Professional Documents
Culture Documents
CH ADSS Specification 09-5 PDF
CH ADSS Specification 09-5 PDF
June, 2009
www.cablehub.co.za
ADSS SPECIFICATIONS
TABLE OF CONTENT
Cable Hub
ADSS SPECIFICATIONS
1. SCOPE
This technical specification covers the construction, mechanical, electrical, and optical performance, installation
guidelines, acceptance criteria, test requirements, environmental consideration, and accessories for
ALL-DIELECTRIC SELF-SUPPORTING FIBER OPTIC CABLEADSS, which is made of aramid yarns and
other nonmetallic components. The ADSS cable is designed to be located primarily on overhead utility facilities.
2. STANDARDS
Unless otherwise specified in this specification, all requirements for individual components and completed cable
shall be mainly in accordance with the following standard specifications.
IEEE Std 1222TM-2004
IEC 60794-4
IEC 60793-1
IEC 60793-2
IEC 60794-1
ITU-T G..650
Definition and test method for the relevant parameters of single-mode fibers
ITU-T G..652
ITU-T G..655
EIA 492A
EIA 472A
Sectional Specification for Fiber Optic Communication Cables for Outside Aerial Use
ISO 9001
ISO14001
Cable Hub
ADSS SPECIFICATIONS
3. SPECIFICATIONS of ADSS
1. Technical parameter of ADSS
Characteristic
Unit
Value
Type
mm
12.4
kg/km
124
20000
8000
MPa
13623
1/
8.2110-6
Temperature range
Operation
-10+50
Installation
10
11
-40+70
Installation
mm
252
Operation
mm
126
Installation
N/ 100mm
2200
Operation
N/ 100mm
1000
KV
<12
Crush resistance
ADSS SPECIFICATIONS
Color of tube
Blue
Orange
Green
Brown
Slate
White
No.
Color of tube
Blue
Orange
Green
Brown
4. Optical fiber
Unless otherwise specified in this specification, all requirements for optical fiber shall be mainly in
accordance with ITU-T G.652D standard.
1. Core and cladding
Each optical fiber shall consist of a core made of fused silica or a composition.
The cladding intimately surrounding the core shall be also fused silica or a composition of slightly
smaller index.
2. Primary coating
The bare fiber shall be coated with a suitable UV cured material for protection from abrasion during
subsequent handling or manufacturing.
3. Fiber parameters
Refractive index profile
Step index
9.30.5m (1310nm)
10.51.0m (1550nm)
1252m
1m
1%
Cladding non-circularity
Fiber cut-off wavelengthc*
1100 1330nm
25015m
Wavelength
Value
1310nm
0.36 Db/km
13838nm
0.35 Db/km
1550nm
0.22 Db/km
1288-1339nm
1550nm
18 ps/(nm km)
PMD
Note : * by Cut-back technique(IEC 60793-1-C1A) or
Backscattering technique (IEC 60793-1-C1C)
Cable Hub
ADSS SPECIFICATIONS
Reference
EIA/TIA-455-170
EIA/TIA-455-82B
EIA/TIA-455-81A
IEEE Std 1222
IEEE Std 1222
IEEE Std 1222
EIA/TIA-455- 41A
EIA/TIA-455-25A
EIA/TIA-455-33A
EIA/TIA-455-3A
IEEE Std 1222
IEEE Std 1222
IEC60068-2-1
TIA-455-85A
EIA/TIA-455-104A
EIA/TIA-455-33A
EIA/TIA-455-78A
EIA/TIA455-62A
EIA/TIA-455-3A
EIA/TIA-455-78A
IEC60793-1-44
IEC60794-1-F5
IEC60794-1-E14
IEC60794-1-E3
IEC60794-1-E4
IEC61395
IEC60794-1-E1
IEC60794-1-F1
ASTM M3349
IEC60793-1-C11
EIA/TIA-455
EIA/TIA-455
EIA/TIA-455
ADSS SPECIFICATIONS
Fig. 3.
Drawing of Reel
According to length of cable, we choose different type reel (D,d,b,w1,w2) for loading cable.
6.INSTALLATION RECOMMENDATIONS
1. Installation procedure
It is recommended that IEEE Std 524-1992 and our company recommended procedures be used for the installation
of ADSS.
2. Hardware and accessories
Suspension and dead-end hardware, vibration damper, bonding clamps and joint enclosure etc. for ADSS must
been designed for a specific size of ADSS. Therefore, hardware and other accessories connected electrically and
mechanically to the ADSS must be suitable for the ADSS being used.
Cable Hub