GENERAL
Design
Type
Motorised
Rated voltage
No. of poles
Rated short-duration power-frequency
withstand voltage
Rated lightning impulse withstand
voltage
Rated frequency
Rated normal current
for ring-main feeders
for busbar
for circuit-breaker feeders
Rated short-time withstand current
Rated peak withstand current
Rated short-circuit making current
for ring-main feeders
for circuit-breaker feeders
Degree of protection
for gas-filled switchgear vessel
for switchgear enclosure
for low-voltage compartment
Internal Arc test
Type of insulation

Requirement
Metal enclosed
Outdoor
Yes
12 kV
3
28 kV RMS - 1 min
75 kV
50 Hz
400A
400 A
200 A
20 kA, 3 sec
50 kA
50 kA
50 kA
IP65
IP54
IP54
20kA, 1 sec
Vaccum

Guaranteed