Error "41" appears at conventional combi boilers.

The flow is monitored by the return and flow sensors. Error "41" appears if the value at the
return sensor is more than 25 C hiher than the value of the flow sensor.

!lease chec" the pressure #1.5 $ 2 bar re%uired& and the function of the heatin circuit pump.

Ta"e hold to the left and riht ne't to the overflow valve( to chec" whether it opens.

)f the heatin circuit pump and the overflow valve are wor"in( and if the pressure of the
installation is within the re%uired rane( we recommend that the flow and return sensors are
e'chaned( since one of the two sensors may be sendin incorrect temperature values to the
controller.