W-SLC Medium Voltage fused contactor truck A safe, reliable and efcient motor starter 2 Hydraulics Powering business worldwide Next generation transportation Eaton is driving the development of new technologies from hybrid drivetrains and emission control systems to advanced engine components that reduce fuel consumption and emissions in trucks and cars. Higher expectations We continue to expand our aerospace solutions and services to meet the needs of new aviation platforms, including the high-ying light jet and very light jet markets. Building on our strengths Our hydraulics business combines localized service and support with an innovative portfolio of uid power solutions to answer the needs of global infrastructure projects, including locks, canals and dams. Powering Greener Buildings and Businesses Eatons Electrical Group is a leading provider of power quality, distribution and control solutions that increase energy efciency and improve power quality, safety and reliability. Our solutions offer a growing portfolio of green products and services, such as energy audits and real-time energy consumption monitoring. Eatons Uninterruptible Power Supplies (UPS), variable-speed drives and lighting controls help conserve energy and increase efciency. Eaton delivers the power inside hundreds of products that are answering the demands of todays fast changing world. We help our customers worldwide manage the power they need for buildings, aircraft, trucks, cars, machinery and entire businesses. And we do it in a way that consumes fewer resources. Automotive Aerospace Electrical Truck Hydraulics Automotive Aerospace Electrical Truck Hydraulics MV Switchgear Technology is in our DNA Complete Global Medium Voltage Switchgear Solutions Eaton, a premier leader in designing and manufacturing power distribution and protection equipment in the electrical industry, offers a comprehensive range of medium voltage (MV) solutions to meet the needs of virtually every application. From products that feature cutting-edge design that allow for easy access, maintenance and space savings, to arc-resistant products that enhance safety, Eatons medium voltage solutions provide a variety of products for every need. Additionally, Eatons global service network provides maximum customer support in all regions of the world. As one of the few completely vertically integrated and diversied industrial manufacturers in the world, Eaton designs not only MV assemblies, but also the key components that comprise the MV solutions from steel housing and circuit breaker compartments to vacuum interrupters, circuit breakers, bus systems and fuses. Eatons MV heritage, strengthened by acquisitions such as Westinghouse DCBU, Cutler Hammer, MEM and Holec, has resulted in breakthrough MV technologies and numerous international patents over the years. Integral to Eatons complete electrical PowerChain Solutions which help businesses increase reliability, efciency and safety Eatons medium voltage equipment meets all applicable standards and certications such as IEC, NEMA / ANSI, GB, UL, IEEE, KEMA and CSA. When it comes to medium voltage solutions, you can trust the one name with a long history of proven performance: Eaton. 3 Eaton Corporation is a worldwide leader in the design, manufacture, and sale of safe, reliable and high-performance medium voltage power distribution equipment in accordance with IEC, GB and ANSI standards. 4 Introduction Developed on cutting-edge technologies, Eatons W-SLC withdrawable type vacuum contactor-fuse combination units are world leading in terms of performance, safety and functionality. The W-SLC vacuum contactor-fuse combination units are applicable in AC systems with voltages up to 7.2 kV and 50/60 Hz. They can be used in frequently operated heavy loads and harsh environments. 5 Product safety features
The contactor is prevented from closing and a panel indication is provided when: Fuse blown and or Fuse not tted Additional interlock options are available to interface with the panel if appropriate panel designs are incorporated such that: The truck is prevented from being racked in if: - The front door is open - The earth switch is ON The earth switch cannot be switched ON if the truck is in the Service Position. The panel door cannot be opened if the truck is in the Service Position. Applications W-SLC vacuum contactor-fuse combination motor starting applications: Squirrel-cage induction motors Synchronous motors Wound-rotor motors Suitable for: Full voltage starting Reduced voltage starting The perfect choice for all applications HVAC Mining Automotive Petrochemical Pulp and Paper Pumps, Fans, Conveyors and Crushers 6 Utilization conditions Eatons vacuum contactor-fuse combination units are suitable for use in the following conditions: Ambient temperatue: -15 C to +40 C Relative humidity: max. 95%non-condensing Altitude: up to 1000 m Please contact Customer service for special requirements.
Design and testing standards
Eatons vacuum contactor-fuse combination units are fully in line with IEC standards. IEC 62271-200 IEC 60470 Key technical features * The ratings for new vacuum contactor-fuse combination units: Voltage: up to 7.2 kV Current: Contactor continuous current: 400 A Combination Continuous current: 200 A Breaking: up to 50 kA with fuse 8500 A interrupting rating without fuse Control voltages: 110, 220 50 Hz Vac 120, 240 60 Hz Vac 110, 120 Vdc Service life: 300,000 electrical operations 1,000,000 mechanical operations
* For detailed information, please refer to technical data table 7 Dimensions Eatons mid-mounted type withdrawable vacuum contactor-fuse combination units Striker Pin length after fuse blown = 10 - 16mm Maximum dimensions for fuse 8 Electrical operation Wiring Diagram Auxiliary contacts when the trolley is on Test Position or connected Position Note: The drawing is shown with the Contactor Truck in the withdrawn Test Position, de-energised, with fuses tted and healthy. +Ve +Ve -Ve K1 K1 K1 Y1 -Ve Q1 +Ve +Ve +Ve +Ve +Ve Y1 Q1 Y2 -Ve -Ve -Ve -Ve Q1 +Ve +Ve -Ve K1 K1 K1 Y1 -Ve Q1 Fuse status Indication Circuit Closing Circuit Housing Earthing Opening Circuit Auxiliary Contact Circuits Electrical operation wiring diagram of W-SLC-400 withdrawable vacuum contactor-fuse combination units 64 Pin Secondary Disconnect K1: Closing / Holding relay PC: Operations counter Q1: Auxiliary contact (switching when the contactor closes or trips) SC: Closing button SO: Opening button S1: Auxiliary contact (switching when fuse is blown or not tted)* S8: Auxiliary contact (switching when the trolley is on Test Position) S9: Auxiliary contact (switching when the trolley is on Connected Position) Ve: Control supply V1: Bridge rectier (not included for DC applications) Y1: Closing coil * When MV fuse is replaced by a link S1 only switches when Open push button is pressed. 9 Mechanical latching option Wiring Diagram Note: The drawing is shown with the Contactor Truck in the withdrawn Test Position, de-energised, with fuses tted and healthy. K1: Closing relay K2: Trip relay PC: Operations counter Q1: Auxiliary contact (switching when the contactor closes or trips) SC: Closing button SO: Opening button S1: Auxiliary contact (switching when the fuse is blown or not tted)* S8: Auxiliary contact (switching when the trolley is on Test Position) S9: Auxiliary contact (switching when the trolley is on Connected Position) Ve: Control supply V1: Bridge rectier (not included for DC applications) V2: Bridge rectier Y1: Closing coil Y2: Trip coil * When MV fuse is replaced by a link S1 only switches when Open push button is pressed. +Ve +Ve +Ve +Ve +Ve Y1 Q1 Y2 -Ve -Ve -Ve -Ve Q1 +Ve +Ve +Ve +Ve +Ve Y1 Q1 Y2 -Ve -Ve -Ve -Ve Q1 Fuse status Indication Circuit Closing Circuit Housing Earthing Opening Circuit Auxiliary Contact Circuits Mechanical latching wiring diagram of W-SLC-400 withdrawable vacuum contactor-fuse combination units 64 Pin Secondary Disconnect Selection and ordering information Type W-SLC, 400 A, vacuum contactor ratings Rated utilization voltage Interrupting rating (kA) Application table Transformer (kVA) Capacitor (A) * Maximum insulation voltage (V) Unfused Fused Induction motor (kW) Synchronous motor (kW) (0.8 PF) (1.0 PF) 2200 - 2500 3000 - 3600 3800 - 4800 6000 - 6900 8.5 8.5 8.5 8.5 50 50 50 50 1300 1675 2250 3350 1300 1675 2250 3350 1500 1850 2600 4100 1500 2000 2500 4000 295 7200 * Ratings not applicable for back-to-back switching. Please contact Customer Service for back-to-back switching applications. Rated current .......................................................400 A enclosed Max fuse rating .................................................................. 355 A Fused combination ............................................................. 200 A IEC make-break capability-AC4 Make ................................................................................ 4000 A Break ................................................................................ 3200 A Maximum interrupting current (3 Operations) ................................................................... 8500 A Short time withstand current 30 Second ........................................................................ 2400 A 1 Second .......................................................................... 6000 A 8.7 ms (0.5 Cycle) ......................................................63 kA peak Fuse protected (based on fuse cut-off) .............................. 50 kA Normal service altitude .......................................... 1000 meters Mechanical life ................................................................ 1 million Electrical life AC3 & AC4 ....................................................300,000 operations Impulse withstand ..............................................................60 kV Dielectric strength ...................................... 20 kV rms (1 minute) Closing time (Energization to contact touch) .................................... < 120 ms Opening times (eld selectable) ......................... < 50 330 ms Arcing time .............................................................12 ms or less Control voltages ac/Hz ..................... 110 / 50, 120 / 60, 220 / 50, 240 / 60 Vac/Hz dc ........................................................................... 110 / 220 Vdc Pickup voltage ..........................................80% rated coil voltage Dropout voltage .......................................60% rated coil voltage Control circuit burden Closing 100 125 V ........................................................... 1 kVA 200 240 V ........................................................ 1.8 kVA Holding 100 125 V ........................................................... 40 VA 200 240 V ........................................................... 50 VA Auxiliary contact rating Voltage (maximum) ............................................................ 600 V Continuous current ............................................................... 10 A Making capacity (ac) ................................................... 7200 VA (dc) ..................................................... 125 VA Breaking capacity (ac) ..................................................... 720 VA (dc) ..................................................... 125 VA Latch (when specied) Mechanical life ............................................. 250,000 Operations Trip voltage (dc) ......................................................... 24 V (dc) ....................................................... 125 V (ac) .............................................. 110 / 120 V Minimum trip voltage .................................... 80% Rated Coil V Trip burden ....................................................................... 400 VA Trip time .............................................................................30 ms Weight (without fuses) .......................................................96 kg Specications Order instruction W-SLC 1 SLC014S 5 Y - 66 5 IEC draw-out contactor IEC SL contactor 7.2 kV, 400 A 1 = with fuses 0 = fuses replaced by conductors Note: fuses are supplied by user Contactors auxiliary contact 66 = 6 NO, 6 NC Coil drop-out time 5 = 30 ms 6 = 50 ms 7 = 130 ms 8 = 250 ms 9 = 330 ms Coil voltage A = 120 Vac/60 Hz B = 240 Vac/60 Hz U = 110 Vac/50 Hz W = 220 Vac/50 Hz X = 110 Vdc Y= 220 Vdc Mechanical latch (Coil voltage) 0 = None 4 = 110/50, 120/60 Hz 5 = 220/50, 240/60 Hz 1874 1886 1911 1998 1893 1990 1962 1999 1983 1908 1906 1899 1963 The power of fusion. Theres a certain energy at Eaton. Its the power of uniting some of the worlds most respected names to build a brand you can trust to meet every power management need. The energy created supports our commitment to powering business worldwide. From power distribution to power quality and control, Eaton allows you to proactively manage your complete power system by providing electrical solutions that make your applications safer, more reliable, and highly efcient. Visit www.eaton.com/electrical. All of the above are trademarks of Eaton Corporation or its affiliates. Eaton has a license to use the Westinghouse brand name in Asia Pacific. 2009 Eaton Corporation. Eatons electrical business is a global leader with expertise in power distribution and circuit protection; backup power protection; control and automation; lighting and security; structural solutions and wiring devices; solutions for harsh and hazardous environments; and engineering services. Eaton is positioned through its global solutions to answer todays most critical electrical power management challenges. Eaton is a diversied power management company providing energy-efcient solutions that help our customers effectively manage electrical, hydraulic and mechanical power. The company is a global technology leader in electrical products, systems and services for power quality, distribution and control, power transmission, lighting and wiring products; hydraulics components, systems and services for industrial and mobile equipment; aerospace fuel, hydraulics and pneumatic systems for commercial and military use; and truck and automotive drivetrain and powertrain systems for performance, fuel economy and safety. Eaton acquired Cooper Industries plc in 2012. Eaton has approximately 100,000 employees and sells products to customers in more than 150 countries. For more information, visit www.eaton.eu. 2012 Eaton Corporation All rights reserved BR022002EN / January 2013 Europe, Middle East and Africa Eaton Industries (Netherlands) B.V. P.O. Box 23 7550 AA Hengelo The Netherlands Tel.: +31 74 246 4012 Fax: +31 74 246 4601 SecretariaatCSsystems@eaton.com www.eaton.eu Asia Pacic Eaton Electrical Sector Asia Pacic Headquarters No.3 Lane 280 Linhong Road Changning District Shanghai 200335, P.R.China Tel.: +86 21 5200 0099 Fax: +86 21 5200 0200 www.eatonelectrical.com.cn South America Eaton Ltda. Av. Pierre Simon de Laplace, 751 Cond. Techno Park Via Anhanguera, Km 104,5 Campinas - SP - 13069-320 - Brasil Tel.: +55 19 2117 0000 eatonelectricalbrasil@eaton.com www.eaton.com.br North America Eaton Corporation Electrical Sector 1000 Cherrington Parkway Moon Township, PA 15108 United States 877-ETN-CARE (877-386-2273) www.eaton.com The information provided in this document reects the general characteristics of the referenced products at the time of issue and may not reect their future characteristics. Eaton Corporation reserves the right to modify the contents of this document and the characteristics of the referenced products without prior notication. Eaton Corporation does not assume liability for potential errors or omission of information in this document.