096
0.28
10
3.08
1.83
3.70
2.20
0.091
0.34
16
1.91
1.15
2.29
1.38
0.085
0.40
25
1.20
0.727 1.44
0.87
0.083
0.42
35
0.868 0.524 1.04
0.63
0.082
0.48
50
0.641 0.387 0.769 0.464
0.082
0.49
70
0.443 0.268 0.532 0.322
0.076
0.56
95
0.320 0.193 0.384 0.232
0.076
0.58
120
0.253 0.153 0.304 0.184
0.075
0.63
150
0.206 0.1240 0.247 0.1488
0.074
0.63
185
0.164 0.0991 0.197 0.1189
0.074
0.64
240
0.125 0.0754 0.151 0.0912
0.073
0.67
300
0.100 0.0601 0.122 0.0733
0.073
0.68
400
0.0778 0.0470 0.0961 0.0580
0.072
0.70
500
0.0605 0.0366 0.0759 0.0459
0.072
0.70
630
0.0469 0.0283 0.0610 0.0368
0.072
0.70
ote
ormal current ratings are given in standard conditions as given in page no
multiplied by rating factor as given in page no. 42

32
27
27
41
40
34
35
50
55
45
47
70
70
58
59
90
90
76
78
115
110
92
99
140
135
115
125
165
160
140
150
205
190
170
185
240
210
190
210
275
240
210
240
310
275
240
275
350
320
275
325
405
355
305
365
450
385
345
420
490
425
380
475
540
465
415
540
640
- 40,41 , if site conditions are

Short Circuit Current


ating for 1Sec. duration

in K. Amps
Al
Cu

35
35
0.304
0.460
44
45
0.456
0.690
58
60
0.760
1.150
75
78
1.220
1.840
97
105
1.90
2.880
120
125
2.66
4.030
145
155
3.80
5.750
180
195
5.32
8.050
215
230
7.22
10.90
235
265
9.12
13.80
270
305
11.40
17.30
300
350
14.10
21.30
345
410
18.20
27.60
385
465
22.80
34.50
485
530
30.40
46.00
460
605
38.00
57.50
550
785
47.90
72.50
different, current rating should be

12

TABLE - 8

TECHNICAL DETAIL FOR HAVELLS 1.1 KV


THREE CORES, AL/COPPER COND., PVC INSULATED, GALVANIZED STEEL WIRE/STRIP ARMOURED CABLES
Cable Code A F / F , A
/
ef Specification IS 1554 PA T -1
PHYSICAL PARAMETERS
SI E
Minimum
Crosso of
-sectional Strands in
area
Conductor
sq mm
Al
Cu

4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630

-1
1
6
6
6
6
12
15
15
15
30
30
30
53
53
53

SS- SECTI

1/7
1/7
6
6
6
6
6
12
15
18
18
30
34
34
53
53
53

ominal Minimum
A M U I G ITH FLAT ST IP A F / F
A M U I G ITH
U D I ES A
/
Thickness Thickness
ominal
Minimum
Appro .
Appro . et t
ominal
Minimum
Appro .
Appro . et t
of
Thick. of
Thick. of
verall
of cable Kg/KM
Diameter Thickness of
verall of cable Kg/KM
of
Insulation inner Sh. armour strip outer sheath Diameter
ith Al cond ith Cu Cond. of wire
outer sheath Diameter ith Al cond ith Cu Cond.
mm
mm
mm
mm
A F
F
mm
mm
mm
A
mm

1.0
1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4
2.6
3.0
3.4

AL VIE
1

0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.40
040
0.40
0.50
0.50
0.60
0.60
0.70
0.70
0.70

/A
/A
/A
0.80
080.
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80

/A
/A
/A
1.40
1.40
1.40
1.56
1.56
1.56
1.72
1.88
1.88
2.20
2.36
2.52
2.84
3.00

/A
/A
/A
20
23
24
27
31
35
37
41
46
51
56
63
70
78

/A
/A
/A
700
900
1000
1300
1600
2000
2400
2800
3400
4200
5050
6300
7800
9700

/A
/A
/A
1000
1350
1650
2230
2900
3750
4630
5600
6840
8650
10630
13740
17100
21418

1.40
1.40
1.40
1.60
1.60
1.60
1.60
2.00
2.00
2.00
2.00
2.50
2.50
2.50
3.15
3.15
4.00

1.24
1.24
1.40
1.40
1.40
1.40
1.56
1.56
1.72
1.72
1.88
2.04
2.20
2.36
2.68
3.00
3.00

18
19
21
21
23
26
29
33
37
39
43
49
54
59
68
75
84

600
700
900
950
1100
1300
1600
2150
2650
3000
3550
4600
5600
6600
8700
11000
14000

650
810
1100
1250
1550
1950
2530
3450
4400
5200
6300
8000
10000
12000
16000
20000
25500

C
DUCT
Material - Aluminium /Copper
Shape AL . Cond - 6 & 10SQMM -Solid circular, 16sqmm & above Stranded compacted shaped

Copper . Cond - 4 & 6sqmm -solid/ stranded non compacted circular, 10sqmm Stranded compacted circular,16sqmm & above Stranded compacted

2
3
4
5

shaped

I SULATI
PVC Type A of IS 5831/ PTI
H PVC Type -C of IS -5831 , Colour ed, ellow, Blue
I E SHEATH PVC as per IS 1554PT-1
A M U I G Single layer of Galvanized steel ound wires / Flat Strips
UTE SHEATH PVC T PE ST-1 F IS 5831
PTI
S PVC T PE ST-2 F IS 5831/ F T PE/ F LS T PE
C L U
F UTE SHEATH BLACK . PTI
S any other colour as per requirement.

Tabulated appro . net wt. of cables are only guidelines for transportation, loading &unloading purpose.
Please ref page no 43 for normal delivery lengths & packing details.

ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM

Ma . Cond. D.C. Appro . Cond. A.C. App. eactance App. Capecitance


ormal Current ating in Amps
esistance at
esistance at
at 50H
of cable
ith Aluminium cond.
ith Copper cond.
o
o
20 C in hm/km 70 C in hm/km
in ohms/km
in microF/KM
Ground Duct
Air
Ground Duct
Air
Al
Cu
Al
Cu

4
4.61
5.53
0.098
0.23
6
4.61
3.08
5.53
3.70
0.096
0.28
10
3.08
1.83
3.70
2.20
0.091
0.34
16
1.91
1.15
2.29
1.38
0.085
0.40
25
1.20
0.727 1.44
0.87
0.083
0.42
35
0.868 0.524 1.04
0.63
0.082
0.48
50
0.641 0.387 0.769
0.464
0.082
0.49
70
0.443 0.268 0.532
0.322
0.076
0.56
95
0.320 0.193 0.384
0.232
0.076
0.58
120
0.253 0.153 0.304
0.184
0.075
0.63
150
0.206 0.1240 0.247
0.1488
0.074
0.63
185
0.164 0.0991 0.197
0.1189
0.074
0.64
240
0.125 0.0754 0.151
0.0912
0.073
0.67
300
0.100 0.0601 0.122
0.0733
0.073
0.68
400
0.0778 0.0470 0.0961 0.0580
0.072
0.70
500
0.0605 0.0366 0.0759 0.0459
0.072
0.70
630
0.0469 0.0283 0.0610 0.0368
0.072
0.70
ote
ormal current ratings are given in standard conditions as given in page no
multiplied by rating factor as given in page no. 42

28
35
46
60
76
92
110
135
165
185
210
235
275
305
335
370
405
- 40,41

23
23
36
30
30
45
39
40
60
50
51
77
63
70
99
77
86
120
95
105
145
115 130
175
140 155
210
155 180
240
175 205
270
200 240
300
235 280
345
260 315
385
290 375
425
320 425
470
350 480
555
, if site conditions are

Short Circuit Current


ating for 1Sec.duration

in K. Amps
Al
Cu

30
30
0.304
38
39
0.456
50
52
0.760
64
66
1.220
81
90
1.900
99
110
2.660
125 135
3.800
150 165
5.320
175 200
7.220
195 230
9.120
225 265 11.400
255 305 14.100
295 355 18.200
335 400 22.800
360 435 30.400
390 520 38.000
470 675 47.900
different, current rating

0.460
0.690
1.150
1.840
2.880
4.030
5.750
8.050
10.900
13.800
17.300
21.300
27.600
34.500
46.000
57.500
72.500
should be

13

TABLE - 9

TECHNICAL DETAIL FOR HAVELLS 1.1 KV THREE AND HALF CORES, AL/CUCOPPER COND.,
PVC INSULATED, GALVANIZED STEEL WIRE/STRIP ARMOURED CABLES
Cable Code 3.5 Core - A F / F , A
/
ef Specification IS 1554PA T -1
PHYSICAL PARAMETERS
SI E
Cross-sectional
area
sqmm

3X25 16
3X35 16
3X50 25
3X70 35
3X95 50
3X120 70
3X150 70
3X185 95
3X240 120
3X300 150
3X400 185
3X500 240
3X630 300
C

Minimum
Minimum
ominal
A M U I G ITH FLAT ST IP A F / F
A M U I G ITH
U D I ES A
/
os of
Thickness of Thickness ominal Minimum
Appro .
Appro . et t
ominal
Minimum
Appro .
Appro . et t
of
Strands in
Insulation
Thickness Thickness of
verall
of cable Kg/KM Diameter Thickness of
verall of cable Kg/KM
inner Sh. Strip outer sheath Diameter ith Al cond ith Cu Cond. of wire outer sheath Diameter ith Al cond ith Cu Cond.
Conductor
mm
Phase/ eutral Phase/ eutral mm
mm
mm
mm
A F
F
mm
mm
mm
A

6/6
6/6
6/6
12/6
15/6
15/12
15/12
30/15
30/15
30/15
53/30
53/30
53/30

SS- SECTI

6/6
6/6
6/6
12/6
15/6
18/12
18/12
30/15
34/18
34/18
53/30
53/34
53/34

AL VIE
1

2
3
4
5

1.20/1.00
1.20/1.00
1.40/1.20
1.40/1.20
1.60/1.40
1.60/1.40
1.80/1.40
2.00/1.60
2.20/1.60
2.40/1.80
2.60/2.00
3.00/2.20
3.40/2.40

0.30
0.30
0.30
0.40
0.40
0.50
0.50
0.50
0.60
0.60
0.70
0.70
0.70

0.80
0.80
0.80
0.80
0.80
0.80
0.8
0.80
0.80
0.80
0.80
0.80
0.80

1.40
1.40
1.56
1.56
1.56
1.72
1.88
2.04
2.20
2.36
2.68
2.84
3.00

24
26
30
34
37
41
45
49
55
61
69
77
87

1000
1200
1500
1800
2300
2800
3200
3900
4800
5800
7300
9000
11500

1550
1950
2600
3300
4350
5450
6400
7900
10000
12300
15800
19500
25000

1.60
1.60
1.60
2.00
2.00
2.00
2.00
2.50
2.50
3.15
3.15
4.00
4.00

1.40
1.40
1.56
1.56
1.72
1.88
1.88
2.04
2.30
2.52
2.63
3.00
3.00

26
28
31
36
39
43
47
53
58
65
75
84
92

1300
1450
1800
2400
3000
3500
4000
5200
6400
8200
9900
13500
16000

1850
2150
2800
3800
5000
6100
7200
9200
11500
14500
18400
24000
28500

C
DUCT
Material - Aluminium /Copper
Shape AL . Cond - 6 & 10SQMM -Solid circular, 16sqmm & above Stranded compacted shaped

Copper. Cond - 4 & 6sqmm -solid/ stranded non compacted circular, 10sqmm Stranded compacted circular,16sqmm & above Stranded compacted
shaped

I SULATI
PVC Type A of IS 5831/ PTI
H PVC Type -C of IS -5831 , Colour ed, ellow, Blue, Black
I E SHEATH PVC as per IS 1554PT-1
A M U I G Single layer of Galvanized steel ound wires / Flat Strips
UTE SHEATH PVC T PE ST-1 F IS 5831
PTI
S PVC T PE ST-2 F IS 5831/ F T PE/ F LS T PE
C L U
F UTE SHEATH BLACK . PTI
S any other colour as per requirement.

Tabulated appro . net wt. of cables are only guidelines for transportation, loading &unloading purpose.
Please ref page no 43 for normal delivery lengths & packing details.

ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM

3X25 16
3X35 16
3X50 25
3X70 35
3X95 50
3X120 70
3X150 70
3X185 95
3X240 120
3X300 150
3X400 185
3X500 240
3X630 300

Ma . Cond. D.C. Appro . Cond. A.C. App.. eactance App. Capecitance


esistance at
esistance at
at 50H
of cable
o
o
20 C in hm/km 70 C in hm/km
in ohms/km
in microF/KM
Al
Cu
Al
Cu

1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469

0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283

1.44
1.04
0.769
0.532
0.384
0.304
0.247
0.197
0.151
0.122
0.0961
0.0759
0.0610

0.87
0.63
0.464
0.322
0.232
0.184
0.1488
0.1189
0.0912
0.0733
0.0580
0.0459
0.0368

0.083
0.082
0.082
0.076
0.076
0.075
0.074
0.074
0.073
0.073
0.072
0.072
0.072

0.42
0.48
0.49
0.56
0.58
0.63
0.63
0.64
0.67
0.68
0.70
0.70
0.70

ormal Current ating in Amps


ith Aluminium cond.
ith Copper cond.
Ground Duct
Air
Ground Duct
Air

76
92
110
135
165
185
210
235
275
305
335
370
405

63
77
95
115
140
155
175
200
235
260
290
320
350

70
86
105
130
155
180
205
240
280
315
375
425
480

99
120
145
175
210
240
270
300
345
385
425
470
555

81
99
125
150
175
195
225
255
295
335
360
390
470

90
110
135
165
200
230
265
305
355
400
435
520
675

Short Circuit Current


ating for 1Sec.duration

in K. Amps
Al
Cu

1.90
2.66
3.80
5.32
7.22
9.12
11.40
14.10
18.20
22.80
30.40
38.00
47.90

2.88
4.03
5.75
8.05
10.90
13.80
17.30
21.30
27.60
34.50
46.00
57.50
72.50

ote
ormal current ratings are given in standard conditions as given in page no - 40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42

16 Drawing

ire Machine

14

TABLE - 10

TECHNICAL DETAIL FOR HAVELLS 1.1 KV FOUR CORE, AL/CUCOPPER COND.,


PVC INSULATED, GALVANIZED STEEL WIRE/STRIP ARMOURED CABLES
Cable Code A F / F , A
/
ef Specification IS 1554PT -1
PHYSICAL PARAMETERS
SI E
Cross-sectional
area
sqmm

4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630

Minimum
ominal Minimum
A M U I G ITH FLAT ST IP A F / F
A M U I G ITH
U D I ES A
/
o of
Thickness Thickness
ominal
Minimum
Appro .
Appro . et t
ominal
Minimum
Appro .
Appro . et t
of
Strands in
of
Thickness Thickness of
verall
of cable Kg/KM
Diameter Thickness of
verall of cable Kg/KM
ith Al cond ith Cu Cond.of armour outer sheath Diameter
ith Al cond
ith Cu Cond.
Conductor Insulation inner Sh. of armour outer sheath Diameter
mm
Al
Cu
mm
mm
mm
mm
A F
F
mm
mm
mm
A

1
1
6
6
6
6
12
15
15
15
30
30
30
53
53
53

SS- SECTI

1/7
1/7
6
6
6
6
6
12
15
18
18
30
34
34
53
53
53

1.0
1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4
2.6
3.0
3.4

AL VIE
1

2
3
4
5

0.30
0.30
0.30
0.30
0.30
0.30
0.40
0.40
0.40
0.50
0.50
0.60
0.60
0.70
0.70
0.70
0.70

/A
/A
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

/A
/A
1.40
1.40
1.40
1.40
1.56
1.56
1.72
1.88
1.88
2.04
2.36
2.52
2.84
3.00
3.00

/A
/A
21
22
25
28
32
35
40
43
48
52
59
67
74
80
90

/A
/A
750
860
1100
1300
1600
2000
2600
3050
3600
4300
5400
6600
8200
10500
13000

/A
/A
998
1260
1720
2170
2850
3740
5000
6030
7325
8890
11355
14050
18128
22900
28625

1.40
1.40
1.60
1.60
1.60
1.60
2.00
2.00
2.00
2.00
2.5
2.5
2.50
3.15
3.15
4.00
4.00

1.24
1.24
1.40
1.40
1.40
1.56
1.56
1.56
1.72
1.88
2.04
2.20
2.36
2.68
2.84
3.00
3.00

18
21
22
23
27
30
34
37
42
47
51
56
62
70
76
86
96

650
880
900
1120
1400
1600
2200
2650
3300
3850
4850
5800
7000
9200
11000
15000
18000

800
1030
1150
1520
2020
2470
3445
4390
5660
6830
8575
10390
12960
16650
20930
27400
33630

C
DUCT
Material - Aluminium /Copper
Shape AL . Cond - 6 & 10SQMM -Solid circular, 16sqmm & above Stranded compacted shaped

Copper . Cond - 4 & 6sqmm -solid/ stranded non compacted circular , 10sqmm Stranded compacted circular,16sqmm & above Stranded
compacted shaped

I SULATI
PVC Type A of IS 5831/ PTI
H PVC Type -C of IS -5831 , Colour ed, ellow, Blue, Black
I E SHEATH PVC as per IS 1554PT-1
A M U I G Single layer of Galvanized steel ound wires / Flat Strips
UTE SHEATH PVC T PE ST-1 F IS 5831
PTI
S PVC T PE ST-2 F IS 5831/ F T PE/ F LS T PE
C L U
F UTE SHEATH BLACK . PTI
S any other colour as per requirement.

Tabulated appro . net wt. of cables are only guidelines for transportation, loading &unloading purpose ..
Please ref page no 43 for normal delivery lengths & packing details.

ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM

4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630

Ma . Cond. D.C. Appro . Cond. A.C. App. eactance App. Capecitance


ormal Current ating in Amps
esistance at
esistance at
of cable at 50H
of cable
ith Aluminium cond.
ith Copper cond.
20oC in hm/km 70oC in hm/km
in ohms/km
in micro F/KM
Ground Duct
Air
Ground Duct
Air
Al
Cu
Al
Cu

4.61
3.08
1.91
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469

4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283

5.53
3.70
2.29
1.44
1.04
0.769
0.532
0.384
0.304
0.247
0.197
0.151
0.122
0.0961
0.0759
0.0610

5.53
3.70
2.20
1.38
0.87
0.63
0.464
0.322
0.232
0.184
0.1488
0.1189
0.0912
0.0733
0.0580
0.0459
0.0368

0.098
0.096
0.091
0.085
0.083
0.082
0.082
0.076
0.076
0.075
0.074
0.074
0.073
0.073
0.072
0.072
0.072

0.23
0.28
0.34
0.40
0.42
0.48
0.49
0.56
0.58
0.63
0.63
0.64
0.67
0.68
0.70
0.70
0.70

28
35
46
60
76
92
110
135
165
185
210
235
275
305
335
370
405

23
30
39
50
63
77
95
115
140
155
175
200
235
260
290
320
350

23
30
40
51
70
86
105
130
155
180
205
240
280
315
375
425
480

36
45
60
77
99
120
145
175
210
240
270
300
345
385
425
470
555

30
38
50
64
81
99
125
150
175
195
225
255
295
335
360
390
470

30
39
52
66
90
110
135
165
200
230
265
305
355
400
435
520
675

Short Circuit Current


ating for 1Sec.duration

in K. Amps
Al
Cu

0.304
0.456
0.760
1.220
1.900
2.660
3.800
5.320
7.220
9.120
11.40
14.10
18.20
22.80
30.40
38.00
47.90

0.460
0.690
1.150
1.840
2.880
4.030
5.750
8.050
10.900
13.800
17.300
21.300
27.600
34.500
46.000
57.500
72.500

ote
ormal current ratings are given in standard conditions as given in page no - 40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42

15

TABLE - 11

TECHNICAL DETAIL FOR HAVELLS 1.1 KV 1.5 SQ MM COPPER COND., PVC INSULATED,
GALVANIZED STEEL WIRE/STRIP ARMOURED CONTROL CABLES
Cable Code
/ F /
ef Specification IS 1554PA T -1
PHYSICAL PARAMETERS
o
of
Cores

2
3
4
5
6
7
10
12
14
16
19
24
27
30
37
40
44
52
61
C

Minimum
Thick.
om thick.
of inner of outer
Sheath
Sheath

U A M U ED
Appro .
Appro . et t
verall
of cable Kg/KM
Diameter mm

mm

mm

Solid cond

Std. Cond.

Solid cond

Std. Cond.

0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.40
0.40

1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.2

12
12.5
13
14
15
15
18
19
20
21
22
25
26
27
28
29
31
33
35

12
13
14
14
15
15
19
20
20
21
23
26
27
28
29
30
33
35
37

180
200
230
250
290
310
420
470
530
600
700
850
920
1000
1200
1270
1400
1650
1850

180
210
250
250
300
320
450
500
550
600
720
900
995
1050
1240
1300
1450
1700
1950

SS- SECTI

A
ominal
Thickness
of Armour
strip mm

/A
/A
/A
/A
/A
/A
/A
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80

M U ED
Minimum
Thickness
of outr sh.

ITH FLAT ST IPS F


Appro .
Appro . et t
verall
of cable Kg/KM
Diameter mm

mm

Solid cond

Std. Cond.

/A
/A
/A
/A
/A
/A
/A
1.24
1.40
1.40
1.40
1.40
1.40
1.40
1.40
1.40
1.56
1.56
1.56

/A
/A
/A
/A
/A
/A
/A
19
20
21
22
25
26
27
29
30
32
34
35

/A
/A
/A
/A
/A
/A
/A
20
21
22
23
27
27
28
30
31
34
35
37

Solid cond

Std. Cond.

/A
/A
/A
/A
/A
/A
/A
700
800
850
950
1150
1250
1330
1530
1650
1850
2050
2300

/A
/A
/A
/A
/A
/A
/A
745
820
900
1000
1200
1300
1400
1600
1750
1950
2150
2450

A M
ominal
Dia of
Armour

wire mm

1.40
1.40
1.40
1.40
1.40
1.40
1.40
1.60
1.60
1.60
1.60
1.60
1.60
1.60
1.60
1.60
1.60
2.00
2.00

U ED ITH
U D I ES
Minimum
Appro .
Appro . et t
Thickness
verall
of cable Kg/KM
of outr sh. Diameter mm
with
with
mm

1.24
1.24
1.24
1.24
1.24
1.24
1.40
1.40
1.40
1.40
1.40
1.40
1.40
1.40
1.40
1.56
1.56
1.56
1.56

Solid cond Std. Cond. Solid cond Std. Cond.

13
14
15
16
17
17
20
21
22
23
24
27
28
29
30
32
34
36
38

14
14
15
16
17
17
21
22
23
24
25
28
29
30
32
35
36
38
40

400
450
500
520
580
650
800
940
1000
1100
1200
1450
1500
1650
1850
2000
2200
2700
3000

420
450
500
550
600
680
840
970
1050
1100
1250
1500
1550
1700
1950
2100
2300
2800
3100

AL VIE
1
2

CONDUCTOR : MATERIAL : Annealed bare copper / option - Tinned Construction : SOLID / STRANDED
INSULATION MATERIAL : PVC Type Aof IS :5831/ OPTION : HR PVC ( Type -C of IS -5831) Nominal insulation thickness - 0.80mm
Cores identification : Up to 5Cores by colour coding & more tthan 5 cores 5cores : By colour coding / Nos. printing on cores as per IS :1554pt-1

INNER SHEATH : Extruded PVC as per IS :1554PT-1

ARMOURING : Single layer of Galvanized steel Round wires / Flat Strips as applicable

OUTER SHEATH : PVC TYPE ST-1 OF IS : 5831 OPTIONS : PVC TYPE ST-2 OF IS : 5831/ FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : any other colour as per requirement

~ Tabulated appro . net wt. of cables are only guidelines for transportation, loading &unloading purpose .
~ Please ref page no 43 for normal delivery lengths & packing details.

ELECTRICAL PARAMETERS
Ma . Cond. D.C.
esistance at
20oC in hm/km

2
3
4
5
6
7
10
12
14
16
19
24
27
30
37
40
44
52
61

12.10
12.10
12.10
12.10
12.10
12.10
12.10
12.10
12.10
12.10
12.10
12.10
12.10
12.10
12.10
12.10
12.10
12.10
12.10

App. Cond. A.C.


esistance at
in hm/km
o
at 70 C
at 85oC

14.52
14.52
14.52
14.52
14.52
14.52
14.52
14.52
14.52
14.52
14.52
14.52
14.52
14.52
14.52
14.52
14.52
14.52
14.52

15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2

eactance
Appro
of cable
Capecitance
at 50H

of cable

Ground

0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20

23
21
21
21
15
14
13
12
11
11
10
9
9
9
8
8
7
6
6

in ohms/km in microF/KM

0.112
0.112
0.112
0.112
0.112
0.112
0.112
0.112
0.112
0.112
0.112
0.112
0.112
0.112
0.112
0.112
0.112
0.112
0.112

ormal Current ating in Amps


ith general insulation

Short Circuit Current

ith H. . insulation

Duct

Air

Ground

Duct

20
17
17
17
13
13
11
10
10
9
9
8
8
7
7
7
7
6
6

20
17
17
17
13
13
11
10
10
9
9
8
8
7
7
7
7
6
6

26
24
24
24
17
16
15
14
13
13
11
10
10
10
9
9
8
7
7

24
21
21
21
16
15
13
12
12
11
11
10
10
8
8
8
7
7
7

Air

24
21
21
21
16
15
13
12
12
11
11
10
10
8
8
8
7
7
7

ating for 1Sec.duration


ith Gen. Purpose

Insulation

0.173
0.173
0.173
0.173
0.173
0.173
0.173
0.173
0.173
0.173
0.173
0.173
0.173
0.173
0.173
0.173
0.173
0.173
0.173

ith Heat esis.

Insulation

0.156
0.156
0.156
0.156
0.156
0.156
0.156
0.156
0.156
0.156
0.156
0.156
0.156
0.156
0.156
0.156
0.156
0.156
0.156

ote
ormal current ratings are given in standard conditions as given in page no -40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42
16

TABLE - 12

TECHNICAL DETAIL FOR HAVELLS 1.1 KV 2.5 SQ MM COPPER COND.,


PVC INSULATED, |GALVANIZED STEEL WIRE/STRIP ARMOURED CONTROL CABLES
Cable Code
/ F /
ef Specification IS 1554PA T -1
PHYSICAL PARAMETERS
o
of
Cores

Minimum
Thick.
om thick.
of inner of outer
Sheath
Sheath

U A M U ED
Appro .
Appro . et t
verall
of cable Kg/KM
Diameter mm
Armour outer

A M U ED ITH FLAT ST IPS F


ominal Minimum
Appro .
Thickness Thickness
verall
of armour of outr. sth.
Diameter mm

mm

mm

Solid cond

Std. Cond.

Solid cond

Std. Cond.

0.30

1.8

13

13

220

240

/A

/A

/A

/A

/A

/A

1.40

1.24

14

15

480

500

3
4
5
6
7
10
12
14
16
19
24
27
30
37
40
44
52
61

0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.40
0.40
0.40
0.40
0.40

1.8
1.8
1.8
1.8
1.8
1.8
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.2
2.2
2.2
2.2
2.2

14
15
16
17
17
20
21
22
24
25
28
29
30
33
34
36
38
40

14
15
16
17
17
21
22
24
25
26
30
31
32
34
36
38
40
43

260
310
340
390
424
570
670
750
840
950
1200
1300
1400
1700
1850
2000
2350
2700

270
320
350
420
440
600
700
800
900
1000
1260
1350
1500
1800
1900
2100
2450
2800

/A
/A
/A
/A
/A
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80

/A
/A
/A
/A
/A
1.40
1.40
1.40
1.40
1.40
1.40
1.40
1.56
1.56
1.56
1.56
1.56
1.56

/A
/A
/A
/A
/A
21
22
23
24
25
29
30
31
34
35
37
39
41

/A
/A
/A
/A
/A
22
23
24
25
26
30
31
32
35
36
37
41
43

/A
/A
/A
/A
/A
850
950
1050
1120
1250
1550
1650
1800
2100
2300
2500
2850
3250

/A
/A
/A
/A
/A
900
1000
1035
1150
1330
1630
1750
1920
2225
2400
2600
2950
3350

1.40
1.40
1.40
1.40
1.40
1.60
1.60
1.60
1.60
1.60
1.60
1.60
1.60
2.00
2.00
2.00
2.00
2.00

1.24
1.24
1.24
1.24
1.24
1.40
1.40
1.40
1.40
1.40
1.56
1.56
1.56
1.56
1.56
1.56
1.72
1.72

15
16
17
19
19
23
24
25
26
27
31
32
33
36
37
40
42
44

16
17
18
20
20
24
25
26
27
28
32
33
34
37
39
41
43
46

530
600
640
730
760
1100
1180
1300
1400
1550
1900
2050
2200
2800
2950
3200
3600
4000

550
620
680
750
790
1150
1250
1350
1450
1620
2000
2100
2250
2900
3100
3350
3700
4200

AL VIE
1
2
3
4
5

DUCT

mm

Solid cond

Std. Cond.

Solid cond

Std. Cond.

wire mm

mm

Appro . et t
of cable Kg/KM
Diameter mm

SS- SECTI

strip mm

A M U ED ITH
U D I ES
Appro . et t
Minimum Minimum
Appro .
of cable Kg/KM
Dia of
Thickness
verall
Armour
outer sheath

Solid cond Std. Cond. Solid cond Std. Cond.

MATE IAL Annealed bare copper / option Tinned Construction S LID / ST A DED

I SULATI
MATE IAL PVC Type A of IS 5831/ PTI
H PVC Type -C of IS -5831 ominal insulation thickness 0.90mm Cores identification Up to 5Cores by colour coding & more than 5 cores 5cores By colour coding / os. printing on
cores as per IS 1554pt-1
I

E SHEATH E truded PVC as per IS 1554PT-1

A M U I G Single layer of Galvanized steel ound wires / Flat Strips as applicable


UTE SHEATH PVC T PE ST-1 F IS 5831
C L U

F UTE SHEATH BLACK . PTI

PTI

S PVC T PE ST-2 F IS 5831/ F T PE/ F LS T PE

S any other colour as per requirement.

Tabulated appro . net wt. of cables are only guidelines for transportation, loading &unloading purpose .
Please ref page no 43 for normal delivery lengths & packing details.

ELECTRICAL PARAMETERS
Ma . Cond. D.C.
esistance at
20oC in hm/km

2
3
4
5
6
7
10
12
14
16
19
24
27
30
37
40
44
52
61

7.41
7.41
7.41
7.41
7.41
7.41
7.41
7.41
7.41
7.41
7.41
7.41
7.41
7.41
7.41
7.41
7.41
7.41
7.41

App. Cond. A.C.


esistance at
in hm/km
at 70oC
at 85oC

8.89
8.89
8.89
8.89
8.89
8.89
8.89
8.89
8.89
8.89
8.89
8.89
8.89
8.89
8.89
8.89
8.89
8.89
8.89

9.34
9.34
9.34
9.34
9.34
9.34
9.34
9.34
9.34
9.34
9.34
9.34
9.34
9.34
9.34
9.34
9.34
9.34
9.34

eactance
of cable
at 50H
in ohms/km

0.107
0.107
0.107
0.107
0.107
0.107
0.107
0.107
0.107
0.107
0.107
0.107
0.107
0.107
0.107
0.107
0.107
0.107
0.107

Appro
ormal Current ating in Amps
ith general insulation
ith H. . insulation
Capecitance
of cable
Ground Duct
Air
Ground Duct
Air
in microF/KM

0.22
0.22
0.22
0.22
0.22
0.22
0.22
0.22
0.22
0.22
0.22
0.22
0.22
0.22
0.22
0.22
0.22
0.22
0.22

32
27
27
27
21
20
18
17
16
15
14
13
12
12
11
11
10
9
8

27
24
24
24
18
17
15
14
13
13
12
11
10
10
9
9
9
8
8

27
24
24
24
18
17
15
14
13
13
12
11
10
10
9
9
9
8
8

38
30
30
30
24
22
20
19
18
17
16
14
13
13
12
12
11
10
9

32
28
28
28
21
20
16
16
15
15
14
13
12
12
10
10
10
10
9

32
28
28
28
21
20
16
16
15
15
14
13
12
12
10
10
10
10
9

Short Circuit Current


ating for 1Sec.duration

General
Insulation

Heat
Insulation

0.288
0.288
0.288
0.288
0.288
0.288
0.288
0.288
0.288
0.288
0.288
0.288
0.288
0.288
0.288
0.288
0.288
0.288
0.288

0.260
0.260
0.260
0.260
0.260
0.260
0.260
0.260
0.260
0.260
0.260
0.260
0.260
0.260
0.260
0.260
0.260
0.260
0.260

ote
ormal current ratings are given in standard conditions as given in page no -40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42
17

TABLE - 13

TECHNICAL DETAIL FOR HAVELLS 1.1 KV SINGLE CORE,


AL/COPPER COND., XLPE INSULATED, UN-ARMOURED CABLES
Cable Code A2X /2X
EF SPEC IS 7098PT-1
PHYSICAL PARAMETERS
SI E
cross-sectional
area Sq MM

4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
SS-SECTI

Minimum
o of Strand in
Conductor
Al
Cu

1
1
6
6
6
6
12
15
15
15
30
30
30
53
53
53
53
53
AL VIE
1

2
3

1/7
1/7
6
6
6
6
6
12
15
18
18
30
34
34
53
53
53
53
53

ominal
Thickness of
Insulation
mm

0.7
0.7
0.7
0.7
0.9
0.9
1.0
1.1
1.1
1.2
1.4
1.6
1.7
1.8
2.0
2.2
2.4
2.6
2.8

ominal
Thickness of
outer sheath
mm

1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
2.0
2.0
2.0
2.0
2.2
2.2
2.2
2.4
2.6

Appro .
veral
Diameter
mm

Appro .

eight of cable in kg /km

ith Al Conductor
A2X

8
9
10
11
12
13
15
16
18
20
22
24
27
30
33
36
40
47
51

ith Cooper conductor


2X

70
80
100
130
180
230
300
370
460
550
620
820
1000
1200
1550
1900
2400
3000
3750

95
120
160
230
335
450
610
800
1050
1300
1550
1950
2500
3050
4000
5000
6300
7950
9950

C
DUCT
Material - Aluminium /Copper
Shape AL . Cond - 6 & 10 SQMM -Solid circular, 16 sq.mm & above Stranded compacted circular
Copper. Cond - 4 & 6 sq. mm-solid/ stranded non compacted circular, 10 sq. mm & above Stranded compacted circular

I SULATI
Crosslinked Polyethylene XLPE
UTE SHEATH PVC T PE ST-2 F IS 5831
C L U
F UTE SHEATH BLACK . PTI

atural colour
PTI
S F T PE/ F LS T PE
S any other colour as per requirement.

- Tabulated appro . net wt. of cables are only guidelines for transportation, loading & unloading purpose..
- Please ref page no 43 for normal delivery lengths & packing details.

ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM

4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000

Ma . Cond. D.C. Appro . Cond. A.C. App. eactance App. Capecitance


ormal Current ating in Amps
esistance at
esistance at
at 50H
of cable
ith Aluminium cond.
ith Copper cond.
o
o
20 C in hm/km 90 C in hm/km
in ohms/km
in microF/KM
Ground Duct
Air
Ground Duct
Air
Al
Cu
Al
Cu

4.61
3.08
1.91
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
0.0367
0.0291

4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
0.0221
0.0176

5.90
3.94
2.44
1.54
1.11
0.820
0.567
0.411
0.325
0.265
0.211
0.162
0.130
0.1023
0.0808
0.0648
0.0530
0.0444

5.90
3.94
2.34
1.47
0.931
0.671
0.495
0.343
0.248
0.197
0.159
0.127
0.0976
0.0778
0.0618
0.0489
0.0391
0.0319
0.0268

0.136
0.128
0.118
0.108
0.102
0.097
0.092
0.088
0.085
0.082
0.082
0.082
0.079
0.078
0.077
0.076
0.075
0.075
0.068

0.29
0.34
0.42
0.50
0.52
0.60
0.63
0.68
0.79
0.79
0.79
0.79
0.84
0.86
0.88
0.90
0.94
0.97
1.01

48
62
81
99
117
138
168
204
230
265
295
340
390
450
500
555
625
690

45
62
80
90
110
125
155
185
210
230
260
300
335
380
430
485
530
570

45
61
83
115
135
170
210
255
300
342
385
450
519
605
700
809
935
1065

48
60
80
104
130
155
185
225
265
300
335
380
435
490
550
610
680
740
780

47
59
78
102
115
140
165
200
235
265
300
335
385
430
480
530
590
630
660

45
57
77
106
145
175
215
270
330
380
430
495
590
670
780
900
1020
1140
1250

Short Circuit Current


ating for 1Sec.duration

in K. Amps
Al
Cu

0.376
0.564
0.940
1.504
2.350
3.290
4.700
6.580
8.930
11.28
14.10
17.39
22.56
28.20
37.60
47.00
59.22
75.20
94.00

0.572
0.858
1.430
2.288
3.575
5.005
7.150
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
71.50
90.09
114.40
143.00

ote
ormal current ratings are given in standard conditions as given in page no -40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42

18

TABLE - 14

TECHNICAL DETAIL FOR HAVELLS 1.1 KV TWO CORE, AL/COPPER COND.,


XLPE INSULATED, UN-ARMOURED CABLES
Cable Code A2X / 2X
ef Specification IS 7098PA T -1
PHYSICAL PARAMETERS
SI E
Cross-sectional
area
sqmm
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
C

Minimum
o of
Strands in
Conductor
Al
Cu
1/7
1
1/7
1
6
6
6
6
6
6
6
6
6
12
12
15
15
15
18
15
18
30
30
30
34
30
34
53
53
53
53
53
53

SS- SECTI

AL VIE
1

2
3
4

ominal
Thickness of
Insulation

Minimum
Thickness of
inner sheath

ominal
Thickness of
UTE sheath

mm
0.7
0.7
0.7
0.7
0.9
0.9
1.0
1.1
1.1
1.2
1.4
1.6
1.7
1.8
2.0
2.2
2.4

mm
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.40
0.40
0.40
0.50
0.50
0.60
0.60
0.70
0.70

mm
1.80
1.80
1.80
1.80
2.00
2.00
2.00
2.00
2.20
2.20
2.20
2.40
2.60
2.80
3.00
3.40
3.60

Appro .
overall
Diameter
mm
13
14
17
17
19
20
22
25
28
31
33
37
41
44
48
54
62

Appro . et t
of cable Kg/KM
ith Al Cond
A2X
200
330
350
310
400
480
590
760
1000
1200
1400
1750
2000
2700
3350
4200
5300

ith Cu Cond.
2X
250
400
470
500
700
900
1200
1630
2200
2700
3300
4000
5000
6400
8300
10400
13000

C
DUCT
Material - Aluminium /Copper
Shape AL . Cond - 6 & 10 sqmm -Solid circular, 16sqmm & above Stranded compacted shaped

Copper . Cond - 4 & 6 sqmm -solid/ stranded non compacted circular, 10 sqmm Stranded compacted circular,16 sqmm & above Stranded compacted
shaped

I SULATI
Crosslinked Polyethylene XLPE
ed & Black colour
I E SHEATH PVC as per IS 7098PT-1
UTE SHEETH PVC T PE ST-2 F IS 5831 -- PTI
S F T PE/F LS T PE
C L U
F UTE SHEATH BLACK, PTI
S any other colour as per requirement.

Tabulated appro . net wt. of cables are only guidelines for transportation, loading &unloading purpose.
Please ref page no 43 for normal delivery lengths & packing details.

ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM

Ma . Cond. D.C. Appro . Cond. A.C. App. eactance App. Capecitance


ormal Current ating in Amps
esistance at
esistance at
at 50H
of cable
ith Aluminium cond.
ith Copper cond.
20oC in hm/km 90oC in hm/km
in ohms/km
in microF/KM
Ground Duct
Air
Ground Duct
Air
Al
Cu
Al
Cu

4
4.61
5.90
0.098
0.11
34
6
4.61
3.08
5.90
3.94
0.090
0.13
43
10
3.08
1.83
3.94
2.34
0.084
0.16
57
16
1.91
1.15
2.44
1.47
0.080
0.18
78
25
1.20
0.727 1.54
0.931
0.080
0.20
95
35
0.868 0.524 1.11
0.671
0.080
0.23
116
50
0.641 0.387 0.820 0.495
0.078
0.24
140
70
0.443 0.268 0.567 0.343
0.077
0.26
170
95
0.320 0.193 0.411
0.248
0.084
0.29
200
120
0.253 0.153 0.325 0.197
0.072
0.29
225
150
0.206 0.1240 0.265 0.159
0.072
0.29
255
185
0.164 0.0991 0.211
0.127
0.072
0.29
285
240
0.125 0.0754 0.162 0.098
0.072
0.31
325
300
0.100 0.0601 0.130 0.078
0.071
0.33
370
400
0.0778 0.0470 0.1023 0.0618
0.070
0.33
435
500
0.0605 0.0366 0.0808 0.0489
0.070
0.34
481
630
0.0469 0.0283 0.0648 0.0391
0.069
0.36
537
ote
ormal current ratings are given in standard conditions as given in page no -40,41
multiplied by rating factor as given in page no. 42

28
37
48
61
80
94
110
140
165
185
210
235
270
305
350
405
470
, if site

30
44
40
55
53
74
70
94
99
120
117
145
140
170
176
210
221
250
258
285
294
315
339
355
402
410
461
460
542
520
624
580
723
680
conditions are

Short Circuit Current


ating for 1Sec.duration

in K. Amps
Al
Cu

37
39
0.376
0.572
47
50
0.564
0.858
61
67
0.940
1.430
78
85
1.50
2.29
100
125
2.35
3.58
120
155
3.29
5.01
145
190
4.70
7.15
175
235
6.58
10.01
210
290
8.93
13.59
240
330
11.28
17.16
270
375
14.10 21.45
300
435
17.39 26.46
350
510
22.56 34.32
390
590
28.20 42.90
440
670
37.60 57.20
480
750
47.00 71.50
575
875
59.22 90.09
different, current rating should be

19

TABLE - 15

TECHNICAL DETAIL FOR HAVELLS 1.1 KV THREE CORES,


AL/COPPER COND., XLPE INSULATED, UN-ARMOURED CABLES
Cable Code A2X / 2X
ef Specification IS 7098 PA T -1
PHYSICAL PARAMETERS
SI E Cross-sectional
area
sqmm
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
C

SS- SECTI

Minimum o of
Strands in
Conductor
Al
Cu

AL VIE

2
3
4

Minimum
thickness of
inner Sh.
mm

ominal thick.
of outer
Sheath
mm

0.7
0.7
0.7
0.7
0.9
0.9
1.0
1.1
1.1
1.2
1.4
1.6
1.7
1.8
2.0
2.2
2.4

0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.40
0.40
0.40
0.50
0.50
0.60
0.60
0.70
0.70
0.70

1.80
1.80
1.80
1.80
2.00
2.00
2.00
2.20
2.20
2.20
2.40
2.60
2.80
3.00
3.20
3.60
3.80

1/7
1/7
6
6
6
6
6
12
15
18
18
30
34
34
53
53
53

1
1
6
6
6
6
12
15
15
15
30
30
30
53
53
53
1

ominal
thickness of
Insulation
mm

Appro .
verall
Diameter
mm

Appro . et t
of cable Kg/KM
ith Al cond
ith Cu Cond.
A2X
2X

14
16
18
18
21
22
25
30
32
35
39
43
49
53
59
66
73

225
330
400
400
530
640
800
1100
1350
1650
2050
2500
3150
3850
4850
6100
7650

300
440
580
700
1000
1300
1700
2400
3100
3800
4800
5950
7600
9400
12000
15000
19000

C
DUCT
Material - Aluminium /Copper
Shape AL . Cond - 6 & 10 SQMM -Solid circular, 16sqmm & above Stranded compacted shaped

Copper. Cond - 4 & 6 sqmm -solid/ stranded non compacted circular, 10sqmm Stranded compacted circular,16sqmm & above Stranded compacted
shaped

I SULATI
Crosslinked Polyethylene XLPE
I E SHEATH PVC as per IS 7098PT-1
UTE SHEATH PVC T PE ST-2 F IS 5831

C L U

F UTE SHEATH BLACK . PTI

ed, ellow & Blue colour


PTI

S F T PE/F LS T PE

S any other colour as per requirement.

Tabulated appro . net wt. of cables are only guidelines for transportation, loading &unloading purpose.
Please ref page no 43 for normal delivery lengths & packing details.

ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM

4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630

Ma . Cond. D.C. Appro . Cond. A.C.


App.
App. Capecitance
ormal Current ating in Amps
esistance at
esistance at
eactance of
of cable
ith Aluminium cond.
ith Copper cond.
o
o
20 C in hm/km 90 C in hm/km
cable at 50H
in microF/KM
Ground Duct
Air
Ground Duct
Air
Al
Cu
Al
Cu
in ohms/km

4.61
3.08
1.91
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469

4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283

5.90
3.94
2.44
1.54
1.11
0.820
0.567
0.411
0.325
0.265
0.211
0.162
0.130
0.1023
0.0808
0.0648

5.90
3.94
2.34
1.47
0.931
0.671
0.495
0.343
0.248
0.197
0.159
0.127
0.098
0.078
0.0618
0.0489
0.0391

0.098
0.090
0.084
0.080
0.080
0.080
0.078
0.077
0.074
0.072
0.072
0.072
0.072
0.071
0.070
0.070
0.069

0.11
0.13
0.16
0.18
0.20
0.23
0.24
0.26
0.29
0.29
0.29
0.29
0.31
0.33
0.33
0.34
0.36

34
43
57
78
95
116
140
170
200
225
255
285
325
370
435
481
537

28
37
48
61
80
94
110
140
165
185
210
235
270
305
350
405
470

30
40
53
70
99
117
140
176
221
258
294
339
402
461
542
624
723

44
55
74
94
120
145
170
210
250
285
315
355
410
460
520
580
680

37
47
61
78
100
120
145
175
210
240
270
300
350
390
440
480
575

39
50
67
85
125
155
190
235
290
330
375
435
510
590
670
750
875

Short Circuit Current


ating for 1Sec.duration

in K. Amps
Al
Cu

0.376
0.564
0.940
1.50
2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
47.00
59.22

0.572
0.858
1.430
2.29
3.58
5.01
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
71.50
90.09

ote
ormal current ratings are given in standard conditions as given in page no - 40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42

20

TABLE - 16

TECHNICAL DETAIL FOR HAVELLS 1.1 KV


THREE & HALF CORE, AL/COPPER COND., XLPE INSULATED, UN-ARMOURED CABLES
Cable Code A2X / 2X
ef Specification IS 7098PA T -1
PHYSICAL PARAMETERS
SI E
Cross-sectional
area
sqmm

Minimum o of
ominal
strands
Thickness of
in conductor
Insulation
Phase / eutral Phase / eutral
Al
Cu
mm

3X25 16
3X35 16
3X50 25
3X70 35
3X95 50
3X120 70
3X150 70
3X185 95
3X240 120
3X300 150
3X400 185
3X500 240
3X630 300

6/6
6/6
6/6
12/6
15/6
15/12
15/12
30/15
30/15
30/15
53/30
53/30
53/30

SS- SECTI

6/6
6/6
6/6
12/6
15/6
18/12
18/12
30/15
34/18
34/18
53/30
53/34
53/34

AL VIE
1
2
3
4

0.90/0.70
0.90/0.70
1.00/0.90
1.10/0.90
1.10/1.00
1.20/1.10
1.40/1.10
1.60/1.10
1.70/1.20
1.80/1.40
2.00/1.60
2.20/1.70
2.40/1.80
DUCT

Shape

mm

ominal
thickness of
UTE
Sheath
mm

Appro .
overall
Diameter
mm

0.30
0.30
0.30
0.40
0.40
0.40
0.50
0.50
0.60
0.60
0.70
0.70
0.70

2.00
2.00
2.00
2.20
2.20
2.20
2.40
2.60
2.80
3.00
3.40
3.60
4.00

22
24
27
31
34
38
43
46
52
57
65
73
82

Minimum
Thickness of
inner sheath

Appro . et t
of cable Kg/KM
ith Al cond
ith Cu Cond.
A2X
2X
600
700
900
1200
1500
1900
2300
2800
3600
4400
5600
7000
8900

1150
1450
2000
2700
3600
4500
5500
6800
8700
10800
14000
17500
22000

Material - Aluminium /Copper

Standed compacted shaped as per Calss - 2 of IS 8130

I SULATI
Crosslinked Polyethylene XLPE Phase - ed, ellow, Blue & neutral - Black colour
I E SHEATH PVC as per IS 7098PT-1
UTE SHEATH PVC T PE ST-2 F IS 5831
PTI
S F T PE F LS T PE
C L U
F UTE SHEATH BLACK . PTI
S any other colour as per requirement.

Tabulated appro . net wt. of cables are only guidelines for transportation, loading & unloading purpose.
Please ref page no 43 for normal delivery lengths & packing details.

ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM

Ma . Cond. D.C. Appro . Cond. A.C. App. eactance App. Capecitance


esistance at
esistance at
of cable at 50H
of cable
o

20 C in hm/km
Al
Cu

90 C in hm/km
Al
Cu

in ohms/km

in microF/KM

ormal Current ating in Amps


ith Aluminium cond.
ith Copper cond.
Ground Duct

3X25 16
1.20
0.727 1.54
0.931
0.080
0.20
3X35 16
0.868 0.524 1.11
0.671
0.080
0.23
3X50 25
0.641 0.387 0.820 0.495
0.078
0.24
3X70 35
0.443 0.268 0.567 0.343
0.077
0.26
3X95 50
0.320 0.193 0.411 0.248
0.074
0.29
3X120 70
0.253 0.153 0.325 0.197
0.072
0.29
3X150 70
0.206 0.1240 0.265 0.159
0.072
0.29
3X185 95
0.164 0.0991 0.211 0.127
0.072
0.29
3X240 120 0.125 0.0754 0.162 0.098
0.072
0.31
3X300 150 0.100 0.0601 0.130 0.078
0.071
0.33
3X400 185 0.0778 0.0470 0.1023 0.0618
0.070
0.33
3X500 240 0.0605 0.0366 0.0808 0.0489
0.070
0.34
3X630 300 0.0469 0.0283 0.0648 0.0391
0.069
0.36
ote
ormal current ratings are given in standard conditions as given in page no
multiplied by rating factor as given in page no. 42

95
116
140
170
200
225
255
285
325
370
435
481
537
- 40,41

80
94
110
140
165
185
210
235
270
305
350
405
470
, if site

Air

Ground

99
120
117
145
140
170
176
210
221
250
258
285
294
315
339
355
402
410
461
460
542
520
624
580
723
680
conditions are

Duct

Air

Short Circuit Current


ating for 1Sec.duration

in K. Amps
Al
Cu

100 2.35
2.35
3.58
120 3.29
3.29
5.01
145 4.70
4.70
7.15
175 6.58
6.58
10.01
210 8.93
8.93
13.59
240 11.28
11.28
17.16
270 14.10
14.10
21.45
300 17.39
17.39
26.46
350 22.56
22.56
34.32
390 28.20
28.20
42.90
440 37.60
37.60
57.20
480 47.00
47.00
71.50
575 59.22
59.22
90.09
different, current rating should be

21

TABLE - 17

TECHNICAL DETAIL FOR HAVELLS 1.1 KV


FOUR CORE, AL/COPPER COND., XLPE INSULATED, UN-ARMOURED CABLES
Cable Code A2X / 2X
ef Specification IS 7098PA T -1
PHYSICAL PARAMETERS
SI E
Cross-sectional
area
sqmm
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
C

Minimum
o of
Strands in
Conductor
Al
Cu
1/7
1
1/7
1
6
6
6
6
6
6
6
6
6
12
12
15
15
15
18
15
18
30
30
30
34
30
34
53
53
53
53
53
53

SS- SECTI

AL VIE
1

2
3
4

ominal
Thickness
of
Insulation
mm
0.7
0.7
0.7
0.7
0.9
0.9
1.0
1.1
1.1
1.2
1.4
1.6
1.7
1.8
2.0
2.2
2.4

Minimum
Thickness
of
inner sheath
mm
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.40
0.40
0.50
0.50
0.50
0.60
0.70
0.70
0.70
0.70

Minimum
Thickness of
outer sheath
mm
1.80
1.80
1.80
1.80
2.00
2.00
2.00
2.20
2.20
2.40
2.60
2.80
3.00
3.20
3.60
3.80
4.00

Appro .
over all
Diameter
mm
17
18
20
20
24
26
29
34
37
41
45
50
56
63
70
79
88

Appro . et t
of cable Kg/KM
ith Al cond
ith Cu Cond.
A2X
2X
250
350
350
500
400
650
450
850
660
1300
800
1700
1000
2200
1400
3100
1700
4000
2150
5150
2650
6350
3250
7850
4100
10000
5050
12050
6400
16000
8000
20000
10000
26000

C
DUCT
Material - Aluminium /Copper
Shape AL . Cond - 6 & 10SQMM -Solid circular, 16sqmm & above Stranded compacted shaped

Copper . Cond - 4 & 6sqmm -solid/ stranded non compacted circular , 10sqmm Stranded compacted circular,16sqmm & above Stranded compacted
shaped

I SULATI
Crosslinked Polyethylene XLPE
I E SHEATH PVC as per IS 7098PT-1
UTE SHEATH PVC T PE ST-2 F IS 5831
C L U
F UTE SHEATH BLACK . PTI

ed, ellow, Blue & Black colour


PTI
S F T PE/ F LS T PE
S any other colour as per requirement.

Tabulated appro . net wt. of cables are only guidelines for transportation, loading & unloading purpose.
Please ref page no 43 for normal delivery lengths & packing details.

ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM

4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630

Ma . Cond. D.C. Appro . Cond. A.C. App. eactance App. Capecitance


ormal Current ating in Amps
esistance at
esistance at
of cable at
of cable
ith Aluminium cond.
ith Copper cond.
20oC in hm/km 90oC in hm/km
50H
in microF/KM
Ground Duct
Air
Ground Duct
Air
Al
Cu
Al
Cu
in ohms/km

4.61
3.08
1.91
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469

4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283

5.90
3.94
2.44
1.54
1.11
0.820
0.567
0.411
0.325
0.265
0.211
0.162
0.130
0.1023
0.0808
0.0648

5.90
3.94
2.34
1.47
0.931
0.671
0.495
0.343
0.248
0.197
0.159
0.127
0.098
0.078
0.0618
0.0489
0.0391

0.098
0.090
0.084
0.080
0.080
0.080
0.078
0.077
0.074
0.072
0.072
0.072
0.072
0.071
0.070
0.070
0.069

0.11
0.13
0.16
0.18
0.20
0.23
0.24
0.26
0.29
0.29
0.29
0.29
0.31
0.33
0.33
0.34
0.36

34
43
57
78
95
116
140
170
200
225
255
285
325
370
435
481
537

28
37
48
61
80
94
110
140
165
185
210
235
270
305
350
405
470

30
40
53
70
99
117
140
176
221
258
294
339
402
461
542
624
723

44
55
74
94
120
145
170
210
250
285
315
355
410
460
520
580
680

37
47
61
78
100
120
145
175
210
240
270
300
350
390
440
480
575

39
50
67
85
125
155
190
235
290
330
375
435
510
590
670
750
875

Short Circuit Current


ating for 1Sec.duration

in K. Amps
Al
Cu

0.376
0.564
0.940
1.50
2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
47.00
59.22

0.572
0.858
1.430
2.29
3.58
5.01
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
71.50
90.09

ote
ormal current ratings are given in standard conditions as given in page no - 40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42

22

TABLE - 18

TECHNICAL DETAIL FOR HAVELLS 1.1 KV SINGLE CORE, AL/COPPER COND.,


XLPE INSULATED, AL WIRE/STRIP ARMOURED CABLES
Cable Code A2XFa / 2XFa , A2X a / 2X a
ef Specification IS 7098PA T -1
PHYSICAL PARAMETERS
SI E
Cross-sectional
area
sqmm

4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
C

Minimum
o of
Strands in
Conductor
Al
Cu

1
1
6
6
6
6
12
15
15
15
30
30
30
53
53
53
53
53

SS- SECTI

ominal

Thickness of
Insulation
mm

1/7
1/7
6
6
6
6
6
12
15
18
18
30
34
34
53
53
53
53
53

1.0
1.0
1.0
1.0
1.2
1.2
1.3
1.4
1.4
1.5
1.7
1.9
2.0
2.1
2.4
2.6
2.8
3.1
3.3

AL VIE

A M U I G ITH FLAT ST IP A2XFa /2XFa


A M U I G ITH
U D I ES A2X a / 2X a
ominal
Minimum
Appro .
Appro . et t
ominal
Minimum
Appro .
Appro . et t
Thickness Thickness of
verall
of cable Kg/KM
Diameter Thickness of
verall of cable Kg/KM
ith Al cond
ith Cu Cond. of wire
outer sheath Diameter ith Al cond ith Cu Cond.
Strip
outer sheath Diameter
mm
mm
mm
A2XFa
2XFa
mm
mm
mm
A2X a
2X a

/A
/A
/A
/A
/A
/A
/A
/A
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80

/A
/A
/A
/A
/A
/A
/A
/A
1.40
1.40
1.40
1.40
1.40
1.56
1.56
1.56
1.72
1.72
1.88

/A
/A
/A
/A
/A
/A
/A
/A
21
23
24
26
30
32
36
39
44
48
54

/A
/A
/A
/A
/A
/A
/A
/A
600
700
800
950
1200
1400
1750
2150
2700
3350
4100

/A
/A
/A
/A
/A
/A
/A
/A
1195
1450
1730
2100
2690
3270
4230
5250
6610
8320
10300

1.40
1.40
1.40
1.40
1.40
1.40
1.40
1.40
1.60
1.60
1.60
1.60
1.60
1.60
2.00
2.00
2.00
2.00
2.50

1.24
1.24
1.24
1.24
1.24
1.24
1.24
1.24
1.40
1.40
1.40
1.40
1.40
1.56
1.56
1.56
1.72
1.88
2.04

10
11
12
13
14
15
17
19
22
24
25
28
30
33
38
41
46
51
56

90
130
160
200
300
350
420
520
650
750
850
1000
1250
1500
1900
2350
2900
3600
4600

C
DUCT
Material - Aluminium /Copper
Shape AL . Cond - 6 & 10SQMM -Solid circular, 16 sqmm & above Stranded compacted shaped circular

I SULATI
Crosslinked Polyethylene XLPE
atural colour
A M U I G Single layer of Aluminium ound wires / Flat Strips
UTE SHEATH PVC T PE ST-2 F IS 5831
PTI
S PVC T PE
C L U
F UTE SHEATH BLACK . PTI
S any other colour as per requirement.

3
4

130
170
222
300
455
567
730
954
1235
1494
1780
2147
2738
3360
4380
5450
6806
8560
10800

Copper. Cond - 4 & 6sqmm -solid/ stranded non compacted circular , 10sqmm Stranded compacted circular

Tabulated appro . net wt. of cables are only guidelines for transportation, loading &unloading purpose ..
Please ref page no 43 for normal delivery lengths & packing details.

ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM

4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000

Ma . Cond. D.C. Appro . Cond. A.C. App. eactance App. Capecitance


ormal Current ating in Amps
esistance at
esistance at
of cable at 50H
of cable
ith Aluminium cond.
ith Copper cond.
20oC in hm/km 90oC in hm/km
in ohms/km
in microF/KM
Ground Duct
Air
Ground Duct
Air
Al
Cu
Al
Cu

4.61
3.08
1.91
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
0.0367
0.0291

4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
0.0221
0.0176

5.90
3.94
2.44
1.54
1.11
0.820
0.567
0.411
0.325
0.265
0.211
0.162
0.130
0.1023
0.0808
0.0648
0.0530
0.0444

5.90
3.94
2.34
1.47
0.931
0.671
0.495
0.343
0.248
0.197
0.159
0.127
0.0976
0.0778
0.0618
0.0489
0.0391
0.0319
0.0268

0.152
0.144
0.133
0.122
0.116
0.110
0.103
0.099
0.097
0.093
0.091
0.090
0.086
0.085
0.085
0.083
0.082
0.081
0.081

0.22
0.26
0.31
0.40
0.40
0.47
0.50
0.55
0.64
0.67
0.67
0.67
0.72
0.75
0.75
0.77
0.81
0.88
0.88

45
59
76
99
117
138
168
204
230
265
295
340
390
450
500
555
625
690

45
62
80
90
110
125
155
185
210
230
260
300
335
380
430
485
530
570

40
53
73
115
140
170
210
255
300
342
385
450
519
605
700
809
935
1065

48
60
80
104
130
155
185
225
265
300
335
380
435
490
550
610
680
740
780

47
59
78
102
115
140
165
200
235
265
300
335
385
430
480
530
590
630
660

45
57
77
106
145
175
215
270
330
380
430
495
590
670
780
900
1020
1140
1250

Short Circuit Current


ating for 1Sec.duration

in K. Amps
Al
Cu

0.376
0.572
0.56
0.858
0.94
1.43
1.50
2.29
2.35
3.58
3.29
5.01
4.70
7.15
6.58
10.01
8.93
13.59
11.28
17.16
14.10
21.45
17.39
26.46
22.56
34.32
28.20
42.90
37.60
57.20
47.00
71.50
59.22
90.09
75.20 114.40
94.00 143.00

ote
ormal current ratings are given in standard conditions as given in page no - 40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42
23

TABLE - 19

TECHNICAL DETAIL FOR HAVELLS 1.1 KV TWO CORES, AL/COPPER COND.,


XLPE INSULATED, GALVANIZED STEEL WIRE/STRIP ARMOURED CABLES
Cable Code A2 F /2 F , A2X
/ 2X
ef Specification IS 7098 PA T -1
PHYSICAL PARAMETERS
SI E
Cross-sectional
area
sqmm

4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630

Minimum
ominal Minimum
A M U I G ITH FLAT ST IP A2XF / 2XF
A M U I G ITH
U D I ES A2X
/ 2X
o of
Thickness Thickness
ominal
Minimum
Appro .
Appro . et t
ominal
Minimum
Appro .
Appro . et t
Strands in
of
Thickness Thickness of
verall
of cable Kg/KM
Diameter Thickness of
verall of cable Kg/KM
of
ith Al cond
ith Cu Cond.
of wire outer sheath Diameter ith Al cond ith Cu Cond.
Conductor Insulation inner Sh. of armour outer sheath Diameter
Al
Cu
mm
mm
mm
mm
A2XF
2XF
mm
mm
mm
A2X
2X
mm

1
1
6
6
6
6
12
15
15
15
30
30
30
53
53
53

SS- SECTI

1/7
1/7
6
6
6
6
6
12
15
18
18
30
34
34
53
53
53

0.7
0.7
0.7
0.7
0.9
0.9
1.0
1.1
1.1
1.2
1.4
1.6
1.7
1.8
2.0
2.2
2.4

AL VIE
1

2
3
4
5

0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.40
0.40
0.40
0.50
0.50
0.60
0.60
0.70
0.70

/A
/A
/A
/A
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80

/A
/A
/A
/A
1.40
1.40
1.40
1.56
1.56
1.56
1.72
1.72
1.88
2.04
2.36
2.52
2.68

/A
/A
/A
/A
20
21
23
26
29
31
34
37
42
45
50
55
63

/A
/A
/A
/A
650
750
900
1100
1350
1600
1900
2250
2800
3300
4100
5000
6100

/A
/A
/A
/A
950
1200
1500
1950
2500
3100
3750
4500
5800
7000
9050
11000
14000

1.40
1.40
1.40
1.40
1.60
1.60
1.60
1.60
2.00
2.00
2.00
2.00
2.50
2.50
2.50
3.15
3.15

1.24
1.24
1.24
1.40
1.40
1.40
1.40
1.56
1.56
1.56
1.72
1.88
2.04
2.20
2.36
2.68
2.84

15
16
18
19
21
23
25
28
31
34
37
40
45
49
52
60
66

500
550
650
700
850
950
1100
1400
1850
2150
2450
2900
3850
4450
5350
7100
8500

550
600
770
900
1150
1400
1700
2250
3000
3600
4300
5200
6800
8200
10300
13300
16300

C
DUCT
Material - Aluminium /Copper
Shape AL . Cond - 6 & 10SQMM -Solid circular, 16sqmm & above Stranded compacted shaped

Copper. Cond - 4 & 6 sqmm -solid/ stranded non compacted circular, 10 sqmm Stranded compacted circular,16sqmm & above Stranded compacted
shaped

I SULATI
Crosslinked Polyethylene XLPE
ed & Black colour
I E SHEATH PVC as per IS 7098PT-1
A M U I G Single layer of galvanized steel round wires / flat strips
UTE SHEATH PVC T PE ST-2 F IS 5831
PTI
S F T PE/ F LS T PE
C L U
F UTE SHEATH BLACK. PTI
S any other colour as per requirement.

Tabulated appro . net wt. of cables are only guidelines for transportation, loading &unloading purpose.
Please ref page no 43 for normal delivery lengths & packing details.

ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM

Ma . Cond. D.C. Appro . Cond. A.C. App. eactance App. Capecitance


ormal Current ating in Amps
esistance at
esistance at
at 50H
of cable
ith Aluminium cond.
ith Copper cond.
20oC in hm/km 90oC in hm/km
in ohms/km
in microF/KM
Ground Duct
Air
Ground Duct
Air
Al
Cu
Al
Cu

4
--4.61
--5.90
0.098
0.11
6
4.61
3.08
5.90
3.94
0.090
0.13
10
3.08
1.83
3.94
2.34
0.084
0.16
16
1.91
1.15
2.44
1.47
0.080
0.18
25
1.20
0.727 1.54
0.931
0.080
0.20
35
0.868 0.524 1.11
0.671
0.080
0.23
50
0.641 0.387 0.820 0.495
0.078
0.24
70
0.443 0.268 0.567 0.343
0.077
0.26
95
0.320 0.193 0.411 0.248
0.074
0.29
120
0.253 0.153 0.325 0.197
0.072
0.29
150
0.206 0.1240 0.265 0.159
0.072
0.29
185
0.164 0.0991 0.211 0.127
0.072
0.29
240
0.125 0.0754 0.162 0.0976
0.072
0.31
300
0.100 0.0601 0.130 0.0778
0.071
0.33
400
0.0778 0.0470 0.1023 0.0618
0.070
0.33
500
0.0605 0.0366 0.0808 0.0489
0.070
0.34
630
0.0469 0.0283 0.0648 0.0391
0.069
0.36
ote
ormal current ratings are given in standard conditions as given in page no
multiplied by rating factor as given in page no. 42

34
43
57
78
95
116
140
170
200
225
255
285
325
370
435
481
537
- 40,41

28
30
44
37
40
55
48
53
74
61
70
94
80
99
120
94
117
145
110
140
170
140 176
210
165 221
250
185 258
285
210 294
315
235 339
355
270 402
410
305 461
460
350 542
520
405 624
580
470 723
680
, if site conditions are

Short Circuit Current


ating for 1Sec. duration

in K. Amps
Al
Cu

37
39
0.376
0.572
47
50
0.564
0.858
61
67
0.940
1.430
78
85
1.50
2.29
100 125
2.35
3.58
120 155
3.29
5.01
145 190
4.70
7.15
175 235
6.58
10.1
210 290
8.93
13.59
240 330
11.28
17.16
270 375
14.10
21.45
300 435
17.39
26.46
350 510
22.56
34.32
390 590
28.20
42.90
440 670
37.60
57.20
480 750
47.00
71.50
575 875
59.22
90.09
different, current rating should be

24

TABLE - 20

TECHNICAL DETAIL FOR HAVELLS 1.1 KV THREE CORES, AL/COPPER COND.,


XLPE INSULATED, GALVANIZED STEEL WIRE/STRIP ARMOURED CABLES
Cable Code A2XF /2XF , A2X
/ 2X
ef Specification IS 7098 PA T -1
PHYSICAL PARAMETERS
SI E
Cross-sectional
area
sqmm

Minimum
ominal Minimum
A M U I G ITH FLAT ST IP A2XF / 2XF
A M U I G ITH
U D I ES A2X
/ 2X
o of
Thickness Thickness
ominal
Minimum
Appro .
Appro . et t
ominal
Minimum
Appro .
Appro . et t
Strands in
of
Thickness Thickness of
verall
of cable Kg/KM
Diameter Thickness of
verall of cable Kg/KM
of
ith Al cond
ith Cu Cond.
of wire outer sheath Diameter ith Al cond ith Cu Cond.
Conductor Insulation inner Sh. of armour outer sheath Diameter
Al
Cu
mm
strip mm
mm
mm
A2XF
2XF
mm
mm
mm
A2X
2X
mm

4
6
1
10
1
16
6
25
6
35
6
50
6
70
12
95
15
120
15
150
15
185
30
240
30
300
30
400
53
500
53
630
53
SS- SECTI

1/7
1/7
6
6
6
6
6
12
15
18
18
30
34
34
53
53
53
AL VIE
1

2
3
4
5

0.7
0.7
0.7
0.7
0.9
0.9
1.0
1.1
1.1
1.2
1.4
1.6
1.7
1.8
2.0
2.2
2.4

0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.40
0.40
0.40
0.50
0.50
0.60
0.60
0.70
0.70
0.70

/A
/A
/A
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

/A
/A
/A
1.24
1.40
1.40
1.40
1.56
1.56
1.56
1.72
1.88
2.04
2.20
2.52
2.68
2.84

/A
/A
/A
19
21
23
26
29
32
35
42
44
49
54
60
66
74

/A
/A
/A
600
800
950
1100
1450
1750
2100
2500
3000
3750
4500
5600
6900
8550

/A
/A
/A
900
1200
1500
2000
2700
3500
4200
5200
6300
8200
10000
13000
16000
20000

1.40
1.40
1.40
1.60
1.60
1.60
1.60
2.00
2.00
2.00
2.00
2.50
2.50
2.50
3.15
3.15
4.00

1.24
1.24
1.24
1.40
1.40
1.40
1.56
1.56
1.56
1.72
1.88
2.04
2.20
2.36
2.68
2.84
3.00

18
19
20
20
23
25
29
32
35
39
43
48
53
58
65
72
81

600
650
750
800
1000
1200
1450
2000
2350
2750
3250
4200
5100
6000
7950
9500
12600

670
770
930
1100
1450
1850
2300
3300
4100
4900
6000
7500
9500
11300
15200
18500
23700

C
DUCT
Material - Aluminium /Copper
Shape AL . Cond - 6 & 10 SQMM -Solid circular, 16 sqmm & above Stranded compacted shaped

Copper. Cond - 4 & 6 sqmm -solid/ stranded non compacted circular, 10 sqmm Stranded compacted circular,16 sqmm & above Stranded compacted
shaped

I SULATI
Crosslinked Polyethylene XLPE ed, ellow, Blue
I E SHEATH PVC as per IS 7098PT-1
A M U I G Single layer of Galvanized steel ound wires / Flat Strips
UTE SHEATH PVC T PE ST-2 F IS 5831
PTI
S F T PE/ F LS T PE
C L U
F UTE SHEATH BLACK. PTI
S any other colour as per requirement.

Tabulated appro . net wt. of cables are only guidelines for transportation, loading & unloading purpose.
Please ref page no 43 for normal delivery lengths & packing details.

ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM

Ma . Cond. D.C. Appro . Cond. A.C. App. eactance App. Capecitance


ormal Current ating in Amps
esistance at
esistance at
at 50H
of cable
ith Aluminium cond.
ith Copper cond.
20oC in hm/km 90oC in hm/km
in ohms/km
in microF/KM
Ground Duct
Air
Ground Duct
Air
Al
Cu
Al
Cu

4
--4.61
--5.90
0.098
0.11
6
4.61
3.08
5.90
3.94
0.090
0.13
10
3.08
1.83
3.94
2.34
0.084
0.16
16
1.91
1.15
2.44
1.47
0.080
0.18
25
1.20
0.727 1.54
0.931
0.080
0.20
35
0.868 0.524 1.11
0.671
0.080
0.23
50
0.641 0.387 0.820 0.495
0.078
0.24
70
0.443 0.268 0.567 0.343
0.077
0.26
95
0.320 0.193 0.411
0.248
0.074
0.29
120
0.253 0.153 0.325 0.197
0.072
0.29
150
0.206 0.1240 0.265 0.159
0.072
0.29
185
0.164 0.0991 0.211
0.127
0.072
0.29
240
0.125 0.0754 0.162 0.0976
0.072
0.31
300
0.100 0.0601 0.130 0.0778
0.071
0.33
400
0.0778 0.0470 0.1023 0.0618
0.070
0.33
500
0.0605 0.0366 0.0808 0.0489
0.070
0.34
630
0.0469 0.0283 0.0648 0.0391
0.069
0.36
ote
ormal current ratings are given in standard conditions as given in page no
multiplied by rating factor as given in page no. 42

34
28
30
44
43
37
40
55
57
48
53
74
78
61
70
94
95
80
99
120
116
94
117
145
140
110
140
170
170
140
176
210
200
165
221
250
225
185
258
285
255
210
294
315
285
235
339
355
325
270
402
410
370
305
460
460
435
350
542
520
481
405
624
580
537
470
723
680
- 40,41 , if site conditions are

Short Circuit Current


ating for 1Sec. duration

in K. Amps
Al
Cu

37
39
0.376
0.572
47
50
0.564
0.858
61
67
0.940
1.430
78
85
1.50
2.29
100 125
2.35
3.58
120 155
3.29
5.01
145 190
4.70
7.15
175 235
6.58
10.01
210 290
8.93
13.59
240 330
11.28
17.16
270 375
14.10
21.45
300 435
17.39
26.46
350 510
22.56
34.32
390 590
28.20
42.90
440 670
37.60
57.20
480 750
47.00
71.50
575 875
59.22
90.09
different, current rating should be

25

TABLE - 21

TECHNICAL DETAIL FOR HAVELLS 1.1 KV THREE AND HALF CORES, AL/CUCOPPER COND.,
XPLE INSULATED, GALVANIZED STEEL WIRE/STRIP ARMOURED CABLES
Cable Code 3.5 Core - A2XF / 2XF , A2X
/ 2X
ef Specification IS 7098PA T -1
PHYSICAL PARAMETERS
SI E
Cross-sectional
area
sqmm

3X25 16
3X35 16
3X50 25
3X70 35
3X95 50
3X120 70
3X150 70
3X185 95
3X240 120
3X300 150
3X400 185
3X500 240
3X630 300
C

Minimum
o of
Strands in
Conductor
Al
Cu

6/6
6/6
6/6
12/6
15/6
15/12
15/12
30/15
30/15
30/15
53/30
53/30
53/30

SS- SECTI

6/6
6/6
6/6
12/6
15/6
18/12
18/12
30/15
34/18
34/18
53/30
53/34
53/34

ominal
Thickness
of
Insulation
mm

0.90/0.70
0.90/0.70
1.00/0.90
1.10/0.90
1.10/1.00
1.20/1.10
1.40/1.10
1.60/1.10
1.70/1.20
1.80/1.40
2.00/1.60
2.20/1.70
2.40/1.80

AL VIE
1
C
2
3
4
5

Minimum
A M U I G ITH FLAT ST IP A2XF / 2XF
A M U I G ITH
U D I ES A2X
/ 2X
Thickness ominal Minimum
Appro .
Appro . et t
ominal
Minimum
Appro .
Appro . et t
of
Thickness Thickness of
verall
of cable Kg/KM Diameter Thickness of
verall
of cable Kg/KM
inner Sh. of Armr. outer sheath Diameter ith Al cond ith Cu Cond. of wire outer sheath Diameter ith Al cond ith Cu Cond.
mm Strip mm
mm
mm
A2XF
2XF
mm
mm
mm
A2X
2X

DUCT

0.30
0.30
0.30
0.40
0.40
0.40
0.50
0.50
0.60
0.60
0.70
0.70
0.70

0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80

1.40
1.40
1.40
1.56
1.56
1.72
1.72
1.88
2.04
2.20
2.52
2.68
3.00

23
25
28
32
35
39
43
47
53
57
66
74
82

900
1000
1200
1600
2000
2400
2800
3400
4300
5000
6400
7900
9900

1400
1800
2300
3200
4100
5100
6000
7400
9500
11500
14500
18000
23000

1.60
1.60
1.60
2.00
2.00
2.00
2.00
2.50
2.50
2.50
3.15
3.15
4.00

1.40
1.40
1.56
1.56
1.56
1.72
1.88
2.04
2.20
2.36
2.68
2.84
3.00

25
27
30
35
38
42
46
51
56
60
71
79
88

1100
1300
1600
2200
2600
3100
3600
4700
5700
6700
9000
11000
14500

1700
2000
2700
3700
4600
5700
6800
8700
10500
13000
17000
21500
28000

Material - Aluminium /Copper

Shape Stranded compacted shaped as per class-2 of IS 8130

I SULATI
Crosslinked Polyethylene XLPE Phase, ed, ellow, Blue & eutral - Black Colour
I E SHEATH PVC as per IS 7098PT-1
A M U I G Single layer of Galvanized steel ound wires / Flat Strips
UTE SHEATH PVC T PE ST-2 F IS 5831
PTI
S F T PE/ F LS T PE
C L U
F UTE SHEATH BLACK . PTI
S any other colour as per requirement.

Tabulated appro . net wt. of cables are only guidelines for transportation, loading &unloading purpose.
Please ref page no 43 for normal delivery lengths & packing details.

ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM

3X25 16
3X35 16
3X50 25
3X70 35
3X95 50
3X120 70
3X150 70
3X185 95
3X240 120
3X300 150
3X400 185
3X500 240
3X630 300

Ma . Cond. D.C. Appro . Cond. A.C. App.. eactance App. Capecitance


esistance at
esistance at
at 50H
of cable
20oC in hm/km 90oC in hm/km
in ohms/km
in microF/KM
Al
Cu
Al
Cu

1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469

0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283

1.54
1.11
0.820
0.567
0.411
0.325
0.265
0.211
0.162
0.130
0.1023
0.0808
0.0648

0.931
0.671
0.495
0.343
0.248
0.197
0.159
0.127
0.098
0.078
0.0618
0.0489
0.0391

0.080
0.080
0.078
0.077
0.074
0.072
0.072
0.072
0.072
0.071
0.070
0.070
0.069

0.20
0.23
0.24
0.26
0.29
0.29
0.29
0.29
0.31
0.33
0.33
0.34
0.36

ormal Current ating in Amps


ith Aluminium cond.
ith Copper cond.
Ground Duct
Air
Ground Duct
Air

95
116
140
170
200
225
255
285
325
370
435
481
537

80
94
110
140
165
185
210
235
270
305
350
405
470

99
117
140
176
221
258
294
339
402
461
542
624
723

120
145
170
210
250
285
315
355
410
460
520
580
680

100
120
145
175
210
240
270
300
350
390
440
480
575

125
155
190
235
290
330
375
435
510
590
670
750
875

Short Circuit Current


ating for 1Sec.duration

Al

in K. Amps
Cu

2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
47.00
59.22

3.58
5.01
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
71.50
90.09

ote
ormal current ratings are given in standard conditions as given in page no -40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42
Testing Laboratory

26

TABLE - 22

TECHNICAL DETAIL FOR HAVELLS 1.1 KV FOUR CORES, AL/COPPER COND.,


XLPE INSULATED, GALVANIZED STEEL WIRE/STRIP ARMOURED CABLES
Cable Code A2XF /2XF , A2X
/ 2X
ef Specification IS 7098 PA T -1
PHYSICAL PARAMETERS
SI E
Cross-sectional
area
sqmm

4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630

Minimum
ominal Minimum
A M U I G ITH FLAT ST IP A2XF /2XF
A M U I G ITH
U D I ES A2X
/ 2X
o of
Thickness Thickness
ominal
Minimum
Appro .
Appro . et t
ominal
Minimum
Appro .
Appro . et t
of
Strands in
of
Thickness Thickness of
verall
of cable Kg/KM
Diameter Thickness of
verall of cable Kg/KM
Conductor Insulation inner Sh. of armour outer sheath Diameter
ith Al cond
ith Cu Cond.
of wire outer sheath Diameter ith Al cond ith Cu Cond.
Al
Cu
mm
strip mm
mm
mm
A2XF
2X F
mm
mm
mm
A2X
2X
mm

1
1
6
6
6
6
12
15
15
15
30
30
30
53
53
53

SS- SECTI

1/7
1/7
6
6
6
6
6
12
15
18
18
30
34
34
53
53
53

0.7
0.7
0.7
0.7
0.9
0.9
1.0
1.1
1.1
1.2
1.4
1.6
1.7
1.8
2.0
2.2
2.4

AL VIE
1

2
3
4
5

0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.40
0.40
0.50
0.50
0.50
0.60
0.70
0.70
0.70
0.70

/A
/A
/A
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80

/A
/A
/A
1.40
1.40
1.40
1.56
1.56
1.56
1.72
1.88
2.04
2.20
2.36
2.68
2.84
3.00

/A
/A
/A
20
24
27
30
34
37
41
46
51
57
63
71
79
88

/A
/A
/A
700
900
1100
1400
1800
2200
2700
3200
3900
4850
5850
7320
9000
11000

/A
/A
/A
1100
1500
2000
2500
3400
4400
5600
6800
8300
10500
13000
17000
21000
27000

1.40
1.40
1.40
1.60
1.60
1.60
1.60
2.00
2.00
2.00
2.50
2.50
2.50
3.15
3.15
4.00
4.00

1.24
1.24
1.40
1.40
1.40
1.40
1.56
1.56
1.72
1.88
2.04
2.20
2.36
2.52
2.84
3.00
3.00

18
19
21
22
26
28
32
37
40
44
49
54
65
68
76
86
94

550
600
670
925
1200
1450
1750
2400
2900
3500
4500
5200
6400
8300
10000
13500
16000

650
750
950
1300
1770
2200
2850
4000
5150
6300
8000
9700
12000
15400
19500
25000
30500

C
DUCT
Material - Aluminium /Copper
Shape AL . Cond - 6 & 10 SQMM -Solid circular, 16 sqmm & above Stranded compacted shaped

Copper. Cond - 4 & 6 sqmm -solid/ stranded non compacted circular, 10 sqmm Stranded compacted circular,16 sqmm & above Stranded compacted
shaped

I SULATI
Crosslinked Polyethylene XLPE
ed, ellow, Blue & Black
I E SHEATH PVC as per IS 7098PT-1
A M U I G Single layer of Galvanized steel ound wires / Flat Strips
UTE SHEATH PVC T PE ST-2 F IS 5831
PTI
S F T PE/ F LS T PE
C L U
F UTE SHEATH BLACK. PTI
S any other colour as per requirement.

Tabulated appro . net wt. of cables are only guidelines for transportation, loading &unloading purpose.
Please ref page no 43 for normal delivery lengths & packing details.

ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM

4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630

Ma . Cond. D.C. Appro . Cond. A.C. App. eactance App. Capecitance


ormal Current ating in Amps
esistance at
esistance at
at 50H
of cable
ith Aluminium cond.
ith Copper cond.
o
o
20 C in hm/km 90 C in hm/km
in ohms/km
in microF/KM
Ground Duct
Air
Ground Duct
Air
Al
Cu
Al
Cu

4.61
3.08
1.91
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469

4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283

5.90
3.94
2.44
1.54
1.11
0.820
0.567
0.411
0.325
0.265
0.211
0.162
0.130
0.1023
0.0808
0.0648

5.90
3.94
2.34
1.47
0.931
0.671
0.495
0.343
0.248
0.197
0.159
0.127
0.0976
0.0778
0.0618
0.0489
0.0391

0.098
0.090
0.084
0.080
0.080
0.080
0.078
0.077
0.074
0.072
0.072
0.072
0.072
0.071
0.070
0.070
0.069

0.11
0.13
0.16
0.18
0.20
0.23
0.24
0.26
0.29
0.29
0.29
0.29
0.31
0.33
0.33
0.34
0.36

34
43
57
78
95
116
140
170
200
225
255
285
325
370
435
481
537

28
37
48
61
80
94
110
140
165
185
210
235
270
305
350
405
470

30
40
53
70
99
117
140
176
221
258
294
339
402
460
542
624
723

44
55
74
94
120
145
170
210
250
285
315
355
410
460
520
580
680

37
47
61
78
100
120
145
175
210
240
270
300
350
390
440
480
575

39
50
67
85
125
155
190
235
290
330
375
435
510
590
670
750
875

Short Circuit Current


ating for 1Sec. duration

in K. Amps
Al
Cu

0.376
0.564
0.940
1.50
2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
47.00
59.22

0.572
0.858
1.430
2.29
3.58
5.01
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
71.50
90.09

ote
ormal current ratings are given in standard conditions as given in page no - 40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42

27

TABLE - 23

TECHNICAL DETAIL FOR HAVELLS 3.3 KV


SINGLE CORE, AL/COPPER COND., XLPE INSULATED, ARMOURED CABLES
Cable Code A2X a /2X a 3.3KV-EA THED/ U EA THED G ADE
ef Specification IS 7098PA T -2
PHYSICAL PARAMETERS
SI E
cross- Sectional
area Sqmm

ominal
Insulation
thickness
mm
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.8
2.8
3.0
3.3
3.5

25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
C

SS- SETI

AL VIE
1

DUCT

A M U I G
UTE

Minimum Thickness
of uter Sheath
mm

1.40
1.40
1.40
1.60
1.60
1.60
1.60
1.60
1.60
1.60
2.00
2.00
2.00
2.00
2.50

1.24
1.24
1.40
1.40
1.40
1.40
1.40
1.40
1.56
1.56
1.56
1.56
1.72
1.88
2.04

MATE IAL C

Appro .
cable wt kg /km
ith Al.
ith Cu
Cond.
Cond.
350
500
400
600
500
800
650
1100
750
1350
850
1600
950
1900
1100
2250
1350
2850
1550
3400
2000
4500
2400
5500
3000
6900
3650
8600
4500
10700

SSLI KED P L ETH LE E XLPE

Single layer of Aluminium

SHEATH PVC T PE ST-2

C L U

Appro .
ver all
Diameter
mm
18
19
21
23
25
26
28
29
32
34
39
42
47
52
56

Stranded Compacted Circular Aluminium / copper as per Class -2 of IS 8130

I SULATI
3

ominal Diameter
of Armour ire
mm

UTE

ound wires.

F IS 5831

SHEATH BLACK .

PTI

PTI
S

S PVC T PE ST-2/ F
THE

C L U S AS PE

T PE/ F LS T PE
EQUI EME T

Tabulated appro . net weights of cables are only for guidelines for transportation / loading/ unloading purpose.

ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM

25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000

Ma . Cond. D.C. Appro . Cond. A.C.


eactance of
esistance at
esistance at
cable at 50H
20oC in hm/km 90oC in hm/km
in ohms/km
Al
Cu
Al
Cu
Appro .

1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
0.0367
0.0291

0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
0.0221
0.0176

1.54
1.11
0.820
0.567
0.410
0.325
0.265
0.211
0.162
0.130
0.1023
0.0808
0.0648
0.0530
0.0444

0.931
0.671
0.495
0.343
0.248
0.197
0.159
0.127
0.098
0.078
0.0618
0.0489
0.0391
0.0319
0.0268

0.133
0.126
0.122
0.116
0.111
0.106
0.103
0.100
0.097
0.095
0.093
0.091
0.090
0.088
0.086

Capecitance
of cable
in microF/KM
Appro .

0.25
0.29
0.33
0.38
0.44
0.49
0.53
0.58
0.67
0.73
0.84
0.86
0.88
0.94
0.99

ormal Current ating in Amps


ith Aluminium cond.
ith Copper cond.
Ground Duct
Air
Ground Duct
Air

100
120
140
175
205
235
260
295
340
385
440
495
560
620
670

91
110
125
155
185
210
230
260
300
335
380
430
485
530
570

110
135
165
210
255
295
335
390
460
530
620
730
840
960
1070

130
155
185
225
265
300
335
380
435
490
550
610
680
740
780

115
140
165
200
235
265
300
335
385
430
480
530
590
630
660

145
175
215
270
330
380
430
495
590
670
780
900
1020
1140
1250

Short Circuit Current


ating for 1Sec.duration

in K. Amps
Al
Cu

2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
47.00
59.22
75.20
94.00

3.58
5.00
7.15
10.00
13.59
17.16
21.45
26.45
34.32
42.90
57.20
71.50
90.10
114.40
143.00

ote
ormal current ratings are given in standard conditions as given in page no - 40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42

28

TABLE - 24

TECHNICAL DETAIL FOR HAVELLS 3.3 KV THREE CORES, AL/COPPER COND.,


XLPE INSULATED, ARMOURED CABLES
Cable Code A2XF / 2XF , A2X
/2X
3.3KV UE/E
ef Specification IS 7098PA T -2
PHYSICAL PARAMETERS
FLAT ST IP A M U ED
SI E
ominal
Minimum
ominal
Minimum
Appro .
Appro .
crossInsulation Inner Sheath Armour strip outer Sheath
ver all
cable wt kg /km
sectional thickness thickness
thickness
thickness
Diameter
ith Al.
ith Cu
area Sqmm
mm
mm
mm
mm
mm
Cond.
Cond.

25
35
50
70
95
120
150
185
240
300
400
C

2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2

0.3
0.3
0.4
0.4
0.4
0.5
0.5
0.5
0.6
0.6
0.7

SS- SECTI

AL VIE
1

0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

1.40
1.56
1.56
1.56
1.72
1.72
1.88
2.04
2.20
2.20
2.36

DUCT

I SULATI
I

A M U I G

1100
1300
1500
1800
2150
2500
2850
3350
4100
4750
5750

1550
1950
2450
3100
3900
4750
5650
6800
8550
10350
13200

1.60
1.60
2.00
2.00
2.00
2.00
2.50
2.50
2.50
2.50
3.15

1.56
1.56
1.56
1.56
1.72
1.88
2.04
2.04
2.20
2.36
2.68

I ES A M U ED
Appro .
cable wt kg /km
ith Al.
ith Cu
Cond.
Cond.

30
33
35
38
42
45
48
51
56
60
67

1450
1600
2100
2400
2850
3300
4100
4650
5450
6300
8350

1900
2250
3050
3700
4600
5550
6900
8100
9900
11900
15800

Material - Aluminium /Copper - Shape stranded compacted shaped.

28
31
33
36
39
42
44
48
52
56
62

U D
ominal
Minimum
Appro .
diameter outer Sheath
ver all
of armour thickness
Diameter
wire mm
mm
mm

Crosslinked Polyethylene XLPE

ed, ellow & Blue

SHEATH PVC as per IS 7098PT-1

UTE

Single layer of Galvanized steel

SHEATH PVC T PE ST-2

C L U

UTE

ound wires / Flat Strips

F IS 5831

SHEATH BLACK.

PTI

PTI
S

T PE/ F LS T PE

any other colour as per requirement.

Tabulated appro . net wt. of cables are only guidelines for transportation, loading &unloading purpose.
Please ref page no 43 for normal delivery lengths & packing details.

ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM

25
35
50
70
95
120
150
185
240
300
400

Ma . Cond. D.C. Appro . Cond. A.C. pp.. eactance App. Capecitance


ormal Current ating in Amps
esistance at
esistance at
at 50H
of cable
ith Aluminium cond.
ith Copper cond.
20oC in hm/km 90oC in
hm/km
in ohms/km
in microF/KM
Ground Duct
Air
Ground Duct
Air
Al
Cu
Al
Cu
APP
X.
APP
X.

1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778

0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470

1.54
1.11
0.820
0.567
0.410
0.325
0.265
0.211
0.162
0.130
0.1023

0.931
0.671
0.495
0.343
0.248
0.197
0.159
0.127
0.098
0.078
0.0618

0.098
0.094
0.086
0.084
0.081
0.078
0.076
0.075
0.073
0.072
0.071

0.25
0.29
0.33
0.38
0.44
0.49
0.53
0.58
0.67
0.73
0.84

94
115
135
165
195
220
245
280
320
360
410

80
95
110
140
165
185
210
235
270
305
350

99
120
145
185
225
255
295
340
400
460
535

120
145
170
210
250
285
315
355
410
460
520

100
120
145
175
210
240
270
300
350
390
440

125
155
190
235
290
330
375
435
510
590
670

Short Circuit Current


ating for 1Sec.duration

in K. Amps
Al
Cu

2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60

3.58
5.00
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20

ote
ormal current ratings are given in standard conditions as given in page no - 40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42

Pay-off CCV Line

Triple Head E trusion Line

29

TABLE - 25

TECHNICAL DETAIL FOR HAVELLS 3.8/6.6 KV SINGLE CORE, AL/COPPER COND.,


XLPE INSULATED, ARMOURED CABLES
Cable Code A2X a /2X a 6.6KV-EA THED G ADE
ef Specification IS 7098PA T -2
PHYSICAL PARAMETERS
SI E
cross-Sectional
area Sqmm
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
C

SS- SECTI

ominal
Insulation
thickness
mm
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
3.0
3.3
3.5
3.5
3.5
3.6

Minimum
Inner Sheath
thickness
mm
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.4
0.4
0.4
0.5
0.5
0.5
0.5

ominal Diameter
of Armour ire
mm

Minimum Thickness
of uter Sheath
mm

1.60
1.60
1.60
1.60
1.60
1.60
1.60
1.60
2.00
2.00
2.00
2.00
2.00
2.50
2.50

1.40
1.40
1.40
1.40
1.40
1.40
1.56
1.56
1.56
1.56
1.72
1.72
1.88
2.04
2.20

Appro .
ver all
Diameter
mm
23
24
25
27
28
30
32
34
37
39
44
47
51
57
61

Appro .
cable wt kg /km
ith Al.
ith Cu
Cond.
Cond.
600
750
650
850
700
1000
800
1250
950
1550
1050
1800
1200
2100
1400
2550
1700
3200
2000
3850
2450
4900
2800
5900
3400
7300
4300
9200
5100
11300

AL VIE
1

DUCT

Stranded Compacted Circular Aluminium / copper as per Class -2 of IS 8130

Conductor screening E truded Semiconducting Compound

I SULATI

MATE IAL C

I SULATI

SC EE I G E truded semiconducting compound followed by helically wrapped 0.050mm thick copper tape.

4
5
6
7

SSLI KED P L ETH LE E XLPE

E SHEATH E truded PVC

A M U I G Single layer of Aluminium ound wires.


UTE SHEATH PVC T PE ST-2 F IS 5831
C L U

F UTE SHEATH BLACK . PTI

PTI
S A

S PVC T PE ST-2/ F T PE/ F LS T PE


THE C L U S AS PE

EQUI EME T

Tabulated appro . net weights of cables are only for guidelines for transportation / Loading/ Unloading Purpose.

ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM

25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000

Ma . Cond. D.C. Appro . Cond. A.C. eactance of App. Capecitance


ormal Current ating in Amps
esistance at
esistance at
cable at 50H
of cable
ith Aluminium cond.
ith Copper cond.
20oC in hm/km 90oC in hm/km
in ohms/km
in microF/KM
Ground Duct
Air
Ground Duct
Air
Al
Cu
Al
Cu
Approc .
Appro .

1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
0.0367
0.0291

0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
0.0221
0.0176

1.54
1.11
0.820
0.567
0.410
0.325
0.265
0.211
0.162
0.130
0.1023
0.0808
0.0648
0.0530
0.0444

0.931
0.671
0.495
0.343
0.248
0.197
0.159
0.127
0.098
0.078
0.0618
0.0489
0.0391
0.0319
0.0268

0.149
0.142
0.133
0.127
0.121
0.116
0.113
0.109
0.105
0.104
0.102
0.100
0.096
0.094
0.092

0.21
0.24
0.27
0.31
0.36
0.39
0.43
0.47
0.53
0.54
0.57
0.60
0.67
0.76
0.82

100
120
140
175
205
235
260
295
340
385
440
495
560
620
680

90
105
125
155
180
205
230
260
300
335
380
430
480
530
580

120
145
170
215
260
305
345
395
470
540
630
730
840
960
1070

130
155
185
225
265
300
335
380
435
490
550
610
680
740
790

115
140
160
195
235
265
295
330
380
425
480
530
580
630
670

155
185
220
275
340
390
440
510
600
680
790
910
1030
1140
1250

Short Circuit Current


ating for 1Sec.duration

in K. Amps
Al
Cu

2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
47.00
59.22
75.20
94.00

3.58
5.00
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
71.50
90.10
114.40
143.00

ote
ormal current ratings are given in standard conditions as given in page no - 40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no.. 42

30

TABLE - 26

TECHNICAL DETAIL FOR HAVELLS 3.8/6.6 KV THREE CORES, AL/COPPER COND.,


XLPE INSULATED, ARMOURED CABLES
Cable Code A2XF / 2XF , A2X
/2X
6.6KVE
ef Specification IS 7098PA T -2
PHYSICAL PARAMETERS
FLAT ST IP A M U ED
SI E
ominal
Minimum
ominal
Minimum
Appro .
Appro .
crossInsulation Inner Sheath Armour strip outer Sheath
ver all
cable wt kg /km
sectional thickness thickness
thickness
thickness
Diameter
ith Al.
ith Cu
area Sqmm
mm
mm
mm
mm
mm
Cond.
Cond.

25
35
50
70
95
120
150
185
240
300
400
C

2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
3.0
3.3

SS- SECTI

0.4
0.4
0.5
0.5
0.5
0.6
0.6
0.6
0.7
0.7
0.7
AL VIE

1 C

0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

1.56
1.72
1.72
1.88
1.88
2.04
2.20
2.20
2.36
2.52
2.84

DUCT

37
39
42
46
50
54
58
61
67
72
82

1800
2000
2300
2800
3300
3800
4300
4800
5900
6800
8500

U D
ominal
Minimum
Appro .
diameter outer Sheath
ver all
of armour thickness
Diameter
wire mm
mm
mm

2250
2650
3250
4100
5050
6050
7100
8250
10350
12400
15950

2.00
2.00
2.00
2.00
2.50
2.50
2.50
2.50
3.15
3.15
4.00

1.72
1.72
1.88
1.88
2.04
2.20
2.20
2.36
2.52
2.68
3.00

40
42
45
49
54
58
61
65
72
77
88

I ES A M U ED
Appro .
cable wt kg /km
ith Al.
ith Cu
Cond.
Cond.

2500
2800
3200
3700
4700
5400
5900
6600
8400
9700
13000

2950
3450
4150
5000
6450
7650
8700
10050
12850
15300
20450

Stranded Compacted Circular Aluminium / copper as per Class -2 of IS 8130

2 Conductor screening E truded Semiconducting Compound


3 I SULATI
MATE IAL C
SSLI KED P L ETH LE E XLPE
4 I SULATI

SC EE I G E truded semiconducting compound followed by helically wrapped 0.050mm thick copper tape.

5 PVC FILLE S
6 I
E SHEATH E truded PVC
7
A M U I G Single layer of Galvanized Flat strip/
8

UTE SHEATH PVC T PE ST-2 F IS 5831

ound wires.
PTI

S PVC T PE ST-2/ F T PE/ F LS T PE

C L U
F UTE SHEATH BLACK . PTI
S A
THE C L U S AS PE
EQUI EME T
Tabulated appro . net weights of cables are only for guidelines for transportation / Loading/ Unloading Purpose.

ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM

Ma . Cond. D.C. Appro . Cond. A.C.


eactance of
esistance at
esistance at
cable at 50H
20oC in hm/km 90oC in hm/km
in ohms/km
Al
Cu
Al
Cu
APP
X.

Capecitance
of cable
in microF/KM
APP
X.

ormal Current ating in Amps


ith Aluminium cond.
ith Copper cond.
Ground Duct
Air
Ground Duct
Air

25
1.20
0.727 1.54
0.931
0.126
0.21
95
82
105
120
35
0.868 0.524 1.11
0.671
0.120
0.24
115
97
125
145
50
0.641 0.387 0.820
0.495
0.114
0.27
130
115
150
170
70
0.443 0.268 0.567
0.343
0.107
0.31
160
140
190
210
95
0.320 0.193 0.410
0.248
0.102
0.36
190
165
230
250
120
0.253 0.153 0.325
0.197
0.098
0.39
220
190
260
280
150
0.206 0.1240 0.265
0.159
0.095
0.43
245
210
295
310
185
0.164 0.0991 0.211
0.127
0.093
0.47
275
240
335
350
240
0.125 0.0754 0.162
0.098
0.090
0.53
315
275
395
400
300
0.100 0.0601 0.130
0.078
0.090
0.54
355
310
450
445
400
0.0778 0.0470 0.1023 0.0618
0.087
0.57
400
350
520
500
ote
ormal current ratings are given in standard conditions as given in page no - 40,41 , if site conditions are
multiplied by rating factor as given in page no. 42

Short Circuit Current


ating for 1Sec.duration

in K. Amps
Al
Cu

105 135
2.35
3.58
125 165
3.29
5.01
150 195
4.70
7.15
180 240
6.58
10.01
215 295
8.93
13.59
240 335
11.28
17.16
270 380
14.10
21.45
305 430
17.39
26.46
350 500
22.56
34.32
390 570
28.20
42.90
440 650
37.60
57.20
different, current rating should be

Double Twist Bunching Machine

31

TABLE - 27

TECHNICAL DETAIL FOR HAVELLS 6.6/6.6KV & 6.35/11 KV SINGLE CORE, AL/COPPER COND.,
XLPE INSULATED, ARMOURED CABLES

Cable Code A2X a /2X a

6.6KV -U EA THED

PHYSICAL PARAMETERS

11KV EA THED G ADE

SI E
cross-Sectional
area Sqmm

ominal
Insulation
thickness
mm

Minimum
Inner Sheath
thickness
mm

ominal Diameter
of Armour ire
mm

25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000

3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6

0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.4
0.4
0.4
0.5
0.5
0.5
0.5
0.5

1.60
1.60
1.60
1.60
1.60
1.60
1.60
2.00
2.00
2.00
2.00
2.00
2.00
2.50
2.50

SS- SECTI

ef Specification IS 7098PA T -2

Minimum Thickness
of uter Sheath
mm

Appro .
ver all
Diameter
mm

1.40
1.40
1.40
1.40
1.40
1.56
1.56
1.56
1.56
1.56
1.72
1.72
1.88
2.04
2.20

Appro .
cable wt kg /km
ith Al.
ith Cu
Cond.
Cond.

24
25
26
28
30
32
33
36
39
41
44
47
51
57
61

650
700
800
900
1050
1200
1300
1600
1850
2050
2500
2900
3450
4300
5100

800
900
1100
1300
1650
1950
2200
2750
3350
3900
5000
6000
7350
9250
11300

AL VIE
1

DUCT

Stranded Compacted Circular Aluminium / copper as per Class -2 of IS 8130

Conductor screening E truded Semiconducting Compound

I SULATI

MATE IAL C

I SULATI

SC EE I G E truded semiconducting compound followed by helically wrapped 0.050mm thick copper tape.

4
5
6
7

SSLI KED P L ETH LE E XLPE

E SHEATH E truded PVC

A M U I G Single layer of Aluminium ound wires.


UTE SHEATH PVC T PE ST-2 F IS 5831
C L U

F UTE SHEATH BLACK . PTI

PTI
S A

S PVC T PE ST-2/ F T PE/ F LS T PE


THE C L U S AS PE

EQUI EME T

Tabulated appro . net weights of cables are only for guidelines for transportation / Loading/ Unloading Purpose.

ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM

25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000

Ma . Cond. D.C. Appro . Cond. A.C.


eactance of
esistance at
esistance at
cable at 50H
20oC in hm/km 90oC in hm/km
in ohms/km
Al
Cu
Al
Cu
Appro

1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
0.0367
0.0291

0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
0.0221
0.0176

1.54
1.11
0.820
0.567
0.410
0.325
0.265
0.211
0.162
0.130
0.1023
0.0808
0.0648
0.0530
0.0444

0.931
0.671
0.495
0.343
0.248
0.197
0.159
0.127
0.098
0.078
0.0618
0.0489
0.0391
0.0319
0.0268

0.164
0.156
0.147
0.139
0.133
0.127
0.124
0.120
0.117
0.113
0.110
0.107
0.104
0.100
0.098

Capecitance
of cable
in microF/KM
Appro

0.18
0.20
0.22
0.26
0.29
0.32
0.35
0.38
0.43
0.46
0.53
0.59
0.66
0.74
0.82

ormal Current ating in Amps


ith Aluminium cond.
ith Copper cond.
Ground Duct
Air
Ground Duct
Air

100
120
140
175
205
235
260
295
340
385
440
495
560
620
680

90
105
125
155
180
205
230
260
300
335
380
430
480
530
580

120
145
170
215
260
305
345
395
470
540
630
730
840
960
1070

130
155
185
225
265
300
335
380
435
490
550
610
680
740
790

115
140
160
195
235
265
295
330
380
425
480
530
580
630
670

155
185
220
275
340
390
440
510
600
680
790
910
1030
1140
1250

Short Circuit Current


ating for 1Sec.duration

in K. Amps
Al
Cu

2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
47.00
59.22
75.20
94.00

3.58
5.00
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
71.50
90.10
114.40
143.00

ote ormal current ratings are given in standard conditions as given in page no -40,41 , if site conditions are different, current rating should be multiplied
by rating factor as given in page no. 42

32

TABLE - 28

TECHNICAL DETAIL FOR HAVELLS 6.6/6.6KV & 6.35/11 KV THREE CORES, AL/COPPER COND.,
XLPE INSULATED, ARMOURED CABLES
Cable Code A2XF / 2XF , A2X
/2X
6.6KV UE / 11KV E
ef Specification IS 7098PA T-2
PHYSICAL PARAMETERS
FLAT ST IP A M U ED
SI E
ominal
Minimum
ominal
Minimum
Appro .
crossInsulation Inner Sheath Armour strip outer Sheath
ver all
sectional thickness thickness
thickness
thickness
Diameter
area Sqmm
mm
mm
mm
mm
mm

25
35
50
70
95
120
150
185
240
300
400
C

3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6

SS- SECTI

0.4
0.5
0.5
0.5
0.6
0.6
0.6
0.7
0.7
0.7
0.7

0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

1.72
1.72
1.88
1.88
2.04
2.20
2.20
2.36
2.52
2.68
2.84

41
43
46
50
54
58
61
65
71
75
83

Appro .
cable wt kg /km
ith Al.
ith Cu
Cond.
Cond.

2100
2350
2700
3100
3700
4200
4700
5300
6300
7200
8700

U D I ES A M U ED
ominal
Minimum
Appro .
Appro .
diameter outer Sheath
ver all
cable wt kg /km
of armour thickness
Diameter
ith Al.
ith Cu
wire mm
mm
mm
Cond.
Cond.

2550
2950
3650
4400
5450
6450
7500
8750
10750
12800
16150

2.00
2.00
2.50
2.50
2.50
2.50
2.50
3.15
3.15
3.15
4.00

1.72
1.88
2.04
2.04
2.20
2.20
2.36
2.52
2.68
2.84
3.00

43
46
50
54
58
62
65
70
76
80
90

2800
3200
4000
4500
5200
5800
6400
7900
9000
10000
13500

3250
3850
4950
5800
6950
8050
9200
11350
13500
15600
20500

AL VIE
1 C

DUCT

Stranded Compacted Circular Aluminium / copper as per Class -2 of IS 8130

2 Conductor screening E truded Semiconducting Compound


3 I SULATI

MATE IAL C

4 I SULATI

SC EE I G E truded semiconducting compound followed by helically wrapped 0.050mm thick copper tape.

SSLI KED P L ETH LE E XLPE

5 PVC FILLE S
6 I
7
8

E SHEATH E truded PVC

A M U I G Single layer of Galvanized Flat strip/ ound wires.


UTE SHEATH PVC T PE ST-2 F IS 5831

PTI

S PVC T PE ST-2/ F T PE/ F LS T PE

C L U
F UTE SHEATH BLACK . PTI
S A
THE C L U S AS PE
EQUI EME T
Tabulated appro . net weights of cables are only for guidelines for transportation / Loading/ Unloading Purpose.

ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM

25
35
50
70
95
120
150
185
240
300
400

Ma . Cond. D.C. Appro . Cond. A.C.


esistance at
esistance at
o
o
20 C in hm/km 90 C in hm/km
Al
Cu
Al
Cu

1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778

0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470

1.54
1.11
0.820
0.567
0.410
0.325
0.265
0.211
0.162
0.130
0.1023

0.931
0.671
0.495
0.343
0.248
0.197
0.159
0.127
0.098
0.078
0.0618

eactance
at 50H
in ohms/km
APP
X.

0.133
0.126
0.118
0.116
0.107
0.102
0.099
0.097
0.084
0.093
0.089

App. Capecitance
ormal Current ating in Amps
of cable
ith Aluminium cond.
ith Copper cond.
in microF/KM
Ground Duct
Air
Ground Duct
Air
APP
X.

0.18
0.20
0.22
0.26
0.29
0.32
0.35
0.38
0.43
0.46
0.53

95
115
130
160
190
220
245
275
315
355
400

82
97
115
140
165
190
210
240
275
310
350

105
125
150
190
230
260
295
335
395
450
520

120
145
170
210
250
280
310
350
400
445
500

105
125
150
180
215
240
270
305
350
390
440

135
165
195
240
295
335
380
430
500
570
650

Short Circuit Current


ating for 1Sec.duration

in K. Amps
Al
Cu

2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60

3.58
5.01
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20

ote
ormal current ratings are given in standard conditions as given in page no -40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42

33

TABLE - 29

TECHNICAL DETAIL FOR HAVELLS 11/11 KV SINGLE CORE, AL/COPPER COND.,


XLPE INSULATED, ARMOURED CABLES
Cable Code A2X a /2X a 11KV - U -EA THED G ADE
ef Specification IS 7098PA T-2
PHYSICAL PARAMETERS
SI E
cross- Sectional
area Sqmm
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
C

SS- SECTI

ominal
Insulation
thickness
mm
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5

Minimum
Inner Sheath
thickness
mm
0.3
0.3
0.3
0.3
0.3
0.4
0.4
0.4
0.4
0.4
0.5
0.5
0.5
0.6
0.6

ominal Diameter
of Armour ire
mm

Minimum Thickness
of uter Sheath
mm

1.60
1.60
1.60
1.60
1.60
2.00
2.00
2.00
2.00
2.00
2.00
2.50
2.50
2.50
2.50

1.40
1.40
1.56
1.56
1.56
1.56
1.56
1.56
1.72
1.72
1.88
1.88
2.04
2.20
2.20

Appro .
ver all
Diameter
mm
28
29
31
33
34
37
38
40
43
44
48
53
56
61
65

Appro .
cable wt kg /km
ith Al.
ith Cu
Cond.
Cond.
900
1050
950
1150
1100
1400
1200
1650
1400
2000
1600
2350
1700
2600
1900
3050
2200
3700
2500
4350
2900
5400
3500
6600
4100
8000
4900
9900
5700
11900

AL VIE
1

DUCT

Stranded Compacted Circular Aluminium / copper as per Class -2 of IS 8130

Conductor screening E truded Semiconducting Compound

I SULATI

MATE IAL C

I SULATI

SC EE I G E truded semiconducting compound followed by helically wrapped 0.050mm thick copper tape.

4
5
6
7

SSLI KED P L ETH LE E XLPE

E SHEATH E truded PVC

A M U I G Single layer of Aluminium ound wires.


UTE SHEATH PVC T PE ST-2 F IS 5831
C L U

F UTE SHEATH BLACK . PTI

PTI
S A

S PVC T PE ST-2/ F T PE/ F LS T PE


THE C L U S AS PE

EQUI EME T

Tabulated appro . net weights of cables are only for guidelines for transportation / Loading/ Unloading Purpose.

ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM

25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000

Ma . Cond. D.C. Appro . Cond. A.C.


eactance of
esistance at
esistance at
cable at 50H
20oC in hm/km 90oC in hm/km
in ohms/km
Al
Cu
Al
Cu
Appro .

1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
0.0367
0.0291

0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
0.0221
0.0176

1.54
1.11
0.820
0.567
0.410
0.325
0.265
0.211
0.162
0.130
0.1023
0.0808
0.0648
0.0530
0.0444

0.931
0.671
0.495
0.343
0.248
0.197
0.159
0.127
0.098
0.078
0.0618
0.0489
0.0391
0.0319
0.0268

0.164
0.156
0.147
0.139
0.132
0.126
0.124
0.120
0.116
0.112
0.109
0.105
0.102
0.097
0.096

Capecitance
of cable
in microF/KM
Appro .

0.14
0.16
0.17
0.20
0.21
0.23
0.25
0.26
0.29
0.32
0.35
0.39
0.43
0.50
0.56

ormal Current ating in Amps


ith Aluminium cond.
ith Copper cond.
Ground Duct
Air
Ground Duct
Air

100
120
140
175
205
235
260
295
340
385
440
495
560
620
680

90
105
125
155
180
205
230
260
300
335
380
430
480
530
580

120
145
170
215
260
305
345
395
470
540
630
730
840
960
1070

130
155
185
225
265
300
335
380
435
490
550
610
680
740
790

115
140
160
195
235
265
295
330
380
425
480
530
580
630
670

155
185
220
275
340
390
440
510
600
680
790
910
1030
1140
1250

Short Circuit Current


ating for 1Sec.duration

in K. Amps
Al
Cu

2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
47.00
59.22
75.20
94.00

3.58
5.00
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
71.50
90.10
114.40
143.00

ote
ormal current ratings are given in standard conditions as given in page no - 40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42

34

TABLE - 30

TECHNICAL DETAIL FOR HAVELLS 11/11KV THREE CORES, AL/COPPER COND.,


XLPE INSULATED, ARMOURED CABLES
Cable Code A2XF / 2XF , A2X
/2X
11KVUE
ef Specification IS 7098PA T -2
PHYSICAL PARAMETERS
FLAT ST IP A M U ED
SI E
ominal
Minimum
ominal
Minimum
Appro .
Appro .
crossInsulation Inner Sheath Armour strip outer Sheath
ver all
cable wt kg /km
sectional thickness thickness
thickness
thickness
Diameter
ith Al.
ith Cu
area Sqmm
mm
mm
mm
mm
mm
Cond.
Cond.

25
5.5
0.5
35
5.5
0.5
50
5.5
0.6
70
5.5
0.6
95
5.5
0.6
120
5.5
0.7
150
5.5
0.7
185
5.5
0.7
240
5.5
0.7
300
5.5
0.7
400
5.5
0.7
C
SS- SETI
AL VIE

0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

1 C

1.88
2.04
2.20
2.20
2.36
2.52
2.52
2.68
2.84
3.00
3.00

DUCT

50
53
56
60
64
68
71
75
81
85
93

3000
3200
3700
4100
4800
5400
5900
6500
7600
8600
10000

3500
3850
4600
5400
6567
7632
8690
9950
12050
14200
17500

U D
ominal
Minimum
Appro .
diameter outer Sheath
ver all
of armour thickness
Diameter
wire mm
mm
mm

2.50
2.50
2.50
2.50
3.15
3.15
3.15
3.15
3.15
4.00
4.00

2.04
2.20
2.20
2.36
2.52
2.52
2.68
2.84
3.00
3.00
3.00

I ES A M U ED
Appro .
cable wt kg /km
ith Al.
ith Cu
Cond.
Cond.

54
57
60
64
69
73
76
80
85
91
98

4300
4700
5100
5800
7300
8000
8600
9400
11000
13000
15000

4750
5350
6050
7100
9100
10250
11400
12850
15500
18600
22450

Stranded Compacted Circular Aluminium / copper as per Class -2 of IS 8130

2 Conductor screening E truded Semiconducting Compound


3 I SULATI
MATE IAL C
SSLI KED P L ETH LE E XLPE
4 I SULATI

SC EE I G E truded semiconducting compound followed by helically wrapped 0.050mm thick copper tape.

5 PVC FILLE S
6 I

E SHEATH E truded PVC

7
A M U I G
8

Single layer of Galvanized Flat strip/ ound wires.

UTE SHEATH PVC T PE ST-2 F IS 5831

PTI

S PVC T PE ST-2/ F T PE/ F LS T PE

C L U
F UTE SHEATH BLACK . PTI
S A
THE C L U S AS PE
EQUI EME T
Tabulated appro . net weights of cables are only for guidelines for transportation / Loading/ Unloading Purpose.

ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM

25
35
50
70
95
120
150
185
240
300
400

Ma . Cond. D.C. Appro . Cond. A.C.


esistance at
esistance at
o
o
20 C in hm/km 90 C in hm/km
Al
Cu
Al
Cu

1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778

0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470

1.54
1.11
0.820
0.567
0.410
0.325
0.265
0.211
0.162
0.130
0.1023

0.931
0.671
0.495
0.343
0.248
0.197
0.159
0.127
0.0976
0.0778
0.0618

eactance of App. Capecitance


ormal Current ating in Amps
cabe at 50H
of cable
ith Aluminium cond.
ith Copper cond.
in ohms/km
in microF/KM
Ground Duct
Air
Ground Duct
Air
APP
X.
APP
X.

0.145
0.138
0.129
0.124
0.116
0.112
0.108
0.105
0.102
0.0999
0.0954

0.14
0.16
0.17
0.20
0.21
0.23
0.25
0.26
0.29
0.32
0.35

95
115
130
160
190
220
245
275
315
355
400

82
97
115
140
165
190
210
240
275
310
350

105
125
150
190
230
260
295
335
395
450
520

120
145
170
210
250
280
310
350
400
445
500

105
125
150
180
215
240
270
305
350
390
440

135
165
195
240
295
335
380
430
500
570
650

Short Circuit Current


ating for 1Sec.duration

in K. Amps
Al
Cu

2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60

3.58
5.01
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20

ote
ormal current ratings are given in standard conditions as given in page no - 40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42

Production in process. . .
35

TABLE - 31

TECHNICAL DETAIL FOR HAVELLS 12.7/22 KV SINGLE CORE, AL/COPPER COND.,


XLPE INSULATED, ARMOURED CABLES
Cable Code A2X a /2X a 22KV - EA THED G ADE
ef Specification IS 7098PA T-2
PHYSICAL PARAMETERS
SI E
cross- Sectional
area Sqmm

25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
SS- SECTI

ominal
Insulation
thickness
mm
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
AL VIE

Minimum
Inner Sheath
thickness
mm
0.3
0.3
0.3
0.3
0.4
0.4
0.4
0.4
0.4
0.4
0.5
0.5
0.5
0.6
0.6

ominal Diameter
of Armour ire
mm

Minimum Thickness
of uter Sheath
mm

1.60
1.60
1.60
1.60
2.00
2.00
2.00
2.00
2.00
2.00
2.00
2.50
2.50
2.50
2.50

1.40
1.40
1.56
1.56
1.56
1.56
1.56
1.56
1.72
1.72
1.88
1.88
2.04
2.20
2.36

Conductor screening E truded Semiconducting Compound

3
4
5
6
7

DUCT

Appro .
ver all
Diameter
mm
29
31
32
34
36
38
39
41
44
46
50
53
57
62
66

Appro .
cable wt kg /km
ith Al.
ith Cu
Cond.
Cond.
950
1100
1050
1250
1150
1500
1300
1750
1600
2200
1700
2450
1800
2750
2000
3150
2300
3800
2600
4500
3000
5500
3600
6700
4300
8200
5000
9950
5800
12000

Stranded Compacted Circular Aluminium / copper as per Class -2 of IS 8130

I SULATI

MATE IAL C

I SULATI

SC EE I G E truded semiconducting compound followed by helically wrapped 0.050mm thick copper tape.

SSLI KED P L ETH LE E XLPE

E SHEATH E truded PVC

A M U I G Single layer of Aluminium ound wires.


UTE SHEATH PVC T PE ST-2 F IS 5831
C L U

F UTE SHEATH BLACK . PTI

PTI
S A

S PVC T PE ST-2/ F T PE/ F LS T PE


THE C L U S AS PE

EQUI EME T

Tabulated appro . net weights of cables are only for guidelines for transportation / Loading/ Unloading Purpose.

ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM

25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000

Ma . Cond. D.C. Appro . Cond. A.C.


eactance of App. Capecitance
ormal Current ating in Amps
esistance at
esistance at
cable at 50H
of cable
ith Aluminium cond.
ith Copper cond.
20oC in hm/km 90oC in hm/km
in ohms/km
in microF/KM
Ground Duct
Air
Ground Duct
Air
Al
Cu
Al
Cu
APP
X.
APP
X.

1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
0.0367
0.0291

0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
0.0221
0.0176

1.54
1.11
0.820
0.567
0.410
0.325
0.265
0.211
0.162
0.130
0.1023
0.0808
0.0648
0.0530
0.0444

0.931
0.671
0.495
0.343
0.248
0.197
0.159
0.127
0.098
0.078
0.0618
0.0489
0.0391
0.0319
0.0268

0.166
0.158
0.149
0.140
0.134
0.130
0.126
0.122
0.118
0.113
0.110
0.107
0.103
0.0997
0.097

0.13
0.15
0.16
0.18
0.20
0.22
0.23
0.25
0.27
0.30
0.32
0.36
0.40
0.46
0.52

100
120
140
170
200
225
250
280
315
345
385
415
450
485
510

90
105
120
150
175
195
215
240
275
300
330
360
385
415
435

120
145
175
220
265
300
340
385
450
500
570
640
720
790
850

130
155
180
215
255
285
310
345
390
420
455
480
510
540
550

115
135
155
190
220
245
270
300
335
360
395
415
440
460
475

155
185
225
280
335
380
430
485
560
620
690
750
820
840
940

Short Circuit Current


ating for 1Sec.duration

in K. Amps
Al
Cu

2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
47.00
59.22
75.20
94.00

3.58
5.00
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
71.50
90.10
114.40
143.00

ote
ormal current ratings are given in standard conditions as given in page no- 40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42

36

TABLE - 32

TECHNICAL DETAIL FOR HAVELLS 12.7/22 KV THREE CORES, AL/COPPER COND.,


XLPE INSULATED, ARMOURED CABLES
Cable Code A2XF / 2XF , A2X
/2X
22KV- E
ef Specification IS 7098PA T -2
PHYSICAL PARAMETERS
FLAT ST IP A M U ED
SI E
ominal
Minimum
ominal
Minimum
Appro .
Appro .
crossInsulation Inner Sheath Armour strip outer Sheath
ver all
cable wt kg /km
sectional thickness thickness
thickness
thickness
Diameter
ith Al.
ith Cu
area Sqmm
mm
mm
mm
mm
mm
Cond.
Cond.

25
35
50
70
95
120
150
185
240
300
400

6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0

SS- SECTI

0.5
0.6
0.6
0.6
0.7
0.7
0.7
0.7
0.7
0.7
0.7

AL VIE

1 C

0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

2.04
2.04
2.20
2.36
2.36
2.52
2.68
2.68
2.84
3.00
3.00

DUCT

53
56
59
63
67
70
74
77
83
88
95

3200
3500
3900
4400
5000
5700
6200
6800
7900
8900
10500

U D
ominal
Minimum
Appro .
diameter outer Sheath
ver all
of armour thickness
Diameter
wire mm
mm
mm

3650
4150
4850
5700
6800
7950
9000
10250
12350
14500
17950

2.50
2.50
2.50
2.50
3.15
3.15
3.15
3.15
4.00
4.00
4.00

2.20
2.20
2.36
2.36
2.52
2.68
2.68
2.84
3.00
3.00
3.00

I ES A M U ED
Appro .
cable wt kg /km
ith Al.
ith Cu
Cond.
Cond.

56
59
61
65
72
75
78
83
90
93
102

4600
5000
5400
6100
7600
8300
9000
9800
12500
13500
15500

5050
5650
6350
7400
9350
10550
11800
13250
16950
19100
22950

Stranded Compacted Circular Aluminium / copper as per Class -2 of IS 8130

2 Conductor screening E truded Semiconducting Compound


3 I SULATI

MATE IAL C

4 I SULATI

SC EE I G E truded semiconducting compound followed by helically wrapped 0.050mm thick copper tape.

SSLI KED P L ETH LE E XLPE

5 PVC FILLE S
6 I
E SHEATH E truded PVC
7
A M U I G Single layer of Galvanized Flat strip/
8

UTE SHEATH PVC T PE ST-2 F IS 5831

ound wires.
PTI

S PVC T PE ST-2/ F T PE/ F LS T PE

C L U
F UTE SHEATH BLACK . PTI
S A
THE C L U S AS PE
EQUI EME T
Tabulated appro . net weights of cables are only for guidelines for transportation / Loading/ Unloading Purpose.

ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM

25
35
50
70
95
120
150
185
240
300
400

Ma . Cond. D.C. Appro . Cond. A.C.


eactance of
esistance at
esistance at
cable at 50H
20oC in hm/km 90oC in hm/km
in ohms/km
Al
Cu
Al
Cu
APP
X.

1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778

0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470

1.54
1.11
0.820
0.567
0.410
0.325
0.265
0.211
0.162
0.130
0.1023

0.931
0.671
0.495
0.343
0.248
0.197
0.159
0.127
0.098
0.078
0.0618

0.148
0.141
0.132
0.125
0.119
0.114
0.111
0.107
0.104
0.102
0.097

Capecitance
of cable
in microF/KM
APP
X.

0.13
0.15
0.16
0.18
0.20
0.22
0.23
0.25
0.27
0.30
0.32

ormal Current ating in Amps


ith Aluminium cond.
ith Copper cond.
Ground Duct
Air
Ground Duct
Air

90
110
130
160
190
215
240
270
310
350
395

85
100
115
140
170
190
215
240
275
310
355

110
130
155
190
230
265
300
340
400
455
530

120
145
170
205
245
275
305
345
395
440
495

100
120
150
180
215
245
275
305
350
390
440

135
165
200
245
300
340
385
435
510
580
660

Short Circuit Current


ating for 1Sec.duration

in K. Amps
Al
Cu

2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60

3.58
5.01
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20

ote
ormal current ratings are given in standard conditions as given in page no - 40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42

Catter Pillar

37

TABLE - 33

TECHNICAL DETAIL FOR HAVELLS 19/33 KV SINGLE CORE, AL/COPPER COND.,


XLPE INSULATED, ARMOURED CABLES
Cable Code A2X a /2X a 33KV - EA THED G ADE
ef Specification IS 7098PA T -2
PHYSICAL PARAMETERS
SI E
cross- Sectional
area Sqmm

25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
SS- SECTI

ominal
Insulation
thickness
mm
8.80
8.80
8.80
8.80
8.80
8.80
8.80
8.80
8.80
8.80
8.80
8.80
8.80
8.80
8.80
AL VIE
1

Minimum
Inner Sheath
thickness
mm
0.40
0.40
0.40
0.40
0.40
0.40
0.40
0.50
0.50
0.50
0.50
0.60
0.60
0.60
0.70

DUCT

ominal Diameter
of Armour ire
mm

Minimum Thickness
of uter Sheath
mm

2.00
2.00
2.00
2.00
2.00
2.00
2.00
2.00
2.00
2.50
2.50
2.50
2.50
3.15
3.15

1.56
1.56
1.56
1.56
1.72
1.72
1.72
1.72
1.88
2.04
2.04
2.20
2.20
2.36
2.52

Appro .
ver all
Diameter
mm
36
38
39
40
43
44
46
47
50
53
57
60
64
70
74

Appro .
cable wt kg /km
ith Al.
ith Cu
Cond.
Cond.
1400
1450
1500
1600
1600
1800
1800
2100
2000
2500
2100
2700
2300
3130
2500
3550
2800
4200
3300
5050
3800
6200
4300
7300
4900
8800
6000
10500
6900
13000

Stranded Compacted Circular Aluminium / copper as per Class -2 of IS 8130

Conductor screening E truded Semiconducting Compound

I SULATI

MATE IAL C

I SULATI

SC EE I G E truded semiconducting compound followed by helically wrapped 0.050mm thick copper tape.

4
5
6
7

SSLI KED P L ETH LE E XLPE

E SHEATH E truded PVC

A M U I G Single layer of Aluminium ound wires.


UTE SHEATH PVC T PE ST-2 F IS 5831
C L U

F UTE SHEATH BLACK . PTI

PTI
S A

S PVC T PE ST-2/ F T PE/ F LS T PE


THE C L U S AS PE

EQUI EME T

Tabulated appro . net weights of cables are only for guidelines for transportation / Loading/ Unloading Purpose.

ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM

25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000

Ma . Condt. D.C. Appro . Cond. A.C.


eactance of
esistance at
esistance at
cable at 50H
20oC in hm/km 90oC in hm/km
in ohms/km
Al
Cu
Al
Cu
Appro .

1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
0.0367
0.0291

0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
0.0221
0.0176

1.54
1.11
0.820
0.567
0.410
0.325
0.265
0.211
0.162
0.130
0.1023
0.0808
0.0648
0.0530
0.0444

0.931
0.671
0.495
0.343
0.248
0.197
0.159
0.127
0.098
0.078
0.0618
0.0489
0.0391
0.0319
0.0268

0.175
0.169
0.161
0.152
0.145
0.140
0.135
0.130
0.126
0.122
0.117
0.113
0.111
0.105
0.102

Capecitance
of cable
in microF/KM
Appro .

0.10
0.11
0.12
0.14
0.15
0.16
0.18
0.19
0.21
0.23
0.25
0.27
0.29
0.34
0.37

ormal Current ating in Amps


ith Aluminium cond.
ith Copper cond.
Ground Duct
Air
Ground Duct
Air

100
120
140
170
200
225
250
280
315
345
385
415
450
485
510

90
105
120
150
175
195
215
240
275
300
330
360
385
415
435

120
145
175
220
265
300
340
385
450
500
570
640
720
790
850

130
155
180
215
255
285
310
345
390
420
455
480
510
540
550

115
135
155
190
220
245
270
300
335
360
395
415
440
460
475

155
185
225
280
335
380
430
485
560
620
690
750
820
840
940

Short Circuit Current


ating for 1Sec.duration

in K. Amps
Al
Cu

2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
47.00
59.22
75.20
94.00

3.58
5.00
7.15
10.00
13.59
17.16
21.45
26.46
34.32
42.90
57.20
71.50
90.10
114.40
143.00

ote
ormal current ratings are given in standard conditions as given in page no - 40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42

38

TABLE - 34

TECHNICAL DETAIL FOR HAVELLS 19/33 KV THREE CORES, AL/COPPER COND.,


XLPE INSULATED, ARMOURED CABLES
Cable Code A2XF / 2XF , A2X
/2X
33KV E
ef Specification IS 7098PA T -2
PHYSICAL PARAMETERS
FLAT ST IP A M U ED
SI E
ominal
Minimum
ominal
Minimum
Appro .
Appro .
crossInsulation Inner Sheath Armour strip outer Sheath
ver all
cable wt kg /km
sectional thickness thickness
thickness
thickness
Diameter
ith Al.
ith Cu
area Sqmm
mm
mm
mm
mm
mm
Cond.
Cond.

25
8.80
0.70
35
8.80
0.70
50
8.80
0.70
70
8.80
0.70
95
8.80
0.70
120
8.80
0.70
150
8.80
0.70
185
8.80
0.70
240
8.80
0.70
300
8.80
0.70
400
8.80
0.70
SS- SETI
AL VIE
1 C

0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

2.36
2.52
2.52
2.68
2.84
2.84
3.00
3.00
3.00
3.00
3.00

DUCT

67
70
72
76
80
84
87
90
95
100
108

4700
5100
5500
6100
6800
7500
8100
8800
9900
11000
12500

U D
ominal
Minimum
Appro .
diameter outer Sheath
ver all
of armour thickness
Diameter
wire mm
mm
mm

5150
5750
6450
7400
8550
9750
10900
12250
14350
16600
19950

3.15
3.15
3.15
3.15
3.15
4.00
4.00
4.00
4.00
4.00
4.00

2.68
2.68
2.68
2.84
3.00
3.00
3.00
3.00
3.00
3.00
3.00

72
75
77
81
86
90
94
97
103
106
114

I ES A M U ED
Appro .
cable wt kg /km
ith Al.
ith Cu
Cond.
Cond.

7400
7800
8200
9000
10000
12000
12700
13500
15000
16000
18000

7850
8450
9150
10300
11750
14250
15500
16950
19450
21600
25450

Stranded Compacted Circular Aluminium / copper as per Class -2 of IS 8130

2 Conductor screening E truded Semiconducting Compound


3 I SULATI

MATE IAL C

4 I SULATI

SC EE I G E truded semiconducting compound followed by helically wrapped 0.050mm thick copper tape.

SSLI KED P L ETH LE E XLPE

5 PVC FILLE S
6 I

E SHEATH E truded PVC

7
A M U I G
8

Single layer of Galvanized Flat strip/ ound wires.

UTE SHEATH PVC T PE ST-2 F IS 5831

PTI

S PVC T PE ST-2/ F T PE/ F LS T PE

C L U
F UTE SHEATH BLACK . PTI
S A
THE C L U S AS PE
EQUI EME T
Tabulated appro . net weights of cables are only for guidelines for transportation / Loading/ Unloading Purpose.

ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM

Ma . Cond. D.C. Appro . Cond. A.C.


eactance of
esistance at
esistance at
cable at 50H
20oC in hm/km 90oC in hm/km
in ohms/km
Al
Cu
Al
Cu
APP
X.

Capecitance
of cable
in microF/KM
APP
X.

ormal Current ating in Amps


ith Aluminium cond.
ith Copper cond.
Ground Duct
Air
Ground Duct
Air

25
1.20
0.727 1.54
0.931
0.160
0.10
90
85
110
120
35
0.868 0.524 1.11
0.671
0.153
0.11
110
100
130
145
50
0.641 0.387 0.820
0.495
0.146
0.12
130
115
155
170
70
0.443 0.268 0.567
0.343
0.138
0.14
160
140
190
205
95
0.320 0.193 0.410
0.248
0.130
0.15
190
170
230
245
120
0.253 0.153 0.325
0.197
0.125
0.16
215
190
265
275
150
0.206 0.1240 0.265
0.159
0.122
0.18
240
215
300
305
185
0.164 0.0991 0.211
0.127
0.118
0.19
270
240
340
345
240
0.125 0.0754 0.162
0.098
0.113
0.21
310
275
400
395
300
0.100 0.0601 0.130
0.078
0.111
0.23
350
310
455
440
400
0.0778 0.0470 0.1023 0.0618
0.106
0.25
395
355
530
495
ote
ormal current ratings are given in standard conditions as given in page no - 40,41 , if site conditions are
multiplied by rating factor as given in page no. 42

Short Circuit Current


ating for 1Sec.duration

in K. Amps
Al
Cu

100
135
2.35
3.58
120
165
3.29
5.01
150
200
4.70
7.15
180
245
6.58
10.01
215
300
8.93
13.59
245
340
11.28
17.16
275
385
14.10
21.45
305
435
17.39
26.46
350
510
22.56
34.32
390
580
28.20
42.90
440
660
37.60
57.20
different, current rating should be

Testing Laboratory

39

BASIC ASSUMPTION FOR CURRENT RATINGS & RATING FACTORS


1.

SC PE
The current ratings of cables as indicated in various tables have been calculated on certain assumed conditions.
In actual practice these conditions may be different. Therefore to determine the actual current ratings as per installation conditions, the tabulated
ratings shall be multiplied with appropriate factors

BASIC ASSUMPTI
F
CU E T ATI GS
i
Ma imum permissible temperature - 90C for XLPE insulation, 70C for general purpose PVC, 85C for H PVC

b
i

ii

Ground/Duct temperature - 30C

iii

Ambient temperature - 40C

iv

Thermal resistivity of soil - 150C cm/

Thermal resistivity of Dielectric 650C cm/

vi

Depth of laying - for 1.1KV cables - 750mm, 3.3KV to 11KV-900MM, Above 11KV-1050mm

vii

Single core cables installed in one circuit in following arrangement

viii

Multicore cables installed in single circuit

ating factors

20

25

30

35

40

45

50

55

ormal PVC

1.32

1.25

1.16

1.09

1.00

0.90

0.80

0.80

H PVC

1.22

1.17

1.12

1.06

1.00

0.94

0.87

0.80

XLPE

1.20

1.16

1.11

1.06

1.00

0.95

0.88

0.81

ating factors related to variation in ground temperature


Air temperature in Deg. C
ating factors

iii

15

20

25

30

35

40

45

50

ormal PVC

1.17

1.12

1.06

1.00

0.94

0.

0.79

0.71

H PVC

1.13

1.09

1.04

1.00

0.95

0.90

0.85

0.80

XLPE

1.12

1.08

1.04

1.00

0.96

0.91

0..87

0.82

ating factors related to variation in ground thermal resistivity of soil for 3 single core cables laid direct in ground. Average value
Thermal es. in oC.Cm/
ating factors

iv

100

120

150

200

250

300

1.20

1.10

1.00

0.90

0.81

0.74

ating factors related to variation in ground thermal resistivity of soil for multi core cables laid direct in ground. Average value
Thermal es. in oC.Cm/
ating factors

100

120

150

200

250

300

1.16

1.08

1.00

0.90

0.82

0.76

ating factors related to variation in depth of laying for 1.1kv cables


For cross-sectional area of conductor 25sqmm
Depth of laying cm
75
ating factors

1.00

90

105

120

150

180 & AB VE

0.99

0.98

0.97

0.96

0.95

105

120

150

180 & AB VE

0.97

0.96

0.94

0.93

For cross-sectional area of conductor 25 to 300sqmm


Depth of laying cm
75
90
ating factors

1.00

0.98

For cross-sectional area of conductor above 300sqmm


Depth of laying cm
75
90
ating factors
vi

1.00

0.97

105

120

150

180 & AB VE

0.96

0.95

0.92

0.91

120
0.98

150
0.96

180 & AB VE
0.95

120
0.99

150
0.98

180 & AB VE
0.96

ating factors related to variation in depth of laying for 3.3kv to 11kv cables
Depth of laying cm
ating factors

vii

for XLPE

ATI G FACT S
ating factors related to variation in ambient air temperature
Air temperature in Deg. C

ii

for PVC, 350C cm/

75

90
1.00

105
0.99

ating factors related to variation in depth of laying for above 11kv cables
Depth of laying cm
ating factors

75

90

105
1.00

40

BASIC ASSUMPTION FOR CURRENT RATINGS & RATING FACTORS


GROUP RATING FACTORS
1.

Cable laid direct in Ground

o of cables/
circuits in groups

Multicore cables in horizontal formation


Touching S 15CM
0.8
0.84
0.68
0.74
0.62
0.69
0.58
0.65
0.55
0.62
0.52
0.59
0.5
0.57
0.48
0.55
0.46
0.54
0.45
0.53
0.44
0.52

2
3
4
5
6
7
8
9
10
11
12

S 30CM
0.87
0.79
0.75
0.72
0.69
0.67
0.66
0.65
0.64
0.63
0.62

S 45CM
0.90
0.83
0.80
0.77
0.75
0.73
0.72
0.71
0.70
0.70
0.69

Single cables in horizontal formation


S 60CM
0.91
0.86
0.83
0.80
0.78
0.77
0.75
0.75
0.74
0.74
0.73

Touching S 15CM
0.80
0.85
0.70
0.78
0.64
0.73
0.59
0.70
0.55
0.67
0.53
0.65
0.51
0.64
0.49
0.63
0.48
0.63
0.47
0.62
0.46
0.61

S 30CM
0.90
0.85
0.81
0.79
0.77
0.76
0.76
0.74
0.74
0.73
0.73

S 45CM
0.92
0.88
0.86
0.84
0.83
0.82
0.82
0.81
0.81
0.80
0.80

S 60CM
0.95
0.91
0.89
0.88
0.87
0.86
0.86
0.85
0.85
0.84
0.84

S a ial spacing of cable


o. of cables/
circuits in groups

o. of Tier

2
3
4
5
6
7
8
9
10
11
12
1

Multicore cables in Tier formation

1
1
2
2
2
3
3
3
4
4
4

Touching

S 15CM

S 30CM

S 45CM

S 60CM

0.80
0.68
0.6
0.55
0.51
0.48
0.46
0.44
0.42
0.41
0.4

0.84
0.74
0.66
0.61
0.57
0.54
0.51
0.48
0.47
0.46
0.45

0.87
0.79
0.73
0.68
0.63
0.59
0.56
0.53
0.52
0.50
0.49

0.90
0.83
0.77
0.71
0.67
0.63
0.6
0.57
0.55
0.54
0.53

0.91
0.86
0.79
0.73
0.69
0.64
0.61
0.58
0.56
0.55
0.54

Cable laid direct in open racks in air

MULTICORE CABLES IN OPEN RACKS IN AIR


25mm

o.
of
racks

1
2
3
6

25mm

WALL

300mm

1
1.00
1.00
1.00
1.00

dia of cable

o. of cables per rack


3
6
0.96
0.93
0.93
0.90
0.92
0.89
0.90
0.87

2
0.98
0.95
0.94
0.93

9
0.92
0.89
0.88
0.86

WALL

1
1.00
1.00
1.00
1.00

300mm

2
0.84
0.80
0.78
0.76

o. of cables per rack


3
6
0.80
0.75
0.76
0.71
0.74
0.70
0.72
0.65

touching

9
0.73
0.69
0.68
0.66

SINGLE CORE CABLES IN OPEN RACKS IN AIR


A

25MM

WALL

o. of acks
1
2
3
4

A GEME T

2d

300mm

o. of Circuit acks 3 single cores


1
2
1.00
0.98
1.00
0.95
1.00
0.94
1.00
0.93

per rack
6
0.96
0.93
0.92
0.90
41

S a ial spacing of cable


No. o a s/
r ts
ro s

No. o
r

M t or

Touching
S
1
0.80
1
0.68
2
0.60
2
0.55
2
0.51
3
0.48
3
0.46
3
0.44
4
0.42
4
0.41
4
0.40
M t or a ( o
No o a s ra s

2
3
4
5
6
7
8
9
10
11
12
No. o a s/
r ts
ro

1
1.00
0.84
0.80
0.76

1
2
3
4

Nom a
ar a o
o d tor
(s . mm)

dro - o ts/ m/Am s)

P. .C. Ca

LP Ca

S
P as

r
P as

S
P as

r
S st m

1.5
2.5
4

43.44
29.04
17.78

37.62
25.15
15.40

46.34
30.98
18.98

40.13
26.83
16.44

6
10
16

11.06
7.40
4.58

9.58
6.41
3.97

11.80
7.88
4.9

10.22
6.82
4.24

25
35
50

2.89
2.10
1.55

2.50
1.80
1.30

3.08
2.23
1.65

2.67
1.94
1.44

70
95
120

1.10
0.79
0.63

0.94
0.68
0.55

1.15
0.83
0.66

1.00
0.70
0.56

150
185
240

0.52
0.42
0.34

0.46
0.37
0.30

0.55
0.44
0.35

0.48
0.40
0.30

300
400
500

0.28
0.24
0.23

0.26
0.22
0.20

0.30
0.24
0.23

0.26
0.22
0.20

630
800
1000

0.20
0.19
0.18

0.18
-

0.21
0.20
0.18

0.18
-

A o

rat d
dro

o ta dro s ( o ts/ m/am s) s a


rr t &
t o Ca
.M. to a
art ar
t a d s o a s.

S 30CM S 45CM
0.87
0.90
0.79
0.83
0.73
0.77
0.68
0.71
0.63
0.67
0.59
0.63
0.56
0.60
0.53
0.57
0.52
0.55
0.50
0.54
0.49
0.53
M t or a s (s a
a to d a m t r o
No o a s ra
1
2
3
1.00
1.00
1.00
0.98
0.95
0.94
0.96
0.93
0.92
0.93
0.90
0.89

4
1.00
0.76
0.72
0.68

Estimated Voltage Drops


in PVC/XLPE Aluminium
Cables For A.C. System
( o ta

r ormat o

15CM
0.84
0.74
0.66
0.61
0.57
0.54
0.51
0.48
0.47
0.46
0.45
)

3
1.00
0.78
0.74
0.70

1.00
0.80
0.76
0.71

S 60CM
0.91
0.86
0.79
0.73
0.69
0.64
0.61
0.58
0.56
0.55
0.54
o a
a
s
4
1.00
0.93
0.90
0.87

S/ or a s tr o to
ormat o
s a
t
r ts
a to t
t d am t r o a ) No o a s ra s
1
2
3
4
1.00
1.00
1.00
1.00
0.98
0.95
0.94
0.93
0.96
0.93
0.92
0.90

* Selection criteria of MV/HV


cable size for primary distribution

SCOPE
o d tor s
t
a s or a
sta at o s a so o r d
s st m. or L. . d str t o a ma
s
t do t
as s o o t
d str t o t s a a s sa r to s
tt
a o t
as s o a t o
rr t. S ort r t rr t rat o a s o d
t s ort r
r t r a rs, ra s orm rs & r a tor t . s d ts a a t to arr
o a s a s ar
r
a t ta s & a
a at d o
o o
ass m t o

a) Temperature of conductor just prior to short circuit


) W t LP s at o - 90
.C

ts a t to arr s ort r t rr t o
o s oad rr t. t
as o M /
o d tor to arr
t d s ort r t
t a a t o dam
a arat s s
as
d s r d oad rr t. S ort r t rat s
t
as s o I C-949 & I C-986 & o t

) W t P C s at o - 70

.C

b) Maximum permissible conductor temperature during short circuit


) W t LP s at o - 250
.C
) W t P C s at o - 160
c) Volumetric specific heat of the conductor
) W t A m m o d tor - 2.5 10-3 /

. C/MM3

) W t Co

.C

r o d tor - 3.45 10-3 /

. C/MM3

d) Receprocal of temperature co-efficient of resistance at 9 Deg. C


) W t A m m o d tor - 228
)
W t Co r o d tor - 234.5
S ort r t rr t rat at d r t d rat o ma
a at d as
Is ( or t d rat o ) Is ( or 1S .)

Is or 1 S .

t
S L C I NC I

IA

. ./M CA L S

P IMA

rat o s

a t ta

m d rat o r

r d to

IS

S .

FOR EXAMPLE

1) Nom a S st m o ta at . . S d
2) S ort r t
or . . s st m
3) a t t sta d t m or . . C s
4) orm a or a at
. . a s
W t A m m o d./ LP s at d a

r o d./ LP

I N

REQUIRED DATAS

W t Co

at d o s ort r

s at d a

11
25 A
0.5 S C
Is t
0.094

Is t
0.143

m t
d t
at tota o ta

ar st

ar st

25 0.5
0.94
188
r s 240s mm s r
25 0.5
0.143
124
r s 150s mm s r

r d

r d

ELECTRICAL FORMULAS FOR CALCULATING A.C. LOAD CURRENT


Load current in Amps when KVA is given
Load current in Amps when Kilo

att is given

Load current in Amps when H.P. is given


V

for Single phase A.C.


KVA X1000
V
for Single phase A.C.
K X1000
VXpf
for Single phase A.C.
H.P. X746
V X EFf X pf

ominal system voltage in Volts, pf

Power factor, KVA

for Three phase A.C.


KVA X1000
1.732 X V
for Three phase A.C.
K X1000
1.732 X V X pf
for Three phase A.C.
H.P. X746
1.732 X V X Eff X pf

Kilo Volts Ampere, H.P.

Horse Power

42

STANDARD DRUM LENGTHS OF CABLES


STA DA D LE GTH MTS
DESC IPTI

F CABLE

U -A M U ED

ITH 5

T LE A CE

ST IP A M U ED

U D

I E A M U ED

1.1KV PVC/XLPE CABLES


WITH ALUMINIUM
SI GLE C
T

E
E

TH EE C

UP T 150SQMM-1000
185 T 1000sqmm-500

UP T 150SQMM-1000
185 to 1000sqmm-500

UP T 150SQMM-1000
185 to 1000sqmm-500

UP T 50SQMM-1000
70 to 630sqmm-500

UP T 50SQMM-1000
70 to 630sqmm-500

UP T 50SQMM-1000, 70 T 500sqmm
500, 630sqmm-250

UP T 50SQMM-1000

UP T 50SQMM-1000
70 to 500sqmm-500
630sqmm-250

UP T 50SQMM-1000, 70 T 300sqmm

70 to 630sqmm-500
TH EE & HALF C

F U C

UP T 50SQMM-1000

500, 500 to 630sqmm-250

70 to 630sqmm-500

UP T 50SQMM-1000
70 to 400sqmm-500
500 to 630sqmm-250

UP T 50SQMM-1000, 70 T 300sqmm

UP T 50SQMM-1000
70 to 500sqmm-500
630sqmm-250

UP T 50SQMM-1000
70 to 400sqmm-500
500 to 630sqmm-250

500, 300 to 630sqmm-250

UP T 150SQMM-1000
185 T 630sqmm-500
800 to 1000sqmm-250

UP T 150SQMM-1000
185 to 630sqmm-500
800 to 1000sqmm-250

UP T 150SQMM-1000
185 to 630sqmm-500
800 to 1000sqmm-250

UP T 10SQMM-1000
16 to 300sqmm-500
400 to 630sqmm-250

UP T 10SQMM-1000
16 to 300sqmm-500
400 to 630sqmm-250

UP T 10SQMM-1000, 70 T 500sqmm
500
500, 300 to 630sqmm-250

UP T 10SQMM-1000

UP T 10SQMM-1000
16 to 240sqmm-500
240sqmm-400sqmm-250

UP T 10SQMM-1000, 16 T 185sqmm
16 to 185sqmm-500
500, 240 to 400sqmm-250

300 to 400sqmm-250

UP T 10SQMM-1000
16 to 240sqmm-500
240 to 400sqmm-250

UP T 10SQMM-1000, 16 T 150sqmm
16 to 185sqmm-500
500, 185 to 400sqmm-250

UP T 10SQMM-1000
16 to 240sqmm-500
300 to 400sqmm-250

UP T 10SQMM-1000
16 to 150sqmm-500
240 to 400sqmm-250

UP T 10SQMM-1000, 16 to 150sqmm

500, 400-630sqmm-250
UP T 50SQMM-1000, 70 to 240sqmm

1.1KV PVC/XLPE CABLES


ITH C PPE C
SI GLE C

DUCT

TH EE C

300 to 400sqmm-250
TH EE & HALF C

F U C

UP T 10SQMM-1000

500, 185 to 400sqmm-250

~ Control cables more than FOUR CORES shall be supplied in 500 mts length
DESC PIT

F CABLE

6.35/11KV G ADE

1/11KV G ADE

19/33KV G ADE

H.T. XLPE CABLES ITH


ALUMI IUM C
DUCT
SI GLE C

E-A2X a

UP T 150SQMM-1000
185 to 1000sqmm-500

UP T 150SQMM-1000
185 to 1000sqmm-500

UP T 150SQMM-1000
185 to 1000sqmm-500

TH EE C

E-A2XF

25 T 300SQMM-500

25 T 185SQMM-500

25 T 95SQMM-500

400sqmm-250

240 to 400sqmm-250

120 to 400sqmm-250

25 T 150SQMM-500
185 to 300sqmm-250
400sqmm-200

25 T 95SQMM-500
120 to 240sqmm-250
300 to 400sqmm-200

25 T 50SQMM-250
70 to 120sqmm-250
185 to 400sqmm-200

TH EE C

E-A2X

43

TEST

QUALITY CONTROL
It has been rightly said that Quality is never an accident, it is always

The tests on cables have been classified broadly in four categories

the result of intelligent efforts .

as follows

In the manufacture of cables, intelligent efforts are incorporated to

Routine Tests :

achieve quality. For a quality end products, control starts from proper
design of the product. All raw materials are selected carefully and
only materials of high quality are used in production. Having done

Tests carried out on each cable to check the requirements which are
likely to vary during production.

this, stage wise inspection is done to ensure conformity with the

Type Tests :

requirements of relevant Indian Standards where these apply.

Tests carried out to prove conformity with the specification. These


are intended to prove the general qualities and design of a given type

Stage - Wise Inspection


i

ii

ire-Drawing

Stranding of

ire diameter
Surface
Shape
Quality of oints in the wire
ires

iv

Curing
for XLPE Insulation

Hot set test, Tensile strength &


elongation test.

Screening
for H.T. Screened cables

Dimension over screen, thick of


screen visual e amination of
surface/defects.

vii

viii

Inner Sheath

Armouring

uter Sheath

acceptance of the lot.

Special tests required for F LS Cables can also be carried out at our

Dimension over Insulation,


Thickness of Insulation,

vi

Tests carried out on samples taken from a lot for the purpose of

Optional Tests :

Insulation

Laying Up

Acceptance Tests :

Quality of oints in the wires


Compaction of conductor
Shape of Conductor
Dimensions
esistance of Conductor

iii

of cable.

Sequence of Cores
Direction of lay
Diameter over laid up cores
Circularity

Special tests to be carried out when required by agreement between


the purchaser and the manufacturer.

works i.e. Halogen gas generation test to IEC - 754 Part - I, Smoke
generation test to ASTMD 2843,

ygen inde

test and

Temperature inde test to ASTMD - 2863, Flammability test to


1 IEC-332-1, 2 Swedish Chimney test to SS-4241475 Class F3
& 3 IEC-332-3, Flame resistance test to IEEE-383.
Together with the most advanced equipment available, we are able
to offer to our valued customers assurances of highest quality and
strict adherence to the required specification. As a third party
guarantee, our cables have passed rigorous tests at various

Thickness of Sheath
Diameter over Sheath
Surface Uniformity
Circularity
Porosity

Government recogonized test laboratories such as CP I, Shri


am Test House, E DA Baroda, ational Test House, E TL, TC.
outine Tests, Type Tests, Acceptance Tests and

Diameter of ires/
Dimensions of Strips
Direction of lay
Coverage
Quality of oints of ires
Thickness of Sheath Diameter
over Sheath Tightness of Sheath
Eccentricity Porosity, Embossing

ptional Tests as

per the Indian Standard Specification for Power and Control Cables
with PVC insulation, Cross linked Polyethylene insulation and
Special Tests are given in the Anne ure.
Tensile Testing Machine

M Testing Lab

44

SELECTION GUIDE
List of Tests as per IS 1554 Part - I 1988, IS 1554 Part- II 1988,
IS 7098 Part - I 1988 and IS 7098 Part-II 1985
1.

2.

which the cable has to operate, is necessary.

Conductor esistance Test

statutory restrictions and the manufacturing facilities available in the

High Voltage Test

Armour esistance Test for mining Type Cables

country will help in finding out as to what type of cable will be

Partial Discharge test for H.T. Screened cable

available for particular usage. The environmental conditions under


which the cable has to operate will decide its protective covering.

Type Tests :
a

material, type of insulation and protective coverings are known, size

Tensile Test for Aluminium Conductor


rapping Test for Aluminium Conductor

Annealing Test for Copper Conductor

Conductor esistance Test

Test for Armour

Test for thickness of Insulation & Sheath

Physical Test for Insulation & uter Sheath

Test for Bleeding & Blooming of Pigments

Insulation esistance Test

Flammability Test

ires/Strips

Hot Set Test - For XLPE Insulation only

Partial Discharge test for H.T. Screened cable

Bending test for H.T. Screened cable

Dielectric Power factor test for H.T. Screened cable


with rated voltage 6.35/11KV & above

Heating cycle test for H.T. Screened cable

Impulse withstand test for H.T. Screened cable

Acceptance Tests :
a
b

of conductor remains to be decided. The first and foremost criteria


for the size of conductor is continuous current rating for the present
load. There after the same should be checked for short circuit,
voltage drop, over load capacities and future e pansions.
decided

rapping Test For Aluminium Conductor

Annealing Test For Copper Conductor

Conductor esistance Test

Test for thickness of Insulation & Sheath

High Voltage Test

Insulation esistance Test

Tensile Strength & Elongation at break test for


Insulation and Sheath

Hot Set Test - for XLPE Insulation only

Optional Tests :
a

Cold Bend Test

Cold Impact Test

Armour esistance Test for other than Mining Type


Cables

nce

the selection of ne t higher size compared to what is

essential for the requirement, will always be worthwhile.


Economic considerations are also necessary.
INFORMATION REQUIRED WITH ENQUIRY & ORDER
The following information should be included in an enquiry
i
ii

Voltage Grade.
hether cable is to be used on Earthed or Unearthed system
for voltages above 3.3 KV .

iii Type of installation whether in air or in ducts or in ground.


iv If cables are grouped together, then number of cables in group
and vertical and horizontal spacing between them.

Tensile Test For Aluminium Conductor

Partial Discharge test for H.T. Screened cable

5.

A knowledge of

Thus once voltage grade of the cable, number of cores, conductor

High Voltage Test

4.

which the cable is to be used, and the installation conditions under

Routine Tests :

For selection of a cable, a first hand knowledge of the system in

equired value and duration of short circuit current.

Following further informations are also required for offering the e act
type of cable for any specific purpose
a

The normal ambient or operating temperature.

The ma imum temperature to which the PVC will be e posed


and the duration and frequency of such e posures.

The material with which the PVC will be in contact i.e. oil, gases,
acids, alkalies etc. at normal and ma imum temperature.

If special flame retardent property is required.

If any special electrical characteristics needed.

Special Tests (As Applicable) :


a
ygen Inde Test as per ASTMD - 2863-77
b
Temp. Inde Test as per ASTMD - 2863-77
c
Smoke Generation Test as per ASTMD - 2843-77
d
Acid Gas Generation Test as per IEC - 754-1
e
Flammability Test as per IEC - 332-1, IEEE-383,
SS-4241475 Class F3 and IEC - 332-3
g
ater absorption test by Electrical Method
h
Ultra voilet resistance to ASTM-G-53
i
Die electric Strength retention test
Test for Antirodent & Antitermite property
45

HANDLING & STORAGE


Handling (Unloading at site) :
n receipt of cable drums visual
inspection of drums should be made ensuring drum packing is
original.
hile unloading the cables certain precautions are to be
taken to ensure the safety of the cables.
1. The cable drums should not be dropped or thrown from railway
wagons or trucks during unloading operations as the shock may
cause serious damage to cable layers. A crane should be used
for unloading cable drums. hen lifting drums with the crane, it
is recommended that the lagging should be kept in place to
prevent the flanges from curshing on to the cable. If the crane is
not available, a ramp should be prepared with appro imate
inclination of 1 3 or 1 4. The cable drum should be rolled over
the ramp by means of ropes and winches. Additionally a sand
bed at the foot of the ramp may be prepared to brake the rolling
the cable drum.
2. Cable should not be dragged along the earth surface.
3. Cable ends should always be sealed by means of suitable end
sealing materials to prevant moisturisation of cores and armour.
4. Drums should be rolled in direction of arrow marked on the
drum.
Storage :
Cables should be stored in a dry covered place to prevent e posure
to climatic conditions and wear and tear of wooden drums and it
should preferably on a concrete surface/firm surface which will not
cause the drums to sink and thus lead to flange rot and e treme
difficulty in moving the drums.
All drums should be stored in such a manner as to leave sufficient
space between them for air circulation. It is desirable for drums to
stand on battens placed directly under the flanges.
In no case should the drums be stored, n the Flat , i.e., with flange
horizontal.

Voltage Rating
KV
Upto 1.1
Above 1.1 but upto 11 K.V.
Above 11 K.V.

For laying of cables special cares to be taken to prevent sharp


bending, kinking, twisting. Cable should be unwound from drum by
proper mounting the cable drum on a cable wheel making sure the
spindle is strong enough to carry the weight without bending and that
it is lying horizontally in the bearings so as to prevent the drum
creeping to one side or the other while it is rotating.
Provision should be made to break
the drum to avoid further rolling &
buckling of cable during sudden stop.
A simple wooden plank can server
this purpose

Cable must be puled


from the top

PVC and XLPE Cables


Single Core
Multi Core
15 D
12 D
15 D
15 D
20 D
15 D

here D is overall
diameter of cable.
7.

Laying :

This is incorrect way of pulling the cable & will


cause kinks & twist in cable. Shall be avoided at all

In case of multicore power cables, cables shall be laid side by side,


with spacings not less than one cable diameter. However derating
factors for cables laid on trenches are to be referred.
Multicore power cables and single core D.C. circuits may be
clamped by means of galvanised mild steel saddles but 1.1 KV
single core cables should be clamped by means of non-magnetic
saddles. The saddles shall not be placed at intervals more than
1500 mm. for horizontal and 1200 mm. for vertical runs.
3. Multicore control cables can be laid touching each other on
cable racks and wherever required may be taken in two layers.
They should be clamped by means of PVC straps both for
horizontal and vertical runs alternatively, fabricated aluminium
clamps may be used at regular intervals.
4. a If the cables are buried directly in ground I.S. 1255 is to be
followed for code of practice. However, generally cables are
laid 1000 mm. below finished ground level at any point of
cable run and 75 mm. of sand cushioning to be provided.
4. b In loose soil concrete pillar should be provided for as
support and hence pipes are recommended to the used for
cable path.
5. If there is a possibility of mechanical damage, cables should be
protected by means of mild steel covers placed on racks.
6.
hile laying cables, special care to be taken at bends.
Followings are the recommended bending radius for power and
control cables.

Ma imum safe pulling force when pulled by pulling eye


Aluminium Conductor Cables 3.0 Kg/mm2 Copper Conductor
Cables 5.0 Kg/mm2 Proper method of pulling of cable should
be used.

TESTING
INSULATION RESISTANCE MEASUREMENT OF CABLE
The voltage rating of I. . Tester Megger should be chosen as
following table
Voltage grade Rating of IR Voltage grade Rating of IR
of cable
Tester (Megger)
of cable
Tester (Magger)
1.1 KV
500 V
11 KV
1000 V
3.3 KV
1000 V
22 KV
2500 V
6.6 KV
1000 V
33 KV
2500 V
Testing during laying :
All new cables shall be megger-tested before ointing. After ointing
is completed all LV Cables shall be megger-tested.
End Terminations & Jointing :
Termination and ointing of Power & Control Cables shall be done by
means of compression methods using solderless tinned copper/
Aluminium terminal lugs. For control cables terminations, ring
tongue or reducer pin type terminal lug can also be used to suit the
purpose.

Cable must be pulled accross hard & sharp


ob ects to avoid the damage to ve covering &
insulation
Cable must be laid in ducts or trenches as
shown in Fig.

However, following salient points are to be considered during laying


procedure of cables laid in racks and in built-in trenches.
1. For laying of cables power cables to be placed at the bottom
most layer and control cables at top most layer.
2. Single core power cable for use on A.C. system shall be laid in
delta formation supported by non-magnetic material. Trefoil
clamps of suitable size are to be placed at regular intervals but
preferably not more than 800 mm. A ial spacing of two circuits
in delta formation shall not be less than 4 times the cable dia.

A view of dispatch yard

46