Professional Documents
Culture Documents
Hugo Monterrubio
Charles Mozina
Mukesh Nagpal
Brent Oxandale
Russell W. Patterson
Mike Reichard
Mohindar Sachdev
Kevin Stephan
Sudhir Thakur
Demetrios Tziouvaras
Joe Uchiyama
Quintin Verzosa, Jr.
Thomas Wiedman
Michael Wright
John Wang
Murty V. V. S. Yalla
Fundamentals
Out-of-Step Protection
Tripping Modes
Generator grounding
Generator stability
IEEE guidelines
Device numbers
Reactive Power
Into System
+
MVAR
Overexcited
Rotor
Winding
Limited
MW
System
MVAR
Normal Overexcited
Operation
Overexcitation
Limiter (OEL)
Stator
Winding
Limited
+ MW Real Power
Into System
Underexcitation
Limiter (UEL)
Underexcited
MVAR
Reactive Power
Into Generator
MW
Underexcited
Operation
G
Stator End
Iron Limited
Steady-State
Stability Limit
System
MVAR
kV 2 RC
MVA =
Z RV
kV 2 RC
Z=
MVA R V
Angle
Angle
Current
Current
Current
wattseconds
8000
wattseconds
6000
4000
Total
Generator
2000
0
0.01
System
0.1
1
time, seconds
10
Types of Instability
Steady-State
Transient
Dynamic
Pmax =
Pe =
Eg Es
X
sin g s
Power Flow
L1
L2
L3
Egg
Power
POWER
System
SYSTEM
L4
Ess
Eg Es
X
Generator
GSU
G
Xd
V
XS
Where:
XT
Xe = XT + XS
Per-Unit MVAR
V2
2
1
1
X
X
d
e
System
Reactance
X
Xe
V2
2
1
1
+
X
X
d
e
Xd Xe
2
Xd + Xe
2
Per-Unit MW
Ess
Power System
Three-Phase
Short Circuit
Substation
1
GSU
78 = Out-of-Step Protection
Es = System Voltage
Eg = Generator Voltage
s = System Voltage Phase Angle
g = Generator Voltage Phase Angle
78
G
Egg
Pmax =
Maximum
Power
Transfer
Eg Es
X
A2
PM = Pe
Pe =
A1
C
0
90
g s
180
Eg Es
X
sin g s
C37.102-2006
updated version now
available includes
significant changes
and additions
Device Number
Function
Tutorial Chapter
11
5.2
21
2.4
24
3.2
27TN
2.2
32
3.5
40
Loss-of-Field Protection
3.3
46
3.4
49
51G
2.2
51TG 1&2
Device Number
Function
Tutorial Chapter
51V
Voltage-Controlled or Voltage-Restrained
Time-Overcurrent Relay Backup for
System and Generator Phase Faults
2.4
59
Overvoltage Protection
3.2
59G
2.2
60
3.7
63
62B
2.5
64F
2.3
71
78
Loss-of-Synchronism Protection
3.6
Device Number
Function
Tutorial Chapter
81
3.1
86
5.1
87G
2.1
87N
2.2
87T
87U
2.2
63
Oil Low
71
87T
51
TG1
Unit
Transformer
51 Transformer Neutral
TG2
Overcurrent
87O
Unit
Differential
50
51
Second
V/Hz
24
2
UAT Backup
Voltage
Balance
60
UAT Fault
Pressure
63
UAT
Overvoltage 59
50/
27
Inadv. Energ.
(Note 4)
81
UAT Neutral
Overcurrent
51
Unit Auxiliary
Bus Phase Time
Overcurrent
78
Loss of
Synchronism
24
1
V/Hz
87T
UAT
Differential
40
Loss of
Field
Auxiliary VTs
32
Field
Breaker
51 51
TG1 TG2
Frequency
Reverse
Power
49
41
Stat.
Temp
64F
53
87G
Generator
Differential
Field (Note 1)
Ground
21/
51V
46
Negative
Sequence
59G
50/
51G
Generator
Neutral
Overvoltage
Generator
Neutral
Overcurrent
System
Backup
(Note 2)
27
TN
100 Percent
Stator Ground
(Note 3)
Notes:
1. Dotted devices optional.
2. Device 21 requires external timer. See Chapter 2.4.
3. See Chapter 2.2 regarding 100 percent ground protection.
4. Device 50 requires external timer. See Chapter 4.1.
Dual MGPSs
Inputs
Outputs
ROM
RAM
Voltage Inputs
EEPROM
Current Inputs
Data
Acquisition
System
User Interface
Microprocessor
Other Analog
Inputs
Targets
Digital
Outputs
Digital Inputs
One or More
Power Supplies
Communications
52
Generator Transformer
87AT
87T
Auxiliary Bus
52
87O
11G
MGPS #1
Relaying Functions
24
27/59
32-1
32-2
40
46
49
50
51V or 21
50/51G
59G
60
78
81
87G
27TH or 59THD or 64S
Field
11G
MGPS #2
Relaying Functions
24
27/59
32-1
32-2
40
46
49
50
51V or 21
50/51G
59G
60
64F
81
87G
27TH or 59THD or 64S
Saturation
Temperature variations
Winding connections
External faults
BUS
Low Resistance
Grounding
Systems
45MVA Generator
2000/5
2000/5 CTs
80%
2000/5
87
400 A
62
IA
IB
Residual current
calculated from
individual phase
currents. Paralleled
CTs shown to
illustrate principle.
90
IC
IG
IG
3I O
3 I0
180
IG
270
IA
IB
Residual current
calculated from
individual phase
currents. Paralleled
CTs shown to
illustrate principle.
90
IC
IG
IG
3I 0
180
IG
3I O 270
59G
59G
XHL
59G
Io
Co
CHL
Z0
VR := V0
Z
+
X
HL
0
Zero-Sequence
Network
XHL
R
3Io
VR
3R
Xo
V0
Rotor MMF
I3h A, B, C
Co
Terminal capacitance
+V3RD
Normal Operation
Neutral
No Load
Full Load
No Load
Terminal
Full Load
+V3RD
Full Load
No Load
Neutral
Terminal
Fault at Terminal
Neutral
No Load
Terminal
Full Load
V3RD
V3RD
Fault at Neutral
I3h
C0
3I3h
59G
27N3
I3h
C0
3I3h
59G
27N3
100%
59G
27N3
5%
0%
59G
27N3
Compares third-harmonic
voltage magnitude at the
generator neutral to that
at the generator terminals
Ferroresonance
damping resistor
59D
59G
100%
59G
~15%30% of winding
from neutral and
terminal by 59D
59D
59D
5%
0%
59G
59D
Is frequency independent
Injection Signal
20 Hz
Generator
Pickup
Setting
64S
Measurement Signal
20 Hz Filter
Measurement
Value
Tripping considerations
Field overcurrent
Field
Field
Breaker
Exciter
64F
DC
Voltage
Relay
Grounding
Brush
Ground #1
Ground #2
Field
Field
Breaker
Exciter
64F
DC
Use on generators
with brushes
Has variable
detection sensitivity
Voltage
Relay
Grounding
Brush
Field Breaker
Control
Positive
Varistor
R2
Generator
Generator
Field
+ Exciter
64F
Test
Pushbutton
(optional)
Field Breaker
Control
Voltage
Relay
R2
Negative
Field
+
Exciter
Field
Breaker
Brush
CR
C2
C1
AC
R
64F
98
V-C overcurrent
Current Level
F5
FLT
F4
F1
F3
F2
GCC
Zone 1
Zone 2
System
jX
30.0
Longest Line
(With Infeed)
75.5 Ohms
25.0
20.0
Zone 2
15.0
10.0
50-67% of GCC
@ RPFA
Shortest Line
(No Infeed)
RPFA
Zone
1
5.0
Transformer
High Side
5.0
GCC
MTA
5.0
10.0
5.0
10.0
15.0
R
20.0
Fault
Abnormal
condition
60
Frequency (Hz)
59
58
57
Generator tripping permitted on
or below curve without requiring
additional equivalent automatic
load shedding.
56
55
0.1
3.3
Time (s)
10
100
300
V%
106
94
96
104
102
98
100
104
102
f%
98
96
Possibility of frequency
operational limits exists for the generator
in the form of time-frequency characteristics
94
61
Restricted Time
Operating Frequency Limits
60
Continuous Operation
Prohibited
Operation
59
Restricted Time
Operating Frequency Limits
58
57
56
0.001
Prohibited
Operation
0.005
0.01
0.05
0.50
0.10
1.0
Time (Minutes)
5.0
10.0
50.0
100.0
60
Have manufacturer
approve protection
scheme
57
59
58
10-Minute
Maximum
56
55
54
1
10
100
1000
Total Accumulated Time Limit (Minutes)
Frequency (Hz)
additional heating
Overvoltage application:
Stresses stator insulation and connected components
Cannot be reliably detected using V/Hz alone
System problems
Unit load rejection: full load, partial rejection
Power system islanding during major disturbances
Transformers:
1.05 pu at rated load at 0.8 PF
1.1 pu at no load
V%
106
104
102
94
96
98
100
98
96
94
Copyright 2005 IEC, Geneva, Switzerland
102
104 f%
130
125
120
115
110
105
100
0.1
10
100
140
130
120
Individual manufacturers
should be consulted for limits
of a specific transformer.
110
0.01
0.1
1
Time (minutes)
10
100
V/Hz (%)
Reactive Power
Into System
Rotor
Winding
Limited
+
MVAR
MW
G
System
MVAR
Overexcited
Stator
Winding
Limited
+ MW
Real Power
Into System
MEL
Underexcited
MVAR
Reactive Power
Into Generator
MW
SSSL
Stator End
Iron Limited
System
G
MVAR
+X
0.5
R
+R
Diameter = 1.0 pu
Offset =
Xd
2
2
Diameter = Xd
1
0.5
+X
+R
Diameter = 1.0 pu
Offset =
Xd
2
2
Diameter = Xd
1
0.8
Generator
Capability
0.4
LOF MEL
Relay
SSSL
0.4
0.8
P
0
0.8
0.4
pu (MW)
1.2
Generator
GSU
G
Xd
Per Unit
Mvar
XT
System
Reactance
XS
Where
Xe=XT + XS
X
Xe
V2
2
1
Xe
1
Xd
V2
2
1_ + 1
Xe
Xd
Xd - Xe
2
R
Xd + Xe
2
Per Unit MW
Z2 Setting
XS
Z1 Setting
R
Xd
Offset =
2
Machine
Capability
MEL
SSSL
Improves coverage
System Asymmetries
Unbalanced loads
Untransposed transmission lines
Single-phase GSU with unequal impedances
as much I2
Permissible I2 Stator
Rating Percent
Salient Pole
Connected Amortisseur Windings
10
Cylindrical Rotor
Indirectly Cooled
10
Directly Cooled
To 350 MVA
3511250 MVA
8 [(MVA-350)/300)]
12511600 MVA
K Permissible
I22 t (I2 in pu)
Salient Pole
40
Synchronous Condenser
30
Cylindrical Rotor
Indirectly Cooled
30
Directly Cooled
0800 MVA
8011600 MVA
10
See Graph (next slide)
I22 t Capability
I22 t = 10
open conductors
Limited protection as damaging heat can
Time (seconds)
1 103
100
K Setting
Adjustable Over
Range 240
10
40
Minimum
Pickup
0.04 pu
10
5
2
0.1
0.01
0.1
1
Negative-Sequence Current (per unit)
10
Generator Type
Potential Damage
Diesel
Risk of Explosion
Gas Turbine
Gear Damage
Hydro
Blade Cavitation
Steam
Overheating
Generator Type
Diesel
5% - 25%
Gas Turbine
> 50%
Hydro
0.2 - 2%
Steam
0.5% - 3%
172
Supervisory offset
mho
Double
Lens
Scheme
Double
Blinder
Scheme
Z3(t3)
Z0(t0)
Z2(t2)
Z1(t1)
Angle (degrees)
Time (seconds)
X (ohm)
X (ohm)
R (ohm)
Case 1
Tc = 0.09 ms
R (ohm)
R (ohm)
Case 2
Tc = 0.18 ms
Case 3
Tc = 0.19 ms
Common causes
Wiring failure
Open in VT draw-out assembly
Blown fuse due to short-circuit
Fuse left out after maintenance
Affected functions
21, 27, 32, 40, 50/27, 51V, 67N, 78, 81
Automatic voltage regulator (AVR runaway)
& no negative-sequence
current = fuse loss
Negative-sequence voltage
Three-Phase Loss
Low three-phase voltages
Mitigation
Line-to-line rated VTs
Broken-delta VTs
VT loading resistor
Operating errors
Breaker head
flashovers
Control circuit
malfunctions
Combination
of above
Unit
Step-Up
Transformer
Equivalent
High-Voltage
System
X1T
X1S
Gen.
Gen.
X2G
R2G
EG
ET
ES
Equivalent
System
Voltage
Generator
Phase
Voltage
Fault Inception
Breaker Opens
Generator
Phase
Currents
(B)
(C)
(D)
(E)
(D)
4
(B)
(C)
(A)
(E)
(A)
0
10
(F)
20
30
40
50
Frequency in Hz
60
70
(A)
(B)
(C)
(D)
(E)
(F)
80
Generator protection
functions with same
trip / shutdown modes
are grouped together
Only trips
generator breaker(s)
Used when
disturbance is on
system and it is
desired to have
generator run its own
auxiliaries
21 or 51V
24
32
40
46
50/27
50/51G
51TG2
50/51 UAT
59
59G
63
63UAT
67N
78
87G
87GN
87T
87T UAT
87O
A generator disconnect
switch is often used
when tie to transmission
system is dual-breaker
arrangement