The document provides calibration procedures for drum level transmitters. It specifies that the transmitters should be calibrated for their total range rather than a restricted range. It then details that between two tapping points at a site, the total distance is 1199 mmWC. The transmitters should be calibrated such that 1199 mmWC corresponds to 4 mA and 0 mmWC corresponds to 20 mA. The high and low limits for the range in the corresponding ATAG should be -437 and 762 respectively.
Original Description:
Level control using PID control loop discussed in detail also given values for point browser to fill and to calibrate it perfectly
It also Contains Drum level transmitter values.
The document provides calibration procedures for drum level transmitters. It specifies that the transmitters should be calibrated for their total range rather than a restricted range. It then details that between two tapping points at a site, the total distance is 1199 mmWC. The transmitters should be calibrated such that 1199 mmWC corresponds to 4 mA and 0 mmWC corresponds to 20 mA. The high and low limits for the range in the corresponding ATAG should be -437 and 762 respectively.
The document provides calibration procedures for drum level transmitters. It specifies that the transmitters should be calibrated for their total range rather than a restricted range. It then details that between two tapping points at a site, the total distance is 1199 mmWC. The transmitters should be calibrated such that 1199 mmWC corresponds to 4 mA and 0 mmWC corresponds to 20 mA. The high and low limits for the range in the corresponding ATAG should be -437 and 762 respectively.
PROCEDURE FOR CALIBRATION OF DRUM LEVEL TRAMITTERS
1. The transmitters should be calibrated for total range. Do not restrict the range to the range of transmitters given in the Instrument Schedule. 2. As per tapping points available at New Parli Site, a total distance between two tapping points is 512 + 687 = 1199 (Calculated for P6 tapping points). 3. Calibrate transmitter as follows: 1199 mmWC = 4 mA 0 mmWC = 20 mA 4. In the corresponding ATAG, the LimRanage Hi should be -437 and Limrange Lo should be 762. 5. In the Level comp block, inrange hi should