You are on page 1of 211

Special Publication of the IEEE Power

System Relaying Committee

Copyright IEEE 2011

IEEE TUTORIAL ON THE PROTECTION


OF SYNCHRONOUS GENERATORS

Copyright IEEE 2011

Developed by a working group of the


Power System Relay Committee (PSRC)

First published in 1995 widely presented


within the industry, including a presentation
at the 2003 PPIC Conference

Updated, published, and presented for the


first time at the 2011 57th IEEE Pulp and
Paper Industry Conference

Michael Thompson, Chair


Christopher Ruckman, Vice Chair
Hasnain Ashrafi
Gabirel Benmouyal
Zeeky Bukhala
Stephen P. Conrad
Everett Fennell
Dale Finney
Dale Fredrickson
Jonathan D. Gardell
Juan Gers
Randy Hamilton
Wayne Hartmann
Gerald Johnson
Patrick M. Kerrigan
Sungsoo Kim
Prem Kumar

Hugo Monterrubio
Charles Mozina
Mukesh Nagpal
Brent Oxandale
Russell W. Patterson
Mike Reichard
Mohindar Sachdev
Kevin Stephan
Sudhir Thakur
Demetrios Tziouvaras
Joe Uchiyama
Quintin Verzosa, Jr.
Thomas Wiedman
Michael Wright
John Wang
Murty V. V. S. Yalla

Michael J. Thompson received his BS, magna cum laude, from


Bradley University in 1981 and an MBA from Eastern Illinois University in 1991. He
has broad experience in the field of power system operations and protection. Upon
graduating, he served nearly 15 years at Central Illinois Public Service (now
AMEREN), where he worked in distribution and substation field engineering before
taking over responsibility for system protection engineering. Prior to joining
Schweitzer Engineering Laboratories, Inc. in 2001, he was involved in the
development of several numerical protective relays while working at Basler Electric.
He is presently a Principal Engineer in SELs Engineering Services Division; a
senior member of the IEEE; a main committee member of the IEEE PES Power
System Relaying Committee; and a registered professional engineer. Michael was a
contributor to the reference book, Modern Solutions for the Protection Control and
Monitoring of Electric Power Systems, has published numerous technical papers,
and has a number of patents associated with power system protection and control.

Charles (Chuck) Mozina received a B.S. degree in electrical engineering


from Purdue University, West Lafayette, in 1965. He is a Consultant, for Beckwith
Electric Co. Inc., specializing in power plant and generator protection. His consulting
practice involves projects relating to protective relaying applications, protection
system design and coordination. Chuck is an active 25-year member of the IEEE
PES Power System Relay Committee and was the past chairman of the Rotating
Machinery Subcommittee. He is active in the IEEE IAS I&CPS, PCIC and PPIC
Committees, which address industrial protection systems. He is the past U.S.
representative to CIGRE Study Committee 34 (now B-5) on System Protection. He
has over 25 years of experience as a protective engineer at Centerior Energy (now
part of FirstEnergy), a major utility in Ohio, where he was Manager of System
Protection. For 10 years, he was employed by Beckwith Electric as the Manager of
Application Engineering for Protection Systems. He is now a consultant for that
company. He is a registered Professional Engineer in the state of Ohio and a Liife
Fellow of the IEEE.
6

Fundamentals

Multifunction Generator Protection Systems

Stator Phase Fault Protection

Stator Ground Fault Protection

Field Fault Protection

System Backup Protection

Generator Breaker Failure

Abnormal Frequency Protection

Overexcitation and Overvoltage Protection

Underexcitation / Loss-of-Excitation Protection

Current Unbalance (Negative-Sequence) Protection

Loss of Prime Mover (Antimotoring) Protection

Out-of-Step Protection

Voltage Transformer Signal Loss

Inadvertent Energization Protection

Other Protective Considerations

Tripping Modes

IEEE TUTORIAL ON THE PROTECTION


OF SYNCHRONOUS GENERATORS

Copyright IEEE 2011

Basic design and operation of


synchronous generators

Power system connections

Behavior under short-circuit conditions

Generator grounding

Generator stability

IEEE guidelines

Device numbers

Reactive Power
Into System
+
MVAR
Overexcited

Rotor
Winding
Limited

MW
System

MVAR
Normal Overexcited
Operation

Overexcitation
Limiter (OEL)

Stator
Winding
Limited
+ MW Real Power
Into System

Underexcitation
Limiter (UEL)
Underexcited

MVAR
Reactive Power
Into Generator

MW

Underexcited
Operation

G
Stator End
Iron Limited

Steady-State
Stability Limit

System
MVAR

kV 2 RC
MVA =

Z RV
kV 2 RC
Z=

MVA R V

Angle
Angle

Current

Current

Current

Accumulation of Damage Over Time

wattseconds

8000
wattseconds

6000
4000

Total
Generator

2000
0
0.01

System
0.1
1
time, seconds

10

Most damage occurs in period after the generator breaker opens

Types of Instability

Steady-State

Transient

Dynamic

Pmax =

Pe =

Eg Es
X

sin g s

Power Flow
L1
L2
L3

Egg

Power
POWER
System

SYSTEM

L4

Ess

Eg Es
X

Generator

GSU

G
Xd
V

XS
Where:
XT
Xe = XT + XS

Per-Unit MVAR

V2
2

1
1

X
X
d
e

System
Reactance

X
Xe

V2
2

1
1
+

X
X
d
e

Xd Xe
2

Xd + Xe
2

Per-Unit MW

MW-MVAR Per-Unit Plot

R-X Diagram Plot

Ess

Power System

Three-Phase
Short Circuit

Substation
1

GSU
78 = Out-of-Step Protection
Es = System Voltage
Eg = Generator Voltage
s = System Voltage Phase Angle
g = Generator Voltage Phase Angle

78
G

Egg

Pmax =

Maximum
Power
Transfer

Eg Es
X

All Lines in Service


Breakers 1 and 2
Tripped

A2
PM = Pe

Pe =
A1
C
0

90
g s

180

Eg Es
X

sin g s

Occurs when fast-acting AVR control


amplifies rather than damps small MW
oscillations

Most likely to occur when generators


are remote from load centers

Power system stabilizer (PSS) damps


oscillations required in Western
United States

Latest developments reflected in

Std. 242, IAS Buff Book

C37.102, IEEE Guide for Generator Protection

C37.101, IEEE Guide for AC Generator


Ground Protection

C37.106, IEEE Guide for Abnormal Frequency


Protection for Power Generating Plants
Created / maintained by the IEEE PSRC & IAS
updated every 5 years

C37.102-2006
updated version now
available includes
significant changes
and additions

Device Number

Function

Tutorial Chapter

11

Multifunction Protection System

5.2

21

Distance Relay Backup for System and


Generator Zone Phase Faults

2.4

24

Volts / Hertz Protection for Generator


Overexcitation

3.2

27TN

100 Percent Stator Ground Fault Protection

2.2

32

Reverse Power Relay Antimotoring


Protection

3.5

40

Loss-of-Field Protection

3.3

46

Negative-Sequence Current Unbalance


Protection for Generators

3.4

49

Stator Thermal Protection

51G

Time-Overcurrent Ground Relay

2.2

51TG 1&2

Backup for Ground Faults

Device Number

Function

Tutorial Chapter

51V

Voltage-Controlled or Voltage-Restrained
Time-Overcurrent Relay Backup for
System and Generator Phase Faults

2.4

59

Overvoltage Protection

3.2

59G

Overvoltage Relay Stator Ground Fault


Protection for Generators

2.2

60

Voltage Balance Relay Detection of Blown


Voltage Transformer Fuses

3.7

63

Transformer Fault Pressure Relay

62B

Breaker Failure Timer

2.5

64F

Field Ground Fault Protection

2.3

71

Transformer Oil or Gas Level

78

Loss-of-Synchronism Protection

3.6

Device Number

Function

Tutorial Chapter

81

Frequency Relay Both Underfrequency


and Overfrequency Protection

3.1

86

Hand-Reset Lockout Auxiliary Relay

5.1

87G

Differential Relay Primary Phase Fault


Protection for Generators

2.1

87N

Stator Ground Fault Differential Protection

2.2

87T

Differential Relay Primary Protection for


Transformers

87U

Differential Relay Overall Generator and


Transformer Protection

2.2

Transformer Fault Pressure

63
Oil Low
71

87T

51
TG1

Unit
Transformer

51 Transformer Neutral
TG2
Overcurrent

87O
Unit
Differential

50
51

Second
V/Hz

24
2

UAT Backup

UAT Oil Low


71

Voltage
Balance

60

UAT Fault
Pressure

63
UAT

Overvoltage 59
50/
27
Inadv. Energ.
(Note 4)

81

UAT Neutral
Overcurrent

51
Unit Auxiliary
Bus Phase Time
Overcurrent

78
Loss of
Synchronism
24
1

V/Hz

87T

UAT
Differential

40

Loss of
Field

Auxiliary VTs

32

Field
Breaker

51 51
TG1 TG2

Frequency

Reverse
Power

49

41
Stat.
Temp
64F

53

87G

Generator
Differential

Field (Note 1)
Ground
21/
51V

46
Negative
Sequence

59G

50/
51G

Generator
Neutral
Overvoltage

Generator
Neutral
Overcurrent

System
Backup
(Note 2)

27
TN

100 Percent
Stator Ground
(Note 3)

Notes:
1. Dotted devices optional.
2. Device 21 requires external timer. See Chapter 2.4.
3. See Chapter 2.2 regarding 100 percent ground protection.
4. Device 50 requires external timer. See Chapter 4.1.

IEEE TUTORIAL ON THE PROTECTION


OF SYNCHRONOUS GENERATORS

Copyright IEEE 2011

Generator protective relaying technology


has evolved from discrete electromechanical
and static relays to digital multifunction
protection systems

With availability, additional performance,


economic advantages, and reliability of
digital multifunction protection systems, this
advanced technology is incorporated into
most new protection schemes

In most cases, new generators are


protected with one of the following:

Dual MGPSs

Single MGPS, possibly backed up by


single-function relays

Inputs

Outputs
ROM
RAM

Voltage Inputs

EEPROM
Current Inputs

Data
Acquisition
System

User Interface
Microprocessor

Other Analog
Inputs

Targets
Digital
Outputs

Digital Inputs
One or More
Power Supplies

Communications

High-Voltage System Bus

52

Generator Transformer
87AT

87T

Auxiliary Bus
52

87O
11G
MGPS #1
Relaying Functions
24
27/59
32-1
32-2
40
46
49
50
51V or 21
50/51G
59G
60
78
81
87G
27TH or 59THD or 64S

Field

11G
MGPS #2
Relaying Functions
24
27/59
32-1
32-2
40
46
49
50
51V or 21
50/51G
59G
60
64F
81
87G
27TH or 59THD or 64S

Note: Only use functions as appropriate.

IEEE TUTORIAL ON THE PROTECTION


OF SYNCHRONOUS GENERATORS

Copyright IEEE 2011

Saturation

Stator differential protection does not


detect turn-to-turn faults

Current can be 6 to 7 times nominal


and can damage stator

Use turn-to-turn protection schemes to


detect and avoid damage

Imperfection in generator construction

Temperature variations

Winding connections

External faults

Terminal voltage and load variations

IEEE TUTORIAL ON THE PROTECTION


OF SYNCHRONOUS GENERATORS

Copyright IEEE 2011

The Method of Generator Neutral


Grounding Determines its Performance
During Ground Faults
Solidly Grounded
Low Impedance
High Impedance
Hybrid Grounding
Ungrounded

Multiple Bus (No/Low Z/High Z)

BUS

Directly connected to bus


Likely in industrial, commercial,

and isolated systems


May have problems with
circulating 3rd harmonic
Use of single grounded machine
can help

Adds complexity to discriminate

ground fault source if ground


resistance is high (less than 25A)

Same type of grounding used on 1 or mutiple generators

Low Resistance
Grounding
Systems

45MVA Generator

2000/5

2000/5 CTs
80%

2000/5

87

87 Set at 0.2A Pickup


20% of Winding Not
Protected

400 A

62

Percentage of Stator Winding


Unprotected

87G Generator Differential


87GD Generator Ground Differential
51N Neutral Overcurrent

IA
IB

Residual current
calculated from
individual phase
currents. Paralleled
CTs shown to
illustrate principle.

90

IC
IG

IG

3I O

3 I0

180

-3Io x IG cos (180) = 3IoIG

IG
270

IA
IB

Residual current
calculated from
individual phase
currents. Paralleled
CTs shown to
illustrate principle.

90

IC
IG

IG

3I 0

180

-3Io x IG cos (0) = -3IoIG

IG
3I O 270

59N, 3V0 overvoltage, covers 95% of winding


Tuned to the fundamental frequency
Must work properly from 10 to 80 Hz during startup.

3rd Harmonic methods cover remaining 5% of


winding near neutral
27TN, 3rd harmonic undervoltage
59D, Ratio of 3rd harmonic voltage at terminal and

neutral ends of winding

64S, Subharmonic voltage injection, covers


100% of winding

High-impedance ground limits


ground fault current (limits
damage on internal winding to
ground fault)
Conventional neutral or zerosequence overvoltage relay
(59G) provides coverage for the
ground faults involving up to
90%95% of the winding from
phase terminal
R

59G

51G connected in the primary


or secondary neutral circuit can
be used as a backup to 59G

Last 5%10% near neutral


not covered by neutral
overvoltage relay (59G)
because a ground fault in this
winding region bypasses
grounding transformer or
resistor (R) or 59G, solidly
grounding the machine

59G

XHL

59G

Sensitively set 59G relay to


detect ground faults (up to
95% of the winding) can also
pick up for faults on the HV
side of GSU or in the VT
secondary circuit

Io

Co

CHL

Z0

VR := V0

Z
+
X
HL
0

Zero-Sequence
Network

XHL
R
3Io

VR

3R

Xo

V0

Third-harmonic voltage develops in


stator due to inherent presence of
third harmonic flux in the rotor field

Rotor MMF

I3h A, B, C

Co

Generator winding and terminal


capacitances provide path for
the third-harmonic stator current
via grounding resistor
R
3I3h

Machine construction the pitch


of the stator

Levels of excitation (MVAR) and


machine output (MW)

Terminal capacitance

+V3RD

Normal Operation
Neutral
No Load

Full Load
No Load
Terminal

Full Load

+V3RD
Full Load
No Load

Neutral

Terminal
Fault at Terminal
Neutral
No Load

Terminal

Full Load
V3RD

Can vary with loading


Detects ground faults
near neutral

V3RD
Fault at Neutral

Present in terminal and


neutral ends

Note: If third harmonic goes away


across neutral resistor, conclude a
ground fault near neutral

I3h

C0

Under normal conditions,


27N3 is picked up because of
the third-harmonic voltage
drop across neutral resistor

3I3h

59G

27N3

I3h

C0

3I3h

59G

27N3

For a fault close to neutral of


the stator winding, 27N3 drops
out because the fault bypasses
the neutral resistor
A supervisory overvoltage
(59C) relay located at the
generator terminal blocks
27N3 operation during startup
or shutdown to avoid
misoperation

100%

59G

~95% of winding from


terminal by 59G
~15%30% of winding
from neutral by 27N3

27N3
5%
0%

59G

27N3

Compares third-harmonic
voltage magnitude at the
generator neutral to that
at the generator terminals
Ferroresonance
damping resistor
59D

59G

100%

~95% of winding from


terminal by 59G

59G

~15%30% of winding
from neutral and
terminal by 59D

59D
59D

5%
0%

59G

59D

Does not rely on third-harmonic signature


of generator

Provides full coverage protection

Provides online and offline protection


prevents serious damage upon application
of excitation

Is frequency independent

Injection Signal
20 Hz
Generator

Pickup
Setting

64S

Measurement Signal
20 Hz Filter

Measurement
Value

For stator ground fault,


20 Hz increases and
relay (64S) operates

IEEE TUTORIAL ON THE PROTECTION


OF SYNCHRONOUS GENERATORS

Copyright IEEE 2011

Hazards of field faults

Field ground protection

Tripping considerations

Field ground relay selection and settings

Field overcurrent

Field

Field
Breaker

Exciter

64F
DC

Voltage
Relay
Grounding
Brush

Ground #1
Ground #2

Shorts out part of field winding expect unit vibrations,


possible damage

Causes local rotor current expect rotor heating, distorted


rotor, vibration

Causes arc damage at fault points

Field

Field
Breaker

Exciter

64F
DC

Use on generators
with brushes

Has variable
detection sensitivity

Voltage
Relay
Grounding
Brush

Field Breaker
Control

Positive
Varistor

R2
Generator

Generator
Field

+ Exciter
64F

Test
Pushbutton
(optional)

Field Breaker
Control

Voltage
Relay

R2

Negative

Field
+

Exciter
Field
Breaker

Brush
CR

C2

C1
AC
R

64F

Immediate tripping is recommended on


first ground

However, most installations alarm and


shutdown the machine in orderly manner if
ground alarm persists

Relays should also be provided with time


delays to override transients

IEEE TUTORIAL ON THE PROTECTION


OF SYNCHRONOUS GENERATORS

Copyright IEEE 2011

System backup protection for


generators consists of time-delayed
protection for phase-to-ground and
multiphase fault conditions

Backup generator protection


schemes protect against failure of
system protection and subsequent
long-clearing system faults

Relay settings for backup relaying


must be sensitive to detect low fault
current conditions

Settings must balance opposing


sensitivity requirements to detect
distant faults and security to prevent
unnecessary generator tripping

Note locations of current and


voltage transformers.

Use either distance or voltagerestrained overcurrent relay to


detect system multiphase faults.

Use a time-inverse transformer


neutral connected overcurrent
relay for system ground faults.

98

Choose protection based on line relay


type
If distance type, back up with distance
If time-overcurrent type, back up with V-R or

V-C overcurrent

Time coordinate with system relays


including breaker failure relaying

Current Level

Voltage element supervises (torque controls) a


sensitive, low pickup time-overcurrent element

Under fault conditions, voltage drops below set


level dropping out voltage element and
permitting overcurrent element to operate

Current Pickup Level

V-R overcurrent consists of an overcurrent element


whose pickup level varies as a function of voltage
applied to relay

Normally, generator terminal voltage is above


voltage setting, VS1, and current pickup setting is IS

Current Pickup Level

When close-in fault occurs, voltage can drop below


voltage setting, VS2, and current pickup level is
reduced by factor k to kIS

For voltages between VS1 and VS2, pickup level


varies proportionately between IS and kIS

Set pickup below generator fault current


using synchronous reactance
V-C pickup will likely be below rated current
V-R pickup must be above rated current

Calculate 51V voltage element setting to


avoid 51V relay misoperation under
extreme emergency conditions (with
lowest expected system voltage)

To allow for selectivity, time-delay settings


must be coordinated with transmission
system primary and backup protection,
including breaker failure time

Coordination is usually calculated with


zero voltage restraint

Use three V-C or V-R time-overcurrent relays for


complete multiphase fault coverage

Note that generator fault current may decay


rapidly when low voltage is at generator
terminals overcurrent phase fault backup may
not operate for system faults

Check setting with fault current decrement curve


for particular generator and excitation system

Setting detects line fault when protection


equipment fails

Relay impedance reach and time delay must be


coordinated with system primary and backup
protection, including breaker failure time

Setting must remain conservatively above


machine rating to prevent inadvertent trips on
generator swings and severe voltage disturbances

F5

FLT

F4

F1

F3

F2

The impedance relay


for each generator
requires sensitive
settings to detect
faults at the ends of
long lines in the
presence of other
sources.

Sensitive settings may cause backup relays


to unnecessarily trip generator under some
loading conditions or for minor, stable swings

With this system configuration, it is generally


possible to set backup relays to detect only
close-in faults

Redundant line relaying and breaker failure


relaying are necessary for line, bus, and
transformer protection

Set impedance relay to smallest of the


three following criteria:

120% of longest line (with infeed) if unit is connected to


breaker-and-a-half bus, calculate percent using adjacent
line length

50%66.7% of load impedance (200%150% of generator


capability curve) at machine-rated power factor

80%90% of load impedance (125%111% of generator


capability curve) at relay maximum torque angle (MTA)

GCC
Zone 1
Zone 2
System

jX
30.0
Longest Line
(With Infeed)
75.5 Ohms

25.0

20.0

Zone 2 reach will not provide adequate phase


fault system backup protection as it would
require an extremely large setting. The only
way to ensure adequate protection to avoid
sustained currents to the fault is to provide
redundant transmission system protection.

Zone 2
15.0

10.0

50-67% of GCC
@ RPFA

Shortest Line
(No Infeed)

RPFA

Zone
1
5.0

Transformer
High Side
5.0

GCC

MTA

5.0

10.0

Zone 2 limited to 67% of


generator capability curve
at rated power factor.

5.0

10.0

15.0

R
20.0

Zone 1 set to cover 120%


of GSU impedance.

IEEE TUTORIAL ON THE PROTECTION


OF SYNCHRONOUS GENERATORS

Copyright IEEE 2011

Provides for tripping of backup breakers when


the generator breaker does not open after trip
initiation upon detection of

Fault

Abnormal
condition

Open circuit to trip coil


Mechanism fails to open breaker
Breaker opens but breaker contacts fail to
interrupt fault
Tripping of circuit breaker left open after
maintenance

Generator trips may not always be from


high-current events (faults)
Overexcitation
Overvoltage
Sequential tripping

Need to include breaker auxiliary contact


status in addition to current detection
BF protection should be fast enough to
maintain stability but not so fast as to
compromise tripping security

Breaker flashover is a type of breaker


failure
Breaker flashover is most likely to occur
just prior to synchronizing or just after
generator is removed from service

Three-phase simultaneous flashovers are


rare, thus most protection schemes are
designed to detect the flashover of one
or two poles

IEEE TUTORIAL ON THE PROTECTION


OF SYNCHRONOUS GENERATORS

Copyright IEEE 2011

Underfrequency occurs as the result of


sudden reduction in input power through
loss of generators or key intertie
importing power

Overfrequency occurs as the result of


sudden loss of load or key intertie
exporting power

Regional reliability councils will typically


provide settings for underfrequency load
shedding and generator tripping

Load shedding schemes must coordinate


and meet regional criteria

Generator tripping criteria must


accommodate any frequency excursion
during any islanding scenario

60

Frequency (Hz)

59

58

57
Generator tripping permitted on
or below curve without requiring
additional equivalent automatic
load shedding.

56

55
0.1

3.3
Time (s)

10

100

300

V%

106

Operation outside shaded area is


limited in extent, duration, and
frequency of occurrence
Severe restrictions
could be imposed on
the generator itself

94

96

104

102

98

100

104

102

f%

98

96

Possibility of frequency
operational limits exists for the generator
in the form of time-frequency characteristics
94

Copyright 2005 IEC,


Geneva Switzerland

Protection of the long tuned blading in the


low-pressure turbine element for steam units

Possibility of cumulative blading fatigue and


blading failure

Similar limitations for combustion and


combined-cycle turbines

Virtually no frequency limitations for hydro


generating units

Example of fictitious steam turbine


operational limits shown in the plot
62

61

Restricted Time
Operating Frequency Limits

60

Continuous Operation

Prohibited
Operation

59
Restricted Time
Operating Frequency Limits
58
57
56
0.001

Prohibited
Operation
0.005
0.01

0.05

0.50
0.10
1.0
Time (Minutes)

5.0

10.0

50.0

100.0

Obtain turbine capability 63


62
from manufacturer
61

Verify if IEC 60034-3:


2007 is applicable

60

Have manufacturer
approve protection
scheme

57

Continuous Operating Region

59
58
10-Minute
Maximum

56
55
54
1

10
100
1000
Total Accumulated Time Limit (Minutes)

Limits similar to steam turbine

Example of frequency limits in the plot

Frequency (Hz)

IEEE TUTORIAL ON THE PROTECTION


OF SYNCHRONOUS GENERATORS

Copyright IEEE 2011

V/Hz application can result in:


Heating of stator core iron
Stray flux increasing beyond design limits causing

additional heating

Overvoltage application:
Stresses stator insulation and connected components
Cannot be reliably detected using V/Hz alone

Offline generator voltage regulator problems


Operating error during unit synchronizing
Control failure
VT fuse loss in voltage regulator (AVR)

System problems
Unit load rejection: full load, partial rejection
Power system islanding during major disturbances

Generators: 1.05 pu (generator base)

Transformers:
1.05 pu at rated load at 0.8 PF
1.1 pu at no load

V%
106

104

102
94

96

98

100

98

96

94
Copyright 2005 IEC, Geneva, Switzerland

102

104 f%

130
125
120
115
110
105
100
0.1

10

100

140

130

120
Individual manufacturers
should be consulted for limits
of a specific transformer.
110
0.01

0.1

1
Time (minutes)

10

100

V/Hz (%)

IEEE TUTORIAL ON THE PROTECTION


OF SYNCHRONOUS GENERATORS

Copyright IEEE 2011

Limiting factors are rotor


and stator thermal limits
Underexcited limiting factor
is stator end iron heat
Excitation control setting
control is coordinated with
steady-state stability limit
(SSSL)
Minimum excitation limiter
(MEL) prevents exciter
from reducing the field
below SSSL

Reactive Power
Into System

Rotor
Winding
Limited

+
MVAR

MW
G

System
MVAR

Overexcited

Stator
Winding
Limited
+ MW

Real Power
Into System

MEL
Underexcited

MVAR
Reactive Power
Into Generator

MW
SSSL
Stator End
Iron Limited

System

G
MVAR

Field open circuit

Field short circuit (flashover across slip rings)

Accidental tripping of field breaker

Voltage regulator control system failure

LOF to main exciter

Loss of ac supply to excitation system

Impedance variation with


the machine operating at
or near full load locus
follows path from C to D
Machine that initially
operates at 30% load and
underexcited. Impedance
locus follows path from E
to F to G and oscillates in
region between F and G
Generally for any loading,
impedance terminates on
or varies from D to L

Two modern offset mho


relays can be used

+X

0.5
R

+R
Diameter = 1.0 pu
Offset =

Relay with 1.0 pu impedance


diameter detects LOF
condition from full load to
about 30% load
First relay is set with short
time delay; 0.1-second delay
suggested for security
against misoperation during
transients

Xd
2

2
Diameter = Xd
1

Second relay is set with time


delay; 0.5 to 0.6 seconds
provides protection for LOE
condition up to no load

0.5

Two offset mho relays


provide LOE protection for
any loading level

Both relays are set with


offset of Xd/2

+X

+R
Diameter = 1.0 pu
Offset =

Xd
2

2
Diameter = Xd
1

Experience has shown that these settings are secure over


a wide range of system conditions. However, transient
stability analysis should be performed to verify this.

MEL and LOF characteristic


are coordinated so they do
not overlap
MEL prevents leading var
excursions into the LOF
characteristic to avoid relay
misoperation for system
transients
Negative-offset mho element
characteristic leaves
underprotected area relative to
SSSL and stator end iron limit
curve of the machine capability

0.8

Generator
Capability

0.4

LOF MEL
Relay
SSSL

0.4

0.8

P
0

0.8

0.4

pu (MW)

1.2

Generator

GSU

G
Xd

Per Unit
Mvar

XT

System
Reactance
XS
Where
Xe=XT + XS
X
Xe

V2
2

1
Xe

1
Xd

V2
2

1_ + 1
Xe
Xd

Xd - Xe
2

R
Xd + Xe
2

Per Unit MW

MW - Mvar PER UNIT PLOT

R-X DIAGRAM PLOT

This scheme combines


positive-offset mho relay,
directional relay, and
undervoltage relay applied
at generator terminals and
set to look into machine 1.1 (X )

Z2 Setting

XS

Z1 Setting
R
Xd
Offset =
2

Machine
Capability

Directional unit supervises


mho unit because positiveoffset allows it to operate
for faults external to
generator terminals

MEL

SSSL

Improves coverage

IEEE TUTORIAL ON THE PROTECTION


OF SYNCHRONOUS GENERATORS

Copyright IEEE 2011

System Asymmetries

Open system circuits


Downed conductors
Stuck breaker poles or open switches

Unbalanced loads
Untransposed transmission lines
Single-phase GSU with unequal impedances

Unbalanced system faults

Strongest I2 source is generator phase-tophase fault

Generators connected with delta-wye


GSU transformer
System ground faults appear as phase-to-

phase faults to the generator


Generator ground faults typically do not create

as much I2

I2 in the stator creates a


magnetic field component
that rotates in opposite
direction of rotor and power
system (positive-sequence)
field component

As a result, double-frequency current is


induced in rotor

At twice fundamental frequency, skin


effect promotes current in rotor surface
areas and, to a smaller degree, in the
field winding

Beyond a point, the induced surface


currents can cause heating of metal
wedges that hold field windings and / or
retaining rings on rotor ends, causing them
to anneal, expand, and loosen with
catastrophic results

For salient-pole machines,


double-frequency currents
concentrate at pole faces
and teeth

Much current appears in


the pole-face amortisseur
windings

Continuous Unbalance Current Capability


Generator Type

Permissible I2 Stator
Rating Percent

Salient Pole
Connected Amortisseur Windings

10

Nonconnected Amortisseur Windings

Cylindrical Rotor
Indirectly Cooled

10

Directly Cooled
To 350 MVA

3511250 MVA

8 [(MVA-350)/300)]

12511600 MVA

Short-Time Unbalance Current Capability


Generator Type

K Permissible
I22 t (I2 in pu)

Salient Pole

40

Synchronous Condenser

30

Cylindrical Rotor
Indirectly Cooled

30

Directly Cooled
0800 MVA
8011600 MVA

10
See Graph (next slide)

I22 t Capability

I22 t = 10

I22 t = 10 [(0.00625)(MVA 800)]

Values shown in Tables I and II of this


chapter are for machines manufactured to
IEEE C50 standards since 2005

Equipment nameplate data and / or the


manufacturer may be consulted to verify
machine capabilities

Has limited I2 sensitivity of about 60% of


generator full-load rating
Generally insensitive to load unbalances or

open conductors
Limited protection as damaging heat can

occur even at low levels of I2

Allows backup protection for unbalanced


faults (high levels of I2)

Allows relay characteristics that can


match generator I2 capabilities

Allows I2 pickup settings down to 0.03 pu

Can be set to alarm at lower than


generator limits, allowing plant operator
to attempt to reduce I2 before trip occurs

Time (seconds)

1 103

100

K Setting
Adjustable Over
Range 240

10

40
Minimum
Pickup
0.04 pu

10
5
2

0.1
0.01

0.1
1
Negative-Sequence Current (per unit)

10

IEEE TUTORIAL ON THE PROTECTION


OF SYNCHRONOUS GENERATORS

Copyright IEEE 2011

Generator Type

Potential Damage

Diesel

Risk of Explosion

Gas Turbine

Gear Damage

Hydro

Blade Cavitation

Steam

Overheating

Generator Type

Typical Motoring Power

Diesel

5% - 25%

Gas Turbine

> 50%

Hydro

0.2 - 2%

Steam

0.5% - 3%

IEEE TUTORIAL ON THE PROTECTION


OF SYNCHRONOUS GENERATORS

Copyright IEEE 2011

The 78 protection scheme protects the


generator from OOS or pole-slip conditions

Common relay schemes for detecting


generator OOS events include:
Single blinder
Double blinder
Concentric circle

When a Generator Goes Out-of-Step (Synchronism)


with the Power System, High Levels of Transient
Shaft Torque are Developed.

If the Slip Frequency Approaches Natural Shaft


Frequency, Torque Produced can Break the Shaft.

High Stator Core End Iron Flux can Overheat and


Damage the Generator Stator Core.

GSU Subjected to High Transient Currents and


Mechanical Stresses.
171

172

One pair of blinders


(vertical lines)

Supervisory offset
mho

Mho limits reach of


scheme to swings
near the generator

Double
Lens
Scheme

Double
Blinder
Scheme

The most popular OOS


protection is the single
blinder scheme

Pickup area is restricted


to shaded area defined
by inner region of mho
circle and area between
Blinders A and B

Z3(t3)
Z0(t0)
Z2(t2)
Z1(t1)

Positive-sequence impedance must


originate outside either Blinder A or
Blinder B

It should swing through the pickup


area and progress to the opposing
blinder

Swing time should be greater than


time-delay setting

Angle (degrees)

Rotor Angle Generator G_1

Case 1 (tc = 90 ms), with controls

Case 2 (tc = 180 ms), with controls

Case 3 (tc = 190 ms), with controls

Case 1 (tc = 90 ms), without controls


Case 2 (tc = 180 ms), without controls
Case 3 (tc = 190 ms), without controls

Time (seconds)

R-X diagrams show trajectory followed by


impedance seen by relay during disturbance

When an oscillation in the generator is


stable, the point of impedance does not
cross the line of the system

When an OOS condition occurs, the point of


impedance crosses the line of the system
impedance each time the slip is completed

R-X Diagram for Case 1

X (ohm)

X (ohm)

R (ohm)

Case 1
Tc = 0.09 ms

R (ohm)

R (ohm)

Case 2
Tc = 0.18 ms

Case 3
Tc = 0.19 ms

Apply OOS if swing impedance passes


through GSU or generator

This zone is protected by differential relays


that do not respond to power swings

Consider application of OOS if swing


passes outside GSU but line protection is
blocked or does not respond to swings

IEEE TUTORIAL ON THE PROTECTION


OF SYNCHRONOUS GENERATORS

Copyright IEEE 2011

Common causes
Wiring failure
Open in VT draw-out assembly
Blown fuse due to short-circuit
Fuse left out after maintenance

Affected functions
21, 27, 32, 40, 50/27, 51V, 67N, 78, 81
Automatic voltage regulator (AVR runaway)

When fuse blows, unbalanced voltages created

Two sets of VTs required

Loss of One or Two Phases


Negative-sequence voltage

& no negative-sequence
current = fuse loss
Negative-sequence voltage

& negative-sequence current


= fault

Three-Phase Loss
Low three-phase voltages

& low three-phase current


& positive-sequence
current = fuse loss
Low three-phase voltages

& high three-phase


currents = fault

Wye-wye grounded VTs on ungrounded system

Mitigation
Line-to-line rated VTs
Broken-delta VTs
VT loading resistor

IEEE TUTORIAL ON THE PROTECTION


OF SYNCHRONOUS GENERATORS

Copyright IEEE 2011

Operating errors

Breaker head
flashovers

Control circuit
malfunctions

Combination
of above

Typically, normal generator relaying is not


adequate to detect inadvertent energizing

Generator behaves as induction motor

Flux induced into generator rotor causing


rapid rotor heating

Rotor current is forced into negativesequence path in rotor body

Unit
Step-Up
Transformer

Equivalent
High-Voltage
System

X1T

X1S

X1S = system positive-sequence


reactance
X1T = transformer positive-sequence
reactance
X2G = generator negative-sequence
reactance

Gen.

Gen.

X2G

R2G

EG

ET

ES
Equivalent
System
Voltage

EG = generator terminal voltage


ES = system voltage
ET = transformer high-side voltage
I = current
R2G = generator negative-sequence
resistance

Undervoltage (27) supervises low-set, instant overcurrent (50)


recommended 27 setting is 50% or lower of normal voltage

Pickup timer ensures generator is dead for fixed


time to ride through three-phase system faults

Dropout timer ensures that overcurrent element


gets a chance to trip if voltage is higher than
27 setting during event

Generator
Phase
Voltage
Fault Inception

Breaker Opens
Generator
Phase
Currents

IEEE TUTORIAL ON THE PROTECTION


OF SYNCHRONOUS GENERATORS

Copyright IEEE 2011

Large gas turbines are started as a motor using


static frequency converter

V/Hz is maintained constant until rated voltage is


reached, after which rated voltage is maintained

Extended operation occurs at low speeds while


purging and firing cycles are completed

Generator must be protected during low-frequency


operation

Some protection such as phase overcurrent and


phase unbalance is provided by converter controls

To be effective, multifunction generator relays


must maintain protection down to low frequencies

At lower frequencies, protective functions may


deviate from normal specifications

In some cases, protective functions may have to


be disabled during starting because of possible
false operation

Fault-to-ground on dc link cannot


be detected by converter controls

Fault causes dc current to flow


through any wye-connected VTs
and generator ground

DC current saturates magnetic elements (VTs and


distribution transformer in generator neutral)

Damage can occur if fault is not cleared PT can


be damaged in approximately 50 ms

Two strategies to address this fault include


Measure dc current in generator neutral (e.g., with

transducer) and use dc relay and turn converter off


before damage occurs
Eliminate any ground path through magnetic elements

during starting (use delta-connected VTs and disconnect


generator neutral while starting)

To avoid damage to generator or GSU unit, synchronizing


across breaker should be done within tight limits

Typical recommendations are


Electrical degrees 10
Voltage 0 to +5 percent

Frequency difference < 0.067 Hz

Synchronizing equipment or supervising relays should take


into account breaker closing time and relative slip, closing
breaker in advance so that angle between generator and
system at closing is as close to zero as possible

Generators may be operated at lower


frequency during startup and shutdown

Electromechanical relays can become


very insensitive at off nominal frequencies

Plunger-type overcurrent relays have flat


characteristics down to low frequencies
and are used to provide supplementary
protection during start up and shutdown
these relays cannot be energized
continuously and have to be disconnected
during normal operation
Microprocessor-based relays can provide
protection down to lower frequencies and
generally do not require supplementary
protection

Pickup in Multiples of 60 Hz Pickup

(B)

(C)

(D)

(E)

(D)
4

(B)
(C)

(A)

(E)

(A)
0

10

(F)
20

30

40
50
Frequency in Hz

60

70

(A)

Plunger-Type Current Relay

(B)

Induction Overcurrent Relay

(C)

Generator Differential Relay

(D)
(E)

Generator Ground Relay


Harmonic Restraint Transformer Differential Relay

(F)

Plunger-Type Voltage Relay

80

IEEE TUTORIAL ON THE PROTECTION


OF SYNCHRONOUS GENERATORS

Copyright IEEE 2011

Generator protection
functions with same
trip / shutdown modes
are grouped together

Operated by protective functions, auxiliary


lockout relays, 86G (usually hand-reset),
perform most tripping

Where possible, primary and backup


relays trip via separate paths / lockouts

Includes tripping of all


electrical and mechanical
power sources

Provides fastest way to


isolate generator

Does not shut down


prime mover

Used when abnormality


can be corrected quickly
allowing fast reconnection

Only trips
generator breaker(s)

Used when
disturbance is on
system and it is
desired to have
generator run its own
auxiliaries

Used to prevent overspeed when delayed


tripping of breakers is not detrimental
following a prime mover trip, planned or
unplanned, breakers are tripped after
reverse or low (hydro) power is detected

Not used for clearing faults

Much tripping philosophy depends on


ability of generating unit to continue
operating after disconnection from system
(full load rejection)

If unit cannot support its own auxiliaries,


then a tripping mode that transfers
auxiliaries should be incorporated

Table II provides suggested steam unit trip


logic by IEEE protective function numbers

Some functions are alarmed only

In general, G means generator and N


means neutral or ground

21 or 51V
24
32
40
46
50/27
50/51G
51TG2
50/51 UAT
59

59G
63
63UAT
67N
78
87G
87GN
87T
87T UAT
87O

51TG1 and 81 are


examples of functions
set to trip in unit
separation mode

Table III provides typical tripping for


hydroelectric units

Trip requirements are similar to thermal


generators but may need slightly
different slip / shutdown operations
Slower rotation devices
Different mechanical control devices

A generator disconnect
switch is often used
when tie to transmission
system is dual-breaker
arrangement

Sometimes generator protective


functions are enabled / disabled by
utilizing auxiliary switch contacts based
on position of disconnect switch

Be cautious about bad or incorrect


disconnect position status leaving
generator unprotected

You might also like