phase-to-ground overcurrent
protection for AC systems.
MIC
Digital
Overcurrent Relay
Applications
■ AC feeders, motors, transformers, etc.
■ Overload protection
■ Rapid short circuit detection
Features
■ 4 inverse and 4 definite time curves
■ Settings with front panel switches
■ Line current metering and last trip data
■ Part of a modular system
■ Independent 4" modules
■ 1/4 standard 19" rack cases available
DESCRIPTION ■ 2 digit display and reset button
The MIC 1000 is a digital, micro- for the instantaneous unit), and a
processor-based overcurrent relay high drop-out to pick-up ratio
that provides nondirectional phase (<95%), along with the instanta-
to phase and phase to ground over- neous unit adjustment tap, allow
current protection. The relay’s optional coordination and reclosing,
overcurrent function can be inverse without compromising selectivity.
time, where four families of curves
are provided, or definite time with Operation of the instantaneous unit
four times offered, as well instanta- can be blocked for both phase to
neous operation with adjustable phase and phase to ground condi-
time delay. All of these features are tions. STANDARD
offered in a single relay.
FEATURES
Line current metering, both phase to CONSTRUCTION
phase and phase to ground, are Front accessible time delay micro-switches.
■ accurate and reliable, with low
provided with a meter. Faults are power consumption
time tagged and the most recent Time Unit
■ fixed rack, 1/3 case, 19" rack
fault and time are displayed. The following characteristics are included in
■ drawout, 1/4 case, 19" rack every relay:
■ LED starting lamps and system ■ BS 142 inverse
APPLICATIONS availability indicators ■ ANSI inverse
The MIC relay is applied on alternat- ■ shock proof, non-flammable, ■ very inverse
ing current circuits (feeders, motors, sealed plastic case, which permits ■ extremely inverse
transformers, etc.), and provides exterior reset of indicating LED’s ■ 2 sec definite time
effective protection against over- ■ anti-seismic waveform response ■ 4 sec definite time
loads, and rapid detection of short ■ high reliability solid-state ■ 6 sec definite time
circuits. components ■ 8 sec definite time
Negligible overtravel (less than 50 ■ microprocessor system (time dial adjustable from 0.05 to 1 in 0.05
ms for the time unit, less than 25 ms steps)
GE Power Management
197
MIC Digital Overcurrant Relay
SELECTION GUIDE
Phase or ground relays Phase and ground relays
The information required to provide a complete definition of a model The information required to provide a complete definition of a model
appears in the tables. It is recommended that the model designation is appears in the tables. It is recommended that the model designation is
accompanied with its characteristics. accompanied with its characteristics.