You are on page 1of 84

507

6. Determining conductor crosssectional areas

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

508

6. DETERMINING CONDUCTOR CROSS-SECTIONAL AREAS


Owing to the respective characteristics of LV and MV conductors, they have been dealt with in
separate paragraphs.

6.1.

Determining conductor cross-sectional areas and choosing protective


devices in low voltage

n definition of terms relating to low voltage wiring systems


(Insulated) cable
Assembly comprising:
- one or more insulated conductors
- their eventual individual screening
- any eventual assembly protection
- any eventual protective shielding
It may also comprise one or several bare conductors.

Multi-core cable
Cable comprising more than one conductor, which may eventually include bare conductors.
Note: the term three-core cable is used to designate the cable making up the phases of a three-phase
system.

Single-core cable
Cable comprising a single insulated conductor.
Note: the term single-core cable is especially used to designate a cable making up one of the phases of a
three-phase system.

Wiring system
Assembly made up of one or more electric conductors and the devices ensuring their fixation and, if
necessary, their mechanical protection.

Cable channel
Ventilated or enclosed duct located above or in the ground, having dimensions preventing persons from
moving around inside it but allowing access to the cables over their entire length during and after
installation.
Note: a cable channel may or may not form part of the building construction.

Cable tray
Holder made up of a base and sides but no cover.
Note: A cable tray may be perforated or unperforated.

Electrical circuit (of an installation)


All the electrical equipment of the installation fed from the same source and protected against
overcurrents by the same protective device(s).

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

509

(Insulated) conductor
Assembly comprising the conductor, its insulating envelope and eventual screens.

(Circular) conduit
Enclosed envelope, having a circular cross-section, designed for the installation or the replacement of
insulated conductors or cables by capstan, in electrical installations.

Ducting
Assembly of closed envelopes having a non circular cross-sectional area, designed for the installation or
the replacement of insulated conductors or cables by capstan, in electrical installations.

Brackets
Horizontal cable supports fixed at one of their ends, arranged from point to point and on which the cables
rest.

Design current of a circuit


Current to be carried in a circuit in normal service

(Continuous) current carrying capacity of a conductor


Maximum value of the current that, in given conditions, can continuously flow in a conductor without its
steady-state operating temperature being higher than the specified value.

Cable ladder
Cable support made up of a series of non-touching elements firmly fixed to main vertical rods.

Sleeve (or tube)


Element surrounding wiring and providing it with extra protection in building passages (walls, partitions,
floor, ceiling) or in buried passages.

Sheath
Enclosure located above ground level having dimensions preventing persons from moving around inside
it but allowing access to the cables over their entire length. A sheath may or may not be built into the
masonry.

Trough
Assembly of envelopes closed by a cover and ensuring mechanical protection of insulated conductors or
cables not installed or removed by a capstan and which allow other electrical equipment to be added .

Building void
Space in a structure or building parts which is only accessible at certain places.
Note:
- spaces in walls, supported floors, ceilings and certain types of window or door frames and
jamb linings are examples of building voids.
- specially built building voids are also called "ducts".

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

510

6.1.1.

Method principle

In compliance with the recommendations of IEC 364-4-43, the cross-sectional area of wiring
systems and the protective device must be chosen to meet several conditions necessary for
the security of the installation.
The wiring system must:
- carry the maximum design current and its normal transient peaks
- not generate voltage drops above the allowed values.

The protective device must:


- protect the wiring system against any overcurrents up to the short-circuit current
- ensure the protection of persons against indirect contact.
The logigram in figure 6-1 sums up the principle of the method which may be described by the
following stages:

1st stage:
- using the load power, the maximum design current I B is calculated and the rated current
I n of the protective device is deduced from this
- the maximum short-circuit current Isc at the origin of the circuit is calculated and the
breaking capacity of the protective device is deduced from this.

2nd stage:
- depending on the installation conditions (installation method, ambient temperature, etc.),
the overall correction factor f is determined
- the suitable conductor cross-sectional area is chosen in relation to I n and f .

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

511

3rd stage:
- the maximum voltage drop is checked
- the thermal withstand of the conductors in the event of a short circuit is checked
- for TN and IT systems, the maximum length relating to the protection of persons against
indirect contact is checked.
The conductor cross-sectional area meeting all these conditions is then chosen.
Note:

an economic cross-sectional area larger than the cross-sectional area determined above may
be chosen if necessary (see 6.3).

apparent power
to be carried

upstream or
downstream
network

short-circuit
power at the origin
of the circuit

short-circuit
current

design current

I sc

IB
rated current of
protective device

protective device
breaking capacity

In
choice of
protective device

choice of
protective device

installation
conditions

wiring system conductor


cross-sectional area

check of thermal
withstand in case
of short-circuit
IT or TN earthing system

maximum voltage
drop check

maximum wiring
system length chek

TT earthing
system
conductor crosssectional area
determination

confirmation of the choice of wiring system


cross-sectional area and its electrical protection

economic
cross-sectional
area possibly chosen

Figure 6-1: wiring system cross-sectional area and protective device choice logigram
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

512

6.1.2.

Determining the maximum design current

The maximum design current ( I B ) is defined according to the type of installation fed by the
wiring system.
In the case of individual power supply to a device, the current I B will be equal to the rated
current of the device being fed. On the other hand, if the wiring system feeds several devices,
the current I B will be equal to the sum of currents absorbed, taking into account the
installation utilisation and coincidence factors.
In the case of motor starting or cyclical operating conditions of loads (spot welding station,
see 3.4.2), current inrushes must be taken into account when their thermal effects are
cumulated.
Some installations are subject to future extensions. The current corresponding to this
extension will be added to the existing value.
In direct current:

I=

In alternating current: I =
S
U

P power consumed (in W )

U duty voltage (in V )


S
S
in three-phase.
in single-phase and I =
U
U 3

: apparent power consumed (VA)


: . voltage between the two conductors for a single-phase power supply
. phase-to-phase voltage for a three-phase power supply

When high harmonic currents circulate in the conductor, they must be taken into account. In
order to choose the cross-sectional area, the following must therefore be taken:

I r .m.s. =
I p2

p =1

(see 8)

I1 : current value at 50 Hz (or 60 Hz)


I p : value of harmonic current of order p
For example, for a speed variator

Ir .m.s.
1.7
I1

When there are compensation capacitors downstream of the wiring system, the design current
is determined as follows:
- assuming that compensation is in operation: in case of failure of the capacitors, the wiring
system is placed out of service
- assuming that compensation is out of service; in case of failure of the capacitors, the
conductor cross-sectional area is sufficient and availability is thus improved.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

513

n factor taking into account the power factor and efficiency:

The apparent power of a load is:


S=

Fp

in kVA

P : active power in kW
: efficiency
Fp : power factor
We define the coefficient: a =

1
Fp

When a current stripped of harmonics flows through the conductor, Fp = cos .

n load utilisation factor: b


In an industrial installation, it is assumed that loads will never be used at their full power level.
A utilisation factor ( b ) is therefore introduced which generally varies from 0.3 to 1.

Without knowing the accurate values, we may take:


-

b = 0.75

for motors

b =1

for lighting and heating

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

514

n coincidence factor:

In an industrial installation, the loads (of a workshop, for example) fed by the same wiring
system do not operate simultaneously in all cases. To take this phenomenon, which is linked to
the operating conditions of the installation, into account, the coincidence factor is applied to
the sum of the load powers in conductor sizing.
In the absence of precise indications resulting from experience of standard installations, the
values of tables 6-1 et 6-2 may be applied:
Use

Coincidence factor c

Lighting

Lighting and air conditioning

Power outlets

0.1 to 0.2 (for a number > 20)

Table 6-1: coincidence factor for an administrative building

Number of circuits having


similar nominal currents

Coincidence factor

2 and 3

0.9

4 and 5

0.8

5 to 9

0.7

10 and more

0.6

Table 6-2: coincidence factor for industrial distribution switchboards

n factor taking into account possible future extensions: d


The value of factor
installation.

must be estimated according to the foreseeable extensions of the

In the absence of precise indications, the value 1.2 is often used.

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

515

n power conversion factor in current:

The power conversion factor in current is:


-

e = 8 in single-phase 127 V
e = 2.5 in three-phase 230 V

e = 4.35 in single-phase 230 V


e = 1.4 in three-phase 400 V

n maximum design current


The maximum design current is thus:
IB = P a b c d e
P

: active power in kW

6.1.3.

Choosing the protective device

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

516

n general rule
In compliance with IEC 364, a protective device (circuit-breaker or fuse) correctly fulfils its
function if the conditions outlined below are met.

o nominal or setting current

This must be between the design current and the current carrying capacity I a of the wiring
system:
I B I n I a , which corresponds to zone a in figure 6.2.

o conventional tripping current

This must meet the following relation:


I2 1.45 I a , which corresponds to zone b in figure 6.2.

case of circuit-breakers
- For domestic circuit-breakers, standard IEC 898 specifies:
I2 = 1.45 In
- For industrial circuit-breakers, standard IEC 947-2 specifies:
I2 = 1.30 I set
we thus have I2 1.45 I n (or I set )
while

I n I a (above condition)

The condition I2 1.45 I a (zone b ) is thus automatically met.

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

517

case of fuses
Standard IEC 269-1 specifies that I 2 is the current which ensures that the fuse fuses in the
conventional time (1 h or 2 h); I 2 is referred to as the conventional fusing current (see 6.3.1
of the Protection guide).
I 2 = k2 I n

where k2 = 1.6 to 1.9

depending on the fuses

Let us define the coefficient k3 such that:


k3 =

k2
1.45

Thus, the condition I2 1.45 I a is met if:


I
In a
k3
For gG fuses:
-

I n 10 A
10 A < I n 25 A
I n > 25 A

k3 = 1.31
k3 = 1.21
k3 = 1.10

o breaking capacity

This must be higher than the three-phase maximum short-circuit current

( Isc 3 )

at its

installation point:

Breaking capacity Isc 3 , which corresponds to zone c in figure 6.2.

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

518

o associating protective devices

The use of a protective device having a breaking capacity below the short-circuit current at the
point where it is installed is permitted by standard IEC 364 under the following conditions:
- there is another device upstream having at least the necessary breaking capacity
- the energy that the device placed upstream lets through is lower than the energy that the
downstream device and wiring systems protected by these devices can withstand without
being damaged.
This possibility is implemented:
.

in circuit-breaker/fuse associations

in the cascading technique which uses the high current limitation capacity of certain
circuit-breakers (e.g. the Compact).

The possible associations resulting from actual tests performed in a laboratory are given in
manufacturer catalogues.
6.1.4.

Current-carrying capacity of wiring systems

This is the maximum current that the wiring system can continuously carry without this being
prejudicial to its lifetime.
To determine this current, it is necessary to carry out the following:
- using tables 6-3 to 6-5, define the installation method, its associated selection number and
letter, and correction factors to be applied
- using the installation conditions, the correction factor values which must be applied are
determined (see tables 6-6 to 6-15)
- calculate the overall correction factor f equal to the product of the correction factors
- using table 6-16 for selection letters B, C, E, F and table 6-17 for selection letter D, the
maximum current
I 0 that the wiring system can carry under standard conditions
( f0 to f10 = 1 ) is determined
- calculate the maximum current that the wiring system can carry in relation to its installation
conditions: I a = f I 0 .

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

519

n installation methods
Tables 6-3 to 6-5 give the main installation methods used in industrial networks.
For each installation method, the following is given:
- its associated selection number and letter
- the correction factors to be applied.
Factor f 0 corresponds to the installation method; factors f1 to f10 are explained below
(see tables 6-6 to 6-15).
Example

Description

Selection

Correction factors

letter

f0

to be applied

11

f1

f4

f5

11A

0.95

f1

f4

f5

12

f1

f4

f5

Single or multi-core cables with or


without armour

- fixed on a wall

- fixed to a ceiling

- on unperforated trays

cables
multi-core

singlecore

- on perforated trays run


horizontally or vertically

13

f1

f4

f5

- on brackets

14

f1

f4

f5

- on ladders

16

f1

f4

f5

Table 6-3: installation methods for selection letters C, E and F

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

520

Example

Description

Single or multi-core cables in


building voids

Single or multi-core cables in


conduits in building voids

Selection

Correction factors

letter

f0

21

0.95

f1

f4

f5

--

22A

0.865

f1

f4

f5

f6

23A

0.865

f1

f4

f5

f6

24A

0.865

f1

f4

f5

f7

25

0.95

f1

f4

f5

--

31A

0.9

f1

f4

f5

--

32A

to be applied

Single or multi-core cables in


ducting in building voids

Single or multi-core cables in


ducting built into the masonry

Single or multi-core
conductors :
- in false ceilings

- in suspended ceilings
Single or multi-core cables in
troughs fixed to walls:

- run horizontally

- run vertically

0.9

f1

f4

f5

--

Table 6-4: installation methods for selection letter B


Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

521

Example

Description

Selection

Correction factors

letter

f0

to be applied

Single or multi-core cables in


troughs built into floors

33A

0.9

f1

f4

f5

--

Single or multi-core cables in


suspended troughs

34A

0.9

f1

f4

f5

--

Multi-core cables in enclosed


channels run horizontally or
vertically

41

0.95

f1

f4

f5

--

Single or multi-core cables in


open or ventilated channels

43

f1

f4

f5

--

Table 6-4 (cont.): installation methods for selection letter B

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

522

Example

Description

Selection

Correction factors

letter

f0

to be applied

Single or multi-core cables in


conduits or in buried ducting

61

0.8

f2

f3

f8

f9

Single or multi-core cables


buried without any extra
mechanical protection

62

f2

f3

f10

--

Single or multi-core cables


buried with extra mechanical
protection

63

f2

f3

f10

--

Table 6-5: installation methods for selection letter D

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

523

n correction factors for ambient temperatures other than 30 C (wiring systems above
ground): f1
When electrical wiring systems are built into walls having heating elements, it is generally
necessary to reduce current-carrying capacities by applying the reduction factors in table 6-6.
This supposes that the distribution of temperatures inside the heated walls in contact with the
electrical wiring system is known.
When the air temperature is other than 30 C, the correction coefficient to be applied is given
in the formula:
f1 =

p 0
p 30o

p : maximum temperature permitted by the insulating material under steady-state conditions, C


0 : air temperature, C
The value of f1 is given in table 6-6 for different values of p and 0 .
Insulation
Ambient
temperatures (C)

PVC

XLPE and EPR

Elastomers
(rubber)
p = 60 C

p = 70 C

p = 90 C

10
15
20
25
35
40
45
50
55
60
65
70
75
80
85
90
95

1.29
1.22
1.15
1.07
0.93
0.82
0.71
0.58
-

1.22
1.17
1.12
1.06
0.94
0.87
0.79
0.71
0.61
0.50
-

1.15
1.12
1.08
1.04
0.96
0.91
0.87
0.82
0.76
0.71
0.65
0.58
0.50
0.41
-

Table 6-6: correction factors for ambient temperatures other than 30 C


(above ground wiring systems)

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

524

n correction factors for ground temperatures other than 20 C


(buried wiring systems): f 2
When the ground temperature is other than 20C, the correction coefficient to be applied is
given in the formula:
f2 =

p 0
p 20

p : maximum temperature permitted by the insulating material under steady-state conditions, C


0 : ground temperature, C
The value of f 2 is given in table 6-7 for different values of p and 0 .

Ground temperature

0 (C)

Insulation

p = 70 C

PVC

XLPE and EPR


p = 90 C

10

1.10

1.07

15

1.05

1.04

25

0.95

0.96

30

0.89

0.93

35

0.84

0.89

40

0.77

0.85

45

0.71

0.80

50

0.63

0.76

55

0.55

0.71

60

0.45

0.65

65

0.60

70

0.53

75

0.46

80

0.38

Table 6-7: correction factor for ground temperatures other than 20 C


(buried wiring systems)

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

525

n correction factors for buried wiring systems, in relation to the soil thermal
resistivity: f 3
The soil thermal resistivity depends on the type and humidity of the ground. The correction
factor to be applied according to the soil resistivity is given in table 6-8.

Soil
thermal resistivity
K.m/W

Correction
factor

0.40

1.25

underwater installation

marshes

0.50

1.21

very moist soil

sand

0.70

1.13

moist soil

clay

0.85

1.05

normal soil

and

1.00

1.00

dry soil

chalk

1.20
1.50

0.94
0.86

very dry soil

2.00

0.76

and

2.50

0.70

clinker

3.00

0.65

Humidity

Observations
Type of soil

ash

Table 6-8: correction factors for buried wiring systems


in relation to the soil thermal resistivity

n correction factors for a group of several multi-core cables or groups of single-core


cables
The circuits or cables may be:
- touching; the correction factor f 4 must be applied
- arranged in several layers; the correction factor f 5 must be applied
- both touching and arranged in several layers (see fig. 6-3); correction factors
must then be applied.

f 4 and

f5

Figure 6-3: 6 multi-core cables - 2 layers of 3 touching cables

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

526

o touching multi-core or groups of single-core cables: f 4

The factors in table 6-9 are to be applied to homogenous groups of cables, equally loaded, for
the given installation methods.
When the horizontal distance between neighbouring cables is greater than twice their external
diameter, no reduction factor is necessary.
The same correction factors are applicable:
- to groups of two or three single-core cables
- to multi-core cables.
N of installation
methods

Number of touching multi-core cables or


groups of single-core cables
1

12

16

20

21, 22A, 23A, 24A,


25, 31, 31A, 32, 32A,
33A, 34A, 41, 43

1.00

0.80

0.70

0.65

0.60

0.55

0.55

0.50

0.50

0.45

0.40

0.40

11, 12

1.00

0.85

0.79

0.75

0.73

0.72

0.72

0.71

0.70

No extra

11A

1.00

0.85

0.76

0.72

0.69

0.67

0.66

0.65

0.64

reduction

13

1.00

0.88

0.82

0.77

0.75

0.73

0.73

0.72

0.72

factor for

14, 16

1.00

0.88

0.82

0.80

0.80

0.79

0.79

0.78

0.78

more than 9 cables

Table 6-9: correction factors for touching multi-core cables or


groups of single-core cables

o multi-core cables or groups of single-core cables arranged in several layers: f 5

When cables are arranged in several layers, the correction factors in table 6-10 must be
applied.
Number of layers
Correction factors f 5

4 or 5

6 to 8

9 plus

0.80

0.73

0.70

0.68

0.66

table 6-10: correction factors for a group of multi-core cables


or groups of single-core cables arranged in several layers

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

527

n correction factors in relation to the number of conduits in air and their arrangement
(see table 6-11): f 6

Number of

Number of conduits arranged horizontally

conduits arranged
vertically

0.94

0.91

0.88

0.87

0.86

0.92

0.87

0.84

0.81

0.80

0.79

0.85

0.81

0.78

0.76

0.75

0.74

0.82

0.78

0.74

0.73

0.72

0.72

0.80

0.76

0.72

0.71

0.70

0.70

0.79

0.75

0.71

0.70

0.69

0.68

Table 6-11: correction factors in relation to the number of conduits in the air and their arrangement

n correction factors in relation to the number of conduits buried or built into concrete
and their arrangement (see table 6-12): f 7

Number of conduits
arranged vertically

Number of conduits arranged horizontally


1

0.87

0.77

0.72

0.68

0.65

0.87

0.71

0.62

0.57

0.53

0.50

0.77

0.62

0.53

0.48

0.45

0.42

0.72

0.57

0.48

0.44

0.40

0.38

0.68

0.53

0.45

0.40

0.37

0.35

0.65

0.50

0.42

0.38

0.35

0.32

Table 6-12: correction factors in relation to the number of conduits buried or built into concrete and their
arrangement

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

528

n correction factors for non-touching buried conduits run horizontally or vertically on


the basis of one cable or group of 3 single-core cables per conduit
(see table 6-13) : f 8
Distance between conduits (a)
Number of conduits

0.25 m

0.5 m

1.0 m

0.93

0.95

0.97

0.87

0.1

0.95

0.84

0.9

0.94

0.81

0.7

0.93

0.79

0.6

0.93

Table 6-13: correction factors for non-touching buried conduits run horizontally or vertically on the basis
of one cable or group of 3 single-core cables per conduit

The distances between conduits are measured as shown in figure 6-4.

a
multi-core cables

a
single-core cables
Figure 6-4: distance between conduits (a)

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

529

n correction factors in the case of several circuits or cables in the same buried conduit
(see table 6-14): f 9
This is applicable to groups of cables with varying cross-sectional areas but having the same
allowable maximum temperature.
Correction factors

Arrangement of
touching circuits
or cables

Number of circuits or multi-core cables

Installed in a buried
conduit

12

16

20

0.71

0.58

0.5

0.45

0.41

0.38

0.35

0.33

0.29

0.25

0.22

Table 6-14: correction factors in the case of several circuits or cables


in the same buried conduit

n correction factors for a group of several cables installed directly in the ground - single
or multi-core cables arranged horizontally or vertically (see table 6-15): f10
Distance between cables or groups of 3 single-core cables (a)
Number of cables
or circuits

Zero
(touching
cables)

One cable
diameter

0.25 m

0.5 m

1.0 m

0.76

0.79

0.84

0.88

0.92

0.64

0.67

0.74

0.79

0.85

0.57

0.61

0.69

0.75

0.82

0.52

0.56

0.65

0.71

0.80

0.49

0.53

0.60

0.69

0.78

Table 6-15: correction factors for a group of several cables installed directly in the ground single or multi-core cables arranged horizontally or vertically

The distances between cables are measured as shown in figure 6-5.


a
a

a
multi-core cables

single-core cables

Figure 6-5: distance between cables (a)


Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

530

n current-carrying capacities (in amps) of wiring systems in standard installation


conditions for selection letters B, C, E, F
The current carrying capacities given in table 6-16 are valid for simple circuits made up of the
following number of conductors:
Selection letter B:
- two insulated conductors or two single-core cables or one two-core cable
- three insulated conductors or three single-core cables or one three-core cable

Selection letter C:
- two single-core cables or one two-core cable
- three single-core cables or one three-core cable

Selection letters E and F (see fig. 6-6):


- one two-core or three-core cable for letter E
- two or three single-core cables for letter F .
E

Figure 6-6: illustration of installation methods for selection letters E and F

The number of conductors to be considered in a circuit is that of the conductors through which
the current actually flows. When, in a three-phase circuit, the currents are assumed to be
balanced, it is not necessary to take into account the corresponding neutral conductor.
When the current value of the neutral conductor is close to that of the phases, a reduction
factor of 0.84 is to be applied. Such currents may, for example, be due to the presence of third
harmonic currents in the phase conductors (see 6.2).

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

531

Selection letter
B

Insulating material and number of loaded conductors


PVC 3

PVC 2

XLPE 3

PVC 3

PVC 2

PVC 3

XLPE 2
XLPE 3
PVC 2

PVC 3

XLPE 2
XLPE 3

XLPE 2

PVC 2

XLPE3

XLPE2

Copper crosssection (mm)


1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630

15.5
21
28
36
50
68
89
110
134
171
207
239

17.5
24
32
41
57
76
96
119
144
184
223
259
299
341
403
464

18.5
25
34
43
60
80
101
126
153
196
238
276
319
364
430
497

19.5
27
36
48
63
85
112
138
168
213
258
299
344
392
461
530

22
30
40
51
70
94
119
147
179
229
278
322
371
424
500
576
656
749
855

23
31
42
54
75
100
127
158
192
246
298
346
395
450
538
621
754
868
1005

24
33
45
58
80
107
138
169
207
268
328
382
441
506
599
693
825
946
1088

26
36
49
63
86
115
149
185
225
289
352
410
473
542
641
741

16.5
22
28
39
53
70
86
104
133
161
186

18.5
25
32
44
59
73
90
110
140
170
197
227
259
305
351

19.5
26
33
46
61
78
96
117
150
183
212
245
280
330
381

21
28
36
49
66
83
103
125
160
195
226
261
298
352
406

23
31
39
54
73
90
112
136
174
211
245
283
323
382
440
526
610
711

24
32
42
58
77
97
120
146
187
227
263
304
347
409
471
600
694
808

26
35
45
62
84
101
126
154
198
241
280
324
371
439
508
663
770
899

28
38
49
67
91
108
135
164
211
257
300
346
397
470
543

161
200
242
310
377
437
504
575
679
783
940
1083
1254

Aluminium crosssection (mm)


2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630

121
150
184
237
289
337
389
447
530
613
740
856
996

Table 6-16: current carrying capacities (in amps) of wiring systems in standard installation conditions
( f0 to f10 = 1) for selection letters B, C, E, F
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

532

n current-carrying capacities (in amps) of wiring systems in standard installation conditions


for selection letter D (buried wiring systems) (see table 6-17)
The number of conductors to be considered in a circuit is that of the conductors through which
the current actually flows. When, in a three-phase circuit, the currents are assumed to be
balanced, it is not necessary to take into account the corresponding neutral conductor.
When the current value of the neutral conductor is close to that of the phases, a reduction
factor of 0.84 is to be applied. Such currents may, for example, be due to the presence of third
harmonic currents in the phase conductors (see 6.2).
Selection letter
D

Insulating material and number of loaded conductors


PVC 3

PVC 2

XLPE 3

XLPE 2

26
34
44
56
74
96
123
147
174
216
256
290
328
367
424
480

32
42
54
67
90
116
148
178
211
261
308
351
397
445
514
581

31
41
53
66
87
113
144
174
206
254
301
343
387
434
501
565

37
48
63
80
104
136
173
208
247
304
360
410
463
518
598
677

57
74
94
114
134
167
197
224
254
285
328
371

68
88
114
137
161
200
237
270
304
343
396
447

67
87
111
134
160
197
234
266
300
337
388
440

80
104
133
160
188
233
275
314
359
398
458
520

Copper cross-sectional
area (mm)
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
Aluminium cross-sectional
area (mm)
10
16
25
35
50
70
95
120
150
185
240
300

Table 6-17: current carrying capacities (in amps) of wiring systems in standard installation conditions
( f0 to f10 = 1) for selection letter D (buried wiring systems)

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

533

6.1.5.

Practical method for determining the minimum cross-sectional area of an LV


wiring system

conductor
installation
conditions

design current

IB
determination of the protective device rated current I n or
setting current I set taken to be just higher than the design
current: I n or I set I B

I n or I set
determination of the
selection letter and
overall correction
factor f
(see tab. 8-3 to 8-5)

determination of current I z of the wiring system to be


protected by the protective device

fuse

circuit-breaker

Iz

1.31 I n if I n

10 A

Iz

1.21 I n if I n

10 A

and I n

25 A

1.10 I n if I n

25 A

Iz

Iz

I n or I set

I z2

I z1

determination of the cross-sectional area S of the wiring system


conductors able to carry I z1 or I z2 :

I z1
I
or z 2 (1)
f
f
'
- determine the cross-sectional area able to carry I z in standard
installation conditions, depending on the insulating material, the
number of loaded conductors and the type of conductor (copper or
aluminium) (see tab. 8-16 and 8-17)
'

- calculate the equivalent current I z

S
check of other required conditions:
- maximum voltage drop
- maximum length for protection against indirect contact
(IT and TN earthing systems)
- check of thermal withstand in case of short circuit
(1) I z' is an equivalent current which, in standard installation
conditions, causes the same thermal effect as I z1 or I z2
in actual installation conditions
Figure 6-7: logigram for determining the cross-sectional area of a LV wiring system
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

534

6.1.6.

Cross-sectional area of protective conductors (PE), equipotential bonding


conductors and neutral conductors (IEC 364)

In a low voltage installation, the protective conductors ensure that the exposed conductive
parts of loads are interconnected and insulation fault currents are evacuated to the ground.
The equipotential bonding conductors allow the exposed conductive parts and extraneous
conductive parts to be set at the same potential, or similar potentials.
In this chapter, we will limit ourselves to conductor sizing rules. Refer to paragraph 2 for the
protection and connection rules.

n cross-sectional area of protective conductors between MV/LV transformer and main


LV switchboard (see fig. 6-8)
main LV switchboard

PE

Figure 6-8: PE conductors between transformer and main switchboard

Table 6-18 gives the protective conductor cross-sectional areas (in mm) in relation:
- to the nominal power of the MV/LV transformer
- to the operating time t (in seconds) of the MV protection. When protection is ensured by a
fuse, the cross-sectional area to be taken into account corresponds to t = 0.2 s
- to the insulating material and type of conductor metal.
In an IT earthing system, if an overvoltage limiter is inserted between the neutral and earth,
the same sizing is applied to its connecting conductors.
In the case where several transformers operate in parallel, the sum of their nominal powers will
be used to determine the cross-sectional area.

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

535

Transformer power
(kVA)
LV voltage
127/220 V 230/400 V

Type of conductors
Copper

t (s)

Aluminium

Bare
conductors
0.2 s 0.5 s
-

PVC-insulated
conductors

0.2 s 0.5 s

0.2 s 0.5 s
-

0.2 s 0.5 s

XLPE-insulated
conductors
0.2 s 0.5 s
-

0.2 s 0.5 s

63

100

25

25

25

25

25

25

25

25

25

100

160

25

25

35

25

25

50

25

25

35

125

200

25

35

50

25

35

50

25

25

50

160

250

25

35

70

35

50

70

25

35

50

200

315

Potective conductor

35

50

70

35

50

95

35

50

70

250

400

cross-sectional area

50

70

95

50

70

95

35

50

95

315

500

S PE (mm)

50

70

120

70

95

120

50

70

95

400

630

70

95

150

70

95

150

70

95

120

500

800

70

120

150

95

120

185

70

95

150

630

1 000

95

120

185

95

120

185

95

120

150

800

1 250

95

150

185

120

150

240

95

120

185

Table 6-18: cross-sectional area of protective conductors


between MV/LV transformer and main LV switchboard

n cross-sectional areas of low voltage exposed conductive part protective conductors: (PE)
The cross-sectional area of the PE conductor is defined in relation to the cross-sectional area
of the phases (for the same metal conductor) as follows:
- for S phase 16 mm ,

S PE = S phase

- for 16 mm < S phase 35 mm ,

S PE = 16 mm

- for S phase > 35 mm ,

S PE =

(1)

S phase
2

(1) when the protective conductor is not part of the wiring system, it must have a cross-sectional area of
at least:
- 2.5 mm if it comprises a mechanical protection
- 4 mm if it does not comprise a mechanical protection

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

536

In the TT earthing system, the protective conductor cross-sectional area may be limited to:
- 25 mm for copper
- 35 mm for aluminium
on condition that the neutral and exposed conductive part earth electrodes are separate,
otherwise the conditions of the TN earthing system are applicable (in a TT earthing
system, there may be an involuntary connection via the metal structure or other part between
the two earth electrodes; the earth fault current is then high).
n cross-sectional area of equipotential bonding conductors
o main equipotential bonding conductor

Its cross-sectional area must be at least equal to half the cross-sectional area of the
installation's largest protective conductor, with a minimum of 6 mm. However, it may be limited
to 25 mm for copper or 35 mm for aluminium.
o supplementary equipotential bonding conductor

If it connects two exposed conductive parts, its cross-sectional area must not be smaller than
the smallest of the protective conductors connected to these parts (see fig. 6-9-a).
If it connects an exposed conductive part to an extraneous conductive part, its cross-sectional
area must not be smaller than half the cross-sectional area of the protective conductor
connected to this exposed conductive part (see fig. 6-9-b).
S PE1 S PE 2

If

S
S LS = PE
2

S LS = S PE1
S PE1

S PE2

S PE

S LS

P1

(*)

S LS

P2

a) between two exposed conductive parts

b) between an exposed conductive part and a


structure

Figure 6-9: cross-sectional area of supplementary equipotential bonding conductors


(*)

with a minimum of:

- 2.5 mm if the conductors are mechanically protected


- 4 mm if the conductors are not mechanically protected

Conductors which are not incorporated in a cable are mechanically protected when they are
installed in conduits, troughs or casing or protected in a similar way.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

537

n cross-sectional area of PEN conductors


In the case of a TNC earthing system, the protective conductor also plays the role of the
neutral conductor.
In this case, the cross-sectional area of the PEN must be at least equal to the greatest value
resulting from the following requirements:
- S PEN

10 mm 2 for copper

16 mm 2 for aluminium

- meet the conditions relating to the PE conductor


- meet the conditions required for the neutral conductor cross-sectional area.

n cross-sectional area of the neutral conductor


- The neutral conductor must have the same cross-sectional area as the phase conductors in
the following cases:
.

single-phase circuit

three-phase circuit having phase cross-sectional areas smaller than or equal to 16 mm


for copper or 25 mm for aluminium.

- For three-phase circuits having a phase cross-sectional area greater than 16 mm for
copper or 25 mm for aluminium, the neutral cross-sectional area may be smaller than that
of the phases as long as the following conditions are met:
.

the maximum current likely to continuously circulate in the neutral is lower than the
current-carrying capacity of the chosen cross-sectional area. The unbalance of singlephase loads and third and multiples of third harmonics which may require the use of a
cross-sectional area greater than the phases must be taken into account (see 8.2 neutral conductor heating).

the neutral conductor is protected against overcurrent by a fuse or a circuit-breaker trip


setting suitable to its cross-sectional area.

the cross-sectional area of the neutral conductor is at least equal to 16 mm for copper or
25 mm for aluminium.

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

538

6.1.7.

Checking voltage drops

The voltage drop over a wiring system is calculated using the following formula:
L

V = b 1 cos + L sin I B

S
V

: voltage drop, in volts


= 1 for three - phase circuit

= 2 for single - phase circuit

: coefficient

: conductor resistivity during normal service, i.e. 1.25 times that at 20 C

1 = 0.0225 mm/m for copper; 1 = 0.036 mm/m for aluminium

L
S
cos
IB

: length of wiring system, in metres


: cross-sectional area of conductors, in mm
: power factor, in the absence of specific indications we can take

cos = 0.8 ( sin = 0.6)

: maximum design current, in amps


: reactance per unit length of the conductors, in /m

The values of in LV are:


-

0.08 10 3 / m for three-core cables

0.09 10 3 / m for single-core cables in a flat formation

0.15 10 3 / m for single-core cables spaced by d = 8 r

d
r

or triangular formation

: mean distance between conductor


: radius of conductor cores

The relative voltage drop is defined as:


V
Vn

for phase-to-neutral fed three-phase or single-phase circuits

V
Un

for phase-to-phase fed single-phase circuits (in this case,


V represents a phase-to-phase voltage drop)

Vn : nominal single-phase voltage


U n : nominal phase-to-phase voltage

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/A

539

In accordance with IEC 364-5-52, in the absence of other considerations, it is recommended


that in practice the voltage between the origin of consumer's installation and the equipment
should not be greater than 4% of the nominal voltage of the installation.

n circuits feeding motors


The voltage drop is calculated by replacing the design current I B by the motor starting current.
Taking into account all the motors able to start simultaneously, the voltage drop must be lower
than 10% to ensure correct motor starting and not disturb the rest of the installation too much.

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/A

540

6.1.8.

Maximum lengths of wiring systems for protection against indirect contact ( TN


and IT earthing system)

Standard IEC 364 specifies that the fault current for TN and IT earthing systems must be
cleared in a time compatible with the protection of persons.
This time is determined by a curve in relation to the prospective touch voltage; it is based on
the physiological effects of the electrical current on the human body. To simplify matters, using
this curve, it is possible to determine a maximum disconnecting time in relation to the nominal
voltage of the installation (see table 6-20 and 6-21).
Nominal a.c. voltage
Vn / U n
(Volts)

Disconnecting time
(seconds) (*)
non-distributed neutral

distributed neutral

120/240

0.8

230/400

0.4

0.8

400/690

0.2

0.4

580/1000

0.1

0.2

Table 6-20: maximum disconnecting times in the IT earthing system (second fault)

Nominal a.c. voltage Vn


(Volts) (**)

Disconnecting time
(seconds) (*)

120

0.8

230

0.4

277

0.4

400

0.2

> 400

0.1

Table 6-21: maximum disconnecting times in the TN earthing system

(*) these values are not valid in premises containing a bath or shower.

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/A

541

Note 1: if the disconnecting time is more than the time t0 , but less than 5 seconds, protection is
allowed by IEC 364 ( 413.1.3.5) in the following cases:
-

in distribution circuits when the protective conductor at the downstream end of the circuit is
directly connected to the main equipotential bonding.

in terminal circuits supplying stationary equipment only and having a protective conductor
that is connected to the main equipotential bonding and which is located in the area that is
influenced by the main equipotential bonding.

Note 2 : in the TT earthing system, protection is in general ensured by residual current devices which
are set to meet the following condition (see IEC 364, 413.1.4.2):

RA IA 50 V
RA : resistance of the earth electrode of the exposed conductive parts
IA : rated residual current of the circuit-breaker
If selectivity is seen to be necessary, an operating time at the most equal to 1 second is
allowed in the distribution circuits without taking into account the touch voltage
Note 3 : in an IT earthing system, when the exposed conductive parts are earthed individually or in
groups, the conditions of the TT earthing system given in Note 2 must be met (see IEC 364,
413.1.5.3).

n circuit-breaker protection
IEC 364 specifies that the magnetic tripping threshold of the circuit-breaker in TN and IT
earthing systems must be lower than the minimum short-circuit current. Furthermore, any
eventual circuit-breaker time delay must be shorter than the maximum disconnecting time
defined in tables 6-20 and 6-21.
For a given circuit-breaker and cross-sectional area, there is thus a maximum circuit length not
to be exceeded in order to comply with the requirements concerning the protection of persons
against indirect contact.
In the following part of the chapter, we will apply the conventional method for determining
maximum circuit lengths. This is more restrictive than the impedance method, but can be
applied by carrying out the calculations by hand.
In the conventional method, we neglect the influence of the reactance of the conductors for
cross-sectional areas smaller than 150 mm.
For large cross-sectional areas, we will take into account the influence of the reactance by dividing
Lmax by:
-

1.15 for a cross-sectional area of 150 mm


1.20 for a cross-sectional area of 185 mm
1.25 for a cross-sectional area of 240 mm
1.30 for a cross-sectional area of 300 mm.

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/A

542

Note:

for minimum short-circuit current calculations, refer to the "Industrial network protection guide"
4.4.1.

o TN earthing system

The maximum length of a circuit in a TN earthing system is:


Lmax =

0.8 Vn S ph
(1 + m) Im

Lmax : maximum length in m


Vn : single-phase voltage in volts
S ph : cross-sectional area of the phases in mm

: resistivity of the conductors taken to be equal to 1.5 times that at 20 C (


copper;

= 0.027 mm 2 / m for

= 0.043 mm 2 / m for aluminium)

S ph : cross - sectional area of phases

SPE : cross - sectional area of protective conductor

Im

: circuit-breaker magnetic trip operating current

o IT earthing system
The maximum length of a circuit in an IT earthing system is:
- if the neutral conductor is not distributed:
Lmax =

0.8 3 Vn S ph
2 (1 + m) I m

- if the neutral conductor is distributed:


Lmax =
= Sph
S1 :

0.8 Vn S1
2 (1 + m) Im

if the outgoing feeder considered does not have a neutral

= Sneutral if the outgoing feeder considered has a neutral

o TT earthing system

No condition on the wiring system length is specified since the protection of persons is
ensured by the residual current device.

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/A

543

n fuse protection
Using the fuse fusing curve, we can determine the current I a ensuring fusion of the fuse in
the time t 0 specified in tables 6-20 and 6-21 (see fig. 6-10). We can then calculate the
maximum length of the wiring system in the same way as for the circuit-breaker replacing I m
by I a .
t

t0

Ia
Figure 6-10: fuse fusing curve

n application
In practice, checking the cross-sectional area of the wiring system in relation to the protection
of persons against indirect contact consists in making sure that the length of the wiring system
is less than Lmax for a given arrangement.
If the wiring system length is greater than Lmax , we can take the following measures:
- choose a circuit-breaker (or trip relay) with a lower magnetic threshold if the selectivity
requirements permit this
- install a residual current circuit-breaker for TNS
earthing system it is not possible to use a RCD)

and

IT

earthing system (in a TNC

- take larger phase and protective conductor cross-sectional areas meeting the maximum
length condition.

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/A

544

6.1.9.

Checking the thermal withstand of conductors

When a short-circuit current flows through the conductors of a wiring system for a very short
time (up to five seconds), the heating of the conductors is considered to be adiabatic; this
means that the energy stored remains in the metal of the core and is not transmitted to the
insulating material. It is therefore necessary to check that the short-circuit thermal stress is
lower than the conductor thermal withstand:
2
tdis I sc
k2 S2

tdis

: protective device disconnecting time in seconds

S
Isc

: cross-sectional area of conductors in mm


: short-circuit current in A

The value of
k
(see table 6-22).

depends on the core metal and the type of insulating material

Insulating material

PVC

XLPE

Copper

115

135

Aluminium

74

87

Core

Table 6-22: value of factor k in accordance with IEC 364-4-43

If the disconnecting time is given, the cross-sectional area must comply with:
I
S sc tdis
k

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/A

545

n circuit-breaker protection
The check must be carried out for the maximum short-circuit current at the circuit-breaker
location.
The curves in manufacturers' catalogues give the maximum disconnecting time of the circuitbreaker. When circuit-breaker tripping is time delayed, the disconnecting time is taken to be
equal to the time delay.
To check the thermal withstand, the short-circuit current value must be calculated with a
resistivity of the conductors taken to be equal to 1.5 times that at 20 C :
-

= 0.027 mm 2 / m for copper

= 0.043 mm 2 / m for aluminium

o case of current-limiting circuit-breakers


On occurrence of a short circuit, current-limiting circuit-breakers only let a current below the
prospective fault current through (see fig. 6-11).

Isc

prospective peak I sc

prospective Isc

limited peak I sc

t
Figure 6-11: current limiting curve

The wiring system protected by this type of device is not therefore subjected to the
(prospective) calculated Isc thermal stress, but a much smaller stress defined by
manufacturers' limiting curves for each type of circuit-breaker.
2
The limiting curves give the thermal stress tdis I sc
expressed in A 2 second .

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/A

546

o example
We want to check the thermal withstand of a PVC-insulated 6 mm copper conductor protected
by a Compact NS 80H-MA 380/415 V circuit-breaker fitted with an LR2-D33 63 thermal relay.
The themal withstand of the cable is:

k 2 S 2 = (115) 2 6 2 = 4.76 10 5 A2 s .

The limiting curves in figure 6-12 give the maximum thermal stress of the circuit-breaker:
2 105 A2 s .
The cable is thus protected up to the circuit-breaker breaking capacity.

The curves are in the table order


Figure 6-12: thermal stress limiting curves
for Compact NS 80H-MA-380/415V circuit-breakers

n fuse protection
The current causing the most stress is the minimum short-circuit current at the end of the
wiring system.
The fusing time t f of the fuse corresponding to I sc min must comply with the relation:
2
2 2
t f Isc
min k S

The method for calculating I sc min is given in paragraph 4.4.1 of the Protection guide.

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/A

547

6.1.10.

Application example

n hypotheses
Let us consider the diagram in figure 6-13 the data of which is given below.
Since the installation feeds loads requiring good continuity of service the IT earthing system
without distributed neutral is chosen.

o W2 wiring system
This is made up of a PVC insulated copper three-core cable which is installed touching 3 other
multi-core cables on perforated trays in an ambient temperature of 40C. It is protected by
fuses. It feeds a load having the following characteristics:
- active power P = 15 kW
- efficiency = 0.89
-

cos = 0.85

- utilisation factor b = 0.9 .

o W1 wiring system
This is made up of 3 XLPE-insulated copper single-core cables in a triangular formation. The
cables are buried alone, without any extra mechanical protection, in soil which has a thermal
resistivity of 0.85 K.m/W and a temperature of 35 C. They are protected by a circuit-breaker.
The wiring system feeds load L1 and 3 other outgoing feeders the I B current values of which
are given in figure 6-13.

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/A

548

250 kVA

U sc = 4 %
unearthed neutral
400 V

W1
L1 = 100 m
cos

= 0.8

400 V

25 A

50 A

40 A

IB

W2
L2 = 15 m
R1

Figure 6-13: diagram of the installation

n determining the maximum design current


o W2 wiring system
-

P = 15 kW

1
= 1.32
cos
- the utilisation factor b = 0.9
- the factor a =

- for a single load the coincidence factor is c = 1


- no extension is planned, thus d = 1
- for a 400 V three-phase network, the power conversion factor in current is e = 1.4 .
We then have:

I B = P a b c d e = 15 1.32 0.9 1 1.4 = 24.9 A

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/A

549

o W1 wiring system
The maximum design current of the W1 wiring system is obtained by calculating the sum of
currents ( I B ) of all the outgoing feeders fed by W1 and by applying a coincidence factor
estimated at 0.8 (see table 6-2):
I B = (25 + 50 + 40 + 24.9) 0.8 = 115.9 A

n correction factors

o W2 wiring system
Table 6-3 gives the installation method N 13 and the selection letter E .
The correction factors to be applied are:
-

ambient temperature
cable group

(see table 6-6)


(see tables 6-9 et 6-10)

: f1 = 0.87
: f 4 = 0.77 and f 5 = 1

The overall correction factor is:


f = 0.87 0.77 1 = 0.67

o W1 wiring system
Table 6-3 gives the installation method N 62 and the selection letter D .
The correction factors to be applied are:
-

ground temperature
soil thermal resistivity
cable group

(see table 6-7)


(see table 6-8)
(see table 6-15)

: f 2 = 0.89
: f 3 = 1.05
: f10 = 1

The overall correction factor is:


f = 0.89 1.05 1 = 0.935

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/A

550

n determining the cross-sectional area and choosing the protective device


o W2 wiring system
I B = 24.9 A
f = 0.67
The fuse nominal current must comply with the condition I n I B .
The fuse with a rating of I n = 25 A is chosen.
For 10 A < I n 25 A , the current I z of the wiring system protected by this fuse is:
I z = k3 In = 1.21 In = 30.3 A
The equivalent current that the wiring system must be able to carry in standard installation
I
. A
conditions is: I 'z = z = 451
f
Table 6-16 (selection letter E , PVC3, copper) gives a minimum cross-sectional area of
S = 10 mm2 which has a current-carrying capacity of I 0 = 60 A .

o W1 wiring system
I B = 115.9 A
f = 0.935
For an adjustable circuit-breaker, the setting current must comply with the condition Iset I B ;
I set = 120 A is chosen.
The current I z of the wiring system protected by this setting is:
I z = I n = 120 A
The equivalent current that the wiring system must be able to carry in standard installation
I
conditions is: I 'z = z = 128.3 A
f
Table 6-17 (selection letter D , XLPE3, copper) gives a minimum cross-sectional area of
S = 25 mm2 which has a current-carrying capacity of I 0 = 144 A .

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/A

551

n maximum length of the wiring system


o W2 wiring system

For

S ph = 10 mm , we have S PE = S ph = 10 mm

whence

m=

S ph
S PE

=1

Table 6-20 gives a maximum disconnecting time of t = 0.4 s for a network with non-distributed neutral.
The time-current characteristic for a 25 A rated fuse gives us a current of

I a = 200 A for a

disconnecting time of 0.4 s.


The neutral is not distributed and we thus have:
Lmax =

0.8 3 Vn S ph 0.8 3 230 10


= 147.5 m
=
2 (1 + m ) Ia
2 0.027 2 200

The length of the W2 wiring system (15 m) is far smaller than

Lmax and the protection of

persons against indirect contact is thus ensured.

o W1 wiring system

For 16 mm < S 35 mm , we have S PE = 16 mm


whence

m=

S ph
SPE

25
= 1.56
16

The circuit-breaker chosen is a Compact NS 125E with an STR 22SE trip relay having a
magnetic tripping threshold set at I m = 1 250 A because of the selectivity.
The neutral is not distributed and we thus have:
Lmax =

0.8 3 Vn S ph
2 (1 + m) I m

0.8 3 230 25
= 46.1 m
2 0.027 2.56 1 250

The length of the W1 wiring system (100 m) is greater than Lmax .


By taking cross-sectional areas greater, i.e. S ph = 35 mm and S PE = 35 mm ( m = 1) , we find
Lmax = 82.6 m < 100 m ; which is not sufficient.
So as not to oversize the conductors, it is decided that the outgoing feeder should be fitted
with a residual current device which ensures the protection of persons against indirect contact.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/A

552

n checking the voltage drop


o W2 wiring system

S = 10 mm , L = 15 m , I B = 24.9 A
The cable is three-core and we thus have = 0.08 10 3 / m .
The power factor is cos = 0.85 , whence sin = 0.53 .
For a three-phase circuit b = 1 .
For copper 1 = 0.0225 mm 2 / m .
We deduce from this that

15

V = 0.0225
0.85 + 0.08 10 3 15 0.53 24.9

10

V = 0.73 V
whence

V 0.73
=
= 0.3 %
Vn
230

The total voltage drop is 4.2 % (the voltage drop in the W1 wiring system is 3.9 %, see below).

o W1 wiring system

S = 25 mm , L = 100 m , I B = 115.9 A
The 3 single-core cables are in a flat formation and we thus have:

= 0.09 10 3 / m
The overall power factor of the installation is cos = 0.8 , whence sin = 0.6 .
100
We deduce from this that
V = 0.0225
0.8 + 0.09 10 3 100 0.6 115.9

25
V = 8.97 V
whence

V 8.97
=
= 3.9 %
Vn
230

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/A

553

n checking the thermal stress


o W2 wiring system

For fuse protection, the current to be taken into account is the minimum short-circuit current at
the end of the wiring system. For the IT earthing system, this is the short-circuit current for a
double phase-earth fault.
By applying the conventional method (see 4.4.1.2 of the Protection guide), we can calculate:
Isc min =

3 Vn 0.8
3 230 0.8
=
= 1.97 kA
1
1 2 15 0.027 1 + 1

+
2 L 2
10 10
S ph SPE

The time-current characteristic of the 25 A rated fuse gives us a fusing time of t f = 5 ms for a
current of 1.97 kA.
The maximum thermal stress is thus:

2
3
Isc
min t = 1.97 10

5 10 3 = 19.4 10 3 A2 s

2
The permitted cable thermal withstand is: k 2 S 2 = (115) 102 = 1322 103 A2 s .

The cross-sectional area of S = 10 mm2 is thus largely able to withstand to the fuse thermal
stress.
o W1 wiring system

The maximum short-circuit current of the circuit-breaker (neglecting the connection linking the
circuit-breaker to the transformer) is:
Isc =

Sn
1
250 103 100

= 9.02 kA
4
3 Un Usc
3 400

We assume that the circuit-breaker trip relay is delayed by 0.1 second, the maximum shortcircuit thermal stress is then:

2
Isc
t = 9.02 10 3

0.1 = 8.14 10 6 A2 s

The permitted cable thermal withstand is: k 2 S 2 = 1432 252 = 12.78 10 6 A2 s


The cross-sectional area of

S = 25 mm2 is thus largely able to withstand the circuit-breaker

thermal stress.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/A

554

n conclusion
The cross-sectional areas to be chosen are:
- W1 wiring system: 3 35 mm 2 + 1 16 mm 2 copper
- W2 wiring system: 3 10 mm 2 + 1 10 mm 2 copper

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/A

555

6.2.

Determining conductor cross-sectional areas in medium voltage

6.2.1.

Method principle

The method for determining the cross-sectional area of conductors in medium voltage consists
in:
- determining the maximum design current I B of the loads to be supplied
- determining the cross-sectional area S1 complying with the heating of the cable core under
normal operating conditions, which may be continuous or discontinuous. To do this, it is
necessary to know:
.

the actual installation conditions of the wiring system and consequently the overall
correction factor f

the current-carrying capacities of the different types of cable in standard installation


conditions.

- determining the cross-sectional area S 2 required for the thermal withstand of the cable in
the event of a three-phase short circuit
- determining the cross-sectional area
screen in the event of an earth fault

S3 required for the thermal withstand of the cable

- possibly checking the voltage drop in the wiring system for the chosen cross-sectional
area S. The technical cross-sectional area S to be selected is the maximum value among
cross-sectional areas S1 , S 2 and S3 .
- possibly calculating and choosing the economical cross-sectional area.

6.2.2.

Determining the maximum design current

The maximum design current I B is determined on the basis of the sum of powers of the loads
fed, applying if necessary utilisation and coincidence coefficients (see 6.1.2.).
In medium voltage, a wiring system most often feeds a single load (transformer, motor,
furnace, steam generator), in this case I B is taken to be equal to the rated current of the
device.

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

556

6.2.3.

Current-carrying capacities in wiring systems

n general rules
The current-carrying capacity is the maximum current that a wiring system can continuously
carry without this affecting its life span.
The current-carrying capacities of cables are given in standards or by manufacturers for
standard installation conditions.
To determine the current-carrying capacity of a wiring system in actual installation conditions,
the following must be carried out:
- using table 6-23, define the installation method, its associated table column number and
correction factors to be applied
- using the installation conditions, determine the correction factor values which must be
applied (see tables 6-24 to 6-28)
- calculate the overall correction factor f equal to the product of the correction factors
- using table 6-29 for impregnated paper-insulated cables and tables 6-30 to 6-34 for
synthetically-insulated cables, determine the maximum current that the wiring system can
carry in standard conditions ( f0 to f6 = 1)
- calculate the maximum current-carrying capacity of the wiring system in relation to its
installation conditions: I a = f I 0 .

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

557

n installation methods
Table 6-23 gives, for each installation method, the current-carrying capacity table column to be
used for choosing the cross-sectional area of the conductors (see tables 6-29 to 6-34).
Factor

f 0 corresponds to the installation method; factors

f1 to

f 6 are explained below

Table

Correction factors
to be applied
f0

(see tables 6-24 to 6-28).


Installation methods

Example

column

A Conduits on wall
(3)

0.90

f1

f5

B Flush mounted
conduits

(3)

0.90

f1

f5

F Installed on cable
trays

(3)

f1

f5

G Installed on brackets
or cable ladders

(3)

f1

f6

H Troughs (enclosed)

(3)

0.90

f1

f5

(3)

f1

f6

(3)

0.80

f1

f5

J Ducts (open troughs)

L1 Conduits in open or
ventilated channels

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

558

Installation method

Example

L3 Directly installed in
open or ventilated
channels

L4 Directly installed in
enclosed channels

L5 Directly installed in
channels filled with
sand

Table

Correction factors
to be applied

column

f0

(3)

0.90

f1

--

f5

(3)

0.80

f1

--

f5

(3)

0.80

f1

--

f5

(3)

0.90

f1

--

f5

(3)

0.90

f1

--

f5

f2

f3

f4

f2

f3

f4

N Troughs (in masonry)

P Manufactured blocks

S1 Directly buried
(armoured cables)

S2 Buried with
mechanical protection

: steady-state operating conditions

: discontinuous operating conditions

P D
____
___
(1) (2)

(1) (2)

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

559

Installation method

Example

Table
column

f0

Correction factors
to be applied

P D
____
___
(1) (2)

S3 Buried in sleeves

0.8

f2

f3

f4

S4 Cables installed in
trefoil formation in a
prefabricated channel,
buried directly in the
ground, possibly with
extra backfill

(1) (2)

0.8

f2

f3

f4

S5 Single-core cables
installed in individual
channels, buried
directly in the
ground, possibly with
extra backfill

(1) (2)

0.8

f2

f3

f4

(1) (2)

0.8

f2

f3

f4

(3)

1,1

f1

--

--

Single-core cables in a
flat formation spaced
out in a prefabricated
channel, buried
directly in the
ground, possibly with
extra backfill

V Overhead lines

: steady-state operating conditions

: discontinuous operating conditions

Table 6-23: installation methods

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

560

n correction factors for ambient temperatures other than 30 C (cables installed in air): f1

Temperature

Type of insulating material

PVC
PE

XLPE
EPR

10

1.22

1.15

15

1.17

1.12

20

1.12

1.08

25

1.06

1.04

30

1.00

1.00

35

0.94

0.96

40

0.87

0.91

45

0.79

0.87

50

0.71

0.82

55

0.61

0.76

Table 6-24: correction factors for ambient temperatures other than 30 C (cables installed in air)

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

561

n correction factors for ground temperatures other than 20 C (buried cables): f 2

Temperature

Type of insulating material

PVC
PE

XLPE
EPR

1.18

1.13

1.14

1.10

10

1.10

1.07

15

1.05

1.04

20

1.00

1.00

25

0.95

0.96

30

0.89

0.93

35

0.84

0.89

40

0.77

0.85

45

0.71

0.80

50

0.63

0.76

60

0.45

0.65

65

0.60

70

0.53

75

0.46

80

0.38

Table 6-25: correction factors for ground temperatures other than 20 C (buried cables)

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

562

n correction factors for soil thermal resistivities other than 1 K.m/W (buried cables): f 3
Soil thermal
resistivity
(K.m/W)

Humidity

0.5

Assembly of
three singlecore cables

Three-core
cables

Very moist soil

1.25

1.20

0.7

Moist soil

1.14

1.10

0.85

Normal soil

Clay

1.06

1.05

Dry soil

and

1.00

1.00

Chalk

0.93

0.95

Ash

0.85

0.88

and

0.75

0.79

Clinker

0.68

0.72

0.62

0.68

Type of soil

1.2

Sand

1.5

Very dry soil

2
2.5
3

Tableau 6-26: correction factors for soil thermal resistivities other than 1 K.m/W (buried cables)

n correction factors for a group of several wiring systems (buried cables): f 4


Number of
circuits

Distance between cables "a"


Zero (cables
touching)

One cable
diameter

0.125 m

0.25 m

0.5 m

0.75

0.80

0.85

0.90

0.90

0.65

0.70

0.75

0.80

0.85

0.60

0.60

0.70

0.75

0.80

0.55

0.55

0.65

0.70

0.80

0.50

0.55

0.60

0.70

0.80

Determination of the distance "a" in the case of single-core cables installed in a flat or trefloid
formation and three-core cables.
single-core cables

three-core cables

a
a
a

Table 6-27: correction factors for a group of several wiring systems (buried cables )

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

563

n correction factors for a group of several circuits or several cables


(cables installed in air and away from direct sunlight): f 5 , f 6

Installation
method

Arrangement

f5

On unperforated horizontal trays.........................

f6

On perforated horizontal trays


or on brackets ....................................................

Number of circuits or
multi-core cables
2

>9

0.85

0.80

0.75

0.70

0.70

0.90

0.80

0.80

0.75

0.75

Table 6-28: correction factors for a group of several circuits or several cables (cables installed in air and
away from direct sunlight)

n current-carrying capacities of cables in standard installation conditions

( f0 to f6 = 1)

References (1), (2) and (3) of tables 6-29 to 6-34 correspond to the column number given in
table 6-23.

o impregnated paper-insulated cables

Impregnated paper-insulated cables have stopped being manufactured for several years.
However, for calculation purposes for existing installations, the current-carrying capacities may
be calculated to an approximate value of 5% using the following formula:
I = 10 B S A
I
: current-carrying capacity, in A
S
: nominal cross-sectional area of the cable, in mm
A and B : are coefficients given for each type of cable (see table 6-29)

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

564

Wiring systems

Columns

Copper

Aluminium

Three-core

(1)

0.540

1.446

0.549

1.321

collectively

(2)

0.543

1.492

0.544

1.386

screened cable

(3)

0.588

1.371

0.598

1.293

3 single-core

(1)

0.556

1.269

0.571

1.130

cables

(2)

0.567

1.286

0.573

1.179

(3)

0.587

1.196

0.605

1.064

Three-core individually

(1)

0.581

1.215

0.594

1.089

screened cables

(2)

0.573

1.264

0.578

1.155

(3)

0.600

1.117

0.608

1.004

Table 6-29: values of coefficients A and B for impregnated paper-insulated cables

o synthetically-insulated cables

The detailed calculation method for current-carrying capacities of cables under steady-state
operating conditions is given in IEC publication 287.
The current-carrying capacities are given in tables 6-30 to 6-34, according to the type of
conductor, the type of insulating material and the rated voltage.
The rated voltage for which a cable is designed is expressed by a set of three values, in kV, as
U 0 / U (Um) , where:
-

U0 :
U :
Um :

voltage between the conductor core and a reference potential (screen or earth)
voltage between the cores of two phase conductors
maximum voltage which may occur between the network phases in normal operating
conditions

The expression of the rated voltage differs depending on whether the cable is an individually
screened type or not (see fig. 2.2.a and 2.2.b). For an individually screened cable, U 0 is
different from U , both values being generally in the ratio of

3 .

However, due to the way it is made, a collectively screened cable has an equivalent insulation
level between two phases and between one phase and the screen. This results in U 0 and U
having identical values.

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

565

PVC-insulated

(*)

Nominal
crosssectional
area (mm)*

EPR or XLPE-insulated

(1)

(2)

(3)

Copper

(1)

(2)

(3)

72

78

62

10

86

94

78

94

100

81

16

110

120

100

120

130

105

25

145

155

130

145

160

130

35

170

190

165

185

205

165

50

215

240

205

225

250

205

70

260

295

255

270

300

250

95

315

355

310

310

345

290

120

360

405

360

345

390

330

150

405

455

410

385

430

370

185

450

505

460

445

500

440

240

525

590

550

(1)

(2)

(3)

Aluminium

(1)

(2)

(3)

56

61

48

10

67

73

60

72

79

62

16

86

94

79

94

100

82

25

110

120

105

115

125

100

35

135

145

125

145

160

130

50

165

185

160

175

195

160

70

205

230

195

210

235

195

95

245

275

240

240

270

225

120

280

315

280

270

300

255

150

315

355

320

300

335

285

185

350

395

360

350

390

345

240

410

460

430

Above 50 mm, the values are calculated for sector conductors

Table 6-30: current-carrying capacities in three-core collectively screened cables having a rated voltage
lower than or equal to 6/6 (7.2) kV
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

566

Copper
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1 000
1 200
1 400
1 600
Aluminium
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1 000
1 200
1 400
1 600
(*)

PE-insulated*

PVC-insulated

Nominal
crosssectional
area (mm)
(1)
80
105
135
160
190
235
285
320
360
410
475
540
610
680
770
850
930
980
1 030
1 080
(1)
62
80
105
125
150
180
220
250
280
320
370
420
480
540
620
700
780
840
890
940

(2)
89
115
150
180
215
265
320
365
410
470
540
610
700
780
880
980
1 070
1 130
1 190
1 250
(2)
69
89
115
140
170
205
250
285
320
365
425
485
550
630
720
810
900
970
1 030
1 080

(3)
71
95
125
150
180
230
280
320
370
425
500
580
670
760
870
990
1 110
1 210
1 290
1 360
(3)
55
73
96
115
140
175
215
250
285
330
390
455
530
610
710
820
940
1 030
1 110
1 180

(1)
86
110
140
170
200
245
295
335
375
425
490
550
600
700
790
870
950
1 000
1 050
1 100
(1)
67
86
110
130
160
190
230
260
290
330
385
435
495
560
640
720
800
860
910
950

(2)
97
125
160
195
230
285
340
385
435
490
570
640
690
810
920
1 010
1 100
1 160
1 220
1 280
(2)
76
97
125
150
180
220
265
300
335
380
445
500
580
650
750
840
930
1 000
1 060
1 110

EPR or XLPE-insulated

(3)
76
100
130
160
190
240
295
340
385
445
530
600
700
790
920
1 040
1 160
1 260
1 350
1 420

(1)
99
125
165
195
230
285
340
385
430
485
560
630
720
800
910
1 000
1 100
1 160
1 220
1 280

(3)
59
78
100
125
150
185
230
265
300
345
410
470
550
640
750
860
980
1 080
1 160
1 230

(1)
77
98
125
150
180
220
260
300
335
380
440
500
570
640
740
830
920
990
1 050
1 100

(2)

(3)

110
145
185
225
265
325
390
445
500
560
650
730
840
940
1 060
1 170
1 270
1 350
1 420
1 480
(2)

93
120
160
200
235
295
360
420
475
550
650
740
860
990
1 140
1 300
1 450
1 570
1 680
1 770
(3)

87
110
145
175
205
250
300
345
385
440
510
580
660
750
860
970
1 070
1 150
1 230
1 290

72
95
125
150
185
230
280
325
370
425
510
580
680
790
920
1 070
1 220
1 340
1 450
1 530

For cables having high density polythene insulation, the values are to be multiplied by:
1.05 for columns (1) and (2)
1.06 for column (3)

Table 6-31: current-carrying capacities in cables made up of three single-core cables having a rated
voltage lower than or equal to 6/10 (12) kV

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

567

PE-insulated*

Nominal
crosssectional
area (mm)

(1)

(2)

(3)*

110
140
170
200
250
295
335
375
425
490
550
630
700
790
870
960
1 010
1 070
1 110

125
160
195
230
280
335
385
430
490
560
640
720
810
920
1 010
1 100
1 170
1 240
1 290

105
135
165
200
250
300
350
395
455
530
610
710
810
930
1 050
1 180
1 270
1 360
1 430

(1)

(2)

(3)

86
110
130
155
190
230
260
290
330
385
435
495
560
640
720
800
860
920
960

96
125
150
180
220
260
300
335
380
445
500
570
650
740
830
930
1 000
1 060
1 110

81
105
130
155
190
235
270
305
355
420
480
560
650
750
860
990
1 090
1 170
1 240

(*)

Copper
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1 000
1 200
1 400
1 600
Aluminium
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1 000
1 200
1 400
1 600

EPR or XLPE-insulated

(1)

(2)

(3)

125
165
195
230
280
335
385
430
490
560
640
720
810
910
1 010
1 110
1 180
1 240
1 290

140
185
220
260
320
385
440
495
560
650
730
830
940
1 060
1 170
1 280
1 360
1 440
1 500

130
170
200
245
305
375
425
485
560
660
750
870
1 000
1 150
1 300
1 470
1 590
1 700
1 790

(1)

(2)

(3)

98
125
150
180
220
260
300
335
380
440
500
570
640
740
830
930
1 000
1 060
1 110

110
140
170
205
250
300
340
385
435
510
570
660
740
850
960
1 070
1 160
1 230
1 290

99
130
160
190
235
290
330
375
430
510
590
680
790
930
1 060
1 230
1 350
1 450
1 540

For cables having high density polythene insulation, the values are to be multiplied by:
1.05 for columns (1) and (2)
1.06 for column (3)

Table 6-32: current-carrying capacities in cables made up of three single-core cables having a rated
voltage greater than 6/6 (7.2) kV and lower than or equal to 18/30 (36) kV

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

568

Copper

PE-insulated*

PVC-insulated

Nominal
crosssectional
area (mm)
(1)

(2)

(3)

(1)

(2)

EPR or XLPE-insulated

(3)

(1)

(2)

(3)

10

80

87

71

85

94

75

97

110

92

16

100

115

90

110

120

98

125

140

120

25

130

145

120

140

155

125

160

180

155

35

160

175

145

165

190

155

190

215

190

50

185

205

175

195

220

185

225

250

225

70

230

255

215

240

270

230

275

310

280

95

275

305

260

285

320

275

330

370

340

120

310

345

300

325

365

315

370

420

385

150

345

385

340

365

415

365

420

475

445

185

390

435

385

410

465

410

470

535

510

240

450

500

450

475

530

485

540

610

590

300

500

560

520

530

605

560

610

690

680

Aluminium

(1)

(2)

(3)

(1)

(2)

(3)

(1)

(2)

(3)

(*)

10

62

68

55

66

73

58

75

84

71

16

79

87

71

84

94

76

96

110

92

25

100

115

93

110

120

99

125

140

120

35

120

135

115

130

145

120

150

165

145

50

145

160

135

150

170

140

175

195

175

70

180

195

165

185

210

175

215

240

215

95

210

235

205

220

250

215

255

285

260

120

240

270

235

250

285

245

290

325

300

150

270

300

265

285

325

280

325

370

345

185

305

340

300

320

360

320

365

415

395

240

350

390

355

370

420

380

425

480

465

300

395

440

405

420

475

435

480

540

530

For cables having high density polythene insulation, the values are to be multiplied by:
1.05 for columns (1) and (2)
1.06 for column (3)

Table 6-33: current-carrying capacities in three-core individually screened cables having a rated voltage
lower than or equal to 6/10 (12) kV

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

569

Nominal crosssectional area (mm)


Copper

EPR or XLPE-insulated

(1)

(2)

(3)

16

125

140

125

25

160

175

160

35

190

210

195

50

225

250

230

70

270

305

280

95

330

370

345

120

370

420

395

150

415

465

450

185

465

525

510

240

540

610

600

Aluminium

(1)

(2)

(3)

16

96

105

95

25

125

135

125

35

145

165

150

50

175

195

175

70

210

235

220

95

255

285

265

120

290

325

305

150

320

360

345

185

360

410

395

240

420

475

470

Table 6-34: current-carrying capacities in three-core individually screened cables having a rated voltage
greater than 6/6 (7,2) kV and lower than or equal to 18/30 (36) kV

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

570

6.2.4.

Thermal withstand of conductors in the event of a short circuit and


determination of the cross-sectional area S 2

The thermal withstand of live conductors must be checked for the maximum short-circuit
current at the origin of the cable. It is calculated using the impedance method taking into
account the participation of all the network elements (motors, generators, etc., see Protection
guide 4.2).
In the case of an installation with an internal generator set, the thermal withstand is
established on the basis of the short-circuit current during the transient period, this
approximately corresponding to the short-circuit clearance time (see Protection guide 4.1.2).
For a short-circuit time less than 5 seconds, cable heating is considered to be adiabatic; this
means that the energy stored stays in the core and is not transmitted to the insulating material.
The thermal calculations are then simplified. They are given below.
Note:

to check the thermal withstand of protective and equipotential bonding conductors, the earth
fault current must be taken into account (see 4.2.2 of the Protection guide)

n general method
The heating calculation results are shown by the curves in figure 6-14. They give the current
density withstands 0 in different types of cable for a short-circuit time of one second, in
relation to the cable temperature before the short circuit.
The minimum conductor cross-sectional area complying with heating in the case of a short
circuit is determined by the fomula:
I
S = sc

Isc : maximum short-circuit current, in A


: current density withstand, in A / mm
for a short-circuit time other than one second, we have:

=
t

0
t

: short-circuit time

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

571

Figure 6-14: short circuit in the core

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

572

n simplified method
This assumes that the cable temperature before the short circuit is equal to the temperature
allowed in steady-state operating conditions.
In this case, the conductor cross-sectional area must meet the following condition:
I
S sc
k

Isc : maximum short-circuit current


t
: short-circuit time
k : coefficient the value of which is given in table 6-35
For protective conductors, the current to be taken into account is the earth fault current I f .

Insulating material
PVC
PE

XLPE
EPR

115

143

74

94

Live conductors
- in copper
- in aluminium
Protective conductors

143

115

176

143

- in aluminium

95

75

116

94

- in steel

52

64

- in copper

a
b

protective conductors not incorporated in cables


protective conductors incorporated in cables
Table 6-35: coefficient k values

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

573

6.2.5.

Short-time withstand currents in cable screens with extruded synthetic


insulation (determination of S3 )

In the event of a phase-to-screen short circuit, the thermal withstand resulting from the
passage of the fault current I f for a time t , must not exceed the thermal withstand of the
cable screen.

If

is the earth fault current and the method for determining its value is

described in the Protection guide, paragraph 4-2.


The calculation of the overcurrent permitted in the cable screens depends on what the screen
is made of and the type of cable.
In the absence of precise indications, the values of tables 6-37, 6-38 and 6-39 can be used.
These values correspond to a screen made up of a copper band 0.1 mm thick wrapped around
the insulating material with an overlap of 15 %.
Table 6-36 gives, for each type of insulating material, the temperatures during normal service
and at the end of overcurrents used for calculating cable screen heating.

Type of insulating
material

Temperature on the screen during


service (C)

Final temperature following


overcurrent
(C)

XLPE

70

250

EPR

70

250

PE

60

150

PVC

60

160

Table 6-36: temperature conditions used for the calculation

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

574

o overcurrent values permitted in cable screens with extruded synthetic insulation

See tables 6-37, 6-38 and 6-39.

Rated voltage
Short-circuit time

6/10 (12) kV
0.5 s

1s

8.7/15 (17.5) kV

2s

0.5 s

1s

2s

12/20 (24) kV
0.5 s

1s

2s

18/30 (36) kV
0.5 s

1s

2s

Conductor cross-sectional
area in mm
16

1 100

900

650 1 350 1 000

800 1 800 1 400 1 100

25

1 200

950

700 1 400 1 050

800 1 800 1 400 1 100

35

1 400 1 000

50

1 600 1 150 1 000 1 750 1 350 1 050 1 950 1 450 1 150 2 500 1 950 1 550

70

1 750 1 250 1 050 1 900 1 450 1 150 2 100 1 600 1 250 2 700 2 050 1 650

95

1 850 1 350 1 100 2 050 1 550 1 200 2 200 1 700 1 300 2 800 2 150 1 700

120

1 900 1 400 1 150 2 150 1 650 1 300 2 500 1 950 1 550 3 100 2 400 1 900

150

2 150 1 650 1 300 2 400 1 850 1 500 2 600 2 000 1 600 3 150 2 450 1 950

185

2 400 1 850 1 450 2 600 2 000 1 600 2 750 2 150 1 700 3 350 2 600 2 100

240

2 700 2 050 1 650 2 800 2 150 1 700 3 100 2 400 1 950 3 600 2 750 2 200

300

2 800 2 150 1 750 3 150 2 450 1 950 3 300 2 550 2 050 3 800 2 950 2 350

400

3 050 2 350 1 800 3 450 2 650 2 150 3 650 2 800 2 250 4 200 3 300 2 650

500

3 400 2 550 1 950 3 800 2 950 2 350 4 100 3 200 2 550 4 550 3 550 2 850

630

3 750 3 000 2 300 4 250 3 300 2 650 4 450 3 450 2 800 4 950 3 850 3 100

800

4 400 3 400 2 600 4 650 3 600 2 900 4 850 3 750 3 000 5 300 4 150 3 300

1 000

5 100 3 900 3 050 5 200 4 050 3 250 5 350 4 200 3 350 5 850 4 550 3 650

1 200

5 350 4 100 3 300 5 450 4 250 3 400 5 650 4 400 3 550 6 150 4 800 3 850

1 400

5 600 4 400 3 550 5 900 4 550 3 650 6 050 4 700 3 800 6 550 5 100 4 100

1 600

6 000 4 700 3 800 6 200 4 850 3 900 6 400 5 000 4 000 6 900 5 350 4 300

900 1 650 1 250 1 000 1 850 1 400 1 100

Table 6-37: single-core or three-core individually screened cables with XLPE or EPR insulation short-circuit current permitted in the screen (A)

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

575

Rated voltage
Short-circuit time

6/10 (12) kV
0.5 s

1s

8.7/15 (17.5) kV

2s

0.5 s

1s

2s

12/20 (24) kV
0.5 s

1s

2s

18/30 (36) kV
0.5 s

1s

2s

Conductor cross-sectional
area in mm
16

800

650

490 1 000

740

560 1 200

870

660

25

900

700

510 1 000

750

570 1 200

870

660

35

1 000

750

540 1 100

800

600 1 200

880

660

50

1 100

800

580 1 150

840

640 1 250 1 000

770 1 750 1 300

70

1 300

920

700 1 350

990

760 1 450 1 100

820 1 750 1 300 1 000

95

1 350 1 000

750 1 450 1 050

820 1 550 1 150

880 2 050 1 550 1 200

120

1 450 1 050

800 1 500 1 150

860 1 650 1 200

930 2 150 1 650 1 230

150

1 550 1 100

840 1 600 1 200

910 1 700 1 300 1 000 2 250 1 700 1 300

185

1 650 1 150

900 1 700 1 250

970 2 000 1 500 1 200 2 350 1 800 1 400

240

1 800 1 450 1 100 2 000 1 550 1 200 2 150 1 650 1 250 2 650 2 050 1 600

300

2 000 1 550 1 200 2 150 1 650 1 300 2 300 1 750 1 350 2 800 2 150 1 700

400

2 300 1 750 1 400 2 600 2 000 1 550 2 650 2 050 1 600 3 000 2 300 1 800

500

2 550 1 900 1 500 2 900 2 200 1 750 3 050 2 350 1 850 3 400 2 600 2 050

630

2 750 2 050 1 550 3 000 2 300 1 800 3 150 2 400 1 900 3 500 2 650 2 050

800

3 000 2 250 1 700 3 300 2 500 2 000 3 450 2 600 2 100 3 700 2 800 2 200

1 000

3 300 2 400 1 800 3 500 2 700 2 100 3 650 2 800 2 200 3 950 3 000 2 400

1 200

3 550 2 550 1 900 3 700 2 850 2 200 3 850 2 950 2 300 4 200 3 200 2 550

1 400

3 650 2 750 2 000 3 900 3 000 2 350 4 050 3 100 2 450 4 350 3 350 2 650

1 600

3 750 2 850 2 100 4 000 3 100 2 400 4 150 3 200 2 500 4 500 3 400 2 700

990

Table 6-38: single-core or three-core individually screened cables with PE insulation short-circuit current permitted in the screen (A)

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

576

Conductor crosssectional area

Short-cicuit time

mm

0.5 s

1s

2s

10

1 550

1 200

980

16

1 700

1 300

1 050

25

1 950

1 450

1 200

35

2 050

1 550

1 250

50

2 150

1 600

1 300

70

2 300

1 700

1 400

95

2 550

1 900

1 550

120

2 750

2 100

1 650

150

2 900

2 200

1 750

185

3 350

2 450

2 050

240

3 500

2 650

2 200

Table 6-39: PVC-insulated three-core collectively screened cables with a rated voltage of 6/6 (7.2 kV) short-circuit current permitted in the screen (A)

o example

Let us consider a PE-insulated single-core cable in a 10 kV network having an earth fault


current I f limited to 1 000 A.
According to table 6-38, the minimum cross-sectional area of the conductor depends on the
short-circuit time:
- for
- for
- for

t = 0.5 s
t= 1s
t= 2s

,
,
,

S min = 35 mm
S min = 95 mm
S min = 240 mm .

The cross-sectional area S3 is selected in relation to I f and the short-circuit time, which is
taken to be equal to the longest time needed to clear the fault (e.g., the back-up protection
time delay).

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

577

6.2.6.

Checking voltage drops

Voltage drops in medium voltage cables in industrial networks are in general negligible.
However, it seems useful to give the calculation method able to be applied notably for very
long wiring systems.
For a three-phase circuit, the voltage drop (single-phase voltage) is calculated by the fomula:
L

V = 1 cos + L sin I B
S

: conductor resistivity during normal service, i.e. 1.25 times that at 20 C

1 = 0.0225 mm 2 / m for copper; 1 = 0.036 mm 2 / m for aluminium


L
S
cos

: length of wiring system, in metres


: conductor cross-sectional areas, in mm

IB

: maximum design current in

: power factor; in the absence of precise indications, we may take

cos = 0.8 (sin = 0.6)

: reactance per unit length of the wiring system, in

/m .

The values of in MV are:


-

0.08 10 3 / m for three-core cables

0.15 10 3 / m for single-core cables

We define the relative voltage drop as:


V
Vn
Vn

: nominal single-phase voltage

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

578

6.2.7.

Practical determination of the minimum cross-sectional area of a medium


voltage cable (see fig. 6-15)

cable installation
conditions

determination of
maximum design
current I B

determination of the
cable column and
overall correction
factor (see tab. 8-23)

equivalent current (1)

Iz

determination of the cross-sectional area S1 of the cable


able to carry I z in standard installation conditions in
relation to the type of cable, its insulation and rated
voltage (see tab. 8-29 to 8-34)

IB
f

thermal withstand

S2

I sc max

S3 function I f , t
(see tab. 8-37 to 8-39)

screen thermal
withstand: If

voltage drop
check

Isc max
t
k

max ( S1 , S 2 , S3 )

economic cross-sectional
area possibly chosen

(1) I z is an equivalent current which, in standard installation conditions,


causes the same thermal effect as I B in actual installation
conditions

Figure 6-15: logigram for determining the minimum cross-sectional area of a medium voltage cable

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

579

6.2.8.

Cable screen earthing conditions

n single-core cables
The passage of a current in the cable core produces an induced voltage in the screen. This
voltage depends on the geometrical arrangement of the cables, the length and the current
carried:
2a
E0 = 0.145 log10 l I
d
a
d
l
I

:
:
:
:

distance between cable axes (mm)


mean diameter of the screen (mm)
connection length (km)
current carried in the core (A).

For very long cables,


E0
may reach dangerous values for persons. The standard
recommends screen earthing at both ends when E0 is likely to exceed the limit of 50 V
under steady-state operating conditions.
However, screen earthing at both ends produces currents continuously circulating in the
screen.
For screen earthing at one end only, on occurrence of a short circuit, the potential induced on
the second end may be high and cause a breakdown of the screen insulation where it is
connected. The necessary precautions must therefore be taken.

o calculation of the current circulating in screens earthed at both ends

In balanced steady-state operating conditions (or during a three-phase short circuit), the
induced voltage in screens earthed at both ends causes a three-phase current to circulate.
This current is given by the formula:
I0 =

where
Rs
Xs
l

E0
Rs2

+ Xs2

2a
Xs = 0.145 log10 l
d
: screen resistance ()
: screen reactance ()
: length of cable or line

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

580

o example

Let us consider a 20 kV aluminium single-core cable with a cross-sectional area of 300 mm ,


with PE insulation and a length of l = 3 km , buried in soil having a resistivity of = 100 m ,
the characteristics of which are as follows:
-

Icapacity = 500 A

d = 33.5 mm
a = 38.5 mm
Rs = 0.45 / km

It is installed in a network such that:


-

I B = 400 A
Isc = 8 kA

The induced voltage under steady-state operating conditions is:


2a
E0 = 0.145 log10 I B l = 63 V
d
The 50 V limit is exceeded and the screen must therefore be earthed at both ends.

The circulation current in the screen is in this case:


I0 =

E0
Rs2 + Xs2

Rs = 1.35
2a
X s = 0.145 log10 l = 0.157
d
whence

Note:

I0 = 46.4 A

the circulation current in the screen is independent of the cable length.

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

581

The induced voltage in the event of a short circuit is:


2a
E0 sc = 0.145 log10 I sc l = 1 260 V
d
The circulation current in the screen is then:
I0 sc = 927 A
This current must be withstood by the screen for the maximum short-circuit time. This is the
case since it can withstand 1 350 A for 2 s (see table 6-38).
Note:

if the cable length was 2 km, the screen would be earthed at one end only. The voltage induced
in the screen on occurrence of the short circuit will then be equal to 840 V. In this case it is
necessary to check that the screen insulation at the point where the terminal box is located is
sufficient.

Evaluation of Ws losses in the screen


Ws = Rs I02
for

Rs = 0.45 / km , l = 3 km

and

I0 = 46.4 A

Ws = 0.45 3 (46.4 )2 = 2.9 kW


The losses in the core are:
Wc = Rc I B2
Rc : core resistance
For an aluminium conductor with a cross-sectional area of S = 300 mm , Rc = 0.1 / km
whence

Wc = 0.1 3 ( 400)2 = 48 kW

We determine the ratio

Ws
=6%
Wc

The screen losses represent 6 % of the core losses. They must therefore be taken into
account when determining the maximum current-carrying capacity of the cable.

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

582

o thermal effect in the cable screens

As we saw in the previous example, when the screen is earthed at both ends, the continuous
circulation of induced current in the screen causes extra heating in the cable and consequently
reduces its current-carrying capacity.
Generally, this phenomenon is only to be taken into account for cables with a cross-sectional
area greater than 240 mm.
We can apply the following rule:
- thin screen without armour, for S > 1 000 mm the current-carrying capacity is reduced by 5 %
- non-thin screen without armour, the current-carrying capacity is to be reduced by:
. 5 % for
. 10 % for

240 mm S 800 mm
S > 800 mm

- cables with screen and armour, the current-carrying capacity is to be reduced by:
. 5 % for
. 10 % for
. 15 % for

240 mm S 400 mm
500 mm S 800 mm
S > 800 mm

n three-core cables
For three-core collectively screened cables, the electromagnetic field is zero in balanced
operating conditions.
In normal operating conditions, there is no circulation current in the screen.

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

583

6.2.9.

Application example

Let us determine the conductor cross-sectional area of the W1 wiring system inserted into the
network illustrated in figure 6-17.
The W1 wiring system is made up of three single-core three-phase 6/10 (12) kV aluminium
cables with XLPE insulation, directly installed in a enclosed channel in a temperature of 35 C.
The time delay of the protection against phase-to-phase short circuits is: t = 0.2 s .

20 kV
T1

1000 A

S n = 10 MVA
U sc = 8 %

U n = 5.5 kV

W1 wiring system
l = 1200 m

T2

S n = 630 kVA
U sc = 4 %

400 V
Figure 6-17: diagram of the installation

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

584

n determining the maximum design current I B


The W1 wiring system only feeds the 630 kVA power transformer T2 .
The current I B is thus taken to be equal to the nominal transformer current:
I B = In =

Sn
630 10 3
= 66 A
=
3 Un
3 5.5 10 3

n correction factors and choice of S1


The direct installation in an enclosed channel corresponds to installation type L4
table 6-23). Column (3) in the current-carrying capacity tables must be used.

(see

The correction factors to be applied are:


- installation method: f0 = 0.8
- ambient temperature (see table 6-24): f1 = 0.96
- group of several cables (see table 6-28): f 5 = 1

The overall correction factor is: f = 0.8 0.96 = 0.77


The equivalent current that the cable must be able to carry in standard installation conditions
is:
I
I z = B = 86 A
f
Table 6-31 (column (3), XLPE, aluminium) gives a minimum cross-sectional area of
S1 = 16 mm2 which has a current-carrying capacity of I 0 = 95 A .

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

585

(S 2 )

n checking thermal withstand

Neglecting the impedance upstream of the transformer and the impedance of the transformerbusbar connection, the maximum short-circuit current at the origin of the cable is equal to the
short-circuit current of the transformer.
The impedance of the transformer T1 is:

5.5 10 3
Un2 U sc

=
ZT 1 =
Sn 100
10 10 6

8
= 0.242
100

The maximum short-circuit current is thus:


Isc = 11
.

Un
5.5 10 3
= 11
= 14.4 kA
.
3 ZT 1
3 0.242

(see Protection guide 4.2.1)

The cross-sectional area complying with the short-circuit requirement is:


I
S2 sc
k

k = 94 : value of the coefficient corresponding to a XLPE-insulated aluminium conductor (see table 6-35)
t = 0.2 s : short-circuit time equal to the protection time delay
whence

S 2 69 mm2

The minimum cross-sectional area to be chosen is thus S 2 = 70 mm2

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

586

n checking the cable screen thermal withstand ( S3 )


The 5.5 kV distribution network has an earthing system with a 1 000 A current limiting resistor.
The fault current is then:
If =

Vn
+ IC
RN

(see Protection guide 4.3.2)

Vn : single-phase network voltage


RN : limiting resistance

I C : 5.5 kV network capacitive current ( I C = 3 j C Vn )

The capacitive current of an industrial network is of the order of several amps to several dozen
amps and it can thus be neglected in relation to the 1 000 A limiting current.

We thus have I f = 1 000 A


We assume that the screen must be able to withstand the fault current for 2 seconds, in order
to take into account the maximum time delay of the protection against phase-earth faults and
eventual reclosing.
The cross-sectional area of the conductor complying with the thermal withstand of the cable
screen is then:
S3 = 50 mm2

(see table 6-37)

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

587

n checking voltage drops


The voltage drop is given by the formula:
l

V = 1 cos + l sin I B

S
l = 1 200 m ; S = 70 mm ; = 0.15 10 3 / m ; I B = 66 A ; 1 = 0.036 mm 2 / m
We assume that the cable load has a cos = 0.6 (sin = 0.8)
whence

1 200

V = 0.036
0.8 + 0.15 10 3 1 200 0.6 66

50
V = 53 V

The relative voltage drop is:

53
V
=
= 1.7 %
Vn 5500
3

In spite of a very long cable length for an industrial network, the voltage drop is acceptable.

n choosing the technical cross-sectional area


The calculations carried out give the following cross-sectional areas:
S1 = 16 mm
S 2 = 70 mm
S3 = 50 mm

The technical cross-sectional area to be chosen is thus:


S = 70 mm

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

588

6.3.

Calculating the economic cross-sectional area

The methods described in chapters 6-1 and 6-2 lead to the choice of technical cross-sectional
areas of wiring systems, complying with the different thermal withstands, voltage drops and
protection of persons.
But it may be useful to take into account the economic criterion, based on the cost of
investment and the operating costs, when looking for the optimum cross-sectional area.
The investment cost is essentially composed of:
- the cable cost, linear function of the cross-sectional area S and length L ,
i.e. K1 L + K2 L S
- the cost of civil engineering and installation, depending on the length and regardless of the
cross-sectional area in a limited interval, i.e. K3 L .
The operating costs comprise:
- the Joule losses in the cable
- the maintenance costs.
To calculate the economic cross-sectional area, only the cost of the Joule losses w relative to
the wiring system is taken into account:
w=n
n

L
HC
I2
S
1 000

Euros.

: number of live conductors


: resistivity of the live conductor during normal service, i.e. 1.25 times that at 20 C.

= 0.0225 mm / m for copper; = 0,036 mm / m for aluminium


L
S
I
H
C

:
:
:
:
:

cable length
cross-sectional area of conductors
current carried, assumed to be constant, in A
number of cable operating hours (for a year H = 8 760)
cost of kWh, Euro/kWh.

The cost of investment and the cost of losses w do not have the same term of payment. It is
necessary to change in order to carry out the sum of their values. This can be done by
converting the operating costs paid at the end of consecutive years to current value, i.e. by
converting them to the period in which the cable is purchased.

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

589

If N (years) is the amortizement time forecast for the cable, and if the price of energy and
the cable load are assumed to be constant for the entire period, the sum of converted values
of Joule losses is:
1
1
1
W =w
+
+ ....... +
2
1 + t (1 + t )
(1 + t ) N

(1 + t ) N 1
= w
N

t (1 + t )

t being the forecast conversion to current value rate.

t (1 + t )
w
We can write W =
, where A =
A
(1 + t ) N 1
N

The total cost is therefore:


P ( S) = K3 L + K1 L + K2 L S + n

L 2 HC
I
S
1 000 A

The function P ( S ) goes via a minimum


= 0
S

for a cross-sectional area of S0 = I

nHC
K2 A 1 000

For an approximate calculation we can use the following formula:


S0 =

KI
100

HC
, mm
A

where K = 2.56 for copper and 4.61 for aluminium.


The value of the economic cross-sectional area to be chosen is the closest standard
value to S 0 .

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

590

n example
Taking the elements from the application example of 6.2.9:
- design current I B = 66 A
-

energy cost: C = 0.061 Euro/kWh

- aluminium conductor, K = 4.61


- conversion to current value rate of 8 %
- amortizement time N = 20 years
- number of operating hours H = 3 800 hours.
A=

0.08 (1 + 0.08)

S0 =

20

(1 + 0.08)20 1

= 0.102

66 4.61 3 800 0.061


= 145 mm
100
0.102

The economic cross-sectional area is the closest standard value to S 0 , i.e. S = 150 mm2 .
In practice, the economic cross-sectional area is often greater than the technical crosssectional area.

n advantages of cable oversizing


- Improved voltage quality under normal operating conditions and reduced amplitude of
voltage surges during motor or other machine starting.
- Presence of reserve power offering the possibility of future extensions.

Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.

Industrial electrical network design guide

T&D

6 883 427/AE

You might also like