Genetron AZ20 R22 Pressure Temperature Chart
Genetron AZ20 R22 Pressure Temperature Chart
GenetronR22
Pressure Temperature Chart
(F)
PSIG
AZ-20 R22
(F)
-40
-39
-38
-37
-36
-35
-34
-33
-32
-31
-30
-29
-28
-27
-26
-25
-24
-23
-22
-21
-20
-19
-18
-17
-16
-15
-14
-13
-12
-11
-10
-9
-8
-7
-6
-5
-4
-3
-2
-1
10.8
11.5
12.1
12.8
13.5
14.2
14.9
15.6
16.3
17.1
17.8
18.6
19.4
20.2
21.1
21.9
22.7
23.6
24.5
25.4
26.3
27.2
28.2
29.2
30.1
31.1
32.2
33.2
34.2
35.3
36.4
37.5
38.6
39.8
40.9
42.1
43.3
44.5
45.7
47.0
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
0.6
1.0
1.4
1.8
2.2
2.6
3.1
3.5
4.0
4.5
4.9
5.4
5.9
6.4
6.9
7.4
8.0
8.5
9.1
9.6
10.2
10.8
11.4
12.0
12.6
13.2
13.9
14.5
15.2
15.9
16.5
17.2
17.9
18.7
19.4
20.1
20.9
21.7
22.4
23.2
PSIG
AZ-20 R22
48.3
49.6
50.9
52.2
53.6
55.0
56.3
57.8
59.2
60.7
62.2
63.7
65.2
66.8
68.3
69.9
71.5
73.2
74.9
76.6
78.3
80.0
81.8
83.6
85.4
87.2
89.1
91.0
92.9
94.9
96.8
98.8
100.9
102.9
105.0
107.1
109.2
111.4
113.6
115.8
24.0
24.9
25.7
26.5
27.4
28.3
29.2
30.1
31.0
31.9
32.8
33.8
34.8
35.8
36.8
37.8
38.8
39.9
40.9
42.0
43.1
44.2
45.3
46.5
47.6
48.8
50.0
51.2
52.4
53.7
55.0
56.2
57.5
58.8
60.2
61.5
62.9
64.3
65.7
67.1
(F)
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
PSIG
AZ-20 R22
118.1
120.3
122.7
125.0
127.4
129.8
132.2
134.7
137.2
139.7
142.2
144.8
147.4
150.1
152.8
155.5
158.2
161.0
163.8
166.7
169.6
172.5
175.4
178.4
181.5
184.5
187.6
190.7
193.9
197.1
200.4
203.6
207.0
210.3
213.7
217.1
220.6
224.1
227.7
231.3
68.6
70.0
71.5
73.0
74.5
76.1
77.6
79.2
80.8
82.4
84.1
85.7
87.4
89.1
90.8
92.6
94.4
96.1
98.0
99.8
101.6
103.5
105.4
107.3
109.3
111.2
113.2
115.3
117.3
119.4
121.4
123.5
125.7
127.8
130.0
132.2
134.5
136.7
139.0
141.3
(F)
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
PSIG
AZ-20 R22
234.9
238.6
242.3
246.0
249.8
253.7
257.5
261.4
265.4
269.4
273.5
277.6
281.7
285.9
290.1
294.4
298.7
303.0
307.5
311.9
316.4
321.0
325.6
330.2
143.6
146.0
148.4
150.8
153.2
155.7
158.2
160.7
163.2
165.8
168.4
171.0
173.7
176.4
179.1
181.8
184.6
187.4
190.2
193.0
195.9
198.8
201.8
204.7
PSIG
AZ-20 R22
(F)
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
334.9
339.6
344.4
349.3
354.2
359.1
364.1
369.1
374.2
379.4
384.6
389.9
395.2
400.5
405.9
411.4
416.9
422.5
428.2
433.9
439.6
445.4
451.3
457.3
207.7
210.8
213.8
216.9
220.0
223.2
226.4
229.6
232.8
236.1
239.4
242.8
246.1
249.5
253.0
256.5
260.0
263.5
267.1
270.7
274.3
278.0
281.7
285.4
(F)
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
PSIG
AZ-20 R22
463.2
469.3
475.4
481.6
487.8
494.1
500.5
506.9
513.4
520.0
526.6
533.3
540.1
547.0
553.9
560.9
567.9
575.1
582.3
589.6
596.9
604.4
611.9
289.2
293.0
296.9
300.8
304.7
308.7
312.6
316.7
320.7
324.8
329.0
333.2
337.4
341.6
345.9
350.3
354.6
359.0
363.5
368.0
372.5
377.1
381.7
AZ-20 (R-410A) pressure is about 60% (1.6 times) greater than R-22.
Only use servicing equipment and components designed for AZ-20 (R-410A).
Recovery cylinder service pressure rating 400 psig, e.g. DOT 4BA400 and DOT BW400.
Manifold sets must be 800 psig high-side and 250 psig low-side with 550 psig lowside retard.
Use hoses with 800 psig service pressure rating.
Use filter driers with service pressure rating of at least 600 psig.
Do not install a suction-line drier in the liquid line.
ARI color code is rose (PMS color code is 507).
Read the label to confirm cylinder contents since lighting conditions may hinder color
identification.
Liquid charge AZ-20.
Use a commercial metering device in the manifold hose.
Use an R-410A TXV on indoor sections originally equipped with a TXV;
do not use an R-22 TXV.
Existing capillary tube indoor coils will not operate properly.
A liquid-line filter drier is recommended.
Use a polyol ester (POE) lubricant approved by the equipment manufacturer.
POE lubricants are not always interchangeable.
Minimize exposure of POE lubricant to the atmosphere; use a pump to transfer
lubricant.
Use a filter drier to remove moisture from POE lubricant in the system a vacuum
pump will not work.
Leak detectors should detect HFC (hydrofluorocarbon) refrigerants.
Halide torches will not work effectively.
Instruments designed for CFCs and HCFCs will not have enough sensitivity for AZ-20.
Do not vent AZ-20 to the atmosphere.
Never pressurize a mixture of air and refrigerant since it may become flammable.
Always read the Genetron AZ-20 material safety data sheet (MSDS) before using
the material.
G525-093 04-05-10K