Sub-Divisional Engineer, Design Circle1, Bangladesh Water Development Board (BWDB), 72, Green Road,
Dhaka-1215, Bangladesh. E-mail: masood35bd@yahoo.com
2)
Professor, Department of Civil Engineering, Bangladesh University of Engineering and Technology (BUET),
Dhaka-1000, Bangladesh. E-mail: iahmed@ce.buet.ac.bd
3)
Assistant Professor, Department of Civil Engineering, Umm Al-Qura University, Makkah, Saudi Arabia.
E-mail: mmassas@uqu.edu.sa
ABSTRACT
Provision of parking may require an opening to be kept at the base of a shear wall. In this paper, an attempt is
made to establish the range of base opening that may be allowed without significantly affecting the strength
and stiffness. The behavior of planar and box shear wall with varying percentages of base opening has been
studied and compared to that of a shear wall without opening. Finite element package ANSYS has been used
for modeling. A set of non-dimensional graphs has been prepared featuring important parameters which will
guide the designer to choose an appropriate opening width. It is observed that the rate of decrease of
stiffnessis is relatively low for up to 60% base opening. Beyond this limit, strength and stiffness degradations
are excessive. Based on the findings of the study, it has been recommended that in high-rise constructions the
provision of a base opening up to 50% of the length of the wall may be considered as a feasible option.
KEYWORDS: Concrete, Shear wall, Base opening, ANSYS, Finite element.
INTRODUCTION
Shear walls may be defined as structural elements,
which provide strength, stiffness and stability against
lateral loads deriving strength and stiffness mainly
from their shape. In many cases, high-rise buildings are
designed as a framed structure with shear walls that can
effectively resist horizontal forces (Kim et al., 2005).
Lateral forces generated either due to wind blowing
against the building or due to the inertia forces induced
by ground shaking tend to snap the building in shear
and push it over in bending. These types of forces can
be resisted by the use of a shear wall system which is
one of the most efficient methods of ensuring the
lateral stability of tall buildings (Norlizian, 2007). The
Accepted for Publication on 20/2/2012.
- 255 -
Behavior of Shear
Table 1. Various ratios for varying % opening and H/B of both types of plane shear wall
Maximum deflection
ratio
Maximum flexural
stress ratio
Maximum shear
stress ratio
Type of
shear
wall
H/B=3.75
H/B=6
H/B=3.75
H/B=6
H/B=3.75
H/B=6
90% base
opening
Type-1
4.7
2.4
20
14.4
51.5
37
Type-2
366
253
86
92
215
233
80% base
opening
Type-1
2.2
1.7
7.6
4.6
15.2
5.6
Type-2
45
30
20
22
100
116
60% base
opening
Type-1
1.16
1.1
2.3
7.3
5.5
Type-2
5.2
5.1
5.4
17.6
20.6
40% base
opening
Type-1
1.1
1.06
1.85
1.2
5.1
3.8
20% base
opening
Type-1
1.03
1.0
1.4
1.2
2.8
1.6
% Base
opening
Table 2. Deflection and stress ratios for varying % of opening and storey height for
both types of box shear wall
% base
opening
Type of
box shear
wall
80% base
opening
60% base
opening
40% base
opening
Type-1
Type-2
6
storeys
1.225
1.062
10
storeys
1.061
1.050
15
storeys
1.027
1.057
6
storeys
2.1
1.7
10
storeys
2.2
1.8
15
storeys
2.6
1.9
6
storeys
1.5
1.0
10
storeys
1.2
1.0
15
storeys
1.2
1.0
Type-1
Type-2
Type-1
1.080
1.036
1.036
1.025
1.034
1.012
1.010
1.034
1.005
1.5
1.4
1.3
1.8
1.6
1.5
2.6
1.6
2.6
1.3
1.0
1.3
1.2
1.0
1.2
1.2
1.0
1.2
Type-2
1.019
1.018
1.018
1.1
1.3
1.3
1.0
1.0
1.0
- 256 -
Table 3. Study of parameter ratios for varying % base opening of shear wall (H/B=3.75) for
both 1st and 2nd alternative measures
% of base
opening
Maximum
deflection
ratio
Maximum
flexural
stress ratio
Maximum
shear
stress ratio
1.16
2.11
5.34
60% base
opening
0.88
0.89
0.74
0.90
4.27
2.18
40% base
opening
20% base
opening
st
1.05
1.44
3.54
st
0.90
0.87
3.14
nd
0.87
1.01
0.88
1.18
1.57
2.25
0.94
0.92
2.10
0.90
0.86
1.33
nd
- 257 -
Behavior of Shear
b/2
b/2
- 258 -
B
B
Y
X
Shear wall
B
Shear wall
Figure 3: Effect of opening size on maximum deflection ratios for varying ratios of H/B
3.0 m above the base. At a particular height of shear
wall and with a particular percentage of base opening,
the deflection ratio is the ratio between the deflection
- 259 -
Behavior of Shear
Shear wall
Shear wall
Shear wall
Shear wall
Figure 4: Effect of opening size on (a) mid deflection ratios (b) deflection(at 3 m height) ratios for
varying ratios of H/B
Results of Parametric Study
Plane Shear Wall with Base Opening
Deflection ratios at three different floor levels for
varying opening size (b/B), are presented in Figure 3
and Figure 4. It is observed that deflection increases
with the increase of base opening. However, the rate of
increase of deflection is very low up to 60% (i.e.,
b/B=0.60) base opening. Beyond 60% opening, wall
stiffness decreases significantly. Maximum deflection
of shear wall (Type-1) with 90% base opening and
H/B= 1 is 67 times than that of solid shear wall,
whereas in the case of shear wall with 60% base
opening it is only 3 times. The influence of height of
shear wall (i.e., H/B) in its stiffness is also observed
here. For all values of H/B with 0 to 60% base opening,
the effect is insignificant, but for base opening higher
- 260 -
Shear wall
Shear wall
Type-1 (T-1)
B
H
H
Shear wall
Shear wall
Type-2 (T-2)
Figure 5: Effect of opening size on (a) maximum shear stress ratios (b)maximum flexural stress ratios for
varying ratios of H/B
- 261 -
Behavior of Shear
Figure 7: Effect of opening size on (a) maximum flexural stress ratios (b) maximum shear stress ratios for
box shear wall with varying height of the building
Box Shear Wall with Base Opening
Maximum deflection ratios for varying percentage
of base opening are presented for both types of box
shear wall, in Table 2 and Figure 6. The deflection
ratios reported here are based on the relevant deflection
at the wall rather than the deflection of the frame. It is
observed that the deflection ratio increases with the
increase of percentage base opening. However, the
effect of base opening on deflection is not very
significant (Figure 6). The influence of shear wall
height in its stiffness is also observed here. The
deflection ratios are reported to an accuracy of three
decimal places. For both types of box shear wall, the
ratio decreases with the increasing storey height. For
example, with 80% base opening, the maximum
deflection ratio of a 6 storied Type-1 shear wall is
- 262 -
Type-2 shear wall are nearly 1.0 which means that the
effect of base opening on shear stress is insignificant
for Type-2 shear wall.
flexural stress ratio is 2.6, while it is only 1.6 for Type2. Type-2 box shear wall is stiffer than Type-1 box
shear wall. It is observed that shear stress ratios for
Compensatory
Element
Increased
Thickness
h
h
b
b/4
st
b/4
b/2
nd
- 263 -
Behavior of Shear
Parametric ratios
- 264 -
REFERENCES
ANSYS 5.4 Manual Set. 2000. ANSYS Inc.,
Southpoint, 275 Technology Drive, Canonsburg,
PA15317, USA.
Balkaya, C. and Kalkan, E. 2004. Three-Dimensional
Effects on Openings of Laterally Loaded Pierced
- 265 -
Behavior of Shear
doi:10.1061/(ASCE)0733-9445 (2005)131:1(75).
Marsono, A. K. and Subedi, N. K. 2000. Analysis of
Reinforced Concrete Shear Wall Structures with
Staggered Openings, Part II: Non-linear Finite
Element Analysis (NLFEA). Proc. of the 4th AsianPacific Structural Engineering and Construction
Conference (APSEC2000), Kuala Lumpur, 341-355.
Norlizian, B.W. 2007. Frame Analysis of Reinforced
Concrete Shear Walls with Opening. Thesis (MS).
University of Technology, Malaysia.
Orakcal, K. and Wallance, J.W. 2006. Flexural
Modeling of Reinforced Concrete WallsExperimental Verification. ACI Structural Journal,
103 (2): 196-206.
Orakcal, K., Wallance, J. W. and Conte, J. P. 2004.
Flexural Modeling of Reinforced Concrete WallsModel Attributes. ACI Structural Journal, 101 (5):
688-698.
Park, R. and Paulay, T. 1975. Reinforced Concrete
Structures. New York: John Wiley and Sons, 769.
Paulay, T. 2002. The Displacement Capacity of
Reinforced Concrete Coupled Walls. Journal of
Engineering Structures, 24 (9): 1165-1175.
Wang, J., Sakashita, M., Kono, S. and Tanaka, S. 2010.
Shear Behaviour of Reinforced Concrete Structural
Walls with Eccentric Openings under Cyclic
Loading: Experimental Study. The Structural Design
of Tall and Special Buildings, John Wiley and Sons,
Ltd., doi: 10.1002/tal.639.
- 266 -