Midea Klima Ariza Kodlari Split
Midea Klima Ariza Kodlari Split
MSG-09CRN2; MSG-09HRN2
MSG-12CRN2; MSG-12HRN2
MSG-16CRN2; MSG-16HRN2
MSG-18CRN2; MSG-18HRN2
MSG-21CRN2; MSG-21HRN2
Content
Content
1.
Precaution .................................................................................................................... 1
1.1
1.2
2.
3.
Function ....................................................................................................................... 3
Dimension .................................................................................................................... 5
3.1
3.2
4.
5.
6.
Indoor unit.................................................................................................................................. 5
Outdoor unit ............................................................................................................................... 6
Specification ................................................................................................................ 7
Refrigerant cycle diagram......................................................................................... 11
Operation limits ......................................................................................................... 12
6.1
6.2
7.
Cooling operation..................................................................................................................... 12
Heating operation .................................................................................................................... 12
8.
Installation details...................................................................................................... 19
8.1
8.2
8.3
8.4
8.5
8.6
8.7
8.8
8.9
9.
10.
10.1
-1-
MSG-07CRN2.......................................................................................................................... 26
MSG-07HRN2.......................................................................................................................... 26
MSG-09CRN2.......................................................................................................................... 27
MSG-09HRN2.......................................................................................................................... 27
MSG-12CRN2.......................................................................................................................... 28
MSG-12HRN2.......................................................................................................................... 28
MSG-16CRN2.......................................................................................................................... 29
MSG-16HRN2.......................................................................................................................... 29
MSG-18CRN2.......................................................................................................................... 30
MSG-18HRN2.......................................................................................................................... 30
MSG-21CRN2.......................................................................................................................... 31
MSG-21HRN2.......................................................................................................................... 31
Content
10.2
10.3
10.4
10.5
10.6
10.7
10.8
10.9
10.10
10.11
10.12
10.13
10.14
11.
12.
12.1
12.2
12.3
12.4
12.5
12.6
12.7
12.8
12.9
13.
-2-
Service manual
1. Precaution
1.1
Safety Precaution
To prevent injury to the user or other people and property damage, the following instructions must be followed.
Incorrect operation due to ignoring instruction will cause harm or damage.
Before service unit, be sure to read this service manual at first.
1.2
Warning
Installation
Do not use a defective or underrated circuit breaker.
Use this appliance on a dedicated circuit.
There is risk of fire or electric shock.
For electrical work, contact the dealer, seller, a
qualified electrician, or an Authorized service center.
Do not disassemble or repair the product, there is risk of
fire or electric shock.
Always ground the product.
There is risk of fire or electric shock.
Install the panel and the cover of control box
securely.
There is risk of fire of electric shock.
Always install a dedicated circuit and breaker.
power cable.
Service manual
unit is so equipped.)
There is risk of physical injury, electric shock, or product
failure.
When the product is soaked (flooded or submerged),
contact an Authorized service center.
There is risk of fire or electric shock.
Be caution that water could not enter the product.
There is risk of fire, electric shock, or product damage.
Ventilate the product from time to time when
operating it together with a stove, etc.
There is risk of fire or electric shock.
Turn the main power off when cleaning or
maintaining the product.
There is risk of electric shock.
When the product is not be used for a long time,
disconnect the power supply plug or turn off the
breaker.
There is risk of product damage or failure, or unintended
operation.
Take care to ensure that nobody could step on or fall
onto the outdoor unit.
This could result in personal injury and product damage.
CAUTION
Always check for gas (refrigerant) leakage after
installation or repair of product.
Low refrigerant levels may cause failure of product.
Install the drain hose to ensure that water is drained
away properly.
A bad connection may cause water leakage.
Keep level even when installing the product.
To avoid vibration of water leakage.
Do not install the product where the noise or hot air
from the outdoor unit could damage the
neighborhoods.
It may cause a problem for your neighbors.
Use two or more people to lift and transport the
product.
Avoid personal injury.
Do not install the product where it will be exposed to
sea wind (salt spray) directly.
It may cause corrosion on the product. Corrosion,
particularly on the condenser and evaporator fins, could
cause product malfunction or inefficient operation.
Operational
Do not expose the skin directly to cool air for long
periods of time. (Do not sit in the draft).
This could harm to your health.
Do not use the product for special purposes, such
as preserving foods, works of art, etc. It is a
consumer air conditioner, not a precision refrigerant
system.
There is risk of damage or loss of property.
Do not block the inlet or outlet of air flow.
It may cause product failure.
Use a soft cloth to clean. Do not use harsh
detergents, solvents, etc.
There is risk of fire, electric shock, or damage to the
plastic parts of the product.
Do not touch the metal parts of the product when
removing the air filter. They are very sharp.
There is risk of personal injury.
Do not step on pr put anything on the product.
(outdoor units)
There is risk of personal injury and failure of product.
Always insert the filter securely. Clean the filter
every two weeks or more often if necessary.
A dirty filter reduces the efficiency of the air conditioner
and could cause product malfunction or damage.
Do not insert hands or other object through air inlet
or outlet while the product is operated.
There are sharp and moving parts that could cause
personal injury.
Do not drink the water drained from the product.
It is not sanitary could cause serious health issues.
Use a firm stool or ladder when cleaning or
maintaining the product.
Be careful and avoid personal injury.
Replace the all batteries in the remote control with
new ones of the same type. Do not mix old and mew
batteries or different types of batteries.
There is risk of fire or explosion.
Do not recharge or disassemble the batteries. Do not
dispose of batteries in a fire.
They may burn of explode.
If the liquid from the batteries gets onto your skin or
clothes, wash it well with clean water. Do not use the
remote of the batteries have leaked.
The chemical in batteries could cause burns or other
health hazards.
-2-
Service manual
2. Function
Indoor unit
Anti-cold function
Prevent the cold wind at
the beginning of unit start.
Independent dehumidification
The function is usually used in rainy days in
springtime or damp areas.
Temp. Compensation
Defrost mode
Auto-restart function
Self-diag. function
The function will be
operate in any operation
Auto mode
-3-
Service manual
Outdoor unit
Anti-rust cabinet
Made from electrolytic zinc steel sheet and anti-rust coated components.
Valve protection
It protects the valves and prevents water from dripping.
-4-
Service manual
3. Dimension
3.1 Indoor unit
Dimension
Mode
7K
9K
12K
16K
18K
21K
-5-
750
750
750
906
906
906
250
250
250
286
286
286
188
188
188
235
235
235
Service manual
Dimension
Mode
7K
9K
12K
16K
18K
21K
-6-
L1
L2
L3
700
700
780
760
760
845
535
535
540
590
590
695
235
235
250
285
285
335
458
458
530
540
540
560
280
280
315
335
335
360
540
540
590
615
615
735
Service manual
4. Specification
Model
Power supply
Cooling
Heating
Capacity
Input
Rated current
EER
Capacity
Input
Rated current
COP
Max. current
Starting current
Model
Type
Brand
Capacity
Input
Compressor
Rated current(RLA)
Locked rotor Amp(LRA)
Thermal protector
Capacitor
Refrigerant oil
Model
Brand
Indoor
Input
fan motor
Capacitor
Speed(hi/mi/lo)
Indoor air flow (Hi/Mi/Lo)
Indoor noise level (Hi/Mi/Lo)
Model
Brand
Outdoor
Input
fan motor
Capacitor
Speed
Outdoor air flow
Outdoor noise level
Refrigerant type R407C
Design pressure
Liquid side/ Gas side
Refrigerant
Max. refrigerant pipe length
piping
Max. difference in level
Operation temp
Ambient temp
Application area
Ph-V-Hz
Btu/h
W
A
Btu/w.h
Btu/h
W
A
W/W
A
A
Btu/h
W
A
A
uF
ml
W
uF
r/min
m3/h
dB(A)
W
uF
r/min
3
m /h
dB(A)
g
MPa
mm
m
m
2
m
MSG-07CRN2
1, 220-240V~,50Hz
7000
780
3.5
9.0,2.6
----------------4.4
18
PG135X1C-4DZ2
Rotary
TOSHIBA
8086/8172
765/785
3.52/3.34
21
UP3SE0591-T71
25
400
RPG13H
Welling
37.5
1.2
1020/960/900
430/400/370
35/32/30
YDK24-6T
Welling
70
3
850
1500
49
650
2.8
6.35/9.53
10
5
17-30
18-45
10-14
MSG-07HRN2
1, 220-240V~,50Hz
7000
780
3.5
9.0,2.6
8000
800
3.6
2.9
4.4
18
PG135X1C-4DZ2
Rotary
TOSHIBA
8086/8172
765/785
3.52/3.34
21.0
UP3SE0591-T71
25
400
RPG13H
Welling
36.5
1.2
1020/960/900
430/400/370
35/32/30
YDK24-6T
Welling
70
3
850
1500
49
740
2.8
6.35/9.53
10
5
17-30
-7 - 45
10-14
MSG-09CRN2
1, 220-240V~,50Hz
9000
1000
4.4
9.0,2.6
----------------6
19.8
PG180X1C-4DZ3
Rotary
TOSHIBA
10800
1015
4.5
19.8
UP3SE0591-T61
30
400
RPG13H
Welling
39.5
1.2
1100/1020/950
470/440/410
36/32/30
YDK24-6T
WELLING
70
3
850
1600
52
620
2.8
6.35/9.53
10
5
17-30
18-45
10-14
Note:
The noise date is base on hemi-anechoic chamber, during actual operation; these values are normally somewhat
different as a result of ambient condition.
The above design and specifications are subject to change without prior notice for product improvement.
-7-
Service manual
Model
Power supply
Capacity
Input
Cooling
Rated current
EER
Capacity
Input
Heating
Rated current
COP
Max. current
Starting current
Model
Type
Brand
Capacity
Input
Compressor
Rated current(RLA)
Locked rotor Amp(LRA)
Thermal protector
Capacitor
Refrigerant oil
Model
Brand
Indoor
Input
fan motor
Capacitor
Speed(hi/mi/lo)
Indoor air flow (Hi/Mi/Lo)
Indoor noise level (Hi/Mi/Lo)
Model
Brand
Outdoor
Input
fan motor
Capacitor
Speed
Outdoor air flow
Outdoor noise level
Refrigerant type R407C
Design pressure
Liquid side/ Gas side
Refrigerant
Max. refrigerant pipe length
piping
Max. difference in level
Operation temp
Ambient temp
Application area
MSG-09HRN2
MSG-12CRN2
MSG-12HRN2
Ph-V-Hz 1, 220-240V~,50Hz 1, 220-240V~,50Hz 1, 220-240V~,50Hz
12000
12000
Btu/h
9000
1330
1330
W
1000
6
6
A
4.4
9.0,2.6
9.0 ,2.6
9.0 ,2.6
Btu/w.h
14000
Btu/h
11000
----1400
W
1100
----6.3
A
4.9
----W/W
2.9
----2.9
A
6
7
8
19.8
A
33
33
PG180X1C-4DZ3
PG225X2C-4FT
PG225X2C-4FT
Rotary
rotary
rotary
TOSHIBA
TOSHIBA
TOSHIBA
Btu/h
10800
13550/13700
13550/13700
W
1015
1290/1335
1290/1335
A
4.5
6.1
6.1
A
19.8
33
33
UP3SE0591-T61
UP3RE0591-T56
UP3RE0591-T56
30
uF
35
35
400
ml
480
480
RPG13H
RPG18H
RPG18H
Welling
WELLING
WELLING
38.5
50
50
W
1.2
1.5
1.5
uF
r/min
1100/1020/950
1250/1150/1050
1250/1150/1050
470/440/410
m3/h
500/450/400
500/450/400
36/32/30
40/36/34
40/36/34
dB(A)
YDK24-6T
YDK25-6C
YDK25-6C
Welling
WELLING
WELLING
70
W
68
68
3
uF
2.5
2.5
850
r/min
900
900
3
1600
1900
1900
m /h
dB(A)
52
55
55
g
800
780
1100
2.8
2.8
MPa
2.8
mm
6.35/9.53
6.35/12.7
6.35/12.7
m
10
10
10
m
5
5
5
17-30
17-30
17-30
-7 - 45
18-45
18-45
2
14-21
18-26
18-26
m
Note:
The noise date is base on hemi-anechoic chamber, during actual operation; these values are normally somewhat
different as a result of ambient condition.
The above design and specifications are subject to change without prior notice for product improvement.
-8-
Service manual
Model
Power supply
Capacity
Input
Cooling
Rated current
EER
Capacity
Input
Heating
Rated current
COP
Max. current
Starting current
Model
Type
Brand
Capacity
Input
Compressor
Rated current(RLA)
Locked rotor Amp(LRA)
Thermal protector
Capacitor
Refrigerant oil
Model
Brand
Indoor
Input
fan motor
Capacitor
Speed(hi/mi/lo)
Indoor air flow (Hi/Mi/Lo)
Indoor noise level (Hi/Mi/Lo)
Model
Brand
Outdoor
Input
fan motor
Capacitor
Speed
Outdoor air flow
Outdoor noise level
Refrigerant type R407C
Design pressure
Liquid side/ Gas side
Refrigerant
Max. refrigerant pipe length
piping
Max. difference in level
Operation temp
Ambient temp
Application area
MSG-16CRN2
Ph-V-Hz 1, 220-240V~,50Hz
Btu/h
16000
W
1810
A
8.3
Btu/w.h
8.8, 2.6
Btu/h
W
A
W/W
A
13
A
41
PG295*2CS-4KU1
Rotary
GD Toshiba
Btu/h
18083
W
1760
A
8.5
A
40
Internal
uF
35UF/370V
ml
750
RPG25
WELLING
W
53
uF
1.5uF/450V
r/min
1260/1100/1000
800/770/740
m3/h
dB(A)
42/40/38
YDK36-6
WELLING
96
W
2.5F/450V
uF
900
r/min
3
1900
m /h
dB(A)
53
g
1380
MPa
2.8
mm
6.35/12.7
m
10
m
5
17-30
18-45
2
25-35
m
MSG-16HRN2
220-240V~,50Hz
16000
1820
8.3
8.8, 2.6
18000
1660
7.6
3.2
13
41
PG295*2CS-4KU1
Rotary
GD Toshiba
18083
1760
8.5
40
Internal
35UF/370V
750
RPG25
WELLING
53
1.5uF/450V
1260/1100/1000
800/770/740
42/40/38
YDK36-6
WELLING
96
2.5F/450V
900
1900
53
1380
2.8
6.35/12.7
10
5
17-30
-7 - 45
25-35
MSG18CRN2
220-240V~,50Hz
17000
1890
8.5
9.0, 2.63
13
41
PG295*2CS-4KU1
Rotary
GD Toshiba
18083
1760
8.5
40
Internal
35UF/370V
750
RPG25
WELLING
53
1.5uF/450V
1260/1100/1000
800/770/740
42/40/38
YDK36-6
WELLING
96
2.5F/450V
900
1900
53
2200
2.8
6.35/12.7
10
5
17-30
18-45
30-40
Note:
The noise date is base on hemi-anechoic chamber, during actual operation; these values are normally somewhat
different as a result of ambient condition.
The above design and specifications are subject to change without prior notice for product improvement.
-9-
Service manual
Model
Power supply
Capacity
Input
Cooling
Rated current
EER
Capacity
Input
Heating
Rated current
COP
Max. current
Starting current
Model
Type
Brand
Capacity
Input
Compressor
Rated current(RLA)
Locked rotor Amp(LRA)
Thermal protector
Capacitor
Refrigerant oil
Model
Brand
Indoor
Input
fan motor
Capacitor
Speed(hi/mi/lo)
Indoor air flow (Hi/Mi/Lo)
Indoor noise level (Hi/Mi/Lo)
Model
Brand
Outdoor
Input
fan motor
Capacitor
Speed
Outdoor air flow
Outdoor noise level
Refrigerant type R407C
Design pressure
Liquid side/ Gas side
Refrigerant
Max. refrigerant pipe length
piping
Max. difference in level
Operation temp
Ambient temp
Application area
MSG-18HRN2
MSG-21CRN2
MSG-21HRN2
Ph-V-Hz 1, 220-240V~,50Hz 1, 220-240V~,50Hz 1, 220-240V~,50Hz
18000
18000
Btu/h
17000
2080
2080
W
1890
9.5
9.5
A
8.5
8.7, 2.54
8.7, 2.54
Btu/w.h
9.0, 2.63
----22000
Btu/h
19000
----W
1900
2450
----A
8.6
11.2
----W/W
2.93
2.63
A
13
13
13
44
44
A
41
PG295*2CS-4KU1 PG340X3CS-4KU2 PG340X3CS-4KU2
Rotary
Rotary
Rotary
TOSHIBA
TOSHIBA
GD Toshiba
Btu/h
18083
20800
20800
W
1760
1970
1970
A
8.5
9.2
9.2
A
40
Internal
UP3SE0391-T09
UP3SE0391-T09
50
50
uF
35UF/370V
850
850
ml
750
RPG25
RPG25
RPG25
WELLING
WELLING
WELLING
53
53
W
53
1.5
1.5
uF
1.5uF/450V
r/min
1260/1100/1000
1260/1100/1000
1260/1100/1000
800/770/740
800/770/740
800/770/740
m3/h
41/37/35
41/37/35
dB(A)
42/40/38
YDK36-6
YDK53-6KB
YDK53-6KB
WELLING
WELLING
WELLING
96
150
150
W
2.5F/450V
3.0F/450V
3.0F/450V
uF
900
840
840
r/min
3
1900
2300
2300
m /h
dB(A)
53
53
53
2100
2200
g
2100
2.8
2.8
MPa
2.8
mm
6.35/12.7
6.35/12.7
6.35/12.7
m
15
20
20
m
8
10
10
17-30
17-30
17-30
-7 - 45
18-45
-7 - 45
2
30-40
34-49
34-49
m
Note:
The noise date is base on hemi-anechoic chamber, during actual operation; these values are normally somewhat
different as a result of ambient condition.
The above design and specifications are subject to change without prior notice for product improvement.
- 10 -
Service manual
- 11 -
Service manual
6. Operation limits
6.1 Cooling operation
Outdoor unit air temp. DB
- 12 -
Service manual
- 13 -
Schematic diagram
Service manual
7.2
Wiring diagram
INDOOR UNIT
)
N
(
2
1
T
I
N
U
R
O
O
D
T
U
O
YG
K
C
A
L
B
K
C
A
L
B
D
E
R
D
E
R
D
AY
OA
L
L
RE
E
VR
O
K
C
A
L
B
D
E
R
C
R
O
S
S
E
R
P
M
O
C
D
E
R
R
O
NT
A
O
FM
R
COMPRESSOR
CAPACITOR
- 14 -
YG
E
U
L
B
E
U
L
B
YG
FAN
CAPACITOR
Service manual
MSG-16CR
INDOOR UNIT
K
C
A
L
B
K
C
A
L
B
D
E
R
D
E
R
R
O
NT
A
O
FM
E
U
L
B
E
U
L
B
FAN
CAPACITOR
COMPRESSOR
CAPACITOR
YG
D
E
R
K
C
A
L
B
- 15 -
D
E
R
D
AY
OA
L
L
RE
E
VR
O
C
R
O
S
S
E
R
P
M
O
C
YG
)
N
(
2
1
T
I
N
U
R
O
O
D
T
U
O
YG
Service manual
MSG-18CR, MSG-21CR
COMPRESSOR RELAY
TRANSFORMER
BLUE
WHITE
BROWN
SWITCH BOARD
CN14
CN4
LOUVER MOTOR
LOUVER MOTOR
HEAT EXCHANGER
SENSOR
AMBIENT SENSOR
INDOOR MOTOR
INDOOR UNIT
)
N
(
2
1
T
I
N
U
R
O
O
D
T
U
O
YG
K
C
A
L
B
K
C
A
L
B
D
E
R
D
E
R
D
AY
OA
L
L
RE
E
VR
O
K
C
A
L
B
D
E
R
C
R
O
S
S
E
R
P
M
O
C
D
E
R
R
O
NT
A
O
FM
R
COMPRESSOR
CAPACITOR
- 16 -
YG
E
U
L
B
E
U
L
B
YG
FAN
CAPACITOR
BLACK
CN5
CN6
CN10
CN8 CN7
WHITE
CN1
CN12
DISPLAY BOARD
CURRENT DETECTOR
CN2
CN9
Service manual
- 17 -
Service manual
- 18 -
Service manual
8. Installation details
8.1
8.2
Torque
Kg.m
1.8
4.2
5.5
6.6
6.6
inch
1/4
3/8
1/2
5/8
3/4
The power cord of connect should be selected according to the following specifications sheet.
Grade
Unit
mm2
8.3
7K
1.0
9K
1.0
12K
1.5
18K
2.5
24K
2.5
28K
2.5
Capacity
Btu/h
7k~12K
16K~28K
30K~36K
Pipe size
GAS
3/8 (9.52)
1/2 (12.7)
1/2 (12.7)
5/8 (15.88)
5/8 (15.88)
5/8 (15.88)
3/4 (19.05)
LIQUID
1/4 (6.35)
1/4 (6.35)
1/4 (6.35)
1/4 (6.35)
3/8 (9.52)
3/8 (9.52)
3/8 (9.52)
Standard
length
Max.
Max.
Additional
(m)
Elevation
Elevation
refrigerant
5
5
5
5
5
5
5
B (m)
5
5
8
10
10
15
15
A (m)
10
10
15
20
20
30
30
(g/m)
30
30
30
30
65
65
65
In case that
more than
5
Caution:
Capacity is base on standard length and maximum allowance length is base of reliability.
Oil trap should be install per 5-7 meters.
- 19 -
Service manual
8.4
Required tools:
Hexagonal wrench; adjustable wrench; torque wrenches, wrench to hold the joints and gas leak
detector.
Note:
The air in the indoor unit and in the piping must be purged. If air remains in the refrigeration piping, it
will affect the compressor, reduce the cooling capacity, and could lead to a malfunction of unit.
Be sure, using a torque wrench to tighten the service port cap (after using the service port), so that it
prevents the gas leakage from the refrigeration cycle.
Procedure
1. Recheck the piping connections.
2. Open the valve stem of the 2-way valve
counterclockwise approximately 90, wait
10 seconds, and then set it to closed
position.
Be sure to use a hexagonal wrench to operate
the valve stem
3. Check for gas leakage.
Check the flare connection for gas leakage
4. Purge the air from the system.
Set the 2-way valve to the open position and
remove the cap from the 3-way valves
service port.
Using the hexagonal wrench to press the
valve core pin, discharge for three seconds
and then wait for one minute.
5. Use torque wrench to tighten the service
port cap to a torque of 1.8 kg.m. (18n.m)
6. Set the 3-way valve to the opened
position.
- 20 -
Service manual
8.5
Procedure
1. Confirm that both the 2-way and 3-way valves are set to the opened position.
Remove the valve stem caps and confirm that the valve stems are in the opened position.
Be sure to use a hexagonal wrench to operate the valve stems.
2. Operate the unit for 10 to 15 minutes.
3. Stop operation and wait for 3 minutes, then connect the charge set to the service port of the
3-way valve.
Connect the charge hose with the push pin to the gas service port.
4. Air purging of the charge hose.
Open the low-pressure valve on the charge set slightly to purge air from the charge hose.
5. Set the 2-way valve to the close position.
6. Operate the air conditioner at the cooling cycle and stop it when the gauge indicates 0.1MPa.
7. Immediately set the 3-way valve to the closed position.
Do this quickly so that the gauge ends up indicating 0.3 to 0.5Mpa.
8. Disconnect the charge set, and amount the 2-way and 3-way valves stem nuts and service
port caps.
Use a torque wrench to tighten the service port cap to a torque of 1.8 kg.m.
Be sure to check for gas leakage.
- 21 -
Service manual
8.6
Procedure:
1. Confirm that both the 2-way and 3-way valves are set to the closed position.
2. Connect the charge set and a charging cylinder to the service port of the 3-way valve.
Leave the valve on the charging cylinder closed.
3. Air purging.
Open the valves on the charging cylinder and the charge set. Purge the air by loosening the flare nut
on the 2-way valve approximately 45 for 3 seconds then closing it for 1 minutes; repeat 3 times.
After purging the air, use a torque wrench to tighten the flare nut to on the 2-way valve.
4. Check the gas leakage.
Check the flare connections for gas leakage.
5. Discharge the refrigerant.
Close the valve on the charging cylinder and discharge the refrigerant until the gauge indicate 0.3 to
0.5 Mpa.
6. Disconnect the charge set and the charging cylinder, and set the 2-way and 3-way valves to
the open position.
Be sure to use a hexagonal wrench to operate the valve stems.
7. Mount the valve stems nuts and the service port cap.
Be sure to use a torque wrench to tighten the service port cap to a torque 18N.m.
Be sure to check the gas leakage.
- 22 -
Service manual
8.7
Procedure:
1. Confirm that both the 2-way and 3-way valves are set to the open position.
2. Connect the charge set to the 3-way valves service port.
Leave the valve on the charge set closed.
Connect the charge hose with the push pin to the service port.
3. Open the valves (Low side) on the charge set and discharge the refrigerant until the gauge
indicates 0.05 to 0.1 Mpa.
If there is no air in the refrigeration cycle [the pressure when the air conditioner is not running is
higher than 0.1Mpa, discharge the refrigerant until the gauge indicates 0.05 to 0.1 Mpa. If this is the
case, it will not be necessary to apply a evacuation.
Discharge the refrigeration gradually; if it is discharged too suddenly, the refrigeration oil sill be
discharged.
- 23 -
Service manual
8.8
Evacuation
Procedure:
1. Connect the vacuum pump to the charge sets centre hose.
2. Evacuation for approximately one hour.
Confirm that the gauge needle has moved toward -0.1 Mpa (-76 cmHg) [vacuum of 4 mmHg or less].
3. Close the valve (Low side) on the charge set, turn off the vacuum pump, and confirm that the
gauge needle does not move (approximately 5 minutes after turning off the vacuum pump).
4. Disconnect the charge hose from the vacuum pump.
Vacuum pump oil, if the vacuum pump oil becomes dirty or depleted, replenish as needle.
- 24 -
Service manual
8.9
Gas charging
Procedure:
1. Connect the charge hose to the charging cylinder.
Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom
of the cylinder.
2. Purge the air from the charge hose.
Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the
air (be careful of the liquid refrigerant).
3. Open the valves (Low side) on the charge set and charge the system with liquid refrigerant.
If the system cannot be charge with the specified amount of refrigerant, if can be charged with a little
at a time (approximately 150g each time0 while operating the air conditioner in the cooling cycle;
however, one time is not sufficient, wait approximately 1 minute and then repeat the
procedure.(pumping down-pin).
4. Immediately disconnect the charge hose from the 3-way valves service port.
Stopping partway will allow the refrigerant to be discharged.
If the system has been charged with liquid refrigerant while operating the air conditioner, turn off the
air conditioner before disconnecting the hose.
5. Mounted the valve stem caps and the service port
Use torque wrench to tighten the service port cap to a torque of 18N.m.
Be sure to check for gas leakage.
- 25 -
Service manual
9. Capacity table
9.1
MSG-07CRN2
9.2
30C
35C
40C
45C
50C
1.97
1.44
0.67
2.13
1.57
0.69
2.27
1.73
0.71
2.53
1.95
0.74
1.85
1.38
0.70
2.04
1.52
0.73
2.17
1.67
0.75
2.43
1.89
0.78
1.71
1.29
0.73
1.90
1.45
0.76
2.05
1.60
0.78
2.35
1.84
0.81
1.58
1.20
0.79
1.80
1.38
0.82
1.94
1.52
0.84
2.18
1.72
0.88
1.47
1.13
0.88
1.68
1.29
0.91
1.81
1.42
0.94
2.00
1.60
0.97
1.37
1.05
0.91
1.55
1.20
0.94
1.66
1.32
0.97
1.88
1.52
1.01
MSG-07HRN2
- 26 -
Capacity kW
Input kW.
Capacity kW
Input kW.
Capacity kW
Input kW.
Capacity kW
Input kW.
30C
35C
40C
45C
50C
1.97
1.44
0.67
2.13
1.57
0.69
2.27
1.73
0.71
2.53
1.95
0.74
1.85
1.38
0.70
2.04
1.52
0.73
2.17
1.67
0.75
2.43
1.89
0.78
1.71
1.29
0.73
1.90
1.45
0.76
2.05
1.60
0.78
2.35
1.84
0.81
1.58
1.20
0.79
1.80
1.38
0.82
1.94
1.52
0.84
2.18
1.72
0.88
1.47
1.13
0.88
1.68
1.29
0.91
1.81
1.42
0.94
2.00
1.60
0.97
1.37
1.05
0.91
1.55
1.20
0.94
1.66
1.32
0.97
1.88
1.52
1.01
0C D
-1C W
1.95
0.67
1.88
0.69
1.83
0.70
1.81
0.73
-4C D
-6C W
1.68
0.59
1.59
0.60
1.51
0.62
1.48
0.66
-7C D
-8C W
1.47
0.53
1.38
0.54
1.25
0.57
1.23
0.59
OUTDOOR CONDITIONS
12C D
7C D
4C D
11C W
6C W
3C W
2.76
2.42
2.22
0.86
0.78
0.73
2.71
2.38
2.16
0.88
0.79
0.74
2.34
2.69
2.14
0.80
0.91
0.76
2.66
2.31
2.11
0.94
0.81
0.77
Service manual
9.3
MSG-09CRN2
9.4
30C
35C
40C
45C
50C
2.50
1.82
0.86
2.71
1.99
0.88
2.88
2.19
0.91
3.21
2.47
0.95
2.35
1.75
0.90
2.58
1.93
0.93
2.75
2.12
0.96
3.08
2.40
1.00
2.17
1.64
0.94
2.42
1.84
0.97
2.60
2.03
1.00
2.98
2.34
1.04
2.00
1.52
1.02
2.28
1.75
1.05
2.46
1.93
1.08
2.77
2.19
1.12
1.87
1.43
1.13
2.13
1.64
1.16
2.29
1.80
1.20
2.53
2.02
1.25
1.73
1.34
1.17
1.96
1.52
1.20
2.11
1.67
1.24
2.38
1.93
1.29
MSG-09HRN2
- 27 -
Capacity kW
Input kW.
Capacity kW
Input kW.
Capacity kW
Input kW.
Capacity kW
Input kW.
30C
35C
40C
45C
50C
2.50
1.82
0.86
2.71
1.99
0.88
2.88
2.19
0.91
3.21
2.47
0.95
2.35
1.75
0.90
2.58
1.93
0.93
2.75
2.12
0.96
3.08
2.40
1.00
2.17
1.64
0.94
2.42
1.84
0.97
2.60
2.03
1.00
2.98
2.34
1.04
2.00
1.52
1.02
2.28
1.75
1.05
2.46
1.93
1.08
2.77
2.19
1.12
1.87
1.43
1.13
2.13
1.64
1.16
2.29
1.80
1.20
2.53
2.02
1.25
1.73
1.34
1.17
1.96
1.52
1.20
2.11
1.67
1.24
2.38
1.93
1.29
0C D
-1C W
2.68
0.92
2.58
0.95
2.52
0.97
2.48
1.01
-4C D
-6C W
2.31
0.81
2.19
0.83
2.07
0.85
2.04
0.91
-7C D
-8C W
2.03
0.73
1.90
0.74
1.72
0.78
1.69
0.81
OUTDOOR CONDITIONS
12C D
7C D
4C D
11C W
6C W
3C W
3.80
3.33
3.05
1.18
1.07
1.00
3.73
3.27
2.98
1.21
1.09
1.01
3.22
3.70
2.94
1.10
1.25
1.05
3.66
3.18
2.90
1.29
1.11
1.06
Service manual
9.5
MSG-12CRN2
9.6
30C
35C
40C
45C
50C
3.36
2.46
1.14
3.64
2.68
1.17
3.88
2.95
1.21
4.32
3.33
1.26
3.16
2.36
1.20
3.48
2.59
1.24
3.71
2.85
1.28
4.14
3.23
1.33
2.93
2.21
1.25
3.25
2.47
1.29
3.50
2.73
1.33
4.01
3.15
1.38
2.69
2.05
1.35
3.07
2.35
1.39
3.31
2.60
1.44
3.73
2.94
1.49
2.52
1.92
1.50
2.86
2.21
1.55
3.08
2.43
1.60
3.41
2.73
1.66
2.33
1.80
1.55
2.64
2.05
1.60
2.84
2.25
1.65
3.21
2.60
1.72
MSG-12HRN2
- 28 -
Capacity kW
Input kW.
Capacity kW
Input kW.
Capacity kW
Input kW.
Capacity kW
Input kW.
30C
35C
40C
45C
50C
3.36
2.46
1.14
3.64
2.68
1.17
3.88
2.95
1.21
4.32
3.33
1.26
3.16
2.36
1.20
3.48
2.59
1.24
3.71
2.85
1.28
4.14
3.23
1.33
2.93
2.21
1.25
3.25
2.47
1.29
3.50
2.73
1.33
4.01
3.15
1.38
2.69
2.05
1.35
3.07
2.35
1.39
3.31
2.60
1.44
3.73
2.94
1.49
2.52
1.92
1.50
2.86
2.21
1.55
3.08
2.43
1.60
3.41
2.73
1.66
2.33
1.80
1.55
2.64
2.05
1.60
2.84
2.25
1.65
3.21
2.60
1.72
0C D
-1C W
3.44
1.18
3.31
1.21
3.23
1.23
3.19
1.28
-4C D
-6C W
2.96
1.02
2.81
1.05
2.66
1.09
2.61
1.15
-7C D
-8C W
2.60
0.93
2.43
0.94
2.21
0.99
2.16
1.03
OUTDOOR CONDITIONS
12C D
7C D
4C D
11C W
6C W
3C W
4.87
4.27
3.92
1.50
1.37
1.27
4.78
4.20
3.82
1.54
1.39
1.29
4.13
4.74
3.77
1.40
1.58
1.33
4.70
4.08
3.72
1.64
1.41
1.35
Service manual
9.7
MSG-16CRN2
9.8
30C
35C
40C
45C
50C
4.50
3.28
1.56
4.87
3.58
1.61
5.19
3.94
1.66
5.78
4.45
1.72
4.23
3.15
1.64
4.65
3.47
1.69
4.96
3.82
1.75
5.54
4.32
1.82
3.91
2.95
1.71
4.35
3.30
1.77
4.68
3.65
1.82
5.36
4.21
1.89
3.60
2.74
1.85
4.11
3.14
1.91
4.42
3.47
1.97
4.98
3.94
2.04
3.36
2.57
2.05
3.83
2.95
2.12
4.12
3.25
2.18
4.55
3.64
2.27
3.12
2.40
2.12
3.53
2.74
2.19
3.80
3.00
2.26
4.29
3.48
2.35
MSG-16HRN2
- 29 -
Capacity kW
Input kW.
Capacity kW
Input kW.
Capacity kW
Input kW.
Capacity kW
Input kW.
30C
35C
40C
45C
50C
4.50
3.28
1.56
4.87
3.58
1.61
5.19
3.94
1.66
5.78
4.45
1.72
4.23
3.15
1.64
4.65
3.47
1.69
4.96
3.82
1.75
5.54
4.32
1.82
3.91
2.95
1.71
4.35
3.30
1.77
4.68
3.65
1.82
5.36
4.21
1.89
3.60
2.74
1.85
4.11
3.14
1.91
4.42
3.47
1.97
4.98
3.94
2.04
3.36
2.57
2.05
3.83
2.95
2.12
4.12
3.25
2.18
4.55
3.64
2.27
3.12
2.40
2.12
3.53
2.74
2.19
3.80
3.00
2.26
4.29
3.48
2.35
0C D
-1C W
4.39
1.39
4.23
1.43
4.13
1.46
4.07
1.52
-4C D
-6C W
3.77
1.22
3.59
1.25
3.39
1.29
3.34
1.37
-7C D
-8C W
3.32
1.10
3.11
1.12
2.81
1.18
2.76
1.22
OUTDOOR CONDITIONS
12C D
7C D
4C D
11C W
6C W
3C W
6.22
5.45
5.00
1.78
1.62
1.51
6.10
5.35
4.87
1.83
1.65
1.53
5.27
6.05
4.82
1.66
1.88
1.58
5.99
5.21
4.74
1.94
1.68
1.60
Service manual
9.9
MSG-18CRN2
30C
35C
40C
45C
50C
4.79
3.50
1.62
5.18
3.81
1.67
5.52
4.19
1.72
6.15
4.73
1.79
4.50
3.35
1.71
4.95
3.69
1.76
5.27
4.06
1.81
5.90
4.60
1.89
4.16
3.14
1.78
4.63
3.52
1.83
4.98
3.88
1.89
5.70
4.48
1.97
3.83
2.91
1.92
4.37
3.34
1.98
4.71
3.69
2.04
5.30
4.19
2.12
3.58
2.74
2.13
4.08
3.14
2.20
4.39
3.46
2.27
4.85
3.88
2.36
3.32
2.56
2.20
3.76
2.91
2.27
4.04
3.19
2.34
4.57
3.70
2.44
9.10 MSG-18HRN2
SUMMER Cooling mode
Indoor
Conditions
21C D
Total capacity kW
15C W
Sensitive capacity kW
Input kW.
24C D
Total capacity kW
17C W
Sensitive capacity kW
Input kW.
27C D
Total capacity kW
19C W
Sensitive capacity kW
Input kW.
32C D
Total capacity kW
23C W
Sensitive capacity kW
Input kW.
WINTER
Indoor
Conditions
15C
18C
20C
22C
- 30 -
Capacity kW
Input kW.
Capacity kW
Input kW.
Capacity kW
Input kW.
Capacity kW
Input kW.
30C
35C
40C
45C
50C
4.79
3.50
1.62
5.18
3.81
1.67
5.52
4.19
1.72
6.15
4.73
1.79
4.50
3.35
1.71
4.95
3.69
1.76
5.27
4.06
1.81
5.90
4.60
1.89
4.16
3.14
1.78
4.63
3.52
1.83
4.98
3.88
1.89
5.70
4.48
1.97
3.83
2.91
1.92
4.37
3.34
1.98
4.71
3.69
2.04
5.30
4.19
2.12
3.58
2.74
2.13
4.08
3.14
2.20
4.39
3.46
2.27
4.85
3.88
2.36
3.32
2.56
2.20
3.76
2.91
2.27
4.04
3.19
2.34
4.57
3.70
2.44
0C D
-1C W
4.64
1.59
4.47
1.64
4.36
1.67
4.30
1.74
-4C D
-6C W
3.99
1.39
3.79
1.43
3.59
1.47
3.53
1.57
-7C D
-8C W
3.51
1.26
3.28
1.28
2.97
1.35
2.92
1.40
OUTDOOR CONDITIONS
12C D
7C D
4C D
11C W
6C W
3C W
6.57
5.76
5.28
2.04
1.85
1.72
6.45
5.66
5.15
2.09
1.88
1.75
5.57
6.39
5.09
1.90
2.15
1.81
6.34
5.51
5.01
2.23
1.92
1.83
Service manual
9.11 MSG-21CRN2
SUMMER Cooling mode
Indoor
Conditions
21C D
Total capacity kW
15C W
Sensitive capacity kW
Input kW.
24C D
Total capacity kW
17C W
Sensitive capacity kW
Input kW.
27C D
Total capacity kW
19C W
Sensitive capacity kW
Input kW.
32C D
Total capacity kW
23C W
Sensitive capacity kW
Input kW.
30C
35C
40C
45C
50C
5.07
3.70
1.78
5.48
4.03
1.84
5.84
4.44
1.89
6.50
5.01
1.97
4.76
3.55
1.88
5.24
3.90
1.94
5.58
4.30
2.00
6.24
4.87
2.08
4.41
3.33
1.96
4.90
3.72
2.02
5.27
4.11
2.08
6.03
4.74
2.16
4.05
3.08
2.11
4.63
3.54
2.18
4.98
3.91
2.25
5.61
4.43
2.34
3.79
2.89
2.35
4.31
3.32
2.42
4.64
3.66
2.50
5.13
4.10
2.60
3.52
2.71
2.42
3.98
3.08
2.50
4.28
3.38
2.58
4.83
3.92
2.68
9.12 MSG-21HRN2
SUMMER Cooling mode
Indoor
Conditions
21C D
Total capacity kW
15C W
Sensitive capacity kW
Input kW.
24C D
Total capacity kW
17C W
Sensitive capacity kW
Input kW.
27C D
Total capacity kW
19C W
Sensitive capacity kW
Input kW.
32C D
Total capacity kW
23C W
Sensitive capacity kW
Input kW.
WINTER
Indoor
Conditions
15C
18C
20C
22C
- 31 -
Capacity kW
Input kW.
Capacity kW
Input kW.
Capacity kW
Input kW.
Capacity kW
Input kW.
30C
35C
40C
45C
50C
5.07
3.70
1.78
5.48
4.03
1.84
5.84
4.44
1.89
6.50
5.01
1.97
4.76
3.55
1.88
5.24
3.90
1.94
5.58
4.30
2.00
6.24
4.87
2.08
4.41
3.33
1.96
4.90
3.72
2.02
5.27
4.11
2.08
6.03
4.74
2.16
4.05
3.08
2.11
4.63
3.54
2.18
4.98
3.91
2.25
5.61
4.43
2.34
3.79
2.89
2.35
4.31
3.32
2.42
4.64
3.66
2.50
5.13
4.10
2.60
3.52
2.71
2.42
3.98
3.08
2.50
4.28
3.38
2.58
4.83
3.92
2.68
0C D
-1C W
5.36
2.06
5.17
2.11
5.04
2.16
4.97
2.24
-4C D
-6C W
4.61
1.79
4.38
1.85
4.15
1.90
4.08
2.02
-7C D
-8C W
4.05
1.63
3.79
1.65
3.44
1.74
3.38
1.81
OUTDOOR CONDITIONS
12C D
7C D
4C D
11C W
6C W
3C W
7.60
6.67
6.11
2.63
2.39
2.22
7.46
6.54
5.95
2.70
2.43
2.26
6.44
7.39
5.89
2.45
2.77
2.33
7.32
6.37
5.80
2.87
2.47
2.36
Service manual
10.3 Function
Remote receiving
Testing and forced running
Position set for indoor unit wind vane
LED displaying and alarm
On or off Timer
Protection for the compressor
Current protection
High temperature protection of indoor heat exchanger at heating mode
Auto defrosting and heating recovery at heating mode
Anti cold air at heating mode
- 32 -
Service manual
10.4 Protection
10.4.1 3 minutes delay at restart for compressor.
10.4.2 Sensor protection at open circuit and breaking disconnection
10.4.3 Fan Speed is out of control. When Indoor Fan Speed is too high(higher than High
Fan+300RPM)or too low(lower than 400RPM), the unit stops and LED displays failure information
and cant returns to normal operation automatically.
10.4.4 Cross Zero signal error warning. If there is no Cross Zero signals in 4 minutes, the unit stops
and LED displays failure information and cant returns to normal operation automatically.
10.4.5 The current protection of the compressor
If compressor turns off for continuously 4 times due to current protection in 5 minutes from
Compressor On, the unit stops and LED displays failure information and cant returns to normal
operation automatically.
- 33 -
Service manual
EVAP. temp. up
TE5
TE6
- 34 -
TA-TS
Service manual
Block
A
B
C
Indoor
Fan
LOW
BREEZE
LOW
BREEZE
LOW
BREEZE
- 35 -
Service manual
10.8.7 The louver opens to Standard Angle ANGLHEAT when power is on for the first time
- 36 -
Service manual
Calculate from the end of latest defrost, evaporator high temp. Protection only closes outdoor fan
with the compressor still running. Add up to 90 minutes.
Defrosting time
At condition , If item B is satisfied before item A, it would be regarded as severe frosting and the
defrosting time is 10 minutes. If item B is satisfied after item A, the defrosting time is 6minutes.
At condition , the defrosting time is 10 minutes.
After three times continuous 6-minute defrost, the fourth defrost time should be 10 minutes.
The circulation is as following:
25s
5s
4-way valve
2s
Outdoor fan
Indoor fan
10s
- 37 -
Service manual
10.10.2
The indoor fan blows automatically in corresponding selected mode
10.10.3
The motion of indoor fans blade should accord with the selected operation mode
10.10.4
One mode should be carried out for at least 15 minutes once selected. If the compressor
cannot start for 15 minutes, reselect the operation mode according to the room temp. and set temp.,
or reselect when the set temp. varies
10.12.3
Heating:
The set temperature decrease 1 per hour. Two hours later, the set temperature will maintain as a
constant and the air circulation is kept at low speed (Anti-cold function takes precedence over all).
- 38 -
Service manual
10.12.4
Auto:
After an hour running under economic mode, the set temp will rise 1,if it is under cooling mode; the
set temp will decrease 1,if it is under heating mode; the set temp will be changeless, if it is under
fan-only mode; the condition will be the same after the air conditioner running under economic mode
after 2 hours, and during the next time the set temp do not change. The total time is 7 hours, after 7
hours the unit stops.
- 39 -
Service manual
MSG-07CR
8.5
6.2
5.2
4.2
2
7
200
124
MSG-07HR
8.5
6.2
5.2
4.2
3.2
28
32
30
26
2
7
60
53
50
200
0
124
16C
MSG-09CR
10
7.5
5.5
4.5
2
7
200
124
MSG-09HR
10
7.5
5.5
4.5A
3.5
28
32
30
26
2
7
60
53
50
200
0
124
14C
MSG-12CR
11
10
8
6
3
8
200
124
MSG-12HR
11
10
8
6
5.5
28
32
30
20
3
8
60
53
50
200
0
124
14C
TMDEFROST
[']
17C
15C
15C
TLDEFROST
[']
18C
16C
16C
Model
I3SEC [A]
I5MIN [A]
IFAN [A]
IRESTORE [A]
IDEFROST [A]
TE1 ['C]
TE2 ['C]
TE3 ['C]
TE4 ['C]
TE5 ['C]
TE6 ['C]
TE7 ['C]
TE8 ['C]
TE9 ['C]
ANGLCOOL [']
ANGLHEAT [']
ANGLOFF [']
THDEFROST [']
TMDEFROST [']
TLDEFROST [']
- 40 -
MSG-16CR
16
MSG-16HR
16
MSG-18CR
16
MSG-18HR
16
MSG-21CR
17
MSG-21HR
17
13
13
13
13
16
16
11
11
11
11
14
14
9.5
9.5
9.5
9.5
12
12
6.5
6.5
34
34
34
36
36
36
30
30
30
20
20
20
10
10
10
10
10
10
50
60
60
64
52
52
56
50
50
50
50
105
0
50
50
50
105
0
50
105
17C
17C
20C
18C
18C
21C
19C
19C
22C
Service manual
12. Troubleshooting
12.1 Display board
Operation
The indicator flashes once every second after power is on and illuminates when the air conditioner is
in operation.
Timer indicator:
The indicator illuminates then TIMER is set ON.
PRE-DEF. indicator (For cooling & heating mode only)
The air conditioner starts defrosting automatically if outdoor unit frosts in heating operating.
At this time, PRE-DEF. indicator illuminates.
Auto indicator:
This indicator flashes when the air conditioner is in AUTO operation.
ECON indicator
This indicator illuminates while the air conditioner is in economic operation.
- 41 -
Service manual
12.2 Troubleshooting
For cooling mode:
Failure phenomenon
Indoor fan speed has been out of control for over 1 minute
Indoor room temp. or evaporator sensor is open circuit or short circuit
Over current protection of the compressor occurs 4 times
EEROM error
No over-zero signal
r Extinguish
Flash at 5Hz
Operation
lamp
X
On
Timer
lamp
X
On
- 42 -
Operation
lamp
X
X
On
Timer
lamp
X
Defrosting
lamp
X
X
Service manual
- 43 -
Service manual
- 44 -
Service manual
- 45 -
Service manual
- 46 -