You are on page 1of 2

RECTANGULAR LED DETECTOR HEAD

BASE
OPENING HERE
LONG ALIGNMENT MARK
SHORT ALIGNMENT MARK


Photoelectric Smoke/HEAT Detector
Installation Wiring Diagram
TYPICAL WIRING DIAGRAM
Figure 1(a) shows the typical wiring diagram of the
2-wire multiple-station smoke detector system.
INITIATING
LOOP
EN54 LISTED
COMPATIBLE
CONTROL
PANEL
+
-
FIRST DETECTOR BASE LAST DETECTOR BASE
EOL
RESISTOR
5 2 5 2
6 1 3 4 6 1 3 4
+ - +
REMOTE
INDICATOR
CLASS A OPTIONAL WIRING
NOTE: IF REMOTE INDICATOR IS NOT USED. POLARITY TO DETECTOR MAY BE REVERSED.
-

DO NOT PLACE LINKS BETWEEN THE WIRING POSITIONS
OF TERMINALS 2 AND 5 TO PROVIDE POWER
SUPERVISION
Figure 1(b) shows the typical wiring diagram of the
4-wire multiple-station smoke detector system.


DO NOT PLACE LINKS BETWEEN THE WIRING POSITIONS
OF TERMINALS 2 AND 5 TO PROVIDE POWER
SUPERVISION
WARNING
TO PREVENT DETECTOR CONTAMINATION AND
SUBSEQUENT WARRANTY CANCELLATION, THE
SMOKE DETECTOR MUST REMAIN COVERED UNTIL
THE AREA IS CLEAN AND DUST FREE.
INSTALLING THE BASE
1. To insure proper installation of the detector head to the
base, all the wires should be properly addressed at
installation:
(A) Position all the wires flat against terminals.
(B) Fasten the wires away from connector terminals.
2. If you use a jumper wire to connect the poles of
terminal 2 and 5 when testing the detector loop
continuity, be sure to remove the jumper wire prior to
the installation of the detector head.
3. The end-of-line device shown in fig. 1(a) and 1(b)
should be compatible with the control unit. The
end-of-line supervisory relay used should be rated for
the DC power voltage used.
4. Open area smoke detectors are intended for mounting
on a ceiling or a wall in accordance with the fire
standard in your country.
5. The base of the smoke detector can be mounted
directly onto an electrical junction box such as an
octagonal (75mm, 90mm or 100mm), a round (75mm),
or a square (100mm) box without using any type of
mechanical adapter.
INSTALLING THE HEAD
1. Align the components as shown in Figure 2.
2. Mate the detector head onto the base and twist
clockwise to secure it.
3. Do not install the detector head until the area is
thoroughly cleaned of construction debris, dusts, etc.
The maximum number of smoke detector installed in
the same loop is 30 units.







Fig. 2 Mating detector head onto base
ADJUSTING THE RELAY FOR NO/NC
The normal condition for the relay is normally open
(NO).
1. To adjust the normal condition of the relay to
normally closed (NC), insert a screwdriver into the
rectangular hole located on the side between the front
cover and base and rotate to remove the front cover.
2. Refer to figure 3. There is a jumper head next to the
relay on the PCB. Remove the jumper head and reinsert
it in the NC position.
3. Carefully replace the front cover.
Relay contact rating:
1A@30VDC,
0.5A@125VAC.





TESTING
1. All the alarm signal services, releasing device and
extinguisher system should be disengaged during the
test period and must be re-engaged immediately at the
conclusion of testing.
2. After energizing the detector head for approximately
one minute, check to see the indicator green LED
flashing once every 3~5 seconds. If green LED fails to
flash, it indicates the non-functioning of the detector or
faulty wiring. Re-check the wiring or replace the
detector if necessary.
3. Allow smoke from a cotton wick or a test smoke
aerosol to enter the detector-sensing chamber for at
least 10 seconds. When sufficient smoke has entered
the chamber, the detector will signal an alarm, this
being visible by a continuous illumination of the LED.
Reset each detector and/or control unit before
attempting to test any additional detectors in the same
zone. If the alarm fails in this step, it indicates a
defective unit, which requires service.
Fig. 3 Schematic of detector structure
When front cover is open.
SMOKE CHAMBER
LED
RELAY
JUMPER SETTING
VRC TEROFIRE PRODUCTS
42-44 Bromley Rd Congleton Cheshire UK
Post Code: CW12 1PT
Tel:44 (0)1260 297578 Fax:44(0)1260 290078
HEAT SENSOR TESTING
The detector to be tested should be subject to a flow of
warm air at a temperature of between 65C and 80C.
(This requirement can be met by some domestic hair
dryers).
Proceed as follows:
1. Switch on the warm airflow and check that temperature
is correct and stable.
2. From a distance of several inches, direct the airflow at
the guard protecting the thermistor. The detector
should alarm within 30 seconds.
3. Upon alarm immediately remove the heat source and
check that the red LED of the detector is illuminated.
Reset the detector from the control panel.
4.If detector fails to go into alarm mode within 30
seconds it is too insensitive and needs to be returned
to the distributor for servicing.
5. After testing, check that the system is set for normal
operation and notify the appropriate authorities that the
testing operation is complete and the system is active
again.
NOT SUITABLE FOR INSTALLATION IN AREAS
WHERE AIR VELOCITIES EXCEED 600 meters/min
MAINTENANCE
The recommended minimum requirement for detector
maintenance consists of an annual cleaning of dust from
the detector head by using a vacuum cleaner cleaning
program should be agreed to the individual environment
in conformance with EN 54-7:2000 and EN 54-5:2000
standards.

CAUTION: DO NOT ATTEMPT TO DISASSEMBLY OF THE
FACTORY SEALED SMOKE DETECTOR. THIS
ASSEMBLY IS SEALED FOR YOUR PROTECTION AND IS
NOT INTENDED TO BE OPENED FOR SERVICING BY
USERS. OPENING THE DETECTOR HEAD WILL VOID
THE WARRANTY.

REFERENCE TO THE TECHNICAL BULLETIN ISSUE NO.
EATB20010215 REV.B

SPECIFICATION
Model 2/4
wire
Ther
mal
Voltage
DC
Standby
Current
(Max.)
Alarm
Current
(Max.)
Surge
Current
(Max.)
Start-Up
Time
(Max.)
Permissible
Current
(Max.)
Frequency Alarm
Sound level
Alarm contact Base model
EN-54-7:2000
listed

10-0001 2 12~35V
35 A
70mA
40 A
60 Seconds 80mA 3-5 Seconds

P/N854001
EN-54-7:2000/
EN-54-5:2000 listed

10-0002 2 57C 12~35V
35 A
70mA
40 A
60 Seconds 80mA 3-5 Seconds

P/N854001


LIMITED WARRANTY STATEMENT
VRC TEROFIRE PRODUCTS represents that this product is free from defects in material and workmanship. And it will
repair or replace any product or part thereof which proves to be defective in workmanship or material for a period of
twelve (12) months from the date of purchase but not to exceed eighteen (18) months after shipment by the
manufacturer. For a full description of VRC TEROFIRE PRODUCTSS LIMITED WARRANTY, which, among other
things, limits the duration of warranties of merchantability and fitness for a particular purpose and excludes liability for
consequential damages. Please read the entire LIMITED WARRANTY on the VRC TEROFIRE PRODUCTS quotation.
Acceptance of order and/or original invoice which will become part of your sales agreement. Please contact VRC
TEROFIRE PRODUCTS directly for a return merchandise authorization (RMA) number before returning goods to the
factory address at 42-44 Bromley Rd Congleton Cheshire UK . Shipment must be prepaid and VRC TEROFIRE
PRODUCTS will repair or replace your returned detector.


ISSUE NO. MSD20010215 REV.A

You might also like