1980 MW, Tirora TPP, APML Power Transformer package Bushing Insulation levels (As per IS: 2026)

Rated voltage kV 22 11 6.35 220 11 6.35 400 11 6.35 400 Voltage class kV 24 12 7.2 245 36 12 7.2 420 36 12 7.2 420 Power frequency test voltage kV 50 28 20 460 70 28 20 630 70 28 20 630

S.No. Equipment 1 Unit Transformer Primary Secondary Secondary Neutral

Lightning impulse withstand voltage kVp 125 75 60 1050 170 75 60 1425 170 75 60 1425

Startup Transformer Primary Primary Neutral Secondary Secondary Neutral Station Transformer Primary Primary Neutral Secondary Secondary Neutral Bus Reactor