MiCOM P125, P126, P127 Series

Directional/Non-Directional Relays

MiCOM P125: MiCOM P126: Three Phase MiCOM P127: Directional/


Directional/Non Directional Overcurrent and Directional/ Non-Directional Overcurrent and
earth fault relay Non-Directional earth fault relay Directional/Non-Directional earth fault relay

Introduction • Residual overvoltage Monitoring


• Broken conductor • Circuit Breaker state monitoring
The MiCOM Directional/non-
• Circuit breaker failure • Circuit Breaker condition
Directional overcurrent Relays
monitoring
provide flexible and reliable Control
integration of protection, control, • Trip circuit supervision
• Multi shot autoreclose
monitoring and measurement Communications
• Blocking logic
functions.
• Circuit breaker control • A choice of protocols
Extensive functionality provides • Selective relay scheme logic • Front and rear communication
complete protection and control for ports
• Start contact
a wide range of overhead lines and
underground cables, from • Four Programmable AND logic Diagnostic
distribution to transmission voltage • P125 one setting group • Power-up diagnostic
levels, capacitors bank, generators • P126 P127 two setting groups • Continuous self monitoring
and transformer generator schemes. • Programmable relay outputs • Test facilities
Protection • Programmable optically isolated
User friendly interface
inputs
• Three phase Overcurrent • Back-lit liquid crystal display
• Directional/Non-Directional Measurement
• Programmable LED indications
phase overcurrent • Comprehensive measurement • Password protection
• Directional/Non-Directional values
earth fault • Active reactive three phase Software support
• Wattmetric/Ie cos ϕ earth fault power, three phase power factor • MiCOM S1 software for
• Undercurrent • Energy setting, measurements, faults,
alarms, events, disturbance
• Negative phase overcurrent • Instantaneous
records, monitoring and fault
• Cold load pick up Post fault analysis analysis.
• Thermal overload • Event and fault records
• Undervoltage • Disturbance records
• Overvoltage

2
Models Available and Functionalities
Functions ANSI code MiCOM MiCOM MiCOM
P125 P126 P127
Three phase overcurrent 50/51 •
Directional/non directional phase overcurrent 67/50/51 •
Thermal overload 49 • •
Undercurrent 37 • •
Negative phase sequence overcurrent 46 • •
Broken conductor detection • •
Directional/non Directional earth fault 67N/50N/51N • • •
Wattmetric earth fault protection (W or Ie cos) 32N/Ie cos • • •
Undervoltage 27 •
Overvoltage 59 •
Residual overvoltage 59N • • •
Auto-reclose (4 shots) 79 • •
Circuit breaker failure 50BF • •
Circuit breaker monitoring and control • •
Trip Circuit Supervision [TCS] • •
Blocking logic • • •
Cold load Pick up • •
Output relay latching 86 • • •
Selective relay scheme logic • •
Start contact • • •
Programmable AND logic • •
Setting group 1 2 2
Measurements • • •
Fault records • •
Event records • •
Disturbance records • •
Test facilities • • •
Diagnostic/self monitoring • • •
Network Communication • • •
RS232 front port • • •
Support software (MiCOM S1) • • •

Application The integration of many functions A comprehensive suite of


provides complete protection for a overcurrent protection provides an
The MiCOM P125 P126 and P127 wide range of overhead lines and economic solution to complex
relays are suitable for all underground cables, from applications.
applications where directional distribution to transmission voltage
overcurrent and directional earth levels. It is suitable for solid
fault protection is required. earthed, resistance earthed,
inductance earthed (Petersen coil)
isolated system.

3
Figure 1a shows the insertion of
MiCOM P126 for a generic
distribution underground line.
Figure 1b shows the MiCOM P127
applied to parallel feeders.
The MiCOM P125 P126 and P127
relays are also applicable in
generator and in generator
transformers schemes.
A range of communication P126
protocols allows connection with 50N 46 49
many external devices thus
51N 37 50BF
providing remote programming
67N 50 BC
control and extraction of
59N 51 79
information as supervision and
SCADA systems.

Protection and Control


functions
(P125 - P126 - P127) Figure 1a: Underground cable application

Three phase tripping with single


phase alarm display is provided
for overcurrent and directional
protection function.

Phase directional overcurrent


(P127)
Three independent stages are
available for directional/
non-directional overcurrent
protection.
Each stage may be selected as non-
directional or directional
(forward/backward).
All stages have definite time delayed
characteristics, the first stage may
also be independently set to one of
twelve IDMT available curves. Figure 1b: Feeder application
The IDMT stage has reset definite
and IDMT timer to reduce clearance Phase overcurrent (P126)
times where intermittent faults occur.
Three independent stages are Ith
The phase fault directional elements available for overcurrent protection.
Time

are internally polarised by


I>
quadrature phase-phase voltages, All stages have definite time t>

and will make a correct directional delayed characteristics, the first I<
I >> t >>

decision down to 0.5V with stage may also be independently I >>> t >>>

Vn = 57 – 130V or 2.0V with set to one of available IDMT curves.


Current
Vn = 220 – 480V. The first stage has reset definite
A synchronous polarising signal is timer and IDMT timer to reduce
maintained for 500ms over the clearance times where intermittent
delay time to 5s maximum, to faults occur.
ensure that the instantaneous and
time delayed overcurrent elements
operate correctly for close-up three
phase faults.

4
Earth Fault Directional Wattmetric Negative phase sequence
overcurrent (P125 - P126 - P127) overcurrent (P126 - P127)
(P125 - P126 - P127) Negative phase sequence overcurrent
The sensitive earth fault protection is
This protection operates from earth also suitable for Petersen Coil is also designed for broken conductor
earthed systems using wattmetric detection when earth fault protection
fault current directly measured using
protection. is not enabled or not sensitive enough
a separate CT. (eg. broken conductor on load side).
The sensitivity can be selected by Two stages are available the first has Instantaneous and time (definite or
ordering code. inverse time the second has definite IDMT) negative sequence
delayed characteristic. An Ie cos ϕ overcurrent setting stages is
The polarising voltage can be mode is available in alternative to Pe identical to the phase and earth
measured by vector sum of the wattmetric mode. overcurrent stages.
phase-neutral voltages or by direct The Pe threshold setting value is
input from a dedicated VT or from Thermal overload (P126 - P127)
automatically corrected by selecting
an open delta VT. the rated Ie current. Thermal overload protection is
suitable to protect transformer and
Three independent stages are Undercurrent (P126 - P127) cables for their particular thermal
available for directional/non- characteristic.
MiCOM P126 and P127 relays
directional earth fault protection. MiCOM P126 and P127 relays
provide undercurrent function.
All stages have definite time include thermal overload based on
This function allows typical thermal replica.
delayed characteristics, the first applications such as lost of load
stage may also be independently detection. Alarm and overload stages are fully
set to one of available ANSI/IEEE programmable to match each
and IEC IDMT curves. device requirement.

The IDMT stage has reset with Undervoltage (P127)


definite or IDMT timer. Two independent stages with
definite time elements are available.
Each earth directional stage Each stage can be configured in
measures the residual overvoltage AND or OR logic mode.
element, the earth fault current
Overvoltage (P127)
element and the angle between
residual voltage and earth fault Two independent stages with
current. Following is shown the definite time elements are available.
Each stage can be configured in
tripping zone. Broken conductor AND/OR logic mode.
Each one, when earth non-directional (P126 - P127)
Residual Overvoltage
stage, operates a standard The broken conductor protection (P125 - P126 - P127)
overcurrent element. detects unbalanced conditions caused An additional fourth residual over-
by broken conductors, mal- operation voltage stage protection is available
of single-phase switchgear or by for earth faults in isolated system or
single phasing conditions. backup for the fault on busbar side.
The neutral voltage can be
measured directly using a VT
RCA transformer or derived in according
angle to the insertion mode of the phase
Directional Overcurrent
voltage.
characteristic U
I Blocking logic
(P125 - P126 - P127)
When MiCOM P125 P126 P127
Forward relays are used in critical networks,
tripping zone management of protections must
take care of surrounding devices.
Two blocking logic inputs can be
configured independently from each
other to lock any combination of the
selected elements (eg. current
elements, thermal overload, etc.)
Tripping zone is settable from:
+/-10˚ to +/-170˚ step 1˚ with reference Each blocking signal freezes its
to Torque angle (characteristic angle) associated memory (timer or
Torque angle is settable form 0˚ to 359˚ step 1˚ thermal state) after drop off, it
restart from the pre-blocking value
and status if conditions are still
Figure 2: Directional Characteristic present.

5
Selective relay scheme logic Programmable inputs and Monitoring and
(P126 - P127) outputs (P125 - P126 - P127) Measurement
P126 and P127 relay include MiCOM P125 P126 and P127
Circuit Breaker monitoring
selective relay scheme logic. include up to 7 digital inputs and 8
(P126 - P127)
outputs relays + 1 watch dog relay.
A dedicated digital input can Preventive circuit breaker
temporarily alter the time delay Two of eight output relays are maintenance is the advance
settings in response to a change over type. function provided by the MiCOM
downstream relay phase/earth fault Change over output type is typically P126 and P127 with adjustable
start condition. used for tripping commands. closing and opening time
measurements and breaker failure
This function allows the MiCOM Protection and control elements can protection.
relays to discriminate correctly easily be assigned to any output.
All phase currents I and I2 during
when used in a cascade scheme. All inputs and outputs are freely faults are memorised and summed.
The selective relay scheme logic configurable.
Trip Circuit Supervision [TCS]
function can be enabled or (P126 - P127)
Latching of the outputs relay
disabled by the user as required.
(P125 - P126 - P127) MiCOM P126 and P127 relays
Cold load pick up allow trip circuit supervision via a
Any of output relays can be
(P126 - P127) specific input. Result of this
latched.
monitoring can be locally or
Cold load pick-up temporarily raises Reset of all outputs is possible by remotely transmitted.
the phase overcurrent, earth logic input, a push button on front
Measurements
overcurrent, thermal status, negative HMI or through the local area
sequence overcurrent settings network. MiCOM P125, P126 and P127
following closure of the circuit relays monitor permanently all of
Circuit breaker failure the analogue inputs (voltage and
breaker, allowing the protection
protection (P126 - P127) current), display the values on the
settings to be set closer to the load LCD and store the measurements in
profile, to avoid untimely trips. Circuit breaker failure protection memory.
may be used for tripping upstream
The measured values are the true
circuit breakers.
400 RMS up to the 10th harmonic with
Autoreclose (P126 - P127) a 0.1% accuracy (nominal
conditions).
Current (% of nominal)

300 It provides three pole up to four -


Peak demands with a 15 minute
shots autoreclose, co-ordination with
window are also memorised.
200 fuse in rural lines, co-ordination of
CBs in cascade. All measured and calculated values
Nominal threshold can be displayed on the HMI or
100 The user may select which transferred locally or remotely upon
protection elements and/or a digital user request.
input may start any of four shots
0 1 2 3 4 5 6 Time (s) independently. Event records (P126 - P127)

Each shot has independently 75 logic events are stored in


MiCOM P126 and P127 relays.
Setting groups (P126 - P127) settable dead and reclaim time.
A counter stores the number of Events include inputs/outputs,
External conditions may request the reclose commands incremented with change of status, alarms and
need for different settings. each reclose order. contact operations.
MiCOM P126 and P127 relays All events are time stamped to 1ms.
provide two setting groups, G1 and Disturbance records
G2 including all the protection, (P126 - P127)
automation features and monitoring
functions. Voltage and current waveforms are
captured by MiCOM P126 and
The switching between group 1 and P127 relays.
group 2 can be achieved locally, Up to 5 records of 3 seconds are
remotely, via a dedicated logic input. stored inside MiCOM relays.
All settings are stored in E2PROM Disturbance recording function is
triggered either by any of the
(non-volatile rewriting memory)
programmed thresholds or by an
external input or through the local
area network.

6
Fault records (P126 - P127) Programmable LEDs Hardware
The last 5 faults are stored inside 4 freely programmable LEDs are MiCOM P125, P126 and P127
the MiCOM relays. provided on all models of the models are numerical protection
MiCOM P125 P126 and P127 and control relays.
Each fault includes: relays.
Record number The user can assign independently Case
• Fault time to each LED any program function For all directional models MiCOM
or combination of thresholds. P125, P126, P127 the unit have a
• Active setting group
draw out metal 4U case high.
• Faulted phase Keypad
The width is:
• Protection operation A seven button tactile keypad on
the front panel allows the user easy P125 20TE
• Magnitude access to any data in the MiCOM
P126 and P127 30TE
Fault indicator helps the user to P125 range relays.
identify clearly the fault and to All CTs inputs are short-circuited if
monitor the MiCOM P126 and Local and Remote the active unit is withdrawn from the
P127 relay settings. case.
Communication
All MiCOM relays can be panel or
User Interface Two communication ports are rack mounted.
available; a rear port providing
Front display and menus remote communication and a front Battery Box
port providing local communication.
All functions including protection, MICOM P125, P126 and P127
automation, communication, LEDs, Remote communication relays can also be powered by
inputs and outputs can be external battery.
programmed and modified using The remote communications are
the front panel user interface. based on RS485 voltage levels. The battery is allocated in a small
case as in figure below. When the
This port is available for MODBUS,
relay is out of its case or when the
Courier, IEC 60870-5-103 and
auxiliary power supply is failing,
DNP3.0 protocols.
the battery box ensures temporary
MiCOM relays can transmit to the supply to the relay thus to read or
local monitoring system (eg. modify internal data by front panel
MiCOM S10) or remotely to the or by interface program MiCOM S1.
SCADA settings, measurements,
alarms, fault events, and The battery type is:
disturbance records. Lithium 1/2AA,
Voltage: 3.7V
The communication parameters Capacity: 850mAh
(relay address, data rate, parity, Warranty: 10 years.
etc.) can be programmed using the
HMI front port.
The 32 alphanumeric back-lit LCD Local communications
(available in a range of languages)
provides the user with key The front serial communications port
information (faults, measurements, has been designed for use with
settings etc) MiCOM S1, which fully supports
functions within the relay by
The menus have a pull-down providing the ability to programme
structure for easy use and quick the setting off-line, extract and view
access to any data. event, disturbance and perform Wiring
Dedicated LEDs control functions.
External connections are made via
Four LEDs indicate the status of the The MiCOM S1 software interface MIDOS type terminal blocks.
MiCOM relays (trip order, alarms, will be full Windows™ last version
compatible. Each connection includes
power on, watchdog)
2 x 4.8mm Faston and one
Acknowledgment of alarm and trip Diagnostic M4 screw fixing.
LEDs can be easily performed
The wiring for all the MiCOM
locally or remotely. Automatic tests performed including
P125, P126 and P127 are
power-on diagnostic and continuous
self-monitoring ensure a high standard to provide maximum
degree of reliability. compatibility.

7
A

35
C B Watch Dog
Phase rotation ~/+ 33 WD 37
36
Auxiliary Voltage 4
A B C Programmable tripping output
~/- 34 RL1 6
2
10
Trip dire ction

P1 55 RL2 12
Programmable output
S1 8
1A 14
56 32N 50N 51N RL Programmable output
16
47 18
59N
RL4 Programmable output
5A 67N 20
48 3
RL5 Programmable output
1
7
RL6 Programmable output
5

22

MiCOM
A da
Programmable input L1
24
26
Programmable input L2

P125
B 28
17
Programmable input L3
19
21
C 39 Programmable input L4
23

N dn 40

Caseearth
connection
29
Terminal
30
RS485
31
+ RS485
Communication Port
32

Figure 3: P125 Wiring Diagram

8
A

C B
Phase rotation
35
A B C 37
~/+ 33 WD
36
Auxiliary Voltage 4
~/- 34
P1 RL1 6
49 2
S1 10
1A 50 51 32N
50 RL2 12
P1 51 8
14
S1 51N RL
1A 67N 50N 16
52 18
53 RL4
P1 20
37 46 49
S1 3
1A RL5
1
54
79 BC
Trip dire ction

59N 7
55 RL6
P1 5
S1 9
1A 50BF TCS RL7
56 11
13
41 RL8
15
5A 22
42
24 Programmable input L1
43
26
5A Programmable input L2
44 28
17
45
Programmable input L3
19
5A 21
46
Programmable input L4

MiCOM
23
47
25
5A Programmable input L5
27
48

P126
58
Programmable input L6
A da 60
57
Programmable input L7
59

B
Case earth
connection
29
Terminal
30
C 73 RS485
31
+ RS485
N dn 74 Communication
32

Figure 4: P126 Wiring Diagram

9
A

C B 35
Phase rotation
37
~/+ 33 WD
36
A B C Auxiliary Voltage 4
~/- 34
RL1 6
P1 49 2
S1 10
1A
50
50 51 67 RL2 12
P1 51 8
14
S1 RL
1A 32N 50N 51N 16
52 18
53 RL4
P1 20
S1
67N 37 46
3
1A RL5
1
Trip dire ction

54
49 79 BC 7
55 RL6
P1 5
S1
9
1A 50BF TCS RL7
56 11
41 13
RL8
15
5A 59 59N 27
22
42
43 24
Programmable input L1
26
5A Programmable input L2
44 28
45 17
Programmable input L3
19
5A 21
46
Programmable input L4

MiCOM
47 23
25
5A Programmable input L5
27
48

P127
58
A a Programmable input L6
69 60
57
Programmable input L7
70 59

B b 71
Case earth
connection
72 29
Terminal
30
C c 73 RS485
31
+
N n 74
RS485
C
32

Internal reconstruction voltageUe

Two phase-neutral plus Open Delta Two phase to phase plus


connection Open Delta connection
A B C A B C
A da a 69
A da a 69

70
70
B b 71
B b 71

72
n 72
C c
C 73

N dn n
N dn 74

73
Internal reconstruction voltage UC
74

Internal reconstruction voltage UCA

Figure 5: P127 Wiring Diagram

10
Technical Specifications CT requirement Directional/non Directional
overcurrent and
• Phase inputs Typical 5VA 5P10
Inputs Directional/non Directional
• Earth inputs earth fault time setting:
• AC phase current 1A and 5A
Core balanced CT or residual
• AC earth current 1A and 5A • Definite time:
connection to phase CTs
• AC phase and residual voltage 0 ms to 150s step 0.01s
from 57V to 130V VT requirement • IDMT curves:
from 220V to 480V IEC type:
• Phase input
• Frequency50/60Hz Typical Protection VT Short time inverse (IEC)
• Auxiliary Voltage Vaux Residual voltage input Standard inverse (IEC)
24V – 60V Very inverse (IEC)
Typical protection VT
48V – 150V Extremely inverse (IEC)
or Open Delta transducer
110V – 250V dc/ Long time inverse (IEC)
110 – 250V ac HMI • IEEE/ANSI type:
Burdens • Display : Short time inverse (CO2)
Moderately inverse (ANSI)
• AC current 2 x 16 alphanumeric characters
Inverse (CO8)
Phase < 0.025VA (1A) back-lit LCD
Very inverse (ANSI)
< 0.3VA (5A) LED : 8 including 4 Extremely inverse (ANSI)
Earth< 0.008VA at 0.1Ie (1A) programmable
• Electromechanical type RI:
< 0.01VA at 0.1Ie (5A) keyboard: 7 sensitive keypad
K curve coefficient from
• AC voltage • Serial port: 0,1to 10? step 0.001
Vn 57 – 130V < 0,25 VA RS232 for setting software • Time multiplier setting (TMS):
Vn 220 – 480V < 0,36 VA 0.025 to 1.5 step 0.025
Directional/Non-Directional
• DC auxiliary voltage • Reset time (1st threshold):
phase Overcurrent settings:
3W standby +0.25 per IDMT curves:
energised relay Current from 0.1 to 40 In, step 0.01In Short time inverse (CO2)
• Optical isolated input Three thresholds Moderately inverse (ANSI)
10mA per input • Torque (Char) Angle Inverse (CO8)
Thermal withstand from 0° to 359° step 1° Very inverse (ANSI)
• Trip zone Extremely inverse (ANSI)
• AC current inputs:
from ±10° to ±170° step 1°. Definite time:
1s @ 100 x rated current
0 to 100s step 0.01s
2s @ 40 x rated current • IDMT Curves / Definite time.
continuous @ 4 x rated current Earth fault Wattmetric
• AC voltage input: Directional/Non-Directional thresholds Pe/Ie cos
earth fault settings:
range: 57 to 130V Pe> and Pe>> thresholds ranges value
10s @ 300 ph-ph eff. Three current input ranges selected • V input 57–130V,
Continuos @ 260 ph-ph eff. by ordering code (Cortec). Three Ie input: 0.002 to 1Ien
range: 220 to 480V current thresholds for each range: from 0.2 to 20 W step 0.02 W
10s @ 1300 ph-ph eff. • (range A): from 0.1 to 40 Ien, • V input 220–480V,
Continuos @ 960 ph-ph eff. step 0.01 Ien Ie input: 0.002 to 1 Ien
Accuracy • (range B): from 0.01 to 8 Ien from 1 to 80 W step 0.1 W
• Current thresholds step 0.005 Ien • V input 57–130V
+/- 2% • (range C): from 0.002 to 1 Ien Ie input: 0.01 to 8 Ien
• Definite Time delay step 0.001 Ien from 1 to 160 W step 0.1 W
+/- 2% + 30 ... 50 ms Torque (Char): • V input 220–480V
• Inverse Time delay Angle from 0 to 359° step 1° Ie input: 0.01 to 8 Ien
from 4 to 640 W step 0.5W
+/- 5% + 30 ... 50 ms Trip zone: ±10 to ±170° step 1°
• V input 57–130V
• Voltage thresholds Voltage input range 57 – 130V :
+/- 2%
Ie input: 0.1 to 40 Ien
thresholds range from from 10 to 800 W step 1W
• Time delay 1V to 260 V, step 0.1V
+/- 2% + 20 ... 40 ms • V input 220–480V
Voltage input range 220 – 480V : Ie input: 0.1 to 40 Ien
• Measurements:
thresholds range from from 40 to 3200 W step 5 W
Current typical+/- 0.5% at In
Voltage typical +/- 0.5% at Un 4V to 960 V, step 0.5V
Angle ≤ 3° Time setting: IDMT Curves/Definite time.

11
Pe>Definite time or IDMT • Voltage input range 220 – 480V: Circuit Breaker control
• IDMT curve identical to phase thresholds range • Trip time
overcurrent Definite time: from 10V to 960V step 0.5V from 0.1 to 5s step 0.1s
from 0 to 150s step 0.01 • Definite time: • Closing time
• All wattmetric ranges are from 0 to 600s step 0.01s from 0.1 to 5s step 0.1s
multiplied by K; Zero Sequence Voltage Contacts
K=1 when Ien=1A; thresholds:
K=5 when Ien=5A • Rating
• Voltage input range 57 – 130V: Make: 30 Amps and carry for 0.2s
IeCos thresholds threshold range Carry: 5 Amps continuous
from 1 to 260V step 0.1V Break: 135 Vdc, 0.3(L/R=30ms)
• IeCos> and IeCos>> have the
same ranges of Ie thresholds • Voltage input range 220 – 480V: 220 Vac, 5A (P.F. = 0.6)
threshold range • Mechanical durability
• IeCos>: Definite time or IDMT
from 5 to 960V step 0.5V >100000 operations
• IDMTcurve identical to phase
• Definite time :
overcurrent; Definite delay time Housing
from 0 to 600s step 0.01 s
from 0 to 150s step 0.01
• Case: High: 4U (177mm)
Cold load Pick Up
Pe/Iecos characteristic angle: MiCOM P125 20 TE,
• form 100% to 500% MiCOM P126 30 TE,
Settable from 0° to 359° step 1°
• Definite time MiCOM P127 30 TE
Under current thresholds from 0.1 to 3600s step 0.1 s • Weight:
• from 0.1 to 1 In step 0.01 In P125 c. 3.0 Kg, P126c. 4.0 Kg,
Auto reclose (79)
• Definite time 0 to 150s step 0.01s P127 c. 4.2 Kg
• 4 shots, dead, reclaim and • Mounting:
Negative sequence current inhibit time Rack or flush mounting
thresholds: • Block from external CB fail input • Connections:
• Three thresholds with range • Ext.CB fail time Rear, (double faston +
from 0.1 to 40 x In step 0.01 In from 0.01 to 600s step 0.01 s M4 screw per connection)
I2> Definite time or IDMT • tD1, tD2 Full draw-out with automatic
from 0.01 to 300s step 0.01 s CT shorting
• IDMT curve identical to phase
overcurrent; • tD3, tD4 • Protection:
from 0.01 to 600s step 0.01 s IEC 529; IP 52, IK 07
• Definite time:
from 0 to 150s step 0.01s. • tR, tI High voltage withstand
from 0.02 to 600s step 0.01 s
Broken Conductor: • Dielectric withstand (50/60Hz)
Ratio I2/I1 from 20 to 100% AND logical gates IEC 60255-5
• 4 “AND” logical gates 2 kV in common mode
Definite time from 0 to 14400s step 1s 1 kV in differential mode
• Pick-up time delay
Thermal replica thresholds: • Impulse voltage
from 0 to 3600 s step 0.1 s
• Threshold from 0.1 to 3.2 In, IEC 60255-5
• Reset time 5 kV in common mode
from 50 to 200%,
from 0 to 3600 s in steps of 0.1 s 1 kV in differential mode
• Thermal constant from 1 to 200 min,
delay time 0 to 150s. Auxiliary timers • Insulation resistance
IEC 60255-5 > 1000 MΩ
Under voltage thresholds: • Two auxiliary timers
• Setting time: Electrical environment
• Voltage input range 57 – 130V
from 0 to 200 s step 0.01s • High frequency disturbance
• thresholds range:
IEC 61000-4-1
from 2V to 130V step 0.1V Circuit breaker control (50BF) 2.5 kV in common mode, class 3
• Voltage input range • t_BF from 0 to 10 s step 0.01 s 1 kV in differential mode, class 3
220 – 480V :
Trip Circuit Supervision • Fast transient disturbance
• thresholds range: IEC 61000-4-4 4 kV auxiliary
from 10V to 480V step 0.5V • CB Sup. time supply, class 4
• Definite time from 0.1 to 10 s step 0.01s ANSI C37.90.1
from 0 to 600s step 0.01s • CB open sup. time 2 kV other, class 4
from 0.05 to 1s step 0.01s • Electrostatic discharge
Over voltage thresholds:
• CB close sup. time IEC 61000-4-2 8 kV, class 4
• Voltage input range 57 – 130V: from 0.05 to 1s step 0.01s • Radio frequency impulse
• thresholds range • CB trip operations ANSI C37.90.2 35 V/m
from 2V to 260V step 0.1V from 0 to 50000 step 1 IEC 61000-4-3 10 V/m

12
Environmental withstand • Tripping curves type IEC (short The relay provides complete
• Temperature time inverse, standard inverse, measurements and recording
IEC 60255-6 very inverse, extremely inverse, functions including
long time inverse) and
Storing and transportation • True RMS values
IEEE/ANSI (short time inverse,
-25°C to +70°C • Event recorder with the
moderately inverse, inverse,
Operation -10°C to + 55°C very inverse, extremely inverse) Last 75 events,
• Humidity IEC 60068-2-3 • 3 Negative phase sequence 1ms time stamped.
56 days at 93% RH and 40°C overcurrent thresholds - 46 • Fault recorder with the
• Enclosure protection • Undercurrent - 37 last 5 faults
IEC 60529 IP 52, IK 07 • Disturbance recorder with
• 2 Thermal overload
• Vibration thresholds - 49 storage of 5 records for
IEC 60255-21-1 3 seconds each
• 2 Phase Overvoltage
Response and endurance, class 2 User interface shall include
thresholds - 59
• Shock and bump
• 2 Phase Undervoltage • A 32 characters backlit display
IEC 60255-21-11
thresholds - 27 • Programmable LEDs
Response and withstand, class 1
• 1 Residual Overvoltage – • A front panel RS232 for
• Seismic thresholds - 59N
IEC 60255-21-3, Class 1 local settings
• Output relay latching - 86 • A RS485 rear port compatible
EMC compliance • Broken conductor detection with MODBUS, Courier or
• 4 shot auto-recloser - 79 IEC60870-5-103, DNP3
89/336/EEC, • Circuit breaker failure • An easy to use PC setting
93/31/EEC, detection 50 BF software.
93/68/EEC • Circuit breaker monitoring
Compliance with European • Trip circuit supervision
Commission EMC Directive.
Generic standards were used to Ordering Code X X
establish conformity:
EN50081-2: 1994 MiCOM P 1 2 5
MiCOM P 1 2 6
EN60952-2: 1995 MiCOM P 1 2 7
Product safety
Earth current input
72/23/EEC 0.1 – 40 Ion A
Compliance with European 0.01 – 8 Ion B
Commission Low Voltage Directive. 0.002 – 1 Ion C

Compliance is demonstrated by Voltage input


reference to generic safety 57 – 130V A
standards: 220 – 480V B
EN61010-1: 1993/A2: 1995 Auxiliary supply voltage
EN60950: 1992/A11: 1997 24 – 60V dc A
48 – 150V dc F
MiCOM P125 P126 P127 130 - 250Vdc / 110 – 250V ac M

outline description Communication protocol


MODBUS 1
Directional / non Directional Phase K-BUS/COURIER 2
Overcurrent Directional / non
IEC 60870-5-103/VDEW 3
Directional earth fault overcurrent
DNP3.0 4
relay in drawout 4U metal case.
The following functions are HMI Language
available : French 0
English/American 1
• 3 independent phase
thresholds (instantaneous and Spanish 2
delayed) - 67/50/51 German 3
Italian 4
• 3 independent earth fault
Russian 5
thresholds (instantaneous and
delayed) 67N/50N/51N Polish 6
Portuguese 7
• 2 Wattmetric Pe/Iecos earth
Dutch 8
fault thresholds - 32N
Czech A
Hungarian B

13
Mechanical Drawings

102.4

158.74
156

177
29.6 98.31
96.3
13.1 13.1
10.5 51.82
4.5

10
247.1
222
159

168

25.1
N.8 3.4

99

Figure 6: Micom P125

154.2
158.74
156

177

29.6 150.11
148.1
13 13
10.7 103.67
4.5

10
247.1
222
159

168

25.1

N.8 3.4

151.05

Figure 7: Micom P126 and P127

14

You might also like