Frequently Asked Questions (FAQ) and Answers On SF Nr. Question Answer
Frequently Asked Questions (FAQ) and Answers On SF Nr. Question Answer
Question
Answer
What is SF6?
1 / 11
Nr.
7
Question
Why is SF6 used in electric power
equipment?
Answer
Because of its outstanding electrical, physical and
chemical properties enabling significant benefits for the
electricity supply network:
it insulates 2.5 times better than air (N2),
over 100 times better arc quenching capability than
air (N2),
better heat dissipation than air;
In addition to this, LCA studies have proven that the use
of SF6 technology in the electrical distribution switchgear
equipment results in lower overall direct and indirect
environmental impacts compared to air-insulated
switchyards [2]
2 / 11
Nr.
Question
Answer
In contrast to air insulation, whose insulating capacity
reduces with increasing altitude, SF6-insulated
switchgear retains its full insulating capacity regardless
of height above sea level. So larger and more costly
special designs, or equipment with higher insulation
ratings - and therefore more costly - are avoided
Small space requirement
Due to the high dielectric strength of the gas, the
switchgear is compact with space requirements
minimised.
The excellent safety and low space requirement of
SF6 switchgear allows it to be sited directly in
conurbations and close to load centres, such as city
centres, industrial manufacturing plants and commercial
areas.
Therefore, this fulfils one of the basic essentials of
power distribution, namely that substations should be
placed as close as possible to load centres in order to
keep transmission losses to a minimum, to conserve
resources and to minimise costs.
Major savings in building, land and transport costs
can be achieved throughout the whole process chain.
In several cases SF6 switchgear is the only possible
solution: for wind power plants (offshore), in caverns, for
large generator circuit-breakers, and for extensions of
existing installations.
This often allows existing buildings use to be
extended where switchgear replacement or extension to
meet load growth is needed.
Excellent economical and ecological features
3 / 11
Nr.
Question
Answer
10
11
12
4 / 11
Nr.
Question
Answer
pressure systems. Low pressure and small size result in
little gas quantities of only some kg. The leakage rate is
extremely low, less than 0.1 % per year. HV switchgear
(< 52 kV) use closed pressure systems with leakage
rates less than 0.5 %, which is the maximum permitted
by the relevant IEC standards. The operating pressure of
HV equipment is approx. 5 times higher compared to MV
13
14
15
16
17
5 / 11
Nr.
Question
Answer
276, 2005 Practical SF6 Handling Instructions [11],
Leakage in service: IEC 60376 (new SF6, technical
graded SF6), IEC 60480 (used SF6), CIGRE 2002 (SF6
in the Electric Industry) [10]
Repair work and maintenance: IEC 61634 (handling
SF6), CIGRE 1991 (handling of SF6), CIGRE report 276,
2005 Practical SF6 Handling Instructions [11], CIGRE
report 163, 2000 (Guide for SF6 gas mixtures)
End of life, recycling: IEC 61634, CIGRE 2003 (SF6
recycling guide) [15]
18
19
20
21
22
4
5
6 / 11
Nr.
Question
Answer
23
24
25
26
27
28
29
How much SF6 (quantified in kg) can This depends on the filling quantity, which depends on the
escape due to "normal" leakage?
rating and design of the equipment (volume and
pressure). For HV switchgear the emission factor ranges
from about 0.1% per year to 0,5% (0,5% per year is the
maximum acceptable leakage rate according to IEC
62271-203)
For sealed for life MV equipment a range below 0,1 % per
year is common. For example, a 3 kg filling quantity
(RMU) results in a calculated loss of 3 g per year.
30
7 / 11
Nr.
Question
Answer
kept lower than 1000 l/l [4]. This is the value accepted for
a full time (8 h/day, 5 day/week) work schedule. This
value is not related to toxicity, but an established limit for
all non-toxic gases which are not normally present in the
atmosphere.
Therefore, this limit does not mean that higher SF6
concentrations pose any toxic hazard. According to
Clause 7.1 of IEC 60480: "In principle, a mixture of 20% of
oxygen and 80% SF6 can be inhaled without adverse
effect. Concentrations above 20% would cause
suffocation due to lack of oxygen.
31
32
33
34
Does a (passive or active) ventilation Buildings containing SF6-filled indoor equipment should be
system have to be installed in the
provided with ventilation; natural ventilation would
switchgear room or cable basement? normally be adequate to prevent the accumulation of SF6
released due to leakage (see IEC 61634, sub-clause 3.4:
"Safety of personnel" and IEC 61936-1) [12]. Type and
extent of required measures depend upon location of the
room, the accessibility, and the ratio of gas to room
volume.
35
8 / 11
Nr.
Question
Answer
36
37
38
39
40
What do I have to do when I came in See IEC 61634 [8], Annex E: "General safety
contact with decomposed SF6?
recommendations, equipment for personal protection and
first aid". Normally only trained and qualified personnel
should deal with this and hence be aware of the
necessary precautions and actions.
41
42
43
44
What has to be observed for cleaning See IEC 61634 [8], sub-clause 5.3/5.3.3 "Abnormal
of the switchgear room after an
release due to internal fault"/"Indoor installations", and
internal fault with emission of
national requirements.
decomposed gas?
9 / 11
Nr.
45
Question
Answer
10 / 11
[1]
[2]
Solvay Germany, 1999: Urban power supply using SF6 technology, Life cycle assessment on
behalf of ABB, PreussenElektra Netz, RWE Energie, Siemens, Solvay Fluor und Derivate
Solvay et al., 2003, - Solvay Management Support: : SF6-GIS technology for energy
distribution medium voltage, Life cycle assessment on behalf of ABB, AREVA T&D,
EnBW Regional, e.on Hanse, RWE, Siemens and Solvay Fluor und Derivate
[3]
SF6 and the global atmosphere: ELECTRA No. 164, February 1996, page 120-131
[4]
[5]
IEC 62271-1 / IEC 60694 Common specifications for high-voltage switchgear and controlgear
standards
[6]
[7]
IEC 60480 Guidelines for the checking and treatment of sulphur hexafluoride (SF6) taken from
electrical equipment and specification for its re-use
[8]
[9]
ECOFYS, Sina Wartmann, Dr. Jochen Harnisch, June 2005, Reductions of SF6 Emissions
from High and Medium Voltage Equipment in Europe
[10]
SF6 in the Electric Industry, Status 2000, (CIGRE Study Committee No.23) P. O'Connel et al,
ELECTRA No. 200, February 2002, pp 16-25
[11]
CIGRE-report 276, 2005: Guide for the preparation of customised "Practical SF6 Handling
Instructions". A short version appears in August 2005 in ELECTRA.
[12]
[13]
Handling of SF6 and its decomposition products in gas insulated switchgear (GIS), CIGRE
Working Group 23-03, ELECTRA No. 136, June 1991, p. 69
[15]
[16]
Solvay, VIK, VDN, ZVEI: Selbstverpflichtung der SF6-Produzenten, Hersteller und Betreiber
von elektrischen Betriebsmitteln > 1kV zur elektrischen Energiebertragung und verteilung in
der Bundesrepublik Deutschland zu SF6 als Isolier- und Lschgas, Mai 2005, www.sf6energietechnik.de