You are on page 1of 2

ENERGY SAVING CALCULATION

1
Description
MD
(KW)
Full load
hrs
Daily
Consumpti
on (Kw-h)
Annual
Diversity
Annual
Consumption
(Kw-h)
%
savings
KWh Saved
per Annum
Savings due to
Residences
Lighting 350 5 1750 0.6 383250 33 126472.5
Use of LED Fittings (12 w) instead of
CFL fittings . Differnce between 18W
CFL and 12W LED lamp is 6 W which
comes to 33% of energy saving
A/C and other
Domestic
Equipments
1936 5 9680 0.5 1766600 20 353320
User to be recommended to use BEE
FIVE star certified appliance and Air
conditioners.
Common Areas
Water Pumps 111 2 222 0.8 64824 15 9723.6 Use of BEE Certified Motors
Lifts 180 5 900 0.6 197100 25 49275
Use of Group controls and Variable
speed drives.
Lighting of
Stairs / Lift
Lobby &
Passages etc
34
12 408 0.7 104244 33 34400.52
Use of LED Fittings (12 w) instead of
CFL fittings . Differnce between 18W
CFL and 12W LED lamp is 6 W which
comes to 33% of energy saving
12 408 0.7 104244 80 83395.2
Common area lighting on Solar Power
Generation
Basement
Lighting
11
10 110 0.7 28105 22 6183.1
Use of T5 Fittings (28 w) instead of
T8 fittings . Differnce between 28W T5
and 36W T8 lamp is 8 W which comes
to 22% of energy saving
10 110 0.7 28105 80 22484
Common area lighting on Solar Power
Generation
ENERGY SAVING CALCULATION
2
Descritption
MD
(KW)
Full load
hrs
Daily
Consumpti
on (Kw-h)
Annual
Diversity
Annual
Consumption
(Kw-h)
%
savings
KWh Saved per
Annum
Savings due to
External
Lighting

10 12 120 0.9 39420 33
13008.6

Stand alone solar
system panel
street light poles to
be used . Use of
LED Fittings (12
w) instead of CFL
fittings . Difference
between 18W CFL
and 12W LED lamp
is 6 W which comes
to 33% of energy
saving

Miscellaneous
loads ( Basement
Ventilation, Stack
Parking, Fitness
Center load)
222 4 888 0.4 129648 0
STP 50 24 1200 0.9 394200 25 98550

Total
3736.0
0
3463923.00 807726.02


% Savings 23.32