You are on page 1of 1

SW Energietechnik GmbH

15528 Spreenhagen, Germany


Am Winkel 7
Telefon 033633 69660 10
Telefax 033633 69660 20
www.sw-energietechnik.de
Technical Specifications
project: Barwa Building Material Company
Site developement, Substations and Transformers
Transformer
Threephase oil immersed transformer according toDIN EN 60076/ DIN50464/ CENELEC/ IEC 76 T.1.5
Insulation class A
fabrication-nr: : serie DkE0 (DIN50464)
pcs: : 18
type: : DCU 4231 IN
rated power: kVA : 1600
rated transformation (no load operation) kV : 11/0,4
tapping (HV) % : +- 2x2,5%
rated frequency Hz : 50
vector group : DYN 5
no load losses (rated voltage) Po W : 2600
short circuit losses Pk W : 20000
(reference temperature 75C, rated power)
short circuit voltage % : 6
(reference temperature 75C, rated power)
sound power level (Lwa) dB(A) : 72
noise pressure level (Lpa) distance 1m dB(A) : 56
operating mode : permanent operation
cooling : ONAN
max. altitude of site m : 1000
ambient temperature C : 50
admissible overtemperature (coil/oil) K : 55/50
tolerance at losses (Po/Pk) %/% : 15/15
tolerance at short circuit voltage Uk % : 10
type of oil : Nynas2000X or equivalent
type of tank : shaft wall tank
anti-corrosion coating : according to AREVA-standard
covering color RAL 7033
type : hermetic / outdoor
type of changers : Elmek
high current feedthroughs HV : Elastimold
LV : porcelain feedthroughs