Legrand Circuit Breakers
Legrand Circuit Breakers
protection devices
01 | Sustainable
development
08 | Protection
against external
disturbances
02 | Power balance
and choice of power
supply solutions
09 | Operating
functions
03 | Electrical
energy supply
10 | Enclosures
and assembly
certication
IE D
CER
T IF
POWER GUIDE:
A complete set of technical documentation
04 | Sizing conductors
and selecting
protection devices
11 | Cabling
components and
control auxiliaries
05 | Breaking
and protection
devices
12 | Busbars
and distribution
06 | Electrical
hazards and
protecting people
13 | Transport and
distribution inside
an installation
07 | Protection
against lightning
effects
Annexes
Glossary
Lexicon
05
POWER GUIDE
EX29009
05
EX29009_couv.indd 1
11/05/09 13:52:26
INTRO
In accordance
rdance with its policy of continuous
ous improvement,
nt,
t, the Company reserves
res
reser
the
th right
rrigh to
t change
c
specifica
specifications
specificatio
ecif
and designs
signs without
thout notice.
ice. All illustrations,
ations,
ns, descriptions,
ons,
ns,
s,, dimensions and we
weig
weights
in this
th catalogue
c
are
e ffor gu
guidance
guida
and cannot
nnot be held
eld binding
ding on the Co
Company.
o mpany.
any
EX29009_couv.indd 2
11/05/09 13:52:27
Circuit breakers
04
Technologies used . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 04
Characteristics of circuit breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . 06
Tripping curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 08
Limitation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
DMX3
12
range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Technical characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Electronic protection units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Communication and supervision . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Connecting DMX3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Supply inverters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Performance data and limitation curves . . . . . . . . . . . . . . . . . . . . . . . . 30
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
44
01
EX29009_001-015.indd 01
11/05/09 13:59:47
54
90
94
110
112
114
EX29009_001-015.indd 02
11/05/09 13:59:47
Fuses
122
130
Back-up protection
138
144
Choice of products
DMX3
ACBs and
DMX3-I
160
trip-free switches . . . . . . . . . . . . . . . . . . . . 160
EX29009_001-015.indd 03
11/05/09 13:59:47
Circuit breakers
TECHNOLOGIES USED
Overcurrents are detected by three different devices:
thermal for overloads, magnetic for short circuits and
electronic for both. Thermal and magnetic releases,
which are generally combined (thermal-magnetic
circuit breakers), use an economical, tried and tested
technology, but provide less flexibility of adjustment
than electronic releases.
TECHNOLOGIES USED
Product standards
Installation standards
1 THERMAL RELEASE
This consists of a bi-metal strip which, if heated
beyond the normal operating values, becomes deformed, releasing the lock holding the contacts.
The reaction time of a bi-metal strip is inversely proportional to the intensity of the current. As a result
of its thermal inertia, the bi-metal strip reacts faster
when a second overload follows the first in quick succession. This improves the protection of the cables,
the temperature of which is already higher.
DPX circuit breakers enable the trip current Ir to
be set between certain limits (0.4 to 1 In depending
on the model).
2 MAGNETIC RELEASE
This consists of a magnetic loop whose effect releases
the lock holding the contacts, thus triggering breaking
if there is a high overcurrent. The response time is
very short (around one tenth of a second). DPX moulded case circuit breakers have an Im setting (up to
10 x Ir), which can be used to set the trip value to the
protection conditions of the installation (fault current
and indirect contact).
Moreover this setting, when combined with a time
delay, can be used to find the best discrimination
conditions between the devices.
04
EX29009_001-015.indd 04
11/05/09 13:59:47
3 ELECTRONIC RELEASE
Thermal-magnetic release
t
Thermal
release zone
Magnetic
release zone
Electronic release
t
Long delay
operating zone
Short delay
operating zone
Instantaneous
operating zone
Electric arc
I
Prospective
Isc
Limited Isc
Arc U
Mains U
Energy
limiting
Restored
voltage
t
TECHNOLOGIES USED
05
EX29009_001-015.indd 05
11/05/09 13:59:47
4 UTILIZATION CATEGORY
06
EX29009_001-015.indd 06
11/05/09 13:59:47
CAPACITY Ics
9 SHORT-TIME WITHSTAND
CURRENT Icw (in kA)
This is the value of the short-circuit current that a
category B circuit breaker is capable of withstanding
for a defined period without altering its characteristics. This value is intended to enable discrimination
between devices. The circuit breaker concerned can
remain closed while the fault is eliminated by the
downstream device as long as the energy I2t does not
exceed Icw2 (1 s).
By convention the value Icw is given for a time
t = 1 s. For a different duration t, this must
be indicated, for example Icw0.2. It is then
necessary to check that the thermal stress
I2t, generated until the downstream device
breaks, is actually less than Icw2t.
Product standards
Standard IEC 60898-1
In practice, reference is made to this standard for the
terminal circuits of household, residential and small
business installations, where those involved are not
qualified. It applies up to 125 A, 25 000 A breaking
capacity and 440 V. Thermal tripping takes place
between 1.13 and 1.45 In. It determines operating
ranges, such as B, C, D, etc. for magnetic tripping.
Products complying with standard IEC 60898 can also
be used in industrial installations as far as their characteristics permit.
Standard IEC 60947-2
This standard is used in industry, and assumes that
those involved are qualified. It does define an operating range: all characteristics (Ir, Im, t, etc.) can be
adjusted.
Legrand DX circuit breakers comply with
both standards.
Standard IEC 61009-1
This applies to circuit breakers with a residual
current function.
Standard IEC 61008-1
This applies to residual current circuit breakers.
8 STANDARD BREAKING
07
EX29009_001-015.indd 07
11/05/09 13:59:47
10 000
t (s)
t (s)
Tr = 30 s 20 %
1 000
1000
Tr = 20 s 20 %
Tr = 10 s 20 %
Tr = 5 s 20 %
100
100
10
10
I2t = K
1
Im
Adjustable magnetic
release zone
0.1
In: 1 600 A
In: 1 250 A
0.1
Im
Tm
0.01
0.001
0.01
3 4 5
10
20
30
50
100
I/Ir
0.001
If
0.2
3 4 5
I/Ir
I: actual current
Ir: thermal protection against overloads
(Ir setting = x In)
Im: magnetic protection against short circuits:
(Im setting = x Ir)
TRIPPING CURVES
In: 630 A
10
7 10
30
70
I/In
I: actual current
Ir: long delay protection against overloads
(adjustable: Ir = x In, 0.4 to 1 x In)
Tr: long delay protection operation time
(adjustable: 5 to 30 s) up to 6 x Ir
Im: short delay protection against short circuits
(adjustable: Im = x Ir, 1.5 to 10 Ir)
Tm: short delay protection operation time
(adjustable: 0 to 0.3 s)
I2t constant (adjustable via Tm) see p. 146
If: fixed threshold instantaneous protection
(fixed: 5 to 20 kA depending on the model)
08
EX29009_001-015.indd 08
11/05/09 13:59:47
10000
t (s)
1000
200 s
100
10
6s
3s
1s
1
In: 630 A
In: 500 A
In: 400 A
In: 320 A
0.1
0.01
0.001
If
0.2
3 4 56
10
7 10
I/Ir
30
70
I/In
long delay
short delay
instantaneous
long delay
instantaneous
TRIPPING CURVES
I = If = 5 kA
Im = 7 x Ir = 3528 A
Im = 10 x Ir = 5040 A
instantaneous
Im = 5 x Ir = 2520 A
long delay
I = Ir = 504 A
09
EX29009_001-015.indd 09
11/05/09 13:59:47
100
10
0.1
0.01
0.001
1
3 4 5
10
20 30
50
100
200
x In
LIMITATION
If there is a short circuit, without any protection, the
current that would flow through the installation is
the prospective short-circuit current.
When a short-circuit current crosses a circuit
breaker, the circuit breaker has the capacity, to a greater or lesser extent, to allow only part of this current to
flow. The short circuit is then limited in amplitude
and duration.
The purpose of limitation is to reduce:
- Thermal stress
- Electrodynamic forces
- Effects of electromagnetic induction
It also makes discrimination and combination easier.
The limitation capacity of devices is represented in the
form of limitation curves.
Prospective Isc
Prospective
rms Isc
Limited
peak Isc
Limited Isc
10
EX29009_001-015.indd 10
11/05/09 13:59:47
1 CURRENT LIMITATION
2 THERMAL STRESS
CURVES
LIMITATION CURVES
Current limitation
I2t (A2s)
Limited
peak Isc
l
Un
im
ite
a
pe
c
Is
Device
breaking
capacity
Prospective Isc
at the device terminals
Prospective
rms Isc
Device breaking
capacity
Icc (A)
Thermal
trip zone
Magnetic
trip zone
LIMITATION
11
EX29009_001-015.indd 11
11/05/09 13:59:48
DMX3
air circuit
breakers
3-poles
DMX3-H 2500
fixed version
Composition of a DMX 3
All the circuit breakers are supplied as standard with:
- Manual control
- Terminal blocks for connecting output auxiliaries
- Connection plates
- 4 auxiliary changeover contacts
- Cover for access to lockable settings
- Mechanical indication of activation
And for draw-out versions:
- Mobile contacts for connecting auxiliaries
- IP 40 protection in draw-out position
- Retractable handles
- Padlock of the circuit breaker in inserted-draw-out
position
F1
F1
F1
F1
F1
F1
F2
F2
F1
F1
F1
F1
F1
F1
F2
F2
F2
F2
F2
F2
F2
F2
F2
F2
12
EX29009_001-015.indd 12
11/05/09 13:59:48
Draw-out DMX 3
Isolator terminal blocks
for auxiliary contacts
Key lock
in Open position
Reset button
Indicator showing
the position of the main
contacts O / I
Key locking in
drawn-out position
200 mm
600 mm
200 mm
600 mm
200 mm
13
EX29009_001-015.indd 13
11/05/09 13:59:49
Characteristics
TECHNICAL CHARACTERISTICS
Frame
F1
Number of poles
Nominal rating protection unit In (A)
Nominal rating In (A)
Rated insulation voltage Ui (V)
Rated impulse withstand voltage Uimp (kV)
Rated operating voltage (50/60Hz) Ue (V)
230 V AC
415 V AC
500 V AC
Ultimate breaking capacity Icu (kA)
600 V AC
690 V AC
Service breaking capacity Ics (% Icu)
230 V AC
415 V AC
Closing capacity on short circuits Icm
500 V AC
(kA)
600 V AC
690 V AC
230 V AC
415 V AC
Short-time withstand current Icw (kA)
500 V AC
for t = 1 s
600 V AC
690 V AC
Neutral protection (% In)
Category of use
Isolation capability
Opening time
Closing time
Endurance (o.c. cycles) mechanical
Endurance (o.c. cycles) electrical
Operating temperature
Storage temperature
DMX 3 4000
F1
3P - 4P
800-2500
800-2500
1000
12
690
65
65
65
60
55
100%
143
143
143
132
121
65
65
65
60
55
OFF-50-100
B
YES
15ms
30ms
10000
5000
-5C to +70C
-25C to +85C
50
50
50
50
50
105
105
105
105
105
50
50
50
50
50
L
F2
N
F2
100
100
100
75
65
50
50
50
50
50
220
220
220
165
143
85
85
85
75
65
105
105
105
105
105
50
50
50
50
50
H
F2
L
F2
3P - 4P
3200-4000
3200-4000
1000
12
690
65
65
65
65
65
100%
143
143
143
143
143
65
65
65
65
65
OFF-50-100
B
YES
15ms
30ms
10000
5000
-5C to +70C
-25C to +85C
100
100
100
75
65
220
220
220
165
143
85
85
85
75
65
Frame
F1
F2
F1
F2
DMX3 2500
DMX3 4000
8 00 A
1000 A
1250 A
1600 A
2000 A
2500 A
20
16
51
31
32
25
80
48
50
39
125
75
82
64
205
123
128
100
320
192
200
156
500
300
3200 A
4000 A
256
400
492
768
14
EX29009_001-015.indd 14
11/05/09 13:59:49
Temperature derating
Ambient temperature
Version
Device
DMX3 2500
Fixed
DMX3
4000
DMX3 2500
Draw-out
DMX3 4000
Up to 40C
50C
60C
65C
70C
Imax (A)
Ir / In
Imax (A)
Ir / In
Imax (A)
Ir / In
Imax (A)
Ir / In
Imax (A)
800
800
800
800
800
Ir / In
1
1000
1000
1000
1000
1000
1250
1250
1250
1250
1250
1600
1600
1600
1600
1600
2000
2000
1960
0,98
1920
0,96
1880
0,94
2500
2450
0,98
2350
0,94
2250
0,9
2150
0,86
3200
3200
3200
3136
0,98
3008
0,94
4000
3920
0,98
3680
0,92
3440
0,86
3120
0,78
800
800
800
800
800
1000
1000
1000
1000
1000
1250
1250
1250
1250
1250
1600
1600
1600
1600
1600
2000
2000
1960
0,98
1920
0,96
1875
0,94
2500
2400
0,96
2250
0,9
2100
0,84
1950
0,78
3200
3200
3200
3072
0,96
2880
0,9
4000
3760
0,94
3440
0,86
3200
0,8
2960
0,74
Altitude derating
Altitude (m)
< 2000
3000
4000
Ue (V)
690
600
500
440
Ui (V)
1000
900
750
600
In
0.98 x In
0.94 x In
0.9 x In
In (A) (T = 40C)
5000
Frame 1
3P
4P
width (mm)
273
358
327
412
depth (mm)
height (mm)
volume (dm3)
354
419
41
41
39
408
354
419
61
59
57
354
419
53
48
45
538
354
419
80
76
73
433
473
67
77
75
425
433
473
87
108
106
433
473
84
94
91
555
433
473
114
137
134
weight (kg)
Frame 2
Draw-out
4P
DMX3
DMX3-I
width (mm)
depth (mm)
height (mm)
volume (dm3)
weight (kg)
DMX3
DMX3-I
TECHNICAL CHARACTERISTICS
Fixed
3P
15
EX29009_001-015.indd 15
11/05/09 13:59:49
Ir
Tr
Im
LSI
t
Ir
Tr
Im
Tm
Ii
I
LSIg
t
t
tg
Ig
Ir
Tr
I
Im
Tm
Ii
I
Ig settings
Ii settings
Im settings
Ir settings
LEDs indicating
correct operation
tg settings
tm settings
tr settings
Mini USB
connector
Neutral protection
16
EX29009_016-031 16
11/05/09 14:01:36
Ir
Tr
Im
Tm
Ii
I
LSIg
Settings lock
tg
Ig
Ir
Tr
ON button
Im
USB port
Tm
Ii
Leds indicating
correct operation
17
EX29009_016-031 17
11/05/09 14:01:37
MP6
LI
LSI
LSIg
LSI
LSIg
Ii adjustable: 2-3-4-6-8-10-12-15-Icw x In
Ig adjustable: OFF-0.2-0.3-0.4-0.5-0.6-0.7-0.8-1 x In
Id adjustable: OFF-1-1-3-3-10-10-30-30 A
optional
optional
optional
optional
optional
td adjustable: 0.1-0.1-0.3-0.3-1-1-3-3 s
optional
optional
optional
optional
optional
4P: OFF-50-100-200%Ir
(no 200% up to 1250 A and 100% above
Current
Current
Position: open/closed/fault
Date, time and reason for last activation
Required protection
Date and time
Activation counter
Memorisation
18
EX29009_016-031 18
11/05/09 14:01:38
MP6
LSI
LSIg
LSI
LSIg
ModBus on RS485
optional
optional
optional
optional
optional
Overheating >75C
Logical discrimination
Management of non-priority loads
Power return: 0.1 to 20 s - 5 to 100% Ir
Current imbalance: 1 to 3600 s - 100 to 600 V
Signalling
and alarms
Memory settings
If a device is changed, the electronic tripping unit
retains the settings and all the data recorded during
operation of the breaker which was previously installed (faults, operations, currents, etc).
This function makes maintenance safe and reduces
downtime to a minimum. The settings are thus no
longer associated with the device, but with the circuit
which is being protected.
On standard, all protection units are equipped with
batteries so you can monitor and adjust the parameters even when the breaker is not connected. For
example, its possible to set the protection unit before
install the breaker or see the info inside during a trip.
External links
19
EX29009_016-031 19
11/05/09 14:01:38
Conversion interface
(RS-485/RS232,
RS-485/USB etc.)
Power
RS-485 link
Circuit breaker/module links
Generator set
Mechanical interlock
Interface for
electronic DPX
Interface
for electronic
DPX
20
EX29009_016-031 20
11/05/09 14:01:38
ACCESSORIES
1 SHUNT TRIP
Shunt trips are devices used for the remote instantaneous opening of the air circuit breaker. They are
generally controlled trough an N/O type contact. The
current range of shunt trips proposes five supply voltages from 24 V to 415 V). The shunt trips are already
equipped with a special fast connector, to be directly
inserted into auxiliary contact block. An auxiliary
contact is connected in series with the coil, cutting off
its power supply when the main poles are open
- Nominal voltage Un: - 24, 48, 110, 230 V AC/DC
- 415 V AC
- Tolerance on nominal voltage: 70 to 110% Un
- Maximum power consumption (for 180 ms):
500 VA AC/500 W DC
- Continuous power: 5 VA AC/5 W DC
- Maximum opening time: 30 ms
- Insulation voltage: 2 500 V 50 Hz for 1 min
- Endurance on pulse: surge proof 4 kV 1.2/50 ms
U1
UVR ST CC
OF1 OF2
2 UNDERVOLTAGE RELEASE
3 CLOSING COILS
These coils are used for remotely controlling the closing of the power contacts of the circuit breaker.
The output
terminal block
has automatic
terminals
for connection
without screws
ACCESSORIES
21
EX29009_016-031 21
11/05/09 14:01:38
5 SIGNALLING CONTACTS
All DMX3 air circuit breakers are equipped as standard
with 4 auxiliary contacts that can be used indipendently like NO or NC contact.
Its also possible to more auxiliary contacts up to
reach the number of 10.
Mounting auxiliaries
Auxiliaries are very easy to mount in the top part
of the DMX3, behind the front panel.
The positions are marked to prevent mounting
errors. It is possible to install up to 2 current shunt
trips or 2 undervoltage releases and a closing coil.
Auxiliaries are identified on the front panel.
The front panel of the DMX3 has windows so that
users can check what auxiliaries are installed
and their characteristics.
Shunt trip
1
0
2
1
1
1
Closing
coil
Undervoltage
release
ACCESSORIES
Motor
operator
22
EX29009_016-031 22
11/05/09 14:01:38
Connection diagram
U2
MOT
ACCESSORIES
U1
ELECTRIC CHARGING
DEVICE
164
RC
161
READY TO CLOSE
154
SC
151
SPRINGS CHARGED
102
OF 10
101
OF 9
91
OF 8
81
OF 7
71
OF 6
61
OF 5
51
OF 4
41
OF 3
31
OF 2
21
OF 1
11
104
92
94
82
84
72
ADDITIONAL
CONTACTS NO/NC
74
62
DMX3 draw-out circuit breakers are provided as standard with safety padlocking shutters preventing access
to live terminals. They have a number of other safety
devices, such as:
Key-operated locks:
- Main contacts open
- Circuit breaker in draw-out position
Padlocks for:
- Main contacts open
- Contact shutters closed (for draw-out position)
Door locking:
in order to prevent the opening of the electrical swhichboard door when the contacts of the ACB are closed.
64
52
54
42
44
32
34
22
4 AUXILIARY CONTACTS
(standard)
24
12
C2
D2
142
C3
CC
C1
ST
D1
UVR
UVR ST CC
C4
CLOSING COIL
TR
14
SHUNT TRIP
TR
141
OF 13
131
TRIPPED SIGNAL
OF 12
121
OF 11
111
UVR SIGNAL
144
132
134
122
112
114
+12Vdc
28801
28802
L3
L2
L1
N
PROTECTION
CONTROL UNIT
MAIN
CIRCUIT
ACCESSORIES
124
23
EX29009_016-031 23
11/05/09 14:01:39
Draw-out version
Draw-out version
breakers are supplied
with rear terminals for
flat connection
Fixed version
Reversible connectors
allow vertical or horizontal
connection
Spreaders
CONNECTING DMX3
For flat
connection
For vertical
connection
For horizontal
connection
24
EX29009_016-031 24
11/05/09 14:01:41
Vertical
connection
Ambient temperature
Horizontal or
at connection
In (A)
35C
45C
55C
Copper bars
(mm2)
800
800
800
800
1 x 60 x 10
1000
1000
1000
1000
1 x 80 x 10
1250
1250
1250
1250
1 x 80 x 10
1600
1600
1600
1600
2 x 60 x 10
2000
2000
2000
1800
2 x 80 x 10
2500
2500
2500
2500
3 x 80 x 10
3200
3200
3100
2800
3 x 100 x 10
4000
4000
3980
3500
4 x 100 x 10
800
800
800
800
1 x 60 x 10
1000
1000
1000
1000
1 x 80 x 10
1250
1250
1250
1200
2 x 60 x 10
1600
1550
1450
1350
2 x 80 x 10
2000
2000
2000
1750
3 x 80 x 10
2500
2500
2450
2400
3 x 80 x 10
3200
3000
2880
2650
3 x 100 x 10
4000
3600
3510
3150
6 x 60 x 10
Horizontal
Vertical
Vertical
Horizontal
Flat
CONNECTING DMX3
Connection options
25
EX29009_016-031 25
11/05/09 14:01:41
DMX3 supply inverters used with XL3 4000 enclosures enable very intuitive configuration of assemblies
and busbars, as shown in the examples below.
D1
D1
SUPPLY INVERTERS
D2
D2
26
EX29009_016-031 26
11/05/09 14:01:42
G
D1
D1
D3
D3
priority
circuits
D2
D2
Priority circuits
D1
D1
D2
priority
circuits
D2
D4
Priority circuits
non priority
circuits
group 2
The ambient temperature in the enclosure must be limited as far as possible to a value which does not exceed
40C. Above this limit it becomes necessary to modify the permissible current value in the protection devices
and the bars (see p. 15).
SUPPLY INVERTERS
D3
D4
27
EX29009_016-031 27
11/05/09 14:01:42
SUPPLY INVERTERS
D1
D2
D1
D2
D1
D3
D3
D2
D1
D2
D3
D1
D2
O
I
O
O
O
I
D1
D2
D3
O
I
O
O
O
O
I
O
O
O
O
I
D1
D2
D3
O
I
O
O
I
O
I
O
O
O
I
I
I
O
O
O
I
O
O
I
I
D1
D2
D3
O
I
O
I
O
O
O
O
O
I
O
O
I
I
O
28
EX29009_016-031 28
11/05/09 14:01:42
Type of
cable
Length
(m)
1
2
3
4
5
6
2.6
3
3.6
4
4.6
5.6
H (mm)
0
0
V
(mm)
Type 3
800 to 1000
Type 1
Type 2
Type 5
1000 to 2000
Type 3
Type 4
Type 6
SUPPLY INVERTERS
Distances
between devices
29
EX29009_016-031 29
11/05/09 14:01:42
103
102
Tr = 30s (20%)
10
Tr = 20s (20%)
I 2t = K
Tr = 10s (20%)
Tr = 5s (20%)
1
Im = 1.5lr (20%)
Im = 10lr (20%)
If = 1000A
If = 630A
If = 1600A
0.01
0.01
If = 1250A
If = 2500A
If = 2000A
0.001
0.5
I/Ir
10
3 4 5
10
I/In
20 20
30
If = 800A
40 50
70
102
I/In
30
EX29009_016-031 30
11/05/09 14:01:43
t(s)
104
103
102
Tr = 30s (20%)
10
Tr = 20s (20%)
I 2t = K
Tr = 10s (20%)
Tr = 5s (20%)
1
Im = 1.5lr (20%)
Im = 10lr (20%)
If = 1000A
If = 1600A
0.01
If = 630A
0.01
If = 1250A
If = 2000A
If = 800A
0.001
1
I/Ir
10
3 4 5
10
I/In
20 20
30
40 50
I/In
70
102
If = 2500A
31
EX29009_016-031 31
11/05/09 14:01:43
t(s)
104
103
102
Tr = 30s (20%)
10
Tr = 20s (20%)
I 2t = K
Tr = 10s (20%)
Tr = 5s (20%)
Im = 1.5lr (20%)
Im = 10lr (20%)
If = 3200A
If = 2000A
0.01
If = 1250A
If = 630A
If = 800A
0.01
If = 4000A
If = 1600A
If = 2500A
0.001
0.5
I/Ir
10
3 4 5
10
I/In
20 20
30
40 50
If = 1000A
70
102
I/In
32
EX29009_032-049.indd 32
11/05/09 15:03:31
104
1010
t(s)
I2t(A2s)
103
0.2... In
DMX3-L
DMX3-H
109
102
DMX3-N
108
t = Cost
101
l2t = Cost
1
107
0.1... I s
10-1
106
10-2
10-2
10-1
10
102
Ig/In
105
10
20
30
40 50
100
Icc (kA)
10-3
33
EX29009_032-049.indd 33
11/05/09 15:03:31
60
60
35
132
45.5
59
82
354
85
30
85
15
45.5
45.5
85
85
85
85
85
85
45.5
58
50
60
9x4
36
11 x 2
40
30
48.5
85
70
50
9x4
40
DIMENSIONS
11
70
50
60
85
223.5
30
74
20
14
3P=4P= 107.5
90
95
357
419
20
11 x 4
20
34
EX29009_032-049.indd 34
11/05/09 15:03:31
70
50
106
70
50
106
M8
70
70
50
190
116.5
50
116.5
M8
34
35
49.5
393
308
70
40
17.5
11
70
13
13
20
20
20
20
20
40
70
40
11
11
70
40
DIMENSIONS
70
16.5
13
16.5
70
52.5
83
35
EX29009_032-049.indd 35
11/05/09 15:03:31
526
198
419
30
90
115
357
30
198
175
175
350
480
408
538
14
132
74
223.5
59
82
36
15
14
100
70
10
100
130
68
68
130
130
130
68
130
130
35
11
21
21
DIMENSIONS
10
15
15
15
130
130
11
35 35
15
10
130
35
100
70
100
68
35
30 10 25
51
100
50
11
130
36
EX29009_032-049.indd 36
11/05/09 15:03:32
350
116
76
51
30
113
115
151
74
111
226
80
417
473
80
473
50
80
41.5
116.5
116.5
41.5
106
106
41.5
80
170
110
106
41.5
70
50
20
70
50
R1
11 x 2
30
DIMENSIONS
36
9x4
37
EX29009_032-049.indd 37
11/05/09 15:03:32
78
350
3P=4P=207
117
100
70
53
30
113
74
98.5
228.5
charged
70
100
473
AUT
100
MAN
473
417
OK
100
M10
77
130
130
77
3P=425 / 4P=555
318
100
70
448
159
48
224
48
170
80
70
100
473
170
80
M10
77
130
130
130
77
30
35
70
100
10
60
16
DIMENSIONS
10.5 (4x)
35
35
38
EX29009_032-049.indd 38
11/05/09 15:03:32
20
Frame 1
60
90
20
95
60
45.5
354
85
85
45.5
45.5
85
85
85
45.5
Frame 2
100
90
30 85
30
100
354
68
130
130
68
68
130
130
130
68
Termination support
150 mm max
DIMENSIONS
11mm
39
EX29009_032-049.indd 39
11/05/09 15:03:33
407
116.5
106
41.5
106
106
41.5
M8
356
70
115
70
50
433
151
151
80
80
115
50
50
M8
Horizontal connection
50
70
20
70
20
30
30
20
115
115
14
151
151
11
85.5
116.5
116.5
41.5
106
106
106
41.5
106
41.5
401
316
Vertical connection
115
115
30
70
14
151
151
DIMENSIONS
11
85.5
116.5
116.5
316
41.5
106
106
401
40
EX29009_032-049.indd 40
11/05/09 15:03:33
100
100
70
70
M10
356
70
130
148.5
148.5
130
70
100
M10
100
Flat connection
77
130
130
77
77
130
130
130
77
433
Horizontal connection
100
100
35 35
35 35
148.5
11
86.5
148.5
130
130
30
16
77
130
130
77
Vertical connection
77
130
130
130
77
100
100
35 35
35 35
86.5
77
130
130
77
77
130
130
130
77
DIMENSIONS
130
148.5
11
148.5
130
100
35 35
16
41
EX29009_032-049.indd 41
11/05/09 15:03:33
Frame 2
419
250
BUSBAR
250
BUSBAR
419
250
BUSBAR
419
419
250
BUSBAR
215
300
350
273
358
408
480
3 POLES
4 POLES
3 POLES
538
118
4 POLES
Door cut-out
264
132
0 to 50 mm
21.5
Panel door
337
354
Frame 1: 1.5
DIMENSIONS
Frame 2: 66
Corner of
the breaker
42
EX29009_032-049.indd 42
11/05/09 15:03:33
Frame 2
473
250
BUSBAR
473
250
473
250
473
BUSBAR
250
BUSBAR
BUSBAR
305
318
327
412
425
448
555
3 POLES
4 POLES
3 POLES
4 POLES
118
220
Door cut-out
4
13.5
170
432
3.5
3.5
4 (x10)
4
110
4
62
3.5
4
13.5
3.5
124
110
124
Panel door
358
284
Frame 1: 16
Corner of
the base
49.5
DIMENSIONS
Frame 2: 65
43
EX29009_032-049.indd 43
11/05/09 15:03:33
DMX-E
air circuit
breakers
44
EX29009_032-049.indd 44
11/05/09 15:03:33
MP 2G unit characteristics
Overload
Instantaneous
Ir = In x
Tr
Time delay in s
at 6 x Ir
Neutral
protection
IN = Ir x
Is
Is = In x
Ts
Time delay in ms
at 10 x In - I2t Off
Time delay in ms
at 10 x In - I2t On
Ip
Thermal
memory
Ip = Ir x
Ig
Ig = Ir x
Tg
Time delay in s
I2t Off
Time delay in s I2t On
Earth fault
Overload
protection settings
(current & time)
Power On
indication
Short-circuit
protection settings
(current & time)
Fault
indications
Instantaneous
setting
Thermal
reflexivity
& neutral
protection
setting
Earth fault
protection settings
(current & time)
Protection
unit testing
Settings
Ir
Short-circuit
Manual
Reset
% load indication
t
lr
Tr
1.5 - 2 - 3 - 4
5 - 6 - 8 - 10
12 - Max.
0.2 - 0.3 - 0.4
0.5 - 0.6
0.1 - 0.2 - 0.3
0.4 - 1 - Off
0.1 - 0.2 - 0.3
0.4
On/Off
ls
Ts
lg
lp
Tg
Parameters
45
EX29009_032-049.indd 45
11/05/09 15:03:34
DMX-E 55
DMX-E 65
DMX-E 80
DMX-E 100
800 -1000
1250 - 1600
800 -1000
1250 - 1600
2000 - 2500
2000 - 2500
3200 - 4000
2000 - 2500
3200 - 4000
Neutral protection
0/50/100%
0/50/100%
0/50/100%
0/50/100%
0/50/100%
0/50/100%
1000
1000
1000
1000
1000
1000
12
12
12
12
12
12
690
690
690
690
690
690
400/415 VA 50/60 Hz
55
65
65
80
80
100
500/550 VA 50/60 Hz
50
55
55
70
65
85
660/690 VA 50/60 Hz
42
50
50
55
55
75
100% Icu
100% Icu
100% Icu
100% Icu
100% Icu
100% Icu
0.5 s
55
65
65
80
80
100
1s
50
50
55
65
65
70
3s
23
26
35
35
42
50
400/415 VA 50/60 Hz
Service breaking capacity
Ics
500/550 VA 50/60 Hz
660/690 VA 50/60 Hz
400/415 VA 50/60 Hz
121
143
143
176
176
220
500/550 VA 50/60 Hz
105
121
121
154
154
187
660/690 VA 50/60 Hz
88
105
105
121
121
165
40
60
yes
yes
yes
yes
yes
yes
Width 3P
347
347
447
447
647
647
Width 4P
447
447
581
581
847
847
TECHNICAL CHARACTERISTICS
Fixed
device
430
Height
Dimensions (mm)
Draw-out
device
Frame size
335
Depth
Width 3P
347
347
447
447
647
647
Width 4P
447
447
581
581
847
847
II
III
III
Depth
421
Height
433
I
II
46
EX29009_032-049.indd 46
11/05/09 15:03:34
CONTROL ACCESSORIES
Shunt releases are devices used for remote instantaneous opening of the device.
These devices are available in AC and DC versions,
with various supply voltages.
They are simply clipped on to the front panel of the
device. No tool is required.
Nominal voltage: 24, 30, 110, 220, 250 V DC, 110, 220,
240, 380, 415 V AC 50/60 Hz
Maximum power consumption: 650 VA
Operating voltage limit: 70% - 110%
2 UNDERVOLTAGE RELEASES
Undervoltage releases are devices which are generally controlled by an NC type contact. They trigger
instantaneous opening of the circuit breaker if their
supply voltage drops below a certain threshold and in
particular if the control contact opens.
These releases are equipped with an energy saving
device for limiting their consumption in spite of continuous supply.
They are simply clipped on to the front panel of the
device. No tool is required.
Nominal voltage: 24, 30, 110, 220, 250 V DC, 110, 220,
240, 380, 415 V AC 50/60 Hz
Maximum power consumption: 650 VA 0.5 s
Operating voltage limit: 85% - 110%
4 CLOSING RELEASES
These coils are used to remotely control
the closing of the circuit breaker (the circuit breaker
being dependent on the prior loading of the springs).
They are controlled by an N/O type contact.
They are simply clipped on to the front panel of the
device. No tool is required.
Nominal voltage: 24, 30, 110, 220, 250 V DC, 110, 220,
240, 380, 415 V AC 50/60 Hz
Maximum power consumption: 650 VA
Operating voltage limit: 85% - 110%
5 MOTOR OPERATORS
Motor operators, which are available in different
voltages, are used for remotely charging the closing
springs of the circuit breaker.
Combined with an opening release (shunt trip or
undervoltage release) and a closing release,
they can thus be used for remotely controlling
the circuit breaker.
They are easy to mount, with three screws.
Nominal voltage: 24, 30, 48, 60, 110, 125, 250 V DC,
110, 220, 240, 380, 415 V AC 50/60 Hz
Maximum power consumption: 300 VA
Operating voltage limit: 85% - 110%
Undervoltage release or
delayed undervoltage release
Closing release
CONTROL ACCESSORIES
1 SHUNT RELEASES
47
EX29009_032-049.indd 47
11/05/09 15:03:34
Closing release
Shunt release
Operation counter
Motor operator
SIGNALLING CONTACTS
1 FAULT SIGNAL CONTACTS
All DMX-E are equipped as standard with 8 auxiliary
contacts (4NO+4NC).
A fault signal contact can be added to indicate a fault
trip (Cat.No 626317). This contact remains closed
48
EX29009_032-049.indd 48
11/05/09 15:03:34
SUPPLY INVERTERS
The cable mechanical interlock is used to interlock
breakers according to the desired control scheme.
It can interlock 2 or 3 devices, which may not be of
the same type (3P, 4P, fixed, draw-out, mixed) in a
vertical or horizontal configuration.
The interlock units are mounted on the right-hand
side of the device.
Vertical
Horizontal
B
O
O
I
Cable length :
2 meters, min.
Two Incomers
Three Incomers
A B C
A
O
I
O
O
B
O
O
I
O
C
O
O
O
I
A B C
A
O
I
O
I
O
B
O
O
I
I
O
C
O
O
O
O
I
A
O
I
O
I
O
I
I
B
O
O
I
O
I
I
O
C
O
O
O
I
I
O
I
A
O
I
O
Two Incomers
One Standby
Two Incomers
One BusCoupler
Radius at cable
bend : 70 mm
O - Breaker Open
EX29009_032-049.indd 49
Schematic diagram
Cable length :
2 meters, min.
Radius at cable
bend : 70 mm
Cable length :
2 meters, min.
Radius at cable
bend : 70 mm
Cable length :
2 meters, min.
Radius at cable
bend : 70 mm
I - Breaker Closed
(see below)
49
11/05/09 15:03:35
12.9
12.9
B
12.9
12.9
17.5
40
15
19
65
15
17.5
38
38
41
F
G
83.5
16
83.5
16
E
G
Up to 1600 A
Fixed
Draw-out
3P
4P
3P
4P
65
65
65
65
98
98
98
98
65
65
65
65
40
40
27
27
28
28
27
27
40
40
27
27
105
105
105
105
105
105
105
105
105
105
105
105
122
122
129
129
122
122
129
129
122
122
129
129
73.5
73.5
73.5
73.5
90
90
90
90
73.5
73.5
73.5
73.5
100
100
100
100
133.3
133.3
133.3
133.3
100
100
100
100
347
447
347
447
447
581
447
581
647
847
647
847
CONNECTION
50
EX29009_050-065.indd 50
11/05/09 15:05:09
TRIPPING CURVE
10 000
0.4
0.8
0.9
0.5
1.0
0.6
0.7
1000
100
30s
30s
0.5s
10
0.2
0.3
0.4
0.5
1.5
0.6
1.0
4.0
6.0
2.0
0.5s
8.0
10.0
1.0
9.0
0.4
0.1
0.1
0.1
Tr
1.5
2.0
5.0
3.0
Ig
4.0
6.0
Is
8.0
10.0
12.0
Ig
Ip
0.01
0.05
0.1
2.4
10
50
TRIPPING CURVE
Ir
51
EX29009_050-065.indd 51
11/05/09 15:05:10
4P
430
430
A
335
347
A
6
112
Panel
Door
25
435
447
355
Draw-out version
3P
A
6
112
25
Panel
Door
355
4P
7
7
Panel
Door
433
433
Panel
Door
16
isolated
49.5
25.5
250
347
47.5
A
62.4
35
test
250
280
421
16
isolated
100
49.5
25.5
250
47.5
A
62.4
447
35
test
250
280
421
4P
7
430
430
DIMENSIONS
A
435
447
A
112
355
25
Panel
Door
569
581
A
112
25
Panel
Door
355
52
EX29009_050-065.indd 52
11/05/09 15:05:10
Draw-out version
3P
4P
7
433
Panel
Door
433
Panel
Door
16
isolated
A
25.5
100
250
47.5
447
62.4
35
test
250
280
421
25.5
49.5
100
250
47.5
581
62.4
35
test
250
280
421
4P
430
430
A
635
647
A
6
112
25
Panel
Door
835
847
355
Draw-out version
3P
A
6
112
355
4P
7
Panel
Door
433
433
Panel
Door
49.5
Panel
Door
25
100
647
25.5
250
47.5
62.4
250
280
421
16
isolated
35
49.5
test
200
100
847
25.5
250
47.5
62.4
250
280
421
16
isolated
35
test
DIMENSIONS
49.5
16
isolated
53
EX29009_050-065.indd 53
11/05/09 15:05:10
DPX
moulded case
circuit breakers
DPX moulded case circuit breakers offer optimum solutions for the protection requirements
of commercial and industrial installations.
They can be installed:
- On
rail or plate up to 250 A
- On plate up to 1600 A
DPX 125
DPX 160
DPX 250 ER
DPX 250
DPX 630
DPX 1600
Thermal-magnetic releases
Circuit breakers are available in thermal magnetic and electronic versions with nominal currents
from 16 to 1600 A and breaking capacities from
16 to 70 kA. The main characteristics of DPX circuit
breakers are their optimised dimensions, their ease
of installation, use and accessorisation, and their
undisputed reliability.
DPX 125, 160 and 250 ER and their side-mounted earth leakage modules can be installed on
a
rail and under a modular faceplate with
window.
Height spacer Cat. No. 262 99 can be used to
combine modular circuit breakers and DPX on
the same rail.
54
EX29009_050-065.indd 54
11/05/09 15:05:11
2 ELECTRONIC DPX
Electrical performance
and standard references
Marker holders
Characteristics
- Cat No.
- Breaking capacity
- Nominal current (rating)
- Standard
Dynamic selectivity
- Low
- High
Test button
Setting the releases
(cf. p. 59)
Test socket
Sealing of settings
Indicator lamps
- Green: normal operation
- Continuous red: I < 0,9 Ir
- Flashing red: I > 1,05 Ir
55
EX29009_050-065.indd 55
11/05/09 15:05:12
1P
3P - 4P - 3P+N/2
DPX 250 ER
3P - 4P - 3P+N/2
3P - 4P - 3P+N/2
Type of MCCB
16 kA
16 kA
25 kA
36 kA
25 kA
36 kA
50 kA
25 kA
36 kA
50 kA
16-125
290
16-125
500
16-125
500
16-125
500
63-160
500
63-160
500
40-160
500
100-250
500
100-250
500
100-250
500
230
500
250
22
16
10
8
500
250
35
25
18
12
500
250
40
36
20
14
500
250
40
25
20
10
500
250
50
36
25
12
500
250
65
50
30
15
500
250
40
25
20
10
500
250
50
36
25
12
500
250
65
50
30
15
16
25
30
25
36
45
25
36
45
50
100
50
75
100
75
50
100
75
50
32
32
52.5
75.6
52.5
75.6
105
52.5
75.6
105
25000
8000
10000
25000
8000
10000
25000
8000
10000
20000
8000
10000
20000
8000
10000
20000
8000
10000
20000
8000
10000
20000
8000
10000
20000
8000
10000
Isolation capability
Release
Earth leakage
modules(2)
Endurance
(o.c. cycle)
Dimensions
L x H x D (mm)
CHARACTERISTICS
DPX 160
Weight (kg)
thermal magnetic
electronic S1
electronic S2
side by side
underneath
mechanical
electrical (at In)
electrical (at 0.5 In)
1P
16
25 x 120
x 74
3P
4P
3P
4P
75.6 x 120 x 74
101 x 120 x 74
1
1.2
90 x 150 x 74
120 x 150 x 74
1.2
1.6
90 x 176 x 74
120 x 176 x 74
1.2
1.6
56
EX29009_050-065.indd 56
11/05/09 15:05:12
DPX 250
electronic
DPX 630
3P - 4P - 3P+N/2
3P - 4P - 3P+N/2
3P - 4P - 3P+N/2
DPX 630
electronic
3P - 4P - 3P+N/2
DPX 1250
DPX 1600
electronic
3P - 4P - 3P+N/2
3P - 4P - 3P+N/2
36 kA
70 kA
36 kA
70 kA
36 kA
70 kA
36 kA
70 kA
100 kA
40-250
690
40-250
690
40-250
690
40-250
690
250-630
690
320-630
690
250-630
690
400-630
690
400-630
690
690
250
60
36
30
25
20
16
36
690
250
100
70
60
40
25
20
40
690
60
36
30
25
20
16
690
100
70
60
40
25
20
690
250
60
36
30
25
20
16
36
690
250
100
70
60
40
25
20
40
690
60
36
30
25
20
16
690
100
70
60
40
25
20
690
170
100
70
45
28
22
690
250
80
50
45
35
25
20
50
690
250
100
70
65
45
35
25
50
690
80
50
45
35
25
20
690
100
70
65
45
35
25
100
75
100
75
100
75
100
75
50
100
75
100
75
75.6
154
75.6
154
75.6
154
75.6
154
220
105
154
105
154
20000
8000
10000
20000
8000
10000
10000
3000
6000
10000
3000
6000
20000
8000
10000
20000
8000
10000
15000
5000
8000
15000
5000
8000
A(250-400) / B(630 A)
15000
5000
8000
15000
5000
8000
15000
5000
8000
50 kA
70 kA
50 kA
70 kA
10000
4000
8000
10000
4000
8000
CHARACTERISTICS
DPX 250
57
EX29009_050-065.indd 57
11/05/09 15:05:12
Im
DPX 125
DPX 160
DPX 250 ER
DPX 250
DPX 630
DPX 1600
0.7 to 1 In
0.64 to 1 In
0.64 to 1 In
0.8 to 1 In
0.8 to 1 In
Fixed: 10 In
(100 and 125 A)
Fixed: 10 In
3.5 to 10 In
5 to 10 In
5 to 10 In
2
I
t
Ir
Ir
1
2
Settings
tr
3
Im
I2t = K
Im
If
tm
If
5 - 10 - 20 - 30 s (for I = 6 x Ir)
(1.5 - 2 - 2.5 - 3 - 4 - 5 - 6 - 8 - 10 ) x Ir
Fixed: 0.05 s
No
DPX 630: 5 kA
DPX 1600: 10 kA (630 - 800 A); 15 kA (1250 A); 20 kA (1600 A)
(0 - 0.5 - 1 ) x In
RELEASES
Neutral protection
Thermal memory
No
Low/high
Dynamic discrimination
Logical discrimination
Yes
No
Yes
58
EX29009_050-065.indd 58
11/05/09 15:05:12
5 6
0
05
lr
1
90
1.05
Neutral
protection
lr
High
10
Dynamic
discrimination
el
o
ln
1 2
5 6
0FF
Short delay
operation time
0
05
lr
3 2
el
o
Neutral
protection
lr
High
1 01
0FF
30 20
4 5
90
1.05
10 5
30
6 8
tr
2 2.5
7 8 9
9 51
S2
1.5
1.5
10
2 2.5
5 6
0FF
1.5
4 5
4 5
6 8
9 51
6 8
7 8 9
7 8 9
9 51
S1
10
Thermal-magnetic releases
Dynamic
discrimination
Long delay
operation time
Advanced functions
RELEASES
59
EX29009_050-065.indd 59
11/05/09 15:05:13
Connection terminals
and accessories
Terminal shields
Spreaders
Rotary handle
Remote control
Rear terminals
On its own
DPX 1 600
On its own
DPX 630
+ Downstr.
RCD
+ Side RCD
On its own
+ Downstr.
RCD
DPX 250
On its own
Rear terminals
+ Side RCD
Rear terminals
Front terminals
DPX 250 ER
+ Downstr.
RCD
Draw-out
Front terminals
On its own
Plug-in
Rear terminals
+ Side RCD
Fixed
Front terminals
On its own
On rail
DPX 160
+ Downstr.
RCD
DPX 125
Mounting
On plate
60
EX29009_050-065.indd 60
11/05/09 15:05:13
Composition of plug-in
and draw-out versions
Plug-in version
Base
DPX
tulip contacts
Draw-out version
61
EX29009_050-065.indd 61
11/05/09 15:05:13
Debro-lift mechanism
Indicator signalling
the different positions
of the mechanism
2 ELECTRICAL ACCESSORIES
2.1. Current shunt trip
Used to open the device remotely.
It is always connected in series with an NO
control type contact.
62
EX29009_050-065.indd 62
11/05/09 15:05:14
Characteristics of releases
Type of release
Current
shunt trip
70 to 110
35 to 70
85 to 110
< 50 ms
< 50 ms
300
300
5
1.6
Operating time
Inrush power consumption
AC (VA)
DC (W)
Undervoltage
release
the tripped position following operation of the protection unit, an auxiliary release, the residual current
device, or following unplugging. The same product
(Cat. No. 261 60) can be used to perform either the
auxiliary contact or fault contact function, depending
on where it is mounted in the DPX.
These contacts are mounted on the right of the control
switch handle under the devices cover.
Characteristics of auxiliary
or fault signal contacts
Nominal voltage
AC (V )
DC (V )
24 to 230
24 to 230
110 V AC
230 V AC
24 V DC
48 V DC
4
3
5
1.7
Trips
FS
trip
DPX 250
DPX 630
DPX 1600
Auxiliary contact
or fault signal
63
EX29009_050-065.indd 63
11/05/09 15:05:15
2s
2s
10 to 13 s
Opening time
< 90 ms
< 50 ms
< 50 ms
< 50 ms
Closing time
< 100 ms
< 100 ms
< 100 ms
< 100 ms
Number of
operations
24 V DC
Power
consumption 230 V AC
24 V DC
230 V AC
3 SUPPLY INVERTORS
250 W
200 W
300 W
110 W
250 VA
200 VA
300 VA
500 VA
8000
10 000
10 000
5000
64
EX29009_050-065.indd 64
11/05/09 15:05:15
4 CONNECTION OF DPX
Numerous accessories are available to meet all the
various connection requirements. In addition to direct
connection on a plate, they include terminals, distribution terminals, connection extensions, spreaders, rear
screw terminals or rear flat terminals, etc.
Connection
DPX 125
Plates
Cage terminals
Front terminals
Fitted
Fitted
Fitted
Fitted
Fitted
Fitted
High-capacity
terminals
Connection extension
Spreaders
Fixed
Threaded
Flat
Rear terminals
Front terminals
Plug-in
Flat short
Flat long
Plates
Threaded
Flat
Plates
Threaded
Flat
Rear terminals
Front terminals
Draw-out
Rear terminals
Flat
Distribution terminals
65
EX29009_050-065.indd 65
11/05/09 15:05:17
Device
Cage terminals
(included with DPX)
DPX 160
fixed
version
Aluminium terminals
standard
compact
standard
compact
Cross-section
(mm2)
rigid
flexible
S-
(mm2-mm)
S-
(mm2-mm)
S-
(mm2-mm)
S-
(mm2-mm)
70
70
6 x 35
6 x 25
15
15
Direct on plate
18
Cage terminals
Cat. No. 262 18
13
Connection extensions
Cat. No. 262 17
20
95
50-6
50-8
70-10
185-10
70
High-capacity
terminals Cat. No. 262 19
120
95
Distribution terminals
Cat. No. 048 67
6 x 35
6 x 25
DPX 160
plug-in
version
12
Distribution terminals
Cat. No. 048 67
Rear screw terminals
Cat. Nos. 263 00/01
DPX 125
plug-in
version
Copper terminals
Connection
method
Width
(mm)
DPX 125
fixed
version
Conductors
25
120-8
185-10
120-10
25
120-8
185-10
120-10
66
EX29009_066-081.indd 66
11/05/09 15:09:09
Connection
method
Width
(mm)
DPX 250 ER
fixed
version
DPX 250 ER
plug-in
version
DPX 250
fixed
version
DPX 250
plug-in
or draw-out
version
Direct on plate
20
Cage terminals
Cat. No. 262 88
18
Spreader
Cat. Nos. 262 90/91
32
Cross-section
(mm2)
rigid
flexible
Copper terminals
Aluminium terminals
standard
compact
standard
compact
S-
(mm2-mm)
S-
(mm2-mm)
S-
(mm2-mm)
S-
(mm2-mm)
300-10
240-12
300-10
70-8
185
150
185-12
Distribution terminals
Cat. No. 048 68
4 x 35
+ 2 x 25
185-12
95-8
185-12
Direct on plate
25
Cage terminals
Cat. No. 262 35
18
Connection extensions
Cat. No. 262 32
Spreaders
Cat. Nos. 262 33/34
240-12
185-10
95-12
185-10
240-12
95-8
185-10
25
150-12
300-10
240-12
300-10
32
185-12
300-10
240-12
300-10
Distribution terminals
Cat. No. 048 68
185
185-10
150
4 x 35
+ 2 x 25
25
185-12
25
95-10
20
25
185-12
Base with at
rear terminals
Cat. Nos. 265 35/36/39
25
95-10
185-10
20
2 x 95-8
2 x 195-10
240-12
185-10
150-12
185-10
240-12
150-12
185-10
2 x 185-10
Device
Conductors
67
EX29009_066-081.indd 67
11/05/09 15:09:09
Device
Connection
method
Width
(mm)
DPX 630
fixed
version
DPX 630
plug-in or
draw-out
version
DPX 1600
fixed
version
DPX 1600
draw-out
version
Direct on plate
32
Cage terminals
Cat. Nos. 262 88
25
Conductors
Cross-section
(mm2)
rigide
souple
300
240
2 x 240
2 x 185
Copper terminals
standard
compact
Aluminium terminals
standard
compact
S-
S-
(mm2-mm) (mm2-mm)
S-
(mm2-mm)
S-
(mm2-mm)
150-12
300-10
240-12
300-10
Connection
extensions Cat. No. 262 47
32
2 x 150-12
2 x 300-10
2 x 240-12
2x 300-10
Spreader
Cat. Nos. 262 48/49
50
2 x 185-12
2 x 300-10
2 x 240-16
2x 300-10
32
2 x 300-16
40
2 x 185-12
2 x 300-10
2 x 240-12
2 x 300-10
25
150-12
300-10
240-12
300-10
32
2 x 300-16
40
2 x 185-12
2 x 300-10
2 x 240-12
2 x 300-10
25
150-12
2 x 300-10
2 x 240-12
2 x 300-10
Direct on plate
50
300-14
300-16
2 x 240
2 x 185
4 x 240
4 x 158
2 x 300-16
2 x 300-16
Connection extensions
Cat. Nos. 262 67/68
50
2 x 300-14
2 x 300-16
2 x 300-14
Spreaders
Cat. Nos. 262 73/74
80
4 x 300-14
2 x 300-16
2 x 300-14
50
2 x 300-14
2 x 300-16
2 x 300-14
50
3 x 300-14
3 x 300-16
3 x 300-14
50
4 x 120-12
2 x 300-14
2 x 300-14
4 x 150-10
50
2 x 185-12
4 x 185-10
2 x 240-12
68
EX29009_066-081.indd 68
11/05/09 15:09:09
DPX 160
DPX 250 ER
DPX 250
DPX 630
Mounting
side
underneath
side
underneath
side
125
125
160
160
160/250
160/250
250
400/630
Number of poles
3-4
3-4
4-3
4-3
Width
101
101
120
120
120
120
140
183
Depth
74
74
74
74
74
74
105
105
Height
120
90
150
115
150
108
108
152
500
500
500
500
500
500
500
500
230-500
230-500
230-500
230-500
230-500
230-500
230-500
230-500
Dimensions
(mm)
0- 0.3-1-3
0- 0.3-1-3
0- 0.3-1-3
0- 0.3-1-3
0- 0.3-1-3
0- 0.3-1-3
0- 0.3-1-3
Device
69
EX29009_066-081.indd 69
11/05/09 15:09:09
DPX 125
9 kA
16
10
15
10
14
13
17
25
16
24
16
23
15
22
40
28
40
27
38
26
37
25
36
63
44
63
42
60
40
58
38
55
100
70
100
67
96
64
92
61
88
9 kA
125
87
125
84
120
80
115
76
110
DPX 250 ER
9 kA
25
16
25
14
23
13
20
12
18
40
25
40
23
36
20
32
18
28
43
DPX 250
16 kA(1)
DPX - H 250
20 kA(1)
DPX 630
16 kA(1)
DPX - H 630
20 kA(1)
DPX 1600
20 kA(1)
DPX - H 1600
25 kA(1)
DPX 160
DPX 250 ER
DPX 250
DPX 630
11
25
DPX 160
(1) Breaking capacity value on one pole, taken as being equal to the
breaking capacity at 690 V 3-phase. (art. 533.3 NF C 15-100)
16
HIGH TEMPERATURES
DPX 1600
63
40
63
36
57
32
50
28
100
63
100
58
91
52
82
48
73
160
100 160
93
145
83
130
73
115
100
64
100
58
91
52
82
47
73
160
102 160
93
145
83
130
74
115
250
100
63
100
58
91
52
82
48
73
160
100 160
93
145
83
130
73
115
250
320
400
500
630
800
Electronic MCCB
In (A)
40C
50C
60C
DPX 250
250
250
250
238
400
400
400
380
630
630
600
567
800
800
760
760
1250
1250
1188
1125
1600
1600
1520
1440
DPX 630
DPX 1600
70
EX29009_066-081.indd 70
11/05/09 15:09:10
110-125 V DC 250 V DC
Thermal setting
Device type In (A)
DPX 125
Protection
thresholds
thermal
% Ir
magnetic
% Im
DPX 160
Rglage du magntique
Correction
factor
Ir max
at 400 Hz
Correction
factor
Im
at 400 Hz
16
16
1000
25
25
1250
40
40
1800
63
0.95
60
1900
100
0.9
90
2500
125
0.9
112
2500
16
25
800
40
40
800
63
0.95
60
1250
100
0.95
95
2000
160
0.9
145
3200
100
0.95
95
2000
160
0.9
145
3200
16 kA
25-125
20
16
100 %
150 %
25 kA
25-125
30
25
100 %
150 %
36 kA
16-125
36
30
100 %
150 %
25 kA
63-160
30
25
100 %
150 %
250
0.85
210
5000
50 kA
25-160
50
36
100 %
150 %
40
40
280 to 800
30
25
100 %
150 %
440 to 1250
DPX 125
DPX 160
DPX 250
DPX-H 250
DPX 250 ER
DPX 250
63
0.95
60
100
0.95
95
700 to 2000
160
0.9
145
1120 to 3200
50 kA 160-250
50
36
100 %
150 %
63-250
40
36
100 %
150 %
250
0.85
210
1800 to 5000
150 %
400
0.8
320
2000 to 4000
630
0.6
380
3200 to 6300
800
0.6
480
4000 to 8000
1250
0.6
750
3800 to 7500
36 kA
70 kA
40-250
45
40
100 %
DPX 630
36 kA 320-630
40
36
100 %
150 %
DPX-H 630
70 kA 320-630
45
40
100 %
150 %
DPX 630
DPX 1600
Appareil
3 DC POWER SUPPLY
71
EX29009_066-081.indd 71
11/05/09 15:09:10
DPX 250
10000
10000
10000
t (s)
t (s)
t (s)
1000
1000
1000
100
100
1
100
1
10
125
100
63
10
40
10
25 16
0.1
0.1
0.1
0.01
0.01
1
3 4 5
10
20 30
50
I/Ir
0.01
100
3 4 5
10
20 30
50
I/Ir
DPX 630
t (s)
20 30
50
I/Ir
100
t (s)
1000
100
100
100
10
10
10
0.1
0.1
0.01
10
10
1000 - 1250 A
1000
3 4 5
3 4 5
10000
t (s)
1000
630 - 800 A
10000
DPX 1600
10000
PERFORMANCE DATA
100
20 30
50
I/Ir
100
0.01
0.1
3 4 5
10
20 30
50
I/Ir
100
0.01
3 4 5
10
20 30
50
I/Ir
100
1: thermal tripping zone when cold - 2: thermal tripping zone when hot
72
EX29009_066-081.indd 72
11/05/09 15:09:10
2 ELECTRONIC DPX
DPX 250 - 630 - 1600 S1 electronic
DPX 250
DPX 630
DPX 1600
1000
t (s)
100
tr = 5 s ( 20%)
10
1,5 Ir 20%
1
630A 1250A
10 Ir 20%
250A
0 .1
160A
100A
40A
630A
400A
250A
1600A
160A
800A
0.01
1
10
10
20
30
40 50
70 100
10
I/In
I/Ir
20
30 40
10
20
30
40
I/In
I/In
DPX 1600
tr = 30 s ( 20%)
1000
tr = 20 s ( 20%)
t (s)
tr = 10 s ( 20%)
100
tr = 5 s ( 20%)
10
1.5 Ir 20%
1600A
1250A
800A
630A
250A
0.1
160A
100A
40A
I2t = K
0.01
0 .5
3
I/Ir
10
10
20
30
40 50
I/In
70 100
10
20
I/In
30
40
50
70
PERFORMANCE DATA
10 Ir 20%
73
EX29009_066-081.indd 73
11/05/09 15:09:10
DPX 125
DPX 250
109
109
109
I2t
(A2s)
I2t
(A2s)
160
108
108
100
108
107
107
100
107
40
DPX-H
DPX 50 kA
63
25
DPX 36 kA
40
DPX 25 kA
25
106
160
63
63
125
100
250
I2t
(A2s)
250
DPX
DPX 25 kA
106
106
105
105
104
104
DPX 16 kA
16
105
104
103
101
103
101
102
103
104
Icc (A)
102
109
500
400
320
105
Icc (A)
1000
800
630
I2t
(A2s)
630
DPX-H
103
104
Icc (A)
105
I2t
(A2s)
DPX-H
108
107
106
102
109
1250
108
107
103
101
DPX 1600
109
108
104
105
DPX 630
I2t
(A2s)
103
DPX-H
DPX
106
DPX
DPX
DPX-H
DPX
107
DPX 1600
106
DPX
DPX 630
LIMITATION CURVES
DPX 250
105
105
105
104
104
104
103
101
102
103
104
Icc (A)
105
103
101
102
103
104
Icc (A)
105
103
101
102
103
104
Icc (A)
105
74
EX29009_066-081.indd 74
11/05/09 15:09:10
2 CURRENT LIMITATION
DPX 125
200
2
0.
IP(k A)
100
50
40
3
0.
30
DPX 36 kA
100 -125A
40-63A
16-25A
5
0.
10
7
0.
3 4 5
10
20
100
30 40 50
Icc (kA)
200
0.2
100
5
0.2
DPX
20
100
30 40 50
Icc (kA)
200
0.9
3 4 5
10
20
100
30 40 50
Icc (kA)
0.2
25
0.
1000-1250 A
50
40
DPX
3
0.
DPX-H
630-800 A
0.5
7
0.
8
0.
5
4
3
0.9
9
0.
3 4 5
10
20
100
30 40 50
Icc (kA)
3 4 5
10
20
100
30 40 50
Icc (kA)
LIMITATION CURVES
10
IP (kA)
10
0.8
3 4 5
20
0.7
5
4
0.7
0.8
30
0.5
10
10
100
DPX-H
0.3
20
63-160A
DPX
0.5
DPX 1600
IP (kA)
30
20
5
4
9
0.
DPX 630
50
40
DPX 25 kA
8
0.
DPX-H
250 A
0.3
25-63 A
7
0.
5
0.2
30
250 A
160 A
5
0.
DPX 50 kA
20
10
0.2
50
40
3
0.
30
200
IP (kA)
100
25
0.
5
4
9
0.
DPX 16 kA
8
0.
5
4
2
0.
50
40
DPX 25 kA
20
200
IP(kA )
100
25
0.
DPX 250
75
EX29009_066-081.indd 75
11/05/09 15:09:10
101
97
8
74
50,8
45
32,25
193
193
M4
25,4
10
45
25,4
32
101
210
45
120
101
45
37,8
12
97
74
101
75,6
120
12
25,4
97
74
101
25,4
25,4
M4
81
39
10
M8
32,25
25,4
45
25,4
191
210
25,4
45
101
97
74
45
101
101
45
120
75,6
4,3 ou M4
25,4
25,4
25,4
DIMENSIONS
10
M4
39
81
M8
76
EX29009_066-081.indd 76
11/05/09 15:09:10
Terminal shields
260
20
2/4
45
103
120
282 max.
72 min.
11.25
74
62.75
10
103
101
25,4
80
35
74
25.4
97
12.7
12,7
113,7
11,2
80
37,8
M4
75.5
202
101
12,7
20
40,2
170
48
74
80
A
DPX 125
60
75,5
103
25,4
M4
DIMENSIONS
(1) Dimensions of 3-pole earth leakage modules are the same as 4-pole
earth leakage modules
77
EX29009_066-081.indd 77
11/05/09 15:09:11
247
45
265
45
150
45
150
23
120
30
45
97
74
150
120
90
30
45
18 max
23
14
115
M4
30
M4
30 30
45
23
74
150
150
45
55
55,5
45
48
95
115
158
161
74
30 30 30
45
265
247
45
30 30
97
120
241
90
30 30 30
74
120
97
45
48
DIMENSIONS
M4
95
M10
78
EX29009_066-081.indd 78
11/05/09 15:09:11
M4
80
60
48
38,5
45
132
=
135
74
1,5 max
15
75,5
60
45
35
86
95
150
15
M4
30
==
30
97
74 8
115
11,25
Y
120
30
M4 8
74
282 maxi
72 mini
35
2/4
38,5
80
30
115
11,25
Terminal shields
A
DPX 160
278
393
15
75,5
DIMENSIONS
(1) Dimensions of 3-pole earth leakage modules are the same as 4-pole earth leakage
modules
79
EX29009_066-081.indd 79
11/05/09 15:09:11
max
18
240
120
30
==
120
30 30 30
45
176
69
18
1,6
74
60
20 max
53,5
38,5
45
145
115
176
95
M4
18
10 max
120
30 30 30
90
11,5
45
15
97
30
135
250 A
270
150
15
38,5
176
30
145
30
115
30
69
30
53,5
30
215,5
30
20 max
30
30
30
30
30
DIMENSIONS
45
80
EX29009_066-081.indd 80
11/05/09 15:09:11
side by side
handle on door
Front terminals
10 max
120
30 30 30
8 18
Rear terminals
18 max
30
M4
74
60
48
282 max.
72 min.
35
2/4
11.25
115
38.5
45
62,7
15
1.5 max.
75.5
30 30 30
20 max 45
10 max
52,8
67,8
83,3
45
80
45
45
62,7
M4
298
267
91,5
107,7
237
M4
35
18
1,6
74
97
8
11,5
74
97
11,5
Terminal shields
A
115
76,5
97
74
296
418
DIMENSIONS
M4
A
DPX 250 ER
81
EX29009_066-081.indd 81
11/05/09 15:09:11
4 mini
35 35
32.5
4
4 min.
27
35 35 35
200
90
66.5
245.5
94
10
341.5
170
173,5
200
94
M5
52,5
25
186.5
20
11
36
140
105
105
17
33
105
100
35
138,5
9
35 35
35
35 35
153
side by side(1)
186,5
153
4 mini
140
35
52,5
35 35
66,5
153
10
35 35
90
4 mini
281,5
278
308
138,5
105
105
100
35
200
100
94
36
Rear terminals
173,5
11
10
140
24
52,5
138,5
105
94
173,5
Front terminals
70
17,5
M5
27
DIMENSIONS
35
82
EX29009_082-099.indd 82
11/05/09 15:09:52
52,35
35 35
187
34 45.5
108.75
173.5
66.5
90
94
35 35 35
M12
93.5
24.75
192,75
144,75
124,5
M12
24,75
313
449,5
X
353,5
66,5
90
155
99,5
94
34
155
99.5
34
47.5
20
140 (4P)
105 (3P)
93.5
47.5
45,5
32,5
187
34
34
187
35 35
19
34 45.5
10
37
81
26
108.75
173.5
90
66.5
94
35 35 35
24.75
34
155
99.5
9
9
35 35 35
19
9
10
37
81
26
Terminal shields
40
100
330
438
50
2.5 max.
25
DPX 250
71.5
2/4
DIMENSIONS
94
265 max.
93 min.
58
83
EX29009_082-099.indd 83
11/05/09 15:09:52
100
100
43,5
43,5
43,5
94
153
29
70
100
X
M5
87
43,5
43,5
398
94
220
260
100
183
130
70
140
32
94
220
32
70
4 mini
50
17
15 maxi
32
144
105
183
94
302
140
15 maxi
27
43,5
4 min.
43.543.5
14
192
43.543.543.5
side by side
Front terminals
70
4 min.
144
105
4 min.
100
87
43.5
43.5
6 or
M5
4 mini
27
DIMENSIONS
43.5
372
372
412
94
100
100
130
17 50
192
153
183
94
70
21.75
140
94
220
32
144
105
265
183
Rear terminals
84
EX29009_082-099.indd 84
11/05/09 15:09:52
34
183
Terminal shields
29
45.5
34
34
14
43.5
43.5
43.5
390
542
24.7
94
155
265
130
302
398
265
A
DPX 630
187
34
34
43,5
43,5
43,5
100
50
40
71.5
58
47
94
155
103
58
24,7
94
130
220
M 16
265 max.
93 min.
187
2.5 max.
2/4
43,5
29
DIMENSIONS
187
24,7
59
94
155
124
43,5
15
34
34
130
220
45,5
85
EX29009_082-099.indd 85
11/05/09 15:09:52
70
20
158
94
320
280
149
100
70
169
25
25 maxi
215
29
8
13 mini
Y
280
70
298
278
70
210
M12
50
M10
70
M8
35
140
140
Vertical
210 (3P)
32
13
140
23
163
12,5
12,5
98
140
56
94
145,5
273
68
118
M8
40
273
94
320
100
145,5
169
90
40
12
105
Horizontal
14
238
6
2,5 max
3
188
238
32
DIMENSIONS
13
6
2,5 max
86
EX29009_082-099.indd 86
11/05/09 15:09:52
34.5
325
360
480
299
256
Terminal shields
70
70
70
218.5
70
253
70
125
62.5
67,5
265 max.
93 min.
81
125
66.5
125
66,5
125
62,5
2/4
DIMENSIONS
2,5 maxi
87
EX29009_082-099.indd 87
11/05/09 15:09:52
A/B
C
D
DIMENSIONS
88
EX29009_082-099.indd 88
11/05/09 15:09:52
Minimum distances
Nominal
rating
mass wall
insulating
wall
mass wall
metal side
panel door
In (A)
A (mm)
B (mm)
C (mm)
D (mm)
E (mm)
F (mm)
G (mm)
DPX 125
16 to 125
60
30
20
20
80
DPX 160
63 to 160
60
30
20
20
100
100 to 250
60
30
20
20
100
DPX 250
40 to 250
70
25
25
25
140
DPX 630
250 to 630
70
25
25
25
160
DPX 1600
800 to 1600
90
40
40
40
160
MCCB
DIMENSIONS
DPX 250 ER
distance between
two MCCBs
89
EX29009_082-099.indd 89
11/05/09 15:09:53
DRX 250
Electrical auxiliaries
mounted by clipping on
front panel
50 mm
45 mm
Exclusive system: with a
single action, change from
the 50 mm standard to the
45 mm DIN standard
90
EX29009_082-099.indd 90
11/05/09 15:09:53
Accessories
Sealable terminal shields
Cage terminals
Shunt trip or
undervoltage
release
Auxiliary contact
blocks
Padlocking system
(up to 3 padlocks in
off position)
TECHNICAL CHARACTERISTICS
DRX 100
DRX 250
600 V AC - 50/60 Hz
600 V AC - 50/60 Hz
690 V AC - 50/60 Hz
690 V AC - 50/60 Hz
6 kV
6 kV
15-20-25-30-40-50-60-75-100
125-150-175-200-225-250
In (xed)
In (xed)
10 In (xed)
10 In (xed)
10 kA, 20 kA, 35 kA
18 kA, 25 kA, 36 kA
TECHNICAL CHARACTERISTICS
1 ELECTRICAL FEATURES
91
EX29009_082-099.indd 91
11/05/09 15:09:53
Connection
method
Device
Width
(mm)
Conductors
Aluminium terminals
Standard
Compacts
Standard
Compacts
S-
2
Flexible (mm -mm)
S-
(mm2-mm)
S-
(mm2-mm)
S-
(mm2-mm)
Cross-section
(mm2)
rigid
Direct on plate
Copper terminals
17
16-8
35-8
50-8
DRX 100
Cage terminals
50
Direct on plate
35
25
95-10
120-10
DRX 250
Cage terminals
150
120
3 DIMENSIONS
60
53.5
100
130
66
37.5
50 (45)
25
130
111
115
50 (45)
75
25
111
50
25
25
115
DRX 100
24
35
105
35
35
17.5
35
35
140
35
35
35
17.5
165
144
126
102
50 (45)
TECHNICAL CHARACTERISTICS
DRX 250
92
EX29009_082-099.indd 92
11/05/09 15:09:54
4 TRIPPING CURVES
DRX 100
DRX 250
10000
10000
t(s)
1000
10
Cold thermal
trip zone
100
15A
100
40-50-60-75-100A
30A
25A
20A
t(s)
1000
10
2
1
0.1
0.1
0.01
0.01
0.001
3 4 5
10
20
30
50
I/Ir
0.001
100
Hot thermal
trip zone
3 4 5
10
20 30
50
100
I/Ir
75100 A
5060 A
1540 A
100
10
N
1000
200250 A
125175 A
100
10
Ue=380415V
1
10
100
Prospective current (kA r.m.s.)
Ue=380415V
1
10
100
Prospective current (kA r.m.s.)
TECHNICAL CHARACTERISTICS
1000
DRX 250
93
EX29009_082-099.indd 93
11/05/09 15:09:54
Lexic DX modular
circuit breakers
DX circuit breakers:
1 module per pole
up to 63 A
Air
-co
ndi
tion
ing
Identification of the
circuits using the
integrated label
holder provides
convenience and
safety for users
94
EX29009_082-099.indd 94
11/05/09 15:09:55
Legrand
Cat. No.
2 protected poles
400 V
C 10
6000
3
Limiting class
Control handle
I - ON / red
DX 2-pole MCB
O - OFF / green
Characteristics
3
T
Breaking capacity
equal to that of
associated MCB
Im = Icn
078 08
TEST
300 mA
Mensuel
Monthly
Rated sensitivity
In : Sensitivity
45
G
D
In = 0.3 A
DX add-on module
C
F
B
A
1P
Thermal-magnetic MCBs
LR, DX, DX-H up to 63 A
70
Thermal-magnetic MCBs
DX-L, DX D curve,
DX-H from 80 to 125 A
70
70
70
1P+N
17.7
26.7
17.7
60
83
44
76
94
60
83
44
76
89
60
93
44
76
99
60
88
44
76
89
2P
3P
4P
95
EX29009_082-099.indd 95
11/05/09 15:09:55
Lexic DX modular
circuit breakers (continued)
CHARACTERISTICS OF DX CIRCUIT BREAKERS
DX 10 kA
Number of poles
DX 6 000 - 10 kA
1P
3P
1P
1P+N
2P/3P/4P
3P+N
6/10/16
20 /25/32
40/50 /63
6/10/16
20 /25/32
40/50 /63
1/2/3/4/6
10/16/20
25/32/40
50/63
0.5/1/2/3/4
6/10/16/20
25/32/40
1/2/3/4/6
10/16/20
25/32/40
50/63
6/10/16
20/25/32
40/50/63
B and C
B and C
B and C
B and C
B and C
B and C
230/400 V
400 V
230/400 V
230 V
400 V
400 V
Nominal frequency
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
240/415 V
415 V
415 V
240 V
415 V
415 V
127/230 V
6 000 A
6 000 A
6 000 A
6 000 A
230/400 V
6 000 A
6 000 A
6 000 A
6 000 A
curve B: 25 kA
curve C:
In < 32 A: 25 kA
In > 32 A: 20 kA
Type of curve
127/230 V
10 kA
10 kA
10 kA
10 kA
curve B: 25 kA
curve C:
In < 32 A: 25 kA
In > 32 A: 20 kA
230/400V
10 kA
10 kA
10 kA
10 kA
10 kA
10 kA
100%
100%
100%
100%
100%
100%
500 V
500 V
500 V
500 V
500 V
500 V
4 kV
4 kV
4 kV
4 kV
4 kV
4 kV
mechanical
20 000
20 000
20 000
20 000
20 000
20 000
electrical
10 000
10 000
10 000
10 000
10 000
10 000
2500 V
2500 V
2500 V
2500 V
2500 V
2500 V
Endurance
(operating cycles)
-25C to +70C -25C to +70C -25C to +70C -5C to +40C -25C to +70C -25C to +70C
96
EX29009_082-099.indd 96
11/05/09 15:09:55
DX 6 000 - 15 kA curve D
DX-L 50 kA
1P
1P+N
2P
3P/4P
3P+N
1P
2P/3P/4P
2P/4P
2/3/6/10
13/16/20
25/32/40
50/63/80
100/125
2/3/6/10
13/16/20
25/32/40
50/63
2/3/6/10
13/16/20
25/32/40
50/63/80
100/125
2/3/6/10
13/16/20
25/32/40
50/63/80
100/125
6/10
13/16/20
25/32/40
50/63
1/2/3/6
10/16/20
25/32/40
50/63
1/2/3/6
10/16/20
25/32/40
50/63/80
100/125
10/16/20
25/32/40
50/63
B and C
B and C
B and C
B and C
B and C
230/400 V
230 V
400 V
400 V
400 V
230/400 V
400 V
400 V
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
415 V
240 V
415 V
415 V
415 V
415 V
415 V
415 V
10000
10000
10000
10000
10000
6 000 A
6 000 A
25000
10000
10000
10000
10000
10000
6 000 A
6 000 A
25000
25 kA
25 kA
In < 40 A: 50 kA
In > 40 A: 25 kA
In < 40 A: 50 kA
In 50/63 A: 25 kA
In > 63 A: 16 kA
In < 40 A: 50 kA
In 50/63 A: 25 kA
In > 63 A: 16 kA
In < 32 A: 25 kA
In < 63 A: 20 kA
In < 32 A: 25 kA
In < 63 A: 20 kA
In > 63 A: 16 kA
70 kA
In < 20 A: 25 kA
In 25 A: 20 kA
In 32 A: 15 kA
In > 32 A: 12.5 kA
In < 20 A: 25 kA
In 25 A: 20 kA
In 32/40 A: 15 kA
In > 40 A: 12.5 kA
In < 20 A: 30 kA
In 25 A: 25 kA
In 32/40 A: 20 kA
In > 40 A: 15 kA
In > 63 A: 16 kA
In < 20 A: 25 kA
In 25 A: 20 kA
In 32/40 A: 15 kA
In > 40 A: 12.5 kA
In < 20 A: 25 kA
In 25 A: 20 kA
In 32/40 A: 15 kA
In > 40 A: 12.5 kA
In < 32 A: 15 kA
In > 32 A: 10 kA
In < 32 A: 15 kA
In > 32 A: 10 kA
50 kA
75%
75%
75%
75%
75%
75%
75%
75%
500 V
500 V
500 V
500 V
500 V
500 V
500 V
500 V
4 kV
4 kV
4 kV
4 kV
4 kV
4 kV
4 kV
4 kV
20 000
20 000
20 000
20 000
20 000
20 000
20 000
20 000
10 000
10 000
10 000
10 000
10 000
10 000
10 000
10 000
2500 V
2500 V
2500 V
2500 V
2500 V
2500 V
2500 V
2500 V
-25C to +70C
-25C to +70C
-25C to +70C
-25C to +70C
-25C to +70C
-25C to +70C
-25C to +70C
-25C to +70C
DX-H 10 000 - 25 kA
97
EX29009_082-099.indd 97
11/05/09 15:09:55
Lexic DX modular
circuit breakers (continued)
AUXILIARIES AND MOTOR-DRIVEN CONTROLS FOR DX
Each device can take up to 3 auxiliaries: 2 signalling
auxiliaries + 1 control auxiliary or a motor-driven
control.
2 UNDERVOLTAGE RELEASES
3 AUXILIARY CONTACTS
4 MOTOR-DRIVEN CONTROLS
These can be used with Lexic DX and DX-H circuit
breakers (except 1-Pole) and RCBOs < 63 A.
They are used to open and close the circuit breakers
remotely.
They incorporate signalling and fault signalling
functions.
Nominal control and supply voltage Uc: 230 V AC
Operating voltages: From 0.85 Uc to 1.10 Uc
Nominal frequency: 50 Hz
Does not operate at 60 Hz or with DC supply
Minimum time between 2 successive commands:
1 s up to 10 consecutive commands, 10 s thereafter
Power consumption in rest mode: 5 W
Maximum power consumption: 30 VA for breaking
or making
Minimum control pulse duration: 20 ms
Circuit breaker opening or closing time at Uc: < 1 s
The module for use with the circuit breaker,
Cat. No. 073 83, meets requirements for continuity of service by giving the reset command
automatically.
Auxiliaries and
motor-driven
controls are
mounted on the
left-hand side of
the devices
98
EX29009_082-099.indd 98
11/05/09 15:09:56
5 STOP&GO MOTOR-DRIVEN
CONTROLS
Can be used with Lexic DX and DX-H circuit breakers
and RCBOs < 63 A with screw terminals.
They automatically reset the devices with which they are
used, in the event of false tripping after a transient fault,
eg: lightning (applications: air cond., fridges, etc.)
The status of the installation is checked before
resetting. Any permanent fault (residual current fault
or short circuit) is indicated by an audible alarm
and an indicator light.
Control voltage: 230 V AC
CONNECTING DX
All the devices are available with incoming and
outgoing screw terminals, which take rigid or flexible
cables as well as copper prong-type busbars.
exible
35 mm2
25 mm2
70 mm2
50 mm2
Auxiliaries
2.5 mm2
2.5 mm2
CONNECTING DX
Copper cable
99
EX29009_082-099.indd 99
11/05/09 15:09:56
Lexic DX modular
circuit breakers (continued)
CHOICE OF PROTECTION DEVICES
ACCORDING TO THE NEUTRAL EARTHING SYSTEM
As a general rule all live conductors (phase and neutral) must be protected against overloads and short-circuits.
It is however possible to do away with this requirement for the neutral conductor in certain configurations.
Main permitted layouts according to the neutral earthing system and the type of circuit
N
Neutral
earthing
system
SN = SPH
SN = SPH
N not distributed
SN = SPH
TT
(1)
(1)
TN-S
(1)
(1)
SN < SPH
SN = SPH
SN < SPH
SN = SPH
SN < SPH
TN-C
IT
(2)
(2)
(1) In TT and TN systems, it is possible to use circuit breakers with unprotected neutral pole if the cross-section of the
neutral conductor is the same as that of the phase conductors. However, the neutral conductor must be protected if
there is a risk of it breaking upstream of the device and there is no residual current protection (TN system).
(2) In IT systems with a distributed neutral conductor, it is possible to use circuit breakers with unprotected neutral pole if
a residual current protection device, with a sensitivity of less than 15% of the current permissible in the neutral, is placed
upstream. This device must break all the poles, including the neutral. This situation should be limited to the supply of devices which can withstand the full voltage (between phases) with no risk of fire.
V3
0
V1
V2
100
EX29009_100-115.indd 100
11/05/09 15:10:45
< 63 A
< 20A
25 A
32 and 40 A
50 and 63 A
80 and 125 A
10 to 63 A
< 32 A
40 to 125 A
10 to 40 A
1.5 kA
3 kA
6 kA
5 kA
4 kA
3 kA
4 kA
6 kA
4 kA
3 kA
6 kA
2 HIGH TEMPERATURES
A standard circuit breaker is set to operate at In at an
ambient temperature of 30C.
For Lexic circuit breakers the values in the following
table are to be used.
When several circuit breakers are installed side by
side and operate simultaneously, the heat dissipation
of one pole is limited. This leads to a rise in the operating temperature of the circuit breakers, causing false
tripping. It is advisable to apply additional coefficients
according to the operating currents:
- 1 to 3 devices: 1
- 4 to 6 devices: 0.8
- 7 to 9 devices: 0.7
- More than 10 devices: 0.6
To avoid using the coefficients, good ventilation must be provided and the devices kept
away from one another.
(A)
-25
-10
10
20
30
40
50
60
70
0.5
0.8
1
2
3
4
6
8
10
13
16
20
25
32
40
50
63
80
100
125
0.64
1.02
1.25
2.5
3.75
5
7.5
10.2
12.2
16.3
19.7
24.6
31.2
40
50
62.5
78.1
102
124
155
0.6
0.96
1.17
2.34
3.5
4.7
7
9.6
11.5
15
18.7
23.2
29.5
37.8
48
60
75.6
96
118
147
0.57
0.92
1.1
2.21
3.36
4.44
6.6
9.2
11.1
14.3
18
22.4
28.3
36.5
46
57.5
72.5
92
114
141
0.55
0.88
1.07
2.14
3.24
4.28
6.4
8.8
10.7
13.9
17.3
21.6
27.2
34.9
44
55
69.9
88
110
137
0.52
0.84
1.03
2.06
3.12
4.12
6.18
8.4
10.3
13.4
16.6
20.8
26
33.3
42
52.5
66.1
84
105
131
0.5
0.8
1
2
3
4
6
8
10
13
16
20
25
32
40
50
63
80
100
125
0.47
0.76
0.97
1.94
2.88
3.88
5.8
7.6
9.7
12.6
15.4
19.2
24
30.7
38
47.5
59.8
76
95
119
0.45
0.72
0.93
1.86
2.76
3.72
5.6
7.2
9.3
12.1
14.7
18.4
22.7
29.1
36
45
56.1
72
90
113
0.42
0.69
0.90
1.80
2.64
3.6
5.4
6.9
9
11.7
14.1
17.6
21.7
27.8
34
42.5
52.9
69
86
108
0.40
0.66
0.87
1.74
2.52
3.48
5.2
6.6
8.7
11.3
13.5
16.8
20.7
26.5
32
40
50.4
66
82
103
101
EX29009_100-115.indd 101
11/05/09 15:10:45
Lexic DX modular
circuit breakers (continued)
4 DC OPERATION
5 SUPPLYING POWER TO
DX and DX-H Lexic circuit breakers (1P/2P/3P/4P In < 63 A) designed to be used with 230/400 V AC supplies, can also be used with DC supplies. In this case,
the maximum value of the magnetic trip threshold
must be multiplied by 1.4. For example: for a curve
C circuit breaker whose trip threshold is between 5
and 10 In with an AC supply, the trip threshold will be
between 7 and 14 In with a DC supply.
The thermal tripping curve is the same as with an AC
supply.
The maximum operating voltage is 80 V per pole
(60 V for single-pole + neutral). For voltages above
this value, several poles must be wired in series.
The breaking capacity is 4000 A for a single-pole circuit breaker at maximum voltage (80 V DC per pole)
At other voltages, the breaking capacities are given
in the table below according to the number of poles
in series.
Voltage
< 48 V DC
110 V DC
DX
230 V DC
< 48 V DC
DX-H 110 V DC
230 V DC
Single pole
6 kA
2-pole
6 kA
6 kA
3-pole
4-pole
6 kA
10 kA
10 kA
10 kA
10 kA
10 kA
FLUORESCENT TUBES
The rating for the protection device should be determined on the basis of an actual rated current (IB)
increased by the K cfficient.
K = 1.8 for compensated tubes (cos 0.85)
K = 3.4 for non-compensated tubes (cos 0.5)
With 230 V three-phase distribution:
IB = P x K
230
With 400 V three-phase distribution:
P
IB =
xK
400 x 3
P: Sum of powers (in W) of fluorescent fittings depending on models (18 W, 36 W, 58 W, 2 36 W, 2 58 W,
2 80 W, 4 18 W, etc).
15 kA
102
EX29009_100-115.indd 102
11/05/09 15:10:45
PERFORMANCE DATA
Curve C
Curve B
10000
10000
t (s)
t (s)
1000
1000
100
100
10
10
0.1
0.1
0.01
0.01
3 4 5
10
20 30
50
I/Ir
100
200
3 4 5
10
20 30
50
I/Ir
100
200
Curve D
10000
t (s)
1000
100
Curve
Z(1)
B
C
D
0.1
0.01
3 4 5
10
20 30
50
I/Ir
100
200
Magnetic threshold
2.4 to 3.6 In
3 to 5 In
5 to 10 In
10 to 14 In(2)
PERFORMANCE DATA
10
103
EX29009_100-115.indd 103
11/05/09 15:10:45
Lexic DX modular
circuit breakers (continued)
THERMAL STRESS LIMITATION CURVES
1 DX 6 000 - 10 KA - CURVE B
2P (400 V - 50 Hz)
107
25
20
20
104
103
103
102
102
102
101
102
103
Ik (A)
104
101
100
101
102
103
Ik (A)
104
101
100
104
10
10
10
16
105
103
101
100
50
63
I2t
(A2s)
16
105
104
40
32
32
20
25
I2t
(A2s)
16
105
106
40
106
40
106
I2t
(A2s)
50
63
50
63
107
32
107
25
2P (230 V - 50 Hz)
101
102
103
104
Ik (A)
2 DX 6 000 - 10 KA - CURVE C
50
63
20
20
10
104
103
102
102
102
102
103
Ik (A)
104
101
100
101
102
103
Ik (A)
104
101
100
10
10
104
103
101
16
105
103
101
100
40
40
I2t
(A2s)
16
105
16
105
106
25 32
32
20
25
I2t
(A2s)
32
50
63
106
40
106
I2t
(A2s)
50
63
107
107
107
104
2P (400 V - 50 Hz)
25
2P (230 V - 50 Hz)
101
102
103
Ik (A)
104
104
EX29009_100-115.indd 104
11/05/09 15:10:45
106
I2t
(A2s)
105
40 A
25/32 A
16/20 A
8-13 A
2-6 A
0.5-1 A
104
103
102
101
101
102
103
Ik (A)
104
105
107
107
63
103
103
102
102
102
101
25 32
40 50
20
104
102
103
Ik (A)
104
105
101
100
101
102
103
Ik (A)
104
105
101
100
10
6
104
103
101
100
16
105
16
105
106
I2t
(A2s)
10
32
16 20
25
I2t
(A2s)
10
105
20 25
32
40
50
106
40
106
63
50
63
107
I2t
(A2s)
104
2P (400 V - 50 Hz)
101
102
103
Ik (A)
104
105
2P (230 V - 50 Hz)
105
EX29009_100-115.indd 105
11/05/09 15:10:45
Lexic DX modular
circuit breakers (continued)
5 DX-H 10 000 - 25 KA - CURVE C - In: 80-100-125 A
2P (400 V - 50 Hz)
108
107
107
80
80
80
100
125
107
108
100
125
108
106
106
106
I2t
(A2s)
I2t
(A2s)
I2t
(A2s)
105
105
105
104
104
104
103
103
103
102
100
101
102
100
125
2P (230 V - 50 Hz)
103
Ik (A)
104
105
102
100
101
102
103
Ik (A)
104
105
102
100
101
102
103
Ik (A)
104
105
107
50
63
105
10
10
10
105
104
104
104
103
103
103
102
102
102
101
32
40
16
105
101
100
16 20
25
I2t
(A2s)
20
20
I2t
(A2s)
16
106
25
106
25
106
I2t
(A2s)
32
40
32
40
50
63
50
63
107
2P (400 V - 50 Hz)
102
103
Ik (A)
104
105
101
100
101
102
103
Ik (A)
104
105
101
100
101
102
103
Ik (A)
104
105
106
EX29009_100-115.indd 106
11/05/09 15:10:46
107
107
107
80
80
80
100
125
108
100
125
108
106
106
106
I2t
(A2s)
I2t
(A2s)
I2t
(A2s)
105
105
105
104
104
104
103
103
103
102
100
101
102
100
125
2P (230 V - 50 Hz)
103
Ik (A)
104
105
102
100
101
102
103
Ik (A)
104
105
102
100
101
102
103
Ik (A)
104
105
8 DX-L - 50 KA - CURVE C
1P (230 V) - 3P/4P (400 V)
2P (400 V - 50 Hz)
107
107
50
63
104
104
103
103
103
102
102
102
101
102
103
Ik (A)
104
105
101
100
101
32 40
25
16
10
104
101
100
20
20
10
10
105
16
105
16
105
106
I2t
(A2s)
25
I2t
(A2s)
20
I2t
(A2s)
32 40
106
25 32
106
50
63
40 50
63
107
102
103
Ik (A)
104
105
101
100
101
102
103
Ik (A)
104
105
2P (230 V - 50 Hz)
107
EX29009_100-115.indd 107
11/05/09 15:10:46
Lexic DX modular
circuit breakers (continued)
CURRENT LIMITATION CURVES
1 DX 6 000 - 10 KA - CURVE B AND C
1P-2P-3P-4P
1P+N
0.
0.
Ip (kA)
50
40
0.
0.
20
100
20
100
15
200
15
200
Ip (kA)
50
40
25
0.
30
25
0.
30
10
10
65
0.
40/50/63 A
20/25/30 A
10/16 A
6A
75
0.
5
.8
10
3 4 5
20
100
30 40 50
Ik (kA)
40 A
32 A
25 A
20 A
16 A
8-13 A
2-6 A
0.5-1 A
5
.8
0.
9
0.
5
4
65
0.
75
0.
9
5
4
0.
0.
45
20
45
20
10
3 4 5
20
100
30 40 50
Ik (kA)
In < 63 A
200
0.
15
200
Ip (kA)
Ip (kA)
100
50
40
25
30
0.
30
45
0.
10
65
0.
75
0.
85
1
1
0.
5
4
3 4 5
10
20
100
30 40 50
Ik (kA)
80/100/125 A
65
0.
75
85
0.
0.
10
0.
9
5
4
50/63 A 32 A
40 A 25 A
20 A
10/16 A
6A
0.
45
20
20
50
40
0.
0.
20
100
3 4 5
10
20
100
30 40 50
Ik (kA)
108
EX29009_100-115.indd 108
11/05/09 15:10:46
3 DX 6 000 - 15 KA - CURVE D
In: 80-100-125 A
In < 63 A
200
15
200
0.
Ip (kA)
Ip (kA)
100
0.
20
100
25
30
0.
30
25
50
40
0.
50
40
20
0.
45
0.
45
20
10
65
0.
75
0.
85
1
1
85
10
3 4 5
20
100
30 40 50
Ik (kA)
0.
0.
0.
9
5
4
0.
80/100/125 A
65
7
0.
0.
5
4
10
40/50/63 A
20/25/32 A
10/16 A
6A
3 4 5
10
20
100
30 40 50
Ik (kA)
4 DX-L - 50 KA - CURVE C
2P-3P-4P
200
Ip (kA)
25
50
40
0.
30
45
20
63 A
32 A
25 A
16 A
10 A
0.
10
75
0.
5
4
85
0.
0.
3
2
6
0.
3 4 5
10
20
100
30 40 50
Ik (kA)
100
109
EX29009_100-115.indd 109
11/05/09 15:10:46
DX-E modular
circuit breakers
2-pole
3-pole
4-pole
1P
6 - 10 - 13 - 16
20 - 25 - 32
40 - 50 - 63
2P
6 - 10 - 13 - 16
20 - 25 - 32
40 - 50 - 63
3P
6 - 10 - 13 - 16
20 - 25 - 32
40 - 50 - 63
4P
6 - 10 - 13 - 16
20 - 25 - 32
40 - 50 - 63
B and C
B and C
B and C
B and C
230/400 V
400 V
400 V
400 V
Nominal frequency
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
Number of poles
Rated current (A) at 30C
Ratings
Types of curve
240/415 V
415 V
415 V
415 V
10 kA/6 kA
15 kA/10 kA
10 kA/10 kA
10 kA/10 kA
6 kA
6 kA
6 kA
10 kA/6 kA
15 kA/10 kA
10 kA/10 kA
10 kA/10 kA
6 kA
6 kA
6 kA
100%
100%
100%
100%
100%
100%
100%
500 V
500 V
500 V
500 V
No-load
20 000
20 000
20 000
20 000
With load
10 000
10 000
10 000
10 000
127 V/230 V AC
Breaking capacity
Icu (kA) acc. to IEC 60947-2
127 V/230 V AC
Standard breaking
capacity Ics (% Icu)
127 V/230 V AC
400 V AC
400 V AC
400 V AC
DC
2000
2000
2000
2000
2500 V
2500 V
2500 V
2500 V
-25C to +70C
-25C to +70C
-25C to +70C
-25C to +70C
110
EX29009_100-115.indd 110
11/05/09 15:10:46
Performance data
Curve B
5
4
Ip (kA)
10000
3
2
0.
t (s)
100
9
8
7
6
5
4
1000
100
2
0.
0.
15
25
2
45
0.
10
100
9
8
7
6
5
4
6
0.
7
0.
8
0.
40, 50, 63 A
20, 25, 32 A
10, 16 A
6A
DX-E B and C curves
0.1
0.
100
100
0.01
3 4 5 6 7 8 9 101
3 4 5 6 7 8 9 102
Icc (kA)
1
3 4 5
10
20 30
50
I/Ir
100
200
Curve C
Voltage
Curve/rated current
Breaking capacity
IEC 60898
10000
t (s)
Electrical
diagram
1000
10
45
83
0.1
0.01
44
60
70
X
1
3 4 5
10
20 30
50
I/Ir
100
X (mm)
1P
2P
3P
4P
17.7
35.6
53.4
71.2
100
111
EX29009_100-115.indd 111
11/05/09 15:10:46
LR modular
circuit breakers
1P
2P
3P
3P+N
4P
6 - 10 - 16
20 - 25 - 32
40 - 50 - 63
B and C
B and C
B and C
230/400 V
230 V
400 V
400 V
400 V
400 V
Nominal frequency
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
240/415 V
240 V
415 V
415 V
415 V
415 V
10 kA/6 kA
10 kA/6 kA
15 kA/10 kA
10 kA/10 kA
10 kA/10 kA
10 kA/10 kA
6 kA
6 kA
6 kA
6 kA
10 kA/6 kA
10 kA/6 kA
15 kA/10 kA
10 kA/10 kA
10 kA/10 kA
10 kA/10 kA
6 kA
6 kA
6 kA
6 kA
Types of curve
1P+N
6 - 10 - 13 - 16
6 - 10 - 13 - 16 6 - 10 - 13 - 16 6 - 10 - 13 - 16
6 - 10 - 13 - 16
20 - 25 - 32
20 - 25 - 32
20 - 25 - 32
20 - 25 - 32
20 - 25 - 32
40 - 50 - 63
40 - 50 - 63
40 - 50 - 63
40 - 50 - 63
127 V/230 V AC
Breaking capacity
Icu (kA) acc. to IEC 60947-2
127 V/230 V AC
Standard breaking
capacity Ics (% Icu)
127 V/230 V AC
400 V AC
400 V AC
Operating temperature
75%
75%
75%
75%
75%
75%
75%
75%
500 V
500 V
500 V
500 V
500 V
No-load
20 000
20 000
20 000
20 000
20 000
20 000
With load
10 000
10 000
10 000
10 000
10 000
10 000
Dielectric strength
75%
500 V
Endurance (mechanical
and electrical
operating cycles)
75%
400 V AC
DC
2000
2000
2000
2000
2000
2000
2500 V
2500 V
2500 V
2500 V
2500 V
2500 V
-25C to +70C -25C to +70C -25C to +70C -25C to +70C -25C to +70C -25C to +70C
112
EX29009_100-115.indd 112
11/05/09 15:10:47
Performance data
Curve B
Ip (kA)
10000
t (s)
10
1000
5
100
40, 50, 63 A
20, 25, 32 A
10, 13, 16 A
6A
4
3
10
4 5
10
20
30
50
100
Icc (kA)
0.1
Marking
0.01
3 4 5
10
20 30
50
I/Ir
100
200
Curve/rated
current
Curve C
Breaking capacity
IEC 60898
10000
t (s)
Legrand
Cat. No.
Voltage
1000
100
Electrical
diagram
0.1
0.01
3 4 5
10
20 30
50
I/Ir
100
200
10
113
EX29009_100-115.indd 113
11/05/09 15:10:47
Legrand isolating
switches
Characteristics of DX-IS
Ith
Capacity of
cage
terminals
exible
rigid
Insulation
voltage (Ui)
Impulse withstand
voltage (Uimp)
Utilization category
Short-time
withstand current
(Icw)
Short-circuit making
capacity (Icm)
Mechanical endurance
(No. of operations)
Protection index
16 - 32 A
1.5 to
16 mm2
1.5 to
16 mm2
250
400 V AC
40 - 63 A
1.5 to
25 mm2
1.5 to
35 mm2
250
400 V AC
100 - 125 A
4 kV
4 kV
4 kV
AC 22 A
AC 23 A
AC 22 A
AC 23 A
AC 22 A
AC 23 A
750 A
1700 A
2500 A
1500 A
3000 A
3700 A
> 30 000
> 30 000
> 30 000
IP 2x wired
IP 2x wired
IP 2x
(25 mm2)
6 to 35 mm2
4 to 50 mm2
250
400 V AC
114
EX29009_100-115.indd 114
11/05/09 15:10:47
The handle can be black, or red/yellow for emergency control. It can be padlocked in open position.
The integrated cage terminals take rigid or flexible
conductors. They can also take distribution terminals
Cat. No. 048 67 (six 35 mm2 rigid or 25 mm2 flexible
outputs) or 12 mm wide copper bars.
1 VISTOP 63 TO 160 A
Vistop devices are available with 3 or 4 poles. They
are mounted on a 3 rail under a modular faceplate
in all XL3 enclosures. Vistop > 100 A can also be
attached using screws. They are available with right
or left side-mounted handles (mounted externally on
the side of the enclosure) or front handles (that can
be mounted externally on the door using accessory
Cat. No. 227 32).
63 A
125 A
16 A(2)
160 A
Cu (exible)
4 to 35 mm2
4 to 50 mm2
Cu (rigid)
4 to 50 mm2
690 V AC
8 kV
63 A (35 kW)
63 A (44 kW)
40 A (38 kW)
63
63
15
2.5
100
800 V AC
8 kV
100 A (55 kW)
100 A (69 kW)
100 A (96 kW)
100
100
15
3.5
100
100 A (gG)
63 A (aM)
4 to 70 mm2
800 V AC
8 kV
125 A (70 kW)
125 A (87 kW)
125 A (120 kW)
125
125
15
3.5
100
125 A (gG)
125 A (aM)
800 V AC
8 kV
160 A (88 kW)
160 A (110 kW)
125 A (120 kW)
125
125
15
3.5
80
160 A (gG)
125 A (aM)
12
12
12
> 30 000
IP 2xB (> 6 mm2)
IP 3xC under faceplates
> 30 000
> 30 000
> 30 000
> 30 000
63 A
100 A
IP 2xB (> 10
mm2)
6 mm2
6 mm2
400 V AC
16 A
16
10
2
1
100
115
EX29009_100-115.indd 115
11/05/09 15:10:48
Legrand isolating
switches (continued)
2 DPX-IS 63 TO 1600 A
Dimensions of Vistop
Front handle
Direct
DPX-IS isolating switches provide visible contact indication from 63 to 1600 A, with 3 poles and 4 poles.
They are fixed on special plates or on a
rail (under
a modular faceplate with window) up to 250 A.
They are available with a front, or right or left
side-mounted handle, which can be remotely mounted
on the outside of the enclosure. The operating handle
can be padlocked in open position.
The standard handle (black) can be replaced by a
handle for emergency operation (red/yellow).
External
98
74
60
C2
83
63
45
78
C1
46
C
22
4
mini 114 - maxi 523
Lateral handle
32
C2
83
66
63
45
24
C1
22,5
DPX-IS 250
22
44
60
C1
C1
C1
Front handle
C
C1
C2
16
50
63 A
100 160 A
3P et 4P
125
17,7
90
3P
4P
133
160
26,7
91
External
lateral handle
63 A
100 160 A
3P et 4P
125
17,7
90
3P
4P
133
160
26,7
91
DPX-IS 630
DPX-IS 1600
116
EX29009_116-131.indd 116
11/05/09 15:11:22
63 A
150
Cu (flexible)
Connection
100 A
Cu (rigid)/
Alumin.
160 A
DPX-IS 630
250 A
mm2
400 A
DPX-IS 1600
630 A
1 x 240 or 2 x 185
mm2
800 A
1000 A
2 x 185
mm2
1250 A
1600 A
or 4 x 185 mm2
185 mm2
Max. width 28 mm
Max. width 32 mm
Max. width 50 mm or 80 mm
690 V AC
690 V AC
690 V AC
800 V AC
800 V AC
690 V AC
8 kVA
8 kVA
8 kVA
63 A
100 A
160 A
250 A
500 V AC
400 A
630 A
800 A
1000 A
1250 A
1600 A
400 A
630 A
800 A
1000 A
1250 A
1600 A
400 A
800 A
1000 A
1250 A
1600 A
800 A
1000 A
1250 A
1600 A
690 V AC
63 A
100 A
160 A
160 A
400 A
AC 22 A
690 V AC
63 A
100 A
160 A
250 A
400 A
DC 23 A
250 V DC
Short-time withstand
current (Icw)
12 kA rms
20 kA rms
100 kA rms
100 kA rms
20 kA rms
100 kA rms
63 A
100 A
160 A
250 A
400 A
630 A
800 A
1000 A
1250 A
1600 A
63 A
100 A
160 A
160 A
400 A
630 A
800 A
1000 A
1250 A
1600 A
Endurance
Protection index
40 kA
40 kA
40 kA
mechanical
25 000 operations
15 000 operations
10 000 operations
electrical
(AC 23 400 V)
2500 operations
1500 operations
IP 20 on front panel
IP 20 on front panel
3000 operations
2000 operations
IP 20 on front panel
DPX-IS 250
117
EX29009_116-131.indd 117
11/05/09 15:11:22
Legrand isolating
switches (continued)
Dimensions of DPX-IS 250
Front handle
74
M4
105
70
35
18
74
11,5
40,4
195
85,5
70
74
35
35 35 35
138
17,5
11,5
162
129
77
45
60
138
107
132
42
72,5
105
M4
74
1
75
76,5
258
90
11,5
45
35 35 35
160
195
27
45
42
1,5
1-6
8,5
74
138
35
42
77
45
45
72,5
32
40,5
40,5
140
42
77
45
107
138
132
M4
35 35 35
55
195
90
50 mini
300 maxi
11,5
42
28
maxi
18 maxi
18
8
10 maxi
M4
10 maxi
90
35 35 35
138
77
17,5
Mounted on rail
17,5
74
162
118
EX29009_116-131.indd 118
11/05/09 15:11:22
90
130,5
87
43,5
38,2
105
32 max.
25 max.
26,4
165,3
11
28
11
330,6
42
200
94
42
15 max.
M5
200
138
65,3
17
108,2
38,7
265
183,2
265
49
81,8
105
116
327,5
265
48
43,5 43,5
26
105
181
48
17
26
42
94
138
160
200
M5
132
90
105
181
42
200
160
138
94
M5
132
90
17
119
EX29009_116-131.indd 119
11/05/09 15:11:23
Legrand isolating
switches (continued)
Dimensions of DPX-IS 1600
3P
Vari-depth handle
IP 40
140
409,5 max
194 min
32
320
74
130
278
60
148
85
50
94
320
74
132
0,8/1,5
130
278
148
85
60
43
35 35
190
70 35 35
190
205
100
205
100
238,7
62,5
74
130
320
105
210
4P
70 35 35
320
74
278
148
85
60
190
130
70
35 35
190
175
238,7
140
149
191,3
207
149
191,3
205
100
140
379 max
162 min
60
105
140
0,8/1,5
105
210
132
278
149
191,3
140
207
43
148
85
105
149
191,3
140
Vari-depth handle
IP 55
105
280
120
EX29009_116-131.indd 120
11/05/09 15:11:23
DMX3-I 4 000
1 250 A
1 600 A
2 000 A
2 500 A
3 200 A
4 000 A
3P - 4P
1250
1000
12
690
105
105
105
88
63
50
50
50
42
36
10 000
5000
3P - 4P
1600
1000
12
690
105
105
105
88
63
50
50
50
42
36
10 000
5000
3P - 4P
2000
1000
12
690
105
105
105
88
63
50
50
50
42
36
10 000
5000
3P - 4P
2500
1000
12
690
105
105
105
88
63
50
50
50
42
36
10 000
5000
3P - 4P
3200
1000
12
690
105
105
105
88
63
50
50
50
42
36
10 000
5000
3P - 4P
4000
1000
12
690
105
105
105
88
63
50
50
50
42
36
10 000
5000
DPX-I 125
Operating voltage (Ue)
50/60 Hz
DC
500
250
500
6
500
250
500
6
500
250
500
6
690
250
690
8
690
250
690
8
690
250
690
8
3.6
4.3
4.3
40
40
2.1
7000
1000
160
160 (500 V)
160
3
7000
1000
250
250 (500 V)
250
3
7000
1000
250
250
250
20
4000
1000
630
630
630
20
2500
500
1600
1600
-
121
EX29009_116-131.indd 121
11/05/09 15:11:23
Fuses
FUSE TECHNOLOGY
The fuse cartridge is inserted in the circuit to be protected. If there is an overcurrent, the circuit is broken
automatically by fusing of the conductive fuse element, which is specially rated, inside the cartridge.
The silica in the body of the cartridge absorbs very
high energies by fusing and vitrification. Unlike a circuit breaker, the fuse cartridge is destroyed by the
fault and must be replaced.
Fuse cartridges comply with standard IEC 60269-1.
Cylindrical
Conductive
end piece
Interior
filled with silica
Striker or indicator
indicating fusing
Size
Standard rating
range
8 x 32
1 - 16 A
10 x 38
0.5 - 25 A
14 x 51
2 - 50 A
22 x 58
4 - 125 A
00
25 - 160 A
63 - 200 A
125 - 250 A
200 - 400 A
Blade type
500 - 630 A
630 - 1250 A
Porcelain insulating
body
Fuse element
Conductive
end piece
Fuse element
solder
FUSE TECHNOLOGY
122
EX29009_116-131.indd 122
11/05/09 15:11:23
Moment of break
Current
Voltage
Transient recovery
voltage
Voltage
recovered
IEC 60269-1
Specific applications
IEC 60269-4
Systems for protecting
semiconductors (may be above
1000 V AC and 1500 V DC)
Household applications
IEC 60269-3
Systems for unqualified
people
Industrial applications
IEC 60269-2
Systems for qualified people
Types of cartridge
IEC 60269-4-1
IEC 60269-3-1
Neozed/Diazed, NF, BS 1361,
type C, pin-type fuses, etc.
IEC 60269-2
NH system, BS 88, 10 x 38,
14 x 51, 22 x 58, etc.
FUSE TECHNOLOGY
General rules
123
EX29009_116-131.indd 123
11/05/09 15:11:24
Fuses (continued)
FUSE CHARACTERISTICS
2 RATED CURRENTS AND VOLTAGES
1 TYPES OF FUSE
Fuses are identified by 2 letters, according to their
application category. In low voltage installations gG
and aM fuses are mainly used.
gG cartridges (general use) protect the circuits
against low and high overloads and, of course, against
short circuits.
gG cartridges are marked in black.
Fuse markings
Type of fuse
Rated current
Rated voltage
FUSE CHARACTERISTICS
124
EX29009_116-131.indd 124
11/05/09 15:11:24
3 CONVENTIONAL NON-FUSING
4 OPERATING ZONE
t (s)
Inf
Non-fusing
current
If
Fusing
current
t
Conventional
time
In < 4
1.5 In
2.1 In
1h
4 < In < 10
1.5 In
1.9 In
1h
10 < In < 25
1.4 In
1.75 In
1h
25 < In < 63
1.3 In
1.6 In
1h
1.3 In
1.6 In
2h
1.2 In
1.6 In
2h
1.2 In
1.6 In
3h
400 < In
1.2 In
1.6 In
4h
40
300 A
I eff. (A)
Fault current
5 BREAKING CAPACITY
Fusing
time
2h
1h
1.3 1.6
FUSE CHARACTERISTICS
Ratings (A)
Fusing
time
125
EX29009_116-131.indd 125
11/05/09 15:11:24
Fuses (continued)
6 LIMITATION CURVE
Example
For a prospective short circuit of 10 000 A rms (or
10 kA rms) in view of the maximum asymmetry of the
current, the short circuit could reach a theoretical
maximum value of 2.5 x I rms, i.e. 25 kA peak.
Limited current
Peak I
(A)
25 000
8 000
A short circuit triggers the release of a considerable amount of energy. The fuse cartridge limits this
energy to a much lower value, conventionally known
as the limited thermal stress, expressed in A2s.
ff.
5
2.
Ie
rve
n cu
atio
mit
li
Prospective
short-circuit
current
10 000
I eff. (A)
126
EX29009_116-131.indd 126
11/05/09 15:11:24
8 SELECTIVITY
Example
I Fault
Peak I
F1
400 A
I Fault
F2
F3
100 A
I Fault
25 A
t(s)
pre-arcing arcing time
time
Fault
arc 220 V
cos = 0,1
arc 500 V
cos = 0,1
pre-arcing
127
EX29009_116-131.indd 127
11/05/09 15:11:24
Fuses (continued)
Cylindrical cartridge fuses gG and aM types
Rupture capacity curves
10
0.1
0.1
10
100
1 000
Current in A
10 000
0.01
0.1
100 000
10
100
Current in A
1 000
100 000
1 000 000
1 000 000
100 000
100 000
10 000
10 000
Thermal stress in A s
400 V
0.01
125
10
4
6
8 10
12 16
20 25
32 40
50 63
80 100
100
100
1 000
0.5
1 000
0.25
80
Time in s
10 000
100
8
12
20
32
50
4
6
10
16
25
40
63
Time in s
10 000
125
aM type
gG type
Thermal stress in A s
1 000
100
10
8 10 12 16 20 25 32 40 50 63 80 100 125
Rating in A
100
100
Limited currents at peak kA
aM type
gG type
FUSE CHARACTERISTICS
10
8 10 12 16 20 25 32 40 50 63 80 100 125
Rating in A
Limitation curves
30
125
100
80
63
50
40
32
25
20
16
10
2.5
Ief
12
10
8
6
4
0.3
0.1
0.1
100
0.2
0.5
1
2
5
10
20
Prospective short-circuit at kA rms
1 000
10
2.5
100
0.1
0.1
Ief
6
4
2
1
0.3
50
125
100
80
63
50
40
32
25
20
16
12
10
8
30
0.5
0.2
0.5
1
2
5
10
20
Prospective short-circuit at kA rms
50
100
128
EX29009_116-131.indd 128
11/05/09 15:11:24
aM type
25
32
35
40
50
63
80
100
125
160
200
250
315
400
500
630
800
1 000
1 250
Times in s
10 000
Time in s
10 000
1 000
1 000
100
100
10
10
0.1
0.1
0.01
10
100
1 000
Current in A
10 000
0.01
100 000
25
32
40
50
63
80
100
125
160
200
250
315
400
500
630
800
1000
gG type
10
100
1 000
Current in A
10 000
100 000
10 000 000
10 000 000
1 000 000
Thermal stress in A s
100 000
10 000
1 000
100
25
32
35
40
50
63
80
315
500
800 1250
125
200
100
400
630 1000
160
250
Rating in A
gG type
1 250
1 000
800
630
500
400
315
250
200
160
125
100
80
63
50
40
32
25
100
30
10
2.5
Ief
1
0.3
0.1
0.1
0.2
0.5
1
2
5
10
20
Prospective short-circuit at kA rms
50
10 000
1 000
100
Limitation curves
100 000
100
25
32
40
50
63
FUSE CHARACTERISTICS
Thermal stress in A s
1 000 000
129
EX29009_116-131.indd 129
11/05/09 15:11:25
Devices that incorporate fuses (isolating switches, fuse carriers, etc.) are efficient protection
methods which are used according to local work
practices. However it is important to have a good
knowledge of their functional limits: difficulty of
selectivity, no accessories, etc.
SPX RANGE
All the devices in the SPX range comply with standard
IEC 60947-3. They take blade type fuse cartridges to
protect three-phase circuits against overloads and
short circuits.
In SPX devices, the fuse cartridges are placed side by
side.
In SPX-V devices, the fuse cartridges are placed one
below the other.
Common characteristics:
- 3 protected poles
Safe handling while energised
- Protection against accidental contact
Fuse can be checked through transparent window
Voltage control via small opening in window
Sealable cover
Simultaneous switching on all poles
- 1600 mechanical operations
Cover position indicated by auxiliary
contact (accessory)
Screw connection for lug
Interchangeable connection accessories
SPX RANGE
130
EX29009_116-131.indd 130
11/05/09 15:11:25
TECHNICAL CHARACTERISTICS
Size
Nominal current ln
Type of current
Nominal voltage Un
Rated insulating voltage Ue
Rated impulse withstand voltage Uimp
400 V AC
Category of use
EN 60947-3
SPX 00
SPX 1
SPX 2
SPX 3
000
00
125 A
AC (50-60 Hz)
DC
690 V AC
250 V DC
800 V
6 kV
AC 23 B
160 A
AC (50-60 Hz)
DC
690 V AC
250 V DC
800 V
6 kV
AC 23 B
AC 22 B,
AC 23 B (125 A)
AC 22 B
250 A
AC (50-60 Hz)
DC
690 V AC
440 V DC
800 V
6 kV
AC 23 B
400 A
AC (50-60 Hz)
DC
690 V AC
440 V DC
800 V
6 kV
AC 23 B
630 A
AC (50-60 Hz)
DC
690 V AC
440 V DC
800 V
6 kV
AC 23 B
AC 23 B
AC 23 B
AC 23 B
AC 23 B
AC 23 B
AC 23 B
DC 22 B (160 A)
DC 22B
DC 22B
DC 22B
500 V AC
AC 22 B
690 V AC
AC 21 B
DC 21 B;
DC 22 B (100 A)
DC 21 B (80 A);
DC 22 B (63 A)
50 kA
(peak 105 kA)
DC 21 B (160 A);
DC 22 B (125 A)
50 kA
(peak 105 kA)
DC 22B
DC 22B
DC 22B
50 kA
(peak 105 kA)
50 kA
(peak 105 kA)
50 kA
(peak 105 kA)
9W
12 W
23 W
34 W
48 W
SPX-V 00
60 mm
SPX-V 00
100 mm
SPX-V 1
SPX-V 2
SPX-V 3
220 V DC
440 V DC
Size
Nominal current ln
Type of current
Nominal voltage Un
Rated insulating voltage Ue
Rated impulse withstand voltage Uimp
400 V
500 V
Category of use EN 60947-3
690 V
Conditional rated short-circuit current
(with gG/gL fuses)
Power dissipated per pole, with blade
type fuse carrier(1)
00
00
160 A
160 A
250 A
400 A
630 A
AC (50-60 Hz)
AC (50-60 Hz)
AC (50-60 Hz)
AC (50-60 Hz)
AC (50-60 Hz)
690 V AC
800 V
6 kV
AC 23 B
AC 23 B (120 A)
AC 22 B
50 kA
(peak 105 kA)
690 V AC
800 V
6 kV
AC 23 B
AC 23 B (125 A)
AC 22 B
50 kA
(peak 105 kA)
690 V AC
1000 V
12 kV
690 V AC
1000 V
12 kV
690 V AC
1000 V
12 kV
AC 23 B
AC 22 B
100 kA
(peak 220 kA)
AC 23 B
AC 22 B
100 kA
(peak 220 kA)
AC 23 B
AC 22 B
100 kA
(peak 220 kA)
12 W
12 W
23 W
34 W
48 W
TECHNICAL CHARACTERISTICS
SPX 000
131
EX29009_116-131.indd 131
11/05/09 15:11:25
160 A
250 A
400 A
630 A
Fuses NH
Size 00
Size 1
Size 2
Size 3
Mounting on
Plate
DIN Rail/Plate
Plate
Plate
800
1000
1000
1000
6000
8000
8000
8000
12
12
12
250
400
630
630
160
250
400
13.5
18.7
30
48
160
250
400
630
400 V
AC rated operational
current Ie (A)
(Rated frequency 50/60 Hz)
AC21A
400 V
AC22A
160
250
400
630
400 V
AC23A
160
250
400
630
500 V
AC21A
160
250
400
630
500 V
AC22A
160
250
400
630
500 V
AC23A
160
250
400
630
690 V
AC21A
160
250
400
630
690 V
AC22A
160
250
400
630
690 V
AC23A
125
200
315
400
800 V
AC20A
160
250
400
630
1000 V
AC20A
250
400
630
3 x 400 V
AC23A
90
132
220
355
3 x 500 V
AC23A
110
160
250
370
3 x 690 V
AC23A
110
160
250
370
400 V
60
115
200
250
1280
2000
3200
5100
1600
2500
4000
6300
100
100
100
100
100
100
100
100
26.3
43.3
43.3
60.8
478
1600
1600
4600
10000
10000
10000
5000
1000
1000
1000
1000
3.1/4
6.6/8
6.6/8
13/15
TECHNICAL CHARACTERISTICS
8
160
132
EX29009_132-147.indd 132
11/05/09 15:12:00
CONNECTION CAPACITY
Lug mounting
Flat xing for exible
copper rail, for exible or
rigid copper and multi-core
cables
Prism xing for exible
copper rail, for exible or
rigid multicore copper and
aluminium cables
Connection
Tensile
strength
Connection
Prism
terminal
Flat terminal
for flat bars
SPX 000
SPX 00
SPX 1
SPX 2
SPX 3
M8
M 10
M 10
M 12
1214 Nm
3035 Nm
3035 Nm
3540 Nm
1.570
mm2
70150
mm2
120240
mm2
150300 mm2
3 Nm
56 Nm
68 Nm
68 Nm
Connection
1670 mm2
70150 mm2
120240 mm2
150300 mm2
Tensile
strength
3 Nm
56 Nm
68 Nm
68 Nm
Connection
Cage terminals
1.550 mm2
3 inputs
connector
Cat.No 6052 26
3 x 1.516 mm2
Tensile
strength
4 Nm
3 Nm
SPX-V 00
60 mm
SPX-V 00
100 mm
SPX-V 1
SPX-V 2
SPX-V 3
M8
M8
M 10
M 10
M 12
1214 Nm
1214 Nm
3035 Nm
3035 Nm
3540 Nm
Connection
Tensile
strength
Connection
1,570
mm2
1,570
mm2
120240
mm2
120240
mm2
120240 mm2
Tensile
strength
3 Nm
3 Nm
68 Nm
68 Nm
68 Nm
Connection
1670 mm2
1670 mm2
120240 mm2
120240 mm2
120240 mm2
Tensile
strength
3 Nm
3 Nm
68 Nm
68 Nm
68 Nm
160 A
250 A
400 A
630 A
SPX-D
Rigid cable (Cu) max. (mm)
Bar (Thickness/Width) max. (mm)
Tightening torque (Nm)
Extension connector
with 3 inputs
Tensile
strength
Other xings
Lug mounting
Cage
terminal
95
240
240
2 x 185
3/25
6/40
6/40
2 x 7/50
13
24
24
45
CONNECTION CAPACITY
133
EX29009_132-147.indd 133
11/05/09 15:12:00
44
25.5
61
60
6
22
25.5
63.5
200
47
60.5
127.5
140
143
60
127.5
143
140
97
94
89.5
77.5
50
30
89
25.5
59
25.5
SPX 00/1/2/3
30.5
89
89
60
6
e
m
p
h
b
60
q
f
SPX 0
106
176
82.5
45
37
60
155
70
151
115
17
M8
33
SPX 0
SPX 1
184
243 111.5
66
84
220
107
SPX 2
210
288
80
92
249
124
SPX 3
256
128
220 45.5
SPX 00
48
48
SPX 1
59.5
200
94
62
94
87
83
221
90
97
228
98
118
57
SPX 1 128.5
255
210
25
M10
65
SPX 2
267
210
30
M12
81
SPX 2
145
285
128 124.5
SPX 3
11
11
162
11
130
50
25
130
50
1
50
1
66
s
97
114
75
DIMENSIONS
t
d
134
EX29009_132-147.indd 134
11/05/09 15:12:01
SPX-V
SPX-V 00 on 60 mm collector rail
max. 254
197.5
145
13
21
33
185
185
33 33
M8
100
100
13
289
610
455
27
185
60
6
289
60
93
135
135
49.6
33
26.5
83.5
100.5
49
26.5
max. 238
120
max. 457
33 33
185
764
580
610
185
280
290
100
280
100
130
100
50
99
455
100
26.5
145
162
16.5
15
263
26.5
50
57
14.5
31
57.5
84.5
26.5
26.5
50
58
DIMENSIONS
50
135
EX29009_132-147.indd 135
11/05/09 15:12:01
34
145
82.5
104
37
150
76
55
37
37
28
58
131
95
184
DIMENSIONS
30
56
4.5
13
84.5
95
56
136
EX29009_132-147.indd 136
11/05/09 15:12:01
SPX-D
SPX-D 160 A and 400 A with direct handle
A
51
163
22
15 2
81
175
410
161
200
C
D
31
214
180
30
70
7
65
115
250 A
400 A
245
203
65
Dimensions (mm)
3P
3P + N
3P
3P + N
max 75 / min 7
274
329
274
329
111
166
111
166
216
216
216
216
246
246
246
246
4
4
5
5
10.5
10.5
10.5
10.5
M10
M10
M10
M10
56
215
30
248
40
15 2
512
232
277
317
212
222
40
214
12,5
81
70
max 56 / min 7
85
163
Dimensions (mm)
250 A
3P
3P + N
222
85
381
426
166
211
M12
M12
DIMENSIONS
360
137
EX29009_132-147.indd 137
11/05/09 15:12:01
Back-up
protection
Ikmax = 23 kA
DX 40 A - C curve
Breaking capacity alone = 10 kA
Breaking capacity in association
with DPX 250 ER = 25 kA
3-level back-up
BACK-UP PROTECTION
138
EX29009_132-147.indd 138
11/05/09 15:12:01
DMX3-H
DMX3-L
Downstream
MCCB
800 &
1000 A
1250 A
1600 to
4000 A
800 &
1000 A
1250 A
1600 to
4000 A
800 &
1000 A
1250 A
1600 to
4000 A
DPX 250
50
50
50
65
65
65
100
100
100
DPX 630
50
50
50
65
65
65
100
100
100
50
50
65
65
100
100
DPX 1250
DPX 1600
50
65
100
Combination applies to devices installed in the same distribution board and also in different boards.
It is therefore generally possible to benefit from the
advantages of combining devices located, for example,
in a main distribution board and in a secondary board.
The upstream device must always have the necessary
breaking capacity at its installation point.
It is also possible to
benefit from the comA
bination of device B (for
Board n1
example a DX with a
breaking capacity of
10 kA) and the secondary devices C (1P+N
Board n2
DX with a breaking
capacity of 6 kA) on distribution board no. 2.
B
Under these conditions
the DX + DNX combination has a breaking
C
capacity of 25 kA.
139
EX29009_132-147.indd 139
11/05/09 15:12:01
DX 6000 - 10 kA
B and C curves
DX-H 10 000 - 25 kA
B and C curves
DX 6000 - 15 kA
D curve
DX-L - 50 kA - C curve
1 to 20 A
25 A
32 A
40 A
50 A
63 A
80 A
100 A
125 A
1 to 16 A
20 A
25 A
32 A
40 A
50 A
63 A
10 to 63 A
DX-L
DPX-E 125
DPX 125
DPX 160
DPX-H 160
2 to 32 A
40 to 125 A
10 to 32 A
40 to 63 A
16 to 125 A
16 to 125 A
25 to 160 A
25(1)
25(1)
12.5
12.5
12.5
12.5
50
50
25
25
25
25
25
16
16
16
16
16
16
25
25
25
25
25
25
20
20
50
50
25
25
25
25
25
25
16
16
16
16
16
16
16
25
25
25
25
25
25
25
50
50
25
25
25
25
20
15
25
25
25
25
20
15
20
20
15
25
50
DX-H 10 000 - 25 kA
B and C curves
MCBs downstream
DX 6000 - 10 kA
B and C curves
DX-H 10 000 - 25 kA
B and C curves
DX 6000 - 15 kA
D curve
DX-L - 50 kA - C curve
1 to 20 A
32 & 40 A
50 A
63 A
80 A
100 A
125 A
1 to 40 A
50 A
DX-L
DPX 125
DPX 160
DPX-H 160
2 to 32 A
40 to 63 A
80 to 125 A
10 to 32 A
40 to 63 A
16 to 125 A
16 to 125 A
25 to 160 A
50
25
25
20
20
50
25
25
25
22
22
16
16
16
16
35
35
25
25
25
25
50
25
25
22
16
35
25
35
35
25
15
25
25
25
35
25
16
25
25
63 A
10 to 63 A
DPX-E 125
70
70
70
TT or TN earthing systems: for a 230/240 V supply, in order to determine the breaking capacity of a 2P MCB used as
L+N (230 V) downstream a 2P or 4P circuit breaker use values indicated in the table for 230/240 V network
140
EX29009_132-147.indd 140
11/05/09 15:12:01
DPX/H/L 250
DPX/H/L
630
DPX/H/L 630
electronic
63 A
100 A
160 A
250 A
160 A
250 A
250 to
400 A
630 A
25
25
25
25
25
25
25
25
25
25
20
25
25
25
25
25
25
25
50
25
25
25
25
25
25
20
50
25
25
25
25
20
15
20
20
15
25
25
25
25
25
20
15
50
25
25
25
25
20
15
20
20
15
25
25
25
25
25
20
15
50
25
25
25
25
20
15
20
20
15
25
25
25
25
25
20
15
50
25
25
25
20
15
15
20
20
15
25
25
25
25
20
15
15
50
25
25
25
20
15
15
20
20
15
25
25
25
25
20
15
15
50
25
25
25
20
15
15
20
20
15
25
25
25
25
20
15
15
50
25
25
25
20
15
15
15
15
10
25
25
25
25
20
15
15
50
DPX 250 ER
DPX/H/L 630
electronic
DPX/H/L 250
DPX/H/L
1250
DPX/H/L
1600
500 to
1250 A
800 to
1600 A
25
20
15
15
12.5
12.5
25
20
15
15
12.5
12.5
25
25
20
15
15
12.5
12.5
50
25
25
20
15
15
12.5
12.5
50
DPX/H/L
1250
DPX/H/L
1600
500 to
1250 A
800 to
1600 A
63 A
100 A
160 A
250 A
160 A
250 A
250 to
400 A
630 A
50
50
36
50
50
36
30
25
50
50
36
30
25
25
25
50
36
50
50
30
30
25
25
25
50
30
50
50
30
30
25
25
25
50
30
50
50
30
30
25
25
25
50
30
50
50
25
25
20
20
20
50
25
50
50
25
25
50
36
50
50
36
30
25
25
25
50
36
50
50
25
25
50
36
50
50
36
30
25
25
25
50
36
50
25
50
25
30
30
30
30
30
30
30
25
25
25
70
70
70
70
70
70
70
70
70
70
DPX 250 ER
141
EX29009_132-147.indd 141
11/05/09 15:12:01
BACK-UP BETWEEN FUSE CARTRIDGES AND MCBs / BACK-UP BETWEEN CIRCUIT BREAKERS AND SWITCHES
MCBs downstream
DX 6000 - 10 kA
C and D curves
DX-H 10 000 - 25 kA
B and C curves
DX-L 50 kA
C curve
1 to 40 A
20 to 32 A
63 to 160 A
100
100
100
50 A to 125 A
2 A to 40 A
100
100
50 A to 63 A
10 A to 40 A
50 A to 63 A
100
100
100
100
DX 6000 - 10 kA
C and D curves
DX-H 10 000 - 25 kA
B and C curves
DX-L 50 kA
C curve
20 to 32 A
63 to 160 A
100
100
1 to 40 A
100
50 A to 125 A
100
2 A to 40 A
100
100
50 A to 63 A
100
10 A to 40 A
100
100
50 A to 63 A
C1
C2
C3
C4
142
EX29009_132-147.indd 142
11/05/09 15:12:02
< 40 A
50 and 63 A
DX-H < 63 A
DX-H 80-125
DPX 125 A
16 A
10
10
20
20
25
25 A
10
10
20
20
25
40 A
10
10
15
20
25
10
10
12.5
12.5
25
12.5
12.5
25
Downstream RCCBs
2-pole 230 V
4-pole 400 V
63 A
80 A
Back-up between DPX circuit breakers and DPX-I switches (in kA)
Upstream circuit breaker
DPX 160
16 kA 25 kA 36 kA 25 kA
DPX 250 ER
DPX 250
DPX 630
50 kA
25 kA
50 kA
36 kA
70 kA
36 kA
70 kA
50 kA
70 kA
25
50
25
50
36
50
36
70
50
50
DPX-I 160
25
50
25
50
36
50
36
70
36
50
DPX-I 250 ER
25
50
25
50
36
50
36
70
36
50
36
70
36
70
50
70
36
70
50
70
50
70
50
70
50
70
16
DPX-I 125
25
36
DPX-I 250
DPX-I 630 In=400 A
50 kA
70 kA
20
20
20
20
Back-up between DPX circuit breakers and Vistop or DPX-I switches (in kA)
Upstream circuit breaker
Downstream
switch
DPX 125
DPX 160
DPX 250 ER
DPX 250
DPX 630
16 kA
25 kA
36 kA
25 kA
50 kA
25 kA
50 kA
36 kA
70 kA
36 kA
70 kA
50 kA
70 kA
50 kA
70 kA
16
25
36
25
36
25
36
36
50
36
50
36
36
36
36
25
36
25
36
36
50
36
50
36
36
36
36
25
36
36
50
36
50
36
36
36
36
DPX-IS 400
36
50
50
70
36
36
DPX-IS 630
36
50
50
70
36
50
Vistop 63
Vistop 160
DPX-IS 250
DPX 125
Downstream switch
143
EX29009_132-147.indd 143
11/05/09 15:12:02
Selectivity between
protection devices
DPX 250 ER
160 A
Ik : 8 kA
DX 40 A
Ik : 3 kA
144
EX29009_132-147.indd 144
11/05/09 15:12:02
Short circuits
To have selectivity in the short-circuit zone, the
ratio of the magnetic setting currents (Im) must be
at least 1.5.
The selectivity limit is then equal to the magnetic
tripping current ImA of the upstream circuit breaker.
The selectivity is then total as long as IkB is lower
than ImA.
Current sensing selectivity is therefore very suitable
for terminal circuits where the short circuits are relatively weak.
IP (kA)
A: upstream MCB
Non-limited current
Limitation curve
of the MCB
Only B opens
A and B open
IrB
IrA
IkB
ImB
ImA
IkB
IkB
Ik (kA)
145
EX29009_132-147.indd 145
11/05/09 15:12:02
Selectivity between
protection devices (continued)
TIME SELECTIVITY
This technique is based on the difference in the times
of the tripping curves of the circuit breakers in series.
It is checked by comparing the curves and is used for
selectivity in the short-circuit zone. It is used in addition to current sensing selectivity in order to obtain
selectivity beyond the magnetic setting current of the
upstream circuit breaker (ImA). The following is therefore necessary:
- It must be possible to set a time delay on the upstream circuit breaker
- The upstream circuit breaker must be able to withstand the short-circuit current and its effects for the
whole period of the time delay
- The trunking through which the current passes must
Electronic releases
with constant I 2 t setting
The use of circuit breakers with electronic releases
on which a constant I2t setting is possible improves t
he selectivity.
t (s) B
t (s)
B
I (A)
Tm
ImB
ImA
I (A)
DYNAMIC SELECTIVITY
Dynamic selectivity is a particular type of selectivity
developed by Legrand. It is based on making maximum
use of the limitation characteristics of moulded case
circuit breakers and extends the concept of time coordination to the highest short-circuit currents.
Dynamic selectivity is implemented between two levels
of circuit breakers by installing:
- Upstream: electronic DPX circuit breakers with S1 or
S2 type releases.
- Downstream: electronic DPX circuit breakers with S1
146
EX29009_132-147.indd 146
11/05/09 15:12:02
Advantages
- Higher selectivity limits (for high intensity
short-circuit currents) than the conventional
current sensing selectivity limits
- Better continuity of service and safer than
with current sensing selectivity
- Flexible, simple and economical solution
Disadvantages
- Two-level selectivity only
- Introduction of a short activation delay with
a consequence on the thermal stress limitation curves
B
Electronic DPX
tm = 0.1
SEL = Low
C
Thermal
magnetic
DPX
D
Electronic DPX
SEL = Low
E
DX
DYNAMIC SELECTIVITY
Downstream
- B: electronic DPX with S2 release and the SEL selector
switch set to Low (tm = 0.1, considered to be result of
the previous time selectivity study on medium intensity
short circuit)
- D: electronic DPX with S1 release and SEL selector
switch set to Low.
It is possible to install other circuit breakers downstream
of the two dynamic selectivity levels: C (thermal-magnetic
DPX) and E (DX).
For high intensity short-circuit currents downstream of
C or downstream of E, the selectivity with the upstream
devices is no longer dynamic but current sensing.
A
Electronic DPX
tm = 0.2
SEL = High
147
EX29009_132-147.indd 147
11/05/09 15:12:02
Selectivity between
protection devices (continued)
LOGICAL SELECTIVITY
Logical selectivity is an intelligent type of selectivity
performed by exchanging data between electronic DPX
or DMX3 linked by an external connection.
Logical selectivity concentrates on the medium and
high intensity short-circuit zone.
Thus, if there is a short circuit, the part of the installation affected by the fault is immediately identified
and isolated using the circuit breaker placed directly
upstream.
This acts immediately, without taking account of the
various time delay settings, which therefore reduces
to the absolute minimum, the time taken to eliminate
the fault. This enables the following:
- Selectivity on several levels, in addition to the various
time delays
- Considerable reduction of the thermal and electrodynamic stresses in the cables or bars, and thus
optimisation of the dimensions of the installation.
Logical selectivity can be implemented using:
- Electronic DPX circuit breakers with S2 protection
unit, with a 12 V DC external auxiliary power supply.
- DMX3 circuit breakers with MP4 or MP6 electronic
protection unit.
LOGICAL SELECTIVITY
Application rules
148
EX29009_148-163.indd 148
11/05/09 15:12:53
OUT
IN
OUT
IN
OUT
IN
C
OUT
IN
OUT
IN
OUT
IN
OUT
IN
OUT
OUT
OUT
IN
IN
IN
OUT
OUT
IN
A2
IN
C
OUT
OUT
IN
OUT
OUT
IN
IN
IN
LOGICAL SELECTIVITY
OUT
IN
149
EX29009_148-163.indd 149
11/05/09 15:12:53
Selectivity between
protection devices (continued)
Advantages
- Reduction of the thermal and electrodynamic stresses on the cables or
bars, thus optimising the dimensions
of the installation
- Creation of selectivity on a number
of levels, in addition to the various
time delays provided by the time
selectivity.
Technical data
Maximum number of electronic DPX that can be
connected
unlimited
unlimited
30 metres
Disadvantages
- Need for an auxiliary power supply
and a wired link between the circuit
breakers
- DPX must be fitted with type S2
electronic protection.
Logical selectivity is particularly suitable for installations characterised by high short-circuit current values and with high
continuity of service requirements.
What happens if there is a break in the wired link or the auxiliary power supply?
In both cases, there is no longer selectivity between the circuit breakers.
LOGICAL SELECTIVITY
B
no alim
12 Vcc
150
EX29009_148-163.indd 150
11/05/09 15:12:53
LOGICAL SELECTIVITY
151
EX29009_148-163.indd 151
11/05/09 15:12:53
Selectivity between
protection devices (continued)
SELECTIVITY TABLES (3-phase network 400/415 V AC)
DMX 3 / DMX 3
Upstream ACB
DMX3
Downstream
ACB
800 A
800 A
1000 A
1250 A
1600 A
2000 A
2500 A
3200 A
4000 A
DMX3 2500
DMX3 4000
DMX3 4000
2500
1000 A
1250 A
1600 A
2000 A
2500 A
3200 A
4000 A
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
Downstream
MCCB
DX/DX-H/DX-L
DPX 125/160/250 ER(1)
DPX 250(1)
DPX 630(1)
630 A
800 A
1000 A
1250 A
630
&
800 A
DPX 1600(1)
1000 A
electronic
1250 & 1600 A
(1) All breaking capacity
DPX 1250(1)
thermal
magnetic
DMX3 4000
2500
800 A
1000 A
1250 A
1600 A
2000 A
2500 A
3200 A
4000 A
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
DMX-E / DPX
DMX-E / DMX-E
Downstream
DMX-E
1600 A
800 A
1000 A
1250 A
1600 A
2000 A
Upstream DMX-E
Upstream DMX-E
2000 A
2500 A
3200 A
4000 A
Downstream
MCCB
T
T
T
T
T
T
T
T
T
T
T
T
T
T
DPX 125/160/250 ER
250 to 400 A
DPX 630
630 A
800 A
DPX 1600
1250 to 1600 A
800 &
1600 to 3200 &
1250 A
1000 A
2500 A 4000 A
T
T
T
T
T
T
T
T
T
T
T
T
T
T
152
EX29009_148-163.indd 152
11/05/09 15:12:54
In (A) 40
Ist(1)
(kA)
Downstream MCCB
16
25
40
DPX 125
(16 kA)
63
100
125
16
25
40
DPX 125
(25, 36 kA)
63
100
125
63
DPX 160
100
DPX 250 ER
160
(25, 36 kA)
250
40
63
DPX 160
DPX 250ER
100
(50 kA)
160
250
40
63
DPX 250
DPX-H 250
100
DPX-L 250
160
250
40
DPX 250
DPX-H 250
100
DPX-L 250
160
elec S1/S2(2) 250
250
320
DPX 630
DPX-H 630
400
DPX-L 630
500
630
250
DPX 630
400
elec S1/S2(2)
630
DPX-H 630
400
DPX-L 630
(2)
630
elec S1/S2
800
DPX 1250
1000
DPX-H 1250
1250
0.8
63
100
125
DPX 160/250 ER
(25, 36, 50 kA)
63
DPX 630
DPX-H 630
DPX 1250
DPX-H 1250
100
160
250
63
100
160
250
250
320
400
500
630
1.6
2.5
0.63
1.6
2.5
2.5
3.2
6.3
7.5
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
0.63
1
1
1
0.63
1
1
1
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
6
6
6
6
4
4
6
6
6
6
4
4
2.5
2.5
2.5
1.6
2.5
2.5
2.5
2.5
2.5
2.5
1.6
1.6
1.6
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
6
6
6
6
4
4
6
6
6
6
4
4
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
6
6
6
6
4
4
6
6
6
6
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
6
6
6
6
6
6
6
6
6
6
6
6
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
8
8
8
8
8
8
8
8
8
8
8
8
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
T
T
T
T
T
T
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
10
10
10
10
10
8
8
8
T
T
T
T
T
T
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
10
10
6
6
6
6
6
6
T
T
T
T
T
T
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
10
10
7.5
7.5
7.5
8
8
8
7.5
7.5
7.5
0.8
0.8
1
1
1
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
0.63
1
1
1
0.8
0.8
1
1
1
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
0.63
1
1
1
tableau en attente
1
1.6 2.5 0.63 1
1.6 2.5
de
mise
jour
1
1.6
2.5
1
1.6 2.5
0.63
EX29009_148-163.indd 153
DPX 250
DPX-H 250
1.6
2.5
2.5
0.63
1
1
6.3
6.3
6.3
Upstream
MCCB
153
11/05/09 15:12:54
Selectivity between
protection devices (continued)
Electronic DPX (SEL: LOW) / DPX
Upstream MCCB
electronic
SEL: LOW
In (A)
Ist(1)
(kA)
DPX 630
DPX-H 630
S1/S2
DPX 1600
DPX 1600
DPX-H 1600 DPX-H 1600
S1
S2
DPX 1600
DPX-H 1600
S1/S2
40
100
160
250
250
400
630
800
800
1250
1600
3.5
3.5
3.5
3.5
10
10
15
20
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
8
8
6
6
6
6
8
8
6
6
6
6
8
8
6
6
6
6
6
6
6
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
6
6
6
8
6
6
6
8
8
6
6
6
6
8
8
6
6
6
6
8
8
6
6
6
6
6
6
6
6
6
6
6
6
8
6
6
6
6
8
8
8
8
6
8
8
8
6
8
8
6
6
6
6
8
8
6
6
6
6
8
8
6
6
6
6
6
6
6
6
6
6
6
6
8
6
6
6
6
8
8
8
8
6
8
8
8
6
T
T
T
T
T
T
T
T
T
T
T
T
25
25
25
25
25
25
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
Downstream MCCB
DPX 160
DPX 250ER
(25 kA)
DPX 160
DPX 250ER
(36 kA)
DPX 160
DPX 250ER
(50 kA)
DPX 250
(36 kA)
16
25
40
63
100
125
16
25
40
63
100
125
16
25
40
63
100
125
63
100
160
250
63
100
160
250
40
63
100
160
250
40
63
100
160
250
40
100
160
250
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
8
8
8
8
1.6
1.6
2.5
2.5
2.5
8
6
6
154
EX29009_148-163.indd 154
11/05/09 15:12:54
In (A)
Ist(1)
(kA)
Downstream MCCB
40
63
DPX-H 250
100
(70 kA)
160
250
40
100
DPX-H 250 S1/S2
(70 kA)
160
250
250
400
DPX 630
(36 kA)
500
630
250
320
DPX-H 630
400
(70 kA)
500
630
250
DPX 630 S1/S2
400
(2)
(36 kA)
630
400
DPX-H 630 S1/S2
(70 kA)(2)
630
800
DPX 1250
1000
(50 kA)
1250
500
630
DPX-H 1250
800
(70 kA)
1000
1250
DPX/DPX-H 1600
800
S1
(50/70 kA)(2)
DPX/DPX-H 1600
800
S2
(50/70 kA)(2)
DPX/DPX-H 1600
1250
S1/S2
1600
(50/70 kA)(2)
DPX 1600
DPX 1600
DPX-H 1600 DPX-H 1600
S1
S2
DPX 1600
DPX-H 1600
S1/S2
40
100
160
250
250
400
630
800
800
1250
1600
3.5
3.5
3.5
3.5
10
10
15
20
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
8
8
8
8
1.6
1.6
2.5
2.5
2.5
8
6
6
8
8
8
8
6
8
6
6
6
6
8
8
8
8
6
8
6
6
6
6
6
6
6
6
6
6
5
5
20
20
20
20
20
20
20
20
20
15
15
10
10
15
15
15
10
10
15
15
15
15
15
30
30
30
30
30
30
30
30
30
20
20
20
20
20
20
20
20
20
20
20
20
20
20
30
30
30
30
30
30
30
30
30
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
15
15
20
20
20
20
20
20
36
36
36
36
36
36
36
36
36
T
T
T
T
36
36
36
36
36
T
T
T
36
36
20
20
20
20
20
20
20
20
EX29009_148-163.indd 155
DPX 630
DPX-H 630
S1/S2
15
20
15
20
20
Upstream MCCB
electronic
SEL: LOW
155
11/05/09 15:12:54
Selectivity between
protection devices (continued)
Electronic DPX (SEL: HIGH) / DPX
Upstream MCCB
electronic
SEL: HIGH
In (A)
Ist(1)
(kA)
Downstream MCCB
16
25
40
DPX 125 (16 kA)
63
100
125
16
25
40
DPX 125 (25 kA)
63
100
125
16
25
40
DPX 125 (36 kA)
63
100
125
63
DPX 160
100
DPX 250ER
160
(25 kA)
250
63
DPX 160
100
DPX 250ER
160
(36 kA)
250
40
63
DPX 160
100
DPX 250ER
(50 kA)
160
250
40
63
DPX 250
100
(36 kA)
160
250
40
100
DPX 250 S1/S2
(36 kA)
160
250
DPX 630
DPX-H 630
S1/S2
DPX 1600
DPX 1600
DPX-H 1600 DPX-H 1600
S1
S2
DPX 1600
DPX-H 1600
S1/S2
40
100
160
250
250
400
630
800
800
1250
1600
3.5
3.5
3.5
3.5
10
10
15
20
T
T
T
T
T
T
T
T
T
T
T
T
25
25
25
25
25
25
T
T
T
T
T
T
T
T
T
T
T
T
25
25
25
25
25
25
25
25
T
T
T
T
T
T
T
T
T
T
T
T
25
25
25
25
25
25
25
25
25
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
25
25
25
25
25
25
T
T
T
25
25
25
25
25
25
25
25
25
36
36
36
36
36
36
36
36
36
36
36
36
36
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
36
36
36
36
36
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
36
36
36
36
36
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
36
36
36
36
36
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
36
36
36
36
36
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
36
36
36
36
36
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
36
36
36
36
36
T
T
T
T
T
T
T
T
T
25
156
EX29009_148-163.indd 156
11/05/09 15:12:54
In (A)
Ist(1)
(kA)
Downstream MCCB
40
63
DPX-H 250
100
(70 kA)
160
250
40
100
DPX-H 250 S1/S2
(70 kA)
160
250
250
400
DPX 630
(36 kA)
500
630
250
320
DPX-H 630
400
(70 kA)
500
630
250
DPX-H 630 S1/S2
400
(36 kA)(2)
630
400
DPX 630 S1/S2
(70 kA)(2)
630
800
DPX 1250
1000
(50 kA)
1250
500
630
DPX-H 1250
800
(70 kA)
1000
1250
DPX/DPX-H 1600
800
S1
(50/70 kA)(2)
DPX/DPX-H 1600
800
S2
(50/70 kA)(2)
DPX/DPX-H 1600
1250
S1/S2
1600
(50/70 kA)(2)
DPX 1600
DPX 1600
DPX-H 1600 DPX-H 1600
S1
S2
DPX 1600
DPX-H 1600
S1/S2
40
100
160
250
250
400
630
800
800
1250
1600
3.5
3.5
3.5
3.5
10
10
15
20
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
25
25
25
25
25
25
36
36
36
36
36
36
36
36
36
T
T
T
T
36
36
36
36
36
T
T
T
36
36
36
36
36
36
36
36
36
36
36
T
T
T
T
36
36
36
36
36
T(2)
T(2)
T(2)
36(2)
36(2)
36
36
36
36
36
36
36
36
36
T
T
T
T
36
36
36
36
36
T(2)
T(2)
T(2)
36(2)
36(2)
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
36
T
T
T
T
36
36
36
36
36
T(2)
T(2)
T(2)
36(2)
36(2)
36
36
36
36
36
36
36
36
EX29009_148-163.indd 157
DPX 630
DPX-H 630
S1/S2
36
36
36
25
36
36
36(2)
36(2)
36(2)
Upstream MCCB
electronic
SEL: HIGH
157
11/05/09 15:12:54
Selectivity between
protection devices (continued)
MCCBs / MCBs
Upstream MCCBs
DPX 125
(16/25/36 kA)
Downstream MCBs
LR 6000
DX 6000 6 kA
DX 6000 10 kA
DX 6000
D curve
DX-L 50 kA
C curve
In
1A
2A
3A
4A
6A
10 A
16 A
20 A
25 A
32 A
40 A
50 A
63 A
80 A
100 A
125 A
1A
2A
3A
6A
10 A
16 A
20 A
25 A
32 A
40 A
50 A
63 A
80 A
100 A
125 A
10 A
16 A
20 A
25 A
32 A
40 A
50 A
63 A
DPX 160
(25/36/50 kA)
DPX 250 ER
(25/36/50 kA)
16 A
25 A
40 A
63 A
100 A
125 A
63 A
100 A
160 A
100 A
160 A
250 A
T
T
T
T
6000
5000
T
T
T
T
6000
5000
4000
3000
T
T
T
T
6000
5000
4000
3000
3000
T
T
T
T
6000
5000
4000
3000
3000
2000
2000
T
T
T
T
T
7500
6000
5000
4500
4000
3000
3000
3000
T
T
T
T
T
7500
6000
5000
4000
4000
3000
3000
3000
2000
T
T
T
T
T
7500
6000
5000
4500
4000
3000
3000
3000
2000
T
T
T
T
T
7000
6000
5000
4500
4000
3000
3000
3000
2000
T
T
T
T
T
T
T
8000
6000
5000
4000
4000
3000
2500
T
T
T
6000
5000
4000
3000
3000
T
T
T
6000
5000
4000
3000
3000
2000
2000
T
T
T
T
7500
6000
5000
4500
4000
3000
3000
3000
T
T
T
T
7500
6000
5000
4500
4000
3000
3000
3000
1500
T
T
T
T
7500
6000
5000
4500
4000
3000
3000
3000
T
T
T
T
7500
6000
5000
4500
4000
3000
3000
3000
T
T
20000
15000
10000
7000
3000
3000
T
T
20000
15000
10000
7000
3000
3000
T
T
T
T
T
T
T
T
8500
7000
6000
5500
5000
5000
4000
2000
T
T
T
T
T
T
T
8500
7000
6000
5500
5000
4000
3000
1500
T
T
T
T
20000
17000
8000
8000
T
T
T
T
T
T
T
T
8500
7000
6000
5500
5000
5000
4000
2000
T
T
T
T
T
T
T
8500
7000
6000
5500
5000
4000
3000
1500
T
T
T
T
T
20000
10000
10000
T
T
T
T
T
T
T
T
T
T
T
7000
6000
6000
5000
3000
T
T
T
T
T
T
T
T
T
T
T
6000
5000
4000
2000
T
T
T
T
T
20000
20000
15000
T
T
T
T
T
6000
6000
5500
4500
4500
3500
3500
T
T
22000
18000
13000
8000
4000
4000
158
EX29009_148-163.indd 158
11/05/09 15:12:54
Fuses / MCCBs
DPX 630 (36 kA)
DPX-H 630 (70 kA)
40 A
63 A
100 A
160 A
250 A
250 A
400 A
630 A
800 A
1000 A
1250 A
T
T
T
T
6000
5000
4000
4000
3000
T
T
T
T
6000
5000
4000
4000
3000
2000
T
T
T
T
T
T
T
8000
6000
5000
5000
4000
4000
T
T
T
6000
5000
4000
4000
3000
2000
2000
T
T
T
T
T
T
8000
6000
5000
5000
4000
4000
T
40000
33000
28000
20000
13000
8000
8000
T
T
T
T
T
T
T
T
T
T
T
8000
8000
8000
7500
3000
T
T
T
T
T
T
T
T
T
T
8000
8000
7000
6500
2000
T
T
T
T
T
T
20000
20000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
8000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
7000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
Upstream fuses
gG type
Downstream
MCCBs
250 A
DPX 125
7500
400 A 1000 A
DPX 160
10 000
DPX 250 ER
10 000
DPX 250
10 000
DPX 630
50 000
159
EX29009_148-163.indd 159
11/05/09 15:12:54
Choice of
products
286 56
50 kA
Version
70 kA
Fixed
Poles
In (A)
Draw-out
100 kA
Fixed
Draw-out
Fixed
Draw-out
3P
4P
3P
4P
3P
4P
3P
4P
3P
4P
3P
4P
800
286 21
286 31
287 21
287 31
286 41
286 51
287 41
287 51
286 61
286 71
287 61
287 71
1000
286 22
286 32
287 22
287 32
286 42
286 52
287 42
287 52
286 62
286 72
287 62
287 72
1250
286 23
286 33
287 23
287 33
286 43
286 53
287 43
287 53
286 63
286 73
287 63
287 73
1600
286 24
286 34
287 24
287 34
286 44
286 54
287 44
287 54
286 64
286 74
287 64
287 74
2000
286 25
286 35
287 25
287 35
286 45
286 55
287 45
287 55
286 65
286 75
287 65
287 75
2500
286 26
286 36
287 26
287 36
286 46
286 56
287 46
287 56
286 66
286 76
287 66
287 76
3200
286 27
286 37
287 27
287 37
286 47
286 57
287 47
287 57
286 67
286 77
287 67
287 77
4000
286 28
286 38
287 28
287 38
286 48
286 58
287 48
287 58
286 68
286 78
287 68
287 78
MP4 LSI
MP4 LSIg
288 00
288 01
288 02
Communication
module
12 V dc
external
power supply
Earth
leakage
module
Module
programmable
output
288 05
288 06
288 07
288 11
288 12
Fixed
Poles
In (A)
1250
1600
2000
2500
3200
4000
Draw-out
3P
4P
3P
4P
286 83
286 84
286 85
286 86
286 87
286 88
286 93
286 94
286 95
286 96
286 97
286 98
287 83
287 84
287 85
287 86
287 87
287 88
287 93
287 94
287 95
287 96
287 97
287 98
Device
Poles
Base for draw-out device
Transformation kit
DMX3/DMX3-I 4000
3P
4P
3P
4P
289 02
289 09
289 03
289 10
289 04
289 11
289 05
289 12
160
EX29009_148-163.indd 160
11/05/09 15:12:55
287 56
288 51
288 37
288 82
288 96
Control auxiliaries
Supply
Shunt trips
Undervoltage
releases
24 V AC/DC
48 V AC/DC
110 V AC/DC
230 V AC/DC
415 V AC
440 V AC
480 V AC
288 48
288 49
288 50
288 51
288 52
288 53
288 54
288 55
288 56
288 57
288 58
288 59
288 60
288 61
Delayed
undervoltage
releases
288 62
288 63
Motor
operators
Closing coils
288 34
288 35
288 36
288 37
288 38
288 39
288 40
288 41
288 42
288 43
288 44
288 45
288 46
288 47
Locking options
Ronis lock
Profalux lock
2 hole support frame for above locks
Left-hand and right-hand side mounting
Padlocking system for ACBs
Padlocking system for safety shutters
Key locking in
open position
Key locking in
draw-out position
288 30
288 31
288 28
288 33
288 32
Padlocking in
open position
Door locking
288 20
288 21
288 26
DMX3
2500
DMX3 4000
288 64
288 65
Automation
control unit
Interlocking cable
Type 1
Type 2
Type 3
Type 4
Type 5
Type 6
Standard
Communicating
289 20
289 21
289 21
289 21
289 21
289 21
261 93
261 94
Rear terminals
Spreaders
Connexion
Flat
Vertical
Horizontal
Flat
Vertical
Horizontal
Fixed version
3P
4P
288 84
288 82
288 85
288 83
288 86
288 88
288 90
288 87
288 89
288 91
DMX3 4000
Draw-out version
3P
288 96
288 96
4P
Fixed version
3P
4P
288 92
288 93
288 97
288 97
288 86
288 88
288 90
288 87
288 89
288 91
Draw-out version
3P
4P
288 94
288 94
288 95
288 95
Interlocking
mecanism
161
EX29009_148-163.indd 161
11/05/09 15:12:55
6261 17
6261 29
55 kA
Version
65 kA
Fixed
Poles
800
1000
1250
1600
2000
2500
In (A)
DMX-E 65
Draw-out
Fixed
Draw-out
3P
4P
3P
4P
3P
4P
3P
4P
6260 02
6260 03
6260 04
6260 05
6260 12
6260 13
6260 14
6260 15
6260 22
6260 23
6260 24
6260 25
6260 32
6260 33
6260 34
6260 35
6260 42
6260 43
6260 44
6260 45
6260 46
6260 47
6260 52
6260 53
6260 54
6260 55
6260 56
6260 57
6260 62
6260 63
6260 64
6260 65
6260 66
6260 67
6260 72
6260 73
6260 74
6260 75
6260 76
6260 77
DMX-E 80
Icu (415 V AC)
80 kA
Version
100 kA
Fixed
Poles
2000
2500
3200
4000
In (A)
DMX-E 100
Draw-out
Fixed
Draw-out
3P
4P
3P
4P
3P
4P
3P
4P
6260 86
6260 87
6260 88
6260 89
6260 96
6260 97
6260 98
6260 99
6261 06
6261 07
6261 08
6261 09
6261 16
6261 17
6261 18
6261 19
6261 26
6261 27
6261 28
6261 29
6261 36
6261 37
6261 38
6261 39
6261 46
6261 47
6261 48
6261 49
6261 56
6261 57
6261 58
6261 59
In
DMX-E 55
800 to 1600 A
2000 and 2500 A
3200 and 4000 A
DMX-E 65
3P
4P
3P
4P
6263 86
6263 87
6263 86
6263 88
6263 87
6263 89
DMX-E 80
DMX-E 100
Rear terminals
(supplied singly)
3P
4P
3P
4P
Horizontal
Vertical
6263 88
6263 90
6263 89
6263 91
6263 90
6263 90
6263 91
6263 91
6263 30
6263 31
6263 30
6263 30
6263 32
6263 30
3 power supplies
6263 80
6263 81
6263 82
6263 83
162
EX29009_148-163.indd 162
11/05/09 15:12:55
6263 04
6262 95
Control auxiliaries
Supply
24/30 V
48 V
60 V
110 V
125 V
220 V
250 V
400 V
110 V
220 V
240 V
250 V
380 V
415 V
110 V
220 V
240 V
380/415 V
DC
AC
50 Hz
AC
60 Hz
Undervoltage
releases
Shunt trips
6262 60
6262 62
Delayed
undervoltage
releases
6262 70
6262 71
6262 81
6262 74
6262 84
6262 65
6262 62
6262 64
6262 64
6262 65
Closing coils
6262 91
6262 92
6262 92
6262 93
6262 93
6262 64
6262 64
6262 62
6262 64
6262 64
Motor
operators
6262 72
6262 82
6262 95
6262 96
6262 93
6262 77
6262 87
6262 95
6262 79
6262 79
6262 73
6262 89
6262 89
6262 83
6262 96
6262 96
6262 93
6262 78
6262 80
6262 88
6262 90
6262 95
6262 96
6263 00
6263 01
6263 01
6263 02
6263 04
6263 04
6263 02
6263 04
6263 05
6263 02
6263 04
6263 04
6263 05
Signalling auxiliaries
Position signal
contact
Undervoltage release
action signal contact
6263 11
6263 17
6263 18
6263 15
6263 16
Locking options
Key locking
in open position
Key locking
in draw-out position
Ronis
Profalux
Castell
Kirk
None
6263 40
6263 41
6263 42
6263 43
6263 45
6263 46
6263 47
6263 48
Door locking
6263 22
Accessories
Rating mis-insertion device
Operation counter
Test box
6263 20
6263 24
6263 79
For lock
(not supplied)
163
EX29009_148-163.indd 163
11/05/09 15:12:56
250 18
250 59
254 23
16 kA
Poles
1P
3P
16
250 00
20
250 01
25
250 02
32
250 03
40
250 04
In
(A)
50
250 05
63
250 06
80
250 07
100
250 08
125
250 09
* 230 V for 1P devices
25 kA
3P + 5 N
36 kA
4P
3P
4P
3P
250 16
250 24
250 36
250 44
250 50
250 58
250 17
250 25
250 37
250 45
250 51
250 59
250 18
250 26
250 38
250 46
250 52
250 60
250 19
250 27
250 39
250 47
250 53
250 61
250 28
250 29
250 40
250 41
250 48
250 49
250 54
250 55
250 20
250 21
250 23
3P + 5 N
250 57
4P
250 62
250 63
DPX 160
Icu (400 V)
25 kA
Poles
In (A)
3P
40
63
100
160
251 23
251 24
251 25
36 kA
3P + 5 N
4P
3P
251 27
251 31
251 32
251 33
251 49
251 50
251 51
50 kA
3P + 5 N
4P
3P
251 53
251 57
251 58
251 59
251 62
251 63
251 64
251 65
3P + 5 N
4P
251 67
251 70
251 71
251 72
251 73
DPX 250 ER
Icu (400 V)
25 kA
Poles
In (A)
3P
100
160
250
252 04
252 05
252 06
36 kA
3P + 5 N
4P
3P
252 09
252 14
252 15
252 16
252 24
252 25
252 26
50 kA
3P + 5 N
4P
3P
252 29
252 34
252 35
252 36
252 44
252 45
252 46
3P + 5 N
4P
252 49
252 54
252 55
252 56
DPX 250
Release
Thermal magnetic
Icu (400 V)
36 kA
Poles
In (A)
164
EX29009_164-180.indd 164
3P
40
63
100
160
250
253 28
253 29
253 30
253 31
253 32
Electronic
70 kA
3P + 5 N
4P
3P
253 41
253 42
253 45
253 46
253 47
253 48
253 49
253 52
253 53
253 54
253 55
253 56
36 kA
70 kA
3P + 5 N
4P
3P
4P
3P
4P
254 01
254 07
254 13
254 19
253 66
253 69
253 70
253 71
253 72
253 73
254 03
254 04
254 05
254 09
254 10
254 11
254 15
254 16
254 17
254 21
254 22
254 23
11/05/09 15:13:33
256 32
257 32
DPX 630
Release
Thermal magnetic
Icu (400 V)
36 kA
Poles
3P
250
320
400
500
630
In (A)
255 21
255 22
255 23
255 25
255 24
Electronic
70 kA
3P + 5N
4P
255 32
255 33
255 35
255 34
255 36
255 37
255 38
255 39
255 40
3P
36 kA
3P + 5 N
255 42
255 43
255 45
255 44
255 52
255 53
255 55
255 54
4P
255 57
255 58
255 59
255 60
70 kA
3P
4P
256 01
256 05
3P
4P
256 02
256 06
256 10
256 14
256 03
256 07
256 11
256 15
Thermal magnetic
Icu (400 V)
Poles
In (A)
800
1000
1250
1600
50 kA
Electronic S1
70 kA
50 kA
Electronic S2
70 kA
50 kA
70 kA
3P
4P
3P
4P
3P
4P
3P
4P
3P
4P
3P
4P
258 02
258 03
258 04
258 09
258 10
258 11
258 16
258 17
258 18
258 23
258 24
258 25
257 02
257 06
257 10
257 14
257 26
257 30
257 34
257 38
257 03
257 04
257 07
257 08
257 11
257 12
257 15
257 16
257 27
257 28
257 31
257 32
257 35
257 36
257 39
257 40
Device
In (A)
DPX 125
63
125
160
DPX 160
DPX 250 ER
DPX 250
3-pole
mounted side by side
4-pole
mounted underneath
mounted underneath
260 02
260 12
260 03
260 13
260 04
260 14
260 20
260 21
260 22
260 31
260 36
260 33
260 38
260 51
260 55
260 61
260 63(1)
260 65
260 67(1)
160
250
160
250
260 54
400
260 60
630
260 64
DPX 630
Electronic earth leakage modules for DPX (Adjustable sensitivity: 0.03 - 0.3 - 1 - 3 A)
165
EX29009_164-180.indd 165
11/05/09 15:13:33
253 99
265 32
265 46
DPX-I 125
DPX-I 160
3P
4P
250 99
4P
251 98
251 99
DPX-I 630
4P
4P
400
255 86
255 87
630
255 88
800
255 89
257 94
257 95
1250
257 96
257 97
1600
257 98
257 99
250
3P
4P
3P
4P
252 98
252 99
253 98
253 99
DPX-I 1600
3P
160
3P
DPX-I 250
3P
125
250 98
DPX-I 250 ER
DPX 250
4P
+ earth
leakage
module
Devices
4P
+ earth
leakage
module
3P
4P
3P
265 12
265 13
265 29
265 14
265 15
265 31
265 32
265 37
265 52
265 53
265 58
265 16
265 17
265 33
265 34
265 38
265 54
265 55
265 59
265 35
265 36
265 39
265 56
265 57
265 60
3P
4P
4P
Front terminal
265 82
265 83
Rear terminal
265 84
265 85
Front terminal
mounting base
Rear terminal
mounting base
Flat rear terminal
mounting base
Fixed version to
draw-out version
(mounting base
+ tulip contacts
+ Debro-lift
mechanism)
4P
DPX 1600
3P
Tulip contacts
Fixed version to
plug-in version
DPX 630
265 45
265 30
265 46
265 47
265 50
265 66
265 51
265 67
265 68
098 19
263 99
263 99
263 43
263 68
265 75
265 75
265 75
263 99
265 74
265 74
265 74
265 76
265 76
265 76
265 78
265 78
265 80
166
EX29009_164-180.indd 166
11/05/09 15:13:33
262 50
262 11
262 79
261 73
261 90
DPX 160
DPX 250 ER
DPX-I 160
262 05
262 06
262 15
262 16
262 85
262 86
262 00
Supplied
262 10
262 18
262 19
262 10
262 88
DPX 250
DPX 630
DPX 1600
262 26/28(1)
262 27/29(1)
262 30
262 21
262 35
262 44
262 45
262 30
262 40
262 50
262 51
262 46
262 47
262 48
262 49
263 50
263 51
263 52
263 53
262 41
262 24(4)
262 25
262 81
262 82(4)
262 92
262 93
262 94
261 40
261 44
261 59
262 64
262 65
262 66
262 60
262 69
262 70
262 31
262 32
262 33
262 34
263 31
263 32
265 27
265 28
262 22
262 24(4)
262 17
263 00
263 01
262 01
262 03
262 25
262 75
262 76
262 92
262 93
262 94
263 10
263 11
262 11
262 13
262 25
262 77
262 78
262 92
262 93
262 94
262 90
262 91
265 10
265 11
262 11
262 13
262 25
262 77
262 78
262 92
262 93
262 94
262 79
262 80(4)
262 92
262 93
262 94
261 30
261 34
261 59
262 67/68(2)
262 73
262 74
263 80/81(3)
263 82/83(3)
262 61
262 25
262 83
262 84
262 92
262 93
262 94
261 54
261 59
Auxiliaries
Supply
Auxiliary
contact or
fault signal
Undervoltage releases
Shunt
releases
261 70
261 71
261 80
261 81
261 72
261 76
261 82
261 86
261 73
261 83
261 90
261 74
261 84
261 91
Time lag
module
261 60
24 V AC
24 V DC
48 V AC
48 V DC
110 V AC
110 V DC
230 V AC
230 V DC
400 V AC
400 V DC
261 64
261 64
261 65
261 65
261 66
261 66
261 67
261 67
261 68
261 68
(1) Long/short | (2) In < 1250 A: Cat.No 262 67 - In = 1600 A: Cat.No 262 68 | (3) Short/long
(4) To be fit on Cat.No 262 22
EX29009_164-180.indd 167
Release for
DPX-IS,
DPX 125/630
261 75
Releases for
DPX 250 ER to
DPX 1600
261 85
DPX 125
DPX-I 125
167
11/05/09 15:13:34
270 46
270 58
270 10
271 04
271 76
271 50
10 kA
3P
270 00
270 01
270 02
270 03
270 04
270 05
270 06
270 07
270 08
15
20
25
30
40
50
60
75
100
In (A)
20 kA
4P
270 10
270 11
270 12
270 13
270 14
270 15
270 16
270 17
270 18
3P
270 20
270 21
270 22
270 23
270 24
270 25
270 26
270 27
270 28
25 kA
4P
270 30
270 31
270 32
270 33
270 34
270 35
270 36
270 37
270 38
1P
270 40
270 41
270 42
270 43
270 44
270 45
270 46
270 47
270 48
35 kA
2P
270 50
270 51
270 52
270 53
270 54
270 55
270 56
270 57
270 58
3P
270 60
270 61
270 62
270 63
270 64
270 65
270 66
270 67
270 68
4P
270 70
270 71
270 72
270 73
270 74
270 75
270 76
270 77
270 78
DRX 250
Icu (415 V)
Poles
18 kA
3P
271 00
271 01
271 02
271 03
271 04
125
150
175
200
225
In (A)
25 kA
4P
271 06
271 07
271 08
271 09
271 10
3P
271 12
271 13
271 14
271 15
271 16
36 kA
4P
271 18
271 19
271 20
271 21
271 22
3P
271 24
271 25
271 26
271 27
271 28
4P
271 30
271 31
271 32
271 33
271 34
Electrical accessories
Auxiliariy contact bloc
Supply
with 1 auxiliary
with 1 alarm
with 1 auxiliary
+ 1 alarm
271 40
271 41
271 42
Up to 250 V AC/DC
12 V AC/DC
24 V AC/DC
48 V AC/DC
110/130 V AC
200/240 V AC
277 V AC
380/415 V AC
440/480 V AC
168
Shunt trips
Undervoltage
releases
271 50
271 51
271 52
271 53
271 54
271 54
271 55
271 55
271 60
271 61
271 62
271 63
271 64
271 67
271 65
271 66
DRX 100
2P
3P
271 81
271 83
271 70
271 71
DRX 250
4P
271 82
271 84
271 72
271 73
3P
271 81
271 85
271 91
Up to 50 A
Cage terminal*
from 60 to 100 A
271 74
Up to 250 A
271 80
Padlocking system (up to 3 padlocks)
271 76
Direct on DRX
Rotary handle
271 77
Vari-depth handle
* Available by set of 60 pieces: Cat.No 271 92 (up to 50 A), Cat.No 271 93 (60 to 100 A), Cat.No 271 94 (up to 250 A)
EX29009_164-180.indd 168
4P
271 82
271 86
271 75
271 81
271 78
271 79
11/05/09 15:13:34
6062 02
6027 10
C curve
1P
3P
1P
3P
6062 02
6062 03
6062 04
6062 05
6062 06
6062 07
6062 08
6062 09
6062 10
6062 24
6062 25
6062 26
6062 27
6062 28
6062 29
6062 30
6062 31
6062 32
6062 46
6062 47
6062 48
6062 49
6062 50
6062 51
6062 52
6062 53
6062 54
6062 68
6062 69
6062 70
6062 71
6062 72
6062 73
6062 74
6062 75
6062 76
0.5
1
2
3
4
6
10
16
20
25
32
40
50
63
B curve
C curve
1P
1P+N
2P
3P
3P+N
061 52
061 53
061 54
061 55
061 56
061 58
061 60
061 61
061 62
061 63
061 64
061 65
061 66
061 95
061 96
061 97
061 98
062 00
062 02
062 03
062 04
062 05
062 06
-
062 57
062 58
062 59
062 60
062 61
062 63
062 65
062 66
062 67
062 68
062 69
062 70
062 71
062 78
062 79
062 80
062 81
062 83
062 85
062 86
062 87
062 88
062 89
062 90
062 91
063 31
063 34
063 36
063 37
063 38
063 39
063 40
063 41
063 42
1P
1P+N
2P
3P
3P+N
4P
063 68
063 69
063 70
063 71
063 72
063 74
063 76
063 77
063 78
063 79
063 80
063 81
063 82
064 01
064 03
064 04
064 05
064 06
064 07
064 09
064 12
064 13
064 14
064 15
064 16
-
064 60
064 61
064 62
064 63
064 64
064 66
064 68
064 69
064 70
064 71
064 72
064 73
064 74
064 80
064 81
064 82
064 83
064 84
064 86
064 88
064 89
064 90
064 91
064 92
064 93
064 94
065 39
065 41
065 43
065 44
065 45
065 46
065 47
065 48
065 49
065 55
065 56
065 57
065 58
065 59
065 61
065 63
065 64
065 65
065 66
065 67
065 68
065 69
Nominal
rating
(A)
169
EX29009_164-180.indd 169
11/05/09 15:13:34
068 60
069 20
1P
1P+N
2P
3P
3P+N
4P
2
3
6
10
13
16
20
25
32
40
50
63
80
100
125
068 53
068 54
068 56
068 58
068 59
068 60
068 61
068 62
068 63
068 64
068 65
068 66
063 83
063 84
063 85
068 96
068 98
068 99
069 00
069 01
069 02
069 03
069 04
069 05
069 06
-
069 13
069 14
069 16
069 18
069 19
069 20
069 21
069 22
069 23
069 24
069 25
069 26
064 75
064 76
064 77
069 33
069 34
069 36
069 38
069 39
069 40
069 41
069 42
069 43
069 44
069 45
069 46
064 95
064 96
064 97
069 76
069 78
069 79
069 80
069 81
069 82
069 83
069 84
069 85
069 86
-
069 93
069 94
069 96
069 98
069 99
070 00
070 01
070 02
070 03
070 04
070 05
070 06
065 70
065 71
065 72
1P
2P
3P
4P
1
2
3
4
6
10
16
20
25
32
40
50
63
80
100
125
065 75
065 76
065 77
065 79
065 81
065 83
065 84
065 85
065 86
065 87
065 88
065 89
-
066 25
066 26
066 27
066 29
066 31
066 33
066 34
066 35
066 36
066 37
066 38
066 39
066 40
066 41
066 42
066 45
066 46
066 47
066 49
066 51
066 53
066 54
066 55
066 56
066 57
066 58
066 59
066 60
066 61
066 62
066 65
066 66
066 67
066 68
066 69
066 71
066 73
066 74
066 75
066 76
066 77
066 78
066 79
066 80
066 81
066 82
2P
3P
4P
10
16
20
25
32
40
50
63
071 12
071 14
071 15
071 16
071 17
071 18
071 19
071 20
071 27
071 29
071 30
071 31
071 32
071 33
071 34
071 35
071 42
071 44
071 45
071 46
071 47
071 48
071 49
071 50
170
EX29009_164-180.indd 170
11/05/09 15:13:35
074 01
075 64
074 63
30 mA
300 mA
300 mA (s)
1A
32
63
80-125
32
63
80-125
63
80-125
63
80-125
2-pole
230/400
V AC
A type
3-pole
400 V AC
4-pole
400 V AC
2-pole
230/400 V AC
074 01
074 02
074 03
074 07
074 08
074 09
074 11
074 28
074 29
074 83
074 84
074 85
074 89
074 90
074 91
074 93
074 23
074 01
074 01
074 55
074 56
074 57
074 61
074 62
074 63
074 65
074 66
074 77
074 78
074 34
074 35
074 36
074 38
Hpi type
3-pole
400 V AC
4-pole
400 V AC
075 37
075 38
075 39
075 43
075 44
075 45
075 47
075 11
075 17
075 18
075 20
2-pole
230/400 V AC
3-pole
400 V AC
075 64
075 68
075 69
4-pole
400 V AC
075 74
Hpi type
2-pole - 230/400 V AC
3-pole - 400 V AC
4-pole - 400 V AC
075 76
075 77
075 78
075 79
075 80
075 81
075 82
075 83
075 84
075 85
075 86
075 87
Signalling auxiliaries
Shunt releases
Undervoltage release
Motor driven control module
Automatic resetting module
STOP&GO automatic resetting
073 50
073 51
073 54
073 60
073 61
073 68
073 80
073 73
073 83
073 81
073 82
171
EX29009_164-180.indd 171
11/05/09 15:13:35
090 53
090 74
091 47
RCDs DX
AC type
Sensitivity
10 mA
30 mA
100 mA
300 mA
300 mA (s)
A type
4-pole - 400 V AC
2-pole
230 V AC
Neutral on
Neutral on
right-hand side left-hand side
Hpi type
4-pole - 400 V AC
2-pole
230 V AC
Neutral on
Neutral on
right-hand side left-hand side
2-pole
230 V AC
4-pole
400 V AC
Neutral on
right-hand side
16
089 06
090 53
25
089 09
089 93
086 93
090 56
091 40
090 98
088 22
6021 08
40
089 10
089 94
086 94
090 57
091 41
090 99
088 23
6021 09
63
089 11
089 95
086 95
090 58
091 42
091 00
088 24
6021 10
80
089 12
089 96
090 59
091 43
100
6027 10
091 44
25
089 15
089 99
091 46
40
089 16
090 00
091 47
63
089 17
090 01
091 48
80
089 18
090 02
091 49
091 50
25
089 27
090 11
090 74
091 58
40
089 28
090 12
090 75
091 59
63
089 29
090 13
090 76
091 60
80
089 30
090 14
090 77
091 61
100
6027 12
091 62
40
090 18
091 65
63
090 19
091 66
25
090 23
091 71
40
090 24
091 72
63
090 25
091 73
80
090 26
091 74
500 mA
In
(A)
172
EX29009_164-180.indd 172
11/05/09 15:13:35
6064 00
078 86
079 19
10 mA
30 mA
3
10
16
20
3
6
10
16
20
25
32
40
45
50
63
6
10
16
20
25
32
40
50
63
Black neutral
lead
Blue neutral
lead
Single pole
+ Neutral on
right-hand side
230 V AC
6064 00
6064 01
6064 02
6064 03
6064 04
6064 05
-
6064 10
6064 11
6064 12
6064 13
6064 14
6064 15
-
078 79
078 81
078 83
078 84
078 86
078 87
078 88
078 89
078 90
078 94
078 95
078 97
078 98
078 99
079 00
079 01
-
2-pole
230 V AC
4-pole
400 V AC
Single pole
+ Neutral on
right-hand side
230 V AC
4-pole
400 V AC
077 45
077 46
077 47
079 11
079 19
079 20
079 21
079 22
079 29
079 30
079 31
079 44
079 46
079 47
079 48
079 49
079 50
079 51
079 52
079 62
079 64
079 65
079 66
079 67
080 13
080 14
080 15
079 75
079 77
079 78
079 79
079 80
080 31
080 32
080 33
085 75
085 79
085 85
085 87
085 88
085 89
085 90
085 91
-
080 75
080 76
080 77
080 78
080 79
080 84
080 85
080 86
080 87
080 88
-
300 mA (s)
In
(A)
A type
173
EX29009_164-180.indd 173
11/05/09 15:13:35
032 70
034 33
033 28
DX-E MCBs
MCBs DX-E 6 000 - 6kA
B curve
C curve
Nominal
rating (A)
1P
2P
3P
4P
1P
2P
3P
4P
6
10
13
16
20
25
32
40
50
63
032 66
032 68
032 69
032 70
032 71
032 72
032 73
032 74
032 75
032 76
033 08
033 10
033 11
033 12
033 13
033 14
033 15
033 16
033 17
033 18
033 22
033 24
033 25
033 26
033 27
033 28
033 29
033 30
033 31
033 32
033 68
033 70
033 71
033 72
033 73
033 74
033 75
033 76
033 77
033 78
033 82
033 84
033 85
033 86
033 87
033 88
033 89
033 90
033 91
033 92
034 29
034 31
034 32
034 33
034 34
034 35
034 36
034 37
034 38
034 39
034 47
034 49
034 50
034 51
034 52
034 53
034 54
034 55
034 56
034 57
034 89
034 91
034 92
034 93
034 94
034 95
034 96
034 97
034 98
034 99
C curve
1P
2P
3P
1P
1P+N
2P
3P
3P+N
4P
6
10
13
16
20
25
32
40
50
63
6049 02
6049 03
6049 04
6049 05
6049 06
6049 07
6049 08
6049 09
6049 10
6049 11
6049 17
6049 18
6049 19
6049 20
6049 21
6049 22
6049 23
6049 24
6049 25
6049 26
6049 32
6049 33
6049 35
6049 36
6049 37
6049 38
6049 39
6049 40
6049 41
6048 02
6048 03
6048 04
6048 05
6048 06
6048 07
6048 08
6048 09
6048 10
6048 11
6048 90
6048 91
6048 92
6048 93
6047 90
6047 91
6047 92
-
6048 17
6048 18
6048 19
6048 20
6048 21
6048 22
6048 23
6048 24
6048 25
6048 26
6048 32
6048 33
6048 34
6048 35
6048 36
6048 37
6048 38
6048 39
6048 40
6048 41
6047 96
6048 94
6048 95
6048 96
6048 97
6048 98
6048 99
6047 97
6047 98
6047 99
6048 47
6048 48
6048 50
6048 51
6048 52
6048 53
6048 54
6048 55
6048 56
Nominal
rating (A)
RCDs LR
AC type
Sensitivity
30 mA
100 mA
300 mA
174
EX29009_164-180.indd 174
In (A)
25
40
63
25
40
25
40
63
A type
2-pole - 230 V AC
4-pole - 400 V AC
Neutral on
right-hand side
2-pole - 230 V AC
4-pole - 400 V AC
Neutral on
right-hand side
6021 36
6021 37
6021 38
6021 39
6021 40
6021 42
6021 43
6021 44
6021 46
6021 47
6021 49
6021 50
6021 52
6021 53
6021 93
-
6021 94
6021 95
-
11/05/09 15:13:36
266 70
255 98
225 15
DPX-IS 250
DPX-IS 630
DPX-IS 1600
Front handle
In (A)
63
100
160
250
400
630
800
1000
1250
1600
Without release
Front handle
3P
4P
3P
4P
3P
4P
3P
4P
3P
4P
3P
4P
266 30
266 31
266 32
266 33
266 72
266 73
265 91
265 92
265 93
265 94
266 34
266 35
266 36
266 37
266 74
266 75
265 95
265 96
265 97
265 98
266 40
266 41
266 42
266 43
266 76
266 77
266 44
266 45
266 46
266 47
266 78
266 79
266 50
266 51
266 52
266 53
266 80
266 81
266 54
266 55
266 56
266 57
266 82
266 83
266 02
266 03
266 60
266 61
266 06
266 07
266 62
266 63
266 12
266 13
266 64
266 65
266 16
266 17
266 66
266 67
266 22
266 23
266 68
266 69
266 26
266 27
266 70
266 71
On faceplate
On faceplate
or rail 2
In (A)
32
63
100
125
160
Side handle
2P
3P
4P
2P
3P
4P
224 98
225 00
225 12
225 20
225 34
225 51
225 02
225 15
225 22
225 39
225 53
225 03
225 05
225 16
225 25
225 44
225 54
225 07
225 18
225 27
225 46
225 56
Auxiliary contact
for on/off
signalling
227 07
Accessories
Direct handle for
emergency use
Vari-depth handle
Front external handle
Palock
Locking accessories for
vari-depth handle
Terminal shields
Insulation shields
DPX-IS 250
DPX-IS 630
266 89
266 89
266 90
266 86
266 87
266 90
266 86
266 87
266 92
266 97
Vistop 63 to 160 A
265 89
265 90
227 32
Ronis
Euro locks
Profalux
Ronis
2P
3P
262 87
262 45
262 92
262 93
262 94
262 64
262 65
262 66
Front handle
Mounting
175
EX29009_164-180.indd 175
11/05/09 15:13:36
216 01
215 36
133 08
153 96
2P
3P
3P + equipped
neutral
3P with changeover
micro-switch
215 01
215 03
215 04
215 05
215 36
216 01
216 04
216 05
216 36
216 96
10 x 38
Without indicator
14 x 51
With indicator
0.5
133 94
133 01
133 02
134 02
133 03
134 03
133 04
134 04
133 06
134 06
Without indicator
22 x 58
With indicator
Without indicator
With indicator
143 06
133 08
134 08
10
133 10
134 10
143 10
16
133 16
134 16
143 16
145 16
153 16
20
133 20
134 20
143 20
145 20
153 20
25
133 25
134 25
143 25
145 25
153 25
32
143 32
145 32
153 32
40
143 40
145 40
153 40
50
143 50
145 50
153 50
155 50
63
153 63
155 63
80
153 80
155 80
100
153 96
155 96
125
153
97(1)
155 97(1)
176
EX29009_164-180.indd 176
11/05/09 15:13:36
120 04
130 08
140 12
151 50
10 x 38 HRC
14 x 51 HRC
22 x 58 HRC
With indicator
0.5
130 95
130 01
130 02
141 02
120 04
130 04
141 04
120 06
130 06
141 06
120 08
130 08
141 08
10
120 10
130 10
140 10
141 10
12
130 12
140 12
141 12
16
130 16
Without indicator
With indicator
140 16
141 16
130
20(2)
140 20
141 20
130
25(2)
140 25
141 25
150 25
151 25
32
140 32
141 32
150 32
151 32
40
140 40
141 40
150 40
151 40
50
140 50(1)
141 50(1)
150 50
151 50
63
150 63
151 63
80
150 80
151 80
100
150 96
151 96
125
150 97
151 97
20
25
Rating
(A)
177
EX29009_164-180.indd 177
11/05/09 15:13:37
6052 18
6052 04
6052 13
6051 13 + 6051 22
00 - 100 A
00 - 160 A
Mounting
2 rail
screw
160 01
162 00
2 - 400 A
170 00
175 00
170 03
175 03
199 09(1)
199 15
199 16
199 17
199 20
199 21
199 22
199 23
Terminal shields
4 - 1250 A
screw
165 03
162 04
3 - 630 A
screw or 2 rail
170 02
160 05
Separation dividers
1 - 250 A
165 02
0 - 160 A
181 02
185 02
199 18
199 19
199 02
Handle
(1) for Cat.Nos 160 01 and 162 00
000
00
125
160
250
400
630
SPX fuse
carriers
Mounting on plate
6052 00
6052 02
6052 04
6052 06
6052 08
6052 01
6052 03
6052 05
6052 07
6052 09
SPX-V fuse
carriers
Distance between
collector rails
6052 11
6052 12
6052 13
6051 00
6051 01
6051 02
6051 03
6051 10
6051 11
6051 12
6051 13
60 mm
6052 14
100 mm
6052 10
185 mm
SPX-D isolating 3P
swiches
P+N
SPX size
00
1
2
3
Prism terminals
Cross section
Cat.Nos
conductor
(mm2)
Flexible rail
(mm)
Cat.Nos
conductor
(mm2)
Flexible rail
(mm)
6052 18
6052 19
6052 20
6052 21
1.5-70
70-150
120-240
150-300
12 x 10
18 x 7-18
21 x 5-19
25 x 7-20
6052 22
6052 23
6052 24
6052 25
16-70
70-150
120-240
150-300
12 x 18
18 x 10
21 x 15
25 x 20
Extension
connector
with
3 inputs
6052 26
Terminals
shields
6052 31/49(1)
6052 32
6052 33
6052 34
178
EX29009_164-180.indd 178
11/05/09 15:13:37
6052 18
6052 23
6052 26
6052 79
6052 69
6052 36
6052 30
6052 62
6052 46
Cross section
Conductor (mm2)
70-150
120-240
150-300
bar (mm)
15 x 5
20 x 5
25 x 5
Size (mm)
25 x 20
30 x 20
35 x 20
50 x 32
63 x 40
63 x 50
80 x 60
In (A)
250
400
600
600
800
1000
1250
Conductor (mm2)
1.5-1.6
4-35
16-70
16-120
In (A)
180
270
400
440
6052 30
6052 35
6052 36
6052 37
6052 45
6052 46
6052 62
6052 50
6052 51
SPX
SPX-V
000
00
00
160 A
250 A
400 A
630 A
6051 20
6051 23
6051 28
6051 26
6051 21
6051 24
6051 29
6051 27
6051 32
6051 21
6051 24
6051 29
6051 27
6051 32
6051 22
6051 25
6051 30
6051 27
6051 33
Cat.Nos
179
EX29009_164-180.indd 179
11/05/09 15:13:37
168 35
178 65
185 80
166 55
00
Voyant
With indicator
With indicator
With indicator
With indicator
With striker
163 18
163 20
163 22
163 25
163 30
163 35
163 40
163 45
163 50
163 55
168 35
168 40
168 45
168 50
168 55
168 60(1)
173 50
173 55
173 60
173 65
178 60
178 65
178 70
178 75
181 25
181 30
185 80
185 85
185 90
185 95(1)
Size
Rating (A)
63
80
100
125
160
200
250
315
400
500
630
800
1000
Taille 00
Taille 0
Taille 1
Taille 2
Taille 3
Taille 4
With indicator
With striker
With striker
With striker
With striker
With striker
160 35
160 40
160 45
160 50(1)
166 35
166 40
166 45
166 50
166 55
171 50
171 55
171 60
171 65
176 60
176 65
176 70
176 75
180 75
180 80
184 80
184 85
184 90
180
EX29009_164-180.indd 180
11/05/09 15:13:37
Breaking and
protection devices
01 | Sustainable
development
08 | Protection
against external
disturbances
02 | Power balance
and choice of power
supply solutions
09 | Operating
functions
03 | Electrical
energy supply
10 | Enclosures
and assembly
certication
IE D
CER
T IF
POWER GUIDE:
A complete set of technical documentation
04 | Sizing conductors
and selecting
protection devices
11 | Cabling
components and
control auxiliaries
05 | Breaking
and protection
devices
12 | Busbars
and distribution
06 | Electrical
hazards and
protecting people
13 | Transport and
distribution inside
an installation
07 | Protection
against lightning
effects
Annexes
Glossary
Lexicon
05
POWER GUIDE
EX29009
05
EX29009_couv.indd 1
11/05/09 13:52:26