19 temperzone limited 2001

100 120 140 160 180 200


0
50
100
150
AIR FLOW (l/s)
A
V
A
I
L
A
B
L
E

E
X
T
E
R
N
A
L

P
R
E
S
S
U
R
E

(
P
a
)
I
N
P
U
T

(
w
a
t
t
s
)
100
80
60
MED
HIGH
LOW
LOW
90
70
Nominal
HIGH
MED
0.41A
0.28A
0.46A
0.26A
0.30A
0.36A
Nominal Airflow: 205 l/s
IMDL 40-H
l/s - Pa - - - - l/s - W
Air Handling Sound Levels
Test Conditions: JIS 8616. 1 m ducting with 25 mm insulation.
Sound Pressure Levels are at 1 m from source.
Note: Return air plenum, filter and standard supply air spigot attached.
550
5
0
0

M
I
N
.

C
L
E
A
R
A
N
C
E
100
DRAIN
19 OD
ELECTRICAL
BOX
WATER
CONN'S
IN
OUT
S/A SPIGOT
225
MTG CTR
525
MTG CTR
675
OVERALL
250
OVERALL
640
OVERALL
SUPPLY AIR SPIGOT
512 x 170
Dimensions (mm)
Standard Unit
Not to Scale Right Handed models shown
Standard Unit with Return Air Plenum
& Multi-Outlet Supply Air Spigot
550
(HEIGHT = 245)
5
0
0

M
I
N
.

C
L
E
A
R
A
N
C
E
100
DRAIN
19 OD
ELECTRICAL
BOX
WATER
CONN'S
IN
OUT
FILTER
ACCESS VIA
EITHER SIDE,
OR LIFT OUT
SPIGOTS TO SUIT 200 DIA.
FLEXIBLE DUCTING
680
OVERALL
675
OVERALL
250
OVERALL
470
MTG CTR
525
MTG CTR
SOUND POWER LEVELS dB
OCTAVE BAND FREQ. Hz
500 1 k 2 k 4 k 250 125 FAN
SPEED
SPL
dB(A)
Cooling Capacity (kW)
Entering Air Temperature 23C D.B., 17C W.B.
5 6 7 8 9
ENTERING WATER TEMPERATURE C
COIL Total Sens. Total Sens. Total Sens. Total Sens. Total Sens.
3.3 2.3 3.0 2.3 2.8 2.2 2.5 2.1 2.3 2.0
3.9 2.6 3.6 2.5 3.3 2.4 3.0 2.2 2.7 2.1
4.3 2.8 3.9 2.6 3.6 2.5 3.3 2.4 2.9 2.2
4.2 2.7 3.9 2.6 3.6 2.5 3.3 2.4 3.0 2.2
4.9 3.0 4.6 2.9 4.2 2.7 3.9 2.6 3.5 2.4
5.3 3.2 4.9 3.0 4.6 2.9 4.2 2.7 3.7 2.5
PRESSURE
DROP
(kPa)
WATER
FLOW
(l/s)
Total = Total Capacity (kW); Sens. = Sensible Capacity (kW)
Note: Cooling capacities are based on the nominal airflow.
3 ROWS
0.12
0.19
0.26
0.15
0.25
0.35
7.6
17.6
30.0
6.6
16.3
30.0
4 ROWS
Heating Capacity (kW)
Entering Air Temperature 21C
ENTERING WATER TEMPERATURE C
COIL 40 45 50 55 60 65 70 75 80
1.3 1.6 2.0 2.3 2.6 3.0 3.3 3.7 4.0
1.5 1.9 2.3 2.7 3.1 3.5 3.8 4.2 4.6
1.6 2.0 2.4 2.9 3.3 3.7 4.1 4.5 5.0
PRESSURE
DROP
(kPa)
WATER
FLOW
(l/s)
Note: Heating capacities are total - based on the nominal airflow. Electric Heating option: 1.5 kW
1 ROW
0.04
0.07
0.10
6.4
17.4
33.0
Note:
1. Air flows given are for a standard unit with
rectangular supply air spigot and no filter installed.
2. In a free blow application, beware of exceeding
indoor fan motor's full load amp limit.
SWL
dB(A)
LOW 34 44 47 46 43 37 32 25
MED 36 46 48 49 45 39 36 28
HIGH 39 49 53 52 47 42 38 31