e) Relays Signal lamps g) Push buttons b) Alarms i) Interface to DCS Note: (a) Main control panel includes the function of power supply and sequential control of each door. (b) Control panel should supply all power and control signal for dumping gate and hydraulic unit. (©) Interlock for preventing pressure below atmosphere within the refuse bunker shall be provided. (@ Base frame(height is 300mm) is needed.(opening of cable is bottom of panel) 2) Local control panel (1) Quantity 1 BS sets (2) Location : beside each door (3) Type Dust-proof and wall-hanger type (4) Push button : open/close/stop and emergency stop Note? Wiring termination for loop coil sensor shall be provided in the local control panel. 3) Interlock panel (1) Quantity + set (2) Location + Crane control room (3) Type : Dust-proof and self-standing type (desk type) (@) Push button + Prohibition 8 sets Permission Bots Note: Inhibition system of door opening from crane operation room. 4) Red/Green lamps () Quantity + 8 sets (2) Type + Dust-proof wall-hanger type (3) Size £200 mm in diameter 8) Loop oil (D Quantity 8 sets (2) Type : Mounted under the platform Note: Complete amplifiers to adjust gain and sensitivity 9