Atlas Copco Airpower NV

ELEKTRONIKON MkIV
User Guide : Elektronikon MkIV Modbus
Name
User Guide : Elektronikon MkIV Modbus
Secr. Class
1102 K/1
Detail
PC
Owner
AII
Edition
01
Modified from :
print date
31/01/03
Family Written By
CTE
Compare Replaces Designation
Design Checked Product Checked Approved Date
19/07/2002 9820 3582 02
User Guide : Elektronikon MkIV Modbus
ii
Document Information
Edition Date Description Author
00 01/08/2002 First edition CTE
01 14/01/2003 Second edition CTE-PDJ
Added exception code Command Refused (07)
.. Added exception code Reprogrammed Refused (06)
User Guide : Elektronikon MkIV Modbus
iii
Preface
This document describes how to implement a Modbus connection to the Elektronikon MkIV compressor controller
network.

User Guide : Elektronikon MkIV Modbus
iv
Table of Contents
1. The Physical set-up ___________________________________________________________6
1.1 Modbus & the Network __________________________________________________________6
1.2 The Module (Combox-S) _________________________________________________________8
1.3 LEDs_________________________________________________________________________9
1.4 Connector lay-out ______________________________________________________________10
1.4.1 Power Supply _____________________________________________________________________ 10
1.4.2 LAN connector ____________________________________________________________________ 10
1.4.3 Modbus connection_________________________________________________________________ 10
Pin Assignment Modbus _________________________________________________________________ 10
1.5 RS485 connections _____________________________________________________________11
1.5.1 Modbus with MKIV________________________________________________________________ 11
1.5.2 Modbus with MKIV and MKIII_______________________________________________________ 12
1.5.3 Modbus with MKIV and Other Equipment ______________________________________________ 13
1.6 Software downloading __________________________________________________________14
2. Modbus protocol implementation_______________________________________________15
2.1 Supported modbus specification _________________________________________________15
2.2 Supported Modbus functions ____________________________________________________15
2.3 Modbus registers and coils for Data Reading _______________________________________16
2.3.1 System Overview __________________________________________________________________ 16
2.3.1.1 General Compressor Condition______________________________________________________ 16
2.3.1.2 Detailed General Compressor Condition ______________________________________________ 17
2.3.2 Inputs & Outputs___________________________________________________________________ 18
2.3.2.1 Analogue Inputs Sensors & Calculated ______________________________________________ 18
2.3.2.2 Registers _______________________________________________________________________ 18
2.3.2.3 Status register Interpretation ______________________________________________________ 19
2.3.2.4 Value register Interpretation ______________________________________________________ 19
2.3.2.4.1 Pressure Input ________________________________________________________________ 19
2.3.2.4.2 Temperature Input_____________________________________________________________ 19
2.3.2.4.3 Vibration Input _______________________________________________________________ 19
2.3.2.4.4 Level Input __________________________________________________________________ 19
2.3.2.4.5 Conductivity Input ____________________________________________________________ 19
2.3.2.4.6 SPM Input ___________________________________________________________________ 19
2.3.2.4.7 Current Input_________________________________________________________________ 20
2.3.2.4.8 Speed Input __________________________________________________________________ 20
2.3.2.5 Digital (Voltage free contacts) Inputs _________________________________________________ 20
2.3.2.6 Status register Interpretation ______________________________________________________ 20
2.3.2.7 Value register Interpretation ______________________________________________________ 20
2.3.2.8 Digital (Relays) Output (Not Yet Implemented)_________________________________________ 20
2.3.3 Counters _________________________________________________________________________ 21
2.3.3.1 Compressor Counters _____________________________________________________________ 21
2.3.3.2 Multi Compressor Controller Counters________________________________________________ 22
2.3.4 Special __________________________________________________________________________ 23
2.3.4.1 VSD motor data _________________________________________________________________ 23
2.4 Modbus registers and coils for parameters change __________________________________24
2.4.1 Load/Unload Pressure Band change ____________________________________________________ 24
2.4.2 VSD Setpoint change _______________________________________________________________ 24
2.4.3 MCC Pressure Band change __________________________________________________________ 25
2.5 Modbus registers and coils for remote control ______________________________________26
2.5.1 Control Commands _________________________________________________________________ 26
2.5.1.1 Compressor Control Mode Selection _________________________________________________ 26
User Guide : Elektronikon MkIV Modbus
v
2.5.1.2 Compressor Commands ___________________________________________________________ 26
2.5.2 VSD external setpoint/speed control __________________________________________________ 27
2.5.3 Reset Initial Settings (Analogue , Digital , Counter Inputs) __________________________________ 27
2.6 Communication examples _______________________________________________________28
2.6.1 Analogue - Digital Inputs ____________________________________________________________ 28
2.6.2 Commands description ______________________________________________________________ 29
2.6.3 Present System Status _______________________________________________________________ 29
2.6.4 Loopback Test ____________________________________________________________________ 30
3. Exception Responses _________________________________________________________31
3.1 Function Code Data Field______________________________________________________31
3.2 Exception Codes _______________________________________________________________31
3.3 Example______________________________________________________________________31
User Guide : Elektronikon MkIV Modbus
- 6 -
1. The Physical set-up
1.1 Modbus & the Network
In the Elektronikon MkIV system all compressors in an installation can be connected by a data and/or control
network. This is done according the Compressor Network Cabling Instruction (9820 3585 00). This instruction
explains what connectors and cables should be used to interconnect the different compressors/controllers in the
network. Basically this is a CAN-based local network.
In order to setup a modbus connection to one or several of the compressors in this network, a special module as to
be inserted in this network.
This module will then behave as a modbus-proxy that allows access to all compressors in the network, whereby
each compressor has its own modbus address (proxy concept).
User Guide : Elektronikon MkIV Modbus
- 7 -
In this drawing the proxy is used to access the compressors with Node Id 1,2 and 5, by using the modbus addresses
4,8 and 10. (This proxy-conversion table has to be set with proper tools). The Node Id the Proxy itself if 11 on the
CAN side.
Modbus
Customer PLC
Atlas Copcos
Modbus-Proxy Server
Node Id 1 Node Id 2
Node Id 5
Node Id 1 2 5
Modbus 4 8 10
Node Id 11
User Guide : Elektronikon MkIV Modbus
- 8 -
1.2 The Module (Combox-S)
For the modbus connection a so-called Combox-S module has to be used (AC n 19000711 41). This is a general
purpose serial communication module. By downloading the correct software in it, it will perform the modbus proxy
function.
Because this is a general purpose module, not all connections/switches will be used for this connection.
For modbus the following will be used
10x14 :
to connect a 24Vac supply
2 top address switches (LAN)
to set the Atlas Copco Lan address (= CAN side address !!), the Fieldbus switches are NOT used,
because the Modbus addresses (proxy) are defined by software and programmed with an external (PC)
software.
10x1:
to connect to the compressor network (CAN)
10x16 :
to connect the RS485 modbus line
The other connectors/switches are NOT used for this application
System
LED
Application
LEDs
24Va
Node Id
CAN side
Compr.
Network
Modbus
Network
User Guide : Elektronikon MkIV Modbus
- 9 -
The module itself can be mounted on a DIN-rail inside one of the compressor cubicles, or on a separate location.
Before installation check the available power of the 24Vac transformer, if connecting to an already supplied
transformer inside a cubicle..
1.3 LEDs
The module also has a number of LEDs on type. They are used as follows :
System LED
Blinking : no program loaded or not running
Lit continuously : program running OK
Application LEDs from left to right
1. not used
2. not used
3. CAN receive (Combox receives CAN message)
4. CAN transmit (Combox transmits CAN message)
5. Modbus receive (Combox receives Modbus message)
6. Modbus transmit (Combox transmits Modbus message)
7. not used
8. not used
9. not used
10. Modbus Mode
11. not used
User Guide : Elektronikon MkIV Modbus
- 10 -
1.4 Connector lay-out
1.4.1 Power Supply
This is a two pole Wago (type ) connector. Power supply is 24Vac, 10VA
1.4.2 LAN connector
Connect here the cable of the compressor network, according AC instruction : Compressor Network Cabling
Instruction (9820 3585 00).
1.4.3 Modbus connection
The module supports the RS485A variant of modbus, with the following pin-layout and termination requirements as
specified
Pin Assignment Modbus
Sub-D 9 pole female
Pin Function
1 GND
2 Reserved
3 TxD/RxD +
4 RTS
5 GND*
6 +5V*
7 Reserved
8 TxD/RxD -
9 Reserved
* galvanic isolated
1
6
User Guide : Elektronikon MkIV Modbus
- 11 -
1.5 RS485 connections
1.5.1 Modbus with MKIV
Elektronikon MkIV, 1900 0711 41
10x16
8
3
R=120 Ohm
Customer, Modbus Master
1
R
S
-
4
8
5

g
r
o
u
n
d
R=120 Ohm
User Guide : Elektronikon MkIV Modbus
- 12 -
1.5.2 Modbus with MKIV and MKIII
Elektronikon MkIV, 1900 0711 41
8
3
10x16
7x15
7x16
8
3
8
3
R=120 Ohm
R=120 Ohm
Elektronikon MkIII, 1900 0701 82
Customer, Modbus Master
1
1
R
S
-
4
8
5

g
r
o
u
n
d
User Guide : Elektronikon MkIV Modbus
- 13 -
1.5.3 Modbus with MKIV and Other Equipment
Elektronikon MkIV, 1900 0711 41
10x16
8
3
R=120 Ohm
R=120 Ohm
Other Modbus equipment
Customer, Modbus Master
1
R
S
-
4
8
5

g
r
o
u
n
d
User Guide : Elektronikon MkIV Modbus
- 14 -
1.6 Software downloading
Before the module can be used for a modbus connection the appropriate software must be loaded. This can be done
by AC Service personal with the AC Field Downloading Program (FDP).
With this program it is also possible to program the modbus/CAN address conversions.
After programming , put power off/on of the combox-S to activate the modbusaddresses.
Before powering the Combox S module , check all cables.
User Guide : Elektronikon MkIV Modbus
- 15 -
2. Modbus protocol implementation
2.1 Supported modbus specification
The Combox-S when downloaded with the proper modbus software supports the following modbus- variant
RTU mode of transmission
Coding system : binary
Mode : half duplex ( RS485 )
Number of start bits : 1
Number of data bits : 8
Baudrate : 300,600,1200,2400,4800,9600*,19200*,38400
Parity control : even*,odd*,none *
Number of stop bits : 1 or 2
Error checking : CRC-16
* These parameters are defined during downloading of the controller.
Frame synchronization in the RTU mode is done by simulating a synchronous message. The slave device monitors
the elapsed time between receipt of characters. If three character time elapsed without a new character, then the
device assumes that the message is completed and the next byte will be the address
The message frame format is following :
2.2 Supported Modbus functions
The Elektronikon MkIV modbus implemenentation supports the following message type , depending on the type of
data involved (see details below)
Function 01 : read coil status
Function 03 : read holding register
Function 06 : preset single register
Function 08 : loop back test
T1 T2 T3 ADDRESS Message body CRC T1 T2 T3
User Guide : Elektronikon MkIV Modbus
- 16 -
2.3 Modbus registers and coils for Data Reading
2.3.1 System Overview
2.3.1.1 General Compressor Condition
Function to be used : Read Coil Status (01)
Modbus Coil Status Information
Load/Unload VSD
0001 Stopped (=0) / Running (=1) X X
0002 Unload (=0)/ Load (=1) X
0003 General Warning X X
0004 General Shutdown-Warning X X
0005 General Shutdown X X
0006 General Service X X
0007 General Start Failure X X
0008 Emergency Stop X X
0009 Manual (=0) /Automatic (=1) X X
0010 Local (=0)/ Remote (=1) X X
User Guide : Elektronikon MkIV Modbus
- 17 -
2.3.1.2 Detailed General Compressor Condition
Function to be used : Read Holding Register (03)
Modbus register High Byte Low Byte
0401 CMS COM
0402 CS CCM
0403 GENERAL STATUS
0404 CS_MCC 0
Parameter Bit
General status 0 Pre Warning
1 General Warning
2 General Shutdown-Warning
3 General Shutdown
4 General Service
5 General Start Failure
6 Emergency Stop
7 Manual/Automatic (COS1)
8 Local/Remote
9 Timer Not Active/Active
10 Pre-warning Service Running Hours
11 Pre-warning Service Accumulated M3
CCM
(Compressor Controller Mode)
CCM2a
CCM2b
CCM3a
CCM3b
CCM4a
CCM4b
CCM4c (Speed control )
CCM4d (MCC)
00
10
01
11
02
12
22
32
CMS
(Compressor Mechanical State)
No Valid Data
Stopped
Unloaded
Loaded
00
01
02
04
CS
(Compressor State)
Load Unload
No Valid Data
A
.
V
0
1
.
22
CS MCC
(Compressor State)
MCC
No Valid Data
A

D
0
1
.
4
CS
(Compressor State)
VSD
No Valid Data
A

V
0
1
.
22
Very Important Note !!!!!.
When CS is 0 or CMS is 0 ALL data for that compressor is not Valid. Check Cables .
When there is bad communication , only the detailed general compressor condition will be set to 0.
User Guide : Elektronikon MkIV Modbus
- 18 -
2.3.2 Inputs & Outputs
2.3.2.1 Analogue Inputs Sensors & Calculated
The Elektronikon MkIV supports up to 55 analogue sensor inputs and 5 additional analogue calculated (virtual)
inputs. Each input has a value and a status register assigned.
The contents of these registers depend on the actual type of sensor that is connected. This can be different for every
type of compressor. E.g. standard compressors may have 1 to 4 pressure inputs, 1 to 10 temperature inputs, up to 7
SPM inputs, Also, features and options may increment the number of sensors that are actually installed on your
compressor.
Before using the modbus system it is therefore required to find out what sensors are really connected to your
compressors. This can e.g. be done with the FDP program. This program has a function that lists the sensors +
modbus registers for a selected compressor type (including features and options).

Once the list of sensors is known, the contents of the registers can be interpreted as described below.
2.3.2.2 Registers
Sensor Inputs
Function to be used : Read Holding Register (03)
Modbus
register
Information
0001 Analogue Input 1 Status
0002 Analogue Input 1 Value
0003 Analogue Input 2 Status
0004 Analogue Input 2 Value
0005 Analogue Input 3 Status
0006 Analogue Input 3 Value

0109 Analogue Input 55 Status
0110 Analogue Input 55 Value
Calculated (virtual) Inputs
Function to be used : Read Holding Register (03)
Modbus
register
Information
0111 Calculated Input 1 Status
0112 Calculated Input 1 Value
0113 Calculated Input 2 Status
0114 Calculated Input 2 Value
0115 Calculated Input 3 Status
0116 Calculated Input 3 Value
0117 Calculated Input 4 Status
0118 Calculated Input 4 Value
0119 Calculated Input 5 Status
0120 Calculated Input 5 Value
User Guide : Elektronikon MkIV Modbus
- 19 -
2.3.2.3 Status register Interpretation
High order byte = 00
Low order byte = Input Status
The Input Status must be interpreted as Binary data (bit coded).
Each part ( bit ) of the data ( byte ) is indicating a specific item that applies on the Input function. In the following
table, an overview is given of all bits together with the corresponding meaning and interpretation.
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Function
Description
Input
Set/Not Set
Sensor
Error
Permissive
Start
Service Shutdown Shutdown
Warning
Warning Pre-
Warning
Bit 1 Set Active Active Active Active Active Active Active
Bit 0 Not Set Not Active Not Active Not Active Not Active Not Active Not Active Not Active
2.3.2.4 Value register Interpretation
This depends on the type of inputs.
2.3.2.4.1 Pressure Input
The Pressure Input Value is a 2 byte integer, and contains the actual reading in mbar (0.001 bar)
For negative values, standard 2-complement notation is used.
Example: Value = 7040 decimal or 0x1B80 hexadecimal = 7.040 bar.
Value = -1000 decimal (2-complement) or 0xFC18 = -1.000 bar
For sensor error the value the value 32767 or 7FFF (hex) is returned.
On some high pressure compressors (with working pressures above 30 bar) a special Pressure Input can be defined
that returns data in cBar (0.01 bar) in stead of mBar.
2.3.2.4.2 Temperature Input
The Temperature Input Value is a 2 byte integer, and contains the actual reading in 0.1C
For negative values, standard 2-complement notation is used.
Example: Value = 855 decimal or 0x0357 hexadecimal = 85.5 C
Value = -250 decimal (2-complement) or 0xFF06 = -25.0 C
For sensor error the value the value 32767 or 7FFF (hex) is returned.
2.3.2.4.3 Vibration Input
tbd
2.3.2.4.4 Level Input
tbd
2.3.2.4.5 Conductivity Input
tbd
2.3.2.4.6 SPM Input
The SPM Input Value is a 2 byte register that must be seen as 2 x 1 byte.
Byte 1 : carpet value (in dB)
Byte 2 : peak value (in dB)
Example: Value = 0x1120 = > carpet value = 0x11, peak value = 0x20
For sensor error the value the value 0xFFFF (hex) is returned.
SPM values cannot be negative
User Guide : Elektronikon MkIV Modbus
- 20 -
2.3.2.4.7 Current Input
tbd
2.3.2.4.8 Speed Input
tbd
2.3.2.5 Digital (Voltage free contacts) Inputs
The Elektronikon MkIV supports up to 18 digital (voltage free) inputs. Each input has a value and a status
register assigned.
The contents of these registers is for digital inputs always the same, if the input is used. Before using the modbus
system it is therefore required to find out what inputs are used on your compressors. This can e.g. be done with the
FDP program. This program has a function that lists the digital inputs + modbus registers for a selected compressor
type (including features and options).

Once the list of inputs is known, the contents of the registers can be interpreted as described below.
Function to be used : Read Holding Register (03)
Modbus
register
Information
0201 Digital Input 1 Status
0202 Digital Input 1 Value
0203 Digital Input 2 Status
0204 Digital Input 2 Value
0205 Digital Input 3 Status
0206 Digital Input 3 Value

0241 Digital Input 21 Status
0242 Digital Input 21 Value
2.3.2.6 Status register Interpretation
High order byte = 00
Low order byte = Input Status
The Input Status must be interpreted as Binary data.
Each part ( bit ) of the data ( byte ) is indicating a specific item that applies on the Input function. In the following
table, an overview is given of all bits together with the corresponding meaning and interpretation.
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Function
Description
Input
Set/Not Set
Sensor
Error
Permissive
Start
Service Shutdown Shutdown
Warning
Warning Pre-
Warning
Value 1 Set Active Active Active Active Not used Active Active
Value 0 Not Set Not Active Not Active Not Active Not Active Not used Not Active Not Active
2.3.2.7 Value register Interpretation
Value: 00 Digital input is Open
Value: 01 Digital input is Closed
2.3.2.8 Digital (Relays) Output (Not Yet Implemented)
tbd
User Guide : Elektronikon MkIV Modbus
- 21 -
2.3.3 Counters
2.3.3.1 Compressor Counters
The Elektronikon MkIV supports up to 28 counters (32-bit counters). Each input as 2 x 16bit value register
assigned, to allow a 32-bit value to be read.
Not all types of compressors use all types of counters. The list in this chapter provides an overview of the used
counters / compressor type, and the units that are used
Function to be used : Read Holding Register (03)
Modbus
registers
Information Units Load/Unload VSD
0301+0302 Running Hours s X X
0303+0304 Loaded Hours s X -
0305+0306 Motor Starts number X -/X *
0307+0308 Module Hours s X X
0309+0310 Accumulated Volume 1000 m - X
0311+0312 Load cycle number X -/X *
0313+0314 VSD 0-20% RPM % - X
0315+0316 VSD 20-40% RPM % - X
0317+0318 VSD 40-60% RPM % - X
0319+0320 VSD 60-80% RPM % - X
0321+0322 VSD 80-100% RPM % - X
0323+0324 Not yet used
0355+0356 Not yet used
yes, if VSD has unloading cycle (e.g. Z-VSD)
Interpretation of data in the registers
Example Running Hours
Higher Byte Lower Byte
301 B4 B3
302 B2 B1
DWORD : Running Hours B4 B3 B2 B1
00 2C 93 45
2921285 sec 811 hrs
User Guide : Elektronikon MkIV Modbus
- 22 -
2.3.3.2 Multi Compressor Controller Counters
The Elektronikon MkIV contains 4 counters (32-bit counters) to perform the MCC load balancing between up to 4
compressors. Each such counter as 2 x 16bit value register assigned, to allow a 32-bit value to be read.
Only units where the MCC master function is active contain real data for this registers.
Function to be used : Read Holding Register (03)
Modbus registers Information unit
501+502 Compressor 1 counter s
503+504 Compressor 2 counter s
505+506 Compressor 3 counter s
504+507 Compressor 4 counter s
Data interpretation is the same as for the other counters
User Guide : Elektronikon MkIV Modbus
- 23 -
2.3.4 Special
2.3.4.1 VSD motor data
The Elektronikon MkIV on VSD units contains some important data about the motor speed.This data can be read
over the modbus system.
Function to be used : Read Holding Register (03)
Modbus registers Information unit
0801 Required motor speed rpm
0802 Actual motor speed motor 1 rpm
0803 Actual motor speed motor 2 rpm
0804 Actual motor speed motor 3 rpm
Each register contains a 16-bit value that is directly readable as the equivalent rpm.
User Guide : Elektronikon MkIV Modbus
- 24 -
2.4 Modbus registers and coils for parameters change
2.4.1 Load/Unload Pressure Band change
It is possible to change the operating pressure band inside the Elektronikon MkIV, or to switch between the two
available pressure bands. These registers are only valid for Load/Unload compressors
Functions to be used :
For reading : Read Holding Register (03)
For writing :Preset Single Register (06)
Modbus
registers
Description
1061 Pressure Band Selection
1062 Loading pressure band 1
1063 Unloading Pressure band 1
1064 Loading pressure band 2
1065 Unloading Pressure band 2
Pressure Band Selection : 1 = band 1, 2 = band 2
Attention : when writing values the following relations should be maintained :
Loading pressure < unloading pressure (per band)
Loading pressure should not be below the minimum setting that was factory defined.
Unloading pressure should not be above the maximum setting that was factory defined.
Values not fulfilling this will be refused.
2.4.2 VSD Setpoint change
It is possible to change the operating set point inside the Elektronikon MkIV, or to switch between the two available
pressure set points. These registers are only valid for VSD compressors
For reading : Read Holding Register (03)
For writing :Preset Single Register (06 )
Modbus
address
Description
1051 Setpoint Selection
1052 Setpoint 1
1053 Setpoint 2
Setpoint Selection : 1 = Setpoint 1, 2 = Setpoint 2
The set point must be within the limits that are factory defined for your machine type.
Values not fulfilling this will be refused by the MKIV.
User Guide : Elektronikon MkIV Modbus
- 25 -
2.4.3 MCC Pressure Band change
In Elektronikons where the MCC master function is active it is possible to change the operating pressure band for
this master, or to switch between the two available pressure bands.
Functions to be used :
For reading : Read Holding Register (03)
For writing :Preset Single Register (06 or 16 for multiple registers)
Modbus
registers
Description
1081 MCC Pressure Band Selection
1082 MCC Loading pressure band 1
1083 MCC Unloading Pressure band 1
1084 MCC Loading pressure band 2
1085 MCC Unloading Pressure band 2
Pressure Band Selection : 0 = band 1, 1 = band 2
Attention : when writing values the following relations should be maintained :
Loading pressure < unloading pressure (per band)
Values not fulfilling this will be refused by the MKIV.
User Guide : Elektronikon MkIV Modbus
- 26 -
2.5 Modbus registers and coils for remote control
2.5.1 Control Commands
2.5.1.1 Compressor Control Mode Selection
The Elektronikon MkIV has a number of control modes that define the behaviour of a compressor in relation to
external inputs (pressure reading, start/stop commands,).
Each mode has a main type (= number 1 to 4), and a sub-type (a,b,c,..). The number of sub-types is different for
each main type.
When Modbus has to be used to control a compressor the main type ust be set to 4 (=remote control over
communication line). This has to be done through the display, select LAN Control. By default the compressor
will then enter the 4a mode.
Through Modbus it is now possible to activate the other sub-types.
Functions to be used : writing method: Preset Single Register Function 06
Modbus address Value to write Description Accepted in mode
2002 1 Switch from 4a or 4c to 4b 4a 4c
2 Switch from 4b or 4c to 4a 4b
3 Switch from 4a or 4b to 4c 4a 4b
Note
Mode 4a : remote control of start/stop but pressure control is done by the controller
Mode 4b : remote control of start/stop and pressure control is done from remote (Supervisory control) (also for
VSD setpoint control)
Mode 4c : remote control of start/stop with external speed (only vsd) speed control)
2.5.1.2 Compressor Commands
The commands that are described here are only available in the defined Compressor Control Modes.
Carefully consult the control concept of the compressors before using them.
Functions to be used : writing method: Preset Single Register Function 06
Modbus address Value to write Command Accepted in mode
2001 1 Start 4a / 4b
2 Stop 4a / 4b
3 Load 4a / 4b
4 Unload 4b ( in 4a = Manual unload )
5 MCC Start System 4a / 4d
6 MCC Stop System 4d
7 MCC Local 4d
2004 1 Reset Shutdown In all Modes
2 Reset Start Failures In all Modes
User Guide : Elektronikon MkIV Modbus
- 27 -
2.5.2 VSD external setpoint/speed control
On VSD units extended external control is possible whereby either the main motor speed of the pressure set point is
directly controlled from remote over Modbus.
This can be done with the following Modbus registers
-> reading method: Read Holding Registers Function 03
-> writing method: Preset Single Register Function 06
Modbus
address
Description
1071
External Setpoint
1072
External Speed
2.5.3 Reset Initial Settings (Analogue , Digital , Counter Inputs)
-> writing method: Preset Single Register Function 06
Modbus
address
Description
2101
Reset Initial Settings
User Guide : Elektronikon MkIV Modbus
- 28 -
2.6 Communication examples
2.6.1 Analogue - Digital Inputs
-> reading method: Read Holding Registers Function 03
Example: read from Analogue input 1, Status and Value
Query
Field Name Example ( Hex)
Device Id Nr 04
Function 03
Starting Address High 00
Starting Address Low 00
Number of points High 00
Number of points Low 02
CRC C4 5E
Response
Field Name Example ( Hex)
Device Id Nr 04
Function 03
Byte Count 04
Data register 0001 00 80 Status
Data register 0002 1D 15 ( = Value : 7505 mbar )
CRC DF CA
Example: read from Digital input 1, Status and Value
Query
Field Name Example ( Hex)
Device Id Nr 22
Function 03
Starting Address High 00
Starting Address Low C8
Number of points High 00
Number of points Low 02
CRC 42 46

Response
Field Name Example ( Hex)
Device Id Nr 22
Function 03
Byte Count 04
Data register 0001 00 88 Status (Set , Shutdown)
Data register 0002 00 00 ( Input Open )
CRC 68 DB
User Guide : Elektronikon MkIV Modbus
- 29 -
2.6.2 Commands description
-> writing method: Preset Single Register Function 06
Example: Send a Start command
Query
Field Name Example ( Hex)
Slave address 01
Function 06
Register Address High 07
Register Address Low D0
Preset Data High 00
Preset Data Low 01
CRC
Response
Field Name Example ( Hex)
Slave address 01
Function 06
Register Address High 07
Register Address Low D0
Preset Data High 00
Preset Data Low 01
CRC
2.6.3 Present System Status
-> reading method: Coil Status Function 01
Example: Read present compressor status ( = read 8 coils )
Query
Field Name Example ( Hex)
Slave address 01
Function 01
Starting Address High 00
Starting Address Low 00
Number of points High 00
Number of points Low 08
CRC 3D CC
Response
Field Name Example ( Hex)
Slave address 01
Function 01
Byte Count 01
Data Coils 1 to 8 00 ( Coils 1 to 8 are = 0 )
CRC 51 88
User Guide : Elektronikon MkIV Modbus
- 30 -
2.6.4 Loopback Test
Query
Field Name Example ( Hex)
Device Id Nr 04
Function 08
Starting Address High 00
Starting Address Low 00
Number of points High A5
Number of points Low 37
CRC
Response
Field Name Example ( Hex)
Device Id Nr 04
Function 08
Starting Address High 00
Starting Address Low 00
Number of points High A5
Number of points Low 37
CRC
User Guide : Elektronikon MkIV Modbus
- 31 -
3. Exception Responses
3.1 Function Code Data Field
In a normal response, the slave echoes the function code of the orginal query.
In an exception response 80hex is added to the function code.
At the same time an exception code is added in the Data Field.
3.2 Exception Codes
Code Name Meaning
01 Illegal Function The function code received in the query is not
an allowable action for the slave.
02 Illegal Data Address The data address received in the query is not an
allowable address for the slave
03 Illegal Data Value A value contained in the query data field is not
an allowable value for the slave
06 Reprogramming Refused Command Refused because previous command
was not yet executed
07 Command Refused Command Refused because previous command
was not yet executed
08 Data Not Available Check communication cable between MKIV and
Combox-S .
09 Illegal Command An unknown command is being sent
3.3 Example
Example: read from Analogue input 1, Status and Value
Query
Field Name Example ( Hex)
Slave address 01
Function 09 ( Wrong function, should be 03 )
Starting Address High 00
Starting Address Low 00
Number of points High 00
Number of points Low 02
CRC 5C 0A
Response
Field Name Example ( Hex)
Slave address 01
Function 89 ( Exception reply )
Exception Code 01 ( Illegal Function in query )
CRC 86 50