Professional Documents
Culture Documents
Mechanical
TABLE OF CONTENTS
Types KS, KS-3 & SC. . . A-4
U-BLOK Mounting
Platforms . . . . . . . . . . A-39
SPEC-BLOK
PLATFORMS . . . . . . . A-42
Electro-Rail
Connectors . . . A-44, A-45
Types 1300A, 1350A,
1500A . . . A-46, A-47, A-48
Types BIBS-MT,
BIBD-MT . . . . . . . . . . A-57
Types KPU-AC,
UCU-AC . . . . . . . . . . . A-35
A-1
BURNDY
Mechanical
LIGHTNING PROTECTION INFO.
Basic rules for selection are:
1 Must be like material to the conductor
(Flexitap out due to steel bolts!).
A-2
2. Two bolts to ground rod minimum.
3 Cable to cable connections can be
anything one bolt, two bolt, compression, etc.
4 Cable to steel structure must have 8
square inch contact with steel.
SPECIAL FEATURES
Other features are also available for products
listed in price book such as undrilled or
special drilling, 45 or 90 pad angles, belling
for extra flexible cable, smooth or special
threaded studs, special labeling or packaging, extra long braid, and nuclear certification. REFER TO FACTORY.
ALL OTHERS
REFER TO FACTORY
1-800-346-4175
BURNDY
Mechanical
REVOLUTIONARY
BURNDY DESIGN
MEETS STRICT UL
486B STANDARDS
A-3
Tin-plated contact
surface inhibits oxide
formation.
BURNDY
Mechanical
TYPES KS & KS-3
SERVIT
A-4
CONDUCTOR
COPPER
CATALOG
NUMBER
KS90
KS15
KS17
* KS17-3
KS20
* KS20-3
KS22
* KS22-3
KS23
KS25
KS26
KS27
KS29
KS31
KS34
KS39
KS44
CROSS
FLATS
.50
.50
.63
.85
.85
1.14
.38
.38
.45
.69
1.20
.51
.75
1.50
.60
.82
.94
1.05
1.36
1.36
1.70
1.82
2.31
2.56
1.54
1.77
1.94
1.86
2.07
2.51
2.79
3.29
3.73
.62
.73
.82
1.17
1.17
1.41
1.48
1.94
2.19
SOL.
12 STR. - 10 STR.
10 STR. - 8 STR.
8 STR. - 6 SOL.
8 STR. - 6 SOL.
8 STR. - 4 SOL.
8 STR. - 4 SOL.
6 STR. - 2 SOL.
6 STR. - 2 SOL.
6 STR. - 2 STR.
4 STR. - 1/0 STR.
2 STR. - 2/0 STR.
1 STR. - 3/0 STR.
1 STR. - 250
1/0 STR. - 350
2/0 STR. - 500
4/0 STR. - 750
300 - 1000
16 STR.
14 STR.
14 STR.
16 STR.
14 STR.
14 STR.
14 STR.
14 STR.
14 STR.
14 STR.
14 STR.
8 SOL.
8 STR.
1/0 STR.
2/0 STR.
4/0 STR.
4/0 STR.
#10
#8
#6
#6
#4
#4
#2
#2
#1
2/0
3/0
4/0
Listed torque values are for maximum conductor combinations accommodated. Consult UL486 Tables 7-4, 7-5,
7-6 for smaller conductor combinations.
COPPERWELD
MIN. TAP
WITH
MAX. RUN
3 #12
3 #12
3 #10
3 #10
3 #8
3 #8
3 #7
3 #5
7 #7
7 #5
19 #8
19 #6
19 #5
8A
8A
6A
6A
4A
4A
3A
2A
9-1/2D
9-1/2D
8D
8D
6D
6D
5D
4D
RECOMMENDED
TIGHTENING
TORQUE in-lb
80
165
275
385
500
650
825
1000
1100
TYPE SC
SERVIT COVER
HUG-A-BUG
Used indoors or outdoors, this compact, onepiece plastic SERVIT cover saves time and
material, eliminates costly taping of splitbolts. Positive latch snaps easily and quickly
over connector, ideal for tight quarters. Selfpositioning plastic fingers wrap around wires
fully insulating joint. UL Listed for 600 volt
indoor application with type KS. Three Covers
accommodate a range of 6 SERVIT sizes
through 2/0 Str.
CATALOG
NUMBER
SC4
SC2
SERVIT and cover combination
can be ordered as follows:
CKS4
KS20 with cover
CKS2/0 KS26 with cover
For other combinations, please
contact factory.
SC2/0
BURNDY
Mechanical
TYPE KSU
UNIVERSAL SERVIT
A-5
CONDUCTOR
RUN
CATALOG
CROSS
NUMBER FIG. FLAT
KSU17
KSU20
KSU22
KSU23
KSU25
KSU26
KSU27
KSU29
KSU31
2
2
2
2
2
2
1
1
1
.62
.69
.74
.81
.93
1.04
1.38
1.38
1.69
KSU34
2.00
COPPER &
ALUMINUM
.92
1.05
1.25
1.48
1.77
1.93
2.34
2.50
2.88
TAP
ACSR AAAC
5005
COPPER &
ALUMINUM
ACSR AAAC
5005
MAXIMUM
CONDUCTOR
STEEL
RECOMMENDED
SOL. 3 STR. NOM
TIGHTENING
BWG BWG DIA. TORQUE in-lb.
8
6
4
8
6
4
5/32
7/32
1/4
5/16
3/8
7/16
1/2
1/2
5/8
165
275
275
385
385
500
650
650
825
BURNDY
Mechanical
TYPE KSA
TRITAP SERVIT
A-6
CATALOG CROSS
NUMBER FLATS L
KSA6
KSA4
KSA2
.75
.81
.94
1.28 .56
1.38 .62
1.58 .69
#6 STR. (.184)
#4 STR. (.232)
#2 STR. (.292)
#6 STR. (.184)
#4 STR. (.232)
#2 STR. (.292)
KSA 1/0
1.00
1.92 .75
KSA 2/0
1.12
1.92 .88
KSA 4/0
1.49
*KSA 350
1.69
*KSA 500
2.00
RECOMMENDED
TIGHTENING
TORQUE in-lb
#6 STR. (.184)
#4 STR. (.232)
#2 STR. (.292)
165
165
275
#8 SOL. (.129)
385
#8 STR. (.146)
385
#6 STR. (.184)
500
#4 STR. (.232)
650
#2 STR. COMPACT
(.268)
825
BURNDY
Mechanical
TYPE KVS
OKLIP
A-7
Mechanical Connector
For Copper & Copperweld
Compact, two-piece, high strength, high
copper alloy BURNDY OKLIP recommended for heavy duty connections. Neoprene
rings hold DURIUM bolts in place during
installation. Installed with ordinary wrench.
CONDUCTOR
COPPER
RUN
TAP
SOL.
COPPERWELD
MAX. RUN AND TAP
STR.
3/0
4/0
7 #8
7 #6
19 #8
19 #6
19 #5
CATALOG
NUMBER
KVS26
KVS28
KVS31
KVS34
KVS40
KVS44
Listed torque values are for maximum conductor combinations accommodated. Consult UL486 Tables 7-4, 7-5,
7-6 for smaller conductor combinations.
TYPE V
RECOMMENDED
TIGHTENING
TORQUE in-lb
V3/0
V250
V350
180
250
325
375
500
500
TYPE KVSU
UNIVERSAL OKLIP
Mechanical Connector
For All Combinations
of Copper, Aluminum,
ACSR, AAAC & 5005
Compact, high strength, tin plated copper
alloy two-piece connector with spacer and tinplated silicon bronze DURIUM hardware.
Recommended for heavy duty connections.
Spacer separates dissimilar conductors and
CONDUCTOR
RUN
CATALOG
NUMBER COPPER & ALUM.
KVSU26
KVSU28
KVSU31
KVSU34
KVSU40
KVSU44
TAP
ACSR,
AAAC,
& 5005
RUN
TAP
COPPER
COPPER
ACSR,
SOL.,
SOL.,
AAAC, COPPERWELD STEEL COPPERWELD STEEL
COPPER & ALUM. & 5005
SOL.,
NOM. DIA.
SOL.,
NOM. DIA. H
6 STR. - 2/0 STR.
6 STR. - 4/0 STR.
6 - 350
4 - 500
4/0 - 800
4/0 - 1000
6 - 2/0
6 - 4/0
6 - 300
5 - 397.5
3/0 - 715.5
4/0 - 900
1 - 3/0
2/0 - 4/0
5/16 - 7/16
3/8 - 1/2
9/16 - 5/8
3/4 - 3/4
3/4 - 1
7/8 - 1-1/8
#6 - 3/0
#6 - 4/0
#6 - 4/0
#4 - 4/0
RECOMMENDED
TIGHTENING
TORQUE in-lb
180
250
325
375
500
BURNDY
Mechanical
TYPE KVSW
OKLIP
A-8
Mechanical Connector
For Copper and Copperweld.
Similiar to OKLIP Type KVS except for a
high copper alloy spacer that separates run
and tap conductors. Provides high contact
pressure, confines conductor strands, and
assures vibration-proof connection. Longer
peened bolt, permits swivel action for easier
installation. Silicon bronze DURIUM hardware.
CATALOG
NUMBER
RECOMMENDED
TIGHTENING
TORQUE in-lb
CONDUCTOR
RUN
KVSW26
KVSW28
KVSW31
KVSW34
KVSW40
KVSW44
TAP
180
250
325
375
500
500
TYPE KVS-A
ALUMINUM OKLIP
Mechanical Connector
For All Combinations of
Copper, Aluminum, ACSR,
AAAC and 5005
Three-piece, high-conductivity, non-copper
bearing aluminum alloy connector with thick
spacer and aluminum hardware. Hardware in
KVS26A and KVS28A is stainless steel.
Recommended for heavy duty dissimilar
metal applications. Spacer separates conductors and provides long contact length. Belled
entrances prevent chafing, permit easier
assembly of conductors. Longer peened bolt
permits swivel action for easier installation.
Neoprene ring prevents loss of shorter bolt.
PENETROX joint compound recommended with aluminum and ACSR.
THESE CONNECTORS
CAN ACCOMMODATE
ACSR CONDUCTORS
OVER ARMOR ROD WITHIN
THE DIAMETER RANGE
INDICATED.
APPLICATION OVER
ARMOR ROD
CONDUCTOR
RUN
CATALOG
NUMBER
KVS26A
KVS28A
KVS31A
KVS34A
KVS40A
KVS44A
COPPER,
& ALUM.
ACSR,
AAAC, & 5005
COPPER,
& ALUM.
TAP
ACSR,
AAAC & 5005
RECOMMENDED
TIGHTENING
TORQUE in-lb
4 - 2/0
1/0 - 4/0
4/0 - 336.4
336.4 - 397.5
336.4 - 715.5
397.5 - 900
6 - 2/0
6 - 4/0
6 - 336.4
5 - 397.5
3/0 - 715.5
3/0 - 900
180
240
300
300
300
480
.281
.360
.565
.728
.728
.806
.116
.116
.184
.216
.470
.470
.447
.564
.681
.814
1.036
1.162
2-1/4
3
3-1/16
3-9/16
4-1/16
4-7/8
5/16
3/8
1/2
1/2
1/2
5/8
1-1/4
1-5/8
1-15/16
2-5/16
2-7/16
2-1/2
1-5/8
2-1/16
2-7/16
2-5/8
2-7/8
3-1/8
BURNDY
Mechanical
TYPE QPX
VERSITAP
A-9
Fig. 1
CATALOG
NUMBER
QPX2C2C
QPX282C
QPX2828
QPX342C
QPX3428
QPX3434
QPX442C
QPX4428
QPX4434
QPX4444
COPPER CONDUCTOR
RUN
TAP
6 STR. - 2 STR.
1 STR. - 4/0 STR.
250 - 500
500 - 1000
FIG. NO.
6 STR. - 2 STR.
6 STR. - 2 STR.
1 STR. - 4/0 STR.
6 STR. - 2 STR.
1 STR. - 4/0 STR.
250 - 500
6 STR. - 2 STR.
1 STR. - 4/0 STR.
250 - 500
500 - 1000
2
1
2
Fig. 2
1-1/2
2-1/16
5/16
2-3/8
3/8
5/16
2-3/4
3
2-11/16
2-7/8
3-1/16
3-7/16
3/8
5/16
3/8
L
1-5/16
1-13/16
1-3/8
1-3/4
2-1/16
1-3/8
1-13/16
2-1/16
2-5/8
W
1-3/8
1-9/16
1-13/16
1-7/8
2-1/16
2-3/16
2-1/4
2-7/16
RECOMMENDED
TIGHTENING
TORQUE in-lb
150
250
375
500
2-9/16
Listed torque values are for maximum conductor combinations accommodated. Consult UL486 Tables 7-4, 7-5, 7-6
for smaller conductor combinations.
See note page A-2.
CONDUCTOR
RUN
CATALOG
NUMBER
QPX2C2C
QPX282C
QPX2828
QPX342C
QPX3428
QPX3434
QPX442C
QPX4428
QPX4434
QPX4444
COPPERWELD
TAP
COPPERWELD
COPPER
5 SOL. - 3 #7
7 #9 - 7 #5
7 #9 - 7 #5
8A - 4A
3A - 3/0 V
3A - 3/0 V
19 #9 - 19 #6
4/0 EK
19 #6
COPPERWELD
5 SOL. - 3 #7
5 SOL. - 3 #7
7 #9 - 7 #5
5 SOL. - 3 #7
7 #9 - 7 #5
19 #9 - 19 #6
5 SOL. - 3 #7
7 #9 - 7 #5
19 #9 - 19 #6
19 #6
COPPERWELD
COPPER
8A - 4A
8A - 4A
3A - 3/0 V
8A - 4A
3A - 3/0 V
4/0 EK
8A - 4A
3A - 3/0 V
4/0 EK
BURNDY
Mechanical
TYPE QPX-Y
UNIVERSAL VERSITAP
A-10
Fig. 1
CATALOG
NUMBER
QPX2C2C-Y
QPX282C-Y
QPX2828-Y
QPX342C-Y
QPX3428-Y
QPX3434-Y
QPX4444-Y
CONDUCTOR
ALUMINUM OR COPPER
RUN
TAP
6 STR. - 2 STR.
1/0 STR. - 4/0 STR.
1/0 STR. - 4/0 STR.
250 - 500
750 - 1000
6 STR. - 2 STR.
6 STR. - 2 STR.
1/0 STR. - 4/0 STR.
6 STR. - 2 STR.
1/0 STR. - 4/0 STR.
200 - 500
750 - 1000
FIG. NO.
Fig. 2
H
1-5/8
1-7/8
2
2-1/4
2-1/2
2-7/8
3-7/8
1
1
2
2
5/16
1-1/2
3/8
5/16
2
1-1/2
2
2-1/2
3-1/2
3/8
1/2
W
1-5/8
1-7/8
2-1/8
2-1/8
2-1/2
2-5/8
3-1/2
APPLICATION
VARIATIONS
PARALLEL
TAP
CROSS
TEE
SPLICE
RECOMMENDED
TIGHTENING
TORQUE in-lb
150
250
375
500
BURNDY
Mechanical
TYPE KPA
SCRULUG
A-11
Fig. 1
CATALOG
NUMBER
KPA8C
KPA4C
KPA25
KPA28
KPA34
WIRE RANGE
FIG.
NO.
8 STR. - 14 SOL.
14 SOL. - 4 STR.
4 STR. - 1/0 STR.
1/0 STR. - 4/0 STR.
4/0 STR. - 500 kcmil
1
1
2
2
2
.38
.50
.75
.97
1.38
.47
.59
.81
1.12
1.38
.72
.94
1.25
1.66
2.44
Fig. 2
STUD
HOLE
SIZE
RECOMMENDED
TIGHTENING
TORQUE in-lb
.21
.27
.33
.40
.54
.10
1/4
5/16
3/8
1/2
.95
1.20
1.70
2.29
3.14
.22
.30
.41
.53
.75
.06
.06
.10
.13
.20
12
45
180
250
375
BURNDY
Mechanical
TYPE KPA-UP
SCRULUG
A-12
Fig. 1
CATALOG WIRE
NUMBER RANGE
KPA8CUP
KPA4CUP
KPA25UP
KPA28UP
KPA34UP
14 SOL.
6 STR.
14 SOL.
4 STR.
6 STR.
1/0 STR.
6 STR.
4/0 STR.
2/0 STR.
500 kcmil
Fig. 2
Fig. 3
STUD
HOLE
SIZE
0.38
0.51
0.81
0.20
#10
1.01
0.24
0.07
0.50
0.71
1.00
0.28
1/4
1.28
0.33
0.07
0.62
0.73
1.37
0.33
5/16
1.54
0.45
0.12
1.00
1.06
1.55
0.41
3/8
2.05
0.57
0.12
1.50
1.65
2.64
0.53
1/2
3.34
0.88
0.18
FIG.
NO.
NOTE: For tin plating drop -UP suffix and add -TP suffix
(example: KPA4CTP).
For use in grounding applications with a green screw - contact factory. Listed for grounding per UL467.
HARDWARE
1/4 Dia. Slot
Robertson
5/16 Dia. Slot
Robertson
3/8 Dia. Slot
Robertson
9/16 Dia. Hex
Socket
5/8 Dia. Hex
Head
RECOMMENDED
TIGHTENING
TORQUE in-lb
35
45
50
250
375
BURNDY
Mechanical
TYPE KLU
SCRULUG
A-13
Fig. 1
CATALOG
NUMBER
KLU25
KLU35
KLU70
KLU125
KLU175
KLU225
KLU300
KLU400
KLU650
FIG.
STUD
WIRE
RANGE
1
1
1
1
2
2
3
3
3
14 - 6
14 - 6
8-2
2 - 1/0
4 - 3/0
2 - 4/0
1/0 - 350
1/0 - 500
600 - 1000
0.28
0.43
0.50
0.61
0.75
1.00
1.21
1.49
1.88
0.31
0.38
0.50
0.62
0.75
1.00
1.10
1.50
2.00
0.47
0.57
0.61
0.86
1.20
1.24
1.60
2.12
1.90
0.66
0.91
1.05
1.50
1.40
1.64
2.63
2.74
3.73
Fig. 2
STUD
HOLE
SIZE
0.14
0.20
0.27
0.26
0.41
0.34
0.41
0.41
0.53
8
10
1/4
1/4
3/8
5/16
3/8
3/8
1/2
0.91
1.17
1.32
1.78
2.20
2.54
3.25
4.26
4.61
Fig. 3
SCREW TYPE
SCREW
SIZE
RECOMMENDED
TIGHTENING
TORQUE in-lb
Slot Robertson
Slot Robertson
Slot Robertson
Slot Robertson
Hex Socket
Hex Socket
Hex Head
Hex Head
Hex Head
8/32
1/4
5/16
3/8
3/8
7/16
5/8
5/8
3/4
20
45
50
50
124
204
325
375
500
BURNDY
Mechanical
TYPE KA
KA-LUG
A-14
Fig. 1
CATALOG
NUMBER
CONDUCTOR
KA8C
KA4C
KA25
KA25-2TC 38
KA28
KA34
14 SOL. - 8 STR.
14 SOL. - 4 STR.
4 STR. - 1/0 STR.
4 STR. - 1/0 STR.
1 STR. - 4/0 STR.
4/0 STR. - 500
STUD
HOLE
SIZE
3/8
9/16
3/4
3/4
15/16
1-3/8
5/8
3/4
15/16
15/16
1-1/4
2-3/32
#12
5/16
1/2
1/2
5/8
13/16
7/32
9/32
27/64
27/64
27/64
9/16
#10
1/4
3/8
3/8
3/8
1/2
FIG.
NO.
1
2
3
2
Fig. 2
Fig. 3
RECOMMENDED
TIGHTENING
TORQUE in-lb
13/16
1-1/8
1-11/16
2-13/16
1-15/16
2-9/16
3/16
1/4
3/8
3/8
7/16
9/16
3/32
7/64
1/8
1/8
3/16
9/32
25
45
200
200
275
375
TYPE EA
VERSILUG
For Copper Cable
Compact, high copper alloy terminal for joining a wide range of cable to equipment pads
or bar. Clamping element adjustable to
several angles. One-wrench installation.
CATALOG
NUMBER
EA2C
EA25
EA28
EA28-2N
EA34
EA34-2N
CONDUCTOR
8 SOL. - 2 STR.
2 STR. - 1/0 STR.
1/0 STR. - 4/0 STR.
250 - 500
NO. OF
HOLES
IN PAD
1
1
1
2 NEMA
1
2 NEMA
13/16
7/8
1-1/16
1-1/8
1-3/8
3-5/8
1-5/8
3-5/8
1-3/4
1-3/4
1-3/8
1-7/16
1-1/16
1-3/8
K
7/16
1-3/4
2-1/4
9/16
STUD
HOLE
SIZE
3/8
3/8
3/8
1/2
1/2
1/2
2-1/2
2-11/16
3-3/16
5-1/8
4
5-5/8
13/32
7/16
17/32
5/8
13/16
5/8
RECOMMENDED
TIGHTENING
TORQUE in-lb
1/4
150
180
5/16
250
3/8
375
BURNDY
Mechanical
TYPE BGBL
LAY-IN QIKLUG
A-15
Fig. 1
Fig. 2
DIMENSIONS
CATALOG
NUMBER
FIG
NO.
CONDUCTOR
RANGE
4 - 14 AWG
BGBL-1/0
1/0 - 14 AWG
BGBL-250
250 kcmil - 6
*BGBL-4
H
REF
.39
[10]
.63
[16]
.88
[22]
.62
[16]
.80
[20]
1.18
[30]
.48
[12]
.83
[21]
1.00
[30]
.79
[20]
1.16
[29]
1.72
[44]
J
1/4 - 28
3/8 - 24
7/16 - 18
TYPE CL50-1
COPPER LAY-IN QIKLUG
FOR COPPER
The Lay-In QIKLUG is manufactured from
high strength pure electrolytic copper to
ensure maximum strength and conductivity.
UL467 Listed for direct burial in earth or concrete. The open-faced design allows for fast
lay-in of the conductor without the need for
cutting or breaking.
CATALOG
NUMBER
CL50-1
WIRE RANGE
COPPER
STUD HOLE
#14 - #4 CU
#10
K
DIA.
.22
[6]
.28
[7]
.28
[7]
1.10
[28]
1.63
[41]
2.18
[55]
.20
[5]
.44
[11]
.45
[11]
.13
[3]
.19
[5]
.25
[6]
HEX
SIZE
SLOT
SLOT
7/32
BURNDY
Mechanical
TYPES QA, QQA
QIKLUG
A-16
Type QA
CATALOG NUMBER*
CONDUCTOR
TYPE QA TYPE QQA COMMERCIAL NAVY
QA8C-B
QA8C-2B
QA4C-B
QA4C-2B
QA1C-B
QA1C-2B
QA26-B
QA26-2B
QA28-B
QA28-2B
QA28-2N*
QA31-B
QA31-2B
QA31-2N*
QA34-B
QA34-2B
QA34-4B
QA34-2N*
QA40-B
QA40-2N*
QQA8C
QQA8C-2
QQA4C
QQA4C-2
QQA1C
QQA1C-2
QQA26
QQA26-2
QQA28
14 SOL. - 8 STR.
4 - 14
8 STR. - 4 STR.
23 - 40
4 STR. - 1 STR.
50 - 75
QQA28-2N*
QQA31
250 - 350
250 - 350
QQA31-2N*
QQA34
400 - 500
400 - 500
QQA34-2N*
QQA40-2N*
QQA40-4N
QA44-B
QA44-2N* QQA44-2N
QA44-4N* QQA44-4N*
QA46-B
QA46-2N*
600 - 800
850 - 1000
1100 - 1500
650 - 800
1000
1300
NO. OF
HOLES
IN PAD
1
2
1
2
1
2
1
2
1
2
2 NEMA
1
2
2 NEMA
1
2
4
2 NEMA
1
2 NEMA
4 NEMA
1
2 NEMA
4 NEMA
1
2 NEMA
C
9/16
5/8
13/16
1
1-3/16
1-3/8
1-7/8
1-3/8
1-5/8
3
9/16
11/16
1-1/4
5/8
7/32
5/8
3/4
1-3/16 5/8
9/32
3/4
1
1-9/16 7/8
11/32
1
1-3/16
1-15/16
1
13/32
1-1/16
2
1
1-5/16
3-1/8 1-3/4
9/16
1-3/8
17/32
1-31/32
1
1-11/16 7/16
3
1-3/4
9/16
1-5/8
17/32
2
13/32
1
2
1-15/16
7/16
3-3/32 1-3/4
9/16
1-7/8
11/16
2-7/16
3
1-3/4
9/16
2
3
3
3-1/16
2-1/8
2-1/8
3
1-7/8
E&F
Type QQA
1-3/4
1-3/4
11/16
2-3/4
3-1/8
STUD
HOLE
SIZE
#10
1/4
5/16
3/8
1/2
3/8
1/2
3/8
1/2
5/8
1/2
5/8
LL
1-3/8
2-5/16
2
3
1-7/16
2-3/8
2
2-15/16
1-3/4 2-13/16
2-9/16
3-5/8
2
3-3/16
3
4-3/16
2-1/4
3-9/16
3-9/16
4-5/16
5-5/8
2-11/36 4-1/8
3-3/8
4-7/16
5-7/8
3-3/16
4-7/8
3-9/16
3-1/2
4-11/16 6-9/32
3-11/16
4-14/16
7-3/32
3-15/16
RECOMMENDED
TIGHTENING
TORQUE in-lb
9/32
5/16
5/32
75
5/16
3/16
110
11/32
150
7/32
7/16
17/32
7/16
5/8
11/16
7/16
5/8
13/16
7/16
7/16
5/8
27/32
5/8
180
1/4
250
5/16
325
5/16
375
3/8
500
9/16
1/2
7-1/8
5/8
13/16
9/16
3/4
1/2
4-3/8
5-1/4
1-1/16
5/8
1/2
9/16
600
BURNDY
Mechanical
TYPE Q2A
QIKLUG
A-17
CATALOG
NUMBER*
Q2A1C-2
Q2A26-2N
Q2A28-2N
Q2A28-4N
Q2A31-2N
Q2A31-4N
Q2A34-2N
Q2A34-4N
Q2A40-2N
Q2A40-4N
Q2A44-4N
Q2A46-4N
CONDUCTOR
NO. OF
HOLES IN
PAD
4 STR. - 1 STR.
1/0 STR. - 2/0 STR.
2
2 NEMA
2 NEMA
4 NEMA
2 NEMA
4 NEMA
2 NEMA
4 NEMA
2 NEMA
4 NEMA
850 - 1000
1100 - 1500
4 NEMA
E&F
STUD
HOLE
SIZE
1-1/2
1-5/8
1-7/8
3
2-3/8
3
2-1/2
3
1-7/8
1
3/4
1-1/16
1-3/16
7/16
3/8
1-3/8
1-3/4
7/16
7/32
7/32
1-13/16
1-15/16
1-15/16
2-1/8
2-1/8
3
3
3-3/4
3-3/4
4-11/32
4-11/32
5
1/4
4-1/2
1-11/16
3-1/8
L
2-7/8
4-3/16
4-3/8
9/16
1/2
4-11/16
5/16
5/8
3/8
2-7/16
7/16
3-1/4
3-1/2
2-3/4
3-1/8
5-1/4
5-1/2
1/2
11/16
3-1/4
RECOMMENDED
TIGHTENING
TORQUE in-lb
150
180
250
325
375
500
600
TYPE Q3A
QIKLUG
For Copper Cable
Compact, high copper alloy terminal for joining three cables to equipment pads or bar.
Each element accommodates a wide range
of cable. One-wrench installation.
CATALOG
NUMBER*
Q3A28-2N
Q3A28-4N
Q3A31-2N
Q3A31-4N
Q3A34-2N
Q3A34-4N
Q3A40-4N
Q3A44-4N
Q3A46-4N
CONDUCTOR
NO. OF
HOLES IN
PAD
2 NEMA
4 NEMA
2 NEMA
4 NEMA
2 NEMA
4 NEMA
4 NEMA
4 NEMA
C
1-7/8
3
2-3/8
3
2-1/2
3-1/8
1-3/4
3
3-1/4
3-1/2
E&F
3-1/4
RECOMMENDED
TIGHTENING
TORQUE in-lb
1-3/8
4-5/16
4-3/8
1/4
3-3/16
250
1-11/16
4-7/16
5/16
4-1/16
325
3/8
4-9/16
375
7/16
1/2
11/16
5-13/16
6-5/8
7-7/8
1-15/16
2-7/16
2-3/4
3-1/8
9/16
STUD
HOLE
SIZE
1/2
4-3/4
5
5-1/4
5-1/2
5/8
500
600
BURNDY
Mechanical
TYPE QB
QIKLUG
A-18
CATALOG
NUMBER*
QB8C
QB4C
QB1C
QB26
QB28
QB31-2N
CONDUCTOR
NO. OF
HOLES
IN PAD
14 SOL. - 8 STR.
8 STR. - 4 STR.
4 STR. - 1 STR.
1/0 STR. - 2/0 STR.
3/0 STR. - 4/0 STR.
250 - 350
1
1
1
1
1
2 NEMA
STUD
HOLE
SIZE
9/16
9/16
27/32
13/16
1
1-1/16
3-1/4
1-3/4
7/8
13/16
1
1-1/32
1-5/16
1-11/16
7/32
#10
9/32
1/4
13/32
3/8
9/16
1/2
STUD
HOLE
SIZE
3/8
1/2
1
5-3/16
5-7/8
6-11/16
11/16
13/16
1
13/16
1-1/8
1-3/8
1-1/2
1-13/16
2-1/16
4-1/2
9/32
5/32
1/4
11/32
7/16
17/32
5/8
7/32
1/4
5/16
RECOMMENDED
TIGHTENING
TORQUE in-lb
75
110
150
180
250
325
TYPE Q2B
QIKLUG
For Copper Cable
Compact, high copper alloy terminal for joining two cables at right angles to a single
terminal block. Each element accommodates
a range of cable. One-wrench installation.
CATALOG
NUMBER*
Q2B28-2N
Q2B31-2N
Q2B40-4N
CONDUCTOR
NO. OF
HOLES
IN PAD
E&F
2 NEMA
2 NEMA
4 NEMA
1-7/8
2-3/8
3
3-1/8
3-3/16
3-1/16
1-3/4
1-11/16
1-3/8
1-3/8
1-3/8
2-5/16
9/16
5/8
1/4
5/16
7/16
RECOMMENDED
TIGHTENING
TORQUE in-lb
250
325
500
BURNDY
Mechanical
TYPE QDA
QIKLUG
A-19
CATALOG
NUMBER
QDA8C
QDA4C
QDA1C
QDA26
QDA28
QDA31
QDA34
QDA40
CONDUCTOR
COMMERCIAL
NAVY
14 SOL. - 8 STR.
8 STR. - 4 STR.
4 STR. - 1 STR.
1/0 STR. - 2/0 STR.
3/0 STR. - 4/0 STR.
250 - 350
400 - 500
600 - 800
3 - 14
23 - 40
50 - 75
100 - 125
150 - 200
250 - 350
400 - 500
650 - 800
1
1-1/4
1-1/2
1-7/8
2-1/8
11/16
3/4
1
1-3/16
1-5/16
1-11/16
2
2-5/16
7/16
STUD
HOLE
SIZE
L
1-7/8
3/8
9/16
1/2
11/16
13/16
1-1/16
5/8
3/4
1
2-3/16
2-1/2
2-5/8
3
3-5/8
4-3/16
RECOMMENDED
TIGHTENING
TORQUE in-lb
3/16
7/32
9/32
75
110
150
180
250
325
375
500
5/16
3/8
TYPE QR QIKLINK
SPLICE OR REDUCER
For Copper Cable to Cable
High copper alloy splicer/reducer for joining a
range of cable end to end. Neat, compact
easy to tape installation. One-wrench
installation.
CATALOG
NUMBER
QR4C
QR1C
QR26
QR28
QR31
QR34
QR40
See note page A-2.
CONDUCTOR
EITHER SIZE
RECOMMENDED
TIGHTENING
TORQUE in-lb
8 STR. - 4 STR.
4 STR. - 1 STR.
1/0 STR. - 2/0 STR.
3/0 STR. - 4/0 STR.
250 - 350
400 - 500
600 - 800
3/4
1-1/16
1-3/16
1-3/8
1-11/16
1-15/16
2-7/16
1-11/16
1-15/16
2-1/8
2-3/8
2-5/8
3-1/16
3-5/8
5/8
11/16
13/16
1
1-1/4
1-7/16
1-7/8
110
150
180
250
325
375
500
BURNDY
Mechanical
TYPE VT
VARITAP T-CONNECTOR
A-20
CATALOG
NUMBER
VT2C2C
VT2525
VT2825
VT2828
VT3025
VT3030
VT3425
VT3428
VT3430
VT3434
VT4040
VT4425
VT4428
VT4834
VT4844
VT4848
CONDUCTOR
RUN
TAP
8 SOL. - 2 STR.
6 SOL. - 1/0 STR.
8 SOL. - 2 STR.
6 SOL. - 1/0 STR.
6 SOL. - 1/0 STR.
1/0 STR. - 4/0 STR.
6 SOL. - 1/0 STR.
1/0 STR. - 300
6 SOL. - 1/0 STR.
1/0 STR. - 4/0 STR.
1/0 STR. - 300
300 - 500
500 - 800
6 SOL. - 1/0 STR.
1/0 STR. - 4/0 STR.
300 - 500
750 - 1000
1500 - 2000
1-5/16
2-5/16
2-5/8
3-1/8
3-1/16
3-3/8
3-5/16
3-11/16
3-1/2
3-5/8
3-3/4
4-1/2
4-5/16
4-1/8
5-1/4
5-3/4
6-1/4
1-5/16
1-7/16
1-1/4
1-11/16
1-3/8
1-15/16
1-1/2
1-11/16
1-15/16
2-1/4
2-5/8
2
2
5
5
5
300 - 500
500 - 800
750 - 1000
1500 - 2000
1-5/8
1-7/8
2-5/16
2-9/16
2-7/8
4-1/4
TYPE E-C-G
TRANSFORMER
TAP ADAPTER
For Copper
Multi-tap, range-taking cast copper alloy connector designed to take 2, 3 or 4 conductors
from a single secondary transformer outlet.
CATALOG
NO. OF
CONDUCTOR A
NUMBER CONDUCTORS
SIZE
DIA.
E2C34G1
E3C34G1
E4C34G1
2
3
4
.78
3-3/4 2-7/8
1/2-13 6-1/4
W
3-1/2
5-1/4
6-7/8
RECOMMENDED
TIGHTENING
TORQUE in-lb
480
RECOMMENDED
TIGHTENING TORQUE in-lb
RUN
TAP
275
385
250
250
325
325
375
375
375
375
500
500
500
600
600
600
275
385
385
250
385
325
385
250
325
375
500
385
250
375
500
600
BURNDY
Mechanical
TYPE VA, VVA
VARILUG
A-21
CATALOG NUMBER*
TYPE VA TYPE VVA
VA2C
VA25
VA28
VA28-2N
VA30
VA30-2N
VA34
VA34-2N
VA34-4N
VA40
VA40-2N
VA40-4N
VVA2
VVA25
VVA28
VVA28-2N
VVA30
VVA30-2N
VVA34
VVA34-2N
VVA34-4N
VVA40
VVA40-2N
VVA40-4N
CONDUCTOR
8 SOL. - 2 STR.
6 SOL. - 1/0 STR.
1/0 STR. - 4/0 STR.
1/0 STR. - 300
300 - 500
500 - 800
Type VVA
Type VA
NO. OF
HOLES
IN PAD
1
1
2 NEMA
1
2 NEMA
1
2 NEMA
4 NEMA
1
2 NEMA
4 NEMA
C
13/16
7/8
1-1/4
1-5/16
1-1/2
1-1/16
3-1/2
1-5/8
1-1/8
3-9/16
2
1-3/8
3-5/8
3
3-5/8
2-5/16
1-5/8
3-5/8
3
2-5/8
E&F
1-3/4
1-3/4
1-3/4
1-3/4
1-3/4
1-3/4
1-1/2
1-7/8
2-1/4
2-3/16
3-11/32
2-7/8
K
7/16
STUD
HOLE
SIZE
3/8
7/16
9/16
7/16
1/2
3/8
9/16
1/2
11/16
9/16
9/16
5/8
1/2
LL
2-3/4
4-1/16
2-7/8
4-5/16
2-7/8
4-1/8
4-15/16 6-3/6
3-1/4
4-5/8
5-3/16 6-9/16
3-13/16 5-5/16
5-3/8
6-7/8
5-3/8
6-7/8
4-1/2
6-3/8
5-13/16 7-11/16
5-13/16 7-11/16
13/32
1/4
7/16
17/32
5/8
5/16
5/8
5/8
13/16
5/8
5/8
3/8
15/16
5/8
5/8
RECOMMENDED
TIGHTENING
TORQUE in-lb
275
385
250
325
375
500
BURNDY
Mechanical
TYPE HFB-P1
A-22
2.00
3.00
4.00
4.00
6.00
6.00
8.00
2.00
3.00
2.00
4.00
3.00
6.00
8.00
3/8
3/8
3/8
1/2
1/2
5/8
3/4
4.38
4.38
5.75
5.75
7.75
8.12
10.50
RECOMMENDED
TIGHTENING
TORQUE in-lb
4.38
4.38
5.75
5.75
4.75
8.12
10.50
*
*
*
*
*
*
*
240
240
240
480
480
660
1990
COPPER
BUS BAR
WIDTH (INCHES)
RUN-A
TAP-AA
2
3
4
4
6
6
8
2
3
2
4
3
6
8
2
2
2
2
2
2
2
BOLTS
HFB22P1
HFB33P1
HFB42P1
HFB44P1
HFB63P1
HFB66P1
HFB88P1
NUTS
QTY.
CAT. NO.
QTY.
CAT. NO.
4
4
4
4
4
4
4
38 X (*) HEB
38 X (*) HEB
38 X (*) HEB
50 X (*) HEB
50 X (*) HEB
62 X (*) HEB
75 X (*) HEB
4
4
4
4
4
4
4
38CHEN
38CHEN
38CHEN
50CHEN
50CHEN
62CHEN
75CHEN
SPLIT LOCK
WASHERS
QTY.
CAT. NO.
4
4
4
4
4
4
4
38SW
38SW
38SW
50SW
50SW
62SW
75SW
CLAMP
NUMBER
J
BOLT DIA.
WHEN
Z = 1.25
WHEN
Z = 1.50
HFB22P1
HFB33P1
HFB42P1
HFB44P1
HFB63P1
HFB66P1
HFB88P1
3/8 (-16)
3/8 (-16)
3/8 (-16)
1/2 (-13)
1/2 (-13)
5/8 (-11)
3/4 (-10)
3.00
3.00
3.00
3.25
3.25
3.50
3.75
3.25
3.25
3.25
3.50
3.50
4.00
4.00
BOLT LENGTH
WHEN
WHEN
Z = 1.75
Z = 2.00
3.50
3.50
3.50
3.75
3.75
4.00
4.50
4.00
4.00
4.00
4.00
4.00
4.50
4.50
WHEN
Z = 2.25
WHEN
Z = 2.50
WHEN
Z = 2.75
WHEN
Z = 3.00
4.00
4.00
4.00
4.50
4.50
4.50
5.00
4.50
4.50
4.50
4.50
4.50
5.00
5.00
4.50
4.50
4.50
5.00
5.00
5.00
5.50
5.00
5.00
5.00
5.00
5.00
5.50
5.50
BURNDY
Mechanical
TYPE HFB-N
BAR CLAMP TAP
PAD ADAPTER
A-23
Fig. 1
Fig. 2
CATALOG
NUMBER
FIG.
NO.
A-C
E&F
HFB33-4N
HFB44-4N
HFB66-6N
1
1
2
3.00
4.00
6.00
1.75
1.75
1.75
7.00
9.12
11.31
.62
1.12
1.12
HFB33P1
HFB44P1
HFB66P1
BURNDY
Mechanical
TYPES KA-U, KKA-U
UNIVERSAL TERMINAL
A-24
Fig. 1
Fig. 2
AL9CU
Fig. 3
CATALOG
NUMBER*
FIG.
NO.
WIRE RANGE
ALUMINUM OR
COPPER
KA6U
KA2U
KA25U
KA26U
KA29U
KA30U
KA31U
KA34U
KA36U
KA40U
KA44U
KKA31U-2N
KA36U-2N
KA40U-2N
KA44U-2N
1
1
1
2
2
2
2
2
2
2
2
3
4
4
4
14 STR. - 6 STR.
14 STR. - 2 STR.
14 STR. - 1/0 STR.
6 STR. - 2/0 STR.
6 STR. - 250
6 STR. - 300
6 STR. - 350
4 STR. - 500
2 STR. - 600
300 - 800
500 - 1000
6 STR. - 350
2 STR. - 600
300 - 800
500 - 1000
STUD
HOLE
SIZE
1/4
5/16
3/8
1/2
1/2
.63
.63
.81
.81
.94
.94
1.03
1.50
1.72
1.69
1.69
3.16
3.22
3.03
3.03
1.06
1.16
1.50
1.47
2.00
2.00
2.25
2.81
3.19
3.38
3.38
5.50
4.69
4.75
4.75
Fig. 4
DIMENSIONS
**
N
W
E
.25
.31
.44
.47
.50
.50
.88
.88
.78
.88
.88
.63
.63
.63
.63
.50
.50
.63
.63
1.00
1.00
1.13
1.51
1.50
1.75
1.75
1.25
1.50
1.75
1.75
1.75
1.75
1.75
1.75
**
H
RECOMMENDED
TIGHTENING
TORQUE in-lb
.09
.10
.19
.19
.25
.25
.25
.31
.44
.50
.50
.38
.44
.50
.50
.50
.55
.80
.80
1.13
1.12
1.25
1.58
1.56
1.94
1.94
1.50
1.57
1.94
1.94
45
50
50
120
275
275
375
500
500
500
600
375
500
500
600
BURNDY
Mechanical
TYPE K2A-U
UNIVERSAL TERMINAL
A-25
(Two Conductor)
For Aluminum and
Copper Conductors
Fig. 1
These dual-rated two-conductor lugs are constructed from high strength aluminum alloy
and electro tin-plated to provide low contact
resistance.
Fig. 2
Fig. 3
CATALOG
NUMBER*
FIG.
NO.
WIRE RANGE
ALUMINUM OR
COPPER
K2A25U
K2A26U
K2A29U
K2A31U
K2A36U
K2A40U
K2A44U
K2A31U-2N
K2A36U-2N
K2A40U-2N
K2A44U-2N
1
2
2
2
2
2
2
3
3
3
3
STUD
HOLE
SIZE
1/4
3/8
1/2
5/8
1/2
.81
.81
1.50
1.69
1.75
1.66
1.66
3.00
3.22
3.03
3.03
1.47
1.47
2.56
2.88
3.20
3.38
3.50
4.50
4.69
4.75
4.75
DIMENSIONS
**
N
W
E
.44
.44
.50
.88
.63
.88
.88
.63
.63
.63
.63
1.13
1.25
1.66
1.94
2.41
3.19
3.52
2.31
2.41
3.19
3.19
1.75
1.75
1.75
1.75
**
H
RECOMMENDED
TIGHTENING
TORQUE in-lb
.19
.19
.25
.25
.44
.50
.50
.31
.44
.50
.50
.79
.79
1.20
1.25
1.58
1.94
1.94
1.38
1.56
1.94
1.94
50
50
275
275
375
375
375
275
375
375
375
BURNDY
Mechanical
TYPES K3A-U, KK3A-U
UNIVERSAL TERMINAL
A-26
(Three Conductor)
For Aluminum and
Copper Conductors
Fig. 1
Dual-rated three-conductor lugs are constructed from high strength aluminum alloy
and electro tin-plated to provide low contact
resistance.
Fig. 2
AL9CU
Fig. 3
CATALOG
NUMBER*
K3A2U-1*
K3A25U-2*
K3A26U-2N
K3A27U-2N
K3A29U-2N
K3A31U-2N
K3A36U-2N
KK3A36U-2N
KK3A40U-2N
KK3A44U-2N
FIG.
NO.
WIRE RANGE
ALUMINUM OR
COPPER
1
1
3
3
3
3
3
2
2
2
* Slotted screw.
** N indicates NEMA standard stud holes.
Listed torque values are for maximum conductor sizes
accommodated.
Consult UL486 Tables 7-4, 7-5, 7-6 for smaller conductor
sizes. All 4N items
See note page A-2
STUD
HOLE
SIZE
11/32
7/16
5/16
3/8
9/16
1/2
1.63
2.09
3.06
3.00
3.00
3.00
3.22
3.00
3.03
3.34
2.19
2.91
3.75
3.88
4.00
4.31
4.69
5.63
5.69
6.19
DIMENSIONS
N
W
E
.34
.34
.63
.63
.63
.63
.63
.56
.63
.63
.19
.25
.19
.31
.31
.31
.44
.44
.50
.56
.62
.88
1.79
1.12
1.19
1.38
1.56
1.69
1.94
1.88
1.59
1.94
1.95
2.81
2.81
3.00
3.63
4.22
4.81
4.75
.88
1.00
1.75
RECOMMENDED
TIGHTENING
TORQUE in-lb
50
275
375
BURNDY
Mechanical
TYPES K3A-U, KK3A-U
(Continued)
A-27
AL9CU
Fig. 1
Fig. 2
Fig. 3
CATALOG
NUMBER**
FIG.
NO.
WIRE RANGE
ALUMINUM OR
COPPER
K3A2U-4*
K3A25U-4*
K3A27U-4N
K3A29U-4N
K3A31U-4N
K3A36U-4N
K3A40U-4N
KK3A36U-4N
KK3A40U-4N
KK3A44U-4N
3
3
3
3
3
3
3
4
4
4
* Slotted screw
** N indicates NEMA standard stud holes.
Listed torque values are for maximum conductor sizes
accommodated. Consult UL486 Tables 7-4, 7-5, 7-6 for
smaller conductor sizes.
All 4N items
See note page A-2
STUD
HOLE
SIZE
11/32
7/16
5/16
3/8
9/16
1/2
Fig. 4
1.63
2.09
3.00
3.00
3.00
3.22
3.03
3.00
3.34
3.34
2.19
2.91
3.88
4.00
4.31
4.69
4.75
5.63
6.19
6.19
DIMENSIONS
N
W
E
.34
.34
.63
1.59
1.94
2.81
2.81
3.00
3.63
4.81
4.22
5.34
4.75
.88
1.00
1.75
.19
.25
.31
.31
.31
.44
.50
.44
.56
.56
.62
.88
1.12
1.19
1.38
1.56
1.94
1.69
1.88
1.88
RECOMMENDED
TIGHTENING
TORQUE in-lb
50
275
375
275
375
BURNDY
Mechanical
TYPES K4A-U, KK4A-U
UNIVERSAL TERMINAL
A-28
(Four Conductor)
For Aluminum and
Copper Conductors
Fig. 2
Fig. 1
AL9CU
CATALOG
NUMBER*
K4A29U-4N
K4A31U-4N
KK4A36U-4N
KK4A40U-4N
WIRE RANGE
ALUMINUM OR
COPPER
FIG.
NO.
1
1
2
2
STUD
HOLE
SIZE
1/2
DIMENSIONS
N
W
E
3
3
3.34
3
4
4.31
5.63
6.19
3.69
5.04
5
6
.63
1.75
.31
.31
.44
.56
1.19
1.38
1.69
1.88
RECOMMENDED
TIGHTENING
TORQUE in-lb
275
375
TYPES K11A-U,
K21A-U, K22A-U
Fig. 3
Fig. 2
Fig. 1
UNIVERSAL TERMINAL
For Aluminum and
Copper Conductors
Fig. 5
Fig. 4
CATALOG
NUMBER*
FIG.
NO.
K11A30U*
K11A34U-2
K11A36U-2
K21A36U-2
K22A36U-2
K11A39U-2
K22A39U-2
1
2
3
4
5
3
5
WIRE RANGE
ALUMINUM OR
COPPER
Two: 6 STR. - 300
Two: 4/0 STR. - 500
Two: 2 STR. - 600
Three: 2 STR. - 600
Four: 2 STR. - 600
Two: 1/0 STR. - 750
Four: 1/0 STR. - 750
STUD
HOLE
SIZE
5/16
1/4
3/8
DIMENSIONS
N
W
E
.69
.31
.63
2.00
2.38
1.38
.75
3.00
.94
3.00
2.91
.47
.25
4.91
.38
2.31
1.00
1.44
1.50
2.50
2.50
1.69
3.06
RECOMMENDED
TIGHTENING
TORQUE in-lb
275
375
BURNDY
Mechanical
TYPE KAU-KIT
TRANSFORMER LUG KIT
A-29
These dual-rated lugs are constructed from
high strength aluminum alloy and electro tinplated to provide low contact resistance.
Lugs and mounting hardware packaged
together in these kits.
TERMINALS
CATALOG TRANSFORMER
CATALOG
NUMBER
KVA RATING QTY.
NUMBER
KAU-KIT1
KAU-KIT2
KAU-KIT3
KAU-KIT4
WIRE RANGE
ALUMINUM
OR COPPER
15 - 37.5
15 - 45
50 - 75
75 - 112.5
100 - 167
150 - 300
1
3
1
3
1
3
8
4
KA2U
KA29U
#14 - 2
#6 - 250
12
KA29U
#6 - 250
6
7
K2A31U
K2A40U
#6 - 350
300 - 800
400 - 500
15
K2A40U
300 - 800
QTY.
BOLT SIZE
1/4-20 3/4 HH
8
8
5
6
7
4
1/4-20 3/4 HH
1/4-20 2 HH
1/2-13 3 HH
1/2-13 2-1/2 HH
1/2-13 2
1/2-13 2-1/2
HARDWARE
QTY.
NUT
QTY.
WASHER
1/4 20 HN
Captive to Nut
16
1/4 20 HN
Captive to Nut
11
1/2-13 HN
11
1/2-13 HN
22
11
22
11
1/2 FW
1/2 Belleville
1/2 FW
1/2 Belleville
BURNDY
Mechanical
TYPE AMS
A-30
DUAL RATED
SPLICER/REDUCER
For Copper and
Aluminum Cable
All splicer/reducers are dual rated for use with
aluminum and copper conductors and are
constructed from high strength, tin plated
aluminum. PENTROX oxide inhibiting joint
compounds are recommended for all
aluminum applications.
CATALOG
NUMBER
WIRE RANGE
MAX.
MIN.
AMS-2*
AMS-0*
AMS-4/0
AMS-250
AMS-350
AMS-500
AMS-750
AMS-1000
2
1/0
4/0
250
350
500
750
1000
14
8
6
6
6
3/0
250
500
H1
H2 MAX.
NO. OF
SCREWS
SCREW
DIA.
HEX
SIZE
1-19/32
1-29/32
2-5/16
4-3/32
4-11/32
4-25/32
6-1/16
8-11/16
9/16
3/4
1
1
1
1-1/4
1-7/16
1-21/32
9/16
3/4
1-3/32
1-3/32
1-3/32
1-3/8
1-5/8
1-7/8
.79
.86
1.28
1.29
1.30
1.48
1.98
2.34
2
2
2
4
4
4
4
6
3/8
7/16
9/16
5/8
11/16
13/16
15/16
1-1/8
S
S
5/16
5/16
5/16
3/8
1/2
9/16
BURNDY
Mechanical
TYPE AGSKIT
ABOVE GRADE SPLICE KITS
A-31
Fig. 1
Catalog
Number
AGSKIT2
AGSKIT250
Figure
Number
1
2
Fig. 2
Wire Range
Maximum Minimum
2
8
250
1
TYPE UGSKIT
WATERTIGHT/UNDERGROUND
SPLICE KITS
For all Aluminum or
Copper/Aluminum
Combinations
Type UGS Watertight Underground Splice Kit
consists of a standard AMS splice/reducer
and two heavy wall heat-shrink sleeves. The
AMS Splice is dual rated for use with
aluminum and copper conductors and are
constructed from high strength, tin plated
aluminum that provides low contact resistance and reduces the effects of galvanic
corrosion. Connector installed with common
installation tools. Both heavy wall heat shrink
sleeves are lined with adhesive material,
providing a watertight splice that can withstand abrasions that may occur during direct
burial applications. Heat shrink sleeve
installed with standard propane torch, or electric heat gun.
Fig. 1
Catalog
Number
UGSKIT2*
UGSKIT250*
Figure
Number
1
2
Wire Range
Maximum Minimum
2
8
250
1
Fig. 2
BURNDY
Mechanical
TYPE UGSKIT8
A-32
UF DIRECT BURIAL
SPLICE KIT
Type UGS UF Splice Kit consists of a UF
splice connector and a heavy wall heat-shrink
sleeve. The UF splice connector can accommodate up to four UF conductors and is
installed with common installation tools. The
heavy wall heat shrink sleeve is lined with an
adhesive material, providing a watertight
splice that can withstand abrasions that may
occur during direct burial applications. Heat
shrink sleeve installed with standard propane
torch, or electric heat gun.
Catalog
Number
UGSKIT8*
Wire Range
Copper
8 AWG 14 AWG
TYPE UGS350ULDB
IN-LINE SPLICE/REDUCER
For Direct Burial
CATALOG
NUMBER
UGS350ULDB
WIRE RANGE
10 AWG - 350 kcmil
LENGTH
In. [mm]
HEIGHT
In. [mm]
8.50
[216]
2.81
[71.4]
HEX SIZE
TORQUE
(In. Lbs.)
5/16
350
BURNDY
Mechanical
TYPE QGFL
BARTAP
A-33
CATALOG
NUMBER
QGFL1CB1
QGFL1CB1T6
QGFL26B1
QGFL26B1T6
QGFL26B2*
QGFL26B2T6*
QGFL29B1*
QGFL29B1T6*
QGFL31B1*
QGFL31B1T6*
QGFL34B1
QGFL34B1T6
QGFL39B1
QGFL39B1T6
QGFL44B1
QGFL44B1T6
QGFL46B1
QGFL46B1T6
QGFL48B1
QGFL48B1T6
COPPER
CONDUCTOR
10 SOL. - 1 STR.
B
1-1/8
1-1/4
1-1/2
6 STR. - 250
1-5/8
2 SOL. - 350
1-3/4
1/0 SOL. - 500
2
350 - 750
750 - 1000
1000 - 1500
2-1/4
1500 - 2000
H
1-7/8
2-3/8
2-1/8
2-5/8
2-1/2
2-1/8
2-5/8
3-1/8
2-7/8
3-1/4
3-1/8
3-5/8
3-1/4
3-5/8
3-3/8
4-1/8
4
4-1/2
5-1/4
5-1/4
J
3/8
1/2
T
(MAX.)
1/4
3/4
1/4
3/4
1/4
3/4
1/4
3/4
1/4
3/4
1/4
3/4
1/4
3/4
1/4
3/4
1/4
3/4
1/4
3/4
W
1
1-1/8
1-3/8
1-5/8
1-3/4
2-1/8
2-1/2
3
BURNDY
Mechanical
TYPE FCB
A-34
TRANSFORMER
TAP ADAPTER
For Copper and Aluminum
Silver brazed 101% conductivity copper
transformer tap adapter designed to accommodate from 1 to 6 NEMA drilled copper or
aluminum terminal taps from a single
secondary transformer outlet. Tin-plated.
Order mounting hardware & tap terminals
separately.
Fig. 1
FIG.
NO.
CATALOG
NUMBER
A
DIA.
H
REF.
1
2
1
2
1
2
FCB63-4N
FCB63-6N
FCB64-4N
FCB64-6N
FCB65-4N
FCB65-6N
FCB63-2NP300
FCB64-44NP50
.50
.50
.75
.75
1.00
1.00
.50
.75
5.25
5.25
5.75
5.75
7.00
7.00
5.00
9.00
3.75
5.50
4.00
5.75
4.25
6.00
3.50
5.00
2.25
2.25
2.75
2.75
4.00
4.00
3.00
5.00
Fig. 2
BURNDY
Mechanical
TYPE KPU-AC
POLYTAP
A-35
CATALOG
NUMBER
KPU29A26AC
KPU29A29AC
KPU34A26AC
KPU34A34AC
KPU39A26AC
KPU39A39AC
CONDUCTOR
COPPER OR ALUMINUM
RUN
TAP
1/0 STR. - 250
1/0 STR. - 250
4/0 STR. - 500
4/0 STR. - 500
500 - 750
500 - 750
RECOMMENDED
TIGHTENING
TORQUE in-lb
2-11/16
3-1/8
375
4-11/32
1-7/8
3-1/2
450
4-13/16
3-1/4
600
Listed torque values are for maximum conductor combinations accommodated. Consult UL486 Tables 7-4, 7-5, 7-6
for smaller combinations.
See note page A-2.
TYPE UCU-AC
RISER TAP
Parallel-groove riser tap and insulation cover
for copper and aluminum. Wide range-taking
assembly for apartment house and light
industrial applications. Cover and connector
are packaged together. Covers having insulating fingers that conform to conductors, fully
insulating the connection. UL486B Listed for
600 volts max. 90 C service.
CATALOG
NUMBER
UCU28AC
CONDUCTOR
RUN
TAP
2 STR. - 4/0 STR.
10 SOL. - 2 STR.
RECOMMENDED
TIGHTENING
TORQUE in-lb
2-1/4
1-13/16
2-5/8
120
BURNDY
Mechanical
TYPE BIPC
INSUL-TAP
A-36
CATALOG
NUMBER
BIPC1/0-2
BIPC4/0-6
BIPC4/0-1/0
BIPC350-4/0
BIPC350-350
BIPC500-4/0
CONDUCTOR RANGE
RUN
TAP
1/0 - 8 AWG
[50 - 6 mm2]
4/0 - 1/0 AWG
[95 - 50 mm2]
4/0 - 1/0 AWG
[95 - 50 mm2]
350 - 4/0 AWG
[185 - 95 mm2]
350 - 4/0 AWG
[185 - 95 mm2]
500 - 350 kcmil
[240 - 185 mm2]
2 - 8 AWG
[35 - 6 mm2]
1/0 - 6 AWG
[50 - 16 mm2]
4/0 - 1/0 AWG
[95 - 50 mm2]
4/0 - 10 AWG
[95 - 6 mm2]
350 - 4/0 AWG
[185 - 95 mm2]
4/0 - 4 AWG
[95 - 25 mm2]
Fig. 1
BOLT
SIZE
SOCKET FIG.
SIZE
NO.
5/16-18
1/2
5/16-18
1/2
5/16-18
1/2
3/8-16
9/16
3/8-16
9/16
3/8-16
9/16
Fig. 2
DIMENSIONS
H
L
W
2.00
[51]
2.50
[64]
2.50
[64]
3.00
[76]
3.00
[76]
3.25
[83]
1.53
[39]
2.12
[54]
2.12
[2.12]
1.59
[40]
2.62
[67]
1.59
[40]
2.56
[65]
2.00
[51]
2.06
[52]
2.50
[64]
2.75
[70]
2.62
[67]
RECOMMENDED
TORQUE (N,m)
180 in. lbs.
[20.3 N.m]
250 in. lbs.
[28.3 N.m]
250 in. lbs.
[28.3 N.m]
375 in. lbs.
[42.4 N.m]
300 in. lbs.
[33.9 N.m]
400 in. lbs.
[45.2 N.m]
MAX.
VOLTAGE
RATING
600V
300V
300V
300V
300V
600V
BURNDY
Mechanical
U-TAP
U-TAP AND MULTI-TAP are ideal for
splicing and tapping Aluminum or Copper
conductors. Each is AL9CU rated, UL Listed
and carries a 600-volt application rating.
A-37
FTU500MT
FTU 500
CATALOG
NUMBER SUPERCEDES
FTU-1
FTU2/0
FTU4/0
DU-1
DU-2/0
DU-4/0
FTU250
DU-250
FTU350
DU-350
FTU500
DU-500
FTU500MT
DU-500MT
FTU750 1, 2
DU-750
AL or CU
WIRE RANGE
RUN
TAP
2-1
1/0 - 2/0
3/0 - 4/0
3/0 thru
250 kcmil
250 kcmil
thru
350 kcmil
400 kcmil
thru
500 kcmil
300 kcmil
thru
500 kcmil
600 kcmil
thru
750 kcmil
#12 thru 1
#12 thru 2/0
#6 thru 4/0
#6 thru
250 kcmil
#6
thru
350 kcmil
#6
thru
500 kcmil
#6
thru
1/0 *
3/0
thru
750 kcmil
(WIRE STRIP
LENGTH)
L
APPROX.
WEIGHT
EACH (oz.)
1
1-1/8
1-1/4
7/8
1
1-1/2
1-7/16
1-5/8
2
1-1/4
1-1/2
3-5/8
1-3/8
1-5/8
2
4-1/4
ALLEN
WRENCH
SIZE
TORQUE
(in-lb)
5/32
100
1/4
200
STD.
PKG.
QTY.
50
40
20
15
1-1/2
1-3/4
2-5/16
15
1-5/8
2-5/16
2-15/16
11
3/8
375
10
1-7/8
2-5/16 RUN
1-5/32 TAP
3-3/8
10
5/16
110
10
2
3
3-3/4
18-1/4
3/8
375
BURNDY
Mechanical
A-38
U-BLOK POWER
DISTRIBUTION
BLOCKS
FT4B500MT
FT4B500
RUN
FT3B500MT
1
TAP*
8
6 thru 4/0
6 thru 350
6 thru 500
WEIGHT
EACH
1-1/4 lbs.
1-1/2 lbs.
3-7/8
5-7/8
4-1/8
2-1/8 lbs.
6 thru 1/0
ALLEN
WRENCH
SIZE
TORQUE
(in-lb)
1/4
200
3/8
375
5/16
110
STRIP
LENGTH
1-1/2
1-3/4
2-5/16
RUN
TAP
2-5/16 1-5/32
SUPERCEDES
3-TB-4/0
3-TB-350
3-TB-500
3-TB-500MT
2
RUN
1
TAP*
8
6 thru 4/0
6 thru 350
6 thru 500
6 thru 1/0
WEIGHT
EACH
2 lbs.
2-3/4 lbs.
3-7/8
7-7/8
4-1/8
2-3/4 lbs.
ALLEN
WRENCH
SIZE
TORQUE
(in-lb)
1/4
200
3/8
375
5/16
110
STRIP
LENGTH
1-1/2
1-3/4
2-5/16
RUN
TAP
2-5/16 1-5/32
SUPERCEDES
4-TB-4/0
4-TB-350
4-TB-500
4-TB-500MT
BURNDY
Mechanical
U-BLOK MOUNTING
PLATFORMS
A-39
CATALOG
NUMBER
TBPT-6*
TBPT-8
TBPT-10
TBPT-12
GUTTER
SIZE
WEIGHT
EACH
4-1/4
4-1/4
4-1/4
4-1/4
5-7/8
7-7/8
9-7/8
11-7/8
1-1/2
3-1/2
4
4
6
8
10
12
3/4 lb.
1-1/4 lb.
1-1/2 lb.
1-3/4 lb.
FLEXI-TAP
ALLOWABLE AMPACITIES OF INSULATED CONDUCTOR, 60 TO 90 C **
Size AWG
kcmil
60 deg. C
Copper
75 deg. C
90 deg. C
60 deg. C
90 deg. C
12
10
8
6
4
3
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
25
30
40
55
70
85
95
110
125
145
165
195
215
240
260
280
320
355
385
400
25
35
50
65
85
100
115
130
150
175
200
230
255
285
310
335
380
420
460
475
30
40
55
75
95
110
130
150
170
195
225
260
290
320
350
380
430
475
520
535
20
25
30
40
55
65
75
85
100
115
130
150
170
190
210
225
260
285
310
320
20
30
40
50
65
75
90
100
120
135
155
180
205
230
250
270
310
340
375
385
25
35
45
60
75
85
100
115
135
150
175
205
230
255
280
305
350
385
420
435
BURNDY
Mechanical
A-40
SPEC-BLOK
POWER
DISTRIBUTION
CONNECTORS
Unique, modular, made-to-order, powerdistribution assemblies accommodate any
number of supply and load conductors in any
number of poles. Capacity matches the conductors accommodated and SPEC-BLOK
assures uniform loading.
Burndy will design, quote, assemble and
ship SPEC-BLOK especially constructed to
suit your particular requirements within
48 hours upon request.
Adjacent poles are separated by easy-tohandle, wrap-around insulating covers which
eliminate taping and reduce heat build-up by
allowing air to flow freely around connectors.
SPEC-BLOK is UL Listed for copper or
aluminum conductors for 600 volts. (AL9CU)
Assemblies are mounted on platforms suitable for easy installation in wireway or
junction box.
BURNDY
Mechanical
SPEC-BLOK
SPEC-BLOK CONNECTORS
CATALOG DESIGNATION
(MAXIMUM
CONDUCTOR)
4
Conductor
2
Conductor
NUMBER OF
CONDUCTORS
ACCOMMODATED
4
Conductor
2
Conductor
AL or CU
WIRE RANGE UNDER
EACH CAP
DIMENSIONS
ALLEN
WRENCH
Second
SIZE
Conductor
Length Without Insulator
(if
Height On
First
Width
required)
Max
4
2
Conductors
May Be Conductors
Conductor Conductor
MUST Be
1/0-2/0
#12-2/0
2-9/16
1-1/2
2-1./8
7/8
3-1/8
1-11/16
4-1/4
1-3/8
5/32"
(2/0)
B
3/0-250
#6-250
(250)
C
S
(350)
1 to 4 (0, 1
or 2
per cap)
1 or 2
per cap
250-350
400-500
1/4"
#6-350
3-5/16
1-13/16
4-5/8
1-1/2
4-1/16
5-5/8
1-3/4
4-7/8
2-1/4
7-1/4
2-5/8
#6-500
(500)
E
600-750
3/8"
3/0-750
(750)
Large
Groove
Small
Grooves**
Height On
Maximum
Conductors
Width
__
6-1/0
3 1/2
3/0-500
6-1/0
4 1/8
Length
Without
Insulator
Allen
Wrench
Size
1 3/4
5/32"
A-41
BURNDY
Mechanical
SPEC-BLOK
MOUNTING PLATFORMS
A-42
SPEC-BLOK Mounting Platforms are rigid
steel construction with a black finish. They
can be supplied for junction box mounting or
wireway construction allowing trough conductors to pass underneath the assemblies.
(CPB-)
(CPT-)
CATALOG
NUMBER
L
(Nominal)
L
(Overall)
W
(Overall)
CPB6
CPB8
CPB10
CPB12
CPB16-5/8
CPB21-1/4
6
8
10
12
16-5/8
21-1/4
7-3/4
9-3/4
11-3/4
13-3/4
18-3/8
23
2-1/2
2-1/2
2-1/2
3-1/2
3-1/2
3-1/2
CATALOG
NUMBER
CPT6
CPT8
CPT10
CPT12
CPT16
5-7/8
7-7/8
9-7/8
11-7/8
15-7/8
2-1/2
3-1/2
3-1/2
3-1/2
3-1/2
2-1/4
3
3-1/2
4
4
SPEC-BLOK catalog numbers describe exactly how the distribution block is assembled:
5DR-NDST-GQP-12
(assembly pictured)
5
DR
12
BURNDY
Mechanical
QUESTIONNAIRE
FOR SPEC-BLOK
OR ELECTRO-RAIL
APPLICATIONS
A-43
___________________________________________________
__________different size
Yes
No
No
QUANTITY
LINE
PER
PHASE
SIZE
CONDUCTOR
TYPE
(Cu/Al)
LOAD
Address:____________________________________________
LINE
PER
NEUTRAL
__________________________________________________
LOAD
LINE
PER
GROUND
LOAD
Phone #:____________________________________________
BURNDY
Mechanical
ELECTRO-RAIL
For unlimited tapping capabilities up to the
maximum amperage rating limits of the bus
A-44 bar assembly, BURNDY offers ELECTRORAIL. UL Listed for Copper or Aluminum
and offering a 600-volt connector rating,
ELECTRO-RAIL can handle up to 4 feeders per phase. Bus bars, available in 3-or 4wire assemblies rated at 1300 to 1500 amps
per phase, come in various lengths. Bus bar
assemblies are pre-assembled on an insulated
platform that can be easily mounted by bolting through a wireway or to a junction box.
Connectors slide onto bus bars from either
end or inserted in the center slot of the rail for
sizes 18 inches and longer.
BURNDY
Mechanical
ELECTRO-RAIL
POWER DISTRIBUTION BUS
CONNECTORS
A-45
Fig. 1
Fig. 2
AL or CU WIRE RANGE
CATALOG NO.
RUN
TAP
NUMBER WIRES MAX. MIN. MAX. MIN.
2/0-2
P2/0-4
250-2
P250-4
400-2
P400-4
2-600-2
4-P600-4
750-2
2
4
2
4
2
4
2
4
2
2/0
2/0
250
250
400
400
600
600
750
1
1
2/0
2/0
4/0
4/0
400
400
750
2/0
2/0
250
250
400
400
600
600
750
12
12
6
6
6
6
6
6
4/0
Fig. 3
WIRE
STRIP
LENGTH
L
WEIGHT
EACH
5/8
1-1/4
7/8
1-5/8
1
1-15/16
1-1/4
2-3/8
1-1/2
7/8
7/8
1-3/8
1-3/8
1-1/2
1-1/2
3
3
3
1-7/8
1-7/8
2-1/4
2-1/4
2-3/4
2-3/4
2-3/4
2-3/4
3-3/8
1/16 lb.
3/16 lb.
3/16 lb.
3/8 lb.
1/4 lb.
9/16 lb.
3/4 lb.
1-13/16 lb.
1-1/16 lb.
Fig. 4
ALLEN
WRENCH TORQUE PCS. PER FIGURE STRIP
SIZE
(in-lb)
CARTON NUMBER LENGTH
5/32
5/32
1/4
1/4
1/4
1/4
3/8
3/8
3/8
100
100
300
300
300
300
450
450
450
6
10
3
10
15
10
6
3
6
1
2
1
2
1
2
3
4
3
7/8
7/8
1-3/8
1-3/8
1-1/2
1-1/2
3
3
3
BURNDY
Mechanical
A-46
3 WIRE BUS
ASSEMBLY
FOR TROUGH
(INSULATING COVERS AND
MOUNTING BASE INCLUDED)
Bus Assemblies consist of tin plated aluminum bus mounted to an insulating platform.
Each phase is separated with 94VO 600 volt
wrap-around adhesive insulations. The entire
assembly is mounted on a trough type base.
CATALOG
NUMBER
1300A-8-3-10
1300A-12-3-10
1300A18-3-10
1300A-24-3-10
1300A-30-3-10
1350A-8-3-12
1350A-12-3-12
1350A-18-3-12
1350A-24-3-12
1350A-30-3-12
1500A-12-3-10
1500A-18-3-10
1500A-24-3-10
1500A-30-3-10
1500A-12-3-12
1500A-18-3-12
1500A-24-3-12
1500A-30-3-12
AMP RATING
PER BUS
1300
1300
1300
1300
1300
1350
1350
1350
1350
1350
1500
1500
1500
1500
1500
1500
1500
1500
DIMENSIONS
LENGTH
BUS
INSULATION
8
12
18
24
30
8
12
18
24
30
12
18
24
30
12
18
24
30
12
16
22
28
34
12
16
22
28
34
16
22
28
34
16
22
28
34
WIDTH
HEIGHT
WEIGHT
10
10
10
10
10
12
12
12
12
12
10
10
10
10
12
12
12
12
4.75
4.75
4.75
4.75
4.75
5.25
5.25
5.25
5.25
5.25
4.75
4.75
4.75
4.75
5.25
5.25
5.25
5.25
8 lbs.
11 lbs.
15 lbs.
22 lbs.
26 lbs.
9 lbs.
12 lbs.
16 lbs.
23 lbs.
27 lbs.
15 lbs.
18 lbs.
27 lbs.
30 lbs.
16 lbs.
19 lbs.
28 lbs.
31 lbs.
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
BURNDY
Mechanical
4 WIRE BUS
ASSEMBLY
FOR TROUGH
A-47
CATALOG
NUMBER
1350A-8-4-12
1350A-12-4-10
1350A-18-4-12
1350A-24-4-12
1350A-30-4-12
1500A-12-4-12
1500A-18-4-12
1500A-24-4-12
1500A-30-4-12
AMP RATING
PER BUS
1350
1350
1350
1350
1350
1500
1500
1500
1500
DIMENSIONS
LENGTH
BUS
INSULATION
8
12
18
24
30
12
18
24
30
12
16
22
28
34
16
22
28
34
WIDTH
HEIGHT
WEIGHT
12
12
12
12
12
12
12
12
12
5.25
5.25
5.25
5.25
5.25
5.25
5.25
5.25
5.25
10 lbs.
13 lbs.
17 lbs.
26 lbs.
30 lbs.
18 lbs.
21 lbs.
30 lbs.
34 lbs.
1
1
1
1
1
1
1
1
1
BURNDY
Mechanical
A-48
WIRE BUS
ASSEMBLY FOR
JUNCTION BOXES
(INSULATING COVERS AND
MOUNTING BASE INCLUDED)
AMP RATING
PER BUS
1350
1350
1350
1350
1350
1500
1500
1500
1500
DIMENSIONS
LENGTH
BUS
INSULATION
8
12
18
24
30
12
18
24
30
12
16
22
28
34
16
22
28
34
WIDTH
HEIGHT
WEIGHT
12
12
12
12
12
12
12
12
12
2.75
2.75
2.75
2.75
2.75
2.75
2.75
2.75
2.75
9 lbs.
12 lbs.
16 lbs.
23 lbs.
27 lbs.
15 lbs.
18 lbs.
27 lbs.
30 lbs.
1
1
1
1
1
1
1
1
1
WIDTH
HEIGHT
WEIGHT
16
16
16
16
16
16
16
16
16
2.75
2.75
2.75
2.75
2.75
2.75
2.75
2.75
2.75
10 lbs.
13 lbs.
17 lbs.
26 lbs.
30 lbs.
18 lbs.
21 lbs.
30 lbs.
34 lbs.
1
1
1
1
1
1
1
1
1
AMP RATING
PER BUS
1350
1350
1350
1350
1350
1500
1500
1500
1500
DIMENSIONS
LENGTH
BUS
INSULATION
8
12
18
24
30
12
18
24
30
12
16
22
28
34
16
22
28
34
BURNDY
Mechanical
VERSI-POLE
POWER DISTRIBUTION
BLOCKS
VERSI-POLE Power Distribution Blocks
are designed to provide modular solutions to
power distribution applications. Each connector element is made from a high conductivity
aluminum alloy which is insulated with a high
strength polymer housing. One, two, and
three pole versions available. "Add" a pole
(snap-together) blocks are also available for
wire sizes up to 500 kcmil. For use with Cu or
Al. 600 V, AL9CU rated.
A-49
RUN
WIRE RANGE
AL9CU
TAP
WIRE RANGE
AL9CU
AMPERE
RATING PER
POLE
NUMBER OF
POLES
BDA-112-350
350 kcmil - 6
4 - 14
350
ADDER
BDA-16-350
350 kcmil - 6
2/0 - 14
350
ADDER
BDA-16-500
500 kcmil - 4
2/0 - 4
430
ADDER
BDA-26-350
350 kcmil - 6
2/0 - 14
700
ADDER
BDA-212-500
500 kcmil - 4
4 - 14
860
ADDER
BDA-26-500
500 kcmil - 4
2/0 - 14
860
ADDER
BDA-24-500
500 kcmil - 4
4/0 - 6
860
ADDER
BDA-11-500
500 kcmil - 4
500 kcmil - 4
430
ADDER
BDA-22-350
350 kcmil - 6
350 kcmil - 6
700
ADDER
BDA-22-500
500 kcmil - 4
500 kcmil - 4
860
ADDER
CATALOG
NUMBER
CONNECTOR
RUN
NOTES:
1. Order Optional BDB COVER1 per pole if desired.
2. Snap-together blocks can also be assembled to 1, 2, 3
pole blocks to create multi-pole distribution blocks.
TAP
BURNDY
Mechanical
VERSI-POLE
A-50
VERSI-POLE 1, 2, 3 POLE
DISTRIBUTION BLOCKS
RUN
WIRE RANGE
AL9CU
TAP
WIRE RANGE
AL9CU
AMPERE
RATING PER
POLE
BDB-16-2/0-1
BDB-16-2/0-2
BDB-16-2/0-3
2/0 - 12
4 - 14
195
1
2
3
BDBCOVER2
BDB-26-2/0-1
BDB-26-2/0-2
BDB-26-2/0-3
2/0 - 14
2 - 14
390
1
2
3
BDBCOVER2
BDB-112-350-1
BDB-112-350-2
BDB-112-350-3
350 kcmil - 6
4 - 14
350
1
2
3
BDBCOVER1
BDB-16-350-1
BDB-16-350-2
BDB-16-350-3
350 kcmil - 6
2/0 - 14
350
1
2
3
BDBCOVER1
BDB-14-500-1
BDB-14-500-2
BDB-14-500-3
500 kcmil - 4
2/0 - 14
430
1
2
3
BDBCOVER2
BDB-16-500-1
BDB-16-500-2
BDB-16-500-3
500 kcmil - 4
2/0 - 14
430
1
2
3
BDBCOVER1
BDB-162-500-1
BDB-162-500-2
BDB-162-500-3
500 kcmil - 4
2 - 14
430
1
2
3
BDBCOVER2
BDB-26-350-1
BDB-26-350-2
BDB-26-350-3
350 kcmil - 6
2/0 - 14
700
1
2
3
BDBCOVER1
BDB-212-500-1
BDB-212-500-2
BDB-212-500-3
500 kcmil - 4
4 - 14
860
1
2
3
BDBCOVER1
BDB-26-500-1
BDB-26-500-2
BDB-26-500-3
500 kcmil - 4
2/0 - 14
860
1
2
3
BDBCOVER1
BDB-24-500-1
BDB-24-500-2
BDB-24-500-3
500 kcmil - 4
4/0 - 6
860
1
2
3
BDBCOVER1
CATALOG
NUMBER
CONNECTOR
RUN
TAP
OPTIONAL
NUMBER OF COVER ORDER
POLES
1 PER POLE
BURNDY
Mechanical
VERSI-POLE
VERSI-POLE 1, 2, 3
SPLICE/REDUCER BLOCKS
A-51
RUN
WIRE RANGE
AL9CU
TAP
WIRE RANGE
AL9CU
AMPERE
RATING PER
POLE
BDB-11-2/0-1
BDB-11-2/0-2
BDB-11-2/0-3
2/0 - 14
2/0 - 14
195
1
2
3
BDBCOVER2
BDB-11-350-1
BDB-11-350-2
BDB-11-350-3
350 kcmil - 6
350 kcmil - 6
350
1
2
3
BDBCOVER2
BDB-11-500-1
BDB-11-500-2
BDB-11-500-3
500 kcmil - 6
500 kcmil - 6
430
1
2
3
BDBCOVER1
BDB-22-2/0-1
BDB-22-2/0-2
BDB-22-2/0-3
2/0 - 14
2/0 - 14
390
1
2
3
BDBCOVER2
BDB-22-350-1
BDB-22-350-2
BDB-22-350-3
350 kcmil - 6
350 kcmil - 6
700
1
2
3
BDBCOVER1
BDB-22-500-1
BDB-22-500-2
BDB-22-500-3
500 kcmil - 4
500 kcmil - 4
860
1
2
3
BDBCOVER1
RUN
WIRE RANGE
AL9CU
TAP
WIRE RANGE
AL9CU
AMPERE
RATING PER
POLE
BDC-14-2/0-1
2/0 - 14
4 - 14
195
BDBCOVER3
BDA-14-2/0-1
2/0 - 14
4 - 14
195
ADDER
BDBCOVER3
BDC-11-2/0-1
2/0 - 14
2/0 - 14
195
BDBCOVER3
BDA-11-2/0-1
2/0 - 14
2/0 - 14
195
ADDER
BDBCOVER3
CATALOG
NUMBER
CONNECTOR
RUN
TAP
OPTIONAL
NUMBER OF COVER ORDER
POLES
1 PER POLE
SNAP TOGETHER
SPLICER/REDUCER
BLOCKS
CATALOG
NUMBER
CONNECTOR
RUN
TAP
OPTIONAL
NUMBER OF COVER ORDER
POLES
1 PER POLE
BURNDY
Mechanical
VERSI-POLE
(Continued)
A-52
VERSI-POLE 1, 2, 3
SPLICE/REDUCER BLOCKS
These tables and illustrations refer to VERSIPOLE Power Distribution Blocks listed on
pages A-48 through A-50.
Number of Poles
Catalog Number
Number of Poles
BDA-11-500
1 (adder)
BDB-16-500-3
BDA-112-350
1 (adder)
BDB-212-500-1
BDA-16-350
1 (adder)
BDB-212-500-2
BDA-16-500
1 (adder)
BDB-212-500-3
BDA-212-500
1 (adder)
BDB-22-350-1
BDA-22-350
1 (adder)
BDB-22-350-2
BDA-22-500
1 (adder)
BDB-22-350-3
BDA-24-500
1 (adder)
BDB-22-500-1
BDA-26-350
1 (adder)
BDB-22-500-2
BDA-26-500
1 (adder)
BDB-22-500-3
BDB-11-500-1
BDB-24-500-1
BDB-11-500-2
BDB-24-500-2
BDB-11-500-3
BDB-24-500-3
BDB-112-350-1
BDB-26-350-1
BDB-112-350-2
BDB-26-350-2
BDB-112-350-3
BDB-26-350-3
BDB-16-350-1
BDB-26-500-1
BDB-16-350-2
BDB-26-500-2
BDB-16-350-3
BDB-26-500-3
BDB-16-500-1
BDB-430-500-1
BDB-16-500-2
NO. OF
POLES
DIMENSIONS A
INCHES
Adder
1
2
3
N
2.50
2.81
5.31
7.81
(2.50 X N) + .31
BURNDY
Mechanical
VERSI-POLE
(Continued)
A-53
VERSI-POLE 1, 2, 3
SPLICE/REDUCER BLOCKS
These tables and illustrations refer to VERSIPOLE Power Distribution Blocks listed on
pages A-48 through A-50.
THE FIGURE TO THE RIGHT IS
APPLICABLE TO THE FOLLOWING:
Catalog Number
Number of Poles
BDB-11-2/0-1
BDB-11-2/0-2
BDB-11-2/0-3
BDB-11-350-1
BDB-11-350-2
BDB-11-350-3
BDB-14-500-1
BDB-14-500-2
BDB-14-500-3
BDB-16-2/0-1
BDB-16-2/0-2
BDB-16-2/0-3
BDB-162-500-1
BDB-162-500-2
BDB-162-500-3
BDB-22-2/0-1
BDB-22-2/0-2
BDB-22-2/0-3
BDB-26-2/0-1
BDB-26-2/0-2
BDB-26-2/0-3
Number of Poles
BDA-14-2/0-1
1 (adder)
BDC-14-2/0-1
BDA-11-2/0-1
1 (adder)
BDC-11-2/0-1
NO. OF
POLES
DIMENSIONS A
INCHES
Adder
1
2
3
N
.81
1.08
1.89
2.70
(.81 X N) + .27
NO. OF
POLES
DIMENSIONS A
INCHES
Adder
1
2
3
N
1.64
1.94
3.57
5.20
(1.64 X N) + .30
BURNDY
Mechanical
BURNDY UNITAP
A-54
CLEAR INSULATED
MULTIPLE TAP CONNECTORS
Tap connections and in-line splice/reductions
are made quickly and easily with the
UNITAP line of connectors. UL486B Listed.
Dual-rated AL9CU for any stranded copper or
stranded aluminum applications. 600 Volt,
90 C.
# of
Ports
Wire Range
(AWG/kcmil)
Hex Key
Fig.
No.
BIT4
BITO4
BIT2/0
BITO2/0
BIT250
BITO250
BIT350
BITO350
BIT600
BITO600
BIT750*
BITO750*
2
2
2
2
2
2
2
2
2
2
2
2
#14 - #4
#14 - #4
#14 - 2/0
#14 - 2/0
#10 - 250
#10 - 250
#10 - 350
#10 - 350
#4 - 600
#4 - 600
#2 - 750
#2 - 750
1.16
1.16
1.52
1.52
2.03
2.03
2.22
2.22
2.72
2.72
2.87
2.87
1.16
1.50
1.40
1.56
2.07
2.64
2.32
3.00
2.38
3.00
2.70
3.38
1.25
1.25
1.38
1.38
2.13
2.13
2.50
2.50
2.75
2.75
3.00
3.00
1/8
1/8
3/16
3/16
5/16
5/16
5/16
5/16
3/8
3/8
3/8
3/8
1
2
1
2
1
2
1
2
1
2
1
2
Fig. 1
* Not UL Listed
Fig. 2
IN-LINE SPLICER/REDUCER
Catalog
Number
Wire Range
(AWG/kcmil)
Hex Key
BISR2
BISR1/0
BISR250
BISR350
BISR500
#14 - 2
#14 - 1/0
#6 - 250
#6 - 350
#2 - 500
2.38
2.91
4.01
4.63
5.00
0.75
0.91
1.19
1.34
1.62
1.22
1.38
2.10
2.35
2.62
5/32
3/16
5/16
5/16
3/8
BURNDY
Mechanical
BURNDY UNITAP
A-55
MULTI-PORT
Single-Sided Entry
Catalog
Number
BIBS4-3
BIBS4-4
BIBS4-5
BIBS4-6
BIBS4-8
BIBS2/0-3
BIBS2/0-4
BIBS2/0-5
BIBS2/0-6
BIBS2/0-8
BIBS2/0-10
BIBS2/0-12
BIBS2/0-14
BIBS250-3
BIBS250-4
BIBS250-5
BIBS250-6
BIBS250-8
BIBS250-10
BIBS250-12
BIBS250-14
BIBS350-3
# of Wire Range
Ports (AWG/kcmil)
3
4
5
6
8
3
4
5
6
8
10
12
14
3
4
5
6
8
10
12
14
3
#14 - 4
#14 - 4
#14 - 4
#14 - 4
#14 - 4
#14 - 2/0
#14 - 2/0
#14 - 2/0
#14 - 2/0
#14 - 2/0
#14 - 2/0
#14 - 2/0
#14 - 2/0
#10 - 250
#10 - 250
#10 - 250
#10 - 250
#10 - 250
#10 - 250
#10 - 250
#10 - 250
#10 - 350
Hex
Key
Catalog
Number
1.59
2.03
2.47
2.91
3.78
2.19
2.86
3.53
4.20
5.55
6.89
8.24
9.58
2.97
3.91
4.84
5.78
7.66
9.53
11.41
13.29
3.13
1.25
1.25
1.25
1.25
1.25
1.31
1.31
1.31
1.31
1.31
1.31
1.31
1.31
2.07
2.07
2.07
2..07
2.07
2.07
2.07
2.07
2.32
1.25
1.25
1.25
1.25
1.25
1.38
1.38
1.38
1.38
1.38
1.38
1.38
1.38
2.13
2.13
2.13
2.13
2.13
2.13
2.13
2.13
2.50
1/8
1/8
1/8
1/8
1/8
3/16
3/16
3/16
3/16
3/16
3/16
3/16
3/16
5/16
5/16
5/16
5/16
5/16
5/16
5/16
5/16
5/16
BIBS350-4
BIBS350-5
BIBS350-6
BIBS350-8
BIBS350-10
BIBS350-12
BIBS350-14
BIBS600-3
BIBS600-4
BIBS600-5
BIBS600-6
BIBS600-8
BIBS600-10
BIBS600-12
BIBS600-14
BIBS750-3*
BIBS750-4*
BIBS750-6*
BIBS750-8*
BIBS750-10*
BIBS750-12*
BIBS750-14*
* Not UL Listed
# of Wire Range
Ports (AWG/kcmil)
4
5
6
8
10
12
14
3
4
5
6
8
10
12
14
3
4
6
8
10
12
14
#10 - 350
#10 - 350
#10 - 350
#10 - 350
#10 - 350
#10 - 350
#10 - 350
#4 - 600
#4 - 600
#4 - 600
#4 - 600
#4 - 600
#4 - 600
#4 - 600
#4 - 600
#2 - 750
#2 - 750
#2 - 750
#2 - 750
#2 - 750
#2 - 750
#2 - 750
Hex
Key
4.04
4.95
5.86
7.68
9.50
11.32
13.14
4.00
5.28
6.56
7.84
10.41
12.97
15.53
18.09
4.25
5.63
8.37
11.13
13.87
16.63
19.37
2.32
2.32
2.32
2.32
2.32
2.32
2.32
2.38
2.38
2.38
2.38
2.38
2.38
2.38
2.38
2.70
2.70
2.70
2.70
2.70
2.70
2.70
2.50
2.50
2.50
2.50
2.50
2.50
2.50
2.75
2.75
2.75
2.75
2.75
2.75
2.75
2.75
3.00
3.00
3.00
3.00
3.00
3.00
3.00
5/16
5/16
5/16
5/16
5/16
5/16
5/16
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
BURNDY
Mechanical
BURNDY UNITAP
A-56
MULTI-PORT
Double-Sided Entry
Catalog
Number
BIBD4-2
BIBD4-3
BIBD4-4
BIBD4-5
BIBD4-6
BIBD4-8
BIBD2/0-2
BIBD2/0-3
BIBD2/0-4
BIBD2/0-5
BIBD2/0-6
BIBD2/0-8
BIBD2/0-10
BIBD2/0-12
BIBD2/0-14
BIBD250-2
BIBD250-3
BIBD250-4
BIBD250-5
BIBD250-6
BIBD250-8
BIBD250-10
BIBD250-12
BIBD250-14
BIBD350-2
# of Wire Range
Ports (AWG/kcmil)
2
3
4
5
6
8
2
3
4
5
6
8
10
12
14
2
3
4
5
6
8
10
12
14
2
#14 - #4
#14 - #4
#14 - #4
#14 - #4
#14 - #4
#14 - #4
#14 - 2/0
#14 - 2/0
#14 - 2/0
#14 - 2/0
#14 - 2/0
#14 - 2/0
#14 - 2/0
#14 - 2/0
#14 - 2/0
#10 - 250
#10 - 250
#10 - 250
#10 - 250
#10 - 250
#10 - 250
#10 - 250
#10 - 250
#10 - 250
#10 - 350
Hex
Key
Catalog
Number
1.16
1.59
2.03
2.47
2.91
3.78
1.52
2.19
2.86
3.53
4.20
5.55
6.89
8.24
9.58
2.03
2.97
3.91
4.84
5.78
7.66
9.53
11.41
13.29
2.22
1.50
1.50
1.50
1.50
1.50
1.50
1.56
1.56
1.56
1.56
1.56
1.56
1.56
1.56
1.56
2.64
2.64
2.64
2.64
2.64
2.64
2.64
2.64
2.64
3.00
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
2.13
2.13
2.13
2.13
2.13
2.13
2.13
2.13
2.13
2.50
1/8
1/8
1/8
1/8
1/8
1/8
3/16
3/16
3/16
3/16
3/16
3/16
3/16
3/16
3/16
5/16
5/16
5/16
5/16
5/16
5/16
5/16
5/16
5/16
5/16
BIBD350-3
BIBD350-4
BIBD350-5
BIBD350-6
BIBD350-8
BIBD350-10
BIBD350-12
BIBD350-14
BIBD600-2
BIBD600-3
BIBD600-4
BIBD600-5
BIBD600-6
BIBD600-8
BIBD600-10
BIBD600-12
BIBD600-14
BIBD750-2*
BIBD750-3*
BIBD750-4*
BIBD750-6*
BIBD750-8*
BIBD750-10*
BIBD750-12*
BIBD750-14*
# of Wire Range
Ports (AWG/kcmil)
3
4
5
6
8
10
12
14
2
3
4
5
6
8
10
12
14
2
3
4
6
8
10
12
14
#10 - 350
#10 - 350
#10 - 350
#10 - 350
#10 - 350
#10 - 350
#10 - 350
#10 - 350
#4 - 600
#4 - 600
#4 - 600
#4 - 600
#4 - 600
#4 - 600
#4 - 600
#4 - 600
#4 - 600
#2 - 750
#2 - 750
#2 - 750
#2 - 750
#2 - 750
#2 - 750
#2 - 750
#2 - 750
Hex
Key
3.13
4.04
4.95
5.86
7.68
9.50
11.32
13.14
2.56
3.77
4.97
6.17
7.37
9.78
12.97
15.53
18.09
2.87
4.25
5.63
8.37
11.13
13.87
16.63
19.37
3.00
3.00
3.00
3.00
3.00
3.00
3.00
3.00
3.00
3.00
3.00
3.00
3.00
3.00
3.00
3.00
3.00
3.38
3.38
3.38
3.38
3.38
3.38
3.38
3.38
2.50
2.50
2.50
2.50
2.50
2.50
2.50
2.50
2.75
2.75
2.75
2.75
2.75
2.75
2.75
2.75
2.75
3.00
3.00
3.00
3.00
3.00
3.00
3.00
3.00
5/16
5/16
5/16
5/16
5/16
5/16
5/16
5/16
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
BURNDY
Mechanical
BURNDY UNITAP
CLEAR INSULATED
MULTIPLE TAP CONNECTORS
A-57
MOUNTING VERSION
TYPE BIBS-MT, BIBD-MT
The BIBS-MT and BIBD-MT series UNITAP
offer the same multi-port capabilities as the
standard UNITAP connectors except these
-MT types are provided with two isolated
mounting holes at both ends of the connector
for direct mounting to a trough, gutter or
wireway. They will accommodate up to
standard 1/4 hardware.
Fig. 2
Fig. 1
MULTI-PORT
Single-Sided Entry
Catalog
Number
BIBS2/04MT
BIBS2/06MT
BIBS2/08MT
BIBS2/010MT
BIBS2/012MT
BIBS2504MT
BIBS2506MT
BIBS2508MT
BIBS25010MT
BIBS25012MT
BIBS3504MT
BIBS3506MT
BIBS3508MT
BIBS35010MT
BIBS35012MT
BIBS6004MT
BIBS6006MT
BIBS6008MT
BIBS60010MT
BIBS60012MT
# of
Fig # Ports
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
4
6
8
10
12
4
6
8
10
12
4
6
8
10
12
4
6
8
10
12
MULTI-PORT
Double-Sided Entry
Wire Range
(AWG/Kcmil)
Hex
Key
Catalog
Number
#14-2/0
#14-2/0
#14-2/0
#14-2/0
#14-2/0
#10-250
#10-250
#10-250
#10-250
#10-250
#10-350
#10-350
#10-350
#10-350
#10-350
#4-600
#4-600
#4-600
#4-600
#4-600
3.95
5.29
6.64
7.98
9.33
5.53
7.40
9.28
11.16
13.03
5.61
7.43
9.25
11.07
12.89
7.59
10.16
12.72
15.28
17.84
1.31
1.31
1.31
1.31
1.31
2.07
2.07
2.07
2.07
2.07
2.32
2.32
2.32
2.32
2.32
2.38
2.38
2.38
2.38
2.38
1.38
1.38
1.38
1.38
1.38
2.13
2.13
2.13
2.13
2.13
2.50
2.50
2.50
2.50
2.50
2.75
2.75
2.75
2.75
2.75
3/16
3/16
3/16
3/16
3/16
5/16
5/16
5/16
5/16
5/16
5/16
5/16
5/16
5/16
5/16
3/8
3/8
3/8
3/8
3/8
BIBD2/04MT
BIBD2/06MT
BIBD2/08MT
BIBD2/010MT
BIBD2/012MT
BIBD2504MT
BIBD2506MT
BIBD2508MT
BIBD25010MT
BIBD25012MT
BIBD3504MT
BIBD3506MT
BIBD3508MT
BIBD35010MT
BIBD35012MT
BIBD6004MT
BIBD6006MT
BIBD6008MT
BIBD60010MT
BIBD60012MT
# of
Fig # Ports
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
4
6
8
10
12
4
6
8
10
12
4
6
8
10
12
4
6
8
10
12
Wire Range
(AWG/Kcmil)
Hex
Key
#14-2/0
#14-2/0
#14-2/0
#14-2/0
#14-2/0
#10-250
#10-250
#10-250
#10-250
#10-250
#10-350
#10-350
#10-350
#10-350
#10-350
#4-600
#4-600
#4-600
#4-600
#4-600
3.95
5.29
6.64
7.98
9.33
5.53
7.40
9.28
11.16
13.03
5.61
7.43
9.25
11.07
12.89
7.59
10.16
12.72
15.28
17.84
1.56
1.56
1.56
1.56
1.56
2.64
2.64
2.64
2.64
2.64
3.00
3.00
3.00
3.00
3.00
3.00
3.00
3.00
3.00
3.00
1.38
1.38
1.38
1.38
1.38
2.13
2.13
2.13
2.13
2.13
2.50
2.50
2.50
2.50
2.50
2.75
2.75
2.75
2.75
2.75
3/16
3/16
3/16
3/16
3/16
5/16
5/16
5/16
5/16
5/16
5/16
5/16
5/16
5/16
5/16
3/8
3/8
3/8
3/8
3/8
BURNDY
Mechanical
TYPE UGS350ULDB
IN-LINE SPLICE/REDUCER
A-58
CATALOG
NUMBER
UGS350ULDB
WIRE RANGE
10 AWG - 350 kcmil
LENGTH
In. [mm]
HEIGHT
In. [mm]
8.50
[216]
2.81
[71.4]
HEX SIZE
TORQUE
(In. Lbs.)
5/16
350