You are on page 1of 15

Transforming 3 Phase to 2 Phase

There are two main reasons for the need to transform from three phases to two phases,
1.
To give a supply to an existing two phase system from a three phase supply.
2.
To supply two phase furnace transformers from a three phase source.
Two-phase systems can have 3-wire, 4-wire, or 5-wire circuits. It is needed to be considering that a twophase system is not 2/3 of a three-phase system. Balanced three-wire, two-phase circuits have two phase
wires, both carrying approximately the same amount of current, with a neutral wire carrying 1.414 times
the currents in the phase wires. The phase-to-neutral voltages are 90 out of phase with each other.
Two phase 4-wire circuits are essentially just two ungrounded single-phase circuits that are electrically 90
out of phase with each other. Two phase 5-wire circuits have four phase wires plus a neutral; the four
phase wires are 90 out of phase with each other.

Scott-T Connection - 2 and 3 phase wire connection

The easiest way to transform three-phase voltages into two-phase voltages is with two conventional
single-phase transformers. The first transformer is connected phase-to-neutral on the primary (threephase) side and the second transformer is connected between the other two phases on the primary side.
The secondary windings of the two transformers are then connected to the two-phase circuit. The
phase-to-neutral primary voltage is 90 out of phase with the phase-to-phase primary voltage, producing a
two-phase voltage across the secondary windings. This simple connection, called the T connection, is
shown in Figure
The main advantage of the T connection is that it uses transformers with standard primary and secondary
voltages. The disadvantage of the T connection is that a balanced two-phase load still produces
unbalanced three-phase currents; i.e., the phase currents in the three-phase system do not have equal
magnitudes, their phase angles are not 120 apart, and there is a considerable amount of neutral current
that must be returned to the source.

The Scott Connection of Transformer


A Scott-T transformer (also called a Scott connection) is a type of circuit used to derive two-phase power
from a three-phase source or vice-versa. The Scott connection evenly distributes a balanced load between
the phases of the source.
Scott T Transformers require a three phase power input and provide two equal single phase outputs
called Main and Teaser. The Main and Teaser outputs are 90 degrees out of phase. The MAIN and the
Teaser outputs must not be connected in parallel or in series as it creates a vector current imbalance on
the primary side.
MAIN and Teaser outputs are on separate cores. An external jumper is also required to connect the
primary side of the MAIN and Teaser sections.
The schematic of a typical Scott T Transformer is shown below:

Typical Scott T Transformer schematic diagram

Scott T Transformer is built with two single phase transformers of equal power rating. The MAIN and
Teaser sections can be enclosed in a floor mount enclosure with MAIN on the bottom and Teaser on top
with a connecting jumper cable. They can also be placed side by side in separate enclosures.
Assuming the desired voltage is the same on the two and three phase sides, the Scott-T transformer
connection consists of a center-tapped 1:1 ratio main transformer, T1, and an 86.6% (0.53) ratio teaser
transformer, T2. The center-tapped side of T1 is connected between two of the phases on the three-phase
side. Its center tap then connects to one end of the lower turn count side of T2, the other end connects to
the remaining phase.
The other side of the transformers then connects directly to the two pairs of a two-phase four-wire
system.

Scott-T connection convert 3-phase to 2-phase

The Scott-T transformer connection may be also used in a back to back T to T arrangement for a threephase to 3 phase connection. This is a cost saving in the smaller kVA transformers due to the 2 coil T
connected to a secondary 2 coil T in-lieu of the traditional three-coil primary to three-coil secondary
transformer. In this arrangement the Neutral tap is part way up on the secondary teaser transformer .
The voltage stability of this T to T arrangement as compared to the traditional 3 coil primary to three-coil
secondary transformer is questioned.

Key Points
If the main transformer has a turns ratio of 1: 1, then the teaser transformer requires a turns ratio of
0.866: 1 for balanced operation. The principle of operation of the Scott connection can be most easily
seen by first applying a current to the teaser secondary windings, and then applying a current to the main
secondary winding, calculating the primary currents separately and superimposing the results.

Load connected between phaseY1 and phase Y2 of the secondary:

Secondary current from the teaser winding into phase X1 =1.0 <90
Secondary current from the teaser winding into phase X2 =-1.0< 90
Primary current from H3 phase into the teaser winding= 1.1547< 90
Primary current from H2 phase into the main winding= 0.5774 <90
Primary current from H1 phase into the main winding= -0.5774< 90
The reason that the primary current from H3 phase into the teaser winding is 1.1547 due to 0.866:
1 turns ratio of the teaser, transforming 1/0.866= 1.1547 times the secondary current. This current
must split in half at the center tap of the main primary winding because both halves of the main
primary winding are wound on the same core and the total ampere-turns of the main winding must
equal zero.

Load connected between phase X2 and phase X1 of the secondary:

Secondary current from the main winding into phase X2 =1.0< 0


Secondary current from the main winding into phase X4= -1.0 <0
Primary current from H2 phase into the main winding =1.0 <0
Primary current from H1 phase into the main winding=- 1.0 <0

Primary current from H3 phase into the teaser winding= 0


Superimpose the two sets of primary currents:
I H3= 1.1547 <90 +0= 1.1547 <90
I H2 =0.5774 <90 +1.0< 0= 1.1547 < 30
I H1 =0.5774 <90+ 1.0 <0=1.1547 <210
Notice that the primary three-phase currents are balanced; i.e., the phase currents have the same
magnitude and their phase angles are 120 apart. The apparent power supplied by the main
transformer is greater than the apparent power supplied by the teaser transformer. This is easily
verified by observing that the primary currents in both transformers have the same magnitude;
however, the primary voltage of the teaser transformer is only 86.6% as great as the primary
voltage of the main transformer.Therefore, the teaser transforms only 86.6% of the apparent
power transformed by the main.
We also observe that while the total real power delivered to the two phase load is equal to the
total real power supplied from the three-phase system, the total apparent power transformed by
both transformers is greater than the total apparent power delivered to the two-phase load.
The apparent power transformed by the teaser is 0.866 X IH1= 1.0 and the apparent power
transformed by the main is 1.0X IH2 =1.1547 for a total of 2.1547 of apparent power transformed.
The additional 0.1547 per unit of apparent power is due to parasitic reactive power owing
between the two halves of the primary winding in the main transformer.
Single-phase transformers used in the Scott connection are specialty items that are virtually
impossible to buy off the shelf nowadays. In an emergency, standard distribution transformers
can be used.

Advantages of the Scott T Connection


If desired, a three phase, two phase, or single phase load may be supplied simultaneously. The neutral
points can be available for grounding or loading purposes

Disadvantages when used for 3 Phase Loading


This type of asymmetrical connection (3 phases, 2 coils), reconstructs three phases from 2 windings. This
can cause unequal voltage drops in the windings, resulting in potentially unbalanced voltages to be
applied to the load.
The transformation ratio of the coils and the voltage obtained may be slightly unbalanced due to
manufacturing variances of the interconnected coils.
This designs neutral has to be solidly grounded. If it is not grounded solidly, the secondary voltages could
become unstable. Since this design will have a low impedance, special care will have to be taken on the
primary protection fault current capacity. This could be an issue if the system was designed for a DeltaStar connection.
The inherent single phase construction and characteristics of this connection produces a comparatively
bulky and heavier transformer when compared with a normal three phase transformer of the same rating.

Application
Main application is for For Industrial Furnace Transformer.
For Traction Purpose: The power is obtained from the 220 kV or 132 kV or 110 kV or 66 kV, three-phase,
effectively earthed transmission network of the State Electricity Board, through single-phase transformers
or Scott connected transformer installed at the Traction Substation. The primary winding of the singlephase transformer is connected to two phases of the transmission network or Where Scott-connected
transformer is used, the primary windings are connected to the three phases of the transmission network.
The single-phase transformers at a Traction Substation are connected to the same two phases of the
transmission network (referred as single-phase connection), or alternatively to different pairs of phasesthe three single phase transformers forming a delta-connection on the primary side. Out of three singlephase transformers, one transformer feeds the overhead equipment (OHE) on one side of the Traction
Substation, another feeds the OHE on the other side of the Traction Substation, and the third remains as
standby. Thus the two single-phase transformers which feed the OHE constitute an open-delta connection
(alternatively, referred as V-connection) on the three-phase transformers network.
The Scott-connected transformer and V-connected single-phase transformers are effective in reducing
voltage imbalance on the transmission network. The spacing between adjacent substations is normally
between 70 and 100 km.

Recommended EE articles //

Configurations and Characteristics Of Distribution Substations


APRIL 13, 2015

Maintenance of Load Tap Changers (LTCs)


MARCH 25, 2015

Do Not Energize Oil-Filled Transformer Without Performing These 15 Tests and


Checks!
FEBRUARY 23, 2015

Basic Transformer Routine Test Measurement of Winding Resistances


FEBRUARY 20, 2015

Do Not Energize Oil-Filled Transformer Without Performing These 15 Tests and Checks! (on photo 3-core type oil-immersed rectifier
transformer 380kV; via electric-power-transformers.com)

Obligatory Checklist
The following tests and checks should be performed at a minimum to ensure that the transformer is
ready to be energized. Do not energize the transformer without performing these tests and checks.
If any of below explained tests fail and transformer is energized anyway, it may lead to the serious hazard,
and thats not good
Thats not what we want.
Lets see these 15 tests

1. Insulating Fluid Test


Draw a fluid sample and test its dielectric strength. Dielectric strength of new fluid should be 26 kv or
greater.

The breakdown voltage indicates how well insulating oil can withstand an electrical load and is therefore decisive for the operational
efficiency of a transformer. The breakdown voltage is measured according to VDE 0370 part 5 (IEC 60156); photo credit: SIEMENS

2. Pressure Test
Check the transformer tank for leaks by pressurizing the tank with dry air or dry nitrogen through the
pressure test fitting to a pressure of 3 to 4 PSIG. let the tank stand under pressure for one to two hours,
then examine the tank and fittings for leaks. leaks above the fluid level can be detected by applying soap
solution to all welds, joints, pipe fittings, and cable connections.
Upon completion of this test, reduce the internal pressure to 1 or 2 PSIG.

Repairing transformer oil-tank for leakage (photo credit: khia.belzona.com)

3. Insulation Megger Test


Perform a 1000-volt Megger test and a power factor test to ensure that none of the windings is grounded.
See the complete procedure here.

Regular insulation testing is one of the most cost effective methods of identifying aging of transformer

4. Ratio Test
Perform a ratio test at each tap position to ensure that transformer coil ratios and tap changer connections
are correct. Read the complete procedure of transformer turns ratio test step by step .

5. Continuity Test and Resistance Test


Perform a continuity check on each winding. Measure the winding resistance of each winding and
compare results to factory test values.
An increase of more than 10% could indicate a loose internal connection.

6. Line Connections
In preparation for making line connections, check to make sure that all mating connector surfaces
are clean and smooth. Connections must be tightened appropriately to prevent overheating and possible
subsequent failure of the connection.
Connections to should be made with care to avoid placing undue stress on the bushings.

Oil-filled transformer bushings (photo credit: khia.belzona.com)

7. Tap Changer Setting


Check the tap changer setting to ensure it is set to the proper position for the required voltage. See an
example of transformer tap-changer correct adjustment .

On-Line Oil Filtration for Load Tap Changer Compartment (photo credit: velcon.com)

8. Delta/Wye and Series/Multiple Switch Settings


Check delta/wye and series/multiple switch settings to make sure they are set correctly.
If these connections are made using an internal terminal board, check to ensure that these connections
are made properly according to the chart on the transformer nameplate.

GE distribution transformer nameplate (photo credit: tucsontransformer.com)

9. Grounding
Check to ensure that the transformer tank is permanently and effectively grounded. The transformer
tank ground pad is located near the bottom of the tank.

10. Wiring
Check wiring of control and alarm circuits (if provided) to make sure there are no loose
connections and no damage to insulation.

Oil-filled transformer terminal box

11. Fluid level

Figure 1 Liquid Level Gauge

Check to make sure the fluid level as indicated by the fluid level gauge is as follows:
The fluid level gauge indicates the fluid level inside the tank. The transformer tank is filled with fluid at the
factory to the normal level at a reference temperature of 25C.

12. Tank Finish


Check all painted surfaces to make sure that there is no damage or corrosion.

13. Bolted Connections


Check all bolted connections for tightness.

Oil transformer bolted connections (photo credit: polywater.com)

14. Tools
Check to make sure that all tools and equipment are accounted for and have been removed from the
transformer.

15. Fluid Temperature


Read the fluid temperature gauge and make sure the temperature is no lower than minus 20C before
the unit is energized.

Figure 2 Liquid Temperature gauge

Reference: Installation, Operation, and Maintenance of Medium Power Substation Transformers


Howard Industries

Recommended EE articles //

Configurations and Characteristics Of Distribution Substations


APRIL 13, 2015

Maintenance of Load Tap Changers (LTCs)


MARCH 25, 2015

Basic Transformer Routine Test Measurement of Winding Resistances


FEBRUARY 20, 2015

4 Essential Features of Transformer On-Load Tap Changer (OLTC)


JANUARY 28, 2015

Share with engineers //


Article Tags //
fluid level, insulating fluid test, oil filled transformer, tap changer, transformer, transformer oil, transformer
tank,

Filed Under Category //

Testing and Commissioning Transformers

About Author //

Edvard Csanyi
Edvard - Electrical engineer, programmer and founder of EEP. Highly specialized for design of LV high
power busbar trunking (<6300A) in power substations, buildings and industry fascilities. Designing of
LV/MV switchgears. Professional in AutoCAD programming and web-design. Present on Google+

RSS Feed for Comments

15 Comments

1.
Nikolay
APR 25, 2015

Also need to check if:


- Radiator valves are open
- Cooling fan motors rotate in the correct direction
- There are no visible oil leaks
- Off-load tap changer handle has been locked
(reply)

2.
Deep
APR 14, 2015

I believe that there are other important test like core balance, short circuit etc
(reply)

3.
Mhmoud Refaat
APR 14, 2015

Many thanks
(reply)

4.
ASIM
APR 13, 2015

thank you Mr.Edvard ,, very nice one but i think there is other tests to be added here like the polarization
index and tan delta test.
(reply)

Older Comments
RSS Feed for Comments

Leave a Comment
Tell us what you're thinking... we care about your opinion!
and oh, not to forget - if you want a picture to show with your comment, go get a freeGravatar!
NAME *

EMAIL *

WEBSITE

WE BELIEVE YOU'RE AN ENGINEER, BUT NEVERTHELESS ... *


six
=5
SIGN ME UP FOR THE NEWSLETTER

Submit Comment

You might also like