You are on page 1of 1

Dry Type

High Speed
Resistor
Tapchanger
TYPE CK16
TAPCHANGER DIVISION
CTR MANUFACTURING INDUSTRIES LTD.
NAGAR ROAD, POONA - 411 014, INDIA
PHONE : (020) 26633402/05
FAX : 91 (020) 26633425
E-MAIL : tapchangers@ctr.in
PMTC. : 1023
JULY 2009
GENERAL INFORMATION
TECHNICAL DATE
TEST VOLTAGE :
On Load Tap Changer (OLTC) also suitable for Off Circuit application. Fitted with changeover selector
enabling utilisation in Coarse-Fine or reversing winding configuration of Transformer. Fully bidirectional.
Flange mounted, comprising driving mechanism and high speed selector switch. Local manual and
electrical control, with provision for remote electrical operation. Optional equipment includes Remote
Tapchange Control Cubical (RTCC) with indicating apparatus, Parallel operation control using group
simultaneous scheme, Automatic, etc.
Rated voltage : 11KV Max. Rated through current : 100 A
Max. system voltage : 12 KV Time per tap change. : 4-6 Secs.
Max. voltage per step : 220 V Total weight : 470 Kgs.
Max. No. of Steps : 16 Short Circuit withstand : 2 KAmps.
Max. No. of positions : 17 For 2 Secs.
Power Freq. (KV) Impulse (KVPeak)
To Earth : 28 75
Between Phases : 28 75
Between Adjacent Contacts : 10 25
Across Tapping range : 10 30
Over Changeover Selector contact : 10 30
Tapchanger
Remote Tapchange
Control Cubical
Selector Switch Local Control Panel
SERVICING
ORDER INFORMATION
Experienced Service Technicians available to attend to repairs. While requesting for such services, kindly
indicate Tapchanger and Remote Tapchange Control Cubicle serial numbers. Price lists for recommended
spares available on request.
Please provide information as required in our data sheet PTTC 1007 to enable correct equipment to be offered.
Our communications will use nomenclature as per exaple shown below :
Rights reserved to amend design data without prior notification
1. VOLTAGE
C = 11 KV
2. CONTAINER
K
3. CONTROL SCHEME
MMC : Mechanical Manual Cranking
ERI : Electrical Remote Independent
EAR : Elctrical Automatic Remote
ERG : Electrial Remote Group
Simultaneous Parallel
ARG : Automatic Remote Group
Simultaneous Parallel
4. NO. OF
STEPS
5. STEP
VOLTAGE
6. PHASE CURRENT
7. USED ONLY
EXCEPTIONALLY
eg. OC : Off. Circiut
OL : Off Load
Tapchanger
Fitted to Secondary
Side
Cyen Black