Introduction
Manufacturing Process ..............................................................................................................
Manufacturing of Cables.............................................................................................................
Advantages................................................................................................................................
Cable ranges at a glance............................................................................................................
1
2
3
4,5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
Basic assumption for current ratings & rating factors .................................................................. 40,41
Selection criteria of M/VHV cable size for primary distribution ..................................................... 42
Standard Drum lengths of Cables ............................................................................................... 43
Quality Control & Test ................................................................................................................
44
Selection Guide .........................................................................................................................
45
Handling & Storage ....................................................................................................................
46
Introduction
Havells India Ltd, a US 1bn company, and one the largest & India s fastest growing
ires, Energy Meters, Fans, CFL Lamps, Luminaires for domestic, commercial &
Manufacturing Process
Copper or
Aluminium Rods
ire to be drawn for required size
Annealing
Stranding
Conductor Screening
Insulation
Insulation Screening
on metallic part
Core
Insulation Screening
Metallic Part
ire Drawing
Laying Up
Inner Sheathing
Armouring
uter Sheath
All cables are rewound on wooden Drums & tests Carriedout as per required specification
Packing
Manufacturing of Cables
Cables with Aluminium and Copper conductor and polymer insulation are manufactured at Havells India Ltd. Cable orks Alwar.
Essentially cables comprise of conductors, insulation, inner-sheath, armour and outersheath. The brief description of the process is
mentioned as under
CONDUCTOR
Havells Cables are available with both aluminum and copper
conductors. It is manufactured with solid/Stranded Circular/
Shaped Aluminium / Copper Conductor. Stranding makes
Cables fle ible and easy to handle while shaping makes them
compact.
Compaction is provided to all stranded conductor constructions
as under
1.
Circular Conductor :
compaction.
3.
IS 5831/IS 7098
BS 6746/BS 5467/IEC 60502
SCREENING
XLPE Cables with rated voltage over 3300V shall be provided
large sized conductor, which are due to skin and pro imity
effects.
Screen
Insulation
Screen
IS 8130
DIELECTRIC INSULATION
ational and
Thermoplastic dielectric
- XLPE Cables
Havells PVC cables use PVC compounds that take care of over
load and short circuit current with both coarse & fine protection
systems.
Havells XLPE cables use XLPE compound with anti o idant
LAYING UP
Cores are tested on line during production both for physical and
electrical characteristics. Control is observed within tight
tolerance limits for dimensions in case pf PVC/XLPE insulation.
For multicore cables cores are laid up on our latest laying up
machine equipped with sector correction equipment. In case of
XLPE insulated cores the same are cured so as to impart the
requisite characteristics both electrical and mechanical and then
are laid up.
INNERSHEATH
Laid up cables are provided with inner sheath with high quality of
PVC which acts as bedding for steel wire / strip armouring.
herever required, filler cords are provided to maintain the
circularity to laid up cables.
2
Advantages
In Havells Cable-polymers used for inner sheath are softer than
insulation or outer sheath & are compatible with temperature
ratings of cables & do not have deleteriocus effect on any other
component of cable.
Inner sheath is applied either with e trusion or by wrapping.
In Havells Cables though the inner sheath is closely applied on
the laid up cores, same can be stripped with ease without
damaging insulation.
The inner sheath dimensions are maintained strictly in
accordance with laid down specification .
Specification
armour coverage.
Outer Sheath
All Havells Cables are provided with PVC/polymer outer sheath.
Havells Cables are manufactured with various characteristics of
sheathing compounds.
General purpose sheathing Compound
Fire etardant Low
Smoke Compound
to EIL Specn.
ork
2.
3.
4.
5.
6.
ot affected by vibration.
2.
3.
4.
5.
6.
7.
8.
9.
ST1
F LS
Final Testing
Arial Bunched /
Bundled required
for over head power
distribution
Copper Control
Cables for Power
Switch yard Control /
Relay Equipment
Railway Signaling
Cables
Telecom / Switch
board cables for
Indoor Telephones
Options
ire/
Available in specified G
& U Series as per MIL-C-17 /
BS 2316 / IS 5608 / IS 11967
Sizes :
Suitable for Impedance
of 50 / 75 / 100 / 125 ohms
uter-Sheath
Armouring
Inner-Sheath
Insulation
Aluminium /
Copper Conductor
PVC
uter-Sheath
Armouring
PVC Inner-Sheath
Filler
Stranded Conductor
Conductor Screening
XLPE Insulation
Insulation Screening
Metallic Screening
uter-sheath
Armour outer layer
Seprator PVC tape
Armour inner layer
Inner-Sheath
Insulation
Conductor
uter Sheath
Cu Tape Screening
Insulation Screening
XLPE Insulation
Conductor Screening
Conductor
AAA
Messenger
Conductor
uter Sheath
Armour
Inner Sheath
Conductor
Insulation
uter Sheath
Armour
Inner Sheath
Conductor
Insulation
uter Sheath
Armour
Inner Sheath
Bedding Tape
Conductor
Insulation
Twisted Pair
Filler
P.E. Insulation
Sheath
Braid
Insulation
Conductor
Sheath
Options
Instrumentation
Signal Cables for
Process control &
Instrumentation
Energy Cables
for Power Supply to
Telephone
Exchanges / UPS /
Battery Backup /
Equipments
Conductor
Insulation
Filler
Sheath
Insulation
Conductor
Color Skin
atural PVC
Multistrand Fle ible
Copper Conductor
Insulation
Conductor
Sheath
TABLE - 1
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
C
SS-SECTI
Minimum
o of Strand in
Conductor
Al
Cu
ominal
Thickness of
Insulation
mm
1/7
1/7
6
6
6
6
6
12
15
18
18
30
34
34
53
53
53
53
53
1
1
6
6
6
6
12
15
15
15
30
30
30
53
53
53
53
53
AL VIE
1.0
1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4
2.6
3.0
3.4
3.4
3.4
ominal
Thickness of
outer sheath
mm
Appro .
veral
Diameter
mm
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
2.0
2.0
2.0
2.0
2.0
2.2
2.2
2.4
2.4
2.6
Appro .
ith Al Conductor
A
8
9
10
11
13
14
16
17
19
21
23
25
28
30
35
38
43
48
52
80
100
120
160
210
250
300
400
500
600
750
900
1100
1350
1700
2150
2750
3300
4100
105
135
180
260
365
460
610
830
1100
1350
1680
2050
2600
3200
4200
5250
6650
8250
10300
C
DUCT
Material - Aluminium /Copper
Shape AL . Cond - 6 & 10 SQMM -Solid circular, 16 sq.mm & above Stranded compacted circular
Copper. Cond - 4 & 6 sq. mm-solid/ stranded non compacted circular, 10 sq. mm & above Stranded compacted circular
I SULATI
PVC Type A of IS 5831 / PTI
H PVC Type-C of IS-5831 , Colour Black
UTE SHEATH PVC T PE ST-1 F IS 5831
PTI
S PVC Type ST-2 of IS 5831/ F T PE/F LS T PE
C L U
- Tabulated appro . net wt. of cables are only guidelines for transportation, loading & unloading purpose..
- Please ref page no 43 for normal delivery lengths & packing details.
ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
4.61
3.08
1.91
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
0.0367
0.0291
4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
0.0221
0.0176
5.53
3.70
2.29
1.44
1.04
0.769
0.532
0.384
0.304
0.247
0.197
0.151
0.122
0.0961
0.0759
0.0610
0.0503
0.0422
5.53
3.70
2.20
1.38
0.87
0.63
0.464
0.322
0.232
0.184
0.1488
0.1189
0.0912
0.0733
0.0580
0.0459
0.0368
0.0303
0.0255
0.140
0.127
0.118
0.110
0.105
0.100
0.098
0.091
0.088
0.086
0.085
0.084
0.082
0.080
0.080
0.079
0.077
0.077
0.076
0.58
0.68
0.83
1.01
1.05
1.22
1.22
1.43
1.47
1.62
1.62
1.62
1.72
1.74
1.81
1.86
1.87
1.98
2.20
39
51
66
86
100
120
140
175
195
220
240
270
295
325
345
390
450
500
37
51
65
84
100
115
135
155
170
190
210
225
245
275
295
320
380
415
35
47
64
84
105
130
155
190
220
250
290
335
380
435
480
550
610
680
39
49
65
85
110
130
155
190
220
250
280
305
345
375
400
425
470
530
590
38
48
64
83
110
125
150
175
200
220
245
260
285
310
335
355
375
425
740
35
44
60
82
110
130
165
205
245
280
320
370
425
475
550
590
660
725
870
in K. Amps
Al
Cu
0.304
0.456
0.760
1.220
1.900
2.660
3.800
5.320
7.220
9.120
11.40
14.10
18.20
22.80
30.40
38.00
47.90
60.80
76.00
0.460
0.690
1.150
1.84
2.88
4.03
5.75
8.05
10.90
13.80
17.30
21.30
27.30
34.50
46.00
57.50
72.50
92.00
115.00
ote
ormal current ratings are given in standard conditions as given in page no 40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42
TABLE - 2
SS- SECTI
Minimum o of
Strands in
Conductor
Al
Cu
AL VIE
2
3
4
Minimum
thickness of
inner Sh.
mm
ominal thick.
of UTE
Sheath
mm
Appro .
verall
Diameter
mm
1.0
1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4
2.6
3.0
3.4
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.40
0.40
0.40
0.50
0.50
0.60
0.70
0.70
0.70
1.80
1.80
1.80
1.80
2.00
2.00
2.00
2.00
2.20
2.20
2.40
2.40
2.60
2.80
3.20
3.40
3.80
14
17
18
17
19
21
24
26
30
32
34
38
42
46
52
54
65
1/7
1/7
6
6
6
6
6
12
15
18
18
30
34
34
53
53
53
1
1
6
6
6
6
12
15
15
15
30
30
30
53
53
53
1
ominal
Thickness of
Insulation
mm
Appro . et t
of cable Kg/KM
ith Al cond
ith Cu Cond.
A
240
300
400
430
450
550
700
850
1150
1300
1600
2000
2500
3000
3800
4800
6000
290
370
520
630
750
980
1300
1700
2300
2800
3450
4300
5500
6700
8750
11000
13800
C
DUCT
Material - Aluminium /Copper
Shape AL . Cond - 6 & 10 SQMM -Solid circular, 16 sqmm & above Stranded compacted shaped
Copper. Cond - 4 & 6sqmm -solid/ stranded non compacted circular, 10sqmm Stranded compacted circular,16sqmm & above Stranded compacted
shaped
I SULATI
PVC Type A of IS 5831/ PTI
H PVC Type -C of IS -5831 , Colour ed & Black
I E SHEATH PVC as per IS 1554PT-1
UTE SHEATH PVC T PE ST-1 F IS 5831
PTI
S PVC T PE ST-2 F IS 5831/ F T PE/ F LS T PE
C L U
F UTE SHEATH BLACK . PTI
S any other colour as per requirement.
Tabulated appro . net wt. of cables are only guidelines for transportation, loading &unloading purpose.
Please ref page no 43 for normal delivery lengths & packing details.
ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
4.61
3.08
1.91
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
5.53
3.70
2.29
1.44
1.04
0.769
0.532
0.384
0.304
0.247
0.197
0.151
0.122
0.0961
0.0759
0.0610
5.53
3.70
2.20
1.38
0.87
0.63
0.464
0.322
0.232
0.184
0.1488
0.1189
0.0912
0.0733
0.0580
0.0459
0.0368
0.098
0.096
0.091
0.085
0.083
0.082
0.082
0.076
0.076
0.075
0.074
0.074
0.073
0.073
0.072
0.072
0.072
0.23
0.28
0.34
0.40
0.42
0.48
0.49
0.56
0.58
0.63
0.63
0.64
0.67
0.68
0.70
0.70
0.70
32
40
55
70
90
110
135
160
190
210
240
275
320
355
385
425
465
27
34
45
58
76
92
115
140
170
190
210
240
275
305
345
380
415
27
35
47
59
78
99
125
150
185
210
240
275
325
365
420
475
540
41
50
70
90
115
140
165
205
240
275
310
350
405
450
490
540
640
35
44
58
75
97
120
145
180
215
235
270
300
345
385
485
460
550
35
45
60
78
105
125
155
195
230
265
305
350
410
465
530
605
785
in K. Amps
Al
Cu
0.304
0.456
0.760
1.220
1.900
2.660
3.800
5.320
7.220
9.120
11.40
14.10
18.20
22.80
30.40
38.00
47.90
0.460
0.690
1.150
1.840
2.880
4.030
5.750
8.050
10.90
13.80
17.300
21.280
27.600
34.500
46.000
57.500
72.550
ote
ormal current ratings are given in standard conditions as given in page no 40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42
TABLE - 3
SS-SECTI
Minimum o of
Strands in
Conductor
Al
Cu
1
1
6
6
6
6
12
15
15
15
30
30
30
53
53
53
AL VIE
1
2
3
4
ominal thick.
Thickness of
Insulation
mm
1/7
1/7
6
6
6
6
6
12
15
18
18
30
34
34
53
53
53
Minimum
thickness of
inner Sh.
mm
1.0
1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4
2.6
3.0
3.4
ominal thick.
of outer
Sheath
mm
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.40
0.40
0.40
0.50
0.50
0.60
0.60
0.70
0.70
0.70
Appro .
verall
Diameter
mm
1.80
1.80
1.80
1.80
2.00
2.00
2.00
2.20
2.20
2.20
2.40
2.60
2.80
3.00
3.40
3.60
4.00
Appro . et t
of cable Kg/KM
ith Al cond
ith Cu Cond.
A
16
18
19
19
22
24
27
30
34
37
40
44
50
55
62
69
77
270
360
440
460
620
740
940
1200
1600
1900
2300
2750
3500
4300
5450
6900
8700
340
470
650
730
1080
1400
1870
2500
3350
4100
5100
6200
7950
9900
12800
16200
20400
C
DUCT
Material - Aluminium /Copper
Shape AL . Cond - 6 & 10 sqmm - Solid circular, 16 sqmm & above Stranded compacted shaped
Copper . Cond - 4 & 6 sqmm-solid/ stranded non compacted circular, 10 sqmm Stranded compacted circular,16sqmm & above Stranded compacted
shaped
I SULATI
PVC Type A of IS 5831/ PTI
H PVC Type -C of IS -5831 , Colour ed, ellow & Blue
I E SHEATH PVC as per IS 1554PT-1
UTE SHEATH PVC T PE ST-1 F IS 5831
PTI
S PVC T PE ST-2 F IS 5831/ F T PE/ F LS T PE
C L U
F UTE SHEATH BLACK. PTI
S any other colour as per requirement.
Tabulated appro . net wt. of cables are only guidelines for transportation, loading &unloading purpose.
Please ref page no 43 for normal delivery lengths & packing details.
ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
4.61
3.08
1.91
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
5.53
3.70
2.29
1.44
1.04
0.769
0.532
0.384
0.304
0.247
0.197
0.151
0.122
0.0961
0.759
0.0610
5.53
3.70
2.20
1.38
0.87
0.63
0.464
0.322
0.232
0.184
0.1488
0.1189
0.0912
0.0733
0.0580
0.0459
0.0368
0.098
0.096
0.091
0.085
0.083
0.082
0.082
0.076
0.076
0.075
0.074
0.074
0.073
0.073
0.072
0.072
0.072
0.23
0.28
0.34
0.40
0.42
0.48
0.49
0.56
0.58
0.63
0.63
0.64
0.67
0.68
0.70
0.70
0.70
28
35
46
60
76
92
110
135
165
185
210
235
275
305
335
370
405
23
30
39
50
63
77
95
115
140
155
175
200
235
260
290
320
350
23
30
40
51
70
86
105
130
155
180
205
240
280
315
375
425
480
36
45
60
77
99
120
145
175
210
240
270
300
345
385
425
470
555
30
38
50
64
81
99
125
150
175
195
225
255
295
335
360
390
470
30
39
52
66
90
110
135
165
200
230
265
305
355
400
435
520
675
in K. Amps
Al
Cu
0.304
0.456
0.760
1.220
1.900
2.660
3.800
5.320
7.220
9.120
11.40
14.10
18.20
22.80
30.40
38.00
47.90
0.460
0.690
1.150
1.840
2.880
4.030
5.750
8.050
10.900
13.800
17.300
21.300
27.600
34.500
46.000
57.500
72.500
ote
ormal current ratings are given in standard conditions as given in page no- 40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42
TABLE - 4
3X25 16
3X35 16
3X50 25
3X70 35
3X95 50
3X120 70
3X150 70
3X185 95
3X240 120
3X300 150
3X400 185
3X500 240
3X630 300
C
SS-SECTI
Minimum nos of
Strands in conductor
Phase
eutral
Al
Cu
6/6
6/6
6/6
12/6
15/6
15/12
15/12
30/15
30/15
30/15
53/30
53/30
53/30
AL VIE
1
2
3
4
6/6
6/6
6/6
12/6
15/6
18/12
18/12
30/15
34/18
34/18
53/30
53/34
53/34
ominal
Thickness of
Insulation mm
Phase / eutral
1.20/1.00
1.20/1.00
1.40/1.20
1.40/1.20
1.60/1.40
1.60/1.40
1.80/1.40
2.00/1.60
2.20/1.60
2.40/1.80
2.60/2.00
3.00/2.20
3.40/2.40
Minimum
Thickness of
inner sheath
mm
0.30
0.30
0.30
0.40
0.40
0.50
0.50
0.50
0.60
0.60
0.70
0.70
0.70
ominal
thickness of
outer sheath
mm
2.00
2.00
2.00
2.20
2.20
2.40
2.40
2.60
3.00
3.20
3.40
3.80
4.00
Appro .
veral
Diameter
mm
24
26
29
32
36
40
44
48
54
62
68
77
87
Appro . et t.
of cable Kg/KM
ith Al Conductor
ith Cu conductor
A
700
850
1050
1400
1800
2200
2600
3200
4100
5000
6300
8000
10000
1264
1600
2100
2900
3900
4850
5800
7200
9300
11500
15000
18500
23500
C
DUCT
Material - Aluminium /Copper
Shape AL . Cond - 6 & 10 sq mm -Solid circular, 16sqmm & above Stranded compacted shaped
Copper . Cond - 4 & 6sqmm -solid/ stranded non compacted circular , 10sqmm Stranded compacted circular,16sqmm & above Stranded compacted
shaped
I SULATI
PVC Type A of IS 5831/ PTI
H PVC Type -C of IS -5831 , Colour ed, ellow, Blue, Black
I E SHEATH PVC as per IS 1554PT-1
UTE SHEATH PVC T PE ST-1 F IS 5831
PTI
S PVC T PE ST-2 F IS 5831/ F T PE/ F LS T PE
C L U
F UTE SHEATH BLACK . PTI
S any other colour as per requirement.
Tabulated appro . net wt. of cables are only guidelines for transportation, loading &unloading purpose ..
Please ref page no 43 for normal delivery lengths & packing details.
ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM
3X25
3X35
3X50
3X70
3X95
3X120
3X150
3X185
3X240
3X300
3X400
3X500
3X630
16
16
25
35
50
70
70
95
120
150
185
240
300
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
1.44
1.04
0.769
0.532
0.384
0.304
0.247
0.197
0.151
0.122
0.0961
0.0759
0.0610
0.87
0.63
0.464
0.322
0.232
0.184
0.1488
0.1189
0.0912
0.0733
0.0580
0.0459
0.0368
0.083
0.082
0.082
0.076
0.076
0.075
0.074
0.074
0.073
0.073
0.072
0.072
0.072
0.42
0.48
0.49
0.56
0.58
0.63
0.63
0.64
0.67
0.68
0.70
0.70
0.70
76
92
110
135
165
185
210
235
275
305
335
370
405
63
77
95
115
140
155
175
200
235
260
290
320
350
70
86
105
130
155
180
205
240
280
315
375
425
480
99
120
145
175
210
240
270
300
345
385
425
470
555
81
99
125
150
175
195
225
255
295
335
360
390
470
90
110
135
165
200
230
265
305
355
400
435
520
675
in K. Amps
Al
Cu
1.90
2.66
3.80
5.32
7.22
9.12
11.40
14.10
18.20
22.80
30.40
38.00
47.90
2.88
4.03
5.75
8.05
10.90
13.80
17.30
21.30
27.60
34.50
46.00
57.50
72.50
ote
ormal current ratings are given in standard conditions as given in page no- 40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42
TABLE - 5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
SS- SECTI
Minimum
o of Strand in
Conductor
Cu
Al
1
1
6
6
6
6
12
15
15
15
30
30
30
53
53
53
AL VIE
1
2
3
4
ominal
Thickness of
Insulation
mm
1/7
1/7
6
6
6
6
6
12
15
18
18
30
34
34
53
53
53
1.0
1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4
2.6
3.0
3.4
Minimum
Thickness of
inner sheath
mm
0.30
0.30
0.30
0.30
0.30
0.30
0.40
0.40
0.40
0.50
0.50
0.60
0.60
0.70
0.70
0.70
0.70
ominal
thickness of
outer sheath
mm
1.80
1.80
1.80
2.00
2.00
2.00
2.20
2.20
2.40
2.40
2.60
2.80
3.00
3.40
3.60
4.00
4.00
Appro .
veral
Diameter
mm
16
18
20
23
26
30
34
38
43
46
51
55
60
66
73
82
92
Appro . et t.
of cable Kg/KM
ith Al Conductor
A
300
390
540
560
750
940
1250
1550
2050
2400
2950
3650
4600
5500
6800
8600
11000
ith Cu
400
540
788
950
1370
1800
2500
3300
4400
5380
6670
8250
10550
12950
16720
21000
26000
C
DUCT
Material - Aluminium /Copper
Shape AL . Cond - 6 & 10SQMM -Solid circular, 16sqmm & above Stranded compacted shaped
Copper . Cond - 4 & 6sqmm -solid/ stranded non compacted circular, 10sqmm Stranded compacted circular,16sqmm & above Stranded compacted
shaped
I SULATI
PVC Type A of IS 5831/ PTI
H PVC Type -C of IS -5831 , Colour ed, ellow, Blue, Black
I E SHEATH PVC as per IS 1554PT-1
UTE SHEATH PVC T PE ST-1 F IS 5831
PTI
S PVC T PE ST-2 F IS 5831/ F T PE/ F LS T PE
C L U
F UTE SHEATH BLACK . PTI
S any other colour as per requirement.
Tabulated appro . net wt. of cables are only guidelines for transportation, loading &unloading purpose ..
Please ref page no 43 for normal delivery lengths & packing details.
ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
4.61
3.08
1.91
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
5.53
3.70
2.29
1.44
1.04
0.769
0.532
0.384
0.304
0.247
0.197
0.151
0.122
0.0961
0.0759
0.0610
5.53
3.70
2.20
1.38
0.87
0.63
0.464
0.322
0.232
0.184
0.1488
0.1189
0.0912
0.0733
0.0580
0.0459
0.0368
0.098
0.096
0.091
0.085
0.083
0.082
0.082
0.076
0.076
0.075
0.074
0.074
0.073
0.073
0.072
0.072
0.072
0.23
0.28
0.34
0.40
0.42
0.48
0.49
0.56
0.58
0.63
0.63
0.64
0.67
0.68
0.70
0.70
0.70
28
35
46
60
76
92
110
135
165
185
210
235
275
305
335
370
405
23
30
39
50
63
77
95
115
140
155
175
200
235
260
290
320
350
23
30
40
51
70
86
105
130
155
180
205
240
280
315
375
425
480
36
45
60
77
99
120
145
175
210
240
270
300
345
385
425
470
555
30
38
50
64
81
99
125
150
175
195
225
255
295
335
360
390
470
30
39
52
66
90
110
135
165
200
230
265
305
355
400
435
520
675
in K. Amps
Al
Cu
0.304
0.456
0.760
1.220
1.900
2.660
3.800
5.320
7.220
9.120
11.400
14.100
18.200
22.800
30.400
38.000
47.900
0.460
0.690
1.150
1.840
2.880
4.030
5.750
8.050
10.900
13.800
17.300
21.300
27.600
34.500
46.000
57.500
72.500
ote
ormal current ratings are given in standard conditions as given in page no 40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42
10
TABLE - 6
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
Minimum
o of
Strands in
Conductor
Al
Cu
1
1
6
6
6
6
12
15
15
15
30
30
30
53
53
53
53
53
SS- SECTI
ominal
Thickness of
Insulation
mm
1/7
1/7
6
6
6
6
6
12
15
18
18
30
34
34
53
53
53
53
53
1.3
1.3
1.3
1.3
1.5
1.5
1.7
1.7
1.9
1.9
2.1
2.3
2.5
2.7
3.0
3.4
3.9
3.9
3.9
AL VIE
1
2
3
4
5
A M U I G ITH FLAT ST IP A Fa / Fa
A M U I G ITH
U D I ES A
a /
a
ominal
Minimum
Appro .
Appro . et t
ominal
Minimum
Appro .
Appro . et t
Thickness Thickness of
verall
of cable Kg/KM
Diameter Thickness of
verall
of cable Kg/KM
ith Al cond ith Cu Cond. of wire
outer sheath Diameter ith Al cond ith Cu Cond.
of armour
outer sheath Diameter
mm
mm
mm
A Fa
Fa
mm
mm
mm
A
a
a
/A
/A
/A
/A
/A
/A
/A
/A
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
/A
/A
/A
/A
/A
/A
/A
/A
1.40
1.40
1.40
1.40
1.40
1.56
1.56
1.56
1.72
1.88
2.04
/A
/A
/A
/A
/A
/A
/A
/A
21
23
24
27
30
32
37
40
45
49
55
/A
/A
/A
/A
/A
/A
/A
/A
650
750
900
1050
1300
1600
1950
2400
3100
3700
4600
/A
/A
/A
/A
/A
/A
/A
/A
1230
1500
1830
2200
2800
3450
4400
5500
7000
8650
10800
1.40
1.40
1.40
1.40
1.40
1.40
1.40
1.40
1.60
1.60
1.60
1.60
1.60
1.60
2.00
2.00
2.00
2.00
2.50
1.24
1.24
1.24
1.24
1.24
1.24
1.24
1.40
1.40
1.40
1.40
1.40
1.56
1.56
1.56
1.72
1.88
1.88
2.04
11
12
13
14
15
16
18
20
22
24
26
29
32
33
39
42
48
52
59
150
180
200
250
300
350
450
550
700
800
950
1100
1400
1650
2100
2700
3300
4000
4900
180
210
260
350
450
560
750
980
1300
1550
1880
2250
2900
3500
4580
5800
7200
8950
11000
C
DUCT
Material - Aluminium /Copper
Shape AL . Cond - 6 & 10 sqmm - Solid circular, 16 sqmm & above Stranded compacted shaped
Copper . Cond - 4 & 6sqmm -solid/ stranded non compacted circular, 10sqmm Stranded compacted circular,16sqmm & above Stranded compacted
shaped
I SULATI
PVC Type A of IS 5831/ PTI
H PVC Type -C of IS -5831 , Colour Black
I E SHEATH PVC as per IS 1554PT-1
A M U I G Single layer of Aluminium ound wires / Flat Strips
UTE SHEATH PVC T PE ST-1 F IS 5831
PTI
S PVC T PE ST-2 F IS 5831/ F T PE/ F LS T PE
C L U
F UTE SHEATH BLACK. PTI
S any other colour as per requirement.
Tabulated appro . net wt. of cables are only guidelines for transportation, loading &unloading purpose.
Please ref page no 43 for normal delivery lengths & packing details.
ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
7.41
4.61
3.08
1.91
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
0.0367
0.0291
4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
0.0221
0.0176
8.89
5.53
3.70
2.29
1.44
1.04
0.769
0.532
0.384
0.304
0.247
0.197
0.151
0.122
0.0961
0.076
0.0610
0.0503
0.0422
5.53
3.70
2.20
1.38
0.87
0.63
0.464
0.322
0.232
0.184
0.1488
0.1189
0.0912
0.0733
0.0580
0.0459
0.0368
0.0303
0.0255
0.157
0.148
0.138
0.128
0.120
0.114
0.110
0.103
0.101
0.096
0.094
0.092
0.090
0.088
0.088
0.087
0.086
0.083
0.082
0.48
0.56
0.67
0.81
0.87
1.00
1.03
1.21
1.27
1.42
1.42
1.44
1.53
1.56
1.59
1.67
1.67
1.75
1.94
31
39
51
66
86
100
120
140
175
195
220
240
270
295
325
345
390
450
500
30
37
51
65
84
100
115
135
155
170
190
210
225
245
275
295
320
380
414
27
35
47
64
84
105
130
155
190
220
250
290
335
380
435
480
550
610
680
39
49
65
85
110
130
155
190
220
250
280
305
345
375
400
425
470
530
590
38
48
64
83
110
125
150
175
200
220
245
260
285
310
335
355
375
423
471
35
44
60
82
110
130
165
205
245
280
320
370
425
475
550
590
660
725
870
in K. Amps
Al
Cu
0.304
0.460
0.456
0.690
0.760
1.150
1.220
1.840
1.900
2.880
2.660
4.030
3.800
5.750
5.320
8.050
7.220 10.90
9.120 13.80
11.400 17.30
14.100 21.30
18.200 27.60
22.800 34.50
30.400 46.00
38.000 57.50
47.880 72.50
60.800 92.00
76.000 115.00
ote
ormal current ratings are given in standard conditions as given in page no - 40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42
11
TABLE - 7
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
Minimum
ominal Minimum
A M U I G ITH FLAT ST IP A F / F
A M U I G ITH
U D I ES A
/
o of
Thickness Thickness
ominal
Minimum
Appro .
Appro . et t
ominal
Minimum
Appro .
Appro . et t
Strands in
of
Thickness Thickness of
verall
of cable Kg/KM
Diameter Thickness of
verall of cable Kg/KM
of
Conductor Insulation inner Sh. of armour outer sheath Diameter ith Al cond ith Cu Cond. of armour outer sheath Diameter ith Al cond ith Cu Cond.
Al
Cu
mm
mm
mm
mm
A F
F
mm
mm
mm
A
mm
1
1
6
6
6
6
12
15
15
15
30
30
30
53
53
53
SS- SECTI
1/7
1/7
6
6
6
6
6
12
15
18
18
30
34
34
53
53
53
1.0
1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4
2.6
3.0
3.4
AL VIE
1
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.40
0.40
0.40
0.50
0.50
0.60
0.70
0.70
0.70
/A
/A
/A
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
/A
/A
/A
1.40
1.40
1.40
1.40
1.56
1.56
1.56
1.72
1.88
2.04
2.20
2.36
2.68
2.84
/A
/A
/A
18
20
22
25
27
30
32
35
38
43
48
53
56
66
/A
/A
/A
580
700
800
1000
1200
1550
1800
2100
2500
3100
3700
4500
5600
6900
/A
/A
/A
780
1000
1230
1620
2050
2720
3290
3970
4800
6080
7400
9450
11800
14700
1.40
1.40
1.40
1.60
1.60
1.60
1.60
1.60
2.00
2.00
2.00
2.00
2.50
2.50
3.15
3.15
4.00
1.24
1.24
1.24
1.40
1.40
1.40
1.56
1.56
1.56
1.72
1.72
1.88
2.04
2.20
2.52
2.84
3.00
18
19
20
20
22
23
26
29
33
35
37
41
47
50
58
64
72
600
660
750
750
900
1030
1300
1500
2050
2400
2760
3200
4200
5000
6600
8000
11000
650
730
870
950
1200
1450
1900
2350
3200
3900
4600
5500
7200
8700
11500
14000
18800
C
DUCT
Material - Aluminium /Copper
Shape AL . Cond - 6 & 10SQMM -Solid circular, 16sqmm & above Stranded compacted shaped
Copper. Cond - 4 & 6 sqmm-solid/ stranded non compacted circular, 10sqmm Stranded compacted circular,16sqmm & above Stranded compacted
shaped
2
3
4
5
I SULATI
PVC Type A of IS 5831/ PTI
H PVC Type -C of IS -5831 , Colour ed & Black
I E SHEATH PVC as per IS 1554PT-1
A M U I G Single layer of Galvanized steel ound wires / Flat Strips
UTE SHEATH PVC T PE ST-1 F IS 5831
PTI
S PVC T PE ST-2 F IS 5831/ F T PE/ F LS T PE
C L U
F UTE SHEATH BLACK . PTI
S any other colour as per requirement.
Tabulated appro . net wt. of cables are only guidelines for transportation, loading &unloading purpose.
Please ref page no 43 for normal delivery lengths & packing details.
ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM
4
--4.61
--5.53
0.098
0.23
6
4.61
3.08
5.53
3.70
0.096
0.28
10
3.08
1.83
3.70
2.20
0.091
0.34
16
1.91
1.15
2.29
1.38
0.085
0.40
25
1.20
0.727 1.44
0.87
0.083
0.42
35
0.868 0.524 1.04
0.63
0.082
0.48
50
0.641 0.387 0.769 0.464
0.082
0.49
70
0.443 0.268 0.532 0.322
0.076
0.56
95
0.320 0.193 0.384 0.232
0.076
0.58
120
0.253 0.153 0.304 0.184
0.075
0.63
150
0.206 0.1240 0.247 0.1488
0.074
0.63
185
0.164 0.0991 0.197 0.1189
0.074
0.64
240
0.125 0.0754 0.151 0.0912
0.073
0.67
300
0.100 0.0601 0.122 0.0733
0.073
0.68
400
0.0778 0.0470 0.0961 0.0580
0.072
0.70
500
0.0605 0.0366 0.0759 0.0459
0.072
0.70
630
0.0469 0.0283 0.0610 0.0368
0.072
0.70
ote
ormal current ratings are given in standard conditions as given in page no
multiplied by rating factor as given in page no. 42
32
27
27
41
40
34
35
50
55
45
47
70
70
58
59
90
90
76
78
115
110
92
99
140
135
115
125
165
160
140
150
205
190
170
185
240
210
190
210
275
240
210
240
310
275
240
275
350
320
275
325
405
355
305
365
450
385
345
420
490
425
380
475
540
465
415
540
640
- 40,41 , if site conditions are
in K. Amps
Al
Cu
35
35
0.304
0.460
44
45
0.456
0.690
58
60
0.760
1.150
75
78
1.220
1.840
97
105
1.90
2.880
120
125
2.66
4.030
145
155
3.80
5.750
180
195
5.32
8.050
215
230
7.22
10.90
235
265
9.12
13.80
270
305
11.40
17.30
300
350
14.10
21.30
345
410
18.20
27.60
385
465
22.80
34.50
485
530
30.40
46.00
460
605
38.00
57.50
550
785
47.90
72.50
different, current rating should be
12
TABLE - 8
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
-1
1
6
6
6
6
12
15
15
15
30
30
30
53
53
53
SS- SECTI
1/7
1/7
6
6
6
6
6
12
15
18
18
30
34
34
53
53
53
ominal Minimum
A M U I G ITH FLAT ST IP A F / F
A M U I G ITH
U D I ES A
/
Thickness Thickness
ominal
Minimum
Appro .
Appro . et t
ominal
Minimum
Appro .
Appro . et t
of
Thick. of
Thick. of
verall
of cable Kg/KM
Diameter Thickness of
verall of cable Kg/KM
of
Insulation inner Sh. armour strip outer sheath Diameter
ith Al cond ith Cu Cond. of wire
outer sheath Diameter ith Al cond ith Cu Cond.
mm
mm
mm
mm
A F
F
mm
mm
mm
A
mm
1.0
1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4
2.6
3.0
3.4
AL VIE
1
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.40
040
0.40
0.50
0.50
0.60
0.60
0.70
0.70
0.70
/A
/A
/A
0.80
080.
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
/A
/A
/A
1.40
1.40
1.40
1.56
1.56
1.56
1.72
1.88
1.88
2.20
2.36
2.52
2.84
3.00
/A
/A
/A
20
23
24
27
31
35
37
41
46
51
56
63
70
78
/A
/A
/A
700
900
1000
1300
1600
2000
2400
2800
3400
4200
5050
6300
7800
9700
/A
/A
/A
1000
1350
1650
2230
2900
3750
4630
5600
6840
8650
10630
13740
17100
21418
1.40
1.40
1.40
1.60
1.60
1.60
1.60
2.00
2.00
2.00
2.00
2.50
2.50
2.50
3.15
3.15
4.00
1.24
1.24
1.40
1.40
1.40
1.40
1.56
1.56
1.72
1.72
1.88
2.04
2.20
2.36
2.68
3.00
3.00
18
19
21
21
23
26
29
33
37
39
43
49
54
59
68
75
84
600
700
900
950
1100
1300
1600
2150
2650
3000
3550
4600
5600
6600
8700
11000
14000
650
810
1100
1250
1550
1950
2530
3450
4400
5200
6300
8000
10000
12000
16000
20000
25500
C
DUCT
Material - Aluminium /Copper
Shape AL . Cond - 6 & 10SQMM -Solid circular, 16sqmm & above Stranded compacted shaped
Copper . Cond - 4 & 6sqmm -solid/ stranded non compacted circular, 10sqmm Stranded compacted circular,16sqmm & above Stranded compacted
2
3
4
5
shaped
I SULATI
PVC Type A of IS 5831/ PTI
H PVC Type -C of IS -5831 , Colour ed, ellow, Blue
I E SHEATH PVC as per IS 1554PT-1
A M U I G Single layer of Galvanized steel ound wires / Flat Strips
UTE SHEATH PVC T PE ST-1 F IS 5831
PTI
S PVC T PE ST-2 F IS 5831/ F T PE/ F LS T PE
C L U
F UTE SHEATH BLACK . PTI
S any other colour as per requirement.
Tabulated appro . net wt. of cables are only guidelines for transportation, loading &unloading purpose.
Please ref page no 43 for normal delivery lengths & packing details.
ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM
4
4.61
5.53
0.098
0.23
6
4.61
3.08
5.53
3.70
0.096
0.28
10
3.08
1.83
3.70
2.20
0.091
0.34
16
1.91
1.15
2.29
1.38
0.085
0.40
25
1.20
0.727 1.44
0.87
0.083
0.42
35
0.868 0.524 1.04
0.63
0.082
0.48
50
0.641 0.387 0.769
0.464
0.082
0.49
70
0.443 0.268 0.532
0.322
0.076
0.56
95
0.320 0.193 0.384
0.232
0.076
0.58
120
0.253 0.153 0.304
0.184
0.075
0.63
150
0.206 0.1240 0.247
0.1488
0.074
0.63
185
0.164 0.0991 0.197
0.1189
0.074
0.64
240
0.125 0.0754 0.151
0.0912
0.073
0.67
300
0.100 0.0601 0.122
0.0733
0.073
0.68
400
0.0778 0.0470 0.0961 0.0580
0.072
0.70
500
0.0605 0.0366 0.0759 0.0459
0.072
0.70
630
0.0469 0.0283 0.0610 0.0368
0.072
0.70
ote
ormal current ratings are given in standard conditions as given in page no
multiplied by rating factor as given in page no. 42
28
35
46
60
76
92
110
135
165
185
210
235
275
305
335
370
405
- 40,41
23
23
36
30
30
45
39
40
60
50
51
77
63
70
99
77
86
120
95
105
145
115 130
175
140 155
210
155 180
240
175 205
270
200 240
300
235 280
345
260 315
385
290 375
425
320 425
470
350 480
555
, if site conditions are
in K. Amps
Al
Cu
30
30
0.304
38
39
0.456
50
52
0.760
64
66
1.220
81
90
1.900
99
110
2.660
125 135
3.800
150 165
5.320
175 200
7.220
195 230
9.120
225 265 11.400
255 305 14.100
295 355 18.200
335 400 22.800
360 435 30.400
390 520 38.000
470 675 47.900
different, current rating
0.460
0.690
1.150
1.840
2.880
4.030
5.750
8.050
10.900
13.800
17.300
21.300
27.600
34.500
46.000
57.500
72.500
should be
13
TABLE - 9
TECHNICAL DETAIL FOR HAVELLS 1.1 KV THREE AND HALF CORES, AL/CUCOPPER COND.,
PVC INSULATED, GALVANIZED STEEL WIRE/STRIP ARMOURED CABLES
Cable Code 3.5 Core - A F / F , A
/
ef Specification IS 1554PA T -1
PHYSICAL PARAMETERS
SI E
Cross-sectional
area
sqmm
3X25 16
3X35 16
3X50 25
3X70 35
3X95 50
3X120 70
3X150 70
3X185 95
3X240 120
3X300 150
3X400 185
3X500 240
3X630 300
C
Minimum
Minimum
ominal
A M U I G ITH FLAT ST IP A F / F
A M U I G ITH
U D I ES A
/
os of
Thickness of Thickness ominal Minimum
Appro .
Appro . et t
ominal
Minimum
Appro .
Appro . et t
of
Strands in
Insulation
Thickness Thickness of
verall
of cable Kg/KM Diameter Thickness of
verall of cable Kg/KM
inner Sh. Strip outer sheath Diameter ith Al cond ith Cu Cond. of wire outer sheath Diameter ith Al cond ith Cu Cond.
Conductor
mm
Phase/ eutral Phase/ eutral mm
mm
mm
mm
A F
F
mm
mm
mm
A
6/6
6/6
6/6
12/6
15/6
15/12
15/12
30/15
30/15
30/15
53/30
53/30
53/30
SS- SECTI
6/6
6/6
6/6
12/6
15/6
18/12
18/12
30/15
34/18
34/18
53/30
53/34
53/34
AL VIE
1
2
3
4
5
1.20/1.00
1.20/1.00
1.40/1.20
1.40/1.20
1.60/1.40
1.60/1.40
1.80/1.40
2.00/1.60
2.20/1.60
2.40/1.80
2.60/2.00
3.00/2.20
3.40/2.40
0.30
0.30
0.30
0.40
0.40
0.50
0.50
0.50
0.60
0.60
0.70
0.70
0.70
0.80
0.80
0.80
0.80
0.80
0.80
0.8
0.80
0.80
0.80
0.80
0.80
0.80
1.40
1.40
1.56
1.56
1.56
1.72
1.88
2.04
2.20
2.36
2.68
2.84
3.00
24
26
30
34
37
41
45
49
55
61
69
77
87
1000
1200
1500
1800
2300
2800
3200
3900
4800
5800
7300
9000
11500
1550
1950
2600
3300
4350
5450
6400
7900
10000
12300
15800
19500
25000
1.60
1.60
1.60
2.00
2.00
2.00
2.00
2.50
2.50
3.15
3.15
4.00
4.00
1.40
1.40
1.56
1.56
1.72
1.88
1.88
2.04
2.30
2.52
2.63
3.00
3.00
26
28
31
36
39
43
47
53
58
65
75
84
92
1300
1450
1800
2400
3000
3500
4000
5200
6400
8200
9900
13500
16000
1850
2150
2800
3800
5000
6100
7200
9200
11500
14500
18400
24000
28500
C
DUCT
Material - Aluminium /Copper
Shape AL . Cond - 6 & 10SQMM -Solid circular, 16sqmm & above Stranded compacted shaped
Copper. Cond - 4 & 6sqmm -solid/ stranded non compacted circular, 10sqmm Stranded compacted circular,16sqmm & above Stranded compacted
shaped
I SULATI
PVC Type A of IS 5831/ PTI
H PVC Type -C of IS -5831 , Colour ed, ellow, Blue, Black
I E SHEATH PVC as per IS 1554PT-1
A M U I G Single layer of Galvanized steel ound wires / Flat Strips
UTE SHEATH PVC T PE ST-1 F IS 5831
PTI
S PVC T PE ST-2 F IS 5831/ F T PE/ F LS T PE
C L U
F UTE SHEATH BLACK . PTI
S any other colour as per requirement.
Tabulated appro . net wt. of cables are only guidelines for transportation, loading &unloading purpose.
Please ref page no 43 for normal delivery lengths & packing details.
ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM
3X25 16
3X35 16
3X50 25
3X70 35
3X95 50
3X120 70
3X150 70
3X185 95
3X240 120
3X300 150
3X400 185
3X500 240
3X630 300
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
1.44
1.04
0.769
0.532
0.384
0.304
0.247
0.197
0.151
0.122
0.0961
0.0759
0.0610
0.87
0.63
0.464
0.322
0.232
0.184
0.1488
0.1189
0.0912
0.0733
0.0580
0.0459
0.0368
0.083
0.082
0.082
0.076
0.076
0.075
0.074
0.074
0.073
0.073
0.072
0.072
0.072
0.42
0.48
0.49
0.56
0.58
0.63
0.63
0.64
0.67
0.68
0.70
0.70
0.70
76
92
110
135
165
185
210
235
275
305
335
370
405
63
77
95
115
140
155
175
200
235
260
290
320
350
70
86
105
130
155
180
205
240
280
315
375
425
480
99
120
145
175
210
240
270
300
345
385
425
470
555
81
99
125
150
175
195
225
255
295
335
360
390
470
90
110
135
165
200
230
265
305
355
400
435
520
675
in K. Amps
Al
Cu
1.90
2.66
3.80
5.32
7.22
9.12
11.40
14.10
18.20
22.80
30.40
38.00
47.90
2.88
4.03
5.75
8.05
10.90
13.80
17.30
21.30
27.60
34.50
46.00
57.50
72.50
ote
ormal current ratings are given in standard conditions as given in page no - 40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42
16 Drawing
ire Machine
14
TABLE - 10
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
Minimum
ominal Minimum
A M U I G ITH FLAT ST IP A F / F
A M U I G ITH
U D I ES A
/
o of
Thickness Thickness
ominal
Minimum
Appro .
Appro . et t
ominal
Minimum
Appro .
Appro . et t
of
Strands in
of
Thickness Thickness of
verall
of cable Kg/KM
Diameter Thickness of
verall of cable Kg/KM
ith Al cond ith Cu Cond.of armour outer sheath Diameter
ith Al cond
ith Cu Cond.
Conductor Insulation inner Sh. of armour outer sheath Diameter
mm
Al
Cu
mm
mm
mm
mm
A F
F
mm
mm
mm
A
1
1
6
6
6
6
12
15
15
15
30
30
30
53
53
53
SS- SECTI
1/7
1/7
6
6
6
6
6
12
15
18
18
30
34
34
53
53
53
1.0
1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4
2.6
3.0
3.4
AL VIE
1
2
3
4
5
0.30
0.30
0.30
0.30
0.30
0.30
0.40
0.40
0.40
0.50
0.50
0.60
0.60
0.70
0.70
0.70
0.70
/A
/A
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
/A
/A
1.40
1.40
1.40
1.40
1.56
1.56
1.72
1.88
1.88
2.04
2.36
2.52
2.84
3.00
3.00
/A
/A
21
22
25
28
32
35
40
43
48
52
59
67
74
80
90
/A
/A
750
860
1100
1300
1600
2000
2600
3050
3600
4300
5400
6600
8200
10500
13000
/A
/A
998
1260
1720
2170
2850
3740
5000
6030
7325
8890
11355
14050
18128
22900
28625
1.40
1.40
1.60
1.60
1.60
1.60
2.00
2.00
2.00
2.00
2.5
2.5
2.50
3.15
3.15
4.00
4.00
1.24
1.24
1.40
1.40
1.40
1.56
1.56
1.56
1.72
1.88
2.04
2.20
2.36
2.68
2.84
3.00
3.00
18
21
22
23
27
30
34
37
42
47
51
56
62
70
76
86
96
650
880
900
1120
1400
1600
2200
2650
3300
3850
4850
5800
7000
9200
11000
15000
18000
800
1030
1150
1520
2020
2470
3445
4390
5660
6830
8575
10390
12960
16650
20930
27400
33630
C
DUCT
Material - Aluminium /Copper
Shape AL . Cond - 6 & 10SQMM -Solid circular, 16sqmm & above Stranded compacted shaped
Copper . Cond - 4 & 6sqmm -solid/ stranded non compacted circular , 10sqmm Stranded compacted circular,16sqmm & above Stranded
compacted shaped
I SULATI
PVC Type A of IS 5831/ PTI
H PVC Type -C of IS -5831 , Colour ed, ellow, Blue, Black
I E SHEATH PVC as per IS 1554PT-1
A M U I G Single layer of Galvanized steel ound wires / Flat Strips
UTE SHEATH PVC T PE ST-1 F IS 5831
PTI
S PVC T PE ST-2 F IS 5831/ F T PE/ F LS T PE
C L U
F UTE SHEATH BLACK . PTI
S any other colour as per requirement.
Tabulated appro . net wt. of cables are only guidelines for transportation, loading &unloading purpose ..
Please ref page no 43 for normal delivery lengths & packing details.
ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
4.61
3.08
1.91
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
5.53
3.70
2.29
1.44
1.04
0.769
0.532
0.384
0.304
0.247
0.197
0.151
0.122
0.0961
0.0759
0.0610
5.53
3.70
2.20
1.38
0.87
0.63
0.464
0.322
0.232
0.184
0.1488
0.1189
0.0912
0.0733
0.0580
0.0459
0.0368
0.098
0.096
0.091
0.085
0.083
0.082
0.082
0.076
0.076
0.075
0.074
0.074
0.073
0.073
0.072
0.072
0.072
0.23
0.28
0.34
0.40
0.42
0.48
0.49
0.56
0.58
0.63
0.63
0.64
0.67
0.68
0.70
0.70
0.70
28
35
46
60
76
92
110
135
165
185
210
235
275
305
335
370
405
23
30
39
50
63
77
95
115
140
155
175
200
235
260
290
320
350
23
30
40
51
70
86
105
130
155
180
205
240
280
315
375
425
480
36
45
60
77
99
120
145
175
210
240
270
300
345
385
425
470
555
30
38
50
64
81
99
125
150
175
195
225
255
295
335
360
390
470
30
39
52
66
90
110
135
165
200
230
265
305
355
400
435
520
675
in K. Amps
Al
Cu
0.304
0.456
0.760
1.220
1.900
2.660
3.800
5.320
7.220
9.120
11.40
14.10
18.20
22.80
30.40
38.00
47.90
0.460
0.690
1.150
1.840
2.880
4.030
5.750
8.050
10.900
13.800
17.300
21.300
27.600
34.500
46.000
57.500
72.500
ote
ormal current ratings are given in standard conditions as given in page no - 40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42
15
TABLE - 11
TECHNICAL DETAIL FOR HAVELLS 1.1 KV 1.5 SQ MM COPPER COND., PVC INSULATED,
GALVANIZED STEEL WIRE/STRIP ARMOURED CONTROL CABLES
Cable Code
/ F /
ef Specification IS 1554PA T -1
PHYSICAL PARAMETERS
o
of
Cores
2
3
4
5
6
7
10
12
14
16
19
24
27
30
37
40
44
52
61
C
Minimum
Thick.
om thick.
of inner of outer
Sheath
Sheath
U A M U ED
Appro .
Appro . et t
verall
of cable Kg/KM
Diameter mm
mm
mm
Solid cond
Std. Cond.
Solid cond
Std. Cond.
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.40
0.40
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.2
12
12.5
13
14
15
15
18
19
20
21
22
25
26
27
28
29
31
33
35
12
13
14
14
15
15
19
20
20
21
23
26
27
28
29
30
33
35
37
180
200
230
250
290
310
420
470
530
600
700
850
920
1000
1200
1270
1400
1650
1850
180
210
250
250
300
320
450
500
550
600
720
900
995
1050
1240
1300
1450
1700
1950
SS- SECTI
A
ominal
Thickness
of Armour
strip mm
/A
/A
/A
/A
/A
/A
/A
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
M U ED
Minimum
Thickness
of outr sh.
mm
Solid cond
Std. Cond.
/A
/A
/A
/A
/A
/A
/A
1.24
1.40
1.40
1.40
1.40
1.40
1.40
1.40
1.40
1.56
1.56
1.56
/A
/A
/A
/A
/A
/A
/A
19
20
21
22
25
26
27
29
30
32
34
35
/A
/A
/A
/A
/A
/A
/A
20
21
22
23
27
27
28
30
31
34
35
37
Solid cond
Std. Cond.
/A
/A
/A
/A
/A
/A
/A
700
800
850
950
1150
1250
1330
1530
1650
1850
2050
2300
/A
/A
/A
/A
/A
/A
/A
745
820
900
1000
1200
1300
1400
1600
1750
1950
2150
2450
A M
ominal
Dia of
Armour
wire mm
1.40
1.40
1.40
1.40
1.40
1.40
1.40
1.60
1.60
1.60
1.60
1.60
1.60
1.60
1.60
1.60
1.60
2.00
2.00
U ED ITH
U D I ES
Minimum
Appro .
Appro . et t
Thickness
verall
of cable Kg/KM
of outr sh. Diameter mm
with
with
mm
1.24
1.24
1.24
1.24
1.24
1.24
1.40
1.40
1.40
1.40
1.40
1.40
1.40
1.40
1.40
1.56
1.56
1.56
1.56
13
14
15
16
17
17
20
21
22
23
24
27
28
29
30
32
34
36
38
14
14
15
16
17
17
21
22
23
24
25
28
29
30
32
35
36
38
40
400
450
500
520
580
650
800
940
1000
1100
1200
1450
1500
1650
1850
2000
2200
2700
3000
420
450
500
550
600
680
840
970
1050
1100
1250
1500
1550
1700
1950
2100
2300
2800
3100
AL VIE
1
2
CONDUCTOR : MATERIAL : Annealed bare copper / option - Tinned Construction : SOLID / STRANDED
INSULATION MATERIAL : PVC Type Aof IS :5831/ OPTION : HR PVC ( Type -C of IS -5831) Nominal insulation thickness - 0.80mm
Cores identification : Up to 5Cores by colour coding & more tthan 5 cores 5cores : By colour coding / Nos. printing on cores as per IS :1554pt-1
ARMOURING : Single layer of Galvanized steel Round wires / Flat Strips as applicable
OUTER SHEATH : PVC TYPE ST-1 OF IS : 5831 OPTIONS : PVC TYPE ST-2 OF IS : 5831/ FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : any other colour as per requirement
~ Tabulated appro . net wt. of cables are only guidelines for transportation, loading &unloading purpose .
~ Please ref page no 43 for normal delivery lengths & packing details.
ELECTRICAL PARAMETERS
Ma . Cond. D.C.
esistance at
20oC in hm/km
2
3
4
5
6
7
10
12
14
16
19
24
27
30
37
40
44
52
61
12.10
12.10
12.10
12.10
12.10
12.10
12.10
12.10
12.10
12.10
12.10
12.10
12.10
12.10
12.10
12.10
12.10
12.10
12.10
14.52
14.52
14.52
14.52
14.52
14.52
14.52
14.52
14.52
14.52
14.52
14.52
14.52
14.52
14.52
14.52
14.52
14.52
14.52
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
eactance
Appro
of cable
Capecitance
at 50H
of cable
Ground
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
23
21
21
21
15
14
13
12
11
11
10
9
9
9
8
8
7
6
6
in ohms/km in microF/KM
0.112
0.112
0.112
0.112
0.112
0.112
0.112
0.112
0.112
0.112
0.112
0.112
0.112
0.112
0.112
0.112
0.112
0.112
0.112
ith H. . insulation
Duct
Air
Ground
Duct
20
17
17
17
13
13
11
10
10
9
9
8
8
7
7
7
7
6
6
20
17
17
17
13
13
11
10
10
9
9
8
8
7
7
7
7
6
6
26
24
24
24
17
16
15
14
13
13
11
10
10
10
9
9
8
7
7
24
21
21
21
16
15
13
12
12
11
11
10
10
8
8
8
7
7
7
Air
24
21
21
21
16
15
13
12
12
11
11
10
10
8
8
8
7
7
7
Insulation
0.173
0.173
0.173
0.173
0.173
0.173
0.173
0.173
0.173
0.173
0.173
0.173
0.173
0.173
0.173
0.173
0.173
0.173
0.173
Insulation
0.156
0.156
0.156
0.156
0.156
0.156
0.156
0.156
0.156
0.156
0.156
0.156
0.156
0.156
0.156
0.156
0.156
0.156
0.156
ote
ormal current ratings are given in standard conditions as given in page no -40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42
16
TABLE - 12
Minimum
Thick.
om thick.
of inner of outer
Sheath
Sheath
U A M U ED
Appro .
Appro . et t
verall
of cable Kg/KM
Diameter mm
Armour outer
mm
mm
Solid cond
Std. Cond.
Solid cond
Std. Cond.
0.30
1.8
13
13
220
240
/A
/A
/A
/A
/A
/A
1.40
1.24
14
15
480
500
3
4
5
6
7
10
12
14
16
19
24
27
30
37
40
44
52
61
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.40
0.40
0.40
0.40
0.40
1.8
1.8
1.8
1.8
1.8
1.8
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.2
2.2
2.2
2.2
2.2
14
15
16
17
17
20
21
22
24
25
28
29
30
33
34
36
38
40
14
15
16
17
17
21
22
24
25
26
30
31
32
34
36
38
40
43
260
310
340
390
424
570
670
750
840
950
1200
1300
1400
1700
1850
2000
2350
2700
270
320
350
420
440
600
700
800
900
1000
1260
1350
1500
1800
1900
2100
2450
2800
/A
/A
/A
/A
/A
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
/A
/A
/A
/A
/A
1.40
1.40
1.40
1.40
1.40
1.40
1.40
1.56
1.56
1.56
1.56
1.56
1.56
/A
/A
/A
/A
/A
21
22
23
24
25
29
30
31
34
35
37
39
41
/A
/A
/A
/A
/A
22
23
24
25
26
30
31
32
35
36
37
41
43
/A
/A
/A
/A
/A
850
950
1050
1120
1250
1550
1650
1800
2100
2300
2500
2850
3250
/A
/A
/A
/A
/A
900
1000
1035
1150
1330
1630
1750
1920
2225
2400
2600
2950
3350
1.40
1.40
1.40
1.40
1.40
1.60
1.60
1.60
1.60
1.60
1.60
1.60
1.60
2.00
2.00
2.00
2.00
2.00
1.24
1.24
1.24
1.24
1.24
1.40
1.40
1.40
1.40
1.40
1.56
1.56
1.56
1.56
1.56
1.56
1.72
1.72
15
16
17
19
19
23
24
25
26
27
31
32
33
36
37
40
42
44
16
17
18
20
20
24
25
26
27
28
32
33
34
37
39
41
43
46
530
600
640
730
760
1100
1180
1300
1400
1550
1900
2050
2200
2800
2950
3200
3600
4000
550
620
680
750
790
1150
1250
1350
1450
1620
2000
2100
2250
2900
3100
3350
3700
4200
AL VIE
1
2
3
4
5
DUCT
mm
Solid cond
Std. Cond.
Solid cond
Std. Cond.
wire mm
mm
Appro . et t
of cable Kg/KM
Diameter mm
SS- SECTI
strip mm
A M U ED ITH
U D I ES
Appro . et t
Minimum Minimum
Appro .
of cable Kg/KM
Dia of
Thickness
verall
Armour
outer sheath
MATE IAL Annealed bare copper / option Tinned Construction S LID / ST A DED
I SULATI
MATE IAL PVC Type A of IS 5831/ PTI
H PVC Type -C of IS -5831 ominal insulation thickness 0.90mm Cores identification Up to 5Cores by colour coding & more than 5 cores 5cores By colour coding / os. printing on
cores as per IS 1554pt-1
I
PTI
Tabulated appro . net wt. of cables are only guidelines for transportation, loading &unloading purpose .
Please ref page no 43 for normal delivery lengths & packing details.
ELECTRICAL PARAMETERS
Ma . Cond. D.C.
esistance at
20oC in hm/km
2
3
4
5
6
7
10
12
14
16
19
24
27
30
37
40
44
52
61
7.41
7.41
7.41
7.41
7.41
7.41
7.41
7.41
7.41
7.41
7.41
7.41
7.41
7.41
7.41
7.41
7.41
7.41
7.41
8.89
8.89
8.89
8.89
8.89
8.89
8.89
8.89
8.89
8.89
8.89
8.89
8.89
8.89
8.89
8.89
8.89
8.89
8.89
9.34
9.34
9.34
9.34
9.34
9.34
9.34
9.34
9.34
9.34
9.34
9.34
9.34
9.34
9.34
9.34
9.34
9.34
9.34
eactance
of cable
at 50H
in ohms/km
0.107
0.107
0.107
0.107
0.107
0.107
0.107
0.107
0.107
0.107
0.107
0.107
0.107
0.107
0.107
0.107
0.107
0.107
0.107
Appro
ormal Current ating in Amps
ith general insulation
ith H. . insulation
Capecitance
of cable
Ground Duct
Air
Ground Duct
Air
in microF/KM
0.22
0.22
0.22
0.22
0.22
0.22
0.22
0.22
0.22
0.22
0.22
0.22
0.22
0.22
0.22
0.22
0.22
0.22
0.22
32
27
27
27
21
20
18
17
16
15
14
13
12
12
11
11
10
9
8
27
24
24
24
18
17
15
14
13
13
12
11
10
10
9
9
9
8
8
27
24
24
24
18
17
15
14
13
13
12
11
10
10
9
9
9
8
8
38
30
30
30
24
22
20
19
18
17
16
14
13
13
12
12
11
10
9
32
28
28
28
21
20
16
16
15
15
14
13
12
12
10
10
10
10
9
32
28
28
28
21
20
16
16
15
15
14
13
12
12
10
10
10
10
9
General
Insulation
Heat
Insulation
0.288
0.288
0.288
0.288
0.288
0.288
0.288
0.288
0.288
0.288
0.288
0.288
0.288
0.288
0.288
0.288
0.288
0.288
0.288
0.260
0.260
0.260
0.260
0.260
0.260
0.260
0.260
0.260
0.260
0.260
0.260
0.260
0.260
0.260
0.260
0.260
0.260
0.260
ote
ormal current ratings are given in standard conditions as given in page no -40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42
17
TABLE - 13
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
SS-SECTI
Minimum
o of Strand in
Conductor
Al
Cu
1
1
6
6
6
6
12
15
15
15
30
30
30
53
53
53
53
53
AL VIE
1
2
3
1/7
1/7
6
6
6
6
6
12
15
18
18
30
34
34
53
53
53
53
53
ominal
Thickness of
Insulation
mm
0.7
0.7
0.7
0.7
0.9
0.9
1.0
1.1
1.1
1.2
1.4
1.6
1.7
1.8
2.0
2.2
2.4
2.6
2.8
ominal
Thickness of
outer sheath
mm
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
2.0
2.0
2.0
2.0
2.2
2.2
2.2
2.4
2.6
Appro .
veral
Diameter
mm
Appro .
ith Al Conductor
A2X
8
9
10
11
12
13
15
16
18
20
22
24
27
30
33
36
40
47
51
70
80
100
130
180
230
300
370
460
550
620
820
1000
1200
1550
1900
2400
3000
3750
95
120
160
230
335
450
610
800
1050
1300
1550
1950
2500
3050
4000
5000
6300
7950
9950
C
DUCT
Material - Aluminium /Copper
Shape AL . Cond - 6 & 10 SQMM -Solid circular, 16 sq.mm & above Stranded compacted circular
Copper. Cond - 4 & 6 sq. mm-solid/ stranded non compacted circular, 10 sq. mm & above Stranded compacted circular
I SULATI
Crosslinked Polyethylene XLPE
UTE SHEATH PVC T PE ST-2 F IS 5831
C L U
F UTE SHEATH BLACK . PTI
atural colour
PTI
S F T PE/ F LS T PE
S any other colour as per requirement.
- Tabulated appro . net wt. of cables are only guidelines for transportation, loading & unloading purpose..
- Please ref page no 43 for normal delivery lengths & packing details.
ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
4.61
3.08
1.91
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
0.0367
0.0291
4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
0.0221
0.0176
5.90
3.94
2.44
1.54
1.11
0.820
0.567
0.411
0.325
0.265
0.211
0.162
0.130
0.1023
0.0808
0.0648
0.0530
0.0444
5.90
3.94
2.34
1.47
0.931
0.671
0.495
0.343
0.248
0.197
0.159
0.127
0.0976
0.0778
0.0618
0.0489
0.0391
0.0319
0.0268
0.136
0.128
0.118
0.108
0.102
0.097
0.092
0.088
0.085
0.082
0.082
0.082
0.079
0.078
0.077
0.076
0.075
0.075
0.068
0.29
0.34
0.42
0.50
0.52
0.60
0.63
0.68
0.79
0.79
0.79
0.79
0.84
0.86
0.88
0.90
0.94
0.97
1.01
48
62
81
99
117
138
168
204
230
265
295
340
390
450
500
555
625
690
45
62
80
90
110
125
155
185
210
230
260
300
335
380
430
485
530
570
45
61
83
115
135
170
210
255
300
342
385
450
519
605
700
809
935
1065
48
60
80
104
130
155
185
225
265
300
335
380
435
490
550
610
680
740
780
47
59
78
102
115
140
165
200
235
265
300
335
385
430
480
530
590
630
660
45
57
77
106
145
175
215
270
330
380
430
495
590
670
780
900
1020
1140
1250
in K. Amps
Al
Cu
0.376
0.564
0.940
1.504
2.350
3.290
4.700
6.580
8.930
11.28
14.10
17.39
22.56
28.20
37.60
47.00
59.22
75.20
94.00
0.572
0.858
1.430
2.288
3.575
5.005
7.150
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
71.50
90.09
114.40
143.00
ote
ormal current ratings are given in standard conditions as given in page no -40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42
18
TABLE - 14
Minimum
o of
Strands in
Conductor
Al
Cu
1/7
1
1/7
1
6
6
6
6
6
6
6
6
6
12
12
15
15
15
18
15
18
30
30
30
34
30
34
53
53
53
53
53
53
SS- SECTI
AL VIE
1
2
3
4
ominal
Thickness of
Insulation
Minimum
Thickness of
inner sheath
ominal
Thickness of
UTE sheath
mm
0.7
0.7
0.7
0.7
0.9
0.9
1.0
1.1
1.1
1.2
1.4
1.6
1.7
1.8
2.0
2.2
2.4
mm
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.40
0.40
0.40
0.50
0.50
0.60
0.60
0.70
0.70
mm
1.80
1.80
1.80
1.80
2.00
2.00
2.00
2.00
2.20
2.20
2.20
2.40
2.60
2.80
3.00
3.40
3.60
Appro .
overall
Diameter
mm
13
14
17
17
19
20
22
25
28
31
33
37
41
44
48
54
62
Appro . et t
of cable Kg/KM
ith Al Cond
A2X
200
330
350
310
400
480
590
760
1000
1200
1400
1750
2000
2700
3350
4200
5300
ith Cu Cond.
2X
250
400
470
500
700
900
1200
1630
2200
2700
3300
4000
5000
6400
8300
10400
13000
C
DUCT
Material - Aluminium /Copper
Shape AL . Cond - 6 & 10 sqmm -Solid circular, 16sqmm & above Stranded compacted shaped
Copper . Cond - 4 & 6 sqmm -solid/ stranded non compacted circular, 10 sqmm Stranded compacted circular,16 sqmm & above Stranded compacted
shaped
I SULATI
Crosslinked Polyethylene XLPE
ed & Black colour
I E SHEATH PVC as per IS 7098PT-1
UTE SHEETH PVC T PE ST-2 F IS 5831 -- PTI
S F T PE/F LS T PE
C L U
F UTE SHEATH BLACK, PTI
S any other colour as per requirement.
Tabulated appro . net wt. of cables are only guidelines for transportation, loading &unloading purpose.
Please ref page no 43 for normal delivery lengths & packing details.
ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM
4
4.61
5.90
0.098
0.11
34
6
4.61
3.08
5.90
3.94
0.090
0.13
43
10
3.08
1.83
3.94
2.34
0.084
0.16
57
16
1.91
1.15
2.44
1.47
0.080
0.18
78
25
1.20
0.727 1.54
0.931
0.080
0.20
95
35
0.868 0.524 1.11
0.671
0.080
0.23
116
50
0.641 0.387 0.820 0.495
0.078
0.24
140
70
0.443 0.268 0.567 0.343
0.077
0.26
170
95
0.320 0.193 0.411
0.248
0.084
0.29
200
120
0.253 0.153 0.325 0.197
0.072
0.29
225
150
0.206 0.1240 0.265 0.159
0.072
0.29
255
185
0.164 0.0991 0.211
0.127
0.072
0.29
285
240
0.125 0.0754 0.162 0.098
0.072
0.31
325
300
0.100 0.0601 0.130 0.078
0.071
0.33
370
400
0.0778 0.0470 0.1023 0.0618
0.070
0.33
435
500
0.0605 0.0366 0.0808 0.0489
0.070
0.34
481
630
0.0469 0.0283 0.0648 0.0391
0.069
0.36
537
ote
ormal current ratings are given in standard conditions as given in page no -40,41
multiplied by rating factor as given in page no. 42
28
37
48
61
80
94
110
140
165
185
210
235
270
305
350
405
470
, if site
30
44
40
55
53
74
70
94
99
120
117
145
140
170
176
210
221
250
258
285
294
315
339
355
402
410
461
460
542
520
624
580
723
680
conditions are
in K. Amps
Al
Cu
37
39
0.376
0.572
47
50
0.564
0.858
61
67
0.940
1.430
78
85
1.50
2.29
100
125
2.35
3.58
120
155
3.29
5.01
145
190
4.70
7.15
175
235
6.58
10.01
210
290
8.93
13.59
240
330
11.28
17.16
270
375
14.10 21.45
300
435
17.39 26.46
350
510
22.56 34.32
390
590
28.20 42.90
440
670
37.60 57.20
480
750
47.00 71.50
575
875
59.22 90.09
different, current rating should be
19
TABLE - 15
SS- SECTI
Minimum o of
Strands in
Conductor
Al
Cu
AL VIE
2
3
4
Minimum
thickness of
inner Sh.
mm
ominal thick.
of outer
Sheath
mm
0.7
0.7
0.7
0.7
0.9
0.9
1.0
1.1
1.1
1.2
1.4
1.6
1.7
1.8
2.0
2.2
2.4
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.40
0.40
0.40
0.50
0.50
0.60
0.60
0.70
0.70
0.70
1.80
1.80
1.80
1.80
2.00
2.00
2.00
2.20
2.20
2.20
2.40
2.60
2.80
3.00
3.20
3.60
3.80
1/7
1/7
6
6
6
6
6
12
15
18
18
30
34
34
53
53
53
1
1
6
6
6
6
12
15
15
15
30
30
30
53
53
53
1
ominal
thickness of
Insulation
mm
Appro .
verall
Diameter
mm
Appro . et t
of cable Kg/KM
ith Al cond
ith Cu Cond.
A2X
2X
14
16
18
18
21
22
25
30
32
35
39
43
49
53
59
66
73
225
330
400
400
530
640
800
1100
1350
1650
2050
2500
3150
3850
4850
6100
7650
300
440
580
700
1000
1300
1700
2400
3100
3800
4800
5950
7600
9400
12000
15000
19000
C
DUCT
Material - Aluminium /Copper
Shape AL . Cond - 6 & 10 SQMM -Solid circular, 16sqmm & above Stranded compacted shaped
Copper. Cond - 4 & 6 sqmm -solid/ stranded non compacted circular, 10sqmm Stranded compacted circular,16sqmm & above Stranded compacted
shaped
I SULATI
Crosslinked Polyethylene XLPE
I E SHEATH PVC as per IS 7098PT-1
UTE SHEATH PVC T PE ST-2 F IS 5831
C L U
S F T PE/F LS T PE
Tabulated appro . net wt. of cables are only guidelines for transportation, loading &unloading purpose.
Please ref page no 43 for normal delivery lengths & packing details.
ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
4.61
3.08
1.91
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
5.90
3.94
2.44
1.54
1.11
0.820
0.567
0.411
0.325
0.265
0.211
0.162
0.130
0.1023
0.0808
0.0648
5.90
3.94
2.34
1.47
0.931
0.671
0.495
0.343
0.248
0.197
0.159
0.127
0.098
0.078
0.0618
0.0489
0.0391
0.098
0.090
0.084
0.080
0.080
0.080
0.078
0.077
0.074
0.072
0.072
0.072
0.072
0.071
0.070
0.070
0.069
0.11
0.13
0.16
0.18
0.20
0.23
0.24
0.26
0.29
0.29
0.29
0.29
0.31
0.33
0.33
0.34
0.36
34
43
57
78
95
116
140
170
200
225
255
285
325
370
435
481
537
28
37
48
61
80
94
110
140
165
185
210
235
270
305
350
405
470
30
40
53
70
99
117
140
176
221
258
294
339
402
461
542
624
723
44
55
74
94
120
145
170
210
250
285
315
355
410
460
520
580
680
37
47
61
78
100
120
145
175
210
240
270
300
350
390
440
480
575
39
50
67
85
125
155
190
235
290
330
375
435
510
590
670
750
875
in K. Amps
Al
Cu
0.376
0.564
0.940
1.50
2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
47.00
59.22
0.572
0.858
1.430
2.29
3.58
5.01
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
71.50
90.09
ote
ormal current ratings are given in standard conditions as given in page no - 40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42
20
TABLE - 16
Minimum o of
ominal
strands
Thickness of
in conductor
Insulation
Phase / eutral Phase / eutral
Al
Cu
mm
3X25 16
3X35 16
3X50 25
3X70 35
3X95 50
3X120 70
3X150 70
3X185 95
3X240 120
3X300 150
3X400 185
3X500 240
3X630 300
6/6
6/6
6/6
12/6
15/6
15/12
15/12
30/15
30/15
30/15
53/30
53/30
53/30
SS- SECTI
6/6
6/6
6/6
12/6
15/6
18/12
18/12
30/15
34/18
34/18
53/30
53/34
53/34
AL VIE
1
2
3
4
0.90/0.70
0.90/0.70
1.00/0.90
1.10/0.90
1.10/1.00
1.20/1.10
1.40/1.10
1.60/1.10
1.70/1.20
1.80/1.40
2.00/1.60
2.20/1.70
2.40/1.80
DUCT
Shape
mm
ominal
thickness of
UTE
Sheath
mm
Appro .
overall
Diameter
mm
0.30
0.30
0.30
0.40
0.40
0.40
0.50
0.50
0.60
0.60
0.70
0.70
0.70
2.00
2.00
2.00
2.20
2.20
2.20
2.40
2.60
2.80
3.00
3.40
3.60
4.00
22
24
27
31
34
38
43
46
52
57
65
73
82
Minimum
Thickness of
inner sheath
Appro . et t
of cable Kg/KM
ith Al cond
ith Cu Cond.
A2X
2X
600
700
900
1200
1500
1900
2300
2800
3600
4400
5600
7000
8900
1150
1450
2000
2700
3600
4500
5500
6800
8700
10800
14000
17500
22000
I SULATI
Crosslinked Polyethylene XLPE Phase - ed, ellow, Blue & neutral - Black colour
I E SHEATH PVC as per IS 7098PT-1
UTE SHEATH PVC T PE ST-2 F IS 5831
PTI
S F T PE F LS T PE
C L U
F UTE SHEATH BLACK . PTI
S any other colour as per requirement.
Tabulated appro . net wt. of cables are only guidelines for transportation, loading & unloading purpose.
Please ref page no 43 for normal delivery lengths & packing details.
ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM
20 C in hm/km
Al
Cu
90 C in hm/km
Al
Cu
in ohms/km
in microF/KM
3X25 16
1.20
0.727 1.54
0.931
0.080
0.20
3X35 16
0.868 0.524 1.11
0.671
0.080
0.23
3X50 25
0.641 0.387 0.820 0.495
0.078
0.24
3X70 35
0.443 0.268 0.567 0.343
0.077
0.26
3X95 50
0.320 0.193 0.411 0.248
0.074
0.29
3X120 70
0.253 0.153 0.325 0.197
0.072
0.29
3X150 70
0.206 0.1240 0.265 0.159
0.072
0.29
3X185 95
0.164 0.0991 0.211 0.127
0.072
0.29
3X240 120 0.125 0.0754 0.162 0.098
0.072
0.31
3X300 150 0.100 0.0601 0.130 0.078
0.071
0.33
3X400 185 0.0778 0.0470 0.1023 0.0618
0.070
0.33
3X500 240 0.0605 0.0366 0.0808 0.0489
0.070
0.34
3X630 300 0.0469 0.0283 0.0648 0.0391
0.069
0.36
ote
ormal current ratings are given in standard conditions as given in page no
multiplied by rating factor as given in page no. 42
95
116
140
170
200
225
255
285
325
370
435
481
537
- 40,41
80
94
110
140
165
185
210
235
270
305
350
405
470
, if site
Air
Ground
99
120
117
145
140
170
176
210
221
250
258
285
294
315
339
355
402
410
461
460
542
520
624
580
723
680
conditions are
Duct
Air
in K. Amps
Al
Cu
100 2.35
2.35
3.58
120 3.29
3.29
5.01
145 4.70
4.70
7.15
175 6.58
6.58
10.01
210 8.93
8.93
13.59
240 11.28
11.28
17.16
270 14.10
14.10
21.45
300 17.39
17.39
26.46
350 22.56
22.56
34.32
390 28.20
28.20
42.90
440 37.60
37.60
57.20
480 47.00
47.00
71.50
575 59.22
59.22
90.09
different, current rating should be
21
TABLE - 17
Minimum
o of
Strands in
Conductor
Al
Cu
1/7
1
1/7
1
6
6
6
6
6
6
6
6
6
12
12
15
15
15
18
15
18
30
30
30
34
30
34
53
53
53
53
53
53
SS- SECTI
AL VIE
1
2
3
4
ominal
Thickness
of
Insulation
mm
0.7
0.7
0.7
0.7
0.9
0.9
1.0
1.1
1.1
1.2
1.4
1.6
1.7
1.8
2.0
2.2
2.4
Minimum
Thickness
of
inner sheath
mm
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.40
0.40
0.50
0.50
0.50
0.60
0.70
0.70
0.70
0.70
Minimum
Thickness of
outer sheath
mm
1.80
1.80
1.80
1.80
2.00
2.00
2.00
2.20
2.20
2.40
2.60
2.80
3.00
3.20
3.60
3.80
4.00
Appro .
over all
Diameter
mm
17
18
20
20
24
26
29
34
37
41
45
50
56
63
70
79
88
Appro . et t
of cable Kg/KM
ith Al cond
ith Cu Cond.
A2X
2X
250
350
350
500
400
650
450
850
660
1300
800
1700
1000
2200
1400
3100
1700
4000
2150
5150
2650
6350
3250
7850
4100
10000
5050
12050
6400
16000
8000
20000
10000
26000
C
DUCT
Material - Aluminium /Copper
Shape AL . Cond - 6 & 10SQMM -Solid circular, 16sqmm & above Stranded compacted shaped
Copper . Cond - 4 & 6sqmm -solid/ stranded non compacted circular , 10sqmm Stranded compacted circular,16sqmm & above Stranded compacted
shaped
I SULATI
Crosslinked Polyethylene XLPE
I E SHEATH PVC as per IS 7098PT-1
UTE SHEATH PVC T PE ST-2 F IS 5831
C L U
F UTE SHEATH BLACK . PTI
Tabulated appro . net wt. of cables are only guidelines for transportation, loading & unloading purpose.
Please ref page no 43 for normal delivery lengths & packing details.
ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
4.61
3.08
1.91
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
5.90
3.94
2.44
1.54
1.11
0.820
0.567
0.411
0.325
0.265
0.211
0.162
0.130
0.1023
0.0808
0.0648
5.90
3.94
2.34
1.47
0.931
0.671
0.495
0.343
0.248
0.197
0.159
0.127
0.098
0.078
0.0618
0.0489
0.0391
0.098
0.090
0.084
0.080
0.080
0.080
0.078
0.077
0.074
0.072
0.072
0.072
0.072
0.071
0.070
0.070
0.069
0.11
0.13
0.16
0.18
0.20
0.23
0.24
0.26
0.29
0.29
0.29
0.29
0.31
0.33
0.33
0.34
0.36
34
43
57
78
95
116
140
170
200
225
255
285
325
370
435
481
537
28
37
48
61
80
94
110
140
165
185
210
235
270
305
350
405
470
30
40
53
70
99
117
140
176
221
258
294
339
402
461
542
624
723
44
55
74
94
120
145
170
210
250
285
315
355
410
460
520
580
680
37
47
61
78
100
120
145
175
210
240
270
300
350
390
440
480
575
39
50
67
85
125
155
190
235
290
330
375
435
510
590
670
750
875
in K. Amps
Al
Cu
0.376
0.564
0.940
1.50
2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
47.00
59.22
0.572
0.858
1.430
2.29
3.58
5.01
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
71.50
90.09
ote
ormal current ratings are given in standard conditions as given in page no - 40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42
22
TABLE - 18
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
C
Minimum
o of
Strands in
Conductor
Al
Cu
1
1
6
6
6
6
12
15
15
15
30
30
30
53
53
53
53
53
SS- SECTI
ominal
Thickness of
Insulation
mm
1/7
1/7
6
6
6
6
6
12
15
18
18
30
34
34
53
53
53
53
53
1.0
1.0
1.0
1.0
1.2
1.2
1.3
1.4
1.4
1.5
1.7
1.9
2.0
2.1
2.4
2.6
2.8
3.1
3.3
AL VIE
/A
/A
/A
/A
/A
/A
/A
/A
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
/A
/A
/A
/A
/A
/A
/A
/A
1.40
1.40
1.40
1.40
1.40
1.56
1.56
1.56
1.72
1.72
1.88
/A
/A
/A
/A
/A
/A
/A
/A
21
23
24
26
30
32
36
39
44
48
54
/A
/A
/A
/A
/A
/A
/A
/A
600
700
800
950
1200
1400
1750
2150
2700
3350
4100
/A
/A
/A
/A
/A
/A
/A
/A
1195
1450
1730
2100
2690
3270
4230
5250
6610
8320
10300
1.40
1.40
1.40
1.40
1.40
1.40
1.40
1.40
1.60
1.60
1.60
1.60
1.60
1.60
2.00
2.00
2.00
2.00
2.50
1.24
1.24
1.24
1.24
1.24
1.24
1.24
1.24
1.40
1.40
1.40
1.40
1.40
1.56
1.56
1.56
1.72
1.88
2.04
10
11
12
13
14
15
17
19
22
24
25
28
30
33
38
41
46
51
56
90
130
160
200
300
350
420
520
650
750
850
1000
1250
1500
1900
2350
2900
3600
4600
C
DUCT
Material - Aluminium /Copper
Shape AL . Cond - 6 & 10SQMM -Solid circular, 16 sqmm & above Stranded compacted shaped circular
I SULATI
Crosslinked Polyethylene XLPE
atural colour
A M U I G Single layer of Aluminium ound wires / Flat Strips
UTE SHEATH PVC T PE ST-2 F IS 5831
PTI
S PVC T PE
C L U
F UTE SHEATH BLACK . PTI
S any other colour as per requirement.
3
4
130
170
222
300
455
567
730
954
1235
1494
1780
2147
2738
3360
4380
5450
6806
8560
10800
Copper. Cond - 4 & 6sqmm -solid/ stranded non compacted circular , 10sqmm Stranded compacted circular
Tabulated appro . net wt. of cables are only guidelines for transportation, loading &unloading purpose ..
Please ref page no 43 for normal delivery lengths & packing details.
ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
4.61
3.08
1.91
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
0.0367
0.0291
4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
0.0221
0.0176
5.90
3.94
2.44
1.54
1.11
0.820
0.567
0.411
0.325
0.265
0.211
0.162
0.130
0.1023
0.0808
0.0648
0.0530
0.0444
5.90
3.94
2.34
1.47
0.931
0.671
0.495
0.343
0.248
0.197
0.159
0.127
0.0976
0.0778
0.0618
0.0489
0.0391
0.0319
0.0268
0.152
0.144
0.133
0.122
0.116
0.110
0.103
0.099
0.097
0.093
0.091
0.090
0.086
0.085
0.085
0.083
0.082
0.081
0.081
0.22
0.26
0.31
0.40
0.40
0.47
0.50
0.55
0.64
0.67
0.67
0.67
0.72
0.75
0.75
0.77
0.81
0.88
0.88
45
59
76
99
117
138
168
204
230
265
295
340
390
450
500
555
625
690
45
62
80
90
110
125
155
185
210
230
260
300
335
380
430
485
530
570
40
53
73
115
140
170
210
255
300
342
385
450
519
605
700
809
935
1065
48
60
80
104
130
155
185
225
265
300
335
380
435
490
550
610
680
740
780
47
59
78
102
115
140
165
200
235
265
300
335
385
430
480
530
590
630
660
45
57
77
106
145
175
215
270
330
380
430
495
590
670
780
900
1020
1140
1250
in K. Amps
Al
Cu
0.376
0.572
0.56
0.858
0.94
1.43
1.50
2.29
2.35
3.58
3.29
5.01
4.70
7.15
6.58
10.01
8.93
13.59
11.28
17.16
14.10
21.45
17.39
26.46
22.56
34.32
28.20
42.90
37.60
57.20
47.00
71.50
59.22
90.09
75.20 114.40
94.00 143.00
ote
ormal current ratings are given in standard conditions as given in page no - 40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42
23
TABLE - 19
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
Minimum
ominal Minimum
A M U I G ITH FLAT ST IP A2XF / 2XF
A M U I G ITH
U D I ES A2X
/ 2X
o of
Thickness Thickness
ominal
Minimum
Appro .
Appro . et t
ominal
Minimum
Appro .
Appro . et t
Strands in
of
Thickness Thickness of
verall
of cable Kg/KM
Diameter Thickness of
verall of cable Kg/KM
of
ith Al cond
ith Cu Cond.
of wire outer sheath Diameter ith Al cond ith Cu Cond.
Conductor Insulation inner Sh. of armour outer sheath Diameter
Al
Cu
mm
mm
mm
mm
A2XF
2XF
mm
mm
mm
A2X
2X
mm
1
1
6
6
6
6
12
15
15
15
30
30
30
53
53
53
SS- SECTI
1/7
1/7
6
6
6
6
6
12
15
18
18
30
34
34
53
53
53
0.7
0.7
0.7
0.7
0.9
0.9
1.0
1.1
1.1
1.2
1.4
1.6
1.7
1.8
2.0
2.2
2.4
AL VIE
1
2
3
4
5
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.40
0.40
0.40
0.50
0.50
0.60
0.60
0.70
0.70
/A
/A
/A
/A
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
/A
/A
/A
/A
1.40
1.40
1.40
1.56
1.56
1.56
1.72
1.72
1.88
2.04
2.36
2.52
2.68
/A
/A
/A
/A
20
21
23
26
29
31
34
37
42
45
50
55
63
/A
/A
/A
/A
650
750
900
1100
1350
1600
1900
2250
2800
3300
4100
5000
6100
/A
/A
/A
/A
950
1200
1500
1950
2500
3100
3750
4500
5800
7000
9050
11000
14000
1.40
1.40
1.40
1.40
1.60
1.60
1.60
1.60
2.00
2.00
2.00
2.00
2.50
2.50
2.50
3.15
3.15
1.24
1.24
1.24
1.40
1.40
1.40
1.40
1.56
1.56
1.56
1.72
1.88
2.04
2.20
2.36
2.68
2.84
15
16
18
19
21
23
25
28
31
34
37
40
45
49
52
60
66
500
550
650
700
850
950
1100
1400
1850
2150
2450
2900
3850
4450
5350
7100
8500
550
600
770
900
1150
1400
1700
2250
3000
3600
4300
5200
6800
8200
10300
13300
16300
C
DUCT
Material - Aluminium /Copper
Shape AL . Cond - 6 & 10SQMM -Solid circular, 16sqmm & above Stranded compacted shaped
Copper. Cond - 4 & 6 sqmm -solid/ stranded non compacted circular, 10 sqmm Stranded compacted circular,16sqmm & above Stranded compacted
shaped
I SULATI
Crosslinked Polyethylene XLPE
ed & Black colour
I E SHEATH PVC as per IS 7098PT-1
A M U I G Single layer of galvanized steel round wires / flat strips
UTE SHEATH PVC T PE ST-2 F IS 5831
PTI
S F T PE/ F LS T PE
C L U
F UTE SHEATH BLACK. PTI
S any other colour as per requirement.
Tabulated appro . net wt. of cables are only guidelines for transportation, loading &unloading purpose.
Please ref page no 43 for normal delivery lengths & packing details.
ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM
4
--4.61
--5.90
0.098
0.11
6
4.61
3.08
5.90
3.94
0.090
0.13
10
3.08
1.83
3.94
2.34
0.084
0.16
16
1.91
1.15
2.44
1.47
0.080
0.18
25
1.20
0.727 1.54
0.931
0.080
0.20
35
0.868 0.524 1.11
0.671
0.080
0.23
50
0.641 0.387 0.820 0.495
0.078
0.24
70
0.443 0.268 0.567 0.343
0.077
0.26
95
0.320 0.193 0.411 0.248
0.074
0.29
120
0.253 0.153 0.325 0.197
0.072
0.29
150
0.206 0.1240 0.265 0.159
0.072
0.29
185
0.164 0.0991 0.211 0.127
0.072
0.29
240
0.125 0.0754 0.162 0.0976
0.072
0.31
300
0.100 0.0601 0.130 0.0778
0.071
0.33
400
0.0778 0.0470 0.1023 0.0618
0.070
0.33
500
0.0605 0.0366 0.0808 0.0489
0.070
0.34
630
0.0469 0.0283 0.0648 0.0391
0.069
0.36
ote
ormal current ratings are given in standard conditions as given in page no
multiplied by rating factor as given in page no. 42
34
43
57
78
95
116
140
170
200
225
255
285
325
370
435
481
537
- 40,41
28
30
44
37
40
55
48
53
74
61
70
94
80
99
120
94
117
145
110
140
170
140 176
210
165 221
250
185 258
285
210 294
315
235 339
355
270 402
410
305 461
460
350 542
520
405 624
580
470 723
680
, if site conditions are
in K. Amps
Al
Cu
37
39
0.376
0.572
47
50
0.564
0.858
61
67
0.940
1.430
78
85
1.50
2.29
100 125
2.35
3.58
120 155
3.29
5.01
145 190
4.70
7.15
175 235
6.58
10.1
210 290
8.93
13.59
240 330
11.28
17.16
270 375
14.10
21.45
300 435
17.39
26.46
350 510
22.56
34.32
390 590
28.20
42.90
440 670
37.60
57.20
480 750
47.00
71.50
575 875
59.22
90.09
different, current rating should be
24
TABLE - 20
Minimum
ominal Minimum
A M U I G ITH FLAT ST IP A2XF / 2XF
A M U I G ITH
U D I ES A2X
/ 2X
o of
Thickness Thickness
ominal
Minimum
Appro .
Appro . et t
ominal
Minimum
Appro .
Appro . et t
Strands in
of
Thickness Thickness of
verall
of cable Kg/KM
Diameter Thickness of
verall of cable Kg/KM
of
ith Al cond
ith Cu Cond.
of wire outer sheath Diameter ith Al cond ith Cu Cond.
Conductor Insulation inner Sh. of armour outer sheath Diameter
Al
Cu
mm
strip mm
mm
mm
A2XF
2XF
mm
mm
mm
A2X
2X
mm
4
6
1
10
1
16
6
25
6
35
6
50
6
70
12
95
15
120
15
150
15
185
30
240
30
300
30
400
53
500
53
630
53
SS- SECTI
1/7
1/7
6
6
6
6
6
12
15
18
18
30
34
34
53
53
53
AL VIE
1
2
3
4
5
0.7
0.7
0.7
0.7
0.9
0.9
1.0
1.1
1.1
1.2
1.4
1.6
1.7
1.8
2.0
2.2
2.4
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.40
0.40
0.40
0.50
0.50
0.60
0.60
0.70
0.70
0.70
/A
/A
/A
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
/A
/A
/A
1.24
1.40
1.40
1.40
1.56
1.56
1.56
1.72
1.88
2.04
2.20
2.52
2.68
2.84
/A
/A
/A
19
21
23
26
29
32
35
42
44
49
54
60
66
74
/A
/A
/A
600
800
950
1100
1450
1750
2100
2500
3000
3750
4500
5600
6900
8550
/A
/A
/A
900
1200
1500
2000
2700
3500
4200
5200
6300
8200
10000
13000
16000
20000
1.40
1.40
1.40
1.60
1.60
1.60
1.60
2.00
2.00
2.00
2.00
2.50
2.50
2.50
3.15
3.15
4.00
1.24
1.24
1.24
1.40
1.40
1.40
1.56
1.56
1.56
1.72
1.88
2.04
2.20
2.36
2.68
2.84
3.00
18
19
20
20
23
25
29
32
35
39
43
48
53
58
65
72
81
600
650
750
800
1000
1200
1450
2000
2350
2750
3250
4200
5100
6000
7950
9500
12600
670
770
930
1100
1450
1850
2300
3300
4100
4900
6000
7500
9500
11300
15200
18500
23700
C
DUCT
Material - Aluminium /Copper
Shape AL . Cond - 6 & 10 SQMM -Solid circular, 16 sqmm & above Stranded compacted shaped
Copper. Cond - 4 & 6 sqmm -solid/ stranded non compacted circular, 10 sqmm Stranded compacted circular,16 sqmm & above Stranded compacted
shaped
I SULATI
Crosslinked Polyethylene XLPE ed, ellow, Blue
I E SHEATH PVC as per IS 7098PT-1
A M U I G Single layer of Galvanized steel ound wires / Flat Strips
UTE SHEATH PVC T PE ST-2 F IS 5831
PTI
S F T PE/ F LS T PE
C L U
F UTE SHEATH BLACK. PTI
S any other colour as per requirement.
Tabulated appro . net wt. of cables are only guidelines for transportation, loading & unloading purpose.
Please ref page no 43 for normal delivery lengths & packing details.
ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM
4
--4.61
--5.90
0.098
0.11
6
4.61
3.08
5.90
3.94
0.090
0.13
10
3.08
1.83
3.94
2.34
0.084
0.16
16
1.91
1.15
2.44
1.47
0.080
0.18
25
1.20
0.727 1.54
0.931
0.080
0.20
35
0.868 0.524 1.11
0.671
0.080
0.23
50
0.641 0.387 0.820 0.495
0.078
0.24
70
0.443 0.268 0.567 0.343
0.077
0.26
95
0.320 0.193 0.411
0.248
0.074
0.29
120
0.253 0.153 0.325 0.197
0.072
0.29
150
0.206 0.1240 0.265 0.159
0.072
0.29
185
0.164 0.0991 0.211
0.127
0.072
0.29
240
0.125 0.0754 0.162 0.0976
0.072
0.31
300
0.100 0.0601 0.130 0.0778
0.071
0.33
400
0.0778 0.0470 0.1023 0.0618
0.070
0.33
500
0.0605 0.0366 0.0808 0.0489
0.070
0.34
630
0.0469 0.0283 0.0648 0.0391
0.069
0.36
ote
ormal current ratings are given in standard conditions as given in page no
multiplied by rating factor as given in page no. 42
34
28
30
44
43
37
40
55
57
48
53
74
78
61
70
94
95
80
99
120
116
94
117
145
140
110
140
170
170
140
176
210
200
165
221
250
225
185
258
285
255
210
294
315
285
235
339
355
325
270
402
410
370
305
460
460
435
350
542
520
481
405
624
580
537
470
723
680
- 40,41 , if site conditions are
in K. Amps
Al
Cu
37
39
0.376
0.572
47
50
0.564
0.858
61
67
0.940
1.430
78
85
1.50
2.29
100 125
2.35
3.58
120 155
3.29
5.01
145 190
4.70
7.15
175 235
6.58
10.01
210 290
8.93
13.59
240 330
11.28
17.16
270 375
14.10
21.45
300 435
17.39
26.46
350 510
22.56
34.32
390 590
28.20
42.90
440 670
37.60
57.20
480 750
47.00
71.50
575 875
59.22
90.09
different, current rating should be
25
TABLE - 21
TECHNICAL DETAIL FOR HAVELLS 1.1 KV THREE AND HALF CORES, AL/CUCOPPER COND.,
XPLE INSULATED, GALVANIZED STEEL WIRE/STRIP ARMOURED CABLES
Cable Code 3.5 Core - A2XF / 2XF , A2X
/ 2X
ef Specification IS 7098PA T -1
PHYSICAL PARAMETERS
SI E
Cross-sectional
area
sqmm
3X25 16
3X35 16
3X50 25
3X70 35
3X95 50
3X120 70
3X150 70
3X185 95
3X240 120
3X300 150
3X400 185
3X500 240
3X630 300
C
Minimum
o of
Strands in
Conductor
Al
Cu
6/6
6/6
6/6
12/6
15/6
15/12
15/12
30/15
30/15
30/15
53/30
53/30
53/30
SS- SECTI
6/6
6/6
6/6
12/6
15/6
18/12
18/12
30/15
34/18
34/18
53/30
53/34
53/34
ominal
Thickness
of
Insulation
mm
0.90/0.70
0.90/0.70
1.00/0.90
1.10/0.90
1.10/1.00
1.20/1.10
1.40/1.10
1.60/1.10
1.70/1.20
1.80/1.40
2.00/1.60
2.20/1.70
2.40/1.80
AL VIE
1
C
2
3
4
5
Minimum
A M U I G ITH FLAT ST IP A2XF / 2XF
A M U I G ITH
U D I ES A2X
/ 2X
Thickness ominal Minimum
Appro .
Appro . et t
ominal
Minimum
Appro .
Appro . et t
of
Thickness Thickness of
verall
of cable Kg/KM Diameter Thickness of
verall
of cable Kg/KM
inner Sh. of Armr. outer sheath Diameter ith Al cond ith Cu Cond. of wire outer sheath Diameter ith Al cond ith Cu Cond.
mm Strip mm
mm
mm
A2XF
2XF
mm
mm
mm
A2X
2X
DUCT
0.30
0.30
0.30
0.40
0.40
0.40
0.50
0.50
0.60
0.60
0.70
0.70
0.70
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
1.40
1.40
1.40
1.56
1.56
1.72
1.72
1.88
2.04
2.20
2.52
2.68
3.00
23
25
28
32
35
39
43
47
53
57
66
74
82
900
1000
1200
1600
2000
2400
2800
3400
4300
5000
6400
7900
9900
1400
1800
2300
3200
4100
5100
6000
7400
9500
11500
14500
18000
23000
1.60
1.60
1.60
2.00
2.00
2.00
2.00
2.50
2.50
2.50
3.15
3.15
4.00
1.40
1.40
1.56
1.56
1.56
1.72
1.88
2.04
2.20
2.36
2.68
2.84
3.00
25
27
30
35
38
42
46
51
56
60
71
79
88
1100
1300
1600
2200
2600
3100
3600
4700
5700
6700
9000
11000
14500
1700
2000
2700
3700
4600
5700
6800
8700
10500
13000
17000
21500
28000
I SULATI
Crosslinked Polyethylene XLPE Phase, ed, ellow, Blue & eutral - Black Colour
I E SHEATH PVC as per IS 7098PT-1
A M U I G Single layer of Galvanized steel ound wires / Flat Strips
UTE SHEATH PVC T PE ST-2 F IS 5831
PTI
S F T PE/ F LS T PE
C L U
F UTE SHEATH BLACK . PTI
S any other colour as per requirement.
Tabulated appro . net wt. of cables are only guidelines for transportation, loading &unloading purpose.
Please ref page no 43 for normal delivery lengths & packing details.
ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM
3X25 16
3X35 16
3X50 25
3X70 35
3X95 50
3X120 70
3X150 70
3X185 95
3X240 120
3X300 150
3X400 185
3X500 240
3X630 300
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
1.54
1.11
0.820
0.567
0.411
0.325
0.265
0.211
0.162
0.130
0.1023
0.0808
0.0648
0.931
0.671
0.495
0.343
0.248
0.197
0.159
0.127
0.098
0.078
0.0618
0.0489
0.0391
0.080
0.080
0.078
0.077
0.074
0.072
0.072
0.072
0.072
0.071
0.070
0.070
0.069
0.20
0.23
0.24
0.26
0.29
0.29
0.29
0.29
0.31
0.33
0.33
0.34
0.36
95
116
140
170
200
225
255
285
325
370
435
481
537
80
94
110
140
165
185
210
235
270
305
350
405
470
99
117
140
176
221
258
294
339
402
461
542
624
723
120
145
170
210
250
285
315
355
410
460
520
580
680
100
120
145
175
210
240
270
300
350
390
440
480
575
125
155
190
235
290
330
375
435
510
590
670
750
875
Al
in K. Amps
Cu
2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
47.00
59.22
3.58
5.01
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
71.50
90.09
ote
ormal current ratings are given in standard conditions as given in page no -40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42
Testing Laboratory
26
TABLE - 22
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
Minimum
ominal Minimum
A M U I G ITH FLAT ST IP A2XF /2XF
A M U I G ITH
U D I ES A2X
/ 2X
o of
Thickness Thickness
ominal
Minimum
Appro .
Appro . et t
ominal
Minimum
Appro .
Appro . et t
of
Strands in
of
Thickness Thickness of
verall
of cable Kg/KM
Diameter Thickness of
verall of cable Kg/KM
Conductor Insulation inner Sh. of armour outer sheath Diameter
ith Al cond
ith Cu Cond.
of wire outer sheath Diameter ith Al cond ith Cu Cond.
Al
Cu
mm
strip mm
mm
mm
A2XF
2X F
mm
mm
mm
A2X
2X
mm
1
1
6
6
6
6
12
15
15
15
30
30
30
53
53
53
SS- SECTI
1/7
1/7
6
6
6
6
6
12
15
18
18
30
34
34
53
53
53
0.7
0.7
0.7
0.7
0.9
0.9
1.0
1.1
1.1
1.2
1.4
1.6
1.7
1.8
2.0
2.2
2.4
AL VIE
1
2
3
4
5
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.40
0.40
0.50
0.50
0.50
0.60
0.70
0.70
0.70
0.70
/A
/A
/A
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
/A
/A
/A
1.40
1.40
1.40
1.56
1.56
1.56
1.72
1.88
2.04
2.20
2.36
2.68
2.84
3.00
/A
/A
/A
20
24
27
30
34
37
41
46
51
57
63
71
79
88
/A
/A
/A
700
900
1100
1400
1800
2200
2700
3200
3900
4850
5850
7320
9000
11000
/A
/A
/A
1100
1500
2000
2500
3400
4400
5600
6800
8300
10500
13000
17000
21000
27000
1.40
1.40
1.40
1.60
1.60
1.60
1.60
2.00
2.00
2.00
2.50
2.50
2.50
3.15
3.15
4.00
4.00
1.24
1.24
1.40
1.40
1.40
1.40
1.56
1.56
1.72
1.88
2.04
2.20
2.36
2.52
2.84
3.00
3.00
18
19
21
22
26
28
32
37
40
44
49
54
65
68
76
86
94
550
600
670
925
1200
1450
1750
2400
2900
3500
4500
5200
6400
8300
10000
13500
16000
650
750
950
1300
1770
2200
2850
4000
5150
6300
8000
9700
12000
15400
19500
25000
30500
C
DUCT
Material - Aluminium /Copper
Shape AL . Cond - 6 & 10 SQMM -Solid circular, 16 sqmm & above Stranded compacted shaped
Copper. Cond - 4 & 6 sqmm -solid/ stranded non compacted circular, 10 sqmm Stranded compacted circular,16 sqmm & above Stranded compacted
shaped
I SULATI
Crosslinked Polyethylene XLPE
ed, ellow, Blue & Black
I E SHEATH PVC as per IS 7098PT-1
A M U I G Single layer of Galvanized steel ound wires / Flat Strips
UTE SHEATH PVC T PE ST-2 F IS 5831
PTI
S F T PE/ F LS T PE
C L U
F UTE SHEATH BLACK. PTI
S any other colour as per requirement.
Tabulated appro . net wt. of cables are only guidelines for transportation, loading &unloading purpose.
Please ref page no 43 for normal delivery lengths & packing details.
ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
4.61
3.08
1.91
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
5.90
3.94
2.44
1.54
1.11
0.820
0.567
0.411
0.325
0.265
0.211
0.162
0.130
0.1023
0.0808
0.0648
5.90
3.94
2.34
1.47
0.931
0.671
0.495
0.343
0.248
0.197
0.159
0.127
0.0976
0.0778
0.0618
0.0489
0.0391
0.098
0.090
0.084
0.080
0.080
0.080
0.078
0.077
0.074
0.072
0.072
0.072
0.072
0.071
0.070
0.070
0.069
0.11
0.13
0.16
0.18
0.20
0.23
0.24
0.26
0.29
0.29
0.29
0.29
0.31
0.33
0.33
0.34
0.36
34
43
57
78
95
116
140
170
200
225
255
285
325
370
435
481
537
28
37
48
61
80
94
110
140
165
185
210
235
270
305
350
405
470
30
40
53
70
99
117
140
176
221
258
294
339
402
460
542
624
723
44
55
74
94
120
145
170
210
250
285
315
355
410
460
520
580
680
37
47
61
78
100
120
145
175
210
240
270
300
350
390
440
480
575
39
50
67
85
125
155
190
235
290
330
375
435
510
590
670
750
875
in K. Amps
Al
Cu
0.376
0.564
0.940
1.50
2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
47.00
59.22
0.572
0.858
1.430
2.29
3.58
5.01
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
71.50
90.09
ote
ormal current ratings are given in standard conditions as given in page no - 40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42
27
TABLE - 23
ominal
Insulation
thickness
mm
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.8
2.8
3.0
3.3
3.5
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
C
SS- SETI
AL VIE
1
DUCT
A M U I G
UTE
Minimum Thickness
of uter Sheath
mm
1.40
1.40
1.40
1.60
1.60
1.60
1.60
1.60
1.60
1.60
2.00
2.00
2.00
2.00
2.50
1.24
1.24
1.40
1.40
1.40
1.40
1.40
1.40
1.56
1.56
1.56
1.56
1.72
1.88
2.04
MATE IAL C
Appro .
cable wt kg /km
ith Al.
ith Cu
Cond.
Cond.
350
500
400
600
500
800
650
1100
750
1350
850
1600
950
1900
1100
2250
1350
2850
1550
3400
2000
4500
2400
5500
3000
6900
3650
8600
4500
10700
C L U
Appro .
ver all
Diameter
mm
18
19
21
23
25
26
28
29
32
34
39
42
47
52
56
I SULATI
3
ominal Diameter
of Armour ire
mm
UTE
ound wires.
F IS 5831
SHEATH BLACK .
PTI
PTI
S
S PVC T PE ST-2/ F
THE
C L U S AS PE
T PE/ F LS T PE
EQUI EME T
Tabulated appro . net weights of cables are only for guidelines for transportation / loading/ unloading purpose.
ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
0.0367
0.0291
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
0.0221
0.0176
1.54
1.11
0.820
0.567
0.410
0.325
0.265
0.211
0.162
0.130
0.1023
0.0808
0.0648
0.0530
0.0444
0.931
0.671
0.495
0.343
0.248
0.197
0.159
0.127
0.098
0.078
0.0618
0.0489
0.0391
0.0319
0.0268
0.133
0.126
0.122
0.116
0.111
0.106
0.103
0.100
0.097
0.095
0.093
0.091
0.090
0.088
0.086
Capecitance
of cable
in microF/KM
Appro .
0.25
0.29
0.33
0.38
0.44
0.49
0.53
0.58
0.67
0.73
0.84
0.86
0.88
0.94
0.99
100
120
140
175
205
235
260
295
340
385
440
495
560
620
670
91
110
125
155
185
210
230
260
300
335
380
430
485
530
570
110
135
165
210
255
295
335
390
460
530
620
730
840
960
1070
130
155
185
225
265
300
335
380
435
490
550
610
680
740
780
115
140
165
200
235
265
300
335
385
430
480
530
590
630
660
145
175
215
270
330
380
430
495
590
670
780
900
1020
1140
1250
in K. Amps
Al
Cu
2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
47.00
59.22
75.20
94.00
3.58
5.00
7.15
10.00
13.59
17.16
21.45
26.45
34.32
42.90
57.20
71.50
90.10
114.40
143.00
ote
ormal current ratings are given in standard conditions as given in page no - 40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42
28
TABLE - 24
25
35
50
70
95
120
150
185
240
300
400
C
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
0.3
0.3
0.4
0.4
0.4
0.5
0.5
0.5
0.6
0.6
0.7
SS- SECTI
AL VIE
1
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
1.40
1.56
1.56
1.56
1.72
1.72
1.88
2.04
2.20
2.20
2.36
DUCT
I SULATI
I
A M U I G
1100
1300
1500
1800
2150
2500
2850
3350
4100
4750
5750
1550
1950
2450
3100
3900
4750
5650
6800
8550
10350
13200
1.60
1.60
2.00
2.00
2.00
2.00
2.50
2.50
2.50
2.50
3.15
1.56
1.56
1.56
1.56
1.72
1.88
2.04
2.04
2.20
2.36
2.68
I ES A M U ED
Appro .
cable wt kg /km
ith Al.
ith Cu
Cond.
Cond.
30
33
35
38
42
45
48
51
56
60
67
1450
1600
2100
2400
2850
3300
4100
4650
5450
6300
8350
1900
2250
3050
3700
4600
5550
6900
8100
9900
11900
15800
28
31
33
36
39
42
44
48
52
56
62
U D
ominal
Minimum
Appro .
diameter outer Sheath
ver all
of armour thickness
Diameter
wire mm
mm
mm
UTE
C L U
UTE
F IS 5831
SHEATH BLACK.
PTI
PTI
S
T PE/ F LS T PE
Tabulated appro . net wt. of cables are only guidelines for transportation, loading &unloading purpose.
Please ref page no 43 for normal delivery lengths & packing details.
ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM
25
35
50
70
95
120
150
185
240
300
400
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
1.54
1.11
0.820
0.567
0.410
0.325
0.265
0.211
0.162
0.130
0.1023
0.931
0.671
0.495
0.343
0.248
0.197
0.159
0.127
0.098
0.078
0.0618
0.098
0.094
0.086
0.084
0.081
0.078
0.076
0.075
0.073
0.072
0.071
0.25
0.29
0.33
0.38
0.44
0.49
0.53
0.58
0.67
0.73
0.84
94
115
135
165
195
220
245
280
320
360
410
80
95
110
140
165
185
210
235
270
305
350
99
120
145
185
225
255
295
340
400
460
535
120
145
170
210
250
285
315
355
410
460
520
100
120
145
175
210
240
270
300
350
390
440
125
155
190
235
290
330
375
435
510
590
670
in K. Amps
Al
Cu
2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
3.58
5.00
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
ote
ormal current ratings are given in standard conditions as given in page no - 40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42
29
TABLE - 25
SS- SECTI
ominal
Insulation
thickness
mm
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
3.0
3.3
3.5
3.5
3.5
3.6
Minimum
Inner Sheath
thickness
mm
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.4
0.4
0.4
0.5
0.5
0.5
0.5
ominal Diameter
of Armour ire
mm
Minimum Thickness
of uter Sheath
mm
1.60
1.60
1.60
1.60
1.60
1.60
1.60
1.60
2.00
2.00
2.00
2.00
2.00
2.50
2.50
1.40
1.40
1.40
1.40
1.40
1.40
1.56
1.56
1.56
1.56
1.72
1.72
1.88
2.04
2.20
Appro .
ver all
Diameter
mm
23
24
25
27
28
30
32
34
37
39
44
47
51
57
61
Appro .
cable wt kg /km
ith Al.
ith Cu
Cond.
Cond.
600
750
650
850
700
1000
800
1250
950
1550
1050
1800
1200
2100
1400
2550
1700
3200
2000
3850
2450
4900
2800
5900
3400
7300
4300
9200
5100
11300
AL VIE
1
DUCT
I SULATI
MATE IAL C
I SULATI
SC EE I G E truded semiconducting compound followed by helically wrapped 0.050mm thick copper tape.
4
5
6
7
PTI
S A
EQUI EME T
Tabulated appro . net weights of cables are only for guidelines for transportation / Loading/ Unloading Purpose.
ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
0.0367
0.0291
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
0.0221
0.0176
1.54
1.11
0.820
0.567
0.410
0.325
0.265
0.211
0.162
0.130
0.1023
0.0808
0.0648
0.0530
0.0444
0.931
0.671
0.495
0.343
0.248
0.197
0.159
0.127
0.098
0.078
0.0618
0.0489
0.0391
0.0319
0.0268
0.149
0.142
0.133
0.127
0.121
0.116
0.113
0.109
0.105
0.104
0.102
0.100
0.096
0.094
0.092
0.21
0.24
0.27
0.31
0.36
0.39
0.43
0.47
0.53
0.54
0.57
0.60
0.67
0.76
0.82
100
120
140
175
205
235
260
295
340
385
440
495
560
620
680
90
105
125
155
180
205
230
260
300
335
380
430
480
530
580
120
145
170
215
260
305
345
395
470
540
630
730
840
960
1070
130
155
185
225
265
300
335
380
435
490
550
610
680
740
790
115
140
160
195
235
265
295
330
380
425
480
530
580
630
670
155
185
220
275
340
390
440
510
600
680
790
910
1030
1140
1250
in K. Amps
Al
Cu
2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
47.00
59.22
75.20
94.00
3.58
5.00
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
71.50
90.10
114.40
143.00
ote
ormal current ratings are given in standard conditions as given in page no - 40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no.. 42
30
TABLE - 26
25
35
50
70
95
120
150
185
240
300
400
C
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
3.0
3.3
SS- SECTI
0.4
0.4
0.5
0.5
0.5
0.6
0.6
0.6
0.7
0.7
0.7
AL VIE
1 C
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
1.56
1.72
1.72
1.88
1.88
2.04
2.20
2.20
2.36
2.52
2.84
DUCT
37
39
42
46
50
54
58
61
67
72
82
1800
2000
2300
2800
3300
3800
4300
4800
5900
6800
8500
U D
ominal
Minimum
Appro .
diameter outer Sheath
ver all
of armour thickness
Diameter
wire mm
mm
mm
2250
2650
3250
4100
5050
6050
7100
8250
10350
12400
15950
2.00
2.00
2.00
2.00
2.50
2.50
2.50
2.50
3.15
3.15
4.00
1.72
1.72
1.88
1.88
2.04
2.20
2.20
2.36
2.52
2.68
3.00
40
42
45
49
54
58
61
65
72
77
88
I ES A M U ED
Appro .
cable wt kg /km
ith Al.
ith Cu
Cond.
Cond.
2500
2800
3200
3700
4700
5400
5900
6600
8400
9700
13000
2950
3450
4150
5000
6450
7650
8700
10050
12850
15300
20450
SC EE I G E truded semiconducting compound followed by helically wrapped 0.050mm thick copper tape.
5 PVC FILLE S
6 I
E SHEATH E truded PVC
7
A M U I G Single layer of Galvanized Flat strip/
8
ound wires.
PTI
C L U
F UTE SHEATH BLACK . PTI
S A
THE C L U S AS PE
EQUI EME T
Tabulated appro . net weights of cables are only for guidelines for transportation / Loading/ Unloading Purpose.
ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM
Capecitance
of cable
in microF/KM
APP
X.
25
1.20
0.727 1.54
0.931
0.126
0.21
95
82
105
120
35
0.868 0.524 1.11
0.671
0.120
0.24
115
97
125
145
50
0.641 0.387 0.820
0.495
0.114
0.27
130
115
150
170
70
0.443 0.268 0.567
0.343
0.107
0.31
160
140
190
210
95
0.320 0.193 0.410
0.248
0.102
0.36
190
165
230
250
120
0.253 0.153 0.325
0.197
0.098
0.39
220
190
260
280
150
0.206 0.1240 0.265
0.159
0.095
0.43
245
210
295
310
185
0.164 0.0991 0.211
0.127
0.093
0.47
275
240
335
350
240
0.125 0.0754 0.162
0.098
0.090
0.53
315
275
395
400
300
0.100 0.0601 0.130
0.078
0.090
0.54
355
310
450
445
400
0.0778 0.0470 0.1023 0.0618
0.087
0.57
400
350
520
500
ote
ormal current ratings are given in standard conditions as given in page no - 40,41 , if site conditions are
multiplied by rating factor as given in page no. 42
in K. Amps
Al
Cu
105 135
2.35
3.58
125 165
3.29
5.01
150 195
4.70
7.15
180 240
6.58
10.01
215 295
8.93
13.59
240 335
11.28
17.16
270 380
14.10
21.45
305 430
17.39
26.46
350 500
22.56
34.32
390 570
28.20
42.90
440 650
37.60
57.20
different, current rating should be
31
TABLE - 27
TECHNICAL DETAIL FOR HAVELLS 6.6/6.6KV & 6.35/11 KV SINGLE CORE, AL/COPPER COND.,
XLPE INSULATED, ARMOURED CABLES
6.6KV -U EA THED
PHYSICAL PARAMETERS
SI E
cross-Sectional
area Sqmm
ominal
Insulation
thickness
mm
Minimum
Inner Sheath
thickness
mm
ominal Diameter
of Armour ire
mm
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.4
0.4
0.4
0.5
0.5
0.5
0.5
0.5
1.60
1.60
1.60
1.60
1.60
1.60
1.60
2.00
2.00
2.00
2.00
2.00
2.00
2.50
2.50
SS- SECTI
ef Specification IS 7098PA T -2
Minimum Thickness
of uter Sheath
mm
Appro .
ver all
Diameter
mm
1.40
1.40
1.40
1.40
1.40
1.56
1.56
1.56
1.56
1.56
1.72
1.72
1.88
2.04
2.20
Appro .
cable wt kg /km
ith Al.
ith Cu
Cond.
Cond.
24
25
26
28
30
32
33
36
39
41
44
47
51
57
61
650
700
800
900
1050
1200
1300
1600
1850
2050
2500
2900
3450
4300
5100
800
900
1100
1300
1650
1950
2200
2750
3350
3900
5000
6000
7350
9250
11300
AL VIE
1
DUCT
I SULATI
MATE IAL C
I SULATI
SC EE I G E truded semiconducting compound followed by helically wrapped 0.050mm thick copper tape.
4
5
6
7
PTI
S A
EQUI EME T
Tabulated appro . net weights of cables are only for guidelines for transportation / Loading/ Unloading Purpose.
ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
0.0367
0.0291
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
0.0221
0.0176
1.54
1.11
0.820
0.567
0.410
0.325
0.265
0.211
0.162
0.130
0.1023
0.0808
0.0648
0.0530
0.0444
0.931
0.671
0.495
0.343
0.248
0.197
0.159
0.127
0.098
0.078
0.0618
0.0489
0.0391
0.0319
0.0268
0.164
0.156
0.147
0.139
0.133
0.127
0.124
0.120
0.117
0.113
0.110
0.107
0.104
0.100
0.098
Capecitance
of cable
in microF/KM
Appro
0.18
0.20
0.22
0.26
0.29
0.32
0.35
0.38
0.43
0.46
0.53
0.59
0.66
0.74
0.82
100
120
140
175
205
235
260
295
340
385
440
495
560
620
680
90
105
125
155
180
205
230
260
300
335
380
430
480
530
580
120
145
170
215
260
305
345
395
470
540
630
730
840
960
1070
130
155
185
225
265
300
335
380
435
490
550
610
680
740
790
115
140
160
195
235
265
295
330
380
425
480
530
580
630
670
155
185
220
275
340
390
440
510
600
680
790
910
1030
1140
1250
in K. Amps
Al
Cu
2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
47.00
59.22
75.20
94.00
3.58
5.00
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
71.50
90.10
114.40
143.00
ote ormal current ratings are given in standard conditions as given in page no -40,41 , if site conditions are different, current rating should be multiplied
by rating factor as given in page no. 42
32
TABLE - 28
TECHNICAL DETAIL FOR HAVELLS 6.6/6.6KV & 6.35/11 KV THREE CORES, AL/COPPER COND.,
XLPE INSULATED, ARMOURED CABLES
Cable Code A2XF / 2XF , A2X
/2X
6.6KV UE / 11KV E
ef Specification IS 7098PA T-2
PHYSICAL PARAMETERS
FLAT ST IP A M U ED
SI E
ominal
Minimum
ominal
Minimum
Appro .
crossInsulation Inner Sheath Armour strip outer Sheath
ver all
sectional thickness thickness
thickness
thickness
Diameter
area Sqmm
mm
mm
mm
mm
mm
25
35
50
70
95
120
150
185
240
300
400
C
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
SS- SECTI
0.4
0.5
0.5
0.5
0.6
0.6
0.6
0.7
0.7
0.7
0.7
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
1.72
1.72
1.88
1.88
2.04
2.20
2.20
2.36
2.52
2.68
2.84
41
43
46
50
54
58
61
65
71
75
83
Appro .
cable wt kg /km
ith Al.
ith Cu
Cond.
Cond.
2100
2350
2700
3100
3700
4200
4700
5300
6300
7200
8700
U D I ES A M U ED
ominal
Minimum
Appro .
Appro .
diameter outer Sheath
ver all
cable wt kg /km
of armour thickness
Diameter
ith Al.
ith Cu
wire mm
mm
mm
Cond.
Cond.
2550
2950
3650
4400
5450
6450
7500
8750
10750
12800
16150
2.00
2.00
2.50
2.50
2.50
2.50
2.50
3.15
3.15
3.15
4.00
1.72
1.88
2.04
2.04
2.20
2.20
2.36
2.52
2.68
2.84
3.00
43
46
50
54
58
62
65
70
76
80
90
2800
3200
4000
4500
5200
5800
6400
7900
9000
10000
13500
3250
3850
4950
5800
6950
8050
9200
11350
13500
15600
20500
AL VIE
1 C
DUCT
MATE IAL C
4 I SULATI
SC EE I G E truded semiconducting compound followed by helically wrapped 0.050mm thick copper tape.
5 PVC FILLE S
6 I
7
8
PTI
C L U
F UTE SHEATH BLACK . PTI
S A
THE C L U S AS PE
EQUI EME T
Tabulated appro . net weights of cables are only for guidelines for transportation / Loading/ Unloading Purpose.
ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM
25
35
50
70
95
120
150
185
240
300
400
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
1.54
1.11
0.820
0.567
0.410
0.325
0.265
0.211
0.162
0.130
0.1023
0.931
0.671
0.495
0.343
0.248
0.197
0.159
0.127
0.098
0.078
0.0618
eactance
at 50H
in ohms/km
APP
X.
0.133
0.126
0.118
0.116
0.107
0.102
0.099
0.097
0.084
0.093
0.089
App. Capecitance
ormal Current ating in Amps
of cable
ith Aluminium cond.
ith Copper cond.
in microF/KM
Ground Duct
Air
Ground Duct
Air
APP
X.
0.18
0.20
0.22
0.26
0.29
0.32
0.35
0.38
0.43
0.46
0.53
95
115
130
160
190
220
245
275
315
355
400
82
97
115
140
165
190
210
240
275
310
350
105
125
150
190
230
260
295
335
395
450
520
120
145
170
210
250
280
310
350
400
445
500
105
125
150
180
215
240
270
305
350
390
440
135
165
195
240
295
335
380
430
500
570
650
in K. Amps
Al
Cu
2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
3.58
5.01
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
ote
ormal current ratings are given in standard conditions as given in page no -40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42
33
TABLE - 29
SS- SECTI
ominal
Insulation
thickness
mm
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
Minimum
Inner Sheath
thickness
mm
0.3
0.3
0.3
0.3
0.3
0.4
0.4
0.4
0.4
0.4
0.5
0.5
0.5
0.6
0.6
ominal Diameter
of Armour ire
mm
Minimum Thickness
of uter Sheath
mm
1.60
1.60
1.60
1.60
1.60
2.00
2.00
2.00
2.00
2.00
2.00
2.50
2.50
2.50
2.50
1.40
1.40
1.56
1.56
1.56
1.56
1.56
1.56
1.72
1.72
1.88
1.88
2.04
2.20
2.20
Appro .
ver all
Diameter
mm
28
29
31
33
34
37
38
40
43
44
48
53
56
61
65
Appro .
cable wt kg /km
ith Al.
ith Cu
Cond.
Cond.
900
1050
950
1150
1100
1400
1200
1650
1400
2000
1600
2350
1700
2600
1900
3050
2200
3700
2500
4350
2900
5400
3500
6600
4100
8000
4900
9900
5700
11900
AL VIE
1
DUCT
I SULATI
MATE IAL C
I SULATI
SC EE I G E truded semiconducting compound followed by helically wrapped 0.050mm thick copper tape.
4
5
6
7
PTI
S A
EQUI EME T
Tabulated appro . net weights of cables are only for guidelines for transportation / Loading/ Unloading Purpose.
ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
0.0367
0.0291
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
0.0221
0.0176
1.54
1.11
0.820
0.567
0.410
0.325
0.265
0.211
0.162
0.130
0.1023
0.0808
0.0648
0.0530
0.0444
0.931
0.671
0.495
0.343
0.248
0.197
0.159
0.127
0.098
0.078
0.0618
0.0489
0.0391
0.0319
0.0268
0.164
0.156
0.147
0.139
0.132
0.126
0.124
0.120
0.116
0.112
0.109
0.105
0.102
0.097
0.096
Capecitance
of cable
in microF/KM
Appro .
0.14
0.16
0.17
0.20
0.21
0.23
0.25
0.26
0.29
0.32
0.35
0.39
0.43
0.50
0.56
100
120
140
175
205
235
260
295
340
385
440
495
560
620
680
90
105
125
155
180
205
230
260
300
335
380
430
480
530
580
120
145
170
215
260
305
345
395
470
540
630
730
840
960
1070
130
155
185
225
265
300
335
380
435
490
550
610
680
740
790
115
140
160
195
235
265
295
330
380
425
480
530
580
630
670
155
185
220
275
340
390
440
510
600
680
790
910
1030
1140
1250
in K. Amps
Al
Cu
2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
47.00
59.22
75.20
94.00
3.58
5.00
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
71.50
90.10
114.40
143.00
ote
ormal current ratings are given in standard conditions as given in page no - 40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42
34
TABLE - 30
25
5.5
0.5
35
5.5
0.5
50
5.5
0.6
70
5.5
0.6
95
5.5
0.6
120
5.5
0.7
150
5.5
0.7
185
5.5
0.7
240
5.5
0.7
300
5.5
0.7
400
5.5
0.7
C
SS- SETI
AL VIE
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
1 C
1.88
2.04
2.20
2.20
2.36
2.52
2.52
2.68
2.84
3.00
3.00
DUCT
50
53
56
60
64
68
71
75
81
85
93
3000
3200
3700
4100
4800
5400
5900
6500
7600
8600
10000
3500
3850
4600
5400
6567
7632
8690
9950
12050
14200
17500
U D
ominal
Minimum
Appro .
diameter outer Sheath
ver all
of armour thickness
Diameter
wire mm
mm
mm
2.50
2.50
2.50
2.50
3.15
3.15
3.15
3.15
3.15
4.00
4.00
2.04
2.20
2.20
2.36
2.52
2.52
2.68
2.84
3.00
3.00
3.00
I ES A M U ED
Appro .
cable wt kg /km
ith Al.
ith Cu
Cond.
Cond.
54
57
60
64
69
73
76
80
85
91
98
4300
4700
5100
5800
7300
8000
8600
9400
11000
13000
15000
4750
5350
6050
7100
9100
10250
11400
12850
15500
18600
22450
SC EE I G E truded semiconducting compound followed by helically wrapped 0.050mm thick copper tape.
5 PVC FILLE S
6 I
7
A M U I G
8
PTI
C L U
F UTE SHEATH BLACK . PTI
S A
THE C L U S AS PE
EQUI EME T
Tabulated appro . net weights of cables are only for guidelines for transportation / Loading/ Unloading Purpose.
ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM
25
35
50
70
95
120
150
185
240
300
400
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
1.54
1.11
0.820
0.567
0.410
0.325
0.265
0.211
0.162
0.130
0.1023
0.931
0.671
0.495
0.343
0.248
0.197
0.159
0.127
0.0976
0.0778
0.0618
0.145
0.138
0.129
0.124
0.116
0.112
0.108
0.105
0.102
0.0999
0.0954
0.14
0.16
0.17
0.20
0.21
0.23
0.25
0.26
0.29
0.32
0.35
95
115
130
160
190
220
245
275
315
355
400
82
97
115
140
165
190
210
240
275
310
350
105
125
150
190
230
260
295
335
395
450
520
120
145
170
210
250
280
310
350
400
445
500
105
125
150
180
215
240
270
305
350
390
440
135
165
195
240
295
335
380
430
500
570
650
in K. Amps
Al
Cu
2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
3.58
5.01
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
ote
ormal current ratings are given in standard conditions as given in page no - 40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42
Production in process. . .
35
TABLE - 31
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
SS- SECTI
ominal
Insulation
thickness
mm
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
AL VIE
Minimum
Inner Sheath
thickness
mm
0.3
0.3
0.3
0.3
0.4
0.4
0.4
0.4
0.4
0.4
0.5
0.5
0.5
0.6
0.6
ominal Diameter
of Armour ire
mm
Minimum Thickness
of uter Sheath
mm
1.60
1.60
1.60
1.60
2.00
2.00
2.00
2.00
2.00
2.00
2.00
2.50
2.50
2.50
2.50
1.40
1.40
1.56
1.56
1.56
1.56
1.56
1.56
1.72
1.72
1.88
1.88
2.04
2.20
2.36
3
4
5
6
7
DUCT
Appro .
ver all
Diameter
mm
29
31
32
34
36
38
39
41
44
46
50
53
57
62
66
Appro .
cable wt kg /km
ith Al.
ith Cu
Cond.
Cond.
950
1100
1050
1250
1150
1500
1300
1750
1600
2200
1700
2450
1800
2750
2000
3150
2300
3800
2600
4500
3000
5500
3600
6700
4300
8200
5000
9950
5800
12000
I SULATI
MATE IAL C
I SULATI
SC EE I G E truded semiconducting compound followed by helically wrapped 0.050mm thick copper tape.
PTI
S A
EQUI EME T
Tabulated appro . net weights of cables are only for guidelines for transportation / Loading/ Unloading Purpose.
ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
0.0367
0.0291
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
0.0221
0.0176
1.54
1.11
0.820
0.567
0.410
0.325
0.265
0.211
0.162
0.130
0.1023
0.0808
0.0648
0.0530
0.0444
0.931
0.671
0.495
0.343
0.248
0.197
0.159
0.127
0.098
0.078
0.0618
0.0489
0.0391
0.0319
0.0268
0.166
0.158
0.149
0.140
0.134
0.130
0.126
0.122
0.118
0.113
0.110
0.107
0.103
0.0997
0.097
0.13
0.15
0.16
0.18
0.20
0.22
0.23
0.25
0.27
0.30
0.32
0.36
0.40
0.46
0.52
100
120
140
170
200
225
250
280
315
345
385
415
450
485
510
90
105
120
150
175
195
215
240
275
300
330
360
385
415
435
120
145
175
220
265
300
340
385
450
500
570
640
720
790
850
130
155
180
215
255
285
310
345
390
420
455
480
510
540
550
115
135
155
190
220
245
270
300
335
360
395
415
440
460
475
155
185
225
280
335
380
430
485
560
620
690
750
820
840
940
in K. Amps
Al
Cu
2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
47.00
59.22
75.20
94.00
3.58
5.00
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
71.50
90.10
114.40
143.00
ote
ormal current ratings are given in standard conditions as given in page no- 40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42
36
TABLE - 32
25
35
50
70
95
120
150
185
240
300
400
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
SS- SECTI
0.5
0.6
0.6
0.6
0.7
0.7
0.7
0.7
0.7
0.7
0.7
AL VIE
1 C
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
2.04
2.04
2.20
2.36
2.36
2.52
2.68
2.68
2.84
3.00
3.00
DUCT
53
56
59
63
67
70
74
77
83
88
95
3200
3500
3900
4400
5000
5700
6200
6800
7900
8900
10500
U D
ominal
Minimum
Appro .
diameter outer Sheath
ver all
of armour thickness
Diameter
wire mm
mm
mm
3650
4150
4850
5700
6800
7950
9000
10250
12350
14500
17950
2.50
2.50
2.50
2.50
3.15
3.15
3.15
3.15
4.00
4.00
4.00
2.20
2.20
2.36
2.36
2.52
2.68
2.68
2.84
3.00
3.00
3.00
I ES A M U ED
Appro .
cable wt kg /km
ith Al.
ith Cu
Cond.
Cond.
56
59
61
65
72
75
78
83
90
93
102
4600
5000
5400
6100
7600
8300
9000
9800
12500
13500
15500
5050
5650
6350
7400
9350
10550
11800
13250
16950
19100
22950
MATE IAL C
4 I SULATI
SC EE I G E truded semiconducting compound followed by helically wrapped 0.050mm thick copper tape.
5 PVC FILLE S
6 I
E SHEATH E truded PVC
7
A M U I G Single layer of Galvanized Flat strip/
8
ound wires.
PTI
C L U
F UTE SHEATH BLACK . PTI
S A
THE C L U S AS PE
EQUI EME T
Tabulated appro . net weights of cables are only for guidelines for transportation / Loading/ Unloading Purpose.
ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM
25
35
50
70
95
120
150
185
240
300
400
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
1.54
1.11
0.820
0.567
0.410
0.325
0.265
0.211
0.162
0.130
0.1023
0.931
0.671
0.495
0.343
0.248
0.197
0.159
0.127
0.098
0.078
0.0618
0.148
0.141
0.132
0.125
0.119
0.114
0.111
0.107
0.104
0.102
0.097
Capecitance
of cable
in microF/KM
APP
X.
0.13
0.15
0.16
0.18
0.20
0.22
0.23
0.25
0.27
0.30
0.32
90
110
130
160
190
215
240
270
310
350
395
85
100
115
140
170
190
215
240
275
310
355
110
130
155
190
230
265
300
340
400
455
530
120
145
170
205
245
275
305
345
395
440
495
100
120
150
180
215
245
275
305
350
390
440
135
165
200
245
300
340
385
435
510
580
660
in K. Amps
Al
Cu
2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
3.58
5.01
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
ote
ormal current ratings are given in standard conditions as given in page no - 40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42
Catter Pillar
37
TABLE - 33
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
SS- SECTI
ominal
Insulation
thickness
mm
8.80
8.80
8.80
8.80
8.80
8.80
8.80
8.80
8.80
8.80
8.80
8.80
8.80
8.80
8.80
AL VIE
1
Minimum
Inner Sheath
thickness
mm
0.40
0.40
0.40
0.40
0.40
0.40
0.40
0.50
0.50
0.50
0.50
0.60
0.60
0.60
0.70
DUCT
ominal Diameter
of Armour ire
mm
Minimum Thickness
of uter Sheath
mm
2.00
2.00
2.00
2.00
2.00
2.00
2.00
2.00
2.00
2.50
2.50
2.50
2.50
3.15
3.15
1.56
1.56
1.56
1.56
1.72
1.72
1.72
1.72
1.88
2.04
2.04
2.20
2.20
2.36
2.52
Appro .
ver all
Diameter
mm
36
38
39
40
43
44
46
47
50
53
57
60
64
70
74
Appro .
cable wt kg /km
ith Al.
ith Cu
Cond.
Cond.
1400
1450
1500
1600
1600
1800
1800
2100
2000
2500
2100
2700
2300
3130
2500
3550
2800
4200
3300
5050
3800
6200
4300
7300
4900
8800
6000
10500
6900
13000
I SULATI
MATE IAL C
I SULATI
SC EE I G E truded semiconducting compound followed by helically wrapped 0.050mm thick copper tape.
4
5
6
7
PTI
S A
EQUI EME T
Tabulated appro . net weights of cables are only for guidelines for transportation / Loading/ Unloading Purpose.
ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
0.0367
0.0291
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
0.0221
0.0176
1.54
1.11
0.820
0.567
0.410
0.325
0.265
0.211
0.162
0.130
0.1023
0.0808
0.0648
0.0530
0.0444
0.931
0.671
0.495
0.343
0.248
0.197
0.159
0.127
0.098
0.078
0.0618
0.0489
0.0391
0.0319
0.0268
0.175
0.169
0.161
0.152
0.145
0.140
0.135
0.130
0.126
0.122
0.117
0.113
0.111
0.105
0.102
Capecitance
of cable
in microF/KM
Appro .
0.10
0.11
0.12
0.14
0.15
0.16
0.18
0.19
0.21
0.23
0.25
0.27
0.29
0.34
0.37
100
120
140
170
200
225
250
280
315
345
385
415
450
485
510
90
105
120
150
175
195
215
240
275
300
330
360
385
415
435
120
145
175
220
265
300
340
385
450
500
570
640
720
790
850
130
155
180
215
255
285
310
345
390
420
455
480
510
540
550
115
135
155
190
220
245
270
300
335
360
395
415
440
460
475
155
185
225
280
335
380
430
485
560
620
690
750
820
840
940
in K. Amps
Al
Cu
2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
47.00
59.22
75.20
94.00
3.58
5.00
7.15
10.00
13.59
17.16
21.45
26.46
34.32
42.90
57.20
71.50
90.10
114.40
143.00
ote
ormal current ratings are given in standard conditions as given in page no - 40,41 , if site conditions are different, current rating should be
multiplied by rating factor as given in page no. 42
38
TABLE - 34
25
8.80
0.70
35
8.80
0.70
50
8.80
0.70
70
8.80
0.70
95
8.80
0.70
120
8.80
0.70
150
8.80
0.70
185
8.80
0.70
240
8.80
0.70
300
8.80
0.70
400
8.80
0.70
SS- SETI
AL VIE
1 C
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
2.36
2.52
2.52
2.68
2.84
2.84
3.00
3.00
3.00
3.00
3.00
DUCT
67
70
72
76
80
84
87
90
95
100
108
4700
5100
5500
6100
6800
7500
8100
8800
9900
11000
12500
U D
ominal
Minimum
Appro .
diameter outer Sheath
ver all
of armour thickness
Diameter
wire mm
mm
mm
5150
5750
6450
7400
8550
9750
10900
12250
14350
16600
19950
3.15
3.15
3.15
3.15
3.15
4.00
4.00
4.00
4.00
4.00
4.00
2.68
2.68
2.68
2.84
3.00
3.00
3.00
3.00
3.00
3.00
3.00
72
75
77
81
86
90
94
97
103
106
114
I ES A M U ED
Appro .
cable wt kg /km
ith Al.
ith Cu
Cond.
Cond.
7400
7800
8200
9000
10000
12000
12700
13500
15000
16000
18000
7850
8450
9150
10300
11750
14250
15500
16950
19450
21600
25450
MATE IAL C
4 I SULATI
SC EE I G E truded semiconducting compound followed by helically wrapped 0.050mm thick copper tape.
5 PVC FILLE S
6 I
7
A M U I G
8
PTI
C L U
F UTE SHEATH BLACK . PTI
S A
THE C L U S AS PE
EQUI EME T
Tabulated appro . net weights of cables are only for guidelines for transportation / Loading/ Unloading Purpose.
ELECTRICAL PARAMETERS
SI E
cross-sectional
area Sq MM
Capecitance
of cable
in microF/KM
APP
X.
25
1.20
0.727 1.54
0.931
0.160
0.10
90
85
110
120
35
0.868 0.524 1.11
0.671
0.153
0.11
110
100
130
145
50
0.641 0.387 0.820
0.495
0.146
0.12
130
115
155
170
70
0.443 0.268 0.567
0.343
0.138
0.14
160
140
190
205
95
0.320 0.193 0.410
0.248
0.130
0.15
190
170
230
245
120
0.253 0.153 0.325
0.197
0.125
0.16
215
190
265
275
150
0.206 0.1240 0.265
0.159
0.122
0.18
240
215
300
305
185
0.164 0.0991 0.211
0.127
0.118
0.19
270
240
340
345
240
0.125 0.0754 0.162
0.098
0.113
0.21
310
275
400
395
300
0.100 0.0601 0.130
0.078
0.111
0.23
350
310
455
440
400
0.0778 0.0470 0.1023 0.0618
0.106
0.25
395
355
530
495
ote
ormal current ratings are given in standard conditions as given in page no - 40,41 , if site conditions are
multiplied by rating factor as given in page no. 42
in K. Amps
Al
Cu
100
135
2.35
3.58
120
165
3.29
5.01
150
200
4.70
7.15
180
245
6.58
10.01
215
300
8.93
13.59
245
340
11.28
17.16
275
385
14.10
21.45
305
435
17.39
26.46
350
510
22.56
34.32
390
580
28.20
42.90
440
660
37.60
57.20
different, current rating should be
Testing Laboratory
39
SC PE
The current ratings of cables as indicated in various tables have been calculated on certain assumed conditions.
In actual practice these conditions may be different. Therefore to determine the actual current ratings as per installation conditions, the tabulated
ratings shall be multiplied with appropriate factors
BASIC ASSUMPTI
F
CU E T ATI GS
i
Ma imum permissible temperature - 90C for XLPE insulation, 70C for general purpose PVC, 85C for H PVC
b
i
ii
iii
iv
vi
Depth of laying - for 1.1KV cables - 750mm, 3.3KV to 11KV-900MM, Above 11KV-1050mm
vii
viii
ating factors
20
25
30
35
40
45
50
55
ormal PVC
1.32
1.25
1.16
1.09
1.00
0.90
0.80
0.80
H PVC
1.22
1.17
1.12
1.06
1.00
0.94
0.87
0.80
XLPE
1.20
1.16
1.11
1.06
1.00
0.95
0.88
0.81
iii
15
20
25
30
35
40
45
50
ormal PVC
1.17
1.12
1.06
1.00
0.94
0.
0.79
0.71
H PVC
1.13
1.09
1.04
1.00
0.95
0.90
0.85
0.80
XLPE
1.12
1.08
1.04
1.00
0.96
0.91
0..87
0.82
ating factors related to variation in ground thermal resistivity of soil for 3 single core cables laid direct in ground. Average value
Thermal es. in oC.Cm/
ating factors
iv
100
120
150
200
250
300
1.20
1.10
1.00
0.90
0.81
0.74
ating factors related to variation in ground thermal resistivity of soil for multi core cables laid direct in ground. Average value
Thermal es. in oC.Cm/
ating factors
100
120
150
200
250
300
1.16
1.08
1.00
0.90
0.82
0.76
1.00
90
105
120
150
180 & AB VE
0.99
0.98
0.97
0.96
0.95
105
120
150
180 & AB VE
0.97
0.96
0.94
0.93
1.00
0.98
1.00
0.97
105
120
150
180 & AB VE
0.96
0.95
0.92
0.91
120
0.98
150
0.96
180 & AB VE
0.95
120
0.99
150
0.98
180 & AB VE
0.96
ating factors related to variation in depth of laying for 3.3kv to 11kv cables
Depth of laying cm
ating factors
vii
for XLPE
ATI G FACT S
ating factors related to variation in ambient air temperature
Air temperature in Deg. C
ii
75
90
1.00
105
0.99
ating factors related to variation in depth of laying for above 11kv cables
Depth of laying cm
ating factors
75
90
105
1.00
40
o of cables/
circuits in groups
2
3
4
5
6
7
8
9
10
11
12
S 30CM
0.87
0.79
0.75
0.72
0.69
0.67
0.66
0.65
0.64
0.63
0.62
S 45CM
0.90
0.83
0.80
0.77
0.75
0.73
0.72
0.71
0.70
0.70
0.69
Touching S 15CM
0.80
0.85
0.70
0.78
0.64
0.73
0.59
0.70
0.55
0.67
0.53
0.65
0.51
0.64
0.49
0.63
0.48
0.63
0.47
0.62
0.46
0.61
S 30CM
0.90
0.85
0.81
0.79
0.77
0.76
0.76
0.74
0.74
0.73
0.73
S 45CM
0.92
0.88
0.86
0.84
0.83
0.82
0.82
0.81
0.81
0.80
0.80
S 60CM
0.95
0.91
0.89
0.88
0.87
0.86
0.86
0.85
0.85
0.84
0.84
o. of Tier
2
3
4
5
6
7
8
9
10
11
12
1
1
1
2
2
2
3
3
3
4
4
4
Touching
S 15CM
S 30CM
S 45CM
S 60CM
0.80
0.68
0.6
0.55
0.51
0.48
0.46
0.44
0.42
0.41
0.4
0.84
0.74
0.66
0.61
0.57
0.54
0.51
0.48
0.47
0.46
0.45
0.87
0.79
0.73
0.68
0.63
0.59
0.56
0.53
0.52
0.50
0.49
0.90
0.83
0.77
0.71
0.67
0.63
0.6
0.57
0.55
0.54
0.53
0.91
0.86
0.79
0.73
0.69
0.64
0.61
0.58
0.56
0.55
0.54
o.
of
racks
1
2
3
6
25mm
WALL
300mm
1
1.00
1.00
1.00
1.00
dia of cable
2
0.98
0.95
0.94
0.93
9
0.92
0.89
0.88
0.86
WALL
1
1.00
1.00
1.00
1.00
300mm
2
0.84
0.80
0.78
0.76
touching
9
0.73
0.69
0.68
0.66
25MM
WALL
o. of acks
1
2
3
4
A GEME T
2d
300mm
per rack
6
0.96
0.93
0.92
0.90
41
No. o
r
M t or
Touching
S
1
0.80
1
0.68
2
0.60
2
0.55
2
0.51
3
0.48
3
0.46
3
0.44
4
0.42
4
0.41
4
0.40
M t or a ( o
No o a s ra s
2
3
4
5
6
7
8
9
10
11
12
No. o a s/
r ts
ro
1
1.00
0.84
0.80
0.76
1
2
3
4
Nom a
ar a o
o d tor
(s . mm)
P. .C. Ca
LP Ca
S
P as
r
P as
S
P as
r
S st m
1.5
2.5
4
43.44
29.04
17.78
37.62
25.15
15.40
46.34
30.98
18.98
40.13
26.83
16.44
6
10
16
11.06
7.40
4.58
9.58
6.41
3.97
11.80
7.88
4.9
10.22
6.82
4.24
25
35
50
2.89
2.10
1.55
2.50
1.80
1.30
3.08
2.23
1.65
2.67
1.94
1.44
70
95
120
1.10
0.79
0.63
0.94
0.68
0.55
1.15
0.83
0.66
1.00
0.70
0.56
150
185
240
0.52
0.42
0.34
0.46
0.37
0.30
0.55
0.44
0.35
0.48
0.40
0.30
300
400
500
0.28
0.24
0.23
0.26
0.22
0.20
0.30
0.24
0.23
0.26
0.22
0.20
630
800
1000
0.20
0.19
0.18
0.18
-
0.21
0.20
0.18
0.18
-
A o
rat d
dro
S 30CM S 45CM
0.87
0.90
0.79
0.83
0.73
0.77
0.68
0.71
0.63
0.67
0.59
0.63
0.56
0.60
0.53
0.57
0.52
0.55
0.50
0.54
0.49
0.53
M t or a s (s a
a to d a m t r o
No o a s ra
1
2
3
1.00
1.00
1.00
0.98
0.95
0.94
0.96
0.93
0.92
0.93
0.90
0.89
4
1.00
0.76
0.72
0.68
r ormat o
15CM
0.84
0.74
0.66
0.61
0.57
0.54
0.51
0.48
0.47
0.46
0.45
)
3
1.00
0.78
0.74
0.70
1.00
0.80
0.76
0.71
S 60CM
0.91
0.86
0.79
0.73
0.69
0.64
0.61
0.58
0.56
0.55
0.54
o a
a
s
4
1.00
0.93
0.90
0.87
S/ or a s tr o to
ormat o
s a
t
r ts
a to t
t d am t r o a ) No o a s ra s
1
2
3
4
1.00
1.00
1.00
1.00
0.98
0.95
0.94
0.93
0.96
0.93
0.92
0.90
SCOPE
o d tor s
t
a s or a
sta at o s a so o r d
s st m. or L. . d str t o a ma
s
t do t
as s o o t
d str t o t s a a s sa r to s
tt
a o t
as s o a t o
rr t. S ort r t rr t rat o a s o d
t s ort r
r t r a rs, ra s orm rs & r a tor t . s d ts a a t to arr
o a s a s ar
r
a t ta s & a
a at d o
o o
ass m t o
ts a t to arr s ort r t rr t o
o s oad rr t. t
as o M /
o d tor to arr
t d s ort r t
t a a t o dam
a arat s s
as
d s r d oad rr t. S ort r t rat s
t
as s o I C-949 & I C-986 & o t
) W t P C s at o - 70
.C
. C/MM3
) W t Co
.C
. C/MM3
Is or 1 S .
t
S L C I NC I
IA
. ./M CA L S
P IMA
rat o s
a t ta
m d rat o r
r d to
IS
S .
FOR EXAMPLE
1) Nom a S st m o ta at . . S d
2) S ort r t
or . . s st m
3) a t t sta d t m or . . C s
4) orm a or a at
. . a s
W t A m m o d./ LP s at d a
r o d./ LP
I N
REQUIRED DATAS
W t Co
at d o s ort r
s at d a
11
25 A
0.5 S C
Is t
0.094
Is t
0.143
m t
d t
at tota o ta
ar st
ar st
25 0.5
0.94
188
r s 240s mm s r
25 0.5
0.143
124
r s 150s mm s r
r d
r d
att is given
Horse Power
42
F CABLE
U -A M U ED
ITH 5
T LE A CE
ST IP A M U ED
U D
I E A M U ED
E
E
TH EE C
UP T 150SQMM-1000
185 T 1000sqmm-500
UP T 150SQMM-1000
185 to 1000sqmm-500
UP T 150SQMM-1000
185 to 1000sqmm-500
UP T 50SQMM-1000
70 to 630sqmm-500
UP T 50SQMM-1000
70 to 630sqmm-500
UP T 50SQMM-1000, 70 T 500sqmm
500, 630sqmm-250
UP T 50SQMM-1000
UP T 50SQMM-1000
70 to 500sqmm-500
630sqmm-250
UP T 50SQMM-1000, 70 T 300sqmm
70 to 630sqmm-500
TH EE & HALF C
F U C
UP T 50SQMM-1000
70 to 630sqmm-500
UP T 50SQMM-1000
70 to 400sqmm-500
500 to 630sqmm-250
UP T 50SQMM-1000, 70 T 300sqmm
UP T 50SQMM-1000
70 to 500sqmm-500
630sqmm-250
UP T 50SQMM-1000
70 to 400sqmm-500
500 to 630sqmm-250
UP T 150SQMM-1000
185 T 630sqmm-500
800 to 1000sqmm-250
UP T 150SQMM-1000
185 to 630sqmm-500
800 to 1000sqmm-250
UP T 150SQMM-1000
185 to 630sqmm-500
800 to 1000sqmm-250
UP T 10SQMM-1000
16 to 300sqmm-500
400 to 630sqmm-250
UP T 10SQMM-1000
16 to 300sqmm-500
400 to 630sqmm-250
UP T 10SQMM-1000, 70 T 500sqmm
500
500, 300 to 630sqmm-250
UP T 10SQMM-1000
UP T 10SQMM-1000
16 to 240sqmm-500
240sqmm-400sqmm-250
UP T 10SQMM-1000, 16 T 185sqmm
16 to 185sqmm-500
500, 240 to 400sqmm-250
300 to 400sqmm-250
UP T 10SQMM-1000
16 to 240sqmm-500
240 to 400sqmm-250
UP T 10SQMM-1000, 16 T 150sqmm
16 to 185sqmm-500
500, 185 to 400sqmm-250
UP T 10SQMM-1000
16 to 240sqmm-500
300 to 400sqmm-250
UP T 10SQMM-1000
16 to 150sqmm-500
240 to 400sqmm-250
UP T 10SQMM-1000, 16 to 150sqmm
500, 400-630sqmm-250
UP T 50SQMM-1000, 70 to 240sqmm
DUCT
TH EE C
300 to 400sqmm-250
TH EE & HALF C
F U C
UP T 10SQMM-1000
~ Control cables more than FOUR CORES shall be supplied in 500 mts length
DESC PIT
F CABLE
6.35/11KV G ADE
1/11KV G ADE
19/33KV G ADE
E-A2X a
UP T 150SQMM-1000
185 to 1000sqmm-500
UP T 150SQMM-1000
185 to 1000sqmm-500
UP T 150SQMM-1000
185 to 1000sqmm-500
TH EE C
E-A2XF
25 T 300SQMM-500
25 T 185SQMM-500
25 T 95SQMM-500
400sqmm-250
240 to 400sqmm-250
120 to 400sqmm-250
25 T 150SQMM-500
185 to 300sqmm-250
400sqmm-200
25 T 95SQMM-500
120 to 240sqmm-250
300 to 400sqmm-200
25 T 50SQMM-250
70 to 120sqmm-250
185 to 400sqmm-200
TH EE C
E-A2X
43
TEST
QUALITY CONTROL
It has been rightly said that Quality is never an accident, it is always
as follows
Routine Tests :
achieve quality. For a quality end products, control starts from proper
design of the product. All raw materials are selected carefully and
only materials of high quality are used in production. Having done
Tests carried out on each cable to check the requirements which are
likely to vary during production.
Type Tests :
ii
ire-Drawing
Stranding of
ire diameter
Surface
Shape
Quality of oints in the wire
ires
iv
Curing
for XLPE Insulation
Screening
for H.T. Screened cables
vii
viii
Inner Sheath
Armouring
uter Sheath
Special tests required for F LS Cables can also be carried out at our
vi
Tests carried out on samples taken from a lot for the purpose of
Optional Tests :
Insulation
Laying Up
Acceptance Tests :
iii
of cable.
Sequence of Cores
Direction of lay
Diameter over laid up cores
Circularity
works i.e. Halogen gas generation test to IEC - 754 Part - I, Smoke
generation test to ASTMD 2843,
ygen inde
test and
Thickness of Sheath
Diameter over Sheath
Surface Uniformity
Circularity
Porosity
Diameter of ires/
Dimensions of Strips
Direction of lay
Coverage
Quality of oints of ires
Thickness of Sheath Diameter
over Sheath Tightness of Sheath
Eccentricity Porosity, Embossing
ptional Tests as
per the Indian Standard Specification for Power and Control Cables
with PVC insulation, Cross linked Polyethylene insulation and
Special Tests are given in the Anne ure.
Tensile Testing Machine
M Testing Lab
44
SELECTION GUIDE
List of Tests as per IS 1554 Part - I 1988, IS 1554 Part- II 1988,
IS 7098 Part - I 1988 and IS 7098 Part-II 1985
1.
2.
Type Tests :
a
Flammability Test
ires/Strips
Acceptance Tests :
a
b
Optional Tests :
a
nce
Voltage Grade.
hether cable is to be used on Earthed or Unearthed system
for voltages above 3.3 KV .
5.
A knowledge of
4.
Routine Tests :
Following further informations are also required for offering the e act
type of cable for any specific purpose
a
The material with which the PVC will be in contact i.e. oil, gases,
acids, alkalies etc. at normal and ma imum temperature.
Voltage Rating
KV
Upto 1.1
Above 1.1 but upto 11 K.V.
Above 11 K.V.
here D is overall
diameter of cable.
7.
Laying :
TESTING
INSULATION RESISTANCE MEASUREMENT OF CABLE
The voltage rating of I. . Tester Megger should be chosen as
following table
Voltage grade Rating of IR Voltage grade Rating of IR
of cable
Tester (Megger)
of cable
Tester (Magger)
1.1 KV
500 V
11 KV
1000 V
3.3 KV
1000 V
22 KV
2500 V
6.6 KV
1000 V
33 KV
2500 V
Testing during laying :
All new cables shall be megger-tested before ointing. After ointing
is completed all LV Cables shall be megger-tested.
End Terminations & Jointing :
Termination and ointing of Power & Control Cables shall be done by
means of compression methods using solderless tinned copper/
Aluminium terminal lugs. For control cables terminations, ring
tongue or reducer pin type terminal lug can also be used to suit the
purpose.
46