You are on page 1of 3

MOTOCARETM

End Winding Discharges + Corona 210 MW, 15.75


kV Generator

R Phase 14000 pC

Y Phase 57.7 pC

B Phase 68.4 pC

-ve half cycle pulses (positive PD) dominate

www.diatechindia.com

MOTOCARETM

Insulation delamination & surface contamination


30 MW , 11 kV Generator

GTG 1 2410 pC

GTG 6 69.4 pC

+ve & -ve half cycle pulses equal, asymmetric

www.diatechindia.com

MOTOCARETM

Poor contact between stress grading & slot corona


protection 2.4 MW , 6.6 kV Motor

Before overhaul 9010 pC

After overhaul 229 pC

Equally distributed high amplitude, low repetition rate pulses

www.diatechindia.com