Catalogue 2011

MCB

MCB Changeover

RCCB

RCBO

Distribution Board Safety Ensured


Building Circuit Protection Devices
Standard Electricals Ltd (SEL), a fagship company of the Rs 5500
Crores (US $ 1.2 Billion) professionally managed group QRG
Enterprises is a market leader in the feld of low voltage electrical
distribution & consumer electrical products. The company has
carved a niche in the switchgear market by constantly creating
innovative solutions and upgrading the product range to meet the
ever-changing needs of the discerning customers.
SEL started its manufacturing operations with conventional
Rewirable Switch Fuse units over four decades ago.
The product range today includes highly sophisticated
domestic & industrial products such as MCBs, RCCBs, RCBOs,
Distribution Boards (DBs), MCCBs, Changeover Switches,
Switch Disconnector Fuses (SDFs), HRC Fuses, CFLs
etc.. All products are designed to comply with major
Indian & International Standards and are tested at CPRI/ERDA
Laboratories.
The quality control systems of the company have been audited
by BVQI and the company is certifed for ISO 9001: 2000.
STANDARD brand of MCBs are CSA, CE, and KEMA marked & being
exported to many European & Middle-East Countries.
SEL emphasises on Research & Development which is the
lifeline of the company. The Company uses state-of-
the-art CAD/CAM for the entire stage of design and
development. It has complete in-house facilities for short circuit
testing upto 10kA and all related equipments for conducting electrical /
mechanical tests.
The company has its manufacturing plant in Haridwar (Uttarakhand),
with a work force of more than 500 people including 100 qualifed
engineers.
STANDARD brand has a wide customer base through its
nationwide marketing network having offces in all major cities
in India with over 750 Authorised Dealers for effective sales &
services.
SEL products are now available internationally having
a strong export base. Its products are being exported
to the Middle East, South East Asian countries,
Malaysia, Singapore, Germany, U.K., South Africa, Kenya, Ghana,
Nigeria.
CONTENTS
Miniature Circuit Breaker (MCB) 6
MCB Changeover Switch 16
Residual Current Circuit Breaker 20
(RCCB/ELCB)
Residual Current Circuit Breaker 28
with Over Current Protection
(RCBO)
Distribution Boards (DB) 32
6
Range
6A-40A (B Type)
0.5A-63A (C Type)
0.5A-63A (D Type)
Execution
SP, SPN, DP, TP, TPN & FP
Specifcation
IS / IEC : 60898-1
M
I
N
I
A
T
U
R
E

C
I
R
C
U
I
T

B
R
E
A
K
E
R
7
Electricity is an inseparable part of our daily lifestyle. In
residential, commercial and industrial sectors there are myriad
systems, equipments and sophisticated appliances that depend
on electrical energy. Uncontrolled electrical power can be
extremely dangerous. Overloads, crowded wiring, short-circuits
and all kinds of interruptions in electric supply can lead to
devastating losses, least of them being fnancial.
We at STANDARD are proud to be known and respected the
world over for our range of superior quality electrical control and
safety devices. Through these, we speak of our lasting concern
for safety, economy and productivity for our customers.
The latest product from STANDARD is 10kA MCB, is an advanced
Indian design of high performance, current limiting and switching
for control and protection of industrial, commercial & domestic
electrical sub circuits. It meets the latest specifcation IS / IEC :
60898-1 of B & C Characteristics.
The primary function of the MCB is to protect the installation
such as cable & other components from damage, resulting due to
overload & short-circuit fault. Under overload heating effect can
occur on cable. Protection in this respect is assured by matching
the cable rating to the current rating of MCB.
Under short-circuit condition, mechanical damage can occur
due to strong magnetic feld caused by high current peaks
and overheating of cables on account of "exclusive let through
energy". The current limiting action of "MCB" ensures low value
of both peak current "cut off" and minimum let through energy.
Features & Benefts
Design
Latest & one of the best designed MCB.
Higher performance in a smaller package.
MCBs conforms to the latest Standards IS / IEC : 60898-1 /
2002.
These MCBs provide reliable protection to circuits against
overload & short-circuit ideal for industrial, commercial &
residential installations.
Certifcations
ISI
Higher breaking capacity
Breaking capacity of 10kA for the complete range from 6A to
63A in single pole and multipole tested at CPRI.
Larger terminals
Dual termination facility for incoming side and can take wire upto
25sq. mm cross section. Wire may be of copper or aluminum.
Shock proof
Offer IP 20 degree of protection. All live parts are out of human
reach ensuring safety to user.
Longer life
Reduced electro magnetic stresses resulting in increased contact
life.
Flexibility
Can be mounted easily in any of the regular Distribution
Boards.
Energy saving
IS / IEC : 60898-1 have recognized the growing importance of
limiting power loss in Switchgear devices and stipulated max.
permissible power loss values per pole of MCB. MCB having
power loss fgures of 50% lower watts than IS requirement.
Thus, 50% energy & cost saving by application.
8
TIME CURRENT CHARACTERISTIC CURVES
Based on the Tripping Characteristics, Standard MCBs are available in
B, C and D curve to suit different types of applications.
B Curve: for protection of electrical circuits with equipment that does
not cause surge current (lighting and distribution circuits).
Short circuit release is set to (3 - 5) In
C Curve: for protection of electrical circuits with equipment that
causes surge current (inductive loads and motor circuits).
Short circuit release is set to (5 - 10) In
D Curve: for protection of electrical circuits which causes high inrush
current, typically 12-15 times the thermal rated current (transformers,
X-ray machines etc.)
Short circuit release is set to (10 - 20) In
CURRENT LIMITING DESIGN
In a current limiting breaker, the tripping & arc control mechanism is so
designed that under short circuit conditions, the contacts are physically
separated and the electrodynamic forces set up by fault current assist
the extinction in less than half cycle.
The fgure shows the current limiting effect of a circuit breakers. Fault
Traces for Voltage & Current
0 = Point of fault initiation
t
x
= Contact opening time (i.e., creation of arc)
t
1
= Current / Voltage peak (i.e., current limitation)
t
2
= Time to total extinction of arc (i.e., complete shutdown of fault
current)
CHARACTERISTIC CURVES
0.01
0.10
1.00
10.00
100.00
1000.00
10000.00
T
im
e

(
s
e
c
.
)
2 3 5 10 20 30 100
1.13 1.45
1
Multiples of Rated Current (x I
n
)
B C D
PROTECTION UNLIMITED
STANDARD MCBs protect against overload and short circuit.
Overload Protection
It is achieved by thermal operation of the bimetal strip which defects when heated by the over current going through it, thereby
tripping the operating mechanism and causing the contact to open.
Thermostatic Bi-metal
It is a composite material comprising of two metallic layers of different co-effcient of thermal expansion which are permanently
bonded together by pressure welding.
Short Circuit Protection
In short circuit, the high current in the range of kA energises the solenoid and a magnetic feld is created. Due to this magnetic
feld the anchor is pulled down which pushes the plunger to strike the inner latch, causing instantaneous opening of the contacts.
Voltage across contacts
during opening of MCB
Time
Maximum
Prospective
Fault
Current
Cut-off
Current
A
B
0 t
X
t
1
t
2
C
u
r
r
e
n
t
V
o
lt
a
g
e
0
As per
Thermal Tripping Magnetic Tripping
No
tripping
Tripping Time Hold Trip Time
IS / IEC
60898-1
Current Current Limits Current Current Limits
I
1
I
2
t I
4
I
5
t
B Curve
1.13 x I
n
>1h 3xI
n
>0.1s
1.45 x I
n
<1h 5 x I
n
<0.1s
C Curve
1.13 x I
n
>1h 5xI
n
>0.1s
1.45 x I
n
<1h 10 x I
n
<0.1s
D Curve
1.13 x I
n
>1h 10xI
n
>0.1s
1.45 x I
n
<1h 20 x I
n
<0.1s
l
3
= 2.55 x l
N
1 s < t < 60s for l
n
< 32A
1 s < t < 120s for l
n
> 32A
9
MINIATURE CIRCUIT BREAKER
POWER LOSS DETAILS
60
44
45
70.5
84 36
1 POLE 1 POLE + NEUTRAL
& 2 POLE
3 POLE 3 POLE + NEUTRAL
& 4 POLE
17.7 35.4 53.1 70.8
DIMENSIONS (in mm)
S. No. MCB Rating
(A)
STANDARD
MCBs Power
Loss (W)
Max. Permissible
Power Loss (W) As per
IS:8828/IEC:60898
1 6 0.9 3.0
2 8 1.1 3.0
3 10 1.6 3.0
4 16 2.5 3.5
5 20 2.8 4.5
6 25 3.2 4.5
7 32 3.4 6.0
8 40 4.9 7.5
9 63 7.3 13
TECHNICAL INFORMATION
*Current Ratings - 0.5A, 1A, 2A, 3A, 4A, 5A, 6A, 8A, 10A, 13A, 16A, 20A, 25A, 32A,
40A, 50A, 63A
*** D Type MCB are available on request
** SP Single Pole
DP Double Pole
TP Three Pole
TP + N Three Pole Neutral
FP Four Pole
MCB Isolator
Standard Conformity IS / IEC 60898-1 IS / IEC 60947 - 3
Type/Series B C D***
Rated Current (In) A 6 - 40* 0.5 - 63* 0.5 - 63* 40 - 125
Rated Voltage (ac) (Ue) V 240/415 240/415
Rated Frequency (f) Hz 50 50
Nos. of Poles (Execution) SP, SPN, DP, TP, TPN, FP ** SP, DP, TP,FP**
Rated Short Circuit kA 10 10 6 to 32 - 10KA
Breaking Capacity 40 to 63 - 4.5kA
Utilization Category Magnetic
Release Setting
(3-5)In (5-10)In (10-20)In
AC 22A in 40A & 63
AC 23A in 100A & 125A
Rated Insulation Voltage (Ui) V 690 690
Rated Impulse Voltage (Uimp) kV 4 4
Electrical / Mechanical
Endurance Endurance (No. of
operations)
Less than 32A
More than 32A
20,000
10,000
10000
Ambient Temperature (
o
C) -5 to +45
Terminal Capacity (Max) sq.mm 25 25
Vibration 3 5
Shock 40 mm free fail
Protection Class IP - 20
Installation Position Vertical / Horizontal
Mounting Clip on DIn Rail (35 mm x 7.5 mm)
Case & Cover Moulded, fame retardant thermoplastic material.
10
MINIATURE CIRCUIT BREAKER MINIATURE CIRCUIT BREAKER
Current Cat No.
Rating (Amps.) B-Curve C-Curve
0.5 - DSMSCSPF0X5
1 - DSMSCSPF001
2 - DSMSCSPF002
2.5 - DSMSCSPF2X5
3 - DSMSCSPF003
5 - DSMSCSPF005
6 DSMSBSPF006 DSMSCSPF006
10 DSMSBSPF010 DSMSCSPF010
16 DSMSBSPF016 DSMSCSPF016
20 DSMSBSPF020 DSMSCSPF020
25 DSMSBSPF025 DSMSCSPF025
32 DSMSBSPF032 DSMSCSPF032
40 DSMSBSPF040 DSMSCSPF040
50 - DSMSCSPF050
63 - DSMSCSPF063
MCB Single Pole (SP)
MCB SINGLE POLE NEUTRAL (SPN)
MCB DOUBLE POLE (DP)
Current Cat No.
Rating (Amps.) B-Curve C-Curve
0.5 - DSMSCSNF0X5
1 - DSMSCSNF001
2 - DSMSCSNF002
2.5 - DSMSCSNF2X5
3 - DSMSCSNF003
5 - DSMSCSNF005
6 - DSMSCSNF006
10 - DSMSCSNF010
16 - DSMSCSNF016
20 - DSMSCSNF020
25 - DSMSCSNF025
32 - DSMSCSNF032
40 - DSMSCSNF040
50 - DSMSCSNF050
63 - DSMSCSNF063
Current Cat No.
Rating (Amps.) B-Curve C-Curve
0.5 - DSMSCDPF0X5
1 - DSMSCDPF001
2 - DSMSCDPF002
2.5 - DSMSCDPF2X5
3 - DSMSCDPF003
5 - DSMSCDPF005
6 - DSMSCDPF006
10 - DSMSCDPF010
16 - DSMSCDPF016
20 - DSMSCDPF020
25 - DSMSCDPF025
32 - DSMSCDPF032
40 - DSMSCDPF040
50 - DSMSCDPF050
63 - DSMSCDPF063
11
MCB TRIPLE POLE (TP)
MCB TRIPLE POLE NEUTRAL (TPN)
Current Cat No.
Rating (Amps.) B-Curve C-Curve
0.5 - DSMSCTNF0X5
1 - DSMSCTNF001
2 - DSMSCTNF002
2.5 - DSMSCTNF2X5
3 - DSMSCTNF003
5 - DSMSCTNF005
6 - DSMSCTNF006
10 - DSMSCTNF010
16 - DSMSCTNF016
20 - DSMSCTNF020
25 - DSMSCTNF025
32 - DSMSCTNF032
40 - DSMSCTNF040
50 - DSMSCTNF050
63 - DSMSCTNF063
Current Cat N o.
Rating (Amps.) B-Curve C-Curve
0.5 - DSMSCTPF0X5
1 - DSMSCTPF001
2 - DSMSCTPF002
2.5 - DSMSCTPF2X5
3 - DSMSCTPF003
5 - DSMSCTPF005
6 - DSMSCTPF006
10 - DSMSCTPF010
16 - DSMSCTPF016
20 - DSMSCTPF020
25 - DSMSCTPF025
32 - DSMSCTPF032
40 - DSMSCTPF040
50 - DSMSCTPF050
63 - DSMSCTPF063
MCB FOUR POLE (FP)
Current Cat No.
Rating (Amps.) B-Curve C-Curve
0.5 - DSMSCFPF0X5
1 - DSMSCFPF001
2 - DSMSCFPF002
2.5 - DSMSCFPF2X5
3 - DSMSCFPF003
5 - DSMSCFPF005
6 - DSMSCFPF006
10 - DSMSCFPF010
16 - DSMSCFPF016
20 - DSMSCFPF020
25 - DSMSCFPF025
32 - DSMSCFPF032
40 - DSMSCFPF040
50 - DSMSCFPF050
63 - DSMSCFPF063
MINIATURE CIRCUIT BREAKER MINIATURE CIRCUIT BREAKER
12
ISOLATOR ISOLATOR
TECHNICAL SPECIFICATION-ISOLATOR
Range
40A, 63A, 100A and 125A
Execution
SP, DP, TP, & FP
Specifcation
IS / IEC: 60947-3
Rated Voltage
240V / 415V AC
Rated Frequency
50 Hz
Utilisation Category
AC 22A in 40A and 63A
AC 23A in 100A and 125A
Electrical Endurance
10000 operations
Mechanical Endurance
20000 operations
Terminal Capacity Flexible Solid
40A, 63A 16 sq.mm 25 sq.mm
100A, 125 A 35 sq.mm 50 sq.mm
ISOLATOR DOUBLE POLE (DP)
Rating(A) Cat No.
40 DSMISODPX040
63 DSMISODPX063
100 DSMIODPX100
125 DSMIODPX125
ISOLATOR SINGLE POLE (SP)
Rating(A) Cat No.
40 DSMISOSPX040
63 DSMISOSPX063
100 DSMIOSPX100
125 DSMIOSPX125
ISOLATOR
13
ISOLATOR TRIPLE POLE (TP)
Rating(A) Cat No.
40 DSMISOTPX040
63 DSMISOTPX063
100 DSMIOTPX100
125 DSMIOTPX125
ISOLATOR FOUR POLE (FP)
Rating(A) Cat No.
40 DSMISOFPX040
63 DSMISOFPX063
100 DSMIOFPX100
125 DSMIOFPX125
ISOLATOR ISOLATOR
14
SHUNT TRIP ATTACHMENT USED FOR REMOTE
TRIPPING

Standard Conformity
IS / IEC : 60947-3
Coil Consumption
6VA
Rated Voltage
(ac) (Ue) (dc) (Ue)
240V 48V, 24V, 12V
Frequency
50Hz
Operating Voltage range
70% - 110% of rated voltage
Electrical Endurance (nos. of ops)
10000
Terminal Capacity (max)
25mm2
Protection Class
IP - 20 as per IS-2147 & IEC-60529
Mounting
Right side of MCB
(Factory assembled)
MINIATURE CIRCUIT BREAKER MINIATURE CIRCUIT BREAKER
AUXILLARY CONTACT

Standard Conformity
IS / IEC : 60947-1
Rated Current (In)
6A
Rated Voltage (Ue)
240 V ac
Contact Confguration
1 NO + 1 NC
2 NO + 2 NC
Utilization Category
AC 11
Electrical Endurance (nos. of operations)
10000
Terminal Capacity (max)
4mm2
Protection Class
IP - 20 as per IS : 2147 & IEC : 60529
Mounting
Left side of MCB (Factory assembled)
ACCESSORIES
15
To trip the Circuit Breaker through Shunt Trip Coil, 70% to
110% of the rated voltage is to be applied across D1 & D2
The Shunt Trip coil is short time rated and it trip the breaker
instantaneously. (i.e., continuous duty not required)
MCB SELECTION CHART
SHUNT TRIP COIL
Appliance Capacity / wattage MCB MCB
(1, 240V~) Current Rating Type

Air Conditioner 1.0 tonnes 10A C series
1.5 tonnes 16A C series
2.0 tonnes 20A C series
Refrigerator 165 litres 3A C series
350 litres 4A C series
Oven cum Griller 4500W 32A B series
1750W 10A B series
Oven 750W 6A B series
Hot plate 2000W 10A B series
Room Heater 1000W 6A B series
2000W 10A B series
Washing Machine 300W 2A C series
Washing Machine
(with heater) 1300W 8A C series
Water Heater
(storage/instant) 1000W 6A B series
2000W 10A B series
3000W 16A B series
6000W 32A B series
Electric iron 750W 6A B series
1250W 8A B series
Toaster
(2 slices) 1200W 8A B series
Electric Kettle 1500W 10A B series
MINIATURE CIRCUIT BREAKER MINIATURE CIRCUIT BREAKER
Outgoing
D
1
CoilTerminal
D
2
CoilTerminal Incoming
1 3
2 4
Shunt trip Connection Digram
Incoming Connection
16
M
C
B

C
H
A
N
G
E
O
V
E
R

S
W
I
T
C
H
Range
25A, 40A
Execution
Double Pole,
Four Pole
Specifcation
IS / IEC : 60947-3
17
MCB Changeover switch fnds wide & varied applications in in-
dustries as well as in domestic sphere for use in low voltage
distribution circuits, wherever continuity of supply is necessary,
for switching to an alternate source of supply from main supply
and vice - versa.
They are switch disconnectors with independent manual opera-
tion, capable of making, carrying and breaking currents under
normal circuit conditions, which may include operating overload
condition and also carry currents under specifed abnormal circuit
conditions such as those of short circuit for a specifed time.
Features
Compact construction
Double break contacts
Silver Cadmium Oxide contact tips
Shrouded terminals
Front operation with three stable positions I-O-II
Centre position OFF
Easy snap on DIN Rail mounting
Can be mounted with other products viz. MCB, RCCB,
Isolator in Distribution Board
CONSTRUCTION
The entire switching mechanism along with the fxed and moving
contact assembly are housed in FR thermo plastic moulded case
/ cover, having high dielectric strength, excellent mechanical &
thermal properties.
The switching mechanism is double break type. The contact
tips are made of Silver Cadmium oxide for long electrical life,
sustained current carrying capacity and they ensure temperature
rise is within specifed limits.
TECHNICAL INFORMATION
Standard Confrmity IS/IEC-60947-3
No. of Poles (Execution) : DP, FP
Rated Current (In) A : 25, 40
Rated Voltage (Ue) V : 240 AC / 415 AC
Rated Frequency Hz : 50
Rated insulation voltage V : 660
Dielectric Strength kV : 2.5
Rated impulse voltage kV : 4
Utilization Category : AC 21A
Ambient Temp. C : -5 to +55
Mechanical life Nos. ops. : 10000
Electrical life Nos. ops. : 10000
Mounting : Standard DIN rail
Mounting Position : Vertical / Horizontal
Terminal Capacity sq. mm : 10
18
CONNECTION DIAGRAMS / TERMINAL MARKING
Double Pole
MCB CHANGEOVER SWITCH MCB CHANGEOVER SWITCH
Current Rating (Amps.) Cat. No.
25 DSMCODPX025
40 DSMCODPX040
I - Incoming terminals (main supply) - 2 & 6
II - Incoming terminals (standby supply) - 4 & 8
Outgoing terminals (to load) - 1 & 5
* Mid position of knob is OFF position
1 3
2 4 6 8
5 7
DIMENSIONS (in mm)
19
Four Pole
MCB CHANGEOVER SWITCH MCB CHANGEOVER SWITCH
Current Rating (Amps.) Cat. No.
25 DSMCOFPX025
40 DSMCOFPX040
I - Incoming terminals (main supply) - 2, 6, 10 & 14
II - Incoming terminals (standby supply) - 4, 8, 12 & 16
Outgoing terminals (to load) - 1, 5, 9 & 13
* Mid position of knob is OFF position
1 5
16 14 12
9 13
10 8 6 4 2
DIMENSIONS (in mm)
20
R
C
C
B

/

E
L
C
B
Range
16A - 63A
Execution
2 Pole, 4 Pole
Specifcation
IS 12640 - 1: 2008
IEC 61008 - 1
21
The fow of current through electrical facilities always involves
risks. Poorly insulated equipment, faulty wires and incorrect use
of an electrical device cause currents to fow through the wrong
path (i.e. through the insulation) to the earth. This current is
called Leakage Current.
Earth leakage is an electrical hazard and is responsible for
electrical shocks and fre risk. Earth leakage and its associated
hazard can be prevented by Residual Current Circuit Breaker
(RCCB), also popularly known as Earth Leakage Circuit Breaker
(ELCB).
Features
Simple and Robust operating mechanism.
Rotary handle with ON/OFF indication
Dual termination for Bus Bar as well as cable connection
Advance neutral
Test button for regular inspection
Positive contact indication
Range
16A - 63A
Sensitivity
30mA, 100mA, 300mA
Execution
Double Pole (DP)
Four Pole (FP)
Specifcation
IEC 61008-1/IS 12640 - 1:2000
Against Electrocution
The use of exposed, substandard, badly wired, wrongly connected
or damaged equipment as well as frayed or badly repaired cables
reduces the safety of an installation and increases the risk of
person receiving an electric shock.
Electrocution is a passage of current through human body, which
is dangerous. The fow of current through human body effects
vital functions.
1. Breathing
2. Heartbeat
A correctly chosen RCCB can detect small currents fowing to
earth and reduces the risk of electrocution. Effect of electric
current through human body has been well researched and
following chart summarizes the results:
Effect of electric current through human body has been
well researched and following chart summarizes the results
Features & Benefts
22
RCCB/ELCB RCCB/ELCB
PROTECTION
Against Electrocution
The use of exposed, substandard, badly wired, wrongly connected or damaged equipment as well as frayed or badly repaired cables
reduces the safety of an installation and increases the risk of person receiving an electric shock.
Electrocution is a passage of current through human body, which is dangerous. The fow of current through human body effects vital
functions.
1. Breathing
2. Heartbeat
A correctly chosen RCCB can detect small currents fowing to earth and reduces the risk of electrocution. Effect of electric current
through human body has been well researched and following chart summarizes the results.
Effect of electric current through human body has been well researched and following chart summarizes the results.
However, electrocution should not be viewed in terms of current
alone, but in terms of contact voltage. A person gets electrocuted
by coming in contact with an object that has a different potential
from his/her own. The difference in potential causes the current to
fow through the body.
The human body has known limits:
Under normal dry conditions, voltage limit = 50V
In damp surroundings, voltage limit = 25V
Rated Tripping Current Maximum permissible
of the RCD earth fault loop impedance in
10 mA 5,000
30 mA 1,666
100 mA 500
300 mA 166
EFFECT OF ELECTRIC CURRENT THROUGH HUMAN BODY
500 mA Immediate cardiac arrest resulting in death
70-100 mA Cardiac fbrillation; the heart begins to vibrate and no

20-30 mA Muscle contraction can cause respiratory paralysis
10 mA Muscle contraction : the person remains stuck to the conductor
1-10 mA Prickling sensations
AGAINST INDIRECT CONTACT
Over current protection devices like MCB are unable to act promptly on small earth leakage currents. To comply with wiring regula-
tions, the earth fault loop impedance in Ohms, multiplied by the rated tripping current of the RCD in amperes must not exceed 50.
Example
For an RCD with a rated tripping current of 30mA, the maximum permissible earth fault loop impedance is calculated as follows: Zs (max) = 50 / In
= 50/0.03 = 1,666
AGAINST FIRE
The majority of fres which occur as a result of faulty wiring are started by current fowing to earth. Fire can be started by fault current
of less than 1 amp.The normal domestic overload protective device such as a fuse or MCB will not detect such a small current. A
correctly chosen RCD will detect this fault current and interrupt the supply, hence, reducing the risk of a fre starting.
23
RCCB/ELCB RCCB/ELCB
Technical Information TWO POLE FOUR POLE
Standard Conformity IS 12640-1: IEC 61008-1 IS 12640-1: IEC 61008-1
Rated Current (In) A 16, 25, 32, 40, 63 25, 40, 63
Sensitivity * (In) mA 30, 100, 300 30, 100, 300
Rated Voltage (Un) Vac 240 415
Rated Insulation Voltage (Ui) V 690 690
Rated Frequency Hz 50 50
Short circuit Withstand Capacity kA 6 6
Residual Making Breaking Capacity A 500 A or 10 In wherever is greater 500 A or 10 In wherever is greater
Ambient Temperature C -25C to + 55C -25C to + 55C
Shock Resistance 40 mm free fall 40 mm free fall
Vibration Resistance g 3 3
Electrical /Mechanical operations 10000 10000
Mounting Din Rail (35 x 7.5) mm Din Rail (35 x 7.5) mm
Degree of Protection IP 20 IP 20
Terminal Capacity (max) mm2 25 25
WORKING PRINCIPLE
The RCCB works on the current balance principle. The supply
conductors, i.e. the phases and the neutral, are passed through
a torroid and form the primary windings of a current transformer.
Its secondary winding is connected to a highly sensitive
electromagnetic trip relay, which operates the trip mechanism.
In a healthy circuit, sum of the currents in phases, is equal to
the current in the neutral and the vector sum of all currents
is equal to zero. If there is any insulation fault in the current
and leakage current fows to earth, the currents do not balance
and their vector sum is not equal to zero. This imbalance is
detected by the core balanced current transformer, the RCCB is
tripped and supply to load is interrupted. The trip mechanism
is operated at a residual current between 50-100% of its rated
tripping current.
Earth
R
Y
B
N
T
*500 mA is available on request
24
WIRING DIAGRAM
The Standard range of four pole RCCBs can be used to provide residual current protection in 3 phase, 3 wire circuits (no neutral),
however a link from the neutral to an incoming should be made on the supply side of the RCCB, to enable the operation of the
RCCB.
Actuation Time Characteristics
RCCB/ELCB RCCB/ELCB
a
Current in milliamperes
b c1c2c3
10000
5000
2000
1000
500
200
100
50
20
10
0.1 0.3 1 3 10 30 100 300 1000 3000 10000
0.2 0.5 2 5 20 50 200 500 2000 5000
30 mA
100 mA
T
i
m
e
in
m
illis
e
c
o
n
d
s
Typical current
limits due to body resistance
at 240 V
ms
350
300
350
200
150
100
50
1 2 3 4 5 6
Residual Current multiple of In (mA)
T
im
e

(
in

m
s
)
For Three Phase
3 Wire connections
For Single Phase
2 Wire connections
For Three Phase
4 Wire connections
Load
1 N
Load
2 4 6 N
Load
2 4 6 N
2 N
2 4 6 N
1N
T
R
1 3
R
T
5 N
1 3 5 N
2 4 6 N
R
T
SELECTION
30 mA : A 30 mA ELCB will provide a high degree of protection
against electrocution in an accidental shock hazard situation.
The current fowing through human body could be between
80mA and 240mA depending on the resistance of the human
body and the voltage across it.
Zone : Physiological Effects
Zone 1 : Usually no reactions
Zone 2 : Usually no harmful physiological effects
Zone 3 : Usually no organic damage to be expected. Likelihood
of muscular contraction and diffculty in breathing, reversible
disturbances of formation and conduction of impulse in the
heart and transient cardiac arrest without ventricular fbrillation
increases with current magnitude and time.
Zone 4 : In addition to the effects of Zone 3, probability if
ventricular fabriliation increased upto 5% (curve C2) upto 50%
(curve C3) and above 50% beyond curve C3. It increases with
magnitude and time, and pathophysiological effects such as
cardiac arrest, breathing arrest and heavy burns may occur.
To be within zone of the IEC curve as shown above. It is necessary
for the ELCB to operate within 50ms at 240 mA and 150ms at
80mA. Both these conditions are satisfed by 30mA ELCB.
For households, individual outlets, wet areas and temporary
installations, ELCB with sensitivity not exceeding 30mA is
advisable.
100 mA : A 100mA ELCB will normally give high degree of
protection against electrocution but there is a possibility that
the shock current could fall below the tripping level of ELCB. This
could occur if additional resistances to that of human body are
included in the earth path.
The 100mA RCCB protects against leakage currents and indirect
contact with earth loop impedance upto 500 Ohms.
300 / 500mA : A 300/500 mA ELCB may be used where only
fre protection is required. eg., on lighting circuits, where the
risk of electric shock is small. 300/500mA ELCB will not give any
protection against electrocution.
25
Dimensions (in mm)
RCCB/ELCB RCCB/ELCB
DOUBLE POLE AC TYPE
FOUR POLE AC TYPE
Current Sensitivity Cat No.
Rating (Amps.) mA
16 30 DSRMCTDF030016
16 100 DSRMCTDF100016
16 300 DSRMCTDF300016
25 30 DSRMCTDF030025
25 100 DSRMCTDF100025
25 300 DSRMCTDF300025
32 30 DSRMCTDF030032
32 100 DSRMCTDF100032
32 300 DSRMCTDF300032
40 30 DSRMCTDF030040
40 100 DSRMCTDF100040
40 300 DSRMCTDF300040
63 30 DSRMCTDF030063
63 100 DSRMCTDF100063
63 300 DSRMCTDF300063
Current Sensitivity Cat No.
Rating (Amps.) mA
16 30 DSRMCRFF030016
16 100 DSRMCRFF100016
16 300 DSRMCRFF300016
25 30 DSRMCRFF030025
25 100 DSRMCRFF100025
25 300 DSRMCRFF300025
32 30 DSRMCRFF030032
32 100 DSRMCRFF100032
32 300 DSRMCRFF300032
40 30 DSRMCRFF030040
40 100 DSRMCRFF100040
40 300 DSRMCRFF300040
63 30 DSRMCRFF030063
63 100 DSRMCRFF100063
63 300 DSRMCRFF300063
36.0
3
6
.
0
4
5
.
0
67.8
60.0
71.0
68.0
60.0
43.5
8
4
.
5
3
6
.
0
4
5
.
0
AC TYPE - STANDARD APPLICATIONS
AC type RCDs detect AC residual currents. In the majority of cses (standard applications), they are used for AC current
detection at 50 / 60 Hz
26
Range
IS : 12640-1:2008
IEC : 61008-1:1996
Sensitivity
30, 100 & 300 mA
Execution
2P, 4P
Specifcation
50Hz
Features
Short circuit breaking with stand capacity 10kA
Different knob position to indicate whether it is switched by a fault or manually switched OFF (mid trip)
Test button for regular inspection
Contact position indication
Technical Information TWO POLE FOUR POLE
Specifcation Reference IEC 61008-1 & IS 12640-1: 2008 IEC 61008-1 & IS 12640-1: 2008
Rated current (In) A 80, 100 80, 100
Sensitivity (IDn) mA 30, 100, 300 30, 100 ,300, 500*
Rated Voltage (Ue) V 240 V~ 415V~
Rated Insulation voltage (Ui) V 660 660
Rated Frequency Hz 50 50
Trip Time 1xIDn<300ms 1xIDn<300ms
5IDn<40ms 5IDn<40ms
Short circuit withstand Capacity kA 10 10
Residual Making Breaking capacity A 10 In 10 In
Ambient Working Temperature C -25C to + 55C -25C to + 55C
Shock Resistance 40mm free fall 40mm free fall
Vibration Resistance g 5 5
Electrical Endurance operations >2000 >2000
Mechanical Endurance operations >3000 >3000
Mounting Din Rail (35 x7.5 mm) Din Rail (35 x7.5 mm)
Degree of protection IP 20 IP 20
Terminals Capacity (Max) mm2 50 50
RCCB/ELCB RCCB/ELCB
*500 mA is available on request
HIGHER RATING (80A-100A)
27
DOUBLE POLE AC TYPE
FOUR POLE AC TYPE
Current Sensitivity Cat No.
Rating (Amps.) mA
80 30 DSRMCMDF030080
80 100 DSRMCMDF100080
80 300 DSRMCMDF300080
100 30 DSRMCMDF030100
100 100 DSRMCMDF100100
100 300 DSRMCMDF300100
Current Sensitivity Cat No.
Rating (Amps.) mA
80 30 DSRMCMFF030080
80 100 DSRMCMFF100080
80 300 DSRMCMFF300080
100 30 DSRMCMFF030100
100 100 DSRMCMFF100100
100 300 DSRMCMFF300100
Dimensions (in mm)
RCCB/ELCB RCCB/ELCB
36.0
30.5
44.0
60.0
69.5
45.0
36.0
87.5 87.5
72.0
2 Pole 4 Pole
28
Range
6A, 10A, 16A, 20A, 25A, 32A & 40A
Sensitivity
30mA, 100mA, 300mA
Execution
Single Pole with neutral (SPN)
Triple Pole with neutral (TPN)
Specifcation
IS:12640 Part2: 2008, IEC 61009-1,
BSEN:61009-1
R
C
B
O
29
Standard New RCBO is a single composite device which provides
protection against over currents and earth leakage faults in the
same width and profle as that of a standard MCB. It is designed
for use in domestic, commercial and industrial distribution sys-
tems at the most downstream circuit for ensuring high degree of
protection to the user for a particular circuit. In normal use, it is
safe to use and free of to user as well as to environment.
Features
Pulsating dc protection - Type A
Discrimination using time delay - Type S RCBO
Controlled response VD RCBO (Electronic)
Protection in case of loss of supply neutral in SPN RCBO only
Enhanced immunity to nuisance tripping
Positive contact indication: Red for ON , Green for OFF
Short circuit breaking capacity 10 kA.
Large terminal capacity: RCBOs have 35 mm2 for cool running
while in operation.
Protection in case of loss of supply neutral: Even in event of
loss of supply neutral, Standard RCBO provides protection
against earth faults . The Functional Earth (FE) white color
wire connected to earth provides this protection.
Controlled response & immunity to nuisance tripping: The
trip level and the response time of the Standard VD (Voltage
Dependent) RCBO using electronic circuit is set to very
precise values and thereby provide greater immunity to
nuisance tripping that can be caused by mains borne noise,
surge voltages, lighting surges, reactive loads, mains flters,
etc.
Neutral to earth faults: A connection that occurs between
N and E on the load side of any RCBO will impact on its
performance and cause the trip level to increase. In the case
of a N - E fault, the user may have no way of knowing that this
fault exists and that the RCBO has been desensitised. Under
this condition, the Standard VD RCBO provides a far greater
level of protection than a normal VI (Voltage Independent)
RCBO.
Aesthetics & Convenience
The new modules unique compact construction enables
far more devices to be ftted into a distribution board than
previously possible, and 2 Module RCBO can simply replace
existing MCB 2 pole when upgrading a board.
High stacking density = smaller chasis & distribution boards.
Reliability & continuity of service
Enhanced discrimination with Standard MCBs
Back up to 10 kA with BS & DIN fuses
Retrofts Standard MCBs in distribution boards with no
modifcations in general
Robust construction.
Energy limiting
Standard RCBO meets the requirements for energy let through
by IEC & British Standard for energy limiting class 3.
Features & Benefts
30
ADDITIONAL RANGE - TYPE A & S
Type A - Pulsating DC Protection: Any electrical appliance with power control has the ability to produce earth fault currents with
pulsating DC (rectifed AC) components. RCBOs that provide this type of protection are referred to as Type A RCBOs.
VI RCBOs do not provide this protection, and are referred to as Type AC RCBOs. Standard VD RCBOs have been specifcally designed
to provide protection against pulsating DC fault currents.
Type S- Selective or Time Delay: RCBOs are also divided into two categories determined by their response time to an earth fault
current, as follows
General Type - having a trip time<300mS for fault currents of I
DN
and < 40ms for fault currents > 5 I
DN
.
S Type- having a trip time of 150 - 500mS for I
DN
, and 40 - 130mS for >5 I
DN
.
(IDn is the rated residual operating current of the RCBO)
As the name implies, general types are intended for general purpose use. However, S (selective) types are normally used in conjunction
with downstream general type RCBOs.
The S type effectively provides discrimination in terms of the response time to earth fault currents for upstream and downstream
RCBOs. For example, when two RCBOs are connected in series the frst RCBO will often be an S type.
Technical Information SPN (2M) TPN (4M)
Specifcation SPN (2M) TPN (4M)
Specifcation Reference IS 12640 (Part 2) & IEC 61009 IS 12640 (Part 2) & IEC 61009
Rated Current In 6A, 10A, 16A, 20A,25A, 32A, 40A 6A, 10A, 16A, 20A,25A, 32A, 40A
Rated Residual Operating Current I
DN
30, 100, 300mA. 30, 100, 300mA.
Instantaneous Tripping Current C curve C curve
Rated Voltage Un (Vac) 240V~ 415V~
Rated Insulation Voltage Un (Vac) 660V 660V
Rated Frequency 50Hz 50Hz
No. of Pole 1P+N 3P+N
Rated Short Circuit Capacity Icn 10kA 10kA
Rated Residual Making Breaking Capacity I
Dm
500A 500A
Operating Characteristics in case of
Residual Currents A type A type
Method of Mounting Panel Board Type (DIN Rail) Panel Board Type (DIN Rail)
Degree of Protection IP 20 IP 20
Terminals for External Conductors (mm
2
) 35
Net Weight (in Kg) 0.420 0.84
Ambient Working Temperature -5C to + 55C -5C to + 55C
Mechanical Endurance (No. of Operations) 4000 4000
Electrical Endurance (No. of Operations) 4000 4000
Trip Time (milli Second) <40 <40
Shock Resistance 40mm free fall 40mm free fall
Vibration Resistance 3g 3g
RCBO RCBO
31
Current Sensitivity Cat No. Cat No.
Rating (Amps.) mA SP&N TP&N
6 30 DSCEACSN2030006 DSCEACTN4030006
6 100 DSCEACSN2100006 DSCEACTN4100006
6 300 DSCEACSN2300006 DSCEACTN4300006
10 30 DSCEACSN2030010 DSCEACTN4030010
10 100 DSCEACSN2100010 DSCEACTN4100010
10 300 DSCEACSN2300010 DSCEACTN4300010
16 30 DSCEACSN2030016 DSCEACTN4030016
16 100 DSCEACSN2100016 DSCEACTN4100016
16 300 DSCEACSN2300016 DSCEACTN4300016
20 30 DSCEACSN2030020 DSCEACTN4030020
20 100 DSCEACSN2100020 DSCEACTN4100020
20 300 DSCEACSN2300020 DSCEACTN4300020
25 30 DSCEACSN2030025 DSCEACTN4030025
25 100 DSCEACSN2100025 DSCEACTN4100025
25 300 DSCEACSN2300025 DSCEACTN4300025
32 30 DSCEACSN2030032 DSCEACTN4030032
32 100 DSCEACSN2100032 DSCEACTN4100032
32 300 DSCEACSN2300032 DSCEACTN4300032
40 30 DSCEACSN2030040 DSCEACTN4030040
40 100 DSCEACSN2100040 DSCEACTN4100040
40 300 DSCEACSN2300040 DSCEACTN4300040
RCBO RCBO
Dimensions (in mm)
10000.00
1000.00
100.00
T
i
m
e
(
s
e
c
)
10.00
1.00
0.10
0.01
1 10
Multiples of Reted Current
100
1000.00
100.00
T
i
m
e

(
s
e
c
)
10.00
1.00
0.10
0.01
0.01 1 10 100 1000 10000
Multiples of Reted Residual Current in In mA
Time Current Characteristics C Curve Residual Current Tripping Characteristics (General Type)
35.4
87.5
36
43.5
68.4
45
70.6
6.8
44
70.8 50.4
45
36
6.8
43.5
68.4
74.5
125
32
Range
Single Phase & Three Phase
Execution
Horizontal & Vertical
Specifcation
IS : 13032 / IS : 8623
D
I
S
T
R
I
B
U
T
I
O
N

B
O
A
R
D
S
33
Superior aesthetics that blend well with the decor.
Made of special grade CRCA sheet steel to provide strength
and longer life to enclosures.
Manufactured with latest technology CNC Punch and Brake
presses to attain highest degree of perfection.
Painted with epoxy polyster and polyster resin based pow-
der paints with latest techniques in powder coating ensures
strong, scratch resistant coatings.
Current carrying parts are made of electrolytic grade of cop-
per having high conductivity and low resistivity thereby keep-
ing temperature rise and distribution losses very low.
Appropriate sizes of DIN rails to facilitate easy and fast
mounting of MCBs, RCCBs, Isolators etc.
Brass neutral and earth bars of suitable cross-sectional areas
are provided to facilitate connections for each outgoing ter-
minals.
Adequate number of knockout holes of various sizes are pro-
vided both at the top and the bottom. This facilitate easy
installation and connection of conduits of all sizes, both for
top and bottom.
Detachable upper and lower end plates provided for easy and
fexibility of cabling.
Superior single phase bus bars provided which are com-
pletely insulated and ftted in PVC channel to avoid accidental
touch.
Suitable for both fush and surface mounting.
Conforms to IS 13032 & IEC : 439 & 529
Standard make Smart Distribution Boards provides fexibility
and a systematic approach to ever increasing need for effective
methods of the electrical distributions in domestic, commercial
and industrial application. Standard Smart distribution boards
have been specially designed to meet all the technical require-
ments and ensure the distribution boxes blend with the decor of
the place of the installation.
The Smart distribution boards with their features and their range
offer a compact, practical and economic solution to any electri-
cal network in residential / commercial complexes, industries
etc. having single phase or three phase connections. The Smart
distribution board is not merely an enclosure but a complete
system in itself comprising of ETP Copper bus bar, brass neutral
link, earth link, earthing studs, and interconnection wires for ef-
fective distribution of current.
Features & Benefts
34
DISTRIBUTION BOARDS
S.No. Type Confguration Application
(a) SPN SPN Simple, Economical & Safe distribution
Consumer Simple, Economical & Safe distribution
(b) TPN TPN (Horizontal) Three phase & Neutral incoming and outgoing can be only single phase
Vertical Three phase and neutral incoming, outgoing can be single phase as
well as multi phase
Per Phase Isolation (PPI) DP RCCB in each phase is provided to avoid the total outage as
only the phase where earth leakage fault exist, get isolated.
(c) Special Extended loose Wire Most fexible design
Three Tier Most fexible design
Power Line For fault level higher then 10kA with a provision for MCCB incomer
7 Segment DB Single point distribution where per phase Isolation facility is required
Phase Selector(40&63A) Used for selection of a phase in case other phase fails
Plug & Socket Used for Air conditioner and motor protection
MCB Enclosures To isolate / connect electrical appliances independently
RANGE
SMART DISTRIBUTION BOARDS
Smart board SPN/TPN DBs Single Door
Smart trek SPN/TPN DBs Double Door
Smart line TPN DBs Single Door
NEW ADDITIONAL FEATURES
Masking - (Cement & Water guard)
During the construction stage the DBs can get ingressed with water &
cement dust. This can spoil the decor and more importantly alter the
performance parameters. Standard Smart Trek DBs come with a
masking arrangement that keeps water and cement dust away.
Flexibility during installation
Standard DBs are provided with an intermediate detachable
door/plate fxed on the inner door to give fexibility of installa-
tion i.e. during installation or maintenance the entire door need
not be dismantled thus saving valuable installation time. Ad-
ditionally this also ensures that electrically live parts do not get
exposed.
Reversible Doors
The outer DB doors are reversible. While the doors come ftted
on the left side these can be reversed and ftted on to the right
side by the user.
Weather proof design
All DBs are provided with perfect ftted gaskets which ensures ingress
protection as per IP-42 category.
Reversible door
Intermediate detachable door
Masking (Cement & waterguard)
35
Ways Dimensions Knock Out Dia
DISTRIBUTION BOARDS
SMART BOARD - SINGLE PHASE SINGLE DOOR DBs IP 40 PROTECTION
A B C D Incoming Outgoing
4 145 135 75 225 2 No. 26 2 No. 26
6 182 172 111 225 3 No. 26 3 No. 26
8 217 207 147 225 4 No. 26 4 No. 26
12 289 279 217 225 6 No. 26 6 No. 26
16 361 351 291 225 8 No. 26 8 No. 26
Dimensions (in mm)
Ways Cat No.
4 DSDMSNHOSI04
6 DSDMSNHOSI06
8 DSDMSNHOSI08
12 DSDMSNHOSI12
16 DSDMSNHOSI16
65
D
2
1
5
1
6
5
C
B
10
A
(
f
ix
in
g

c
e
n
t
e
r
)
(fixing center)
36
DISTRIBUTION BOARDS DISTRIBUTION BOARDS
A B C 31
4 266 256 175 4 Nos.
6 336 326 245 6 Nos.
8 406 396 315 8 Nos.
12 546 536 455 12 Nos.
Ways Dimensions Knock Out Dia
SMART LINE - THREE PHASE SINGLE DOOR DBs IP 40 PROTECTION
Dimensions (in mm)
Ways Cat No.
4 DSDMTNHCSI04
6 DSDMTNHCSI06
8 DSDMTNHCSI08
12 DSDMTNHCSI12
(fixing center)
(
f
ix
in
g

c
e
n
t
e
r
)
B
C
3
9
0
3
0
5
A
65
37
DISTRIBUTION BOARDS DISTRIBUTION BOARDS
A B C Incoming Outgoing
2+4 217 207 157 4 No. 26 4 Nos. 26
2+8 289 279 229 1 No. 38 1 No. 38
4 Nos. 26 4 Nos. 26
2+12 361 351 301 1 No. 38 1 No. 38
6 Nos. 26 6 Nos. 26
Ways Dimensions Knock Out Dia
CONSUMER UNIT - IP 40 PROTECTION
Dimensions (in mm)
Ways Cat No.
2+4 DSDCSNHOSI04
2+8 DSDCSNHOSI08
2+12 DSDCSNHOSI12
1
7
1
.
5
2
1
5
.
0
2
2
5
.
0
(
f
ix
in
g

c
e
n
t
e
r
)
(fixing center)
22.0
65.0 C
B
A
A B C 26 38
4 578 560 484 6 No. 1 Nos.
6 632.5 614.5 538.5 6 No. 1 Nos.
8 687 669 593 6 No. 1 Nos.
12 796 778 702 6 No. 1 Nos.
Ways Dimensions Knock Out Dia
Dimensions (in mm)
Ways Cat No.
Single Door Double Door
4 DSDMTNVOSI04 DSDMTNVODI04
8 DSDMTNVOSI08 DSDMTNVODI08
12 DSDMTNVOSI12 DSDMTNVODI12
3.5
A C
270.0
113.0
350.0
367.0
B
(
f
ix
in
g

c
e
n
t
e
r
)
(fixing center)

M
o
u
n
t
in
g

h
o
le




7
.
0
VERTICAL TYPE DBs - IP 42 PROTECTION
38
SQVE SERIES - SPN DOUBLE DOOR DISTRIBUTION BOARD
Ways Cat No.
4 DSDESHODRW04
6 DSDESHODRW06
8 DSDESHODRW08
12 DSDESHODRW12
16 DSDESHODRW16
A
B
3
8
8
4
.
5
C
2
4
4
2
2
2
D
Knockout holes O/G
( 25) knockout holes
on each side
Knockout holes I/C
Dimensions (in mm)
Ways
Dimensions Knockout holes
A B C D
Top Bottom Side (Each
Side) (25) (31) (25) (31)
4 125 175 197 172 3 - 3 - 1
6 151 211 232 166 2 1 2 1 1
8 187 247 268 166 2 2 2 2 1
12 269 319 340 176 4 2 4 2 1
16 341 391 412 172 4 2 4 2 1
39
SQVE SERIES - TPN DOUBLE DOOR DISTRIBUTION BOARD
Ways Cat No.
4 DSDETHODRW04
6 DSDETHODRW06
8 DSDETHODRW08
12 DSDETHODRW12
Knockout holes O/G
Knockout holes I/C
A
B
Knockout holes
each side
C
3
8
9
7
.
5
Dimensions (in mm)
Ways
Dimensions Knockout holes (31)
A B C Top Bottom Side (Each Side)
4 196 251 272 3 3 1
6 268 323 344 2 2 1
8 340 395 416 2 2 1
12 479 534 555 4 4 1
40
PREWIRED DISTRIBUTION BOARD - SPN SINGLE DOOR
Dimensions (in mm)
Ways Cat No.
4 DSDMSHMSIW04000
6 DSDMSHMSIW06000
8 DSDMSHMSIW08000
12 DSDMSHMSIW12000
Ways
Sheet
Thickness
Dimensions Knock out holes
A B C Top Bottom
Side (Each
Side)
4 1.2 206 129 218 4 4 1
6 1.2 278 192 290 5 5 1
8 1.2 278 192 290 5 5 1
12 1.2 345 274 360 6 6 1
B (fixing center) 65
3
7
1
2
9
5

(
f
i
x
i
n
g

c
e
n
t
e
r
)
3
7
2
C
A
41
PREWIRED DISTRIBUTION BOARD - SPN DOUBLE DOOR
Ways Cat No.
4 DSDMSHMDIW04000
6 DSDMSHMDIW06000
8 DSDMSHMDIW08000
12 DSDMSHMDIW12000
Dimensions (in mm)
Ways
Sheet
Thickness
Dimensions Knock out holes
A B C Top Bottom
Side (Each
Side)
4 1.2 206 129 223 3 3 1
6 1.2 278 201 296 5 5 1
8 1.2 278 201 296 7 7 1
12 1.2 350 274 366 9 9 1
B (fixing center) 100
3
9
4
2
9
5

(
F
i
x
i
n
g

c
e
n
t
e
r
)
3
7
2
C
A
42
PREWIRED DISTRIBUTION BOARD - TPN SINGLE DOOR
Ways Cat No.
4 DSDMTHMSIW04000
6 DSDMTHMSIW06000
8 DSDMTHMSIW08000
12 DSDMTHMSIW12000
Dimensions (in mm)
Ways
Sheet
Thickness
Dimensions Knock out holes
A B C Top Bottom
Side (Each
Side)
4 1.2 385 318 400 5 5 0
6 1.2 423 353 437 7 7 0
8 1.2 460 389 472 9 9 0
12 1.2 605 534 618 13 13 0
B (fixing center) 65
6
8
7
6
0
5

(
F
i
x
i
n
g

c
e
n
t
e
r
)
6
7
2
C
A
43
PREWIRED DISTRIBUTION BOARD - TPN DOUBLE DOOR
Ways Cat No.
4 DSDMTHMDIW04000
6 DSDMTHMDIW06000
8 DSDMTHMDIW08000
12 DSDMTHMDIW12000
Dimensions (in mm)
Ways
Sheet
Thickness
Dimensions Knock out holes
A B C Top Bottom
Side (Each
Side)
4 1.2 389 315 410 5 5 0
6 1.2 442 349 445 7 7 0
8 1.2 460 387 482 9 9 0
12 1.2 605 534 624 13 13 0
B (fixing center) 81.0
7
0
2
6
0
5

(
F
i
x
i
n
g

c
e
n
t
e
r
)
6
7
5
C
A
9
6
44
Ways Capacity of Cat No.
17.8 mm module
Incomer + Outgoing
04 4 + (6+12) DSDPTHPDRW04
06 8 + (6+18) DSDPTHPDRW06
08 8 + (6+24) DSDPTHPDRW08
No. of Dimensions Knockout Holes (31)
Ways A B C Top Bottom Side(Each Side)
04 323 268 333 6 6 2
06 395 340 405 8 8 2
No. of Dimensions Knockout Holes (31)
Ways A B C Top Bottom Side(Each Side)
08 557 482 587 11 11 2
Ways Dimensions Knock Out Dia
A B C 26 38
4 578 560 484 6 Nos. 6 Nos.
6 632.5 614.5 538.5 6 Nos. 1 Nos.
8 687 669 593 6 Nos. 1 Nos.
12 796 778 702 6 Nos. 1 Nos.
Dimensions (in mm)
Dimensions (in mm)
Ways Cat No.
4 DSDPVDIBEOTO04
6 DSDPVDIBEOTO06
8 DSDPVDIBEOTO08
12 DSDPVDIBEOTO12
DISTRIBUTION BOARDS DISTRIBUTION BOARDS
POWERLINE VERTICAL TYPE DBs - IP 42 PROTECTION
3.5
A C
270.0
113.0
350.0
367.0
B
(
f
ix
in
g

c
e
n
t
e
r
)
(fixing center)

M
o
u
n
t
in
g

h
o
le




7
.
0
E
88
B
A
7
2
0
C
3
7
5
4
5
0
4
8
0
C
B
C
3
1
0
3
1
0
PER PHASE ISOLATION (PPI) HORIZONTAL DBS - IP 42 PROTECTION
45
Dimensions (in mm)
Ways Capacity of Cat No.
17.8 mm module
Incomer + Outgoing
2 + 12 8 + (6 + 36) DSDPTVPDRW12
No. of Dimensions Knockout Holes (31)
Ways A B C Top Bottom Side
(Each Side)
2 + 12 395 320 405 7 7 6
PER PHASE ISOLATION (PPI) VERTICAL DBs - IP 42 PROTECTION
DISTRIBUTION BOARDS DISTRIBUTION BOARDS
PHASE SELECTOR (HORIZONTAL) DBS - 4 QUADRANT DESIGN (With Rotary Switches & Wires)
PHASE SELECTOR DBS (Without Rotary Switches & Wires)
No. of Rating Cat. No. (DD)
Ways Horizontal
4 40A DSDSCHDRZ04040 With eight way incomer slot
4 63A DSDSCHDRZ04063 With eight way incomer slot
6 40A DSDSCHDRZ06040 With eight way incomer slot
6 63A DSDSCHDRZ06063 With eight way incomer slot
8 40A DSDSCHDRZ08040 With eight way incomer slot
8 63A DSDSCHDRZ08063 With eight way incomer slot
No. of Regal Grey
Ways Cat. No. (DD)
4 DSDSCHDRZ04000
6 DSDSCHDRZ06000
8 DSDSCHDRZ08000
A
B
3
1
0
3
1
1
4
6
0
4
5
0
3
7
5
C
46
DISTRIBUTION BOARDS DISTRIBUTION BOARDS
4 456 320 494 8
6 562 428 602 8
8 672 536 710 8
12 888 752 926 12
Ways A B C Knock Out Holes (31)
7 SEGMENT DBs - IP 42 PROTECTION
Dimensions (in mm)
Ways Cat No.
4 DSDMTHDDRW04
6 DSDMTHDDRW06
8 DSDMTHDDRW08
12 DSDMTHDDRW12
Dimensions (in mm)
PHASE SELECTOR (VERTICAL) DBs DOUBLE DOOR
4 8+12 40A 333 323 248 9 8 9 8 3
4 8+12 63A 333 323 248 9 8 9 8 3
6 8+18 40A 405 395 320 9 8 9 8 3
6 8+18 63A 405 395 320 9 8 9 8 3
8 8+24 40A 405 395 320 9 8 9 8 3
8 8+24 63A 405 395 320 9 8 9 8 3
Ways Capacity of Rating A B C Knockout Holes
17.8 mm module Top Bottom Each Side
Incoming+Outgoing 25 20 25 20 20
No. of Rating Cat. No.
Ways Double Door

4 40A DSDSNVDRZ04040
4 63 A DSDSNVDRZ04063
6 40 A DSDSNVDRZ06040
6 63 A DSDSNVDRZ06063
8 40 A DSDSNVDRZ08040
8 63 A DSDSNVDRZ08063
1
1
1
0
5
5
9
5
6
7
0
6
8
0
A
B
C
3
D- 31 Knockout holes O/G
6W, 8W & 12W
B
A
C
22 22
1
0
2
8
6
8
0
6
5
0
5
5
0
4W
D- 31 Knockout holes O/G
D- 31 Knockout holes O/G D- 31 Knockout holes O/G
6
8
0
6
5
0
5
5
0
B
A
C
22 22
1
0
2
8
47
DISTRIBUTION BOARDS DISTRIBUTION BOARDS
A B C
1/2 140 45 65
3/4 140 81 65
Ways Dimensions
MCB PLASTIC ENCLOSURES
Dimensions (in mm)
Ways Cat No.
DSDEPDP
3/4 DSDEPFP
A B C D E Incoming Outgoing
1 78 64 28 164 150 1Nos. 26 1Nos. 26
2 118 104 49 189 175 1Nos. 26 1Nos. 26
3 118 104 49 189 175 1Nos. 26 1Nos. 26
4 136 122 67 189 175 1Nos. 26 1Nos. 26
Ways Dimensions Knock Out Dia
Dimensions (in mm)
MCB SHEET STEEL ENCLOSURES
Ways (Amp.) Cat No.
1 DSDESSP
2 DSDESDP
3 DSDESTP
4 DSDESFP
C
63.0
1
0
7
.
0
1
2
5
.
0
(
f
ix
in
g

c
e
n
t
e
r
)
(
f
ix
in
g

c
e
n
t
e
r
)
(fixing center) (fixing center)
E
A A
B B (KSS-1+N / 2+N/ 3 /4+N)
(KSS-2+N/ 3+N / 4+N) (KSS-1+N)
53.5
Earth Terminal
C
D D
B C
A
48
PLUG AND SOCKET ENCLOSURES
Rating (Amp.) Cat No.
20A/SPN/DP (AC Box) DSDPUSN020
20A/TP DSDPUTN020
30A/TP DSDPUTN032
Dimensions (in mm)
20 KSPS/SP 133 162 1 No. f 26 1 No. f 26
20 KSPS/TP 123 287 1 No. f 26 1 No. f 26
30 KSPS/TP 123 287 1 No. f 26 1 No. f 26
Rating Item Surface Knockout
Amps. Code Mounting Incoming Outgoing
W L
ACCESSORIES
Neutral Bar/Earth Bar
DIN Channel
Bus Bar with PVC Sleeve
Blanking Plate 1/2
CUSTOMIZED DBs
Prewired DB
Dbs with extended loose wire box
Meter Box (1 Phase & 3 Phase)
ROW TYPE DISTRIBUTION BOARDS
STANDARD make row type distribution boards are versatile in design and aesthetics. These are specially designed for domestic as
well as multi-storey complexes. Keeping in view the capacity usage requirement, these are available in 1,2,3,4 and 5 rows both in
12 module and 16 module versions.
The fush mounting and aesthetic look adds to the grace of interiors. These are supplied duly epoxy powder coated with shade RAL
7035 or as per specifc requirement of the customers.
FEATURES
The DB can be supplied with neutral and earth bars if so required
The enclosures are made of special grade CRCA steel sheet manufactured with latest CNC punch and brake presses to attain higher
degree of perfection.
Adequate number of knockouts at the end plates are provided for ease of wiring.
Din rails are provided for snap mounting of MCBs/RCCBs.
The DB is suitable for IP 40 degree of protection.
2
5
4
.
0
(
f
ix
in
g

c
e
n
t
e
r
)
L
L
2
7
8
.
0
1
1
0
.
0
1
5
2
.
0
TP
SPN
63.0
63.0
56.0
Earth terminal
W
W
49
IP RATINGS
The IP (International Protection) rating given to an enclosure states the degree of protection it offers by means of two digits. A
summary of these is shown below, for a more detaileddeftion, see IEC 529 : 1989, BS EN 60529 : 1992.
FIRST DIGIT
Protection against solid foreign objects and access to hazardous parts.The frst digit covers protection against penetration by solid
objects, which includes hands and tools such as screwdrivers.
At the lowest of seven levels, 0, no protection is offered, either of the equipment itself from damage by intrusion or of a person
contacting live or moving parts. At the highest, there shall be no entry of dust.
SECOND DIGIT
Protection against ingress of water. The second digit covers the degree of protection against the entry of water, on a progressive
scale. for example, number 1 indicates that dripping water shall have no harmful effect, and number 6, that water projected in
powerfuljets against the enclosure from any direction shall have no harmful effects.
The letter X can be used in place of the frst or second digit to indicate that tests have either not been made or are
not applicable.
Protected against strong
jets of water e.g. for use on
ship decks -limited ingress
permitted
Protected against low
pressure jets of water from
all directions -limited ingress
permitted
Protected against after
splashed from all directions
-limited ingress permitted
Protected against sprays of
water up to 60

from the
vertical
Protected against direct
sprays of water up to 15

from
the vertical
Protected against vertically
falling drops of water eg.
condensation
No Protection No Protection 0
1
2
3
4
5
6
0
1
2
3
4
5
6
Protected against solid objects up
to 50 mm. e.g. accidental touch by
hands
Protected against solid objects up to
12 mm e.g. fngers
Protected against solid objects over
2.5 mm e.g. tools and wires
Protected against solid objects over 1
mm e.g. tools, wires and small wires
Protected against dust -limited
ingress, no harmful deposits
Totally protected against
dust.
50
CATEGORY OF DUTY
The category of duty defnes the basic type of circuit and
switching capability of the device, and
selection should be made accordingly.
Utilisation Category Typical Applications
AC20/DC20 Connecting and disconnecting under
no-load.
Assumes all switching operations are
carried out by other capable devices before
this device is operated.
AC21/DC21 Switching of resistive loads including
moderate overloads.
Suitable for purely resistive type loads
devices can switch 150% of its rated
current under fault conditions
Ue = Rated Operational Voltage
The normal line-to-line voltage of the
system should not exceed (Ue)
Ui = Rated Insulation Voltage
The voltage on which the dielectric
properties have conventionally been
based using tests at high voltage and
mains frequency. It is intended to
replace this value with (Uimp)
Uimp = The voltage on which
clearance distances are based.
The value of transient peak voltage
the circuit breaker can withstand from
switching surges or lighting strikes
imposed on the supply.
e.g. Uimp = 8kV, Tested @8kV peak
with
1.2/50m (ms)S impulse wave
In = Rated Current
The current which the circuit breaker
will carry continuously under specifed
conditions and on which the time /
current characteristics are based.
Unless otherwise slated (In) is based
on a reference ambient temperature
of 30 centigrade.
Icu Rated Ultimate Short Circuit
Breaking Capacity
The calculated prospective fault
current at the incoming terminals of
the circuit breaker should not exceed
(Icu).
Exception: Using back-up protection
as specifed by the manufacturer.
Ics Rated Short-time Withstand
Current
The maximum level of fault current
operation after which further service is
assured without loss of performance.
Icw Rated Short-time Withstand
Current
Circuit breakers of utilisation category
B have a short-time delay allowing
time-graded selectivity between
circuit breakers in series.
(Icw) is the current the circuit breaker
will withstand for the maximum short-
time delay time. Preferred times are
0.05, 0.1, 0.25, 0.5 and 1.0 second.
Ui = 660V
Tested@
2500V ac 50Hz
AC22/DC22 Switching of mixed resistive / inductive
loads, including moderate overloads.
Suitable for mixed resistive / inductive
loads. Devices can switch 300% of its
rated current under fault conditions.
AC23/DC23 Switching of highly inductive loads.
Devices complying with AC23/DC23 are
provided mainly as back-up to other means
of switching. e.g. contacts. In the event
of failure of functional devices, an AC23
/ DC23 type device can safety interrupt a
stalled motor current. Where devices are
the only means of controlling individual
motors, they should comply with the
requirements of appendix A of the standard.
(IEC 60947-3)
REPRESENTATIVE OFFICES
Goa Solapur Gwalior Jabalpur Hubli Davanagere Gulbarga Mysore Trichy Kathmandu Sambalpur
Jalandhar Bhopal Calicut Madurai Trivandrum
REGIONAL BRANCH OFFICES
NORTH - REGIONAL OFFICE : Delhi : QRG Towers, 2D, Sector-126, Expressway, Noida-201304
Noida : Tel: 0120-4771000, Fax: 0120-4772000
Chandigarh : Tel: 0172-4232400 -401, Fax: 0172-4232403,
Dehradun : Tel: 0135-2521025, 2521552
Haryana : Tel: 91-120 2477848 / 853, Fax: 0120-2583904
Noida : Tel: 0120-3055609 / 3055610, Fax: 0120-3055611
Ludhiana : Tel: 0161-4676001 / 6024, Fax: 0161-46766007
Jammu : Tel:0191-2490424, Fax: 0191-2490405
Jaipur : Tel: 0141-3988210, Fax: 0141-2389024
Lucknow : Tel: 0522-2201032, 2200938
Kanpur : Tel: Airtel: 09935533751/52/53, 0512-2690128/129/130, Fax: 0512-2692800
EAST - REGIONAL OFFICE : Kolkata : ICC Tower, 5th Floor, 4 India Exchange Place, Kolkata-700 001
Kolkata : Tel: 033-40129851/52, Fax: 033-40127339
Bhubaneshwar : Tel: 0674-2598104, 2598105, 2598106, Fax: 0674-2598107
Guwahati : Tel: 0361-2134521, 2458923, Fax: 0361-2460355
Siliguri : Tel: 0353-2525907-3290402 (RIM)
Jamshedpur : Tel: 0657-6542492, 09234369436
Patna : Tel: 0612-3244218, 2655519, Telefax: 0612-2655518

WEST - REGIONAL OFFICE : Mumbai : 302, Boston House, 3rd Floor Suren Road, CTS No. 260/261, Andheri
(E), Mumbai-400 093
Mumbai : Tel: 022-67298600-603
Ahmedabad : Tel: 079-40061111, 40060738-740, Fax: 079-40060741
Indore : Tel: 0731-2572340-41, 4009998 (Airtel), Fax: 0731-2551626
Rajkot : Tel: 0281 3013289 / 3013290
Nagpur : Tel: 0712-2224132, 2222692, 2222029
Pune : Tel: 020-64016413/14
Raipur : Tel: 0771-4243400 / 01, Telefax: 0771-4243402
Surat : Telefax: 0261-2350137
SOUTH - REGIONAL OFFICE : Chennai : Block 1, A & D Wing, Shakthi Towers, 7th Floor, 766, Annna Salai,
Chennai-600 002
Chennai : Tel: 044-28526941-44, Fax: 044-28524326
Bangalore : Tel: 080-39882100, 30515801 / 2 / 3 /4, Fax: 080-30515804
Coimbatore : Telefax: 0422-2305767, 2306199, 2305199
Hyderabad : Tel: 040-27533372, 27533355, 27533632, 66320407/0408/6401/6402, Fax: 040-27533211
Kochi : Tel: 0484-4099000, 2393165, 2393068, Fax: 0484-2393170
Vishakapatnam : Tel: 0891-6514339, Fax: 0891-2522547
STANDARD ELECTRICAL LIMITED
Corporate Ofce: QRG Towers, 2D, Sector -126, Expressway, Noida - 201 304 (UP),
Ph. +91-120-4771000, India E-mail: standard.ho@sel.co.in
Consumer Care No.: 1800 11 0303 (Toll Free), 011-41 66 0303 (Landline), 1800 103 1313 (All connections)
Registered Ofce: 1/7, Ram Kishore Road, Civil Lines, Delhi - 110054
Visit us at : www.sel.co.in
For International Trade Enquires, please E-mail to: export.sel@sel.co.in