Short Circuit Calculation
Short Circuit Calculation
(Short Circuit)
** Co ordination **
(Short Circuit)
(Short Circuit)
** Interrupting Rating **
(Short Circuit)
Line to Ground Fault
Line to Neutral Fault
Line to Line Fault
Double Line to Ground Fault
Three Phase Fault
!!
= 70 %
= 15 %
= 10 %
= 5%
(Panel Board)
MDB (Main Distribution Board)
+
-
-
-
- ()
- /
-
(> 1,000 A)
(fuse & Circuit Breaker)
-
-
-
-
/
- Fuse
- Circuit Breaker
1.
2.
3.
4.
(Symmetrical)
(Unsymmetrical)
IEC 60909 2
1.
( MDB)
IC
1.
:
IU
(IU)
(IM)
A
IU
B
IM
IM
M
(IU)
IU = 100 * IFL,Tr
% Zk
IU
IFL,Tr
% Zk (Impedance Voltage)
(IFL)
I FL,Tr =
S
3VL
S (VA)
VL
(V)
(. = 400 V ; . = 416 V)
Rp
Xs
P sh_s
Rs
W
Ish_s
I
V
Vsh_s
Zk
%Z k
Vs / c ( meter )
100
Vrate
22 kV / 416-240 V
Voltmeter 850 V.
%Z k
850
100
22000
3.86 %
Italy
France
1
1600 kVA 24 kV/416-240 V
MEA 24 kV
IU
CEI Std
1600 kVA
24 kV / 416-240 V
I FL,Tr =
S
3VL
1600103
=
3 416
= 2,221 A
()
IU =
I FL ,Tr 100
%Z k
CEI Zk = 6.25 %
IU =
2,221100
6.25
= 35,536 A.