Professional Documents
Culture Documents
Chap3 Slow Transients
Chap3 Slow Transients
1. INTRODUCTION
This report is intended for practicing power system engineers
who are involved in system analysis, system control, and system planning. To use the report efficiently, adequate understanding of the physical phenomenon of interest and
familiarity with the concepts and techniques of digital computer simulation approaches are necessary.
2. LOW-FREQUENCY ELECTROMECHANICAL
DYNAMICS
This section provides modeling and analysis guidelines for low-frequency dynamics which involve electromechanical oscillations. The phenomena which are covered in
this section are torsional oscillations, transient torques, tur-
phenomena of 60 Hz power systems in the LF range are divided into the following categories:
3-1
The phenomenon of torsional oscillation is referred to as subsynchronous resonance (SSR) when it is a result of interaction
between a shaft system and a series capacitor compensated
transmission line. The problems associated with the phenomenon of small-signal torsional oscillations are:
3-2
mode which propagates almost through the entire of an interconnected electric network, the phenomena described in Section 2.1 are experienced only within a limited part of the
network. The section of the network which experiences the
phenomenon of interest, and must be represented in adequate
detail for the study of the phenomenon, is referred to as the
Study Zone The rest of the network is referred to as the external system The external system is represented by an
equivalent model. Identification of border nodes of the study
zone for a meshed network requires significant familiarity
with the network, as well as engineering judgment. As of
now, there is no straightforward and systematic approach to
identify the border nodes. One approach involves multiple
harmonic analyses of the system under investigation as
boundaries are extended to identify if new resonant frequencies (at the frequency range of interest) with low dampings exist.
The normal and alternate power source connections are always selected such that they are in phase. Therefore, manual
transfers can be accomplished in a make-before-break, i.e.,
the motors and loads are connected to the second power
source before the first power source is disconnected. In this
overlapping transfer, the power supply is not interrupted and
the motors are not subjected to transients. However, during
automatic transfers, the motors may be disconnected from
both power sources for a short duration depending on the type
of transfer and the associated circuit breakers operating times.
The time during which the motors are disconnected from both
power sources is termed the dead time. Dead time is usually
between two cycles to 12 cycles. If the relative angle between
the motor residual voltage and the power source voltage becomes large enough at the time of reconnection with significant residual voltage remaining, the resultant voltage
Proper determination of the study zone can exert a major impact on the investigations of torsional dynamics and transient
torques. Comparatively, the impact of the study zone on the
vibrations of turbine blades is less significant. Identification
of the study zone for bus transfer studies is relatively straightforward.
2.2.2 Component Model
between the power source and the motor will produce an inrush current. The inrush current may be significantly largely
than the normal full voltage staging current. Such high inrush
currents cause high winding stresses and transient shaft
torques which can damage the motor and/or the driven equipment.
Table 1 identifies the study zone components and their equivalent models for investigations of slow transient phenomena.
Further explanation of the system components are given in the
following sections.
Component
T urbine-B lade
Vibrations
Third-Order Model
(d-q-o Model)
Including
Saturation
Fast Bus
Trans fer
Not
applicable
Not
Applicable
C onventional
Low-Frequency
Model including
Saturation
Characteristic
Detail
Mass-SpringDashpot Model
Conventional
Low-Frequency
Model including
Saturation
Characteristic
Equivalent- %
Model
Ideal Capacitor
Equivalent- %
Model
Ideal Capacitor
Equivalent-%
Model
Ideal Capacitor
Series R-L
Series R-L
Series R-L
Fixed I mpedance
Load
Fixed Impedance
Load
Fixed I mpedance
Load
d-q-o Model of
Electrical System,
Mass-SpringDashpot Model of
Shaft System
Voltage Source
Behind Fixed
Impedance
Voltage Source
Behind Fixed
Impedance
HVDC Converter
Stat ion
Detailed Model of
C onverter and
Linearized
(Simplified)
Model of C ontrols
Detailed Model of
Power C ircuitry and
Linearized
(Simplified)
Model of C ontrols
Ideal Switch
Unimportant
Detailed Models of
Converter and
Controls
Detailed Models of
C onverter and
Controls
Detailed Model of
Power C ircuitry
and Controls
Detailed Model of
Power C ircuitry
and C ontrols
Not
Applicable
Ideal Sw itch
Unimportant
Ideal Switch
Unimportant
Unimportant
Series Capacitor
Overvoltages
Protection System
Ideal Switch
Not
Applicable
Not
Applicable
Synchronous
Generators
Electrical System
Turbine-Generator
Shaft System
Power
Transfor mer
SVC
C ircuit Breaker
Generator
Controls
Protection System`
To rsion al
Oscillatio ns
Second-Order
Model and
Preferably ThirdOrder Model (d-q-o
Model)
Mass-SpringDashpot Model
T ra nsient
Torques
Third-Order
Model (d-q-o
Model)
Including
Saturation
Mass-SpringDashpot Model
Conventional
Low-Frequency
Model including
Saturation
Characteristic
Conventional
LowFrequency
Model
including
Saturation
C haracterist ic
Not
Applicable
Ideal
Capacitor
Series R-L
Fixed
Impedance
Load
d-q-o Model
of
Electrical
System,
Mass-SpringDashpot
Model of
Shaft System
Not
Applicable
In most studies, the power plant under consideration is composed of more than one turbine-generator unit. If all the turbine-generator units are nominally identical, and under almost
equal loading conditions, they can be represented by a single,
equivalent turbine-generator unit. Otherwise, each turbinegenerator unit must be separately represented.
3-5
Shaft dynamics of a turbine-generator can be excited as a result of interaction between the turbine-generator and either
rectifier current-control or the inverter extinction angle (voltage) control of an HVDC link. Thus, if both the rectifier and
the inverter stations are within the study zone, both converter
stations, dc line, and the associated controls, with adequate
level of sophistication, must be represented in the system
model.
When the inverter station is not within the Study Zone, the inverter station and the dc line can be represented by an equivalent controlled voltage source, and only the rectifier station
and its controls must be modelled in details. Similarly, the
rectifier station and the dc line can be modelled as an equivalent controlled current source and only the inverter station and
its control system be represented in detail, if the rectifier station is not within the Study Zone.
2.2.2.7 Loads
Fixed Impedance model is an adequate load representation when turbine-generator shaft dynamics are of concern.
However, if an induction motor load or a synchronous motor
load is comparable to the MVA rating of the turbine-generator
under consideration, fixed impedance representation of the load
may result in erroneous conclusions. Under such conditions, the
load is best represented by either an equivalent induction motor
or an equivalent synchronous motor.
3-6
benchmark models have been extensively used for time-domain as well as frequency-domain investigation of the phenomenon of torsional oscillations. Numerous study results,
using the benchmark model, have been published in the IEEE
PES Transactions [2.1, 2.2, 2.3, 2.4, 2.5].
Time-domain simulation and frequency-domain eigen analysis are widely used as complementary approaches for reciprocal verification of torsional studies.
2.3.2 Transient Torques
The first and the second IEEE benchmark models for SmallSignal torsional studies introduced in Section 2.3.1 also have
been extensively used for transient torque studies. Due to the
nonlinear nature of large-signal torsional oscillations, digital
time-domain simulation is the only approach to investigate
the phenomenon. There are no measurement results regarding
transient torques in the widely circulated technical literature.
Thus, simulation results cannot be readily compared with actual field tests. At this stage, a general verification rule is to
ensure that the simulation results satisfy the well understood
behavioral patterns and immediately after switching incidents.
2.3.4 Bus-Transfer
The simplified system introduced in [2.7], is recommended as
the test system for bus transfer studies. Typical motor load
data for simulation studies are available in [2.19].
loop control system and a natural oscillatory mode of an apparatus. One practical case of controller interaction phenomenon is that of multiple SVCs [3.1]. The problem of controller
interactions attracts more attention as the number of power
electronic based devices increases.
be validated by simulating motor starting and running conditions and comparison of other simulation results to data recorded during an actual motor instantaneous current, power,
apparent power (VA), and speed. However, since a typical
bus transfer model may include 15 or more motors, it may not
be practical to validate individual motor models.
To establish the dead time and a range of the expected accuracy, it is recommended to perform a fast bus transfer test with
a few motors connected and simulating the test conditions using motor models based on the manufacturer supplied data.
Since measuring the transient variations in the motor shaft
torque is a complex task, it is suggested to monitor, simulate
and compare the following parameters:
Appendix A provides further information regarding fast bustransfer and typical time-domain simulation results.
3-8
trolled current source and only the inverter station and its control system be represented in details, if the rectifier station is
not within the Study Zone.
All the steady-state continuous controls of rectifier and inverter stations, e.g. DC current control, DC voltage control, AC
voltage control or reactive power control, real power control,
and frequency control must be represented in the model. The
control model must adequately represent firing and synchronization schemes used for the converter values.
When the inverter station is not within the Study Zone, the inverter station and the dc line can be represented by an equivalent controlled voltage source, and only the rectifier station
and its controls be modelled in detail. Similarly, the rectifier
station and the dc line can be modelled as an equivalent con-
3-9
The main concerns with the presence of noncharacteristic harmonics are (1) harmonic interactions and/or resonance [4.1],
and (2) the interference phenomenon [4.2].
Radio and telephone interference as a result of dc side harmonics of HVDC converters is a well known phenomenon.
Also, second and third harmonic instability of ac systems due
to harmonic modulation characteristic of HVDC converter
has been encountered in the existing installations [4.1].
Both stray capacitances and magnetic saturation characteristics of power transformers within the study zone can have significant impact on power system harmonics. The magnetic
saturation characteristic has a deterministic impact on the second harmonic instability and can be fairly represented by the
no-load V-I characteristic in the magnetization branch of the
transformer. The winding stray capacitances to the tank have
a noticeable effect on the interference phenomenon [4.2]. The
stray capacitance can be adequately modelled by a single capacitance from the winding terminal to the ground [4.2].
4.3.4 Transmission Lines
Transmission lines within the study zone are best represented
as distributed parameter lines including parameter frequency
dependency. However, if the frequency range of interest does
not cover high frequencies (more than 300 Hz), each transmission line can be represented by multiple sections.
4.3.5 Series and Shunt Capacitor Banks
Series and shunt capacitors have deterministic impacts on series and parallel resonant frequencies of the system and must
be represented in the overall system model for harmonic studies. Both series and shunt capacitors are adequately represented by lumped three-phase capacitor banks.
3-10
Similar to series and shunt capacitors, shunt reactors also influence the system natural resonant frequencies and must be
represented in the system model. A shunt reactor is adequately represented by a three-phase lumped reactor bank.
4.3.7 Loads
Fixed Impedance model is a valid representation for loads
within the study zone, unless the load is known to have particular resonant frequency or generates particular harmonic(s)
which can affect the harmonic phenomenon of interest.
4.3.8 HVDC Converter Station
The HVDC converter station is one of the major
sources for generation of harmonics which cause interference
and/or instability of electrical power networks [4.1]. The
required model of an HVDC converter station for studying interference and harmonic interaction phenomena is the same as the
model described in Section 3.3.8.
The model of valve firing circuitry must be capable of generating exact firing instants.
Operating point and parameter values of a SVC can readily
influence series/parallel resonant frequencies of a network
and consequently tune the system for resonant conditions, e.g.
second harmonic resonance [4.4]. The above model can also
be used for this class of resonant conditions which normally
occur at noncharacteristic harmonics generated by power
electronic circuits.
4.3.10 Generator Control
Automatic voltage regulator, power system stabilizer, and
governor system do not influence harmonic related problem.
Thus, their model can be excluded from the system model for
time-domain harmonic studies.
4.3.11 Harmonic Filters
SVC and HVDC harmonic filters must be modelled as described in Section 3.3.11.
4.4 TEST SYSTEM
The HVDC-AC system of Fig. 4.3 is proposed as the test system for the investigation of harmonic interactions phenomena
and the second harmonic instability issues.
3-11
modelling approach of [4.15] are reported in [4.14]. References [4.16, 4.17, 4.18] provide a comprehensive and fundamental description of the harmonic interaction phenomenon.
However, there are not that many measurements and investigation of the harmonic interaction phenomenon to establish a
method for verification of time-domain simulation studies.
Reference [4.19] introduces an alternative approach based on
frequency scanning method for identification of harmonic instabilities in HVDC systems. This approach may be used for
qualitative verification of digital time-domain simulation approach.
5. FERRORESONANCE
The inverter ac system consists of a 230-kV ac source which
is connected to the inverter station through a 500-kV, 832-km
transmission system. The transmission line is equipped with
240/525-kV Y - Y connected transformer at the source side.
The ac line is divided in three sections, Fig. 4.3. Each intermediate station is equipped with a 400 MVA capacitor bank
for voltage profile improvement. Loads #1, #2, and #3 are rated at 920-MVA, 400-MVA and 360-MVA respectively. The
inverter station is also equipped with an SVC which can adjust its reactive power from 180-MVAR inductive to 510MVAR capacitive. Electrical parameters of the inverter ac
system are given in [4.7]. The ESCR of the inverter ac side is
2.2.
References [4.8] and [4.9] provide various HVDC/ac benchmark models that also can be used for the analyses of harmonic interactions and resonance phenomena. The first HVDC
benchmark model [4.8] proposed by CIGRE WG 14-02 also
exhibits second harmonic resonance and can be adopted for
investigation of harmonic instability phenomenon. This system is less complicated as compared with that of Fig. 4.3.
Reference [4.10] provides a very simple circuit configuration
which exhibits instability due to switching characteristic of
thyristor-controlled reactor (TCR). A set of time-domain
simulations results of the test systems of Fig. 4.3 is given in
[4.4].
4.5 VERIFICATION OF SIMULATION RESULTS
There are several technical papers which deal with analysis
and measurement of noncharacteristic harmonics of HVDC
converter stations [4.2, 4.11, 4.12, 4.13]. The primary concern in these papers is the dc side triplen harmonics which
cause interference and not the second harmonic instability
problem. Reference [4.15] provides a modelling approach for
representation of a six-pulse converter with respect to the second harmonic for eigen analysis. Such eigen analysis approach can be used as an alternative technique for validation
of simulation results. Eigen analysis studies based on the
3-12
2 0 0 .0
1 .0
1 5 0 .0
0 .7 5
1 0 0 .0
0 .5
5 0 .0
0 .2 5
0 .0
0 .0
-5 0 .0
-0 .2 5
-1 0 0. 0
-0 .5
-1 5 0. 0
-0 .7 5
-2 0 0. 0
0 .0 s
1 0 . 0m s
2 0 . 0m s
3 0 . 0m s
4 0 . 0m s
-1 .0
5 0 . 0m s
T IM E
Fig. 5.1. Unloaded single phase transformer with rated voltage applied.Solid
waveform is applied voltage; dashed waveform is exciting current
3-13
Fig. 5.2. Same transformer as in Fig. 5.1, fed through a 75F capacitance,operating in ferroresonance. Solid waveform is terminal voltageof
transformer; dashed waveform is the current.
Fig. 5.1. Core configurations commonly used in three phase transformers.Only one set of windings is shown.
3-14
If one or two poles of the switch are open and if either the capacitor bank or the transformer have grounded neutrals, then
a series path through capacitance(s) and magnetizing reac-
3-15
Either overhead lines or underground cables connect transformers to the system. Cables have a relatively large shunt capacitance compared to overhead lines, so this type of
ferroresonance most often involves underground cables, but is
also possible due solely to transformer winding capacitance.
Three phase or single phase transformers can appear at the
end of a distribution line or at any point along the line. Three
phase transformers may have any one of the several core types
discussed in the previous section.
3-16
3-17
3-18
For three phase transformers, it is possible to make a simplified model by connecting together three of the above single
phase models. If this is done, a triplex core configuration is
assumed (see Fig. 5.3). A delta-wye transformer of this type
is shown in Fig. 5.7. It is postulated that zero sequence (homopolar) effects are included almost entirely by the leakage
inductance of the delta windings [5.11,5.22].
Fig. 5.1. Model of a delta to wye transformer bank made up of three single
phase transformer models [22].
If the transformer does not have any delta windings, zero sequence effects may be included by adding a set of delta windings to the model whose total leakage impedance is equal to
the transformer's zero sequence inductance. This may work
for a three-legged core transformer that has an air path for
zero sequence flux, but is highly questionable in the case of
transformers having a saturable zero sequence flux path.
Factory three-phase excitation test reports will not provide the
information needed to get the magnetizing inductances for
this model. Note that standards require the exciting current to
be stated as the "average" value of the RMS exciting currents
of the three phases. Unless it is a triplexed core, this is meaningless, since the currents are not sinusoidal and they are not
the same in every phase. Therefore, the waveforms of the applied voltage and exciting currents in all three phase should be
given by the manufacturer for all levels of applied voltage.
3-19
rameters are referenced to the low voltage windings. The portion of the model inside the coupling transformers represents
the core and leakages. Winding resistance and interconnection of the windings appears external to the coupling transformers. The advantage to this is that the derived core
equivalent can be used independently of winding configuration (delta, wye, zig-zag, etc.). Winding resistance, core losses, and capacitive coupling effects are not obtained directly,
but can be added to this topologically-correct equivalent electrical circuit.
Fig. 5.1. Duality derived equivalent circuit with current sources replaced by
ideal coupling transformers. Winding resistances have also been added
Fig. 5.1. Development of magnetic circuit for grounded-wye togroundedwye five-legged wound core transformer. At top, transformer core sectional
view used as a basis for duality derivation. Leakageflux paths are labeled.
Bold dividing lines mark division in corereluctances. Equivalent magnetic
circuit is shown at bottom.
The delta side will "float" with respect to earth, until some
load or other source of grounding is connected. If there is a
A recent problem occurring in a 50-kV network in the Hafslund area near Moss, Norway, serves as an excellent example
[5.18]. The clearing of a short circuit removed the only remaining source of grounding on the system. After the fault
was cleared, the only remaining zero sequence impedance
was due to capacitive coupling to earth. After operating in
this way for only 3 minutes, ferroresonance had destroyed 72
of the VTs used for measurement and protective relaying. All
72 of the damaged VTs were from the same manufacturer.
The VTs of two other manufacturers that were also in service
during this time were not damaged.
Fig. 5.10 shows the typical VT arrangement used in this system. The VTs have two low voltage windings. The secondary
is used for measurement and protective relaying purposes.
The burden on that winding has a very high impedance and its
effects can be ignored when considering ferroresonance. It is
the tertiary windings which are shown in Fig. 5.10. These
windings are connected in open delta and loaded with a damp-
3-20
EMTP model. System positive and negative sequence impedances were found to be very small compared to the primary
impedances of the VTs, and could be neglected. The zero
sequence impedance ZO consists almost entirely of the stray
capacitance of the floating system, and is therefore very important. Values of ZO varied from 0.6 - j219 to 0.2 - j221 , depending where in the system. ZO therefore becomes the only system
impedance needed in the model, and the positive sequence voltage sources can be modeled as stiff sources. The core losses of
the VTs were also neglected, their values being much higher
than the damping resistance RO.
Since some of the VTs were damaged and the others weren't,
the VTs of different manufacturers obviously must have different characteristics. The problem at Hafslund therefore
forced a re-evaluation of the specification and application of
voltage transformers. EMTP was used to simulate the system
conditions that caused the VT failures. VT model parameters
were obtained from the manufacturers. Parameters are shown
in Table 1. Saturation characteristics were calculated based
on core material B-H data, core dimensions, and number of
primary turns. Data for the damaged VTs are listed as VT #1.
Fig. 5.3. Comparison of the saturation characteristics of the three VTs. Note
the much lower saturation level of VT #1, the ones that were damaged.
RP
XP
XT
N 1 :N 3
B M AX
VT # 1
32 50 6
2 500 6
0.0 1 6
20 k:2 3
1. 05T
VT # 2
32 18 6
3 094 6
0.0 1 6
~3 6k:42
0. 77T
VT # 3
75 88 6
4 833 6
0.0 1 6
25 k:2 9
0. 83T
Fig. 5.4. Reduced system equivalent, neglecting line impedances and lumping all VTs in each phase into an aggregate jXM.
3-21
Fig. 5.2. Ontario Hydro 230-kV system. Ferroresonance involving line X3H
and connected transformer at Cataraqui Transformer Station.
Fig. 5.1. Sample bifurcation diagram. Shunt capacitance on X1 is ramped
from 0 to 30 F. Blurred areas correspond to chaos.
Fig. 5.14 shows the result of one of the EMTP simulations and compares it to the actual measurements. The model
Several EMTP simulations were run, with Y-connected resistive loads of zero, 133 kW/phase, and 266 kW/phase attached
to the tertiary of T2. In each case, the 115-kV breaker of T2
was assumed to open last. Two double-circuit 230-kV lines,
an existing 500-kV line, and a future 500-kV line were includ-
3-22
3.0E+5
CATARAQUI T2 FERRORESONANCE
EXTERNAL DAMPING = 133 kW / phase
2.0E+5
1.0E+5
0.0
-1.0E+5
-2.0E+5
-3.0E+5
402 kV peak
-4.0E+5
0.0s
100.0ms
200.0ms
300.0ms
400.0ms
TIME
Fig. 5.4. Cataraqui (T2) Autotransformer Ferroresonance. HV terminal voltage on Phase C is 2.0 per unit, with 133 kW/phase of damping.
5.8 RECOMMENDATIONS
Is seen that many different types of ferroresonance can and
do occur. Because of the nonlinear nature of ferroresonance,
it is difficult to predict if and where it might next occur. The
power system engineer should be aware, however, that it is
possible for lightly-loaded transformers operating in the presence of source or shunt capacitance to experience ferroresonance. Capacitance can be present in the form of cables,
series or shunt capacitor banks, or even stray capacitances in
inadequately-grounded portions of the system.
Transient simulations are helpful in confirming or predicting the likelihood of ferroresonance, but only if a correct model is used. Per phase simulations of three phase systems will
not give correct results, due to various possible transformer
core configurations and winding connections. A complete
three phase model must be used. Therefore, the key to transient modeling is use of the proper transformer model. Development and use of acceptable transformer models should be a
priority task.
The development of improved topologically correct models is
a significant advancement, but model performance still depends on improving the way in which the cores are represented. Transformer core configuration must be considered and
saturation characteristics must be accurately known to operating levels well above rated voltage.
At this time, it is seen that modeling of ferroresonance is as
much an art as a science. As such, it is important if possible
to verify the results by checking the simulations against system measurements. It is highly recommended that anyone active in this area must continually monitor the literature for
improvements in modeling techniques.
6. SUMMARY
This document provides a set of general guidelines for digitalcomputer time-domain simulation of low-frequency (approximately 5 to 1000Hz) transients of electric power systems.
3-23
The report is intended for practicing engineers who are involved in analysis, control and system planning issues related
to electronic power systems. It is assumed that the reader has
(1) a fair understanding of the physical phenomena and (2) an
adequate knowledge of digital simulation techniques. The
guidelines are provided for seven transient torsional torques,
(3) turbine-blade vibrations, (4) fast bus transfer, (5) controller interactions, (6) harmonic interactions and resonance, and
(7) ferroresonance. For those phenomena which have extensively discussed in the literature, i.e. (1) to (4), general guidelines are provided and the reader is frequently referred to the
technical literature for further in-depth modeling and simulation issues. The emphasis of this document is on phenomena
(5), (6) and particularly (7).
7. REFERENCES
[1.1]CIGRE, Guidelines For Representation of Network Elements When Calculating Transients, CIGRE Working
Group 33.02, 1990.
[2.1] IEEE Torsional Issues Working Group, Fourth Supplement To A Bibliography For The Study of Subsynchronous
Resonance Between Rotating Machines and Power Systems,
IEEE Trans., Vol. PWRS-12, No. 3, pp. 1276-1282, August
1997.
[2.2] IEEE SSR Working Group, A Bibliography for the
Study of Subsynchronous Resonance Between Rotating Machines and Power Systems, IEEE Trans., Vol. PAS-95, No.
1, pp. 216-218, Jan. - Feb. 1976.
[2.3]IEEE SSR Working Group, First Supplement to a Bibliography for the Study of Subsynchronous Resonance Between Rotating Machines and Power Systems, IEEE Trans.,
Vol. PAS-98, No. 6, pp. 1872-1875, Nov. - Dec. 1979.
[2.16]N. Rostamkolai, et al, Subsynchronous Torsional Interactions with Static VAR Compensators - Influence of
HVDC, IEEE Trans. on Power Systems, Vol. PWRS-6, No.
1, pp. 255-261, Feb. 1991.
[2.5]IEEE SSR Working Group, Third Supplement to a Bibliography for the Study of Subsynchronous Resonance Between Rotating Machines and Power Systems, IEEE Trans.,
Vol. PWRS-6, No. 2, pp. 830-834, May 1991.
[2.6]T.P. Tsao, C. Chgn, Restriction of Turbine Blade Vibrations in Turbogenerators, IEE Proceedings, Vol. 137, Part C,
No. 5, pp. 339-342, 1990.
[2.7]J.D. Gill, Transfer of Motor Loads, Between Out-ofPhase Sources, IEEE Trans. on Industrial Applications, Vol.
IA-15, No. 4, pp. 376-381, 1979.
[2.8]T.A. Higgins, P.L. Young, W.L. Snider, H.J. Holley,
Report on Bus Transfer: Part II, Computer Modelling for
[2.18]A.N. Vasconcelos, et al, Detailed Modeling of an Actual Static VAR Compensator for Electromagnetic Transient
Studies, IEEE Trans. on Power Systems, Vol. PWRS-7, No.
1, pp. 11-19, 1992.
[2.19]H.J. Holley, T.A. Higgins, P.L. Young, W.L. Snider,
A Comparison of Induction Motor Models for Bus Transfer
Studies, IEEE Trans. on Energy Conversion, Vol. EC-5, No.
2, pp. 310-319, 1990.
[2.20]EPRI Report, Bus Transfer Studies for Utility Motors, EERI EL-4286, Vol. 2, Project 1763-2, October 1986.
[2.21]G.J. Rogers, D. Shirmohammadi, Induction Machine
Modelling For Electromagnetic Transients Program, IEEE
Trans., Vol. EC-2, No. 4, pp. 622-628, December 1987.
3-24
[3.1]A.J.P. Ramos, H. Tyll, Dynamic Performance of a Radial Weak Power System with Multiple Static VAr Compensators, IEEE Trans., Vol. PWRS-4, pp. 1316-1325,
November 1989.
[3.4]M. Parniani, Small-Signal Stability Analysis And Robust Control Design of Static VAR Compensators, Ph.D
Thesis, University of Toronto, 1995.
...[3.5]M. Parniani, M.R. Iravani, Voltage Control Stability
and Dynamic Interaction Phenomena of Static VAR Compensators, IEEE Trans., Vol. PWRS-10, No. 3, pp. 1592-1597,
August 1995.
[3.6]G. Gross, C.F. Imparato, P.M. Look, A Tool for Comprehensive Analysis of Power System Dynamic Stability,
IEEE Trans., Vol. PAS-101, No. 1, pp. 226-234, January
1982.
[3.7]R.M. Hamouda, M.R. Iravani, R. Hackam, Coordinated
Static VAR Compensators and Power System Stabilizers for
Damping Power System Oscillations, IEEE Trans., Vol.
PWRS-2, pp. 1059-1067, 1987.
[3.8]M. Parniani, M.R. Iravani , Computer Analysis of
Small-Signal Stability of Power System Including Network
Dynamics, Proceeding IEE, Gen-Trans-Distrib, Vol. 142,
No. 6, pp. 613-617, November 1995.
[4.1]A.E. Hammad, Analysis of Second Harmonic Instability for the Chateauguay HVDC/SVC Scheme, IEEE Trans.,
Vol. PWRD-7, No. 1, pp. 410-415, January 1992.
[4.2]E.V. Larsen, M. Lublich, S.C. Kapoor, Impact of Stray
Capacitance on HVDC Harmonics, IEEE Trans., Vol.
PWRD-4, No. 1, pp. 637-645, 1989.
[4.3]A.S. Morched, J.H. Ottevangers, L. Marti, Multi-Port
Frequency Dependent Network Equivalents for the EMTP,
IEEE Trans., Vol. PWRD-8, No. 3, pp. 1402-1412, July 1993.
[4.4]A. Sarshar, M.R. Iravani, J. Li, Calculation of Noncharacteristic Harmonics of HVDC Station Using Digital TimeDomain Simulation Method, IEEE Trans., Vol. PWRD-11,
[4.5]Manitoba HVDC Research Center, EMTDC User Manual, pp. 12.44-12.50, 1988.
[4.10]L.A.S. Pilotto, J.E.R. Alves, E.H. Watanabe, A.E. Hammad, A Non-Linear Switching Function Model for Static
VAR Compensators, Proceedings of International Power
Electronics Conference (IPEC), pp. 627-631, Yokohama,
April, 1995.
[4.11]N.L. Shore, G. Andersson, A.P. Canelhas and G. Asplund, A Three-Pulse Model of DC Side Harmonic Flow in
HVDC Systems, IEEE Trans., Vol. PWRD-4, No. 3, pp.
1945-1954, July 1989.
[4.12]D.L. Dickmander, K.J. Peterson, Analysis of DC Harmonics Using the Three-Pulse Model for the Intermountain
Power Project HVDC Transmission, IEEE Trans., Vol.
PWRD-4, No. 2, pp. 1195-1204, April 1989.
[4.13]T.F. Garrity, I.D. Hassan, K.A. Adamson, J.A.
Donahue, Measurement of Harmonic Currents and Evaluation of DC Filter Performance of the New England - Hydro
Quebec Phase I HVDC Project, IEEE Trans., Vol. PWRD-4,
No. 1, pp. 779-786, January 1989.
[4.14]D.L. Dickmander, S.Y. Lee,, G.L. Desilets, M. Granger, AC/DC Harmonic Interaction in the Presence of GIC for
the Hydro Quebec - New England Phase II HVDC Transmission, IEEE Trans., Vol. PWRD-9, No. 1, pp. 68-78, January
1994.
[4.15]H. Stemmler, HVDC Back-to-back Interties on Weak
AC Systems - Second Harmonic Problems Analysis and Solution, CIGRE Symposium, Paper 300-08, Boston, 1987.
[4.16]R.H. Lasseter, L.J. Bohmann, Harmonic Interactions
in Thyristor Controlled Reactor Circuits, IEEE Trans., Vol.
PWRD-4, No. 3, pp. 1919-1925, July 1989.
[4.17]L.J. Bohmann, R.H. Lasseter, Stability and Harmonics
in Thyristor Controlled Reactors, IEEE Trans., Vol. PWRD-
3-25
28-30, 1989.
[4.18]S.G. Jalali, R.H. Lasseter, A Study of Nonlinear Harmonic Interaction Between a Single Phase Line-Commutated
Converter and a Power System, IEEE Trans., Vol. PWRD-9,
No. 3, pp. 1616-1624, July 1994.
[5.15]J.G. Frame, N. Mohan and T. Liu, "Hysteresis Modeling in an Electro-Magnetic Transients Program", IEEE Trans.
PAS, vol. PAS-101, no. 9, pp. 3403-3411, September, 1982.
[5.16]J. Gleick, Chaos: Making a New Science, Viking, New
York, NY, copyright 1987.
[5.17]C. Hayashi, Nonlinear Oscillations in Physical Systems, McGraw-Hill Book Company, New York, NY, copyright 1964.
[5.18]T. Henriksen and O. Rrvik, "Ferroresonans i 50-kV
Nett til Hafslund", Energiforsyningens Forskningsinstitutt A/
S, Trondheim, Norway, ISBN 82-594-0229-7, EFI TR 3779,
December 19, 1990 (in Norwegian).
[5.19]R.H. Hopkinson, "Ferroresonance During Single-Phase
Switching of 3-Phase Distribution Transformer Banks", IEEE
Trans. PAS, vol. PAS-84, no. 4, pp. 289-293, April 1965.
[5.20]D.C. Jiles and D.L. Atherton, "Theory of Ferromagnetic
Hysteresis," Elsevier Science Publishers B.V., Journal of
Magnetism and Magnetic Materials, vol. 61. pp. 48-60, January 21, 1986.
[5.21]Kieny, "Application of Bifurcation Theory in Studying
and Understanding the Global Behavior of a Resonant Electric Power Circuit," IEEE PES Summer Meeting, SM 265-9
PWRD, July 1990.
[5.22]K.U. Leuven EMTP Center, Alternate Transients Program Rule Book, Leuven EMTP Center, Heverlee, Belgium,
Revised July, 1987, copyright 1987.
[5.23]D.D. Mairs, D.L. Stuehm and B.A. Mork, "Overvoltages on Five-Legged Core Transformers on Rural Electric Systems", IEEE Trans. on Industrial Applications, vol. 25, no. 2,
pp. 366-370, March, 1989.
[5.24]L.W. Match and J.D. Morgan, Electromagnetic and
Electromechanical Machines, Third Edition, Harper & Row
Publishers, Inc., New York, copyright 1986.
[5.25]R.D. Millet, D.D. Mairs and D.L. Stuehm, "The Assessment and Mitigation Study of Ferroresonance on GroundedWye to Grounded-Wye 3-Phase Padmounted Transformers",
Summary Report, NRECA Project 86-7, July, 1987.
[5.26]B.A. Mork, Ferroresonant Modeling Using EMTP, MS
Thesis, North Dakota State University, September 1981.
[5.27]B.A. Mork and D.L. Stuehm, "Application of Nonlinear
Dynamics and Chaos to Ferroresonance in Distribution Systems," IEEE Trans. Power Systems, vol. 9, no. 2, pp. 10091017, April 1994.
3-26
[5.30]A. Narang and R.H. Brierley, "Topology Based Magnetic Model for Steady-State and Transient Studies for Three
Phase Core Type Transformers," IEEE Trans. PWRS, vol. 9,
no. 3, pp. 1337-1349, August 1994.
[5.45]J.M.T. Thompson and H.B. Stewart, Nonlinear Dynamics and Chaos - Geometrical Methods for Engineers and Scientists, John Wiley and Sons, New York, NY, (Reprinted
October 1987), copyright 1986.
[5.46]J. Usaola and G. Empereur, "Comparison Between Different Transformer Models in EMTP," EMTP News, vol. 2,
no. 2, pp. 25-34, June 1989.
[5.47]R.A. Walling, K.D. Barker, T.M. Compton, and L.E.
Zimmerman, "Ferroresonant Overvoltages in Grounded WyeWye Padmount Transformers with Low-Loss Silicon-Steel
Cores", IEEE Trans. Power Delivery, vol. 8, no. 3, pp. 16471660, July, 199.
APPENDIX A
[5.36]R. Rudenberg, Transient Performance of Electric Power Systems, McGraw-Hill Book Company, New York, NY,
chapter 48, copyright 1950.
Motors and other loads in utility and heavy industrial applications are supplied during normal operation from a
preferred power source. An alternate power source is normally provided to supply such motors and other loads during
planned shutdowns and upon loss of normal power from the
preferred power source. The process of disconnecting the
motors and other loads from one source and reconnecting to
an alternate source is commonly defined as bus transfer.
Manual transfer means are normally provided to
allow transferring the motors and other loads from one power
source to the other. However, upon loss of the preferred
power source, the motors and other loads are automatically
transferred to the alternate power source. This automatic
transfer is necessary to allow uninterrupted operation of the
motors and other loads important to personnel safety and process operation.
3-27
3-28
A.2.7 Cables/Lines
Cable and Lines may be modelled by their -equivalents.
A.2.8Simulation and Analysis
In selecting conditions to be analyzed, the following
should be taken into consideration:
3-29