You are on page 1of 14

ILLUMINATION SURVEY PYRO

DATE : 24-01-12

Sr. No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39

AREA
F/C-MCC ROOM
F/C-MCC ROOM
F/C-MCC ROOM
F/C-MCC ROOM
F/C-MCC ROOM
F/C-MCC ROOM
GCP-MCC ROOM
GCP-MCC ROOM
GCP-MCC ROOM
GCP-MCC ROOM
GCP-MCC ROOM
GCP-MCC ROOM
GCP-MCC ROOM
OXYGEN PLANT
OXYGEN PLANT
OXYGEN PLANT
BLOWER HOUSE
BLOWER HOUSE
PUMP HOUSE
GCP AREA
GCP AREA
GCP AREA
GCP AREA
GCP AREA
GCP AREA
CANSOLV AREA
CANSOLV AREA
CANSOLV AREA
F/C BUILDING
F/C BUILDING
F/C BUILDING
F/C BUILDING
F/C BUILDING
F/C BUILDING
F/C BUILDING
F/C BUILDING
F/C BUILDING
F/C BUILDING
F/C BUILDING

40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58

F/C BUILDING
F/C BUILDING
F/C BUILDING
F/C BUILDING
F/C BUILDING
F/C BUILDING
F/C BUILDING
F/C BUILDING
F/C BUILDING
F/C BUILDING
F/C BUILDING
RMHS BUILDING
RMHS BUILDING
RMHS BUILDING
RMHS BUILDING
RMHS BUILDING
RMHS BUILDING
RMHS BUILDING
RMHS BUILDING

59
60
61
62
63
64
65

RMHS BUILDING
RMHS BUILDING
RMHS BUILDING
JUNCTION TOWER STAIRS
TURBINE AREA
HOT ESP STAIRS
HOT ESP FIRST FLOOR

LOCATION
11 K.V S/B FRONT SIDE
11 K.V S/B REAR SIDE
3.3 K.V S/B FRONT SIDE
3.3 K.V S/B REAR SIDE
PMCC PANEL FRONT SIDE
PMCC PANEL REAR SIDE
MCC WAYWARD STAIRS
PMCC FRONT SIDE
PMCC REAR SIDE
CANSOLV MCC FRONT SIDE
CANSOLV MCC REAR SIDE
GCP MCC FRONT SIDE
GCP MCC REAR SIDE
BOC-MCC ROOM
COMPRESSOR ROOM
A.B.-01 & A.B.-02 ROOM
LAB FRONT AREA
SAB FRONT AREA
PUMP HOUSE
50-P-12-A,50-P-12-B PUMPS-AREA
G.C.P GROUND FLOOR
STAIRS (GROUND TO FIRST FLOOR) (WESP)
FIRST FLOOR (WESP)
STAIRS (FIRST FLOOR TO SECOND FLOOR) (WESP)
SECOND FLOOR (WESP)
RICH AMINE TANK AREA
LEAN AMINE TANK AREA
FIRST FLOOR
GROUND FLOOR
STAIRS (GROUND TO FIRST FLOOR)
TAPPING FLOOR
L3 LAUNDER (TAPPING FLOOR)
L1 & L2 LAUNDER (TAPPING FLOOR)
STAIRS (FIRST TO SECOND)
SECOND FLOOR
STAIRS ( SECOND TO THIRD)
THIRD FLOOR
STAIRS (THIRD TO FOURTH)
LANCE FLOOR

CATEGORY
(Select From Drop Down)
Substation (Indoor)
Substation (Indoor)
Substation (Indoor)
Substation (Indoor)
Substation (Indoor)
Substation (Indoor)
Indoor Plant area
Substation (Indoor)
Substation (Indoor)
Substation (Indoor)
Substation (Indoor)
Substation (Indoor)
Substation (Indoor)
Substation (Indoor)
Indoor Plant area
Indoor Plant area
Indoor Plant area
Indoor Plant area
Indoor Plant area
Indoor Plant area
Indoor Plant area
Indoor Plant area
Indoor Plant area
Indoor Plant area
Indoor Plant area
Indoor Plant area
Indoor Plant area
Indoor Plant area
Indoor Plant area
Indoor Plant area
Indoor Plant area
Indoor Plant area
Indoor Plant area
Indoor Plant area
Indoor Plant area
Indoor Plant area
Indoor Plant area
Indoor Plant area
Indoor Plant area

LANCE PARKING AREA


STAIRS (FOURTH TO FIFTH)
CONTROL ROOM
STAIRS (FIFTH TO SIXTH)
SIXTH FLOOR
STAIRS ( SIXTH TO SEVENTH)
SEVENTH FLOOR
LANCE CHANGE PANEL FLOOR
STAIRS ( SEVENTH TO TOP)
TOP FLOOR (HEAD TANK AREA)
L.T.C AREA
STAIRS (GROUND TO FIRST)
FIRST FLOOR
STAIRS ( FIRST FLOOR TO SECOND FLOOR)
SECOND FLOOR ( PUGMILL)
STAIRS (SECOND TO THIRD)
CV-04 DISCHARGE CHUTE
STAIRS (THIRD TO FOURTH)
BIN FLOOR

Indoor Plant area


Indoor Plant area
Control Rooms
Indoor Plant area
Indoor Plant area
Indoor Plant area
Indoor Plant area

STAIRS (FOURTH TO FIFTH)


CV-03 FLOOR
CV-02 FLOOR
JUNCTION TOWER STAIRS
TURBINE AREA
HOT ESP STAIRS
HOT ESP FIRST FLOOR

RMH Area
RMH Area
RMH Area
RMH Area
Turbines Floor
Indoor Plant area
Indoor Plant area

Indoor Plant area


Indoor Plant area
Indoor Plant area
Indoor Plant area

RMH
RMH
RMH
RMH
RMH
RMH
RMH
RMH

Area
Area
Area
Area
Area
Area
Area
Area

Performed By: Mahaveer Singh Rawat


Location : PYRO
REQUIRED LUX LEVEL
As Per IS 3646
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100

ACTUAL LUX LEVEL


(24-11-11)
128
102
142
94
107
78
105
150
135
120
150
240
200
160
124
144
64
36
17
4
64
30
20
28
15
30
10
34
106
80
178
160
98
76
52
70
10
52
40

ACTUAL
LUX
(24-01-12)
128
102
142
102
107
78
450
157
137
120
280
242
360
160
124
143
64
36
17
4
65
30
20
28
22
30
7
34
106
85
178
160
98
90
70
69
70
70
46

LEVEL

100
100
250
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
200
100
100
#N/A
#N/A
#N/A

106
53
240
15
10
15
20
250
44
35
38
9
25
70
93
15
58
12
28

106
70
256
70
26
69
40
250
72
42
38
9
25
70
93
64
58
18
28

25
128
22
57
52
8
14

32
130
112
57
109
8
14

TARGET DATE

10 Days upon receipt of Materials

10 Days upon receipt of Materials


10 Days upon receipt of Materials
10 Days upon receipt of Materials
10 Days upon receipt of Materials
10 Days upon receipt of Materials
10 Days upon receipt of Materials
10 Days upon receipt of Materials
10 Days upon receipt of Materials
10 Days upon receipt of Materials
10 Days upon receipt of Materials
10 Days upon receipt of Materials
10 Days upon receipt of Materials
10 Days upon receipt of Materials
10 Days upon receipt of Materials

10 Days upon receipt of Materials


10 Days upon receipt of Materials
10 Days upon receipt of Materials
10 Days upon receipt of Materials
10 Days upon receipt of Materials
10 Days upon receipt of Materials
10 Days upon receipt of Materials

10 Days upon receipt of Materials


10 Days upon receipt of Materials
10 Days upon receipt of Materials
10 Days upon receipt of Materials
10 Days upon receipt of Materials
10 Days upon receipt of Materials
10 Days upon receipt of Materials
10 Days upon receipt of Materials
10 Days upon receipt of Materials
10 Days upon receipt of Materials
10 Days upon receipt of Materials
10 Days upon receipt of Materials
10 Days upon receipt of Materials
10 Days upon receipt of Materials
10 Days upon receipt of Materials
10 Days upon receipt of Materials
10 Days upon receipt of Materials

10 Days upon receipt of Materials


10 Days upon receipt of Materials
10 Days upon receipt of Materials
10 Days upon receipt of Materials

Industrial Building / Plant area


RMH Area
Indoor Plant area
All Office Building
Internal Factories Road
Canteens
Work Shops
Coal & Ash Handling Plant
Control Rooms
Turbines Floor
Laboratories and Test Rooms
Boiler Houses
Coal unloading /Storage area (out
door)
Oil storage Area
Switch Yard
Substation (Indoor)

Recommended
Values of
Illumination (Lux)
as per IS :3646
100
100
300
20
150
300
100
250
200
300
100
20
50
100
100

You might also like