Professional Documents
Culture Documents
Chapter 5
Portable Extinguishers
INTRODUCTION inspection of portable fire extinguishers. NFPA 10,
The portable fire extinguisher, one of the most Standard for Portable Fire Extinguishers, provides
common fire-protection appliances in use today, is additional information on rating, placement (loca-
found in fixed facilities and on fire apparatus (Fig- tion), and use of portable extinguishers.
ure 5.1). A portable fire extinguisher is excellent to
use on incipient fires. In many cases, a portable TYPES OF PORTABLE FIRE EXTINGUISHERS
extinguisher can extinguish a small fire in much [NFPA 1001: 3-3.15(a)]
less time than it would take to deploy a hoseline. There are many different types of portable
It is important that firefighters be knowledge- fire extinguishers. This section highlights some
able about the different types of portable fire extin- of the common extinguishers encountered by fire
guishers and their correct use. This chapter covers service personnel. Table 5.1 shows the opera-
the various types of portable fire extinguishers tional characteristics of different types of por-
that firefighters are likely to encounter. Also cov- table fire extinguishers discussed in the follow-
ered is information on the rating, selection, and ing subsections.
Firefighters should not rely on extinguishers
found in occupancies. These extinguishers may not
have been maintained properly or they may be
obsolete. Responding firefighters should rely on
the extinguishers carried on their pumping appa-
ratus. NFPA 1901, Standard for Automotive Fire
Apparatus, requires that pumping apparatus have
two approved portable fire extinguishers with
mounting brackets. These must be suitable for use
on Class B and Class C fires. The stated minimum
size requirement for a dry chemical extinguisher is
one with a rating of 80 B:C; the required rating for
a carbon dioxide (CO2) extinguisher is 10 B:C.
Ratings represent the type of fire plus performance
capability (see Extinguisher Rating System sec-
tion). NFPA 1901 also requires pumping appara-
tus to carry one 2¹₂ gallon (10 L) or larger water
extinguisher with a mounting bracket for use on
Class A fires.
Extinguisher Type Agent Fire Class Size Stream Reach Discharge Time
Pump-Tank Water Hand-carried; Water A only 1¹₂–5 gal 30–40 ft 45 sec to 3 min
backpack (6 L to 20 L) (9.1 m to 12.2 m)
Stored-Pressure Hand-carried Water A only 1¹₄–2¹₂ gal 30 ft–40 ft 30–60 sec
Water (5 L to 10 L) (9.1 m to 12.2 m)
Aqueous Film Hand-carried Foam A&B 2¹₂ gal (10 L) 20–25 ft Approximately 50 sec
Forming Foam (6.1 m to 7.6 m)
(AFFF)
Halon 1211* Hand-carried; Halon B&C Hand-carried: 2¹₂– 8–18 ft 8–18 sec
wheeled 20 lb (1 kg to 9 kg) (2.4 m to 5.5 m)
Wheeled: to 150 lb 20–35 ft 30–44 sec
(68 kg) (6.1 m to 10.7 m)
Halon 1301 Hand-carried Halon B&C 2¹₂ lb 4–6 ft 8–10 sec
(1 kg) (1.2 m to 1.8 m)
Carbon Dioxide Hand-carried Carbon dioxide B&C 2¹₂–20 lb 3–8 ft 8–30 sec
(1 kg to 9 kg) (1 m to 2.4 m)
Carbon Dioxide Wheeled Carbon dioxide B&C 50–100 lb 8–10 ft 26–65 sec
(23 kg to 45 kg) (2.4 m to 3 m)
Dry Chemical Hand-carried Sodium B&C 2¹₂–30 lb 5–20 ft 8–25 sec
stored-pressure; bicarbonate, (1 kg to 14 kg) (1.5 m to 6.1 m)
cartridge-operated potassium
bicarbonate,
ammonium
phosphate,
potassium chloride
Multipurpose Dry Hand-carried Monoammonium A, B, & C 2¹₂–30 lb 5–20 ft 8–25 sec
Chemical stored-pressure; phosphate (1 kg to 14 kg) (1.5 m to 6.1 m)
cartridge-operated
Dry Chemical Wheeled; ordinary A, B, & C 75–350 lb Up to 45 ft 20 sec to 2 min
ESSENTIALS
* Rating: Those larger than 9 lb (4 kg) capacity have small Class A ratings (1-A to 4-A).
Portable Extinguishers 127
exposed to temperatures lower than 40°F (4°C).
Freeze protection may be provided by adding anti-
freeze to the water or by storage in warm areas. Figure 5.3 A typical stored-pressure
water extinguisher. Courtesy of
Ansul, Inc., Marinette, Wisconsin.
Pump-Tank Water Extinguishers
Pump-tank water extinguishers are intended
for use on small Class A fires only (Figure 5.2).
There are several kinds of pump-tank water extin-
guishers, but all operate in a similar manner. They
are generally equipped with a double-acting pump.
The procedures for operating a pump-tank water
extinguisher are shown in Skill Sheet 5-1.
Figure 5.22 The dry powder must completely cover the area that is
burning to create a smothering blanket. Figure 5.23 Class D agent may be shoveled onto the fire.
and Class B extinguishers are also rated according expected to extinguish 1 square foot (0.09 m2) for
to performance capability, which is represented by each numerical rating or value of the extin-
a number. The classification and numerical rating guisher rating.
system is based on tests conducted by Underwrit-
Class C Ratings
ers Laboratories Inc. (UL) and Underwriters Labo-
There are no fire extinguishing capability tests
ratories of Canada (ULC). These tests are designed
specifically conducted for Class C ratings. Extin-
to determine the extinguishing capability for each
guishers for use on Class C fires receive only the
size and type of extinguisher.
letter rating because Class C fires are essentially
Class A Ratings Class A or Class B fires involving energized electri-
Class A portable fire extinguishers are rated cal equipment. The extinguishing agent is tested
from 1-A through 40-A. The Class A rating of water for nonconductivity. The Class C rating confirms
extinguishers is primarily based on the amount of the extinguishing agent will not conduct electric-
extinguishing agent and the duration and range of ity. The Class C rating is assigned in addition to the
the discharge used in extinguishing test fires. For rating for Class A and/or Class B fires.
a 1-A rating, 1¹₄ gallons (5 L) of water are required.
Class D Ratings
A 2-A rating requires 2¹₂ gallons (10 L) or twice the
Test fires for establishing Class D ratings vary
1-A capacity (Figure 5.25).
with the type of combustible metal being tested.
Class B Ratings The following factors are considered during each
Extinguishers suitable for use on Class B fires test.
are classified with numerical ratings ranging from • Reactions between the metal and the agent
1-B through 640-B (Figure 5.26). The rating is
• Toxicity of the agent
based on the approximate square foot (square meter)
area of a flammable liquid fire that a nonexpert • Toxicity of the fumes produced and the
operator can extinguish. The nonexpert operator is products of combustion
• Time to allow metal to burn out without fire
suppression efforts versus time to extin-
guish
Figure 5.25 A typical faceplate on an When an extinguishing agent is determined to
air-pressurized water extinguisher. be safe and effective for use on a combustible metal,
the details of instruction are included on the face-
plate of the extinguisher, although no numerical
rating is given. Class D agents cannot be given a
multipurpose rating for use on other classes of fire.
Multiple Markings
Extinguishers suitable for more than one class
of fire are identified by combinations of the letters
A, B, and/or C or the symbols for each class. The
three most common combinations are Class A-B-C,
Class A-B, and Class B-C (Figure 5.27). All new
portable fire extinguishers must be labeled with
their appropriate markings. Any extinguisher not
properly marked is not a listed unit and should not
be used.
The ratings for each separate class of extin-
Figure 5.26 Class B extinguishers are available in a guisher are independent and do not effect each
variety of sizes. other. To better understand the rating system, a
Portable Extinguishers 135
common-sized extin-
guisher, such as the
multipurpose extin-
guisher rated 4-A 20-
B:C, can be reviewed.
This extinguisher
should extinguish a
Class A fire that is 4
times larger than a
1-A fire, extinguish
approximately 20 times
as much Class B fire as
a 1-B extinguisher, and
extinguish a deep-layer
flammable liquid fire of
a 20 square-foot (2 m2)
area. It is also safe to
use on fires involving
energized electrical Figure 5.27 An extinguisher
intended for Class A, Class B, and Figure 5.28 The alphabetical/
equipment. Class C fires. geometric symbols for the four
classes of fire.
There are two systems of labeling portable
fire extinguishers. One system uses geometric
shapes of specific colors with the class letter
shown within the shape (Figure 5.28). The other Figure 5.29 The pictographs
representing Class A, Class B, and
system, currently recommended in NFPA 10, Class C fires.
uses pictographs to make the
selection of the most appro-
priate fire extinguishers
easier (Figure 5.29). This
system also shows the types
of fires on which the extin-
guisher should not be used
(Figure 5.30). Regardless of
which system is used, it is
important that the markings
are clearly visible.
SELECTING PORTABLE
FIRE EXTINGUISHERS
[NFPA 1001: 3-3.15; 3-3.15(b)]
Selection of the proper
portable fire extinguisher de-
pends on numerous factors:
• Classification of the
burning fuel
Figure 5.30 Pictographs showing the classes of fires for which an extinguisher is not suitable.
136 ESSENTIALS
• Rating of the extinguisher spected regularly to ensure that they are accessible
• Hazards to be protected and operable (see Inspecting Fire Extinguishers
section).
• Severity of the fire
A firefighter should quickly check an extin-
• Atmospheric conditions
guisher before attempting to use it in an emer-
• Availability of trained personnel gency (Figure 5.32). This check is necessary to
• Ease of handling extinguisher assure the firefighter that the extinguisher is
• Any life hazard or operational concerns charged and operable. Such a check may protect
the firefighter from injury caused by a defective
Select extinguishers that minimize the risk to extinguisher. If the extinguisher appears to be in
life and property but are effective in extinguishing working order, the firefighter can then use it to
the fire. It is unwise to use dry chemical extinguish- suppress a fire.
ers with a corrosive agent in areas where highly
sensitive computer equipment is located. The resi- When inspecting an extinguisher immediately
due left after use could potentially do more damage before use, a firefighter should check the following:
to the sensitive electronic equipment than a fire. In • External condition — no apparent damage
these particular areas, halon or carbon dioxide • Hose/nozzle — in place
extinguishers are better choices (Figure 5.31).
• Weight — feels as though it contains agent
• Pressure gauge (if available) — in operable
range
Figure 5.32 The firefighter should quickly check the extinguisher before
using it.
Figure 5.31 Halon extinguishers are used in computer areas.
After selecting the appropriate size and type of
USING PORTABLE FIRE EXTINGUISHERS extinguisher for the situation, a firefighter ap-
proaches a fire from the windward side (wind at the
[NFPA 1001: 3-3.15; 3-3.15(a)(b)]
firefighter’s back). The firefighter must be sure the
Portable extinguishers come in many sizes and extinguishing agent reaches the fire — if it cannot,
types. While the operating procedures of each type the agent is wasted (Figure 5.33). Smaller extin-
of extinguisher are similar, firefighters should be- guishers require a closer approach to the fire than
come familiar with the detailed instructions found larger units, thus radiant heat may prevent the
on the label of the extinguisher. Fire extinguishers firefighter from getting close enough for the agent
on the emergency response vehicles must be in- to reach the fire. Adverse winds also can limit the
Portable Extinguishers 137
reach of an agent. However, operating an extin-
guisher close to the fire can cause another problem.
Discharging agent directly onto the fuel can some-
times scatter lightweight solid fuels or penetrate
the surface of liquid fuels (Figure 5.34). Apply
agent from a point where it reaches but does not
disturb the fuel (Figure 5.35). The general operat-
ing procedures shown in Skill Sheets 5-1 through
5-3 should be followed when operating fire extin-
guishers.
After the fire is knocked down, the firefighter
may move closer to achieve final fire extinguish-
ment. However, if extinguishment is not achieved
after an entire extinguisher has been discharged Figure 5.35 Agent being applied from an appropriate distance.
onto the fire, the firefighter should withdraw and
reassess the situation. If the fire is in solid fuel that be overhauled using an appropriate tool to pull it
has been reduced to the smoldering phase, it should apart and a charged hoseline to achieve complete
extinguishment. If the fire is in a liquid fuel, it may
be necessary to either apply the appropriate type of
foam through a hoseline or simultaneously attack
the fire with more than one extinguisher. If more
than one extinguisher is used simultaneously,
firefighters must work in unison and maintain a
constant awareness of each other’s actions and
positions. Firefighters should lay empty fire extin-
guishers on their sides after use. This procedure
signals that they are empty and reduces the chance
of someone taking one and approaching a fire with
an empty extinguisher.
Pump-Tank Extinguishers
Step 3: Unfold the footpad (if the unit is equipped with one)
and place a foot on it.
Stored-Pressure Extinguishers
Water, Halon, Dry Chemical, CO2
Step 7: Sweep the nozzle back and forth at the base of the
flames to ensure full coverage by the extinguishing agent
until fire is extinguished.
NOTES:
• Do not plunge dry chemical into flammable liquid fires.
Cartridge-Operated Extinguishers
Dry Chemical, Dry Powder
Step 8: Sweep the nozzle back and forth. Start at the near
edge of the fire and move forward while sweeping the
nozzle from side to side until fire is extinguished.