Professional Documents
Culture Documents
Com binations
for Ste el S truct ure s
B C S A P u b l i c a t i o n N o . 5 3/ 10
B C S A P u b l i c a t i on N o . 5 3 / 1 0
T h e B r it is h Co n s t r u ct i o n a l
Ste e l wo rk Asso c i ati o n L i mi te d
Apart from any fair dealing for the purpose of research or private
study or criticism or review, as permitted under the Copyright
Design and Patents Act 1988, this publication may not be
reproduced, stored or transmitted in any form by any means
without the prior permission of the publishers or in the case of
reprographic reproduction only in accordance with the terms of the
licences issued by the UK Copyright Licensing Agency, or in
accordance with the terms of licences issued by the appropriate
Reproduction Rights Organisation outside the UK.
Enquiries concerning reproduction outside the terms stated here
should be sent to the publishers, The British Constructional
Steelwork Association Ltd. at the address given below.
Although care has been taken to ensure, to the best of our
knowledge, that all data and information contained herein are
accurate to the extent that they relate to either matters of fact or
accepted practice or matters of opinion at the time of publication,
The British Constructional Steelwork Association Limited, the
authors and the reviewers assume no responsibility for any errors
in or misinterpretations of such data and/or information of any loss
or damages arising or related to their use.
Publications supplied to members of the BCSA at a discount are
not for resale by them.
The British Constructional Steelwork Association Ltd.
4, Whitehall Court, Westminster, London SW1A 2ES
Telephone: +44(0)20 7839 8566 Fax: +44(0)20 7976 1634
Email: postroom@steelconstruction.org
Website: www.steelconstruction.org
Publication Number
First Edition
53/10
December 2010
ISBN-10 1-85073-063-6
ISBN-13 978-1-85073-063-7
British Library Cataloguing-in-Publication Data
A catalogue record for this book is available from the British Library
The British Constructional Steelwork Association Ltd
F or e wo r d
One of the most challenging aspects of the Eurocodes is gaining a
thorough understanding of the loading and load combination for
practical buildings. This challenge is not technical but primarily one
related to the way the information is presented and the terminology
used in the Eurocodes. The presentation and terminology used in
the Eurocodes are very different to that found in British Standards
such as BS 5950. The Eurocodes have a preference for
mathematical formulae over tables and graphs and some of the
explanations are brief.
The principal aim of this publication is to provide the reader with
straightforward guidance on the loading and load combinations for
both the serviceability and ultimate limit states for the following
building types:
C on t e n t s
1. INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.1 Background . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.2 Introduction to EN 1990 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.3 Introduction to EN 1991 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2. ABBREVIATIONS, DEFINITIONS AND SYMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.1 Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.2 Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.3 Symbols (Greek letters) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3. COMBINATIONS OF ACTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.1 Ultimate limit states . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.2 Serviceability limit states . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
4. MULTI-STOREY BUILDINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.1.1 Classification of frames . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.1.2 Frame imperfections and equivalent horizontal forces (EHF) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.1.3 Second order (P-) effects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.1.4 Reduction factors for number of storeys (n) and floor area (A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.1.5 Pattern loading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.1.6 Dead loads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.1.7 Overturning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.2 Braced frames (simple construction) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.2.1 ULS load combinations based on Equation 6.10 with cr > 10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.2.2 ULS load combinations based on Equation 6.10 with cr < 10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.2.3 ULS load combinations based on Equations 6.10a and 6.10b with cr > 10 . . . . . . . . . . . . . . . . . . . . . . . . 14
4.2.4 ULS load combinations based on Equations 6.10a and 6.10b with cr < 10 . . . . . . . . . . . . . . . . . . . . . . . . 15
4.2.5 SLS load combinations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4.3 Moment resisting frames (continuous construction) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4.4 Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
5. INDUSTRIAL BUILDINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
5.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
5.1.1 EN 1991-1-3: 2003 - Snow loading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
5.1.2 EN 1991-1-4: 2003 - Wind loading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
5.1.3 Frame imperfections and second order P- effects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
5.2 Portal frames . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
5.2.1 Serviceability limit state design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
5.2.2 SLS design example for a single span portal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
5.2.3 Ultimate limit state design (STR) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
5.2.4 ULS design example for a single span portal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
5.3 Portal frames with cranes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
5.3.1 Serviceability limit state design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
5.3.2 SLS design example for a single span portal with overhead crane . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
5.3.3 Ultimate limit state design (STR) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
5.3.4 ULS design example for a single span portal with overhead crane . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
6. REFERENCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
1 . I n t ro d u ct i o n
1.1 Background
1991-1
1991-2
1991-3
1991-4
Action type
General actions
Traffic loads on bridges
Actions induced by cranes and machinery
Silos and tanks
1991-1-1
1991-1-2
1991-1-3
1991-1-4
1991-1-5
1991-1-6
1991-1-7
Action type
2 . A b b re v i at i o n s , de f i n i t io n s a n d s ym b o l s
The terminology adopted in the Eurocodes will be unfamiliar to the
majority of designers and may prove an obstacle to the rapid
uptake of the Eurocodes. Most of the definitions given in the
Eurocodes derive from:
Characteristic:
The typical value of a parameter to be used in design.
Combinations of actions:
The combination of different sources of load acting
simultaneously for the verification of structural reliability for a
given limit state.
2.1 Abbreviations
B
EHF
EN
EQU
FAT
GEO
I
N
NA
NCCI
P
STR
2.2 Definitions
Action:
A load, or imposed deformation to which a structure is subjected
(e.g. temperature effects or settlement).
Application rules:
Clauses marked P in the Eurocodes are principles, which must
be followed. Clauses not marked P are application rules which,
when followed, satisfy the principles. Alternative design rules
may be adopted. Application rules make up the bulk of the
codes and give the values and formulae to be used in the design.
Capacity:
The ability to conform to a limit state, e.g. bearing capacity.
Co-existence:
Eurocodes being in force in parallel with national codes.
Conformity:
Compliance with standards.
Design resistance:
The capacity of the structure or element to resist the design load.
Effects of actions:
Internal moments and forces, bending moments, shear forces
and deformations caused by actions.
Execution:
All activities carried out for the physical completion of the work
including procurement, the inspection and documentation thereof.
The term covers work on site; it may also signify the fabrication
of components off site and their subsequent erection on site.
Fatigue:
A mode of failure in which a member ruptures after many
applications of load.
Fundamental combinations:
Combinations of actions for the persistent or transient design
situations.
Frequent:
Likely to occur often, but for a short duration on each occasion.
Informative:
For information, not a mandatory requirement see normative.
Load arrangement:
Identification of the position, magnitude and direction of the loads
(loading pattern).
Load case:
Compatible loading arrangements considered simultaneously
Load combination:
See Combinations of actions.
National Annex:
The document containing nationally determined parameters
(NDPs). This is an essential supplement without which the
Eurocode cannot be used.
NDPs:
Values left open in a Eurocode for definition in the country
concerned.
Non-Contradictory Complementary Information:
Permitted additional information and guidance.
Normative:
Mandatory, having the force of a Standard.
Persistent:
Likely to be present for most of the design life.
Principles:
Clauses marked P define structural performance that must be
achieved.
Quasi-:
Being partly or almost.
Quasi-permanent action:
An action that applies for a large fraction of the design life.
Quasi-static:
The static equivalent of a dynamic action.
Reference period:
Any chosen period, but generally the design life.
Reliability:
The mathematical probability of a structure fulfilling the design
requirements.
Transient:
Likely to be present for a period much shorter than the design life
but with a high probability of occurring.
Verify:
Check the design output to make sure it complies.
The following Greek letters are used in EN 1990 and this document:
(alpha)
A
n
cr
(gamma)
G
Q
(psi)
0
1
2
(xi)
(sigma)
3 . C om bi n at i o n s o f a ct i o n s
Combinations of actions, generally referred to as load
combinations, are set out for all structures in Clause 6.4.3.2 of EN
1990. They are presented not simply as a series of multiplication
factors to be applied to the various loading components, but
instead in an unfamiliar algebraic format, which requires
explanation. In Sections 4 and 5 of this guide, the provisions of the
code are explained and presented in a format that is more familiar
to UK engineers.
j1
i>1
j1
i>1
G,jGk,j + PP + Q,1Qk,1 + Q,i0,iQk,i
j1
i>1
where
G
P
Q
P
(6.10)
(6.10a)
(6.10b)
10
Tables 3.1 to 3.3 set out values for the partial factors (G and Q)
for permanent and variable actions. These tables are based on
Tables NA.A1.2(A) and (B) of the UK National Annex to EN 1990.
Note that Table NA.A1.2(A) of the UK National Annex to EN 1990
applies to verification of static equilibrium (EQU) of building
structures, Table NA.A1.2(B) applies to the verification of structural
members (STR) in buildings, and Table NA.A1.2(C) relates to any
verifications involving geotechnical actions, such as piles and
footings (which are not considered in this guide).
In clause 6.4.3.1(4) of EN 1990 a distinction is made between
favourable and unfavourable actions. For permanent actions, the
upper characteristic (superior) value Gkj,sup should be used when
that action is unfavourable, and the lower characteristic (inferior)
value Gkj,inf should be used when that action is favourable. This
clause allows the designer to consider a permanent action as
either favourable or unfavourable, in separate load combinations.
As stated in EN 1990, this approach is only necessary where the
results of verification are sensitive to variations in the magnitude of
a permanent action from place to place in a structure. This idea is
considered in more detail in Reference [7] with a continuous beam
example. All variable actions should generally be present within a
load combination unless they have a favourable influence, in which
case they are assigned a partial factor Q of zero, effectively
excluding them.
Table 3.1: Design values of actions for equilibrium (EQU)
1.10 Gkj,sup
0.9 Gkj,inf
1.35 Gkj,sup
1.0 Gkj,inf
1.5 Qk,1
1.50,i Qk,i
1.35 Gkj,sup
1.0 Gkj,inf
1.50,i Qk,i
Action
0
0.7
1
0.5
2
0.3
0.7
0.5
0.3
0.7
0.7
0.6
0.7
1.0
0.7
0.9
0.7
0.7
0.5
0.2
0.5
0.2
0.6
0.5
0.5
0.2
i>1
j1
(6.14b)
j1
i>1
(6.15b)
Gk, j + P + 2,iQk,i
j1
i>1
(6.16b)
0.6
0.3
0.7
0.8
0.5
0.6
0.7
Category H: roofs
11
4 . M u l t i - s t or e y b u i l di n g s
In this section, Eurocode load combinations for multi-storey
buildings are set out. General guidance for both simple and
moment resisting frames is given in Section 4.1, since, in principle,
load combinations are the same for both types of structure.
However, differences in treatment often arise due to differences in
sway stiffness, member interaction etc. and hence, specific
guidance and examples for simple and moment resisting frames is
provided in Sections 4.2 and 4.3, respectively.
4.1 General
4.1.1
Classification of frames
Structural frames may be classified with regards to their lateral
load resisting system and sway stiffness. Concerning the lateral
load resisting system, a frame may be regarded as either braced
or unbraced. As a guide, for a frame to be classified as braced,
it should contain a bracing system with lateral stiffness of at least
five times that of the unbraced frame [8], which will be the case in
braced simple construction. Bracing systems using wire ties (as
opposed to open or hollow sections) may result in the frame being
classified as unbraced.
Sway stiffness is commonly achieved through the provision of a
suitable bracing system or by utilising the inherent bending
resistance of a rigid frame. Adequate sway stiffness is important
because it limits the lateral deflections of the frame and hence
controls second order (P-) effects. Sway stiffness is assessed in
EN 1993-1-1 in a similar way as it is in BS 5950, through the cr
parameter (equivalent to cr in BS 5950), which represents the
factor by which the vertical design loading would have to be
increased to cause overall elastic buckling of the frame (Clause
5.2.1(3) of EN 1993-1-1). A simplified means of determining cr for
regular frames is also given in Equation 5.2 of EN 1993-1-1.
Regardless of the frame type, if cr is greater than 10, the sway
stiffness is deemed sufficiently large for second order effects to be
ignored. Conversely, if cr is less than 10, second order effects
may no longer be ignored. Second order effects are discussed
further in Section 4.1.3.
4.1.2
12
10 > cr > 3
cr < 3
Result
Second order
effects ignored
4.1.4
1
1-1/cr
(D4.1)
beams and roofs, the area reduction factor A may be applied. For
the design of columns and walls, the reduction factor n for the
number of storeys may be applied. The reduction factor n relates
to the number of floors supported by the column section under
consideration, and may be applied to the total imposed load being
carried. If, for a given column or wall, A < n, then A may be
used in place of n, but A and n may not be used together
(Clause NA.2.6).
Reduction factors A for imposed loads on floors and accessible
roofs are provided in Clause NA.2.5 of the UK National Annex to
EN 1991-1-1 (see Equation D4.2), and replace those given in
Clause 6.3.1.2(10) of EN 1991-1-1.
A = 1.0 A/1000 0.75
(D4.2)
GGk
GGk + QQk
(D4.3)
n = 0.5
for 5 < n 10
(D4.4)
for n > 10
(D4.5)
n = 0.6
4.1.5
Pattern loading
For the design of floors within one storey and for the design of
roofs, EN 1991-1-1 Clause 6.2.1(1) states that pattern loading
should be considered for continuous construction, though the
storeys other than the one under consideration may be assumed
to be uniformly loaded (Clause 6.2.1 of EN 1991-1-1). Pattern
loading need not be considered for simple construction. The two
loading patterns indentified in Clause AB.2 of EN 1993-1-1 for
continuous floor beams to assess (a) the span moments and (b)
support moments for the storey under consideration are shown in
Figures 4.1(a) and (b), respectively. In Figure 4.1(a), alternative
spans carry the design permanent and variable load (GGk + QQk)
while other spans carry only the design permanent load ( GGk). In
Figure 4.1(b), two adjacent spans carry the design permanent and
variable load (GGk + QQk) while all other spans carry only the
design permanent load ( GGk).
GGk
GGk + QQk
4.1.7
Overturning
Overturning of a structure as a rigid body is independent of its
lateral load resisting system and sway stiffness. It is solely a
matter of equilibrium (EQU), for which only Equation 6.10 of EN
1990 should be applied. The critical load combination for general
multi-storey buildings emerges on the basis of maximising the
overturning moment due to the horizontal loading (wind and EHF)
and minimising the restoring moment due to the vertical loading. It
is generally appropriate to consider only a single value for dead
loading, but the concept of upper (superior) Gk,sup and lower
(inferior) Gk,inf characteristic values should be considered where
sensitivity to variability in dead loads is very high (Clause A1.3.1 of
EN 1990). For the overturning load case, a factor of 0.9 is applied
to the dead load (where it is contributing to the restoring moment)
and factor of 1.5 is applied to the wind load, as the leading variable
action. The wind load has been denoted Wk in this document.
Equivalent horizontal forces are included, as in all ULS
combinations, but these are not factored (again) since they are
already based on factored loading. Thus, the overturning load
combination is given by Equation D4.6.
13
(D4.6)
(D4.7)
(D4.8)
14
(D4.9)
(D4.10)
The wind load itself may also be favourable, for example where
uplift results in reduced columns loads. Assuming wind load to be
favourable leads to the load combination given by Equation D4.10.
4.2.2
(D4.11)
(D4.12)
(D4.13)
(D4.14)
(D4.15)
1.00Wk + 0.70Qk
(D4.16)
(D4.17)
(D4.18)
1.00Wk
(D4.19)
Vertical deflection
Limit
Span/360
Cantilevers
Length/180
Span/200
Limit
Height of
that storey/300
4.4 Example
15
3.6 m
kN/m2
Gkf = 3.5
Qkf = 5 kN/m2
3.6 m
6m
3.6 m
6m
6m
EHF = 10.0 kN
Wind = 21.9 kN
EHF = 19.2 kN
Wind = 43.7 kN
Wk = 0.2 kN/m2
Wk = 0.7 kN/m2
3.6 m
Figures 4.3 to 4.7 present the total factored design loading on the
structure arising from the five load combinations defined by
Equations D4.11 to D4.15, respectively.
EHF = 19.2 kN
Wind = 43.7 kN
EHF = 19.2 kN
Wind = 43.7 kN
Bracing FEd
External
column FEd
Internal
column FEd
FEd = 752.0 kN
External column
Bracing
Bracing FEd
External
column FEd
Internal
column FEd
16
FEd = 1504.0 kN
FEd = 1807.1 kN
EHF = 8.1 kN
Wind = 43.7 kN
EHF = 15.6 kN
Wind = 87.5 kN
EHF = 15.6 kN
Wind = 87.5 kN
EHF = 15.6 kN
Wind = 87.5 kN
Bracing FEd
External
column FEd
Internal
column FEd
Bracing FEd
External
column FEd
Internal
column FEd
EHF = 19.2 kN
Wind = 0.0 kN
EHF = 19.2 kN
Wind = 0.0 kN
Wind = 14.6 kN
Wind = 29.2 kN
FEd = 470.0 kN
FEd = 920.2 kN
Wind = 29.2 kN
Wind = 29.2 kN
FEd = 235.0 kN
External column
From Figures 4.3 to 4.7, it may be seen that the maximum loadings
in different members often arise from different load combinations.
For the case considered (Figure 4.2), the maximum design UDL on
the roof and floors arise from Equation D4.15 (1.25Gk + 1.5Qk +
EHF), as does the maximum external column load and the
maximum internal column load (for the unbraced frames in the
structure). The maximum force in the bracing members results
from Equation D4.13 (1.25Gk+ 1.05Qk + 1.5Wk + EHF), while
the maximum internal column load (for the braced frames in the
structure) arises from Equation D4.12 (1.25Gk + 1.5Qk +
0.75Wk + EHF).
Bracing FEd
External
column FEd
Internal
column FEd
17
Wind = 58.3 kN
Wind = 58.3 kN
HEd = 29.2 kN
HEd = 58.3 kN
Wind = 0.0 kN
Wind = 0.0 kN
HEd = 29.2 kN
HEd = 58.3 kN
EHF = 1.2 kN
Wind = 14.6 kN
EHF = 1.7 kN
Wind = 29.2 kN
1.00Qk
1.00Wk
1.00Qk + 0.7Qk
Wind = 0.0 kN
Wind = 29.2 kN
Wind = 58.3 kN
Wind = 0.0 kN
EHF = 1.7 kN
Wind = 29.2 kN
EHF = 1.7 kN
Wind = 29.2 kN
Equilibrium assessment:
0.9Gk + 1.5Wk + EHF
18
M = 893.7 kNm
M = 11330 kNm
5 . In d u s t r i al bu i l d i n gs
5.1 General
Crane loads
0.7
0.0
0.0
0.5
0.2
0.0
1.0
0.9
Gkc/(Gkc+Qkc)
0.5
0.2
0.0
19
The resulting diagrams show that, for the range of roof pitches
considered, the primary condition for wind loading on the roof is
suction. If dominant openings are regarded as closed in a storm
(elective dominant openings) the maximum uplift for ULS design is
always for longitudinal wind (wind blowing directly onto the gable
causing suction on all external faces of the portal) with internal
pressure as is common with current practice.
-0.6
-0.6
-0.8
-0.8
-0.8
-0.8
Longitudinal Wind 1
-1.2
-0.6
0.3
Longitudinal Wind 1
-0.4
-1.02
-0.3
0.7
0.3
0.595
-0.255
-0.4
-0.255
0.0
0.595
-0.34
-0.255
Transverse Wind 2
Transverse Wind 2
Key
Overall coefficients shown thus:
Pressure shown as positive values
Suction shown as negative values
20
-0.34
Transverse Wind 1
-0.3
0.7
-0.255
-0.51
Transverse Wind 1
0.0
-0.6
-0.6
The same process can be applied to a portal with 6 roof pitch to give:
-0.6
-0.6
-0.8
-1.0
-0.8
-0.8
Internal
pressure 0.2
-1.0
-0.6
-0.6
-0.8
-0.8
-0.8
-1.0
Longitudinal Wind 1
0.595
0.255
-0.51
-1.02
-0.71
-1.22
0.395
-0.455
Internal
pressure 0.2
-0.54
-0.255
0.7 x 0.85
0.595
-0.21
-0.72
0.895
Internal
suction -0.3
0.045
-0.693
-1.186
0.595
0.395
0.2
-0.055
Internal
pressure 0.2
0.395
-0.34
-0.04
0.595
0.895
0.3
Internal
suction -0.3
0.045
-0.455
-0.3 x 0.85
-0.3
0.595
-0.193
-0.686
0.895
-0.006
Internal
suction -0.3
-0.389
-0.089
0.045
-0.255
Transverse Wind 1a
0.02 x 0.85
-0.34
-0.14
-0.5
-0.255
-0.41 x 0.85
-0.589
-0.306
-0.493
-0.986
-0.3
0.595
0.395
-0.183
Transverse Wind 2
0.0
-0.8
Transverse Wind 1
0.0
-0.255
-0.506
Internal
pressure 0.2
Transverse Wind 1a
0.0
-0.36 x 0.85
-0.58 x 0.85
-1.16 x 0.85
-0.34
-0.455
0.255
-0.51
-1.0
Longitudinal Wind 1
Transverse Wind 1
-1.02
-0.8
Internal
pressure 0.2
-0.36 x 0.85
-0.506
Internal
pressure 0.2
-0.41 x 0.85
-0.489
-0.455
-0.255
Transverse Wind 2
0.017
-0.34
-0.04
0.0
-0.3
0.595
0.895
0.317
-0.306
-0.006
Internal
suction -0.3
-0.389
-0.089
0.045
-0.255
Transverse Wind 2a
Transverse Wind 2a
Note: Longitudinal wind 1 gives the maximum overall suction on the roof.
Transverse wind 2 gives maximum local suction. Transverse wind 2a
causes maximum sidesway.
Note: Longitudinal wind 1 gives the maximum overall suction on the roof.
Transverse wind 2 gives maximum local suction. Transverse wind 2a
causes maximum sidesway.
Key
Overall coefficients shown thus: -0.3
Pressure shown as positive values
Suction shown as negative values
21
-0.65
-0.65
-0.8
-0.85
-1.0
-0.85
Internal
pressure 0.2
-1.0
-0.8
Longitudinal Wind 1
0.7 x 0.85
-0.6 x 0.85
-0.5 x 0.85
-1.00 x 0.85
-0.625
-1.05
-0.71
Internal
pressure 0.2
0.395
-0.45 x 0.85
-0.583
-0.455
-0.3 x 0.85
Transverse Wind 1
0.595
-0.51
-0.425
-0.85
-0.125
-0.55
0.895
Internal
suction -0.3
-0.21
-0.383
-0.083
0.045
-0.255
Transverse Wind 1a
-0.51
0.1 x 0.85
0.595
0.395
-0.115
Internal
pressure 0.2
-0.71
-0.455
-0.255
-0.51
0.595
0.895
0.385
Internal
suction -0.3
-0.21
Wk
Ad
6.14b
Transverse Wind 2
0.085
Gksup
Gkinf
Qk
-0.383
-0.583
-0.383
-0.083
0.045
-0.255
Transverse Wind 2a
=
=
=
=
=
Key
Overall coefficients shown thus: -0.15
Pressure shown as positive values
Suction shown as negative values
Figure 5.1e: Wind Pressure Coefficients Portal frame with
10 roof pitch
Note: Longitudinal wind 1 gives the maximum overall suction on the roof.
Transverse wind 2 gives maximum local suction. Transverse wind 2a
causes maximum sidesway.
22
0.150 kN/m2
0.032 kN/m2
0.099 kN/m2
0.281 kN/m2
1.0055
0.283 kN/m2
Gkinf = Dead
= 0.283 kN/m2
Qk
Wk
Ad
= Imposed load
= 0.600 kN/m2
= Wind load:
Wind pressure = 0.500 kN/m2;
Wind suction = -0.800 kN/m2
Load (kN/m2)
Equation 6.14b
Qk =
0.600
0.600
0.420
0.000
Wk (pressure)
= +0.500
Wk (suction)
= -0.800
0.250
0.500
-0.800
Ad =
0.550
Design load
(kN/m2)
0.000
0.000
0.000
0.850
0.920
-0.800
The normal roof pitch for portal frame structures in the UK is in the
range 5-15. In this range it is unlikely that the roof will be
subjected to wind pressure throughout the span. Hence, all three
combinations to Equation 6.14b must be considered.
Now consider the same example, but removing the load condition
of pressure on the roof the load combinations of Table 5.2a
emerge.
Table 5.2a: Load combinations for the serviceability limit
state (no uniform roof pressure)
Load (kN/m2)
Equation 6.14b
Qk =
0.600
0.600
0.000
Wk (suction)
= -0.800
0.000
-0.800
Ad =
0.550
0.000
0.000
Design load
(kN/m2)
0.600
-0.800
Wk
Ad
if the typical load cases that were considered for the serviceability
limit state are now considered for ultimate limit state with the
following possible load combinations result:
6.10
6.10a
6.10b
+ 1.50Qk + 0.00Wk
+ 1.50Qk + 0.75Wk (pressure)
+ 1.05Qk + 1.50Wk (pressure)
+ 0.00Qk + 1.50Wk (suction)
+
+
+
+
EHF
EHF
EHF
EHF
Accidental
6.11b 1.00Gksup + 0.00Qk + 0.00Wk + 1.00Ad + EHF
23
Wk
Ad
= Imposed
= 0.600 kN/m2
= Wind load:
Wind pressure = 0.500 kN/m2;
Wind suction = -0.800 kN/m2
Gksup =
0.433
Gkinf =
0.283
Qk = Wk (pressure)
0.600
= +0.500
Wk (suction)
= -0.800
Ad =
0.550
0.630
0.630
0.000
0.000
0.000
0.000
Design
load
(kN/m2)
0.900
0.900
0.630
0.000
0.000
0.375
0.750
-1.200
0.000
0.000
0.000
0.000
1.485
1.860
1.965
-0.917
0.900
0.900
0.630
0.000
0.000
0.375
0.750
-1.200
0.000
0.000
0.000
0.000
1.441
1.816
1.921
-0.917
BS5950-1:
0.000
0.000
0.375
-0.600
0.100
0.550
1.215
1.590
-0.317
1.083
Notes:
1. No reduction in loading can be applied on the basis of area since such
reduction only applies to roofs with access.
2. For shallow pitched portals there is no pressure on the whole rafter and
since suction will reduce the total load it must not be included if the most
onerous design combination is to be considered.
Portal frame designers will generally set out to provide the most
economic frame solution and, given the choice of 6.10 or 6.10a
and 6.10b the design loads to be considered in 6.10 are more
onerous and therefore are likely to be ignored. It would appear
that there are more combinations to consider if we apply 6.10a and
6.10b but, by observation, 6.10b combinations are more onerous
than those of 6.10a, other than for a high ratio of dead to imposed
load (see Section 3.1) which is particularly unlikely for this form of
construction.
As shown in Figures 5.1, positive pressure on the whole roof does
not occur for normal portal frame roof pitches. If this pressure is
removed from the example, the design loads in Table 5.3a result.
24
Qk =
0.600
Wk (suction)
= - 0.800
Ad =
0.55
0.630
0.000
0.750
-1.200
0.000
0.000
0.000
0.000
0.550
Design
load
(kN/m2)
1.921
-0.917
0.983
0.585
0.585
0.585
0.283
Gksup =
0.433
Gkinf =
0.283
Load
(kN/m2)
Qkc
Wk
Ad
Other combinations are possible, but those that are most likely to
provide the critical design condition are as follows:
6.14b
1.00Qk
0.70Qk
0.70Qk
0.00Qk
+
+
+
+
1.00Qkc
1.00Qkc
1.00Qkc
0.00Qkc
+
+
+
+
0.50Wk
0.50Wk
1.00Wk
1.00Wk
(pressure)
(pressure)
(pressure)
(suction)
Qkc
Wk
Ad
Qkc
Wk
Ad
= Imposed load
= 0.600 kN/m2
= 0.500 kN/m2;
= -0.800 kN/m2
Load
(kN/m2)
Qk = Wk (pressure) Ad = Design
Qkc =
0.600
= +0.500
0.550 load
56.0/
Wk (suction)
(kN/m2) 17.5kN
= -0.800
0.250
0.250
0.500
-0.800
+
+
+
+
+
6.10b
1.25Gksup
1.25Gksup
1.25Gksup
1.00Gkinf
+
+
+
+
6.10a
1.35Gksup + 1.05Qk + 1.50Qkc + 0.00Wk (suction) + EHF
1.35Gksup + 1.05Qk + 1.50Qkc + 0.75Wk (pressure) + EHF
1.00Gkinf + 0.00Qk + 0.00Qkc + 0.75Wk (suction) + EHF
1.50Qk
1.05Qk
1.05Qk
0.00Qk
+
+
+
+
1.50Qkc
1.50Qkc
1.50Qkc
0.00Qkc
+
+
+
+
0.00Wk
0.75Wk
1.50Wk
1.50Wk
(suction) + EHF
(pressure) + EHF
(pressure) + EHF
(suction) + EHF
Accidental 6.11b
Gksup + 1.00Ad + 0.00Qk + 0.40Qkc + 0.00Wk (pressure) + EHF
Gksup + 1.00Ad + 0.00Qk + 0.90Qkc + 0.00Wk (pressure) + EHF
Gksup + 1.00Ad + 0.00Qk + 0.40Qkc + 0.20Wk (pressure) + EHF
5.3.4 ULS design example for a single span portal with
overhead crane
Substituting the loadings for the example into these equations
yields the design loads as summarised in Table 5.5. The bold
figures identify the critical load combinations.
25
Load
(kN/m2)
Equation 6.10
Gksup =
0.433
Gkinf =
0.283
Qk = Wk (pressure) Ad = Design
0.600
= +0.500
0.550
load
Wk (suction)
(kN/m2)
= -0.800
Qkc =
56.0/
17.5kN
0.585
0.585
0.585
0.585
0.283
0.900
0.900
0.630
0.630
0.000
0.000
0.375
0.375
0.750
-1.200
0.000
0.000
0.000
0.000
0.000
1.485
1.860
1.590
1.965
-0.917
84.0 / 26.25
84.0 / 26.25
84.0 / 26.25
84.0 / 26.25
0.00
0.900
0.630
0.630
0.000
0.000
0.375
0.750
-1.200
0.000
0.000
0.000
0.000
1.441
1.546
1.921
-0.917
84.0 / 26.25
84.0 / 26.25
84.0 / 26.25
0.00
Equation 6.11b
0.433
0.433
0.630
0.630
0.000
0.000
0.000
0.000
0.375
-0.600
0.000
0.100
0.000
0.000
0.000
0.550
0.550
1.215
1.590
-0.317
0.983
1.083
84.0 / 26.25
84.0 / 26.25
0.000
50.4 / 15.75
22.4 / 7.0
Notes:
1. Transverse wind load cases will cause suction on the roof but will also cause the portal
to sway. SLS will identify the load case for maximum sway.
2. EHF to be applied in the same direction as the horizontal surge.
3. Frame may naturally sway therefore important to ensure that the surge load is applied
in two alternative directions to find the natural sway and ensure that the EHF does not
prop the frame.
26
6 . Re fe r e n ce s
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
[9]
Roof loads due to local drifting of snow, BRE Digest 439, The
Building Research Establishment, 1999.
27