Professional Documents
Culture Documents
CLIENTE - CUSTOMER
FIRENZE
COMMESSA - JOB
IMPIANTO - PLAN
QAFCO 5 PROJECT
1102339 - 40
TITOLO - TITLE
Job No.
Doc. ID code
Q5-PT-C900-01004
Q5-SH-T151.32000-022
Job No.
Doc. No.
317300
51-MA-E-32022
Plant
QAFCO 5 PROJECT
A company of Saipem
Category Code:
Acceptance Code:
Rev.
Status
Sh. 1 of 13
00
TAGGING RULE
Instrument to be wired (transmitter, limit switch, ecc)
st
TOTAL SHEET : 13
51.K0701
ITEM
N.
0
REV.
EMESSO - ISSUED
DESCRIZIONE - DESCRIPTION
EA
Nardi G.
Mannucci S.
CONT-CHK'D
APP-APPR'D
PREP'D
SOS9972962
/4
22/12/08
LINGUA-LANG.
PAGINA-SHEET
DATA-DATE
1/2
Il presente documento di propriet NUOVO PIGNONE. A termine di legge ogni diritto riservato.
SOSTITUISCE IL - REPLACES
This document is the property of NUOVO PIGNONE. All rights are reserved according to law.
SOSTITUITO DA - REPLACED BY
ANTISURGE WRITE-UP
for
AMMONIA SYNTHESIS COMPRESSOR
Nuovo Pignone
FIRENZE
INDEX
SECTION 1 : GENERAL DESCRIPTION
1.1 - GENERAL FEATURES
1.2 - SYMBOLS LEGEND
1.3 - ANTISURGE CONTROL LAW
1.4 - ANTISURGE CONTROL ALGORITHM
page 3/4
page 4/5
page 5/6
page. 7/8
page 8/9
page 9/10
page 11/12
page 12/13
51.K0701
ITEM
N.
REV.
SOS9972962
/4
LINGUA-LANG.
PAGINA-SHEET
2 / 3
DESCRIZIONE - DESCRIPTION
Il presente documento di propriet NUOVO PIGNONE. A termine di legge ogni diritto riservato.
SOSTITUISCE IL - REPLACES
This document is the property of NUOVO PIGNONE. All rights are reserved according to law.
SOSTITUITO DA - REPLACED BY
Nuovo Pignone
FIRENZE
SECTION 1
1.1 GENERAL FEATURES
For each compressor speed, its possible to determine, on the plane SUCTION FLOW
COMPRESSION RATIO, a curve that describes all compressor operating points. Each obtained
curve meets its limits on the surge point, corresponding to the maximum polytropic head. All
surge points, defined for different speeds represent the limit line, on the left of this line (called
SURGE LIMIT LINE SLL) the compressor operates in an unstable area.
The purpose of the ANTISURGE CONTROL SYSTEM is to avoid that the operating point
A reaches the SLL. To achieve this objective, its defined, on the right of the SLL, a
protection line where (point B) the control system will operate opening the antisurge valve.
This line is called SURGE CONTROL LINE (SCL). The opening of the antisurge valve
increases the suction flow moving the operating point along the speed characteristic curve, from
the critical condition to the stable operating area (fig. 1).
Fig. 1
51.K0701
ITEM
N.
REV.
SOS9972962
/4
LINGUA-LANG.
PAGINA-SHEET
3 / 4
DESCRIZIONE - DESCRIPTION
Il presente documento di propriet NUOVO PIGNONE. A termine di legge ogni diritto riservato.
SOSTITUISCE IL - REPLACES
This document is the property of NUOVO PIGNONE. All rights are reserved according to law.
SOSTITUITO DA - REPLACED BY
Nuovo Pignone
FIRENZE
compressor speed
K1,K2,K3,K4
constants
QS
volumetric flow
Hp
polytropic head
Pd
discharge pressure
Ps
suction pressure
compressibility factor
gas constant
hs
PSD
deviation margin
SLL
SCL
PV
51.K0701
ITEM
N.
REV.
SOS9972962
/4
LINGUA-LANG.
PAGINA-SHEET
4 / 5
DESCRIZIONE - DESCRIPTION
Il presente documento di propriet NUOVO PIGNONE. A termine di legge ogni diritto riservato.
SOSTITUISCE IL - REPLACES
This document is the property of NUOVO PIGNONE. All rights are reserved according to law.
SOSTITUITO DA - REPLACED BY
Nuovo Pignone
FIRENZE
Qs
(3) Hp K 2
K1
where
K2
K 1
K 3 = constant .So :
Hp K 3 Q s 2
being
n 1
n
Pd
n
(4) Hp ZRT
1
n 1 Ps
n Pd
ZRT
n 1 Ps
(5)
n 1
1 K 3 Q s 2
If Qs is measured through a flow element installed at the compressor suction, we can express it
related to the measured p
Qs
(6)
since s
Ps
the (6) becomes
RZT
hs
s
Qs
hs * RZT
(7)
Ps
n Pd
so we can describe the (5) as : ZRT
n 1 Ps
n 1
h ZRT
1 K 3 2 s
Ps
51.K0701
ITEM
N.
REV.
SOS9972962
/4
LINGUA-LANG.
PAGINA-SHEET
5 / 6
DESCRIZIONE - DESCRIPTION
Il presente documento di propriet NUOVO PIGNONE. A termine di legge ogni diritto riservato.
SOSTITUISCE IL - REPLACES
This document is the property of NUOVO PIGNONE. All rights are reserved according to law.
SOSTITUITO DA - REPLACED BY
Nuovo Pignone
FIRENZE
Simplifying ZRT in the expression, the obtained equation, that represents all the surge points in
function of the orifice p; we can demonstrate how the surge phenomenon is not influenced by
the gas condition and composition.
n Pd
hs
K 3 * 2 n 1 Ps
n 1
Ps
(8)
Moreover for small compression ratios, using series expansion at first order m 1 m 1
we have:
n Pd
n 1 Ps
hs
n 1
P
1 d 1 ;
Ps
Pd
K 3 * Ps
Ps
where
1
K3 * 2
hs Ps * K 4 * d 1
Ps
(9)
K 4 is a constant
hs
1
Pd
1 * Ps * K 4
Ps
The equation (9) defines the SLL shape, on the plane of compression ratio () versus flow (Q),
represented by a parabola which has the minimum located in = 1 and Q = 0 , Fig 1a .
SLL
SCL
SLL
SCL
Fig.1a
Fig.1b
The fig. 1a represents a theoretical performance characteristic for a single stage compressor (one
impeller only), while the Fig. 1b represents a typical characteristic for a multistage compressor.
As we can see in the latter conditions the antisurge control line can not be realized utilizing a
parabola without cutting a large zone of compressor operability .
51.K0701
ITEM
N.
REV.
SOS9972962
/4
LINGUA-LANG.
PAGINA-SHEET
6 / 7
DESCRIZIONE - DESCRIPTION
Il presente documento di propriet NUOVO PIGNONE. A termine di legge ogni diritto riservato.
SOSTITUISCE IL - REPLACES
This document is the property of NUOVO PIGNONE. All rights are reserved according to law.
SOSTITUITO DA - REPLACED BY
Nuovo Pignone
FIRENZE
In order to avoid this inconvenient, the Surge Control Line is calculated by a eight break lines
P Ps
that permits to realize the SLL and consequently the relevant SCL.
function generator f d
Ps
The SCL will be positioned at a pre-set percentage margin (K), to the right of the first one .
SLL
SCL
Psd
Ps
P Ps
f d
Ps
K2
Where :
ITEM
N.
REV.
SOS9972962
/4
LINGUA-LANG.
PAGINA-SHEET
7 / 8
DESCRIZIONE - DESCRIPTION
Il presente documento di propriet NUOVO PIGNONE. A termine di legge ogni diritto riservato.
SOSTITUISCE IL - REPLACES
This document is the property of NUOVO PIGNONE. All rights are reserved according to law.
SOSTITUITO DA - REPLACED BY
Nuovo Pignone
FIRENZE
SECTION 2
2.1 ANTISURGE CONTROLLER
The picture 2 shows the antisurge system diagram. With reference to the picture, the instruments
range will be :
INSTRUMENT
PT-278
PT-280
FT-258
MEASURED VARIABLE
SUCTION PRESSURE
DISCHARGE PRESSURE
FLOW ELEMENT DIFFER. PRESSURE
RANGES
0 6 Mpa(g)
0 25 Mpa(g)
0 25 Kpa
Fig. 2
51.K0701
ITEM
N.
REV.
SOS9972962
/4
LINGUA-LANG.
PAGINA-SHEET
8 / 9
DESCRIZIONE - DESCRIPTION
Il presente documento di propriet NUOVO PIGNONE. A termine di legge ogni diritto riservato.
SOSTITUISCE IL - REPLACES
This document is the property of NUOVO PIGNONE. All rights are reserved according to law.
SOSTITUITO DA - REPLACED BY
Nuovo Pignone
FIRENZE
FLOW ELEMENT
Volumetric flow
Differential pressure
Molecular weight
Absolute suction pressure
Absolute suct. temperature
Compressibility
FE calc.
values
FE values @
refer.conditions
Flow
Margin %
15642.0
250.00
8.702
31.40
290.2
1.012
15643.3
250.00
8.702
31.40
290.2
1.012
10
bara
K
hs_safe
81.45
PSD
98.55
Antisurge curve
10.0
9.0
8.0
(Pd/Ps)-1
7.0
6.0
5.0
4.0
3.0
hs(SLL)
hs(SCL)
N
R
2.0
1.0
140
120
100
80
60
40
20
0.0
Fig. 3
51.K0701
ITEM
N.
REV.
SOS9972962
/4
LINGUA-LANG.
PAGINA-SHEET
9 / 10
DESCRIZIONE - DESCRIPTION
Il presente documento di propriet NUOVO PIGNONE. A termine di legge ogni diritto riservato.
SOSTITUISCE IL - REPLACES
This document is the property of NUOVO PIGNONE. All rights are reserved according to law.
SOSTITUITO DA - REPLACED BY
Nuovo Pignone
FIRENZE
Qsurge
Diff . press.span
hs ( sll )
Vol. flow.span @ ref .cond .
Flow.mar. 100
hs ( scl ) hs ( sll )
100
51.K0701
ITEM
N.
REV.
SOS9972962
/4
LINGUA-LANG.
PAGINA-SHEET
10 / 11
DESCRIZIONE - DESCRIPTION
Il presente documento di propriet NUOVO PIGNONE. A termine di legge ogni diritto riservato.
SOSTITUISCE IL - REPLACES
This document is the property of NUOVO PIGNONE. All rights are reserved according to law.
SOSTITUITO DA - REPLACED BY
Nuovo Pignone
FIRENZE
SECTION 3
3.1 ANTISURGE CONTROLLER OPERATION
Controller Operation; Cascade PI control by direct action with the following signals:
Inputs :
a) Suction pressure (Ps)
b) Discharge Pressure (Pd)
c) Differential pressure on suction orifice Suction Flow (hs)
d) HIC Antisurge valve manual opening/closing command.
e) Safety Protection/Correction disabling.
f) External protection (EP)
g) L4AS (min. control speed) antisurge controller enable / disable.
h) External Transient.
i) PURGE command.
j) Zero Speed.
k) Solenoid Reset push button.
l) External override controller.
Outputs :
a) Antisurge valve control signal (ASVC)
b) Solenoid Valve Command.
c) Transmitter Failure indication.
d) Safety Protection/Correction disabling indication.
e) A/S Solenoid Valve de-energize indication.
f) A/S Controller Manual Control indication.
g) Feedback to external override controller.
51.K0701
ITEM
N.
REV.
SOS9972962
/4
LINGUA-LANG.
PAGINA-SHEET
11 / 12
DESCRIZIONE - DESCRIPTION
Il presente documento di propriet NUOVO PIGNONE. A termine di legge ogni diritto riservato.
SOSTITUISCE IL - REPLACES
This document is the property of NUOVO PIGNONE. All rights are reserved according to law.
SOSTITUITO DA - REPLACED BY
Nuovo Pignone
FIRENZE
Pressure
Ratio
Compressor
Operating
Point
Suction Flow
b) Transient Absorption :
If the measure decreases very fast, to anticipate the controller response, the controller set point is
incremented by a fixed value.
When the condition resets, the set point return to the previous value following a pre-set ramp .
51.K0701
ITEM
N.
REV.
SOS9972962
/4
LINGUA-LANG.
PAGINA-SHEET
12 / 13
DESCRIZIONE - DESCRIPTION
Il presente documento di propriet NUOVO PIGNONE. A termine di legge ogni diritto riservato.
SOSTITUISCE IL - REPLACES
This document is the property of NUOVO PIGNONE. All rights are reserved according to law.
SOSTITUITO DA - REPLACED BY
Nuovo Pignone
FIRENZE
c) Safety Correction :
When the measure is lower of the Safety Correction Line (SLL + 5% in term of flow) the
antisurge controller output decreases following fixed steps in fixed time gaps until the measure
goes back to a value higher than Safety Correction Line.
d) Safety Protection :
When the measure is lower of the Safety Protection Line (SLL + 2% in term of flow) the
antisurge controller output decreases following quick opening ramp until the measure goes back
to the right of the Safety Correction Line .
h) Controller Enabling/Disabling
When the controller is disabled the antisurge valve is forced to open position. Controller is
generally enabled when min. control speed is reached.
i) Purge function :
Allows the complete closing of the antisurge valve when the compressor is stopped .
51.K0701
ITEM
N.
REV.
SOS9972962
/4
LINGUA-LANG.
PAGINA-SHEET
13 / 13
DESCRIZIONE - DESCRIPTION
Il presente documento di propriet NUOVO PIGNONE. A termine di legge ogni diritto riservato.
SOSTITUISCE IL - REPLACES
This document is the property of NUOVO PIGNONE. All rights are reserved according to law.
SOSTITUITO DA - REPLACED BY