Professional Documents
Culture Documents
System
PART 02
ezazsidd@outlook.co
m
CONTENTS
* DESIGN OF SPRINKLER
* TYPE OF COMBUSTIBLE
MATERIAL
* DESIGN OF BUILDING
WHERE THE SYSTEM IS
INSTALLED
* LAYOUT -- SPRINKLER
INSTALLATION PIPING
ARRAY
* SYSTEM FLOW AND
PRESSURE
REQUIREMENTS
Sprinklers for general application are manufactured with three different
orifice sizes of 10,15 and 20mm which respectively deliver 57, 80 and 115
LPM of water at 1 bar pressure
Ordinary hazard (Group 1) occupancies shall be occupancies or portions of other occupancies where combustibility is low, quantity of
combustibles is moderate, stockpiles of combustibles do not exceed 8 ft (2.4 m), and fires with moderate rates of heat release are expected.
Ordinary hazard (Group 2) occupancies shall be occupancies or portions of other occupancies where the quantity and combustibility of contents
is moderate to high, stockpiles do not exceed 12 ft (3.7 m), and fires with moderate to high rates of heat release are expected.
5.4 Extra Hazard Occupancies.
LIGHT HAZARD : Not less than 20 minutes run for the pumping
capacity or 35 m3 whichever is greater
ORDINARY HAZARD : Not less than 1 hour run for the aggregate
pumping capacity or 200 m3 whichever is greater.
HIGH HAZARD : Not less than 2 hours run for the aggregate pumping
capacity.
3
Reservoirs of and over 225M capacities shall be in two independent
but interconnected compartments with a common sump to facilitate
cleaning and repairs.
Sprinkler System
Type of Sprinkler Sytem
Sprinkler systems would be supplied by different systems,
such as:
The actuation of the system takes place by a fire alarm system, The types of
sprinklers are open sprinklers, connected to a deluge valve, once the system is
actuated the valve opens and accordingly water flows through the whole sprinklers
connected to the system. ALSO KNOWN AS TOTAL FLOODING SYSTEM.
Deluge system with Electric
Actuated
Deluge system with Wet Pilot
Actuated
Deluge system with Dry Pilot
Actuated
Pre-action Sprinkler
System
The actuation of sprinkler doesn’t take place only by the action of heat, but
also by action of fire alarm system(Smoke\Heat Detector), pipes are pressurized of
air or any appropriate gas.
Single Interlock system
Double Interlock system
Anti Freeze System
Antifreeze solution dissolved through water, prevents the water inside pipes
from getting freeze at the very cold areas.
ZONE CONTROL VALVE
Zone Control Valve is used to control the sprinkler system for each
floor and to separate the floors when a maintenance is needed at any
specific floor.
Components of Z.C.V:
1. OS&Y Gate Valve with Tamper Switch.
2. Pressure Gauge.
3. Flow Switch / Water flow detector
4. Test and Drain Assembly with Sight
Glass.
5. Check valve(optional).
ZONE CONTROL
UNIT FUNCTION
Electrical switch
installed with the OS&Y
gate valve to check the valve
position.(Alarm will actuate
if the valve got closed)
TEST & DRAIN
ASSEMBLY
Test position: to check
whether the flow is accurate or
not.
In case of storage in racks or shelves, if the height of storage is more than what is
specified, intermediate sprinklers shall be provided for each shelf/rack in addition to
the ceiling sprinklers and overall design density and AMAO shall be maintained.
If the top of the storage in the top tiers of the racks or shelves is within 3 M of the roof
sprinklers, top tiers need not be protected by the intermediate sprinklers. However,
the other tiers shall need to be sprinklered.
The aisle width between the storage stacks shall not be less than 2.5 meters and the
maximum area of each storage stack shall not be more than 150 M 2. If these
parameters are exceeded, the design density applicable shall be loaded by 2.5 LPM/ M2
.
CATEGORY MAXIMUM STORAGE DESIGN DENSITY AMAO
HEIGHT IN METRES lpm/m2 m2
I 6.5 12.50 260
II 5.5 15.00 260
III 4.5 17.50 300
IV 3.5 22.50 300
PRESSURE AND FLOW REQUIREMENTS
Highest sprinkler
Pump room
FIRST FLOOR
Grd. floor
Pipe line valve
Sprinkler Coverage
Hazard Type of Sprinklers Coverage
combustible -
asbestos cement 75 300 150
sheets, wired
glasses etc
combustible with
exposed rafters 75 150 ---
and/or open joists
etc
non-combustible-
either plane or 75 450 150
arched or sloping
Obstructions
Ducts :- 0.8m in width or 1m in diameter
to be sprinklered below hoods,
storage racks, worktables etc . to be
sprinklered below.
Concealed space :- if the space between
the false ceiling and the main ceiling is
more than 800mm, to be sprinklered.
A clear space of 0.6m shall be radially
available from the bottom of the deflector
of sprinkler.
Sprinkler Protection for specific hazards
Again, generally followed spacing and design can not be adhered to
certain specific risks as follows:
Sprinkler head is
normally closed, while
Spray head is normally
open.
COMPARISION BETWEEN WATER SPRINKLER & MIST DROPLET
SIZE
WATER MIST SYSTEM
BENIFITS DISADVANTAGE
• No 2.5” L.V would be connected
to the system.
WHERE TO USE WATER
MIST SYSTEM
• Water Mist system is required for firefighting of
high valued places, which may be damaged with
the action of traditional sprinkler system due to the
high amount of water, such as:
• Museums.
• Historical Palaces& Galleries.
• National Library& Archives.
• Tunnels.
• ships.
• Egyptians people's Assembly.
WHERE NOT TO USE
WATER MIST SYSTEM
FEATURES OF WATER MIST SYSTEM
Water cylinders of 50
liters.
MACHINERY
SPACE UNIT
Used at small enclosed
areas.
Each cylinder is
connected to 4 nozzles to
supply about 10 minutes.
Maximum height is 5
meters.
VIDEO
FOAM SYSTEM
NFPA 11 & NFPA 16
FOAM SYSTEM
• Foam generators are installed at the highest level in the protected space and at
strategic locations above high risks areas. The water/foam mixture is expanded with air
in the generators.
• The air used for producing foam is drawn from the protected space, thus, no
ducting and fans for external air is required .
• The foam produced by the foam generators falls due to gravity to cover the entire
protected space..
FOAM EXPANSION TYPES
• Low-expansion foams have an expansion rate less than 20 times.
Used on burning spills
Design parameters
Foam Concentration 3%
Length 20.0 m
Width 10.0 m
Height 5.0 m
2 2
Area 200.0 m 2152.8 ft
3
Volume 1,000 m
Generators.
CO2 SYSTEM
OPERATION METHOD
• Fire detectors sense fire conditions in Three methods of application :
the hazard area (smoke,heat,gas,air
sampling...) •Total flooding for enclosed spaces.
• Electrical signal is sent through the •Local application for discharge directly
fire alarm alarm control panel FACP into the fire (surface fire in flammable
to the control head. liquid, gases..).
• Control head releases CO2 from the •Hand hose line for fixed supply of CO2.
cylinders and is delivered through a
fixed piping network to discharge
nozzles in 1 min for surface fires and
less than 7 min for deep-seated fire.
CO2 SCHEMATIC
CO2 SYSTEM EQUIPMENT
CO2 CYLINDER
CO2 SYSTEM DESIGN
CO2 SYSTEM
CALCULATION EXCEL SHEET
Where:
Flooding Factor for room volume less than 56.6m3 the flooding factor should be 1.6kg CO2/m3
, and for room volume greater than 56.6m3 the flooding factor should be 1.33kg CO2/m3
Input Data
V= 324 m
3 ←
3
V= 11442 ft
Fl oodi ng Factor= 1.33
Output Data
CO2 Quanti ty 431 kg
0
Minimum anticipated temperature of the protected area 15.5 C
The amount of clean agent required shall be calculated from the formula.
Equation 1. W = V / S [ C /( 100 - C )] C = Clean agent concentration by volume
8.0%
Equation 2. S = K1 + K2 (T) K1 = 0.1269
S= 0.13465 m /kg
3
K2 = 0.0005
} for FM200 only
Calculation Result
Total Weight of clean agent 16.95 kg
No. of Nozzle Required -
FM200 Maximum Discharge Time -
Maximum Discharge Rate of Each Nozzle -
Symbols
W Weight of FM200 [kg]
3
S Specific Volume [m /kg]
C FM200 Concentration [%]
o
T Temperature [ C]
3
V Volume [m ]
K1, K2 Constant Specific to the FM200
NOVEC CALCULATION
SHEET
Computed By : Eng. H.S
Project:
Chec ked By: Eng. M. Gamal
Height 3.0 m
2 2
Area 100.0 m 1076.4 ft
3
Volume 300 m
Design Parameters
3
Net Volume of Hazard Area 300.0 m
o
Design T emperature in Hazard Area 20 C
3
Agent Specific Volume @ 1 Atm. pressure 0.072 m /kg
System Sizing ّ
Operation: Upon discharge, the FE-13 is discharged as a gas through the nozzles to a predetermined
concentration, usually 18%-20% within 10 seconds. The FE-13 extinguishes the fire through a cooling
effect at the molecular level. (The agent cools the combustion process, thereby, extinguishing the fire.)
The system can be activated by smoke, infrared, or ultraviolet detectors, and manual pull stations.
Technical Specifications:
Manufactured by Dupont
Active Agent: HFC-23
Ozone Depletion Potential (ODP): Zero
Acceptable under the EPA Significant New Alternatives Policy (SNAP)
Limitations: Enclosure Integrity
Approximate Agent Needed: Amount of FE-13 agent = (0.0438)(Volume of protected space in Cubic
Feet (FT3))
The conversion factor is dependent upon several variables such as: elevation, products protected,
temperature, and concentration required.
NAF SIII CLEAN AGENT
SYSTEM
• NAF S III®
• Identified as “HCFC Blend A” by US EPA and in the international standards on clean agent extinguishing
systems, NAF S III® shows physical characteristics similar to those of Halon 1301. By weight NAF S III
is the most effective halocarbon extinguishing agent.
• For most common fires it requires 10% more agent by weight compared to Halon 1301. In most cases it is
possible to replace NAF S III into existing Halon 1301 systems without the need to modify the existing
pipe-work. The overall environmental impact (ODP, GWP and Atmospheric Lifetime) is extremely low.
• With a boiling point of – 38.3 °C, NAF S III is easily distributed inside the protected environment, even in
low temperature conditions. Toxicity allows its safe use in normally occupied areas in most common
applications. In addition the presence of a patented additive, which reduces the decomposition by-
products, makes it safer for humans and goods.
1.NAF S-III is a clean, non-conductive media used for the protection of a variety of
potential fire hazards, including electrical and electronic equipment. NAF S-III is a clean
gaseous agent at atmospheric pressure and does not leave a residue. It is colorless and non-
corrosive.
NAF S-III acts as a fire-extinguishing agent by breaking the free radical chain reaction that
occurs in the flame during combustion and pyrolysis. Like Halon 1301, NAF S-III has a
better efficiency with flaming liquids than with deep-seated Class A fires.
NAF S-III fire extinguishing systems have the capability to rapidly suppress surface-
burning fires within enclosures. The extinguishing agent is a specially developed chemical
that is a gas at atmospheric pressure and is effective in an enclosed risk area. NAF S-III
extinguishes most normal fires at the design concentration by volume of 8.60% at 20° C.
Once the system is activated, the container valves are opened and the nitrogen propels the
liquid under pressure through the pipe work to the nozzles, where it vaporizes. The high
rate of the discharge through the nozzles ensures a homogeneous mixture with the air.
Sufficient quantities of NAF S-III should be discharged to meet the concentration required
and the pressure at each nozzle must be located to achieve uniform mixing.
PDF FILE FOR FM 200,
NOVEC & CO2
DRY CHEMICAL POWDER
FEATURES OF DRY
CHEMICAL POWDER
USE & LIMITATION OF DCP
WET CHEMICAL POWDER
FIRE TERRACE
CO2 SYSTEM