If you dont have 1784-PKTX card or PCMK card, you are still able to configure PanelView Plus talking to SLC504 thru DH+ network. Here is the example.
1.Create a RSLogix500 application the processor - Link SLC504 to your PC using AB_DF1-1 - Create a RSLogix500 application, we will just use N7:0 address. Download the application to the processor. - Leave SLC504 in running. Go to RSLinx and delete AB_DF1-1 2.Create a RSView ME application - Link PC to SLC504 using RS232 cross-over cable - Launch RSView ME > Double click Communication Setup > Create a new configuration. - Under Local tab, add DF1 driver and configure it as following screens
Create a new display, put a numeric display and a numeric input objects on it. Make sure to connect N7:0. Save the display as Test
- Test the display and make sure you can input and display N7:0 data
- Back Communication setup screen > Target tab > Add driver and choose DH+ (1784-PKTX, 2711-RN6, 2711RN8) > OK
- Driver selection is followed by a dialog that lets you set the drivers Name, the adapters Station ID and Jumper ID, and the network Baud rate:
This same configuration dialog can be modified later, by doing a Right click on the Driver properties.
- Now add the processor beneath that adapter: Right click DHPlus, DH+ > Add device > Choose relevant processor > OK
- Re-point the shortcut name to the processor again. Be sure, this time you define the pointer in Target tab
3. Download application to PanelView Plus - Use a straight thru cable to link PC and PanelView Plus - Under communication setup > Local Tab > Right click DF1 > Properties
Create a runtime application Use Transfer Utility to download the application to PVP thru DF1 drive
Connect PanelView Plus and SLC504 using DH+ cable When downloading finishes, load the application and run it.
4.Cable connection DH+ 3. Clear 2. Shield 1. Blue PanelView Plus RIO 3. Blue 2. Shield 1. Clear SLC504 DH+ 1. Blue Shield 2. Clear