MONITORING RELAYS

These relays are best suitable for monitoring


balanced or unbalanced supplies, either of single
phase, 3-phase 3-wire or 3-phase 4 wire loads
powered by generators, UPS, stabilizers, inverters,
or Mains (by Electricity Boards / Utilities); in AMF
panels, PCCs, distribution boards and for power
monitoring of individual loads / motors / pumps.

MODELS
D1 VCR1, D1 VCR2
VCT D2, VCF D2, D2 VCT1, D1 VCT1,
S2 VMR 4, S2 VMR 5,
D2 EFR1, F3 EFR 1, OCS D1,
S2 CMR2, S2 CMR3, S2 CMR4,
OFS D1, S2 FMR1,
RPT D2, RPF D2, CBCT, CT

FEATURES

Fixed/adjustable under/Over trip


settings for parameters.
Fixed/adjustable trip delays and Power
On delays
Built-in or external power supply
Resetting Auto or Manual
Output contacts : 1 CO or 2 CO
Choice of enclosures (DIN-Rail, Flush)
Models with Micro-Controller based
design
Use of SMD Technology
User-friendly LED indications

PROTECTIONS / FUNCTIONS

Under/Over Voltage,
Under/Over Current
Under/Over Frequency
Reverse Power
Earth Fault/Ground Fault
Earth leakage

Ordering Instructions
Product Family Name
Model Name
System Supply Voltage
& frequency
Aux. Supply/Control
supply voltage
Current input (1A or 5A)
17

VOLTAGE MONITORING RELAYS


D1 VCR1

D1 VCR2

1 Phase Voltage
Monitoring Relay

Single Phase Under &


Over voltage, Auto Reset,
Adjustable under / over
voltage settings, 2 CO
output relay.

Note: Mention specific voltage


( Fixed/wide range ) in order

VCT D2

1 Phase Voltage
Monitoring Relay

VCF D2

Voltage Monitoring
Relay, 3-3W

Single Phase Under &


Over voltage,
Auto Reset,
Adjustable under/over
voltage settings,
2 CO output relay

Voltage Monitoring
Relay, 3-4W

3-Phase 3-Wire Under


& Over voltage
Auto/Manual Reset,
Adjustable under/over
voltage settings,
adjustable trip delay &
ON delay,
2 CO output relay

3-Phase 4-Wire Under


& Over voltage
Auto/Manual Reset,
Adjustable under/over
voltage settings,
adjustable trip delay &
ON delay,
2 CO output relay

System Supply

220/230/240 V AC (+20%-30%), 50/60 Hz 3%

Output Relay Contact


Trip Setting
Under Voltage

2 CO

2 CO

2 CO

75 - 95% [Variable] of set value

165 V to 225 V (in step of 15) (2%)

75% - 95% (adjustable)

75% - 95% (adjustable)

105 - 120% [Variable] of set value

230 V to 290 V (in step of 15) (2%)

105% -120% (adjustable)

105% -120% (adjustable)

2- 5 Sec (Fixed) (UV/OV)


Auto Reset
180 gms.

3.5 sec. (1.5 sec.)


3 min.( 20 sec)
Auto Reset
180 gms.

1-10 secs. (adjustable)


1-10 secs. (adjustable)
Auto / Manual
450 gms.

1-10 secs. (adjustable)


1-10 secs. (adjustable)
Auto / Manual
450 gms.

76 x 30.5 x 117.5
68 mm centre to centre / 35 mm rail
mounting

76 x 30.5 x 117.5
68 mm centre to centre / 35 mm rail
mounting

76 x 56.5 x 117.5
67 x 46
/ 35 mm rail
mounting

76 x 56.5 x 117.5
67 x 46
/ 35 mm rail
mounting

Over Voltage

Trip Time Delay


Power on Delay
Reset
Weight
Dimensions (mm)
Overall (L x W x D)
Mounting

Wherever not specified


Contact Rating :
5A @ 230 V AC
(resistive)

220/240 VAC,(+20%,-25%), 50/60 Hz3%

110/240/380/415/440 V AC +20%, 25%,50/60Hz


2 CO

OV SET
OV RESET
OV SET

3 Ph

OV RESET

1 Ph N

UV RESET

UV RESET

UV SET

UV SET
TD 2 to 5sec.

13

14

TD

Reset
DLY=
180 Sec.

15

Reset
DLY=
180 Sec.

13

14

16

17

13

15

16

18

TD

T on

2
P.ON
DLY= 180 Sec.

13

TD
1 to 10sec.

TRIP DLY
2 to 5Sec.

1 to 10sec.

L
O
A
D

N
OFF

L
O
A
D

L
N

OFF

ON

ON

L
O
A
D

R
Y
B

D1 VCR1
1

OFF

N/V

N/V

L
O
A
D

Y
B
N

OFF

D1 VCR2
1

N/V

D1 VCR1
7

13

14

15

ON

1 2 3 4 5 6

1 2 3 4 5 6

VCT D2

VCF D2

A/M
LINK

A/M
LINK

7 8 9 10 11 12

7 8 9 10 11 12

13 14 15

13 14 151617 18

Relay contact position shown in 'Power off' condition


18

13 14 151617 18

N/V

ON

VOLTAGE MONITORING RELAYS


D1 VCT1

D2 VCT1

Voltage Monitoring
Relay, 3-3W

S2 VMR4

Voltage Monitoring
Relay

3-Phase 3-Wire Under


& Over Voltage,
Auto reset,
Adjustable UV/OV
settings,
fixed trip delay,
2 CO output relay.

Voltage Monitoring
Relay, 3-4W

US

3-Phase 3-Wire and 3-Phase


4-Wire (selectable) Under & Over
voltage, Microcontroller based
design, Auto/Manual Reset,
Adjustable under/over voltage
settings, Absolute values for
UV/OV, adjustable trip delay &
ON delay, 2 CO output relay (or
selectable 1CO for UV, 1CO for OV)
Failsafe-non-failsafe selectable

100-120/220-240/380-440 V AC, 48-63Hz


2 CO

S2 VMR5

Voltage Monitoring
Relay, 3-3W

US

3-Phase 3-Wire Under & Over


voltage, Microcontroller based
design, SMD Technology
Auto/Manual Reset, Adjustable
under/over voltage settings,
Absolute values for UV/OV,
adjustable trip delay & ON delay, 2
CO output relay (or selectable 1CO
for UV, 1CO for OV)
Failsafe-non-failsafe selectable

US

3-Phase 4-Wire Under & Over


voltage, Microcontroller based
design, SMD Technology, Auto /
Manual Reset, Adjustable
under/over voltage settings,
Absolute values for UV/OV,
adjustable trip delay & ON delay,
2 CO output relay (or selectable
1CO for UV, 1CO for OV)
Failsafe-non-failsafe selectable

100-120/220-240/380-440V AC -25%+20%,48-63 Hz 100-120/220-240/380-440V AC -25%+20%,48-63 Hz 100-120/220-240/380-440V AC -25%+20%,48-63 Hz


1 CO + 1 CO / 2 CO
1 CO + 1 CO / 2 CO
1 CO + 1 CO / 2 CO
Ph Ph Setting:
For 380-440V AC
For 220-240V AC
For 100-120V AC
Ph N Sensing:
For 380-440V AC
For 220-240V AC
For 100-120V AC

75-115 Unit of 100-120 V AC


165-225 Unit of 220-240 V AC
285-425 Unit of 380-440 V AC

285-425V AC (Variable)
165-225V AC (Variable)
75-115V AC (Variable)
165-245V AC (Variable)
95-135V AC (Variable)
45-65V AC (Variable)

Ph Ph Sensing:
For 380-440V AC
For 220-240V AC
For 100-120V AC
Ph N Sensing:
For 380-440V AC
For 220-240V AC
For 100-120V AC

105-145 Unit of 100-120 V AC


230-290 Unit of 220-240 V AC
400-520 Unit of 380-440 V AC

3.51.5 Sec (UV/OV)


Auto Reset
200 gms. (Approx).
76 x 30.5 x 117.5
68 centre to centre / 35 mm rail
mounting

285 - 425V AC (Variable)


165-225V AC (Variable)
75-115V AC (Variable)
165-245V AC (Variable)
95-135V AC (Variable)
45-65V AC (Variable)
400-520V AC (Variable)
230-290V AC (Variable)
105-145V AC (Variable)

400-520V AC (Variable)
230-290V AC (Variable)
105-145V AC (Variable)
230-310V AC (Variable)
130-170V AC (Variable)
60-80V AC (Variable)

230-310V AC (Variable)
130-170V AC (Variable)
60-80V AC (Variable)

1-10 Sec (Variable) UV/OV/NF


1-10 Sec (Variable)
Auto/ Manual Reset
300 gms (Approx.)

1-10 Sec. (Variable)


1-10 Sec (Variable)
Auto / Manual Reset

1-10 Sec. (Variable)


1-10 Sec (Variable)
Auto / Manual Reset

110 gms (Approx.)

110 gms (Approx.)

76 X 56.5 X 117.5
67 x 46
/ 35 mm rail mounting

90 X 35 X 60
35 mm Rail Mounting

90 X 35 X 60
35 mm Rail Mounting

OV SET
OV SET

OV SET

OV SET

OV RESET
OV RESET

OV RESET

OV RESET

3 Ph

3 Ph N

3 Ph

3 Ph N

UV RESET

UV SET

13

13

UV SET

TD

14

13

14

16

17

15

13

15

16

18

L
O
A
D

TD
1 to 10sec.

T on

L
O
A
D
N

UV SET

TD
1 to 10sec.

TD

1 to 10sec.

UV RESET

UV RESET

UV RESET

TD
3.5 sec.

10

11

10

12

T on
1 to 10sec.

R
Y
B

UV SET

TD
1 to 10sec.

TD

L
O
A
D

10

11

10

12

TD

T on
1 to 10sec.

R
Y
B
N

L
O
A
D

3 or 4 Wire
selection link
OFF

DOL STARTER

D2 VCT1

Relay position shown in Power off condition


Note: S2 Series - RoHS Product available on request.

19

CURRENT MONITORING RELAYS


OCS D1

S2 CMR2

1 Phase Over Current Relay

1 Phase Current Monitoring Relay

Single phase over current Auto reset,


Input 1A or 5 A through CT,
Adjustable over current trip settings,
Adjustable trip delay,
1 CO output relay

Note: Mention specific voltage


( Fixed/wide range ) in order

Supply Voltage
System
Auxiliary
Ext. Input
Output contact

US

Single phase under & over current


Microcontroller based design, SMD technology,
Auto/Manual reset, Input 1A or 5 A through CT,
Adjustable under / over current trip settings,
adjustable trip delay & ON delay,
2 CO output relay (or selectable 1CO for UC,
1CO for OC)
Failsafe-non-failsafe mode selectable

110-120/220-240/380-440 V AC 20%,
12 V DC/24/30 V DC10%
1 Amp / 5 Amp (Secondary) CT or 250/500 mA
1 CO

100-120 / 220-240 / 415 V AC 20%,


24 V DC 10%
1 Amp / 5 Amp (Secondary) CT
1 CO + 1 CO / 2 CO

EF Trip Setting

Under Current

N.A.

10% - 100% (Variable) Of CT Sec.

50% -140% (adjustable) of CT sec

3.5 secs 1.5 sec (fixed)


1 - 10 secs (adjustable)
Auto
250 gms.

50% - 140% (Variable) Of CT Sec.


1-10 Sec. (Adjustable) 1 Sec.
1-10 Sec. (Adjustable) 1 Sec.
Auto / Manual
140 gms

76 x 30.5 x 117.5
68mm centre to centre / 35mm rail Mounting

90 X 35 X 60
35 mm Rail Mounting

Trip setting

Over Current
Power On Delay
Trip Time Delay
Resetting
Weight
Dimensions (mm)
Overall (L x W x D)
Mounting (L x W)

Wherever not specified


Contact Rating :
5A @ 230 V AC
(resistive)

Aux. Supply

Aux. Supply
OC SetPoint

OC SetPoint

OC Reset

OC Reset
UC Reset

UC SetPoint

Current Input

Current Input

T ON
2 to 5 sec.

Application
D2 EFR1, S2 CMR3, S2 CMR4
can be used for breaker tripping

T ON
1 to 10 sec.

Td 1 to 10 sec.

13

14

10

11

13

15

9 10

12

L
O
A
D

L
N

BUSBAR
TRIP COIL

BATTERY

TRIP COIL

N/V

C.B.

1 2

DOL STARTER

OCS D1

ON OFF

RELAY CONTACTS
C.T.

RELAY COIL

AUX.
SUPPLY
7

FAULT
A
CIRCUIT TO BE
PROTECTED

13 14 15

Interlocking circuit is required for shunt trip coil as shunt coil require pulse
only for tripping, incase of contineous power shunt coil burns.

20

Relay contact position shown in 'Power off' condition


Note: S2 Series - RoHS Product available on request.
CCS D2 Model Available on request.

AUTO
RESET

Td 1 to 10 sec.

L
O
A
D

GROUND FAULT MONITORING RELAYS


D2 EFR1

F3 EFR1

Earth Fault Relay

Earth Fault Relay

New

Earth fault/Ground fault


monitoring of 3 phase systems
Manual Reset, Input 1A or 5A
through CBCT, Adjustable earth
fault trip setting,
adjustable trip delay,
2 CO relay output

S2 CMR3

S2 CMR4

Ground Fault Relay

Earth Leakage Relay

Earth fault/Ground fault


monitoring of 3 phase systems
Manual Reset, Input 1A or 5A
through CBCT, Adjustable earth
fault trip setting,
adjustable trip delay,
2 CO relay output

24-30 VDC / 110-240 V AC / DC / 380-440 V AC 20% 24/30VDC10%,110/220/230/240VAC/DC 20%


380/415/440VAC 20%, 50Hz

US

Earth fault/Ground fault monitoring


of 3 phase systems, Microcontroller
based design, SMD technology,
Manual Reset, Input 1A or 5A
through CBCT, Adjustable earth
fault trip setting, Adjustable trip
delay & ON delay, 2 CO relay output
Failsafe-non-failsafe selectable

US

Earth leakage monitoring of 3


phase systems, Microcontroller
based design, SMD technology,
Manual Reset, Input through CBCT,
Adjustable trip setting,
Adjustable trip delay & ON delay,
2 CO relay output
Failsafe-non-failsafe selectable

100-120/220-240/415 V AC 20%, 48-63 Hz


100-120/220 -240 / 415 V AC / 24V DC 20%
1A or 5A (Selectable) CBCT Secondary
2 CO

100-120/220-240/415 V AC 20%, 48-63 Hz


100-110/240 / 415 V AC / 24V DC 20%
300mA CBCT Secondary
2 CO

1A or 5A (Selectable) CBCT Secondary


1 CO (2 CO) (Pick up on Fault)

5A or 1A (selectable) CBCT Secondary

10% - 100 % (adjustable) of CT sec

10% - 100 % (adjustable) of CT sec

10% - 100 % (adjustable) of CT sec

10% - 100 % (adjustable) of CT sec

N.A.

N.A.

N.A.

N.A.

N.A.
N.A.
0.1-1.0 / 1-10 Sec. (Adjustable)
Manual / Remote (Selectable)
550gms.

N.A.

N.A.

N.A.

N.A.
0.1-1.0 / 1-10 Sec. (Adjustable)
Manual / Remote (Selectable)
550gms.

1 -10 Sec.(Adjustable)
0.1 - 1 Sec.(Adjustable)
Manual
140 gms

1 -10 Sec.(Adjustable)
0.1 Sec to 1 Sec.(Adjustable)
Manual
140 gms

76 x 56.5 x 117.5
67 x 46
/ 35 mm rail Mounting

96 x 96 X 80 mm
92 X 92

90 X 35 X 60
35 mm Rail Mounting

90 X 35 X 60
35 mm Rail Mounting

1CO / (2CO)

In

Td
13

14

16

17

13

15

16

18

Td

CBCT (ZCT) With Secondary of 300 mA only

EXTERNAL
5 Amp. CT.

EXTERNAL
5 Amp. CT.

CBCT ( ZCT)

R
Y
B

N/V

L
O
A
D

L
O
A
D

R
Y
B

L
O
A
D
OFF

N/V

OFF ON

1 2 3 4 5 6

AUX.
SUPPLY
D2 EFR1

13 14 15 16 17 18

*Use either
3 x 5A Ext. CTs
or 3 x 1A Ext. CTs
or 1 x 5A (or 1A) CBCT

*Use either
3 x 5A Ext. CTs
or 3 x 1A Ext. CTs
or 1 x 5A (or 1A) CBCT

S2 CMR 4

7 8 9 10 11 12

Relay contact position shown in 'Power off' condition


Note: S2 Series - RoHS Product available on request.

21

ON

FREQUENCY MONITORING RELAYS


OFS D1

S2 FMR1

Over Frequency Relay

Frequency Monitoring Relay

Supply Voltage
System
Auxiliary
Ext. Input
Output contact
Trip setting

Note: Mention specific voltage


( Fixed/wide range ) in order

Under Frequency
Over Frequency
Reverse Power
Power On Delay
Trip Time Delay
Resetting
Weight
Dimensions (mm)
Overall (L x W x D)
Mounting (L x W)

Wherever not specified


Contact Rating :
5A @ 230 V AC
(resistive)

US

Single phase over frequency,


Auto reset,
Adjustable over frequency trip
settings,'
Adjustable trip delay,
1 CO output relay

Single phase under & over


frequency, Microcontroller based
design, SMD technology, Auto
reset, Adjustable under/over
frequency trip settings,
Adjustable trip delay & ON delay,
2 CO output relay Failsafe-nonfailsafe mode selectable

100-120 / 220-240 / 380-440 V AC 20%, 50Hz / 60 Hz


12 / 24 V DC or Built in
1 CO

100-120/220-240/380-440 V AC 20%, 38-72 Hz


In Built

1 CO + 1 CO / 2 CO

N.A.
50 Hz - 70 Hz

40 Hz - 60 Hz (Variable)
50 Hz - 70 Hz (Variable)

3.5 secs. 1.5 sec (fixed)


1 - 10 secs. (adjustable)
Auto
450 gms.

1 - 10 Sec.(Adjustable) 1 Sec.
1 - 10 Sec.(Adjustable) 1 Sec.
Auto / Manual
130 gms

76 x 30.5 x 117.5
68 centre to centre / 35 mm Rail Mounting

90 X 35 X 60
35 mm Rail Mounting

Aux. Supply

Aux. Supply
OF SetPoint

OF SetPoint

OF Reset

OF Reset
UF Reset

UF SetPoint
Freq. Input

Freq. Input

T ON
2 to 5 sec.

T ON
1 to 10 sec.

Td 1 to 10 sec.

13

14

8 10

11

13

15

9 10

12

AUTO
RESET

Td
1 to 10 sec.

L
O
A
D

L
N

OFF

L
O
A
D

ON

OFF

N/V
DOL STARTER

N/V
DOL STARTER

OFS D1

13

14

15

Relay contact position shown in 'Power off' condition

22

Note: S2 Series - RoHS Product available on request.

ON

POWER MONITORING RELAYS


RPT D2

RPF D2

Reverse Power Relay,(3-4W)

Reverse Power Relay,(3-3W)

3-phase 3-wire generators reverse


power monitoring
Auto/Manual reset,
Reverse power (current) trip settings
adjustable,
ON delay and trip delay adjustable,
2 CO output relay

Single phase or 3-phase 4-wire


generators reverse power monitoring
Auto/Manual reset,
Reverse power (current) trip settings
adjustable,
ON delay and trip delay adjustable,
2 CO output relay

100-120 / 220-240 / 380-440 V AC 20%


Built-in
5A CT Secondary & R,Y, B
2 CO

100-120 / 220-240 / 380-440 V AC 20%


Built-in
5A CT Secondary & B, Neutral
2 CO

2% - 20% (adjustable)
1 - 10 secs. (adjustable)
1 - 10 secs. (adjustable.)
Auto / Manual
460 gms.

2% - 20% (adjustable)
1 - 10 secs. (adjustable)
1 - 10 secs. (adjustable)
Auto / Manual
460 gms.

76 x 56.5 x 117.5
67 x 46
/ 35 mm Rail Mounting

76 x 56.5 x 117.5
67 x 46
/ 35 mm Rail Mounting

POWER
SOURCE

POWER
SOURCE

ASYN.
MOTOR

ASYN.
MOTOR

RPT D2 / RPF D2

3 Ph
Supply

RPT D2 / RPF D2

Forward Power

Increasing Foward Current

Reverse Power

Increasing Reverse Current

Recovery
Level
Current Tripping
Level

13

14 16

17

13

15 16

18

Td 1 to 10 sec.

T ON

1 to 10 sec.

ASYN.
MOTOR

LOAD

L
O
A
D

RPF D2
A/M
LINK

Relay contact position


shown in 'Power off' condition

23