HINDUSTAN ZINC LTD

1 X 80MW, ZAWAR CPP


ZAWAR MINES, RAJASTHAN
ABB LIMITED

SIZING CALCULATION FOR UPS

Doc Ref.No.
3VYN591602

Sheet 1 of 3

SIZING CALCULATION FOR UPS

OWNER:

MAIN
CONTRACTOR

e-BOP
CONTRACTOR:

HINDUSTAN ZINC LIMITED.


ZAWAR MINES, RAJASTHAN.

TATA PROJECTS LTD.


HYDERABAD.

ABB LIMITED.
FARIDABAD.

We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
ABB eBoP.

HINDUSTAN ZINC LTD


1 X 80MW, ZAWAR CPP
ZAWAR MINES, RAJASTHAN
ABB LIMITED

Doc Ref.No.
3VYN591602

SIZING CALCULATION FOR UPS

Sheet 2 of 3

REVISION STATUS SHEET

REV. NO.

R0

DATE

DESCRIPTION

10.07.2007

FOR REFERENCE ONLY

Rev. No.

Date

KK

AB

For Reference

R0

10.07.2007

Prepared by

Reviewed by

Remarks

We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
ABB eBoP.

HINDUSTAN ZINC LTD


1 X 80MW, ZAWAR CPP
ZAWAR MINES, RAJASTHAN
ABB LIMITED

3VYN591602

SIZING CALCULATION FOR UPS

Sheet 3 of 3

LOAD IN
REMARKS
kVA

FEEDER/LOAD DESCRIPITION

S.No.

Doc Ref.No.

A
1

BTG LOADS
SG/TG DCS

12

BOP DCS

6.5

HMI & MAXNET FOR UNIT # 1

10

6.5

MAX DNA BMS PANELS (SOLENOIDS)

4.0

LEVEL SWITCH

1.0

VMS

0.75

EWLI

1.20

COAL FLOW DETECTOR

0.60

10

ESP IOS

2.0

11

LIGHT OIL FLOW METER PD TYPE

0.2

12

SPARE FEEDERS

1.5

13

0.55

14

CONTROL PANEL (FOR TRANSDUCERS &


RECORDERS)
TSI MONITORING SYSTEM

15

VMS SYSTEM WORK STN & PRINTER

1.5

BOP LOADS

SWAS & GAS ANALYSERS

2.00

TOTAL KVA

50.55

LOADING FACTOR OF 25% AS PER CONTRACT


UPS RATING (STANDARD RATING)

63.18

Reference has been taken from


UPS sizing calculation of HZL,
Phase-I, Unit-1. Vide Doc. No:
TCE.4221A-EL-CAL-580-01, R1,
Dated 08-09-2004

Feeder Description not enlisted in


the TPL document. However, load
has been retained.

0.25

65 KVA

As per the standard rating.

CONCLUSION
Selected UPS Rating
Voltage Rating
No. of UPS per Unit
in line with HZL, phase-1 & 2.

:
:
:

65 kVA
110V AC
1 No., parallel redundant type