You are on page 1of 38

...................................................................................

Cahier technique no. 211


The protection of LV motors
G. Baurand
V. Moliton
Collection Technique
Building a New Electric World
"Cahiers Techniques" is a collection of documents intended for engineers
and technicians, people in the industry who are looking for more in-depth
information in order to complement that given in product catalogues.
Furthermore, these "Cahiers Techniques" are often considered as helpful
"tools" for training courses.
They provide knowledge on new technical and technological developments
in the electrotechnical field and electronics. They also provide better
understanding of various phenomena observed in electrical installations,
systems and equipments. Each "Cahier Technique" provides an in-depth study
of a precise subject in the elds of electrical networks, protection devices,
monitoring and control and industrial automation systems.
This constantly updated collection can be downloaded from:
http://www.technical-publications.schneider-electric.com
Please contact your Schneider Electric representative if you want either a
"Cahier Technique" or the list of available titles.
The "Cahiers Techniques" collection is part of the Schneider Electrics
"Collection technique".
Foreword
The author disclaims all responsibility subsequent to incorrect use of
information or diagrams reproduced in this document, and cannot be held
responsible for any errors or oversights, or for the consequences of using
information and diagrams contained in this document.
Reproduction of all or part of a "Cahier Technique" is authorised with the
compulsory mention:
"Extracted from Schneider Electric "Cahier Technique" no. ..." (please
specify).
no. 211
The protection of LV motors
ECT 211 rst issue, January 2007
Vivien MOLITON
He graduated from the Ecole Nationale Suprieure dIngnieurs
of Limoges (ENSIL) in 2002, specializing in Mechatronics.
In the same year, he set up the Mechatronics R&D Laboratory at
Schneider Electric. In the Measurement and Protection department,
he participated in the development of a new range of motor circuit-
breakers and the Tesys U starter-controller under the Telemecanique
brand.
Gilles BAURAND
Graduate in Electromechanical Engineering, ENSICAEN (Ecole
Nationale Suprieure dIngnieurs de Caen) in 1977.
He joined Telemecanique in 1978 as a technical manager for the
development of control and electronic protection relays, holding this
post until 1985.
He managed the laboratory of the Motor Protection Contactor and
Relay Department from 1986 to 1991, and was then responsible for the
advance development of this department from 1992 to 2004.
He has been responsible for the advance development of the PPC
(Power Protection & Control) eld at Schneider Electric since early in
2005.
Cahier Technique Schneider Electric no. 211 / p.2
Cahier Technique Schneider Electric no. 211 / p.3
The protection of LV motors
Contents
1 Introduction p. 4
2 Brief guide to electric motors 2.1 The various types of motor p. 5
2.2 The applications of low-voltage motors p. 6
3 Causes of faults and their consequences 3.1 Internal faults in the motor: p. 7
Damage to the stator or rotor winding
3.2 Faults external to the motor: p. 8
Phenomena related to the motor power supply
3.3 Faults external to the motor: p. 11
Phenomena related to the use of the motor
3.4 Summary p. 12
4 Protection functions 4.1 Short-circuit protection p. 13
4.2 Overload protection p. 14
4.3 Selection table for protection relays p. 19
4.4 Motor circuit-breakers (thermal-magnetic circuit-breakers) p. 20
5 Motor starters 5.1 Background p. 21
5.2 The basic functions of motor starters p. 21
5.3 The special case of electronic starters and variable speed drives p. 23
5.4 A complementary function: communication p. 23
5.5 Motor starters and coordination p. 24
5.6 Control and protective switching devices (CPS) p. 26
5.7 Discrimination p. 27
5.8 Example p. 27
6 Conclusion p. 29
Appendix 1: Modular system of the Tesys U starter-controller p. 30
Appendix 2: The main starting modes p. 31
Appendix 3 : Bibliography p. 35
All electric motors must be designed to meet the requirements of specied
operating conditions, and cannot operate outside these without the
risk of immediate or long-term damage to the motor itself and/or to its
environment.
In order to eliminate this risk, or at least reduce it considerably, machine
designers and installers provide protection devices selected from
manufacturers catalogs.
But which of all these existing devices should be provided, given that they
must interact (operate) with isolation and control equipment? How do we
choose? And, above all, how can we be sure that the chosen equipment
will be fully compatible?
This Cahier Technique is designed to answer these questions, by
describing all the factors to be taken into account and then detailing the
various solutions offered by manufacturers, including complete units known
as motor starters.
Cahier Technique Schneider Electric no. 211 / p.4
1 Introduction
All electric motors have operating limits. Exceeding
these limits will result, sooner or later, in the
destruction of the motor and also of the machines
driven by it, causing immediate stoppages and
lost production.
This form of load, which converts electrical
energy to mechanical energy, can be the site of
mishaps due to electrical or mechanical factors.
Electrical
overvoltage, voltage drop, unbalance, or phase
loss, causing variations in the current drawn;
short circuits where the current can reach
destructive levels for the load;
Mechanical
Rotor stall, momentary or prolonged overload
leading to an increase in the current drawn by
the motor and consequently a dangerous heating
of its windings.
The cost of these mishaps can be high. It includes
lost production, the loss of raw materials, the
repair of the production equipment, the loss of
production quality, and delays in delivery. The
economic imperative of increasing competitiveness
for businesses implies the reduction of costs related
to the loss of service continuity and low quality.
These mishaps can also have dramatic
consequences for the safety of personnel coming
into direct or indirect contact with the motor.
b
v
v
b
To avoid these mishaps, or at least limit their
consequences and prevent them from causing
damage to equipment and disturbances in the
line supply, protective systems must be used.
They can isolate equipment to be protected from
the line, by tripping breaking devices in response
to the detection and measurement of variations
in electrical values (voltage, current, etc.).
Each motor starter must therefore incorporate:
short circuit protection, to detect and cut off, as
quickly as possible, abnormal currents which are
generally more than 10 times the nominal current
(I
n
)
overvoltage protection, to detect current
increases up to approximately 10 I
n
and cut off
the starter before the heating of the motor and
the conductors damages the insulation
This protection is provided by specic devices
such as fuses, circuit-breakers, overload relays
or combination devices offering several types of
protection.
Note: Protection against ground faults, which
includes protection of personnel and re-proong,
is not covered in this document, since it is
usually provided as part of the power distribution
system for a piece of equipment, a workshop or
a whole building.
b
b
Cahier Technique Schneider Electric no. 211 / p.5
2 Brief guide to electric motors
2.1 The various types of motor
There are three main categories of electric
motor:
asynchronous motors
synchronous motors
DC motors
Each of these consists of a xed part, the stator or
eld coil, and a moving part, the rotor or armature.
Asynchronous motors
The stators of these motors have windings
supplied with alternating current and positioned
so as to create a rotating magnetic eld
(rotating ux) at the synchronous speed W. For
a three-phase power supply, the most common
conguration has three windings (which may
include several coils) connected in a delta or
star arrangement. The rotors usually consist of
conductive bars short-circuited at their ends,
as in squirrel cage motors (for low power
applications), or, less commonly, windings, as in
asynchronous motors with wound rotors (for high
power applications). The rotating ux generated
by the stator induces a current in the rotor and
causes it to rotate (see Laplaces law). Its speed
W is less than the synchronous speed W of the
rotating ux; this difference is called the slip (s),
corresponding to the relative loss of speed:
,
demonstrating the concept of asynchronism.
Asynchronous motors are suitable for low and
medium power applications, especially those in
which the starting torque has to increase with the
speed. These are the most widely used motors,
because of their low cost, robustness and ease
of installation and maintenance. Under local
control, they have the disadvantage of having
high starting currents, up to 8 times the nominal
current (see Fig. 1 ).
Synchronous motors
Like asynchronous motors, these have a stator
consisting of windings supplied with alternating
current. The characteristic feature of these motors
is the synchronization between the rotation speed
of the rotor and that of the rotating eld created
by the stator. This feature is present because the
rotor of a synchronous motor consists of
permanent magnets or a winding supplied with
direct current, establishing a xed magnetic eld.
This characteristic makes their construction more
complex and is reected in their higher cost.
b
b
b
s =
'

s =
'

Synchronous motors are mainly used for very


high power applications (> 5 MW), requiring a
constant speed regardless of the load, but they
can be difcult to start, and for this reason they
are often combined with variable speed drives.
DC motors
In these motors, the stator and the rotor both
consists of windings through which direct current
is passed. The current is taken to the armature
by means of a commutator with brushes. The
stator creates a xed magnetic eld which makes
the conductors in the rotor move, according to
Laplaces law.
Direct current motors are mainly used for
applications requiring precise, rapid speed
control, and can withstand high overloads. They
have the disadvantage of having commutators
whose brushes and rings require regular
maintenance. Precautions must also be taken
when starting and stopping these motors, and it
is especially important to avoid cutting off the
excitation if the armature is live: stopping in this
way will cause the rotor to race.
For further information on the different types of
motors and their operation, see Schneider
Electric Cahier Technique no. 207.
Fig. 1 : Graph of I = f(t) for an asynchronous motor.
Starting peak
(magnetizing peak)
I
p
= 10 to 13
n
: Magnetizing current
I
d
= 4 to 8 I
n
: Starting current
I
n
: Nominal rms current
Motor starting
phase
Normal motor
operation
20 to 30 ms 1 to 10 s t
I
p
I
d
I
n
Cahier Technique Schneider Electric no. 211 / p.6
2.2 The applications of low-voltage motors
There are two types of low-voltage (LV) motors:
single-phase
three-phase
They are supplied at voltages ranging from
220 to 690 V. Most low-voltage electric motors
have a power of less than 100 kW. As the power
increases, the current becomes greater
(P = UI.cosj), and the components involved
(motors, equipment, wiring and protection) must
be given suitable dimensions.
For economic reasons, medium-voltage (MV)
motors are used above the 1500 kW level
(see Fig. 2 ).
b
b
Fig. 2 : Applications of electric motors according to
their power and supply voltage.
13.8
2.20
0.69
0.22
100 1500 P (kW)
Voltage (kV)
LV
MV
Cahier Technique Schneider Electric no. 211 / p.7
3 Causes of faults and their consequences
In an installation including electric motors,
we can distinguish two types of fault: faults
originating internally in the motor, and faults
originating externally.
Internal faults:
short-circuit between phase and ground
short-circuit between phases
short-circuit between coils
overheating of the windings
breaking of a bar in squirrel cage motors
problems relating to the bearings
etc.
External faults:
The origins of these faults lie outside the electric
motor, but their consequences can cause
damage to the motor.
b
v
v
v
v
v
v
v
b
These malfunctions can arise from:
the power source:
- power cuts
- phase reversal or unbalance
- brownout
- overvoltage
- etc.
the operating mode of the motor:
- overload operation
- the number of starts and the starting operations
- the load inertia
- etc.
the installation of the motor:
- misalignment
- unbalance
- excessive stresses on the shaft
- etc.
v
v
v
3.1 Internal faults in the motor:
Damage to the stator or rotor winding
The stator winding of an electric motor consists
of copper conductors insulated with varnish.
Breaks in this insulation can cause a permanent
short circuit between a phase and ground,
between two or even three phases, or between
the coils of a single phase (see Fig. 3 ).
It can be caused by phenomena which may be
electrical (surface discharge, overvoltage), thermal
(overheating) or even mechanical (vibration,
Fig. 3 : The windings of motors are the parts which are most vulnerable to electrical faults and operating
mishaps.
electrodynamic stresses on the conductors).
Insulation faults can also occur in the rotor
winding, with the same result: the motor
becomes unserviceable.
The most common cause of damage to the
windings of a motor is an excessive rise in their
temperature. This rise is often caused by an
overload which leads to an increase in the
current owing in these windings.
Stator
windings
Cahier Technique Schneider Electric no. 211 / p.8
The graph in Figure 4, supplied by most electric
motor manufacturers, shows the change in
insulation resistance as a function of temperature:
as the temperature rises, the insulation
resistance decreases. The service life of the
windings, and therefore of the motor, is greatly
reduced as a result.
The graph in Figure 5 shows how a 5% increase
in the current, equivalent to a temperature rise of
approximately +10, cuts the service life of the
windings by half. Overload protection is therefore
essential to prevent overheating and reduce the
risks of internal damage to the motor due to the
breakdown of insulation in the windings.
100
10
1
0.1
0 80 60 40 20
C
Insulation
resistance (M)
100
75
50
25
0
In
T
1.05xIn
T+10
1.1xIn
T+20
1.15xIn
T+30
Current
C
Service life (%)
Fig. 4 : Change in the insulation resistance of motor
windings as a function of their temperature
Fig. 5 : Service life of motors as a function of their
operating temperature or current consumption
3.2 Faults external to the motor: Phenomena related to the motor power supply
Overvoltage
Any voltage applied to equipment where the
peak value exceeds the limits of a range dened
by a standard or a specication is an overvoltage
(see Schneider Electric Cahiers Techniques
nos. 151 and 179).
Temporary or permanent overvoltages (see
Fig. 6 ) can have different origins, namely:
atmospheric (lightning strikes)
electrostatic discharges
operation of equipment connected to the same
network
etc.
Their principal characteristics are shown in the
table in Figure 7 hereafter.
These disturbances, which are superimposed on
the line voltage, can act in two ways:
in common mode, between the active
conductors and the ground
in differential mode, between the different
active conductors
b
b
b
b
b
b
t
V
Fig. 6 : Example of overvoltage.
In most cases, the effect of an overvoltage is
a dielectric breakdown in the motor windings,
which destroys the motor.
Cahier Technique Schneider Electric no. 211 / p.9
Phase unbalance
A three-phase system is unbalanced when the
three voltages are not equal in amplitude and/or
are not at angles of 120 to each other.
The unbalance (see Fig. 8 ) can be caused by
the disconnection of a phase (asymmetry fault),
by the presence of single-phase loads in the
immediate environment of the motor, or by the
power source itself.
Fig. 7 : Characteristics of different types of overvoltage.
Type of overvoltage Duration Edge steepness -
frequency
Damping
Atmospheric Very short (1 to 10 s) Very high (1000 kV/s) High
Electrostatic discharge Very short (ns) High (10 MHz) Very high
Operational Short (1 ms) Average (1 to 200 kHz) Average
At ????? frequency Long (> 1 s) Line supply frequency Zero
which generates high rotor currents, causing
a very considerable overheating of the rotor
and leading to the overheating of the motor
(see Fig. 9 ).
t
V
V
max
V
min
Fig. 8 : Voltage readings from an unbalanced three-
phase system.
The following equation can be used to approach
the calculation of the unbalance:
U= 100 MAX
V
max
V
mean
V
mean
,
V
mean
V
min
V
mean








where:
U is the unbalance (%)
V
max
is the highest voltage
V
min
is the lowest voltage
V
mean
=
V
1
+V
2
+V
3
( )
3
The consequences of an unbalance of the
voltages applied to a motor are a decrease in
the useful torque and an increase in losses; the
unbalances give rise to an inverse component
Amount of
unbalance (%)
0 2 3,5 5
Staotr current (A) I
n
1.01 I
n
1.04 I
n
1.075 I
n
Increased losses
(%)
0 4 12.5 25
Heating (%) 100 105 114 128
Fig. 9 : Effect of voltage unbalance on the operating
characteristics of a motor.
IEC standard 60034-26 provides a derating rule
based on the voltage unbalance (see Fig. 10 )
which is recommended for use when this
phenomenon is known or predictable in the
power line supplying the motor. This derating
factor can be used either to increase the motor
dimensions to allow for the unbalance, or to
decrease the operating current of a motor with
respect to its nominal current.
1
0.9
0.8
0.7
0 4 5 3 2 1
Voltage
unbalance
(%)
Derating factor
Fig. 10 : Derating of a motor as a function of the
voltage unbalance in its power supply.
Cahier Technique Schneider Electric no. 211 / p.10
Brownouts and power cuts
A brownout (see Fig. 11 ) is an abrupt voltage
drop at one point of an electrical power network,
to a value which is conventionally taken to be
from 90% to 1% of the nominal voltage of the
LV network (IEC 61000-2-1). Power cuts are a
special case of brownout where the drop
exceeds 99% (IEC). They are characterized by a
single parameter: their duration. Short power
cuts have a duration of less than 1 minute (IEC),
while long power cuts have a longer duration.
The term micro-cut is used for durations of
about one millisecond.
If precautions are not taken, the fast
reconnection (~ 150 ms) of a decelerating
asynchronous motor runs the risk of reclosing in
phase opposition between the source and the
residual voltage maintained by the asynchronous
motor. In this case, the rst current peak can be
as much as three times the starting current
(15 to 20 I
n
) (see Schneider Electric Cahier
Technique no. 161).
These overcurrents and the consequent voltage
drops have a number of effects on the motor:
additional heating and electrodynamic forces in
the coils which may cause breaks in the
insulation
shocks with abnormal mechanical stresses on
the couplings, leading to premature wear or even
breakage
They can also affect other equipment such as
contactors (causing wear on the contacts or even
welding them together), or cause the tripping of
the master protection devices of the installation
and thus stop a production line or a workshop.
The consequences for a synchronous motor
The consequences are practically the same as
those for asynchronous motors. However,
synchronous motors can withstand larger
brownouts (about 50% greater) without stalling,
because their inertia is generally greater and the
voltage has less effect on the torque.
If stalling occurs, the motor stops, and the whole
starting procedure, which may be complex, has
to be recommenced.
Effects on variable speed machines
The problems posed by brownouts affecting
variable speed drives are as follows:
the impossibility of supplying sufcient voltage
to the motor (loss of torque, deceleration)
malfunction of the control circuits supplied
directly from the line
overcurrent when the voltage is restored
(recharging of the lter capacitors of the variable
speed drives)
overcurrent and current unbalance in the line if
a brownout occurs in one phase only
Variable speed drives generally fail if a voltage
drop of more than 15% occurs.
Presence of harmonics
Any periodic function (of frequency f) can be
broken down into a sum of sine waves with a
frequency of h x f (where h is an integer)
y(t) = Y
0
+ Y
h
sin(
h=1

ht +
h
)
where
Y
0
is the continuous component
h is the order of the harmonic
w is the pulsation (2pf)
Y
h
is the amplitude of the harmonic of order h
Y
1
is the fundamental component
v
v
b
b
v
v
v
v
-1
1
0.5
V
-0.5
0
t
Fig. 11 : Example of a brownout and a brief power cut.
These voltage variations may be due either to a
random phenomenon outside the application
(a fault in the mains network or an accidental
short circuit) or a phenomenon caused by the
installation itself (connection of high loads such
as motors, transformers, etc.). These variations
can have drastic effects on the motor.
The consequences for an asynchronous motor
When a brownout occurs, the torque of an
asynchronous motor (proportional to the square
of voltage) decreases abruptly and causes
deceleration. This deceleration is a function of
the amplitude and duration of the brownout, the
inertia of the rotating frames and the torque-
speed characteristic of the driven load. If the
torque developed by the motor becomes less
than the resistive torque, the motor stops (stalls).
After a power cut, the return of the power generates
a demand for reacceleration current which is
similar to the starting current and with a duration
dependent on the duration of the power cut.
When the installation has numerous motors, their
simultaneous reacceleration can cause a voltage
drop in the upstream impedances in the network.
The duration of the brownout is then prolonged
and can make reacceleration difcult (requiring
long restarts with overheading) or even
impossible (where the motor torque is less than
the resistive torque).
b
Cahier Technique Schneider Electric no. 211 / p.11
The harmonic distortion rate (or THD, Total
Harmonic Distortion) provides a measure of the
deformation of the signal:
THD(%) = 100x
Y
h
Y
1






2
h=2

The harmonic currents and voltages are created


by non-linear loads connected to the line supply.
Harmonic distortion (see Fig. 12 ) is a form of
pollution of the line supply which can give rise to
problems at a rate of more than 5%.
The electronic power devices (variable speed
drives, inverters, etc.) are the principal sources
which inject harmonics into the line. Since the
motor is not perfect, it can also create 3
rd
order
harmonics; in a delta connection, ux rebalancing
can then occur, generating a current in its windings.
The presence of harmonics causes an increase in
eddy current losses, leading to additional heating.
They can also generate pulsating torques (causing
vibration and mechanical fatigue) and noise
nuisance, and limit the use of motors at full load
(see Schneider Electric Cahier Technique no. 199).
t
V
h1
h5
h total (h1+h5)
Fig. 12 : Sinusoidal voltage reading, including 5
th
order harmonics.
3.3 Faults external to the motor: Phenomena related to the use of the motor
Motor starting: excessively long and/or
frequent starting
The starting phase of a motor is the period
required for it to reach its nominal rotation speed.
The starting time (t
S
) depends on the resistive
torque (T
r
) and the motor torque (T
m
). An increase
in the resistive torque, due to the load to be driven,
together with a decrease in the motor torque, due
to a line voltage drop (20 to 30% of Un), causes
an increase in the motor starting time as follows:
t
S
(s) =

30
J
N
T
m
T
r
where
J is the global moment of inertia of the moving
frames
N(r.p.s.) is the rotation speed of the rotor.
Because of its intrinsic characteristics, each
motor can only withstand a limited number of
starts, generally specied by its manufacturer (as
the number of starts per hour).
Similarly, each motor has a maximum starting
time which is a function of its starting current
(see Fig. 13 ).
t (s)
20
15
10
9
8
7
6
5
4
3
3 4 5 7 10 15
I
S
I
N
Fig. 13 : Permissible start times of motors as a function
of the ratio between starting current and nominal current.
Cahier Technique Schneider Electric no. 211 / p.12
Rotor locking
The locking of a motor due to mechanical factors
creates an overcurrent approximately equal to
the starting current. However, the heating which
it causes is much greater, since the losses in the
rotor are kept at their maximum level throughout
the locking and ventilation is prevented if it is
dependent on the rotation of the rotor. The rotor
temperatures can become very high (350 C).
Fig. 14 : Summary of the faults which can affect a motor, with their causes, effects and consequences.
3.4. Summary
This summary, shown in table form in Figure 14,
shows the possible causes, the probable effects
and the established consequences of each type
of fault.
In all cases, two forms of protection are always
required for motors:
short-circuit protection
overload (overheating) protection
b
b
Fault Cause Effects Consequences
for the motor
Short circuit b Contact between more than one phase,
between one phase and neutral, or
between several coils of a single phase
b Current peak
b Electrodynamic forces on
the conductors
Destruction of the
windings
Overvoltage b Lightning
b Electrostatic discharge
b Operation
b Dielectric breakdown in
the windings
Destruction of the
windings due to loss
of insulation
Voltage
unbalance
b Disconnection of a phase
b Single phase load upstream of the motor
b Decreased useful torque
b Increased losses
Overheating
(1)
Brownouts b Instability of the line supply voltage
b Connection of large loads
b Decreased useful torque
b Increased losses
Overheating
(1)
Harmonics b Pollution of the line supply by variable
speed drives, inverters, etc.
b Decreased useful torque
b Increased losses
Overheating
(1)
Excessive
starting time
b Excessively high resistive torque
b Brownouts
Increased starting time Overheating
(1)
Locking b Mechanical problem Overcurrent Overheating
(1)
Overload b Increased resistive torque
b Brownouts
Increase in current drawn Overheating
(1)
(1) Followed by short-circuiting and destruction of the windings after a period which depends on the importance and/or frequency of the fault.
Overload (deceleration or overspeed)
The overload of a motor is caused by an
increase in the resistive torque or by a drop in
the supply line voltage (> 10% Un). The increase
in the current drawn by the motor causes heating
which reduces its service life and can be fatal in
the longer or shorter term.
Cahier Technique Schneider Electric no. 211 / p.13
4 Protection functions
4.1 Short-circuit protection
Background
A short circuit is a direct connection between two
points having different electrical potentials; the
types of short circuit are:
alternating current: A connection between
phases, between a phase and neutral, between
a phase and a conductive frame, or between the
coils of a single phase
direct current: A connection between the two
polarities or between a conductive frame and the
polarity insulated from it
There are various possible causes: Deterioration
of the insulating varnish on the conductors,
loosening, breakage or stripping of wires or
cables, presence of metallic foreign bodies,
conductive deposits (dust, moisture, etc.),
penetration of water or other conductive liquids,
deterioration of the load, and errors in wiring at
start-up or during servicing.
A short circuit is indicated by an abrupt increase
in the current, which may become several
hundred times greater than the operating current
in just a few milliseconds. A short circuit can
have devastating effects and cause major
damage to equipment. It is characterized by two
phenomena:
A thermal phenomenon which corresponds to
the amount of energy released in the electrical
circuit through which the short-circuit current I
ows for a time t, according to the formula I
2
t,
expressed in A
2
s. This thermal effect can cause:
melting of the contacts of the contactor
destruction of the thermal elements of a
bimetallic relay, in the case of type I coordination
(see the Coordination section)
generation of electric arcs
burning of insulating materials
re in the equipment.
An electrodynamic phenomenon between the
conductors gives rise to strong mechanical
forces, caused by the ow of current, with the
following effects:
deformation of the conductors forming the
motor windings
breakage of the insulating supports of the
conductors
repulsion of the contacts (inside contactors)
which may lead to their melting and welding
b
b
b
v
v
v
v
v
b
v
v
v
Such effects are dangerous to both property and
personnel. It is therefore essential to use short-
circuit protection devices designed to detect faults,
and to break the circuit very quickly, if possible
before the current reaches its maximum level.
Two protection devices are commonly used for
this purpose:
fuses (circuit breakers) which break the circuit
by blowing, and must be replaced subsequently
magnetic trip circuit-breakers, often simply
called magnetic circuit-breakers which
automatically break the circuit when their poles
are opened, and which only require a resetting
operation to bring them back into service.
Short-circuit protection can also be incorporated
into multi-function devices such as motor circuit-
breakers and contactor/circuit-breakers.
Denitions and characteristics
The main characteristics of short-circuit
protection devices are:
the breaking capacity: i.e. the highest
presumed short-circuit current which a protection
device can interrupt at a given voltage
the making capacity: i.e. the highest current
which the protective device can pass at its
nominal voltage in specied conditions. The
making capacity is equal to k times the breaking
capacity, according to the table in Figure 15 .
Fuses
Fuses provide protection for one phase at a time
(single-phase protection), with a high breaking
capacity in a small volume. They limit the level of
I
2
t and the electrodynamic stresses (I
peak
).
v
v
b
b
Fig. 15 : Breaking and making capacity as specied by
IEC Standard 60947-2 for circuit-breakers.
Breaking capacity
(BC)
Cos j Making
capacity (MC)
4.5 kA < BC < 6 kA 0.7 1.5 BC
6 kA < BC < 10 kA 0.5 1.7 BC
10 kA < BC < 20 kA 0.3 2 BC
20 kA < BC < 50 kA 0.25 2.1 BC
50 kA < BC 0.2 2.2 BC
Cahier Technique Schneider Electric no. 211 / p.14
They are tted as follows:
either to special supports called fuseholders
or in isolators, where they replace sockets or
terminal strips (see Fig. 16 ).
b
b
currents, circuit-breakers operate more quickly
than fuses.
This protection conforms to IEC Standard 60947-2.
Effective interruption of a short-circuit current
requires three essential functions:
very fast detection of the fault current
very fast separation of the contacts
interruption of the short-circuit current
Most magnetic circuit-breakers for motor
protection are current limiters, and therefore
also contribute to the coordination (see Fig. 18 ).
Their particularly short breaking time enables
them to interrupt the short-circuit current before
it reaches its maximum amplitude. The thermal
and electrodynamic effects are therefore also
limited, thus providing better protection of cables
and equipment.
b
b
b
L1 L3 L2
a b
Fig. 16 : Fused 32 A and 125 A isolators
(Telemecanique LS1-D32 [a] and GS1-K4 [b]).
Note that fuse cartridges with strikers can be
combined with an all-pole breaking device (often
the motor control contactor) to prevent single-
phase operation after they have blown.
Type aM fuses are used for motor protection.
They have the characteristic of allowing excess
magnetizing currents to pass when motors are
switched on. Therefore, they are unsuitable for
overload protection (unlike gG fuses). For this
reason, an overload relay has to be added to the
motor supply circuit.
As a general rule, their rating must be
immediately above the full load current of the
motor to be protected.
Magnetic circuit-breakers
Subject to their breaking capacity, these circuit-
breakers can protect installations against short
circuits by means of their magnetic trip releases
(one per phase) (see Fig. 17 ).
Magnetic circuit-breakers are intrinsically all-
pole breaking devices: the tripping of a single
magnetic trip release causes the simultaneous
opening of all the poles. For low short-circuit
I > I > I >
L1 L3 L2
Fig. 17 : Telemecanique GV2-L magnetic circuit-
breaker and its graphic symbol.
I
I
d
t
Non-limiting
Limiter
Limiting zone
Fig. 18 : Tripping curves of magnetic circuit-breakers.
4.2 Overload protection
Background
Overloading is the most common motor fault. It
causes an increase in the current drawn by the
motor, as well as thermal effects. The insulation
class determines the normal heating of a motor
at an ambient temperature of 40 C. If the
maximum operating temperature is exceeded,
this reduces the service life as a result of the
premature ageing of the insulation.
However, it should be noted that an overload
leading to heating above the normal level does
not have immediate negative consequences if
it is limited in time and infrequent. Thus it does
not necessarily mean that the motor must be
stopped, but normal operating conditions must
be resumed as soon as possible.
The importance of proper overload protection is
obvious, because:
it protects the service life of motors by preventing
them from operating in abnormal heating conditions
it ensures continuity of operation, by:
avoiding untimely stoppage of motors
enabling restarting to be carried out in the best
safety conditions for personnel and equipment,
after tripping.
The actual operating conditions (ambient
temperature, altitude of use and standard
service) must be known in order to determine the
b
b
v
v
Cahier Technique Schneider Electric no. 211 / p.15
operating levels of the motor (in terms of power and
current) and in order to choose effective overload
protection (see Fig. 19 ). These operating levels
are supplied by the motor manufacturer.
According to the desired level of protection,
overload protection can be provided in the form
of relays of the following types:
overload, thermal (bimetallic) or electronic,
which will at least protect the motors in the
following two cases:
overload, by controlling the current drawn in
each phase
phase unbalance or failure, by means of their
differential devices
PTC (Positive Temperature Coefcient)
thermistor probe
excess torque
multi-function
Reminder: A protection relay does not have a
circuit-breaking function. It is designed to open a
circuit-breaking device, generally a contactor,
which must have the requisite breaking capacity
for the fault current to be interrupted.
b
v
v
b
b
b
Fig. 19 : Derating factors of motors according to their operating conditions.
For this purpose, a protection relay has a fault
contact (NC) which is to be connected in series
with the power supply to the contactor coil.
Overload relays (thermal or electronic)
Background
These relays protect motors against overloads,
but they must allow the temporary overload
caused by starting, and must not trip unless the
starting time is abnormally long.
Depending on the application, the motor starting
time can vary from a few seconds (for no-load
starting, low resistive torque, etc.) to several tens
of seconds (for a high resistive torque, high inertia
of the driven load, etc.). It is therefore necessary
to t relays appropriate to the starting time.
To meet this requirement, IEC Standard
60947-4-1 denes several classes of overload
relays, each characterized by their trip time
(see Fig. 20 ).
The relay rating is to be chosen according to the
nominal motor current and the calculated starting
time.
b
Altitude Ambient temperature
m 30 C 35 C 40 C 45 C 50 C 55 C 60 C
1000 1.07 1.04 1.00 0.96 0.92 0.87 0.82
1500 1.04 1.01 0.97 0.93 0.89 0.84 0.79
2000 1.01 0.98 0.94 0.90 0.86 0.82 0.77
2500 0.97 0.95 0.91 0.87 0.84 0.79 0.75
3000 0.93 0.91 0.87 0.84 0.80 0.76 0.71
3500 0.89 0.86 0.83 0.80 0.76 0.72 0.68
4000 0.83 0.81 0.78 0.75 0.72 0.68 0.64
The values in the table above are provided for guidance only. In reality, the derating of a motor
depends on it size, its insulation class, its type of construction (self-cooled or forced-cooled, IP 23 or
IP44 degree of protection, etc.), and varies according to the manufacturer
Note: The nominal power which is generally shown on a motor plate is specied by the manufacturer
for a continuous service S1 (operation at constant speed and for a long enough time to reach
thermal equilibrium).
There are other standard services, such as temporary service S2, or periodic intermittent services
S3, S4 and S5 for which the motor manufacturer species an operating power, different from the
nominal power, for each case.
Fig. 20 : Main tripping classes of overload relays according to IEC 60947-4-1.
Trip time from the following states:
Cold
at 1.05 x I
r
Hot
at 1.2 x I
r
Hot
at 1.5 x I
r
Cold
at 7.2 x I
r Narrower tolerances (band E)
Class
10 A > 2 hrs < 2 hrs < 2 mins 2 s < tp < 10 s -
10 > 2 hrs < 2 hrs < 4 mins 4 s < tp < 10 s 5 s < tp < 10 s
20 > 2 hrs < 2 hrs < 8 mins 6 s < tp < 20 s 10 s < tp < 20 s
30
(1)
> 2 hrs < 2 hrs < 12 mins 9 s < tp < 30 s 20 s < tp < 30 s
(1) class used infrequently in Europe, but used widely in the United States
Cold state: Initial state without previous load
Hot state: Thermal equilibrium reached at I
r

I
r
: Setting current of the overload relay
Cahier Technique Schneider Electric no. 211 / p.16
The limits of use are also characterized by graphs
(see Fig. 21 ) showing time as a function of the
adjustment current (expressed as multiples of I
r
).
These relays have a thermal memory (except for
some electronic overload relays, as indicated by
their manufacturers) and can be connected as
follows:
in series with the load
or, for high power, to current transformers in
series with the load
Bimetallic thermal relays (see Fig. 22 )
These are combined with contactors to protect
motors, lines and equipment from small prolonged
overloads. They are therefore designed to allow
the normal starting of motors without tripping.
However, they must be protected from large
overloads by a circuit-breaker, or by fuses (see
Short-circuit protection).
The operating principle of a thermal overload
relay is based on the deformation of its bimetallic
strips when heated by the current owing
through them (see Fig. 23 ).
The bimetallic strips are deformed when the
current ows, and, depending on their
adjustment, can cause the sudden opening of
the relay contacts.
Resetting is only possible when the bimetallic
strips have cooled down sufciently.
Thermal overload relays can be used for both
alternating and direct current, and are generally:
three-pole
compensated, i.e. non-sensitive to variations in
ambient temperature (identical trip curve from
0 to 40 C over a standard range (see Fig. 24
hereafter)
v
v
b
v
v
30
20
10
1.05
1.20
1.50 7.2
I/I
r
t (s)
Class 30
Class 20
Class 10
Fig. 21 : Tripping curves of overload relays.
Fig. 22 : Telemecanique LRD bimetallic overload relay
and its graphic symbol.
Current conductor
Blade with high
coefcient of expansion
Blade with zero
coefcient of
expansion Bimetallic strip after heating
Support forming
xed point
Current input
Trip release
system
Trip capacity
setting Current output
Bimetallic strip with
resistor
Fig. 23 : View of the inside of a thermal overload relay and detail of one of its bimetallic strips.
Cahier Technique Schneider Electric no. 211 / p.17
manually or automatically reset
graduated in motor amperes: the current
shown on the motor name plate is displayed
directly on the relay
They can also be sensitive to a phase failure: this
is the differential concept. This function
prevents the single-phase operation of the motor,
and meets the conditions of IEC 60947-4-1 and
60947-6-2 (see Fig. 25).
v
v
Fig. 24 : Tripping zone for compensated thermal
overload relays according to ambient air temperature
(source: IEC 60947-4-2 and 6-2).
Fig. 25 : Operating limit of a differential thermal
overload relay (sensitive to a phase failure).
Fig. 26 : Electronic overload relay (Telemecanique LR9F)
0.8 I
r
0.9 I
r
1 I
r
1.1 I
r
1.2 I
r
1.3 I
r
1.4 I
r
-10 30 40 50 20 10 0
C
Ambiant air temperature
Lower limit
Upper limit
Tripping zone
Trip time Multiple of the setting
current
> 2 hrs 2 poles : 1.0 I
r
1 pole : 0.9 I
r
< 2 hrs 2 poles : 1.15 I
r
1 pole : 0
basis of a model which reconstitutes the thermal
time constants of the motor, the electronic system
calculates the motor temperature constantly as a
function of the current owing through it and the
operating time. The protection thus gives a better
approximation of the actual conditions and can
prevent incorrect tripping. Electronic overload
relays are less sensitive to the thermal environment
of the location where they are installed.
In addition to the conventional functions of overload
relays (protection of motors from overloads and
phase unbalance and failure), electronic overload
relays can be supplemented with options such as:
PTC probe temperature monitoring
protection against locking and excess torque
protection against phase inversions
protection against insulation faults
protection against no-load operation
etc.
PTC thermistor probe relays
These protection relays monitor the actual
temperature of the motor to be protected. They
offer extremely precise temperature measurement:
the small volume of the probes gives them a very
low thermal inertia and therefore a very short
response time.
Allowing direct monitoring of the stator winding
temperature, they can be used to protect motors
against overload, rises in ambient temperature,
ventilation circuit faults, excessive starting
frequency, jerky running, etc.
They comprise:
One or more Positive Temperature Coefcient
(PTC) thermistor probes placed within the
windings of the motors or in any area subject to
heating (bearings, etc.).
They are static components whose resistance
increases sharply when the temperature reaches
a threshold called the Nominal Operating
Temperature (NOT), as shown in Figure 27 next
page.
An electronic device, supplied with alternating
or direct current, which constantly measures the
resistance of the probes combined with it. When
the NOT is reached, the threshold circuit detects
the sharp resistance increase of the probe and
then causes the output contacts to change state.
Depending on the probes chosen, this protection
method can be used as follows:
either to provide an alarm without stopping
the machine (where the NOT is lower than
the maximum temperature specied for the
component to be protected)
or to stop the machine (where the NOT is
equal to the maximum specied temperature).
(see Fig. 28 next page)
The use of this protection method must be
specied in advance, because the probes
have to be incorporated in the windings during
the manufacture of the motor, or during any
rewinding operation after an mishap.
v
v
v
v
v
v
b
b
v
b
Widely used, this relay offers excellent reliability,
and is inexpensive. It is particularly recommended
if there is a risk of the rotor locking.
However, it has the disadvantage of not taking into
account in a very precise way the thermal state of
the motor to be protected, and of being sensitive
to the thermal environment of the location where
it is installed (cabinet ventilation, etc.).
Electronic overload relays (see Fig. 26 )
These relays benet from the advantages of
electronics which enables a more detailed
thermal image of the motor to be created. On the
b
Cahier Technique Schneider Electric no. 211 / p.18
The choice of the PTC probes to be incorporated
depends on the insulation class and structure of
the motor. This choice is normally made by motor
manufacturers or rewinders who are the only
ones who have the necessary skill.
Because of these two constraints, the choice of
PTC probe protection is generally reserved for
top-range equipment with expensive motors.
Excess torque relays: a supplementary form
of protection (see Fig. 29 )
As a supplement to thermal protection by relay or
PTC probe, these protect the drive chain in case
of rotor locking, seizing or mechanical shock.
Fig. 28 : Electronic device (Telemecanique LT3) to be
combined with three thermistor probes to stop a motor
when the maximum temperature is exceeded.
Fig. 29 : The excess torque relay (Telemecanique
LR97D) is a supplementary form of protection in case
of rotor locking, seizing or mechanical shock.
Fig. 30 : Multi-function relay (Telemecanique LT6).
Unlike most overload relays, these relays do not
have a thermal memory. They have a operating
characteristic for a specied time (with adjustable
threshold current and delay).
The excess torque relay can be used as overload
protection for motors where starting is lengthy or
very frequent (e.g. those used for hoists).
Multi-function relays (see Fig. 30 )
These relays can protect motors from the main
causes of heating.
Moreover, the electronic technology provides
these relays with capacity for communication
with PLCs and supervisors via eldbuses.
This link with a PLC facilitates the set-up and
maintenance.
It makes it possible to set parameters and
activate the necessary protection, to congure
and operate the motor driver, and to monitor
the states of starting, alarms and tripping. It can
be used for exchanging data, measurement
information (currents, heating, etc.) with the
higher PLC level (controlling PLC), and for
monitoring the thermal state of the motor. This
facilitates diagnostics and the implementation of
preventive measures.
These relays are used for the isolated protection
of sensitive motors, i.e. those for which an
incorrect stop would have serious effects on
personal protection, safety, production losses, etc.
The diagram below shows the possibilities of a
multi-function relay connected to a supervising
PLC (see Fig. 31 opposite page).
4000
1330
550
250
20
NOT -20 -20 0
NOT -5
NOT+5
NOT+15
TNF
T (C)
High markers
Low markers
R ()
(Logarithmic scale)
Fig. 27 : Markers or operating points of PTC
thermistor probes.
Cahier Technique Schneider Electric no. 211 / p.19
4.3. Selection table for protection relays
M
3 a
M
3 a
M
3 a
Modbus network
PTC probes
PLC
Multi-function
protection relay
Computer
I > I > I >
Fig. 31 : Example of a communications network based on a multi-function relay (source: Telemecanique).
Type of relay Overload relay
(thermal or
electronic)
PTC probe relay Overload relay Multi-function
relay
Causes of heating:
Overload
Rotor locking
Phase failure
Ventilation fault With PTC probe
Shaft bearing seizing With PTC probe
Excessive starting time Class 20 or 30
Demanding service With PTC probe
Torque shocks With PTC probe
Some
Telemecanique
references
LR2K, LRD,
LR9D, LR9F
LT3 LR97D & LT47 LT6
Tesys U : Standard or
expandable CU*
Multi-function CU*
(*) CU: Control Unit Entirely suitable Possible solution Unsuitable (no protection)
Cahier Technique Schneider Electric no. 211 / p.20
4.4 Motor circuit-breakers (thermal-magnetic circuit-breakers)
Background
A motor circuit-breaker is a thermal-magnetic
circuit-breaker which provides protection against
both short circuits and overloads, by rapidly
opening the faulty circuit. It is a combination of a
magnetic circuit-breaker (see Short-circuit
protection) and an overload relay (see Overload
protection). It conforms to IEC 60947-2 and
60947-4-1 (see Fig. 32 ).
In these circuit-breakers, the magnetic devices
(short-circuit protection) have a non-adjustable
trip threshold, generally about 10 times the
maximum setting current of thermal trips.
Their thermal elements (overload protection) are
compensated against variations in ambient
temperature. The thermal protection threshold
can be adjusted on the front panel of the circuit-
breaker. Its value must match the nominal
current of the motor to be protected.
In all these circuit-breakers, coordination (type II)
between the thermal elements and the short-
circuit protection is provided by the design.
Additionally, in the open position, most of these
devices have a sufcient clearance distance
(between their contacts) to provide an isolation
function. They also incorporate a padlocking
device required for logging.
Tripping curves
A motor circuit-breaker is characterized by its
tripping curve, which represents the trip time of
the circuit-breaker as a function of the current
(multiple of I
r
).
This curve has four zones (see Fig. 33 ):
Fig. 32 : Motor circuit-breaker (Telemecanique GV7)
and its graphic symbol.
I > I > I >
L1 L3 L2
the normal operation zone 1 . Since I < I
r
,
there is no tripping.
the thermal overload zone 2 . The thermal
element trips; the trip time decreases as the
overload increases. This tripping mode is
therefore called inverse time in standards.
The high current zone 3 , monitored by the
instantaneous magnetic element or short-circuit
element whose operation is instantaneous (less
than 5 ms).
And, in some circuit-breakers (electronic circuit-
breakers), an intermediate zone 4 monitored by
a time-delayed magnetic element whose operation
is delayed (by 0 to 300 ms). This tripping mode is
called independent delay mode in standards. It
can be used to avoid incorrect tripping when
peak magnetizing current of motors is present at
switch-on.
Their limits are:
I
r
: setting current of the overload protection; this
must match the nominal current (I
n
) of the motor
to be protected.
I
m
: trip current of the time-delayed magnetic
protection.
I
inst
: trip current of the instantaneous magnetic
protection. This can vary from 3 to 17 times I
r
,
but is generally close to 10 I
r
.
I
cs
: rated breaking capacity in short circuit
I
cu
: ultimate (maximum) breaking capacity in
short circuit
b
b
b
b
I(A)
I
m
I
inst
I
r
t(s)
I
cu
I
cs
Overload
zone
Short-circuit
zone
1.05 I
r
1.20 I
r
1 2
3
4
Fig. 33 : Operating zones of a thermal-magnetic circuit-
breaker.
Cahier Technique Schneider Electric no. 211 / p.21
5 Motor starters
5.1 Background
A motor starter has four basic functions:
Isolation
Short-circuit protection
Overload protection
Control (on - off).
Each motor starter can be enhanced with
additional functionality according to the
application requirements. These relate to:
b
b
b
b
Power: speed adjustment, progressive starting,
phase inversion, etc.
Control: auxiliary contacts, time delay,
communication, etc.
In the design of a motor starter, the functions
are distributed in different ways, as shown
schematically in Figure 34 .
b
b
M
Thermal-magnetic
circuit-breaker:
b short-circuit protection,
b overload protection
b isolation for maintenance.
Contactor :
b on-off
Motor
M
Magnetic circuit-breaker:
b short-circuit protection,
b isolation for maintenance.
Contactor :
b on-off
b disconnection in case
of fault.
Variable speed drive:
b progressive starting,
b variable speed control,
b motor protection,
b overload protection.
Motor
M
Isolator-fuse:
b short-circuit
protection,
b isolation for
maintenance.
Contactor:
b on-off
Overload relay:
b overload
protection
Motor
Fig. 34 : The various functions and their combinations forming a motor starter.
5.2 The basic functions of motor starters
Isolation
The isolation function is essential, and must
form the basis of any circuit (see installation
standards NF C15-100, IEC 60364-5-53); it is
not stipulated but is recommended for all motor
starters. It serves to isolate the circuits from their
power source (power supply line) in a secure
way in order to protect property and personnel
during maintenance, repair or modication work
carried out on the downstream electrical circuits.
This isolation must be designed according to the
specications, which require:
simultaneous all-pole breaking
conformity with specied clearances according
to the supply voltage
interlocking
visible, or fully apparent, circuit-breaking:
b
b
b
b
visible breaking signies that the opening of
the poles can be viewed directly by an operator
apparent breaking is identied either by the
position of the actuator, or by a position indicator
which, according to the standard, must not
indicate the off position unless the contacts
are actually separated by a sufcient distance
specied in the standards. Manufacturers offer
numerous devices to perform this function. The
isolation and short-circuit protection functions
are often combined in a single device (e.g. fused
isolator). For this purpose, some basic devices
have to be supplemented with an additional
device, such as a plug-in support.
Reminder: An isolator is intended to isolate
a circuit; it has no breaking or making capacity.
It is therefore always operated in no-load
conditions.
v
v
Cahier Technique Schneider Electric no. 211 / p.22
Short-circuit protection
This function requires the detection of overcurrents
following short circuits (generally more than
10 times the nominal current) and the opening
of the faulty circuit. It is provided by fuses or
magnetic circuit-breakers.
Overload protection
This function requires the detection of excess
currents following overloads (I
r
< I
overloads
< I
m
)
and the opening of the faulty circuit. It is provided
by electromechanical or electronic devices
(overload relays) combined with a breaking device
(circuit-breaker or contactor) or incorporated in
electronic starters or variable speed drives. It also
protects the motor line against thermal overloads.
Control
Control signies the closing (making) and
opening (breaking) of an electrical circuit under
load. The control function is provided by switches
or possibly by motor circuit-breakers, starters or
variable speed drives. However, the contactor
is the product most commonly used for this
function, since it allows remote control. For
motors, this control device must permit a large
number of operations (electrical durability) and
must conform to IEC 60947-4-1. According to
these standards, manufacturers must specify the
following characteristics for this equipment:
Control circuit
the nature of the control current, and its
frequency in the case of alternating current
the rated voltage of the control circuits (U
c
) or
the control supply voltage (U
s
)
Power circuit
the rated operating voltage (U
o
): this is
generally expressed as the voltage between
phases. It determines the operation of the
b
v
v
b
v
circuits to which the making and breaking
capacity relates, the type of application and the
starting characteristics
the rated operating current (I
o
) or rated
operating power : this characteristic is dened
by the manufacturer according to the specied
conditions of use and takes into account, in
particular, the rated operating voltage and the
conventional thermal current (I
th
corresponds to
the maximum value of the test current: I
th
u I
e
).
In the case of equipment for the direct control of
a single motor, the indication of a rated operating
current can be replaced or supplemented by that
of the rated maximum available power.
In some cases, this information is supplemented
with:
the duty rating, with details of the intermittent
duty class, if applicable. The classes dene
different operating cycles
the rated making and/or breaking capacity.
These are maximum currents, specied by the
manufacturer, which a piece of equipment can
establish (making) or interrupt (breaking) in a
satisfactory way in specied conditions. The
rated making and breaking capacities are not
necessarily specied by the manufacturer, but
the standard requires minimum values for each
category of operation.
The standards of the IEC 60947 series
dene operating categories according to the
applications for which the control devices
are intended (see Fig. 35 ). Each category
is characterized by one or more operating
conditions such as:
currents
voltages
the power factor or time constant
and other operating conditions if necessary.
v
v
v
b
v
v
v
v
Fig. 35 : The different operating categories of contactors according to their intended applications,
as shown in IEC 60947-1.
Type of current Operating categories Typical applications
Alternating
current
AC-1 Non-inductive or low-inductance loads, resistance furnaces. Power
distribution (lighting, generator sets, etc.)
AC-2 Slip-ring motors: starting, disconnection. Equipment for intensive use
(lifting, handling, grinding machines, rolling mill trains, etc.)
AC-3 Squirrel cage motors: starting, disconnection of started motors
(1)
. Motor
control (pumps, compressors, fans, machine tools, conveyors, presses, etc.)
AC-4 Squirrel cage motors: starting, reversing, inching. Equipment for
intensive use (lifting, handling, grinding machines, rolling mill trains, etc.)
Direct current DC-1 Non-inductive or low-inductance loads, resistance furnaces.
DC-3 Shunt motors: starting, reversing, inching. Dynamic disconnection of
motors for direct current.
DC-5 Series motors: starting, reversing, inching. Dynamic disconnection of
motors for direct current.
(1) The AC-3 category can be used for inching or reversing for occasional operations of limited duration, such as the assembly of a
machine; the number of these operations during these limited periods does not normally exceed ve operations per minute or ten
in a period of 10 minutes.
Cahier Technique Schneider Electric no. 211 / p.23
Thus the following characteristics are taken into
account, for example:
the making and breaking conditions
the nature of the controlled load (squirrel cage
motor, slip-ring motor, resistor)
conditions in which making and breaking takes
place (motor running, motor stalled, during
starting, counter-current braking, etc.).
Choosing a contactor:
The operating categories dened in the standard
can be used for an initial selection of equipment
capable of meeting the requirements of the
motors intended application. However, other
constraints must be taken into account, and not
v
v
v
b
all of these are dened by the standard. Thus
there are factors external to the application,
such as the climatic conditions (temperature,
humidity), the geographical location (altitude,
coast).
In some situations, the reliability of the
equipment can also be a critical factor,
particularly when maintenance is difcult. The
electrical life (durability of the contacts) of the
equipment (the contactor) is also an important
characteristic.
It is therefore essential to consult
comprehensive, detailed catalogues, in order
to ensure that the chosen equipment meets all
these requirements.
5.3 The special case of electronic starters and variable speed drives
Starting asynchronous motors by direct connection
to the line supply is the solution which is most
common, most economical and most suitable for a
wide range of machines. However, this may entail
constraints (such as the inrush current on starting,
mechanical shocks on starting, the impossibility
of controlling acceleration and deceleration and
the impossibility of varying the speed) which may
be troublesome for some applications, or even
incompatible with the desired operation of the
machine. Electronic starters and variable speed
drives (see Fig. 36 ) can overcome these problems,
but the conventional protection described above
is ineffective with equipment which modulates
the electrical energy supplied to the motor.
Electronic variable speed drives and starters
therefore have integrated protection. Modern
variable speed drives generally provide overload
protection for motors and self-protection. On the
basis of the current measurement and data on
the speed, a microprocessor calculates the
motor temperature increase and sends an alarm
or trip signal if the heating is excessive. Variable
speed drives, and in particular frequency
inverters, are also often tted with protection
against:
short-circuits between phases and between
phase and ground
overvoltages and voltage drops
phase unbalance
single-phase operation
Additionally, data produced by the thermal
protection incorporated in the variable speed
drive can be exchanged with a PLC or a
supervisor via the communications link provided
in the more advanced variable speed drives and
starters.
For further information about electronic starters
and variable speed drives, see Schneider-
Electric Cahier Technique no. 208.
b
b
b
b
Fig. 36 : Variable speed drive (Telemecanique ATV58H).
5.4 A complementary function: communication
Communication is a function that has become
almost indispensable in industrial production
processes and systems. It provides a remote
method of monitoring the machines of a
production system, interrogating different
devices, and controlling the machines.
Industrial network communication can be
broken down into ve levels, represented by
a triangle, according to the CIM (Computer
Integrated Manufacturing) concept (see Fig. 37
next page).
For this form of communication, which can also
be global, between all elements of a production
system, communicating components or modules
(see Fig. 38 next page) are integrated into many
devices, including protection devices such as
multi-function relays or motor starters.
With communication modules such as AS-i,
Modbus, Probus, etc., it is possible, for
example, to control a motor (remote on-off
control of the motor starter), and also to remotely
monitor the motor load (current measurement)
Cahier Technique Schneider Electric no. 211 / p.24
and/or existing faults (overcurrent overload, etc.)
or earlier faults (log).
Communication systems are not only useful
for integrating protection into automatic
industrial processes, but also enable any
breakdown to be anticipated (pre-alarm
conditions, etc.), thus reducing downtime and
ensuring continuity of operation. It therefore
helps to improve equipment management, with
positive effects on the economic outcome.
Entreprise level Production management
Factory level Scheduling
Workshop level Supervision
Cell level Automated systems
Machine level Sensors - Actuators
Fig. 37 : The ve levels of industrial communication.
5.5. Motor starters and coordination
Fig. 38 : A starter-controller with the Modbus
communication module (Telemecanique Tesys U).
Motor starter solutions
As explained at the start of this chapter, the main
functions required from a motor starter (isolation,
control and protection against short circuits and
overloads) can be provided by different devices.
There are three possible combinations of devices
(see Fig. 39 ) which enable a motor starter to
provide all these functions correctly, but they
require compatibility between the characteristics
of each of the combined devices.
The all in one solution:
The three functions are combined in a single
device; its overall performance is guaranteed by
the manufacturer. For the user, this is the simplest
solution, from the design phase through to
installation: it is easy to install (less wiring) and
can be chosen immediately (no special research
needed).
The two device solution
Thermal-magnetic circuit-breaker + contactor
Compatibility between the characteristics of the
two devices must be checked by the user.
The three device solution
Magnetic circuit-breaker + contactor + overload
relay
This can cover a wide power range. This
combination requires a compatibility study for the
selection of the devices and an installation study
for their mounting on a chassis or in an enclosure.
b
b
b
Fig. 39 : The three possible combinations of devices for
a motor starter.
Solution "1 product"
Solution "2 products"
Solution "3 products"
GVE LE LC1 K LRK
Magnetic + contactor + overload
circuit-breaker relay
GV2 M LC1 K
Thermal-magnetic + contactor
circuit-breaker
LU
motor starter
Cahier Technique Schneider Electric no. 211 / p.25
This nature of this operation (compatibility,
choice and installation) is not always obvious
to users, since it is necessary to combine the
characteristics of the different devices and
have the skill to compare them. For this reason,
manufacturers investigate the combinations of
devices and then offer them in their catalogues.
As part of this operation, they attempt to nd
optimal combinations of protection devices: this
is the coordination concept.
Coordination between protection and control
This coordination is the optimal combination of
different protection devices (for short circuits and
overloads) and the control device (contactor)
which make up a motor starter.
Designed for a given power rating, it provides the
best protection for the equipment controlled by
the motor starter (see Fig. 40 ).
It has the double advantage of reducing
equipment and maintenance costs, since the
different protection devices are matched with
each other as precisely as possible, without
unnecessary redundancy.
There are different types of coordination.
Two types of coordination (type 1 and type 2) are
dened by IEC 60947-4-1.
Type 1 coordination: this is the standard
solution and is most commonly used. It requires
that, in short-circuit conditions, the contactor
or starter must not create any risk to personnel
or installations. It allows the necessary repair
or replacement of components before the
restoration of service.
b
v
Type 2 coordination: this is the high-
performance version; it requires that the
contactor or starter must not create any risk
for personnel or installations, and must be
capable of operating afterwards. The risk of
contact welding is accepted; if this occurs, the
manufacturer must state the action to be taken
for the maintenance of the equipment.
There is a very high performance version,
provided in CPS (control and protective switching
devices) and offered by some manufacturers,
called Total Coordination.
This type of coordination requires that, in short-
circuit conditions, the contactor or starter must
not create any risk for personnel or installations,
and must be capable of operating afterwards.
The risk of contact welding is not acceptable; the
motor starter must be capable of being restarted
immediately.
What type of coordination should be chosen?
The choice of the type of coordination depends
on the operating parameters.
It must meet the users requirements at an
optimal installation cost.
Type 1
Acceptable when continuity of service is not
required and service can be restored after the
replacement of the faulty elements.
In this case, the maintenance service must be
effective (available and competent).
The advantage is a lower equipment cost.
Type 2
To be chosen when continuity of service is required.
It requires less maintenance.
v
v
b
v
v
I(A)
0.75I
c
1.25I
c
I
n
t(s)
I
c
Tripping curves:
overload relay
magnetic trip release
fuse
Thermal withstand limits:
- contactor
- circuit-breaker
- overload relay
Overload
zone
Impedance-
earthed
short-circuit
Short-circuit
zone
1
1
2
2
3
3
To enable a motor starter to operate
correctly, the coordination between all
the devices must meet all the following
requirements:
the overload relay must protect the
magnetic circuit-breaker in the overload
zone : its curve 1 must pass below that of
the thermal withstand of the circuit-breaker;
and, conversely, in the short-circuit
zones, in order to protect the thermal relay,
the short-circuit trip curve must pass below
that of the thermal withstand of the relay;
nally, in order to protect the contactor,
its thermal withstand limit must be above
the curves of the two trip releases (thermal,
1, and magnetic, 3) (or the fuse, 2).
Note that the standard species the limit
test currents:
up to 0.75 I
c
only the thermal protection
must operate;
above 1.25 I
c
only the short-circuit
protection must operate.
b
b
b
b
b
Fig. 40 : The principles of coordination.
Cahier Technique Schneider Electric no. 211 / p.26
When immediate restarting of the motor
is essential, Total Coordination must be
chosen.
No maintenance is required.
v The types of coordination offered in
manufacturers catalogues simplify the users
choices and provide assurance that the motor
starter conforms to the standard.
5.6 Control and protective switching devices (CPS)
CPS or starter-controllers are designed
to perform the functions of control and
protection (against overload and short circuit)
simultaneously; they are also designed to enable
control to be provided in short-circuit conditions.
They can also provide complementary functions
such as isolation, enabling them to perform all the
functions of a motor starter. They conform to IEC
60947-6-2, which in particular denes the rated
values and the operating categories of CPS, and
to the principles of IEC 60947-1 and 60947-4-1.
The various functions of a CPS are combined
and coordinated to provide continuity of service
for all currents up to the rated breaking capacity
for short-circuit operation, Ics, of the device. The
system may or may not incorporate a single
device, but its characteristics are always rated as
if for a single device. Additionally, the guarantee
of total coordination between all the functions
gives the user a simple choice of an optimal
protection device which is easy to use.
Even if it takes the form of a single device, a
CPS can provide a degree of modularity equal
to, or even greater than, that of a three product
motor starter. This is true of the Telemecanique
Tesys U starter-controller (see Fig. 41 ). This
allows a control unit integrating the protection
and control functions for motors from 0.15 A to
32 A to be added, or changed at any time, on a
general-purpose power base unit or sub-base
rated at 32 A (see Fig. 42 ).
Additional functionality can also be installed, for
the following aspects:
power: inverter unit, limiter
control:
function modules: alarms, motor load,
automatic reset, etc.
communication modules: AS-i, Modbus,
Probus, CAN-Open, etc.
auxiliary contact modules, additional contacts.
b
b
v
v
v
Fig. 42 : Example of optional functions available with a modular system (Telemecanique Tesys U starter-controller).
1
/
L
1
1
/
L
3
1
/
L
2
2
/
T
1
6
/
T
3
4
/
T
2
Control unit
Power base unit
Control
units
Fig. 41 : Example of a modular CPS (Telemecanique
Tesys U starter-controller).
Possible functions Control units:
Standard Expandable Multi-function
Starter states (ready, operating, faulty)
Alarms (overcurrent, etc.)
Thermal alarm
Remote reset via the bus
Indication of the motor load
Fault differentiation
Parameter setting and protection functions look-up
Log function
Supervision function
Start and stop commands
Information carried on the bus (Modbus) and functions provided
Cahier Technique Schneider Electric no. 211 / p.27
5.7 Discrimination
total discrimination, which covers all fault
current levels up to the maximum available in the
installation, or partial discrimination which does
not cover the whole range.
Discrimination methods
There are several types of discrimination:
current-based, using a difference between the
trip thresholds of the circuit-breakers connected
in series
time-based, where the tripping of the upstream
circuit-breaker is delayed by a few tens or
hundreds of milliseconds, or use is made of the
ordinary operating characteristics related to the
ratings of the devices. Thus discrimination can
be provided between two overload relays by
meeting the condition I
r1
> 1.6 I
r2
(where r1 is
upstream of r2).
SELLIM or energy-based, in the electricity
supply eld: here a limiting circuit-breaker is
connected upstream, and opens for the time
required for the operation of the downstream
circuit-breaker, and then recloses.
logic, in which one circuit-breaker informs the
other that the threshold has been exceeded,
leaving the more downstream circuit-breaker the
choice of whether to open.
For further information on discrimination, see
Schneider Electric Cahiers Techniques no. 167.
Discrimination in processes
For process control equipment (production lines,
chemical production units, etc.), the
discrimination methods most commonly used
between motor starters and the electrical line
supply to these processes are generally current-
based and time-based. In most cases,
discrimination is provided by the limiting or ultra-
limiting capacity of the motor starters.
b
b
b
b
In an electrical installation, the loads are
connected to the generators via a sequence of
isolation, protection and control devices.
Unless there is a carefully implemented
discrimination plan, an electric fault may affect
several protection devices. Thus a single fault
can result in a larger or smaller part of the
installation being switched off. This causes an
additional loss of availability of electrical energy
in correctly operating feeders.
To prevent this loss, in a radial feeder layout
(see Fig. 43 ) the aim of discrimination is to
disconnect only the faulty feeder or motor
from the line supply, while keeping the largest
possible part of the installation live. Thus
discrimination makes it possible to combine
safety and continuity of service. It also facilitates
fault location.
To provide maximum continuity of service,
protection devices which are coordinated with
each other must be used. For this purpose,
different methods are used to achieve either
D
1
D
2
D
3
Fig. 43 : Discrimination between two circuit-breakers
D
1
and D
2
connected in series, where the same fault
current is owing through both, requires that only the
circuit-breaker D
2
downstream of D
1
should open
5.8 Example
The aim is to select a motor starter for protecting
and controlling a lifting pump where continuity of
service is essential.
Technical characteristics of the motor to be
protected
Three-phase asynchronous motor
Power: 4 kW at 400 V, 50 Hz, and nominal
current I
n
8.1 A
Operating category AC-3
Normal start (no specic starting time)
b
b
b
b
Short-circuit current of the installation calculated
in relation to the equipment: I
sc
= 35 kA
Control voltage: 230 V.
Essential limit characteristics
The operating conditions lead to the following
choice:
for short-circuit protection, and in order to
provide the requisite continuity of service, a
magnetic circuit-breaker must be provided, with a
breaking capacity in excess of I
sc
, calculated as
35 kA in this case.
b
b
b
Cahier Technique Schneider Electric no. 211 / p.28
To allow the continuous passage of the nominal
current, the operating current of the magnetic
circuit-breaker must be more than I
n
= 8.1 A.
for overload protection, given normal starting,
the relay must be of class 10 or 10 A, with a
setting current I
s
of 8.1 A or slightly more.
a contactor having an operating current of
more than 8.1 A. Its control coil must be supplied
at 230 V a.c.
Since continuity of service is essential, type
II coordination or total coordination of the
protection devices is required.
b
b
Fig. 44 : Two solutions in which good coordination between the different functions of a motor starter is guaranteed
(source: Telemecanique).
The hardware solutions
The selection of equipment having all these
characteristics can be difcult, especially if
devices made by different manufacturers have
to be combined. However, most manufacturers
catalogues show ranges of motor starters
together with tables of tested combinations,
facilitating the selection process. (see Fig. 44 ).
Standard power ratings of 50/60 Hz three-phase
motors in Category AC-3
Circuit-breaker Contactor Thermal overload
relay
400/415 V 440 V 500 V Ref. Rating FLAm
(1)
Ref.
(2)
Ref. Setting
range P Ie Iq P Ie Iq P Ie Iq
kW A kA kW A kA kW A kA A A A
0.08 0.22 130 0.06 0.19 130 - - - GV2 L03
or LE03
0.4 5 LC1 D09 LRD 02 0.160.25
0.09
-
0.36
-
130
-
0.09
0.12
0.28
0.37
130
130
-
-
-
-
-
-
GV2 L03
or LE03
0.4 5 LC1 D09 LRD 03 0.250.40
0.12
0.18
0.42
0.6
130
130
-
0.18
-
0.55
-
130
GV2 L04
or LE04
0.63 8 LC1 D09 LRD 04 0.40.63

3 6.5 130 - - - - - - GV2 L14
or LE14
10 10 LC1 D09 LRD 12 5.58
- - - - - - 4 6.5 10 GV2 LE14 10 138 LC1 D12 LRD 12 5.58
- - - - - - 4 6.5 50 GV2 L14 LC1 D12 LRD 12 5.58
4 8.4 130 GV2 L14
or LE14
10 138 LC1 D09 LRD 14 710
Solution: GV2 L14 + LC1 D09 + LRD 14
D.O.L. starters with circuit-breaker and thermal overload relay 3-product solution, type 2 coordination
TeSys U starter-controllers 1 product solution, total coordination
- Power base
Rated short-circuit breaking capacity (Isc)
Volts 230 440 500 690
kA 50 50 10 4
Note: For higher values, use limiters. At 690 V, use phase barrier LU9 SP0.
Connection Rating Ref.
Power Control y 440 V 500 V 690 V
A A A
Screw clamp Screw clamp 12 12 9 LUB 12
32 23 21 LUB 32
- Control units
Maximum standard power ratings of
50/60 Hz single-/three-phase motors
Setting
range
Clip on power
base rating
Ref. to be
completed with
code indicating
voltage
400/415 V 500 V 690 V
kW kW kW A A
Advanced control Pressing the Test button on the front panel simulates tripping on thermal overload.
Class 10 for three-phase motors
0.09 - - 0.150.6 12 and 32
LUCB X6pp
0.25 - - 0.351.4 12 and 32
LUCB 1Xpp
1.5 2.2 3 1.255 12 and 32
LUCB 05pp
5.5 5.5 9 312 12 and 32
LUCB 12pp
7.5 9 15 4.518 32
LUCB 18pp
15 15 18.5 832 32
LUCB 32pp
Existing control circuit voltages
Volts 24 4872 110240
c BL
a B
c or a - ES FU
Solution: LUB12 + LUCB 12 FU
GV2 L
LC1 D
LR D
LUB 12
Cahier Technique Schneider Electric no. 211 / p.29
6 Conclusion
In any installation including electric motors,
different kinds of faults can occur. But, whether
they originate in the motors (short circuits
between phases, etc.) or are related to the
operation of the motor (rotor locking, prolonged
starting, etc.) or to the power supply (overvoltage,
unbalance, etc.), their effects on the motors can
include short circuits and/or overheating of the
windings, which may destroy them.
Accordingly, in order to avoid these mishaps or
limit their effects, every motor should be
protected from:
short circuits: by fuses, magnetic circuit-
breakers, etc.
and overloads: by thermal or electronic
overload relays, multi-function relays, etc.
In a motor starter, these protection elements are
combined with an isolation device and a control
device. To ensure that they perform their
functions correctly, their coordination must be
ensured. This is an operation which is often
difcult for the designer of the installation or
machine, since he has to take into account not
only the type of motor, but also its mode of
operation and the characteristics of the
installation.
To facilitate the selection process, all major
manufacturers of motor starters publish
combination tables for their equipment in their
catalogues. Only a few manufacturers, such as
Schneider Electric, have produced devices which
incorporate all the necessary elements to
guarantee the correct operation of a whole
installation. Thus the requisite motor protection
devices can be rapidly specied and installed
without the risk of random occurrences.
b
b
Cahier Technique Schneider Electric no. 211 / p.30
Appendix 1: Modular system of the Tesys U starter-controller
The Tesys U CPS, or starter-controller (made by
Telemecanique) is a direct motor starter for
protecting and controlling single-phase or three-
phase motors. Its functions are integrated simply
by plugging control units and modules into a
power base unit (see Fig. 45 ).
With this technology, the CPS can be adapted up
to the last minute, and other plug-in elements are
available to simplify or even eliminate the wiring
in it.
Power base unit [1]
Independent of the control voltage and the
motor power
Integrates the circuit-breaker function with a
breaking power of 50 kA at 400 V, total coordination
(continuity of service), and the switch function
Control units [2]
Standard control unit
Protection against overloads and short circuits
Protection against phase failure and unbalance
Protection against isolation faults (equipment
protection only)
Manual reset
Expandable control unit
Includes the functionality of the standard
control unit (see above)
When combined with a function or
communication module:
- fault differentiation with manual reset
- fault differentiation with remote or automatic
reset
- thermal pre-alarm
- indication of the motor load.
Multi-function control unit
Includes the functionality of the standard
control unit (see above)
Reset parameters can be modied in manual
or automatic mode
Protection system alarm
Display on front panel or on remote terminal,
using Modbus RS 485 port
Log function
Monitoring function, displaying the main
motor parameters on the front panel of the
control unit or on a remote terminal
Fault differentiation (short circuit, overload, etc.)
Protection against excess torque and no-load
operation
b
b
b
v
v
v
v
b
v
v
b
v
v
v
v
v
v
v
v
Modules [3-4]
Auxiliary contacts
Function
Fault differentiation (with manual reset or
remote or automatic reset)
Thermal pre-alarm
Indication of the motor load
Communication
Parallel bus
Serial bus: AS-Interface, Modbus, Probus, etc.
Inverter unit [5]
Limiter-isolator unit [6]
b
b
v
v
v
b
v
v
6
5
1
2
3
4
Fig. 45 : Tesys U modular starter-controller.
Cahier Technique Schneider Electric no. 211 / p.31
Appendix 2: the main starting modes
DOL starting (see Fig. 46 )
This is the simplest and most economical starting
mode, but, owing to its electromechanical
Fig. 47 : Electrical diagram of a star-triangle starter.
In the power network
Starting current Large overcurrent (5 to 10 I
n
)
Brownout Considerable
Harmonic disturbance Considerable during starting
Power factor Low during starting
In the motor
Number of successive starts Limited (thermal withstand)
Available torque Low during starting (see graph)
Temperature stress Very considerable (rotor)
In the mechanism
Stress on couplings Very considerable
Suitable load types Low-inertia load
N
C
Resistive torque
Acceleration
torque
I
N
I
d
/ I
n

C
d
C
n
C
r
C
max
N
n
N
1
N
n
N
1
I
f
(C
r
)
I
n

characteristics, it cannot be used unless:
the load allows a large starting torque
and the line supply allows a starting current
which may be up to 10 times the nominal current.
b
b
Fig. 46 : Graphs and summary of the induced effects of the DOL starting mode.
Star-triangle starting
The principle of this mode is that the motor is
started by coupling the windings in star
conguration under the line voltage (see Fig. 47 ),
which is equivalent to dividing the nominal
voltage of the motor in star conguration by 3.
The peak starting current is then divided by 3,
i.e. I
s
= 1.5 to 3 I
n
.
This is a simple and economical starting mode
which reduces the current peak on starting (see
Fig. 48 next page).
It can only be used if:
the starting load is zero, or has a low torque
not exceeding 1/3 of the nominal torque
and the line can withstand the excess current
during the coupling changeover.
Rheostatic stator starting
The principle is to start the motor at a reduced
voltage by connecting resistors in series with the
windings (see Fig. 49 next page). When the speed
is stabilized, the resistors are short-circuited and
the motor is coupled directly to the line supply.
This operation is generally controlled by a timer.
b
b
KM2
Q1
KM3
F2
KM1
M
3
(U) (V) (W)
2 4 6
2 4 6
1 3 5
1 3 5
1 3 5 1 3 5
2 4 6
1 3 5
2 4 6
2 4 6
(X) (Y) (Z)
U1 V1 W1
U2 V2 W2
U V W
X Y Z
L1 L3 L2
U V W
X Y Z
Cahier Technique Schneider Electric no. 211 / p.32
Fig. 48 : Graphs and summary of the effects of the star-triangle starting mode.
Fig. 49 : Electrical diagram and sequence of a
rheostatic stator starter.
Fig. 50 : Current and torque graphs for a rheostatic
stator starter.
This starting mode avoids power cuts during the
starting phase; it can greatly reduce the
magnetizing current peaks (transients).
However, the starting current remains high, at about
4.5 I
n
. This starting mode causes a considerable
loss of torque and power (see Fig. 50 ).
2
N
Resistive torque
I
n

2
4
I
I in
I in Y
N
I
d
/ I
n

C in
C in Y
1
C
r
C
max
N
n
N
1
N
n
N
1
C / C
n
I
f
(C
r
)
KM1
Q1
F2
KM1
M
3
U V W
2 4 6
2 4 6
1 3 5
1 3 5
1 3 5
1 3 5
2 4 6
2
R1 R3 R5
R2 R4 R6
4 6
L1 L3 L2
6
5
4
3
2
1
100 50
I
c
N
I
d
I (stage 2)
without
resistance
I (stage 1)
with resistances
C
m
(stage 2)
C
m
(stage 1)
I (direct)
1.5
1
0.5
100 50
Torque
N
C
resistive
C (direct)
In the power network
Starting current Low overcurrent (1.5 to 3 I
n
)
Brownout Considerable on change of coupling
Harmonic disturbance Considerable during starting
Power factor Degraded during starting
In the motor
Number of successive starts 2 to 3 times greater than in direct connection
Available torque Reduced during starting (1/3 C
n
)
Temperature stress Lower than in direct connection
In the mechanism
Stress on couplings Lower than in direct connection
Suitable load types Low-inertia
Autotransformer starting
The motor is supplied at reduced voltage by
means of an autotransformer which is switched
out of the circuit after starting.
Cahier Technique Schneider Electric no. 211 / p.33
Starting takes place in three stages (see Fig. 51 ).
This starting mode is used mostly in
LV applications for power ratings of more than
150 kW and for mechanisms having low inertia
where the torque characteristics can withstand
the decrease in motor torque in a ratio varying
from 0.4 to 0.85 with respect to the starting
torque of the motor (see Fig. 52 ).
Fig. 52 : Current and torque graphs for an
autotransformer starter.
Fig. 53 : Progressive starting and deceleration unit
(Telemecanique Altistart 01).
Stage 1
L1 L3 L2
M
3
U V W
Stage 2
L1 L3 L2
M
3
U V W
Stage 3
L1 L3 L2
M
3
U V W
K3 K2
M
3
U V W
U2 V2 W2
U1 V1 W1
I > I > I >
L1 L3 L2
K1
U3
V3
W3
Fig. 51 : Electrical diagram and sequence of autotransformer starting.
Electronic starting (soft starter)
When the motor is switched on, it is supplied
with a progressively increasing voltage. This
is produced by means of a power controller
whose output voltage can be controlled by an
acceleration ramp which is determined by the
value of the limit current, or the torque, or is
related to these two parameters (see Fig. 53 ).
This is a high-performance starting mode which
allows soft starting and stopping.
In current limiting control, a maximum current
(3 to 4 I
n
) is xed during the starting phase,
although this decreases the torque performance.
This form of starting is particularly suitable for
turbine machines such as centrifugal pumps
and fans.
6
5
4
3
2
1
100 50
Ic
N
Id
I (3
e
temps)
I (1
er
temps)
Cm (2
e
tps) Cm (3
e
tps)
Cm (1
er
tps)
I (direct)
1,5
1
0,5
100 50
Couple
N
C
rsistant
C (direct)
Cahier Technique Schneider Electric no. 211 / p.34
In torque regulation control, the torque
performance is optimized on starting, but with
negative effects on the current drawn from the
line supply.
Frequency converter starting
This operates on a principle similar to that of
PWM (Pulse Width Modulation) according to a
PWM sinus law. This method provides regular
and shock-free rotation of the machines, even at
low speed, because the output current waveform
is very close to a sine wave.
This is a high-performance starting mode, used
when the speed must be controlled.
Suitable for all types of machine, it can be used
for the following purposes, among others:
starting high-inertia loads
starting large loads in a network with a low
short-circuit capacity
optimizing electricity consumption in
accordance with the speed of turbine machines.
b
b
b
Cahier Technique Schneider Electric no. 211 / p.35
Appendix 3: Bibliography
Standards
IEC 60034-26: Rotating electrical machines.
Part 26: Effects of unbalanced voltages on the
performance of three-phase induction motors.
IEC 60364, NF C 15-100: Low-voltage
electrical installations.
IEC 60947-1: Low-voltage switchgear and
controlgear - Part 1 : General rules.
IEC 60947-2: Low-voltage switchgear and
controlgear - Part 2 : Circuit-breakers.
IEC 60947-4-1: Low-voltage switchgear and
controlgear - Part 4-1: Contactors and motor-
starters - Electromechanical contactors and
motor-starters.
IEC 60947-6-2: Low-voltage switchgear and
controlgear - Part 6-2: Multiple function
equipment - Control and protective switching
devices (or equipment) (CPS).
IEC 60947-8: Low-voltage switchgear and
controlgear - Part 8 : Control units for built-in
thermal protection (PTC) for rotating electrical
machines.
IEC 61000-2-1: Electromagnetic compatibility
(EMC) - Part 2: Environment - Section 1:
Description of the environment - Electromagnetic
environment for low-frequency conducted
disturbances and signalling in public power
supply systems.
Schneider Electric Cahiers Techniques
Overvoltages and insulation coordination in MV
and HV
Cahier Technique no. 151- Didier FULCHIRON
Energy-based discrimination for LV protective
devices
Cahier Technique no. 167 - Marc SERPINET and
Robert MOREL
LV surges and surge arresters - LV insulation
coordination
Cahier Technique no. 179 - Christophe SRAUDIE
Discrimination with LV power circuit-breakers
Cahier Technique no. 201 - Jean-Pierre NEREAU
LV protection devices and variable speed
drives (frequency converters)
Cahier Technique no. 204 - Jacques SCHONEK
and Yves NEBON
Electric motors ... and how to improve their
control and protection
Cahier Technique no. 207 - Etienne GAUCHERON
Electronic starters and variable speed drives
Cahier Technique no. 208 - Daniel CLENET
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
Miscellaneous
Schmathque Technologies du contrle
industriel, Edition CITEF - Collection Technique
Telemecanique 1994
Utilisation industrielle des moteurs courant
alternatif, TEC & DOC, Schneider-Electric 2001 -
Jean BONAL
Protections lectriques des alternateurs et
moteurs, Techniques de lIngnieur no. D 3775 -
Bernard GUIGUES
Protections lectriques des alternateurs et
moteurs, Techniques de lIngnieur no. D 4820 -
Jacques VERSCHOORE
Guide dinstallation et de maintenance des
Moteurs asynchrones triphass ferms cage
ou bagues, Leroy Somer Document
b
b
b
b
b
Schneider Electric Schneider Electric Industries SAS
Head Ofce
89, bd Franklin Roosevelt
92506 Rueil-Malmaison Cedex
FRANCE
DTP: AXESS Valence.
Transl.: Lloyd International - Tarpoley - Cheshire - GB
Editor: Schneider Electric


2
0
0
7

S
c
h
n
e
i
d
e
r

E
l
e
c
t
r
i
c
01-07

You might also like