You are on page 1of 4

Monitoring of HV

Apparatus Insulation

Monitoring of HV Apparatus Insulation


Leakage current sensors
Yuanxing ALT series leakage current transducer is based
on zero flux principle, used for high voltage electrical
equipment on-line insulation monitoring devices of
transformer substation, accurately measuring the mA
and leakage current of equipment, output direct current
standard signal, the primary measured current is electrical
isolated from the secondary output signal. Nice appearance, waterproof
paint surface treatment, directly suitable for outdoor installation.
Yuanxing can design and produce various leakage current transducers
according to customers special demands, the devices showed on the
right side are just several representative ones.

Transformers

Features

Sensors

Cross core design, convenient installation, safe and reliable


Metal case design, strong anti interference capability, suitable for
indoor and outdoor environment
High sensitivity design, high accuracy, good linearity
Passive and active series are optional.
Nice appearance, waterproof paint surface treatment, suitable for
outdoor using.

Specification

Transducers

Application
Used for high voltage electrical equipment on-line
insulation monitoring devices of transformer substation,
accurately transmitting the mA grade leakage current in
the high voltage equipments, such as transformer bushing,
current transformer, voltage transformer, coupling
capacitor, arrester, and so on.

Operating frequency50Hz
Rated current10mA20mA30mA
Measuring range0.5700mA
Output signalV
Ratio0.1%
Phase difference: 1
Environment temperature: -25+55, the influence of
temperature changes to phase difference is <1 min
Primary cross core diameter12mm, 20mm,25mm, 40mm, 50mm,70 mm, 90mm, 100mm

Representative
Specification

Performance
parameter

AC leakage current sensor: Rated current 50mA(AC), isolation measuring AC current, output AC voltage signal.
Model No.

ALS12B-50mA/3.53V

IN

Rated input(AC)

50mA

Ip

Measuring range(AC)

0.01-100mA

RM

Measuring resistance

>100K

VM

Rated output (AC)

3.53V

KN

Turn ratio

----

Ta=+25 Accuracy

IN 0.3%

Vc

Power supply voltage

12VDC/ 15VDC

Vi

Isolation voltage

Between the primary and secondary circuit: 2.5KV rms/50HZ/1 min

Voff

Offset VoltageTa=+25

<1mV for primary current IN=0

Td

Temperature driftTa=-40+85

0.05%/ of VM

Linearity

<0.3%

di/dt

----

Frequency range

50HZ(400HZ)

Ta

Operating temperature

-40+85

Ts

Storage temperature

-40+100

Ic

Consumption

10mA

Rs

Secondary internal resistanceTa=+25

----

Primary internal resistanceTa=+25

----

Weight

450g

Phone: +86-533-381-8450
Fax: +86-533-381-8724

0.3% of IN

YUANXING Electronics Co., Ltd.

Pioneering Park, Science & Technology Industry Zone,


Zhangdian, Zibo, Shandong, PRC 255095

4 -3

www.yuanxing.net
sales@yuanxing.net

Monitoring of HV
Apparatus Insulation

Leakage current sensors

YUANXING

Circuit connection diagram

Outline Dimensionmm

Green

+
-

Yellow

Output

Black

GND

Red

Transformers

Shield

IN measured current

Sensors

Transducers

Representative Specification
Performance parameter
AC leakage current sensor: Rated current 50mA(AC), isolation measuring AC current, output AC voltage signal
Model No.

ALS25-50mA/3.53V

IN

Rated input (AC)

50mA

Ip

Measuring range(AC)

0.01-100mA

RM

Measuring resistance

>100K

VM

Rated output(AC)

3.53V

KN

Turn ratio

----

AccuracyTa=+25

IN 0.3%

Vc

power supply voltage

12VDC/ 15VDC

Vi

Isolation voltage

Between the primary and secondary circuit: 2.5KV rms/50HZ/1 min

Voff

Offset voltageTa=+25

<1mV for primary current IN=0

Td

Temperature driftTa=-40+85

0.05%/ of VM

Linearity

<0.3%

di/dt

----

Frequency range

50HZ(400HZ)

Ta

Operating temperature

-40+85

Ts

Storage temperature

-40+100

Ic

Consumption

10mA

Rs

Secondary internal resistanceTa=+25

----

Primary internal resistanceTa=+25

----

Weight

760g

Phone: +86-533-381-8450
Fax: +86-533-381-8724

0.3% of IN

YUANXING Electronics Co., Ltd.

Pioneering Park, Science & Technology Industry Zone,


Zhangdian, Zibo, Shandong, PRC 255095

4 -4

www.yuanxing.net
sales@yuanxing.net

Leakage current sensors


Circuit connection diagram

Outline Dimensionmm

pinhole explanation
1 +
2 3 GND
4 M

Monitoring of HV
Apparatus Insulation

YUANXING

Transformers

Sensors

Transducers

Representative Specification
Performance parameter
AC leakage current sensor: Rated current 50mA(AC), isolation measuring AC current, output AC voltage signal
Model No.

ALS50-50mA/3.53V

IN

Rated input(AC)

50mA

Ip

Measuring range(AC)

0.01-100mA

RM

Measuring resistance

>100K

VM

Rated output(AC)

3.53V

KN

Turn ratio

----

AccuracyTa=+25

IN 0.3%

Vc

power supply voltage

12VDC/ 15VDC

Vi

Isolation voltage

Between the primary and secondary circuit: 2.5KV rms/50HZ/1 min

Voff

Offset voltageTa=+25

<1mV for primary current IN=0

Td

Temperature driftTa=-40+85

0.05%/ of VM

Linearity

<0.3%

di/dt

----

Frequency range

50HZ(400HZ)

Ta

Operating temperature

-40+85

Ts

Storage temperature

-40+100

Ic

Consumption

10mA

Rs

Secondary internal resistanceTa=+25

----

Primary internal resistanceTa=+25

----

Weight

2200g

Phone: +86-533-381-8450
Fax: +86-533-381-8724

0.3% of IN

YUANXING Electronics Co., Ltd.

Pioneering Park, Science & Technology Industry Zone,


Zhangdian, Zibo, Shandong, PRC 255095

4 -5

www.yuanxing.net
sales@yuanxing.net

Monitoring of HV
Apparatus Insulation

Leakage current sensors

YUANXING
Outline Dimensionmm

Circuit connection diagram


pinhole explanation

Transformers

1
2
3
4

+
GND
M

Sensors

Representative Specification
Performance parameter

AC leakage current sensor: Multi-switch selective rated current, isolation measuring AC current, output AC voltage signal.
Model No.

IN

ALS20K-2.5800mA/6.72V

Rated input (AC)/mA

Switch

S1

S2

S3

S4

S5

S6

S7

S8

S9

Mode 1

2.5

10

15

20

25

30

35

40

Mode 2

50

100

200

300

400

500

600

700

800

RM

Measuring resistance

>100K

VM

Rated output(AC)

6.72V

Accuracy

IN 0.3%@Ta=+25

Vc

power supply voltage

12VDC/ 15VDC/85V220VAC

Vi

Isolation voltage

Between the primary and secondary circuit: 2.5KV rms/50HZ/1 min

Voff

Offset voltage

<1mV @Ta=+25for primary current IN=0

Td

Temperature drift

0.05%/ of VM @Ta=-40+85

Linearity

<0.3%

Frequency range

50HZ(400HZ)

Ta

Operating temperature

-40+85

Ts

Storage temperature

-40+100

Ic

Consumption

10mA

Rs

Secondary internal resistance

----@Ta=+25

Weight

1650g

Outline Dimensionmm
111

0.5% of IN@Ta=+25

85
75
R2
,5

Circuit connection diagram

+
-

22

98
35

180

Transducers

GND
,5
R2

IN measurand current
108
100
60

Jumper connection mode


Mode 1V03VO2 connectionconnect with 20 times amplification.
VO2

VO1

Mode 2V03VO1 connectionwithout 20 times amplification


VO2

Phone: +86-533-381-8450
Fax: +86-533-381-8724

VO1

YUANXING Electronics Co., Ltd.