EMV CALCULATION
1 The resultant air flow out of the tank due to the in-flow of liquid during filling
2 Thermal out-breathing due to the atmospheric heating effect (expansion) on the vapour within the tank.
3 The maximum flow from the tank blanketing valve, should it fail fully open.
1 METRIC - For each M3/h (1000 l/h) of liquid being filled, an out-breathing rate of 2.02 Nm3/h of air is required
357.373 T/H
681.97 kg/m3
0.68197 T/m3
1.46634 m3/T
412.5304 m3/h
412530.4 l/h
412.5304 833.3114 Nm3/h Air

2 Tank capacity
15436.24 m3

2.495 Nm3/h Air

A
Q
F
L
T
M
VR

wetted surface area


Q=43,200A^0.82

821.4974
10603782
1
1371200
239.5
17

lattent heat

m2
Watts
J/kg
K

25587.94 Nm3/h Air

Required EMV capacity

26423.74 Nm3/h Air

68962.5 Nm3/h NH3


40074.46

Kd

0.462

P2+At/P1+At

0.957788

P1
P2
K
T
M
Z
At
F
k

0.147
0.098
1.334
240
17
0.983
1.0138
1
1.31

1871.281 cm2

---> 20"

0.936275

0.926768

0.001073

---> 24"

vapour within the tank.

2.02 Nm3/h of air is required

design pressure

MW air

0.15 kg/cm2 G
0.147 bar G

28.96
0.76617

0.003194

EMV CALCULATION
1 The resultant air flow out of the tank due to the in-flow of liquid during filling
2 Thermal out-breathing due to the atmospheric heating effect (expansion) on the vapour within the tank.
3 The maximum flow from the tank blanketing valve, should it fail fully open.
1 METRIC - For each M3/h (1000 l/h) of liquid being filled, an out-breathing rate of 2.02 Nm3/h of air is required
510 T/H
681.97 kg/m3
0.68197 T/m3
1.46634 m3/T
747.8335 m3/h
747833.5 l/h
747.8335 1510.624 Nm3/h Air

2 Tank capacity
30521.98 m3

2.495 Nm3/h Air

A
Q
F
L
T
M
VR

wetted surface area


Q=43,200A^0.82

2426.908
25776708
0.01
1371200
239.5
17

lattent heat

m2
Watts
J/kg
K

622.0165 Nm3/h Air

Required EMV capacity

2135.135 Nm3/h Air

2786.764 Nm3/h NH3

Kd

0.462

2113.634 kg/h

P2+At/P1+At

0.914322

P1
P2
K
T
M
Z
At
F
k

0.095
0
1.31
240
17
0.983
1.0138
1
1.31

379.5258 cm2

21.988 cm

0.872186

0.853893

0.001054

8.656695 inch

vapour within the tank.

2.02 Nm3/h of air is required

design pressure

MW air

0.15 kg/cm2 G
0.147 bar G

28.96
0.76617

8094.1 kg/h
10671.83

0.00439

106.6879
10.32898 20.65797
26.23562 2161.286

VR

Kd
P1+At
P2+At
K
T
M
Z
F

(P2+At/P1+At)^2/k
(P2+At/P1+At)^k+1/k
k/mtz(k-1)

VR

Kd
P1+At
P2+At
K
T
M
Z
F

8094.1
10671.83
376830.3
0.6907
0.095

kg/h
Nm3/h
scfh
kg/cm2 g

1SCFH =

1.3509 psig

1.3
432.27 Rankine
17
0.9836
1

(P2+At/P1+At)^2/k
(P2+At/P1+At)^k+1/k
k/mtz(k-1)

0.873490886
0.855947514
0.000599514 *
0.00324307
10020.3326
37.60656146 in2
6.921448383 in

0.02832 Nm3/h

16.0509 psia
14.7 psia

P2/P1abs

0.915836