Algo-Tec 6300 INTERACTIVE
ADDRESSABLE FIRE CONTROL
SYSTEM
(1-4 LOOPS)

LOOP COMMISSIONING MANUAL


CUSTOMER DETAILS
Customer / Company Name :
Customer / Company Address :
Customer Order Number :
SITE DETAILS
Site Name :
Site Address :
EQUIPMENT DETAILS
Panel Location :
Technical Help
Please contact : Technical Support Department
Protec Fire Detection
Protec House
Churchill Way
Nelson
Lancs
BB9 6RT
e-mail : technical@protec.co.uk
Telephone : (01282) 717444
Technical Support & Training
Protec Fire Detection plc 6300 Loop Commissioning Manual 93-507-07 Issue 2
Please refer to the following diagram:-
Device
Loop Commissioning Manual
Add Address Serial No
*L1001*
001
*L1002*
002
A guide on how to attach Bar-codes to the Algo-Tec 6300 Loop Commissioning Manual
Loop 1 of 4
Remove the 'Device Bar-code' label (WHITE) and place
next to the appropiate address INPUT number on the
following sheets
Leave
blank
INPUT DEVICE
Not
Used
INPUT DEVICE
Not
Used
Leave
blank
Rear of
6000PLUS
device
Device Bar-code label
Protec Fire Detection plc 6300 Loop Commissioning Manual 93-507-07 Issue 2
LOOP 1 of 4 6300 Loop Commissioning Manual
Add Address Serial No Add Address Serial No Add Address Serial No
*L1001* *L1009* *L1017*
001 009 017
*L1002* *L1010* *L1018*
002 010 018
*L1003* *L1011* *L1019*
003 011 019
*L1004* *L1012* *L1020*
004 012 020
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
*L1005* *L1013* *L1021*
005 013 021
*L1006* *L1014* *L1022*
006 014 022
*L1007* *L1015* *L1023*
007 015 023
*L1008* *L1016* *L1024*
008 016 024
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
Protec Fire Detection plc 6300 Loop Commissioning Manual 93-507-07 Issue 2
LOOP 1 of 4 6300 Loop Commissioning Manual
Add Address Serial No Add Address Serial No Add Address Serial No
*L1025* *L1033* *L1041*
025 033 041
*L1026* *L1034* *L1042*
026 034 042
*L1027* *L1035* *L1043*
027 035 043
*L1028* *L1036* *L1044*
028 036 044
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
*L1029* *L1037* *L1045*
029 037 045
*L1030* *L1038* *L1046*
030 038 046
*L1031* *L1039* *L1047*
031 039 047
*L1032* *L1040* *L1048*
032 040 048
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
Protec Fire Detection plc 6300 Loop Commissioning Manual 93-507-07 Issue 2
LOOP 1 of 4 6300 Loop Commissioning Manual
Add Address Serial No Add Address Serial No Add Address Serial No
*L1049* *L1057* *L1065*
049 057 065
*L1050* *L1058* *L1066*
050 058 066
*L1051* *L1059* *L1067*
051 059 067
*L1052* *L1060* *L1068*
052 060 068
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
*L1053* *L1061* *L1069*
053 061 069
*L1054* *L1062* *L1070*
054 062 070
*L1055* *L1063* *L1071*
055 063 071
*L1056* *L1064* *L1072*
056 064 072
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
Protec Fire Detection plc 6300 Loop Commissioning Manual 93-507-07 Issue 2
LOOP 1 of 4 6300 Loop Commissioning Manual
Add Address Serial No Add Address Serial No Add Address Serial No
*L1073* *L1081* *L1089*
073 081 089
*L1074* *L1082* *L1090*
074 082 090
*L1075* *L1083* *L1091*
075 083 091
*L1076* *L1084* *L1092*
076 084 092
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
*L1077* *L1085* *L1093*
077 085 093
*L1078* *L1086* *L1094*
078 086 094
*L1079* *L1087* *L1095*
079 087 095
*L1080* *L1088* *L1096*
080 088 096
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
Protec Fire Detection plc 6300 Loop Commissioning Manual 93-507-07 Issue 2
LOOP 1 of 4 6300 Loop Commissioning Manual
Add Address Serial No Add Address Serial No Add Address Serial No
*L1097* *L1105* *L1113*
097 105 113
*L1098* *L1106* *L1114*
098 106 114
*L1099* *L1107* *L1115*
099 107 115
*L1100* *L1108* *L1116*
100 108 116
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
*L1101* *L1109* *L1117*
101 109 117
*L1102* *L1110* *L1118*
102 110 118
*L1103* *L1111* *L1119*
103 111 119
*L1104* *L1112* *L1120*
104 112 120
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
Protec Fire Detection plc 6300 Loop Commissioning Manual 93-507-07 Issue 2
LOOP 1 of 4 6300 Loop Commissioning Manual
Add Address Serial No Add Address Serial No Add Address Serial No
*L1121* *L1129* *L1137*
121 129 137
*L1122* *L1130* *L1138*
122 130 138
*L1123* *L1131* *L1139*
123 131 139
*L1124* *L1132* *L1140*
124 132 140
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
*L1125* *L1133* *L1141*
125 133 141
*L1126* *L1134* *L1142*
126 134 142
*L1127* *L1135* *L1143*
127 135 143
*L1128* *L1136* *L1144*
128 136 144
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
Protec Fire Detection plc 6300 Loop Commissioning Manual 93-507-07 Issue 2
LOOP 1 of 4 6300 Loop Commissioning Manual
Add Address Serial No Add Address Serial No Add Address Serial No
*L1145* *L1153* *L1161*
145 153 161
*L1146* *L1154* *L1162*
146 154 162
*L1147* *L1155* *L1163*
147 155 163
*L1148* *L1156* *L1164*
148 156 164
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
*L1149* *L1157* *L1165*
149 157 165
*L1150* *L1158* *L1166*
150 158 166
*L1151* *L1159* *L1167*
151 159 167
*L1152* *L1160* *L1168*
152 160 168
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
Protec Fire Detection plc 6300 Loop Commissioning Manual 93-507-07 Issue 2
LOOP 1 of 4 6300 Loop Commissioning Manual
Add Address Serial No Add Address Serial No Add Address Serial No
*L1169* *L1177* *L1185*
169 177 185
*L1170* *L1178* *L1186*
170 178 186
*L1171* *L1179* *L1187*
171 179 187
*L1172* *L1180* *L1188*
172 180 188
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
*L1173* *L1181* *L1189*
173 181 189
*L1174* *L1182* *L1190*
174 182 190
*L1175* *L1183* *L1191*
175 183 191
*L1176* *L1184*
176 184
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE
Protec Fire Detection plc 6300 Loop Commissioning Manual 93-507-07 Issue 2
LOOP 2 of 4 6300 Loop Commissioning Manual
Add Address Serial No Add Address Serial No Add Address Serial No
*L2001* *L2009* *L2017*
001 009 017
*L2002* *L2010* *L2018*
002 010 018
*L2003* *L2011* *L2019*
003 011 019
*L2004* *L2012* *L2020*
004 012 020
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
*L2005* *L2013* *L2021*
005 013 021
*L2006* *L2014* *L2022*
006 014 022
*L2007* *L2015* *L2023*
007 015 023
*L2008* *L2016* *L2024*
008 016 024
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
Protec Fire Detection plc 6300 Loop Commissioning Manual 93-507-07 Issue 2
LOOP 2 of 4 6300 Loop Commissioning Manual
Add Address Serial No Add Address Serial No Add Address Serial No
*L2025* *L2033* *L2041*
025 033 041
*L2026* *L2034* *L2042*
026 034 042
*L2027* *L2035* *L2043*
027 035 043
*L2028* *L2036* *L2044*
028 036 044
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
*L2029* *L2037* *L2045*
029 037 045
*L2030* *L2038* *L2046*
030 038 046
*L2031* *L2039* *L2047*
031 039 047
*L2032* *L2040* *L2048*
032 040 048
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
Protec Fire Detection plc 6300 Loop Commissioning Manual 93-507-07 Issue 2
LOOP 2 of 4 6300 Loop Commissioning Manual
Add Address Serial No Add Address Serial No Add Address Serial No
*L2049* *L2057* *L2065*
049 057 065
*L2050* *L2058* *L2066*
050 058 066
*L2051* *L2059* *L2067*
051 059 067
*L2052* *L2060* *L2068*
052 060 068
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
*L2053* *L2061* *L2069*
053 061 069
*L2054* *L2062* *L2070*
054 062 070
*L2055* *L2063* *L2071*
055 063 071
*L2056* *L2064* *L2072*
056 064 072
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
Protec Fire Detection plc 6300 Loop Commissioning Manual 93-507-07 Issue 2
LOOP 2 of 4 6300 Loop Commissioning Manual
Add Address Serial No Add Address Serial No Add Address Serial No
*L2073* *L2081* *L2089*
073 081 089
*L2074* *L2082* *L2090*
074 082 090
*L2075* *L2083* *L2091*
075 083 091
*L2076* *L2084* *L2092*
076 084 092
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
*L2077* *L2085* *L2093*
077 085 093
*L2078* *L2086* *L2094*
078 086 094
*L2079* *L2087* *L2095*
079 087 095
*L2080* *L2088* *L2096*
080 088 096
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
Protec Fire Detection plc 6300 Loop Commissioning Manual 93-507-07 Issue 2
LOOP 2 of 4 6300 Loop Commissioning Manual
Add Address Serial No Add Address Serial No Add Address Serial No
*L2097* *L2105* *L2113*
097 105 113
*L2098* *L2106* *L2114*
098 106 114
*L2099* *L2107* *L2115*
099 107 115
*L2100* *L2108* *L2116*
100 108 116
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
*L2101* *L2109* *L2117*
101 109 117
*L2102* *L2110* *L2118*
102 110 118
*L2103* *L2111* *L2119*
103 111 119
*L2104* *L2112* *L2120*
104 112 120
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
Protec Fire Detection plc 6300 Loop Commissioning Manual 93-507-07 Issue 2
LOOP 2 of 4 6300 Loop Commissioning Manual
Add Address Serial No Add Address Serial No Add Address Serial No
*L2121* *L2129* *L2137*
121 129 137
*L2122* *L2130* *L2138*
122 130 138
*L2123* *L2131* *L2139*
123 131 139
*L2124* *L2132* *L2140*
124 132 140
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
*L2125* *L2133* *L2141*
125 133 141
*L2126* *L2134* *L2142*
126 134 142
*L2127* *L2135* *L2143*
127 135 143
*L2128* *L2136* *L2144*
128 136 144
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
Protec Fire Detection plc 6300 Loop Commissioning Manual 93-507-07 Issue 2
LOOP 2 of 4 6300 Loop Commissioning Manual
Add Address Serial No Add Address Serial No Add Address Serial No
*L2145* *L2153* *L2161*
145 153 161
*L2146* *L2154* *L2162*
146 154 162
*L2147* *L2155* *L2163*
147 155 163
*L2148* *L2156* *L2164*
148 156 164
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
*L2149* *L2157* *L2165*
149 157 165
*L2150* *L2158* *L2166*
150 158 166
*L2151* *L2159* *L2167*
151 159 167
*L2152* *L2160* *L2168*
152 160 168
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
Protec Fire Detection plc 6300 Loop Commissioning Manual 93-507-07 Issue 2
LOOP 2 of 4 6300 Loop Commissioning Manual
Add Address Serial No Add Address Serial No Add Address Serial No
*L2169* *L2177* *L2185*
169 177 185
*L2170* *L2178* *L2186*
170 178 186
*L2171* *L2179* *L2187*
171 179 187
*L2172* *L2180* *L2188*
172 180 188
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
*L2173* *L2181* *L2189*
173 181 189
*L2174* *L2182* *L2190*
174 182 190
*L2175* *L2183* *L2191*
175 183 191
*L2176* *L2184*
176 184
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE
Protec Fire Detection plc 6300 Loop Commissioning Manual 93-507-07 Issue 2
LOOP 3 of 4 6300 Loop Commissioning Manual
Add Address Serial No Add Address Serial No Add Address Serial No
*L3001* *L3009* *L3017*
001 009 017
*L3002* *L3010* *L3018*
002 010 018
*L3003* *L3011* *L3019*
003 011 019
*L3004* *L3012* *L3020*
004 012 020
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
*L3005* *L3013* *L3021*
005 013 021
*L3006* *L3014* *L3022*
006 014 022
*L3007* *L3015* *L3023*
007 015 023
*L3008* *L3016* *L3024*
008 016 024
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
Protec Fire Detection plc 6300 Loop Commissioning Manual 93-507-07 Issue 2
LOOP 3 of 4 6300 Loop Commissioning Manual
Add Address Serial No Add Address Serial No Add Address Serial No
*L3025* *L3033* *L3041*
025 033 041
*L3026* *L3034* *L3042*
026 034 042
*L3027* *L3035* *L3043*
027 035 043
*L3028* *L3036* *L3044*
028 036 044
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
*L3029* *L3037* *L3045*
029 037 045
*L3030* *L3038* *L3046*
030 038 046
*L3031* *L3039* *L3047*
031 039 047
*L3032* *L3040* *L3048*
032 040 048
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
Protec Fire Detection plc 6300 Loop Commissioning Manual 93-507-07 Issue 2
LOOP 3 of 4 6300 Loop Commissioning Manual
Add Address Serial No Add Address Serial No Add Address Serial No
*L3049* *L3057* *L3065*
049 057 065
*L3050* *L3058* *L3066*
050 058 066
*L3051* *L3059* *L3067*
051 059 067
*L3052* *L3060* *L3068*
052 060 068
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
*L3053* *L3061* *L3069*
053 061 069
*L3054* *L3062* *L3070*
054 062 070
*L3055* *L3063* *L3071*
055 063 071
*L3056* *L3064* *L3072*
056 064 072
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
Protec Fire Detection plc 6300 Loop Commissioning Manual 93-507-07 Issue 2
LOOP 3 of 4 6300 Loop Commissioning Manual
Add Address Serial No Add Address Serial No Add Address Serial No
*L3073* *L3081* *L3089*
073 081 089
*L3074* *L3082* *L3090*
074 082 090
*L3075* *L3083* *L3091*
075 083 091
*L3076* *L3084* *L3092*
076 084 092
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
*L3077* *L3085* *L3093*
077 085 093
*L3078* *L3086* *L3094*
078 086 094
*L3079* *L3087* *L3095*
079 087 095
*L3080* *L3088* *L3096*
080 088 096
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
Protec Fire Detection plc 6300 Loop Commissioning Manual 93-507-07 Issue 2
LOOP 3 of 4 6300 Loop Commissioning Manual
Add Address Serial No Add Address Serial No Add Address Serial No
*L3097* *L3105* *L3113*
097 105 113
*L3098* *L3106* *L3114*
098 106 114
*L3099* *L3107* *L3115*
099 107 115
*L3100* *L3108* *L3116*
100 108 116
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
*L3101* *L3109* *L3117*
101 109 117
*L3102* *L3110* *L3118*
102 110 118
*L3103* *L3111* *L3119*
103 111 119
*L3104* *L3112* *L3120*
104 112 120
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
Protec Fire Detection plc 6300 Loop Commissioning Manual 93-507-07 Issue 2
LOOP 3 of 4 6300 Loop Commissioning Manual
Add Address Serial No Add Address Serial No Add Address Serial No
*L3121* *L3129* *L3137*
121 129 137
*L3122* *L3130* *L3138*
122 130 138
*L3123* *L3131* *L3139*
123 131 139
*L3124* *L3132* *L3140*
124 132 140
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
*L3125* *L3133* *L3141*
125 133 141
*L3126* *L3134* *L3142*
126 134 142
*L3127* *L3135* *L3143*
127 135 143
*L3128* *L3136* *L3144*
128 136 144
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
Protec Fire Detection plc 6300 Loop Commissioning Manual 93-507-07 Issue 2
LOOP 3 of 4 6300 Loop Commissioning Manual
Add Address Serial No Add Address Serial No Add Address Serial No
*L3145* *L3153* *L3161*
145 153 161
*L3146* *L3154* *L3162*
146 154 162
*L3147* *L3155* *L3163*
147 155 163
*L3148* *L3156* *L3164*
148 156 164
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
*L3149* *L3157* *L3165*
149 157 165
*L3150* *L3158* *L3166*
150 158 166
*L3151* *L3159* *L3167*
151 159 167
*L3152* *L3160* *L3168*
152 160 168
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
Protec Fire Detection plc 6300 Loop Commissioning Manual 93-507-07 Issue 2
LOOP 3 of 4 6300 Loop Commissioning Manual
Add Address Serial No Add Address Serial No Add Address Serial No
*L3169* *L3177* *L3185*
169 177 185
*L3170* *L3178* *L3186*
170 178 186
*L3171* *L3179* *L3187*
171 179 187
*L3172* *L3180* *L3188*
172 180 188
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
*L3173* *L3181* *L3189*
173 181 189
*L3174* *L3182* *L3190*
174 182 190
*L3175* *L3183* *L3191*
175 183 191
*L3176* *L3184*
176 184
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE
Protec Fire Detection plc 6300 Loop Commissioning Manual 93-507-07 Issue 2
LOOP 4 of 4 6300 Loop Commissioning Manual
Add Address Serial No Add Address Serial No Add Address Serial No
*L4001* *L4009* *L4017*
001 009 017
*L4002* *L4010* *L4018*
002 010 018
*L4003* *L4011* *L4019*
003 011 019
*L4004* *L4012* *L4020*
004 012 020
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
*L4005* *L4013* *L4021*
005 013 021
*L4006* *L4014* *L4022*
006 014 022
*L4007* *L4015* *L4023*
007 015 023
*L4008* *L4016* *L4024*
008 016 024
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
Protec Fire Detecion plc 6300 Loop Commissioning Manaul 93-507-07 Issue 2
LOOP 4 of 4 6300 Loop Commissioning Manual
Add Address Serial No Add Address Serial No Add Address Serial No
*L4025* *L4033* *L4041*
025 033 041
*L4026* *L4034* *L4042*
026 034 042
*L4027* *L4035* *L4043*
027 035 043
*L4028* *L4036* *L4044*
028 036 044
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
*L4029* *L4037* *L4045*
029 037 045
*L4030* *L4038* *L4046*
030 038 046
*L4031* *L4039* *L4047*
031 039 047
*L4032* *L4040* *L4048*
032 040 048
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
Protec Fire Detecion plc 6300 Loop Commissioning Manaul 93-507-07 Issue 2
LOOP 4 of 4 6300 Loop Commissioning Manual
Add Address Serial No Add Address Serial No Add Address Serial No
*L4049* *L4057* *L4065*
049 057 065
*L4050* *L4058* *L4066*
050 058 066
*L4051* *L4059* *L4067*
051 059 067
*L4052* *L4060* *L4068*
052 060 068
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
*L4053* *L4061* *L4069*
053 061 069
*L4054* *L4062* *L4070*
054 062 070
*L4055* *L4063* *L4071*
055 063 071
*L4056* *L4064* *L4072*
056 064 072
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
Protec Fire Detecion plc 6300 Loop Commissioning Manaul 93-507-07 Issue 2
LOOP 4 of 4 6300 Loop Commissioning Manual
Add Address Serial No Add Address Serial No Add Address Serial No
*L4073* *L4081* *L4089*
073 081 089
*L4074* *L4082* *L4090*
074 082 090
*L4075* *L4083* *L4091*
075 083 091
*L4076* *L4084* *L4092*
076 084 092
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
*L4077* *L4085* *L4093*
077 085 093
*L4078* *L4086* *L4094*
078 086 094
*L4079* *L4087* *L4095*
079 087 095
*L4080* *L4088* *L4096*
080 088 096
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
Protec Fire Detecion plc 6300 Loop Commissioning Manaul 93-507-07 Issue 2
LOOP 4 of 4 6300 Loop Commissioning Manual
Add Address Serial No Add Address Serial No Add Address Serial No
*L4097* *L4105* *L4113*
097 105 113
*L4098* *L4106* *L4114*
098 106 114
*L4099* *L4107* *L4115*
099 107 115
*L4100* *L4108* *L4116*
100 108 116
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
*L4101* *L4109* *L4117*
101 109 117
*L4102* *L4110* *L4118*
102 110 118
*L4103* *L4111* *L4119*
103 111 119
*L4104* *L4112* *L4120*
104 112 120
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
Protec Fire Detecion plc 6300 Loop Commissioning Manaul 93-507-07 Issue 2
LOOP 4 of 4 6300 Loop Commissioning Manual
Add Address Serial No Add Address Serial No Add Address Serial No
*L4121* *L4129* *L4137*
121 129 137
*L4122* *L4130* *L4138*
122 130 138
*L4123* *L4131* *L4139*
123 131 139
*L4124* *L4132* *L4140*
124 132 140
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
*L4125* *L4133* *L4141*
125 133 141
*L4126* *L4134* *L4142*
126 134 142
*L4127* *L4135* *L4143*
127 135 143
*L4128* *L4136* *L4144*
128 136 144
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
Protec Fire Detecion plc 6300 Loop Commissioning Manaul 93-507-07 Issue 2
LOOP 4 of 4 6300 Loop Commissioning Manual
Add Address Serial No Add Address Serial No Add Address Serial No
*L4145* *L4153* *L4161*
145 153 161
*L4146* *L4154* *L4162*
146 154 162
*L4147* *L4155* *L4163*
147 155 163
*L4148* *L4156* *L4164*
148 156 164
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
*L4149* *L4157* *L4165*
149 157 165
*L4150* *L4158* *L4166*
150 158 166
*L4151* *L4159* *L4167*
151 159 167
*L4152* *L4160* *L4168*
152 160 168
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
Protec Fire Detecion plc 6300 Loop Commissioning Manaul 93-507-07 Issue 2
LOOP 4 of 4 6300 Loop Commissioning Manual
Add Address Serial No Add Address Serial No Add Address Serial No
*L4169* *L4177* *L4185*
169 177 185
*L4170* *L4178* *L4186*
170 178 186
*L4171* *L4179* *L4187*
171 179 187
*L4172* *L4180* *L4188*
172 180 188
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
*L4173* *L4181* *L4189*
173 181 189
*L4174* *L4182* *L4190*
174 182 190
*L4175* *L4183* *L4191*
175 183 191
*L4176* *L4184*
176 184
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
INPUT DEVICE
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Not
Used
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
Leave
blank
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE INPUT DEVICE
INPUT DEVICE
Protec Fire Detecion plc 6300 Loop Commissioning Manaul 93-507-07 Issue 2

N 93-572-88 ISSUE 0 NH Page 2 of 2 Protec Fire Detection PLC 2012































































Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT.

Telephone: +44 (0) 1282 717171
Fax: +44 (0) 1282 717273
Web: www.protec.co.uk
Email: sales@protec.co.uk

You might also like