Professional Documents
Culture Documents
Directional/Non-
Directional Relays
T&D
Energy Automation & Information
MiCOM P125, P126, P127 Series
Directional/Non-Directional Relays
2
Models available and functionalities
Functions ANSI code MiCOM MiCOM MiCOM
P125 P126 P127
Three phase overcurrent 50/51 •
Directional/non directional phase overcurrent 67/50/51 •
Thermal overload 49 • •
Undercurrent 37 • •
Negative phase sequence overcurrent 46 • •
Broken conductor detection • •
Directional/non Directional earth fault 67N/50N/51N • • •
Wattmetric earth fault protection (W or Ie cos) 32N/Ie cos • • •
Undervoltage 27 •
Overvoltage 59 •
Residual overvoltage 59N • • •
Auto-reclose (4 shots) 79 • •
Circuit breaker failure 50BF • •
Circuit breaker monitoring and control • •
Trip Circuit Supervision [TCS] • •
Blocking logic • • •
Cold load Pick up • •
Output relay latching 86 • • •
Selective relay scheme logic • •
Start contact • • •
Programmable AND logic • •
Setting group 2 2 2
Measurements • • •
Fault records • •
Event records • •
Disturbance records • •
Diagnostic/self monitoring • • •
Network Communication • • •
RS232 front port • • •
Support software (MiCOM S1) • • •
3
Figure 1a shows the insertion of
MiCOM P126 for a generic
distribution underground line.
Figure 1b shows the MiCOM P127
applied to parallel feeders.
The MiCOM P125 P126 and P127
relays are also applicable in
generator and in generator
transformers schemes.
A range of communication protocols
allows connection with many P126
external devices thus providing 50N 46 49
remote programming control and 51N 37 50BF
extraction of information as 67N 50 BC
supervision and SCADA systems. 59N 51 79
Protection and control
functions
(P125 - P126 - P127)
Three phase tripping with single
phase alarm display is provided Figure 1a: Underground cable application
4
Earth fault directional Wattmetric Negative phase sequence
overcurrent (P125 - P126 - P127) overcurrent (P126 - P127)
(P125 - P126 - P127) The earth fault protection is also Negative phase sequence
suitable for Petersen Coil earthed overcurrent is also designed for
This protection operates from earth
systems using wattmetric protection. broken conductor detection when
fault current directly measured using earth fault protection is not enabled
a separate CT. Two stages are available the first has or not sensitive enough (eg. broken
inverse time the second has definite conductor on load side).
The sensitivity can be selected by delayed characteristic. An Ie cos ϕ
ordering code. mode is available in alternative to Pe Instantaneous and time (definite or
wattmetric mode. IDMT) negative sequence overcurrent
The polarising voltage can be
setting stages is identical to the
measured by vector sum of the The Pe threshold setting value is phase and earth overcurrent stages.
phase-neutral voltages or by direct automatically corrected by selecting
input from a dedicated VT or from the rated Ie current. Thermal overload (P126 - P127)
an open delta VT. Thermal overload protection is
Undercurrent (P126 - P127) suitable to protect transformer and
Three independent stages are MiCOM P126 and P127 relays cables for their particular thermal
available for directional/non- provide undercurrent function. characteristic.
directional earth fault protection. This function allows typical MiCOM P126 and P127 relays
All stages have definite time delayed applications such as lost of load include thermal overload based on
characteristics, the first stage may detection. thermal replica.
also be independently set to one of Alarm and overload stages are fully
available ANSI/IEEE, IEC, RI and programmable to match each device
Rectifier IDMT curves. requirement.
The IDMT stage has reset with Undervoltage (P127)
definite or IDMT timer. The DT stages Two independent stages with definite
have definite reset timer. time elements are available. Each
stage can be configured in AND or
Each earth directional stage OR logic mode.
measures the residual overvoltage
Overvoltage (P127)
element, the earth fault current
Two independent stages with definite
element and the angle between time elements are available. Each
residual voltage and earth fault Broken conductor stage can be configured in AND or
current. Following is shown the (P126 - P127) in OR logic mode.
tripping zone. The broken conductor protection
Residual overvoltage
Each one, when set as earth non- detects unbalanced conditions
(P125 - P126 - P127)
caused by broken conductors, mal-
directional stage, operates a An additional fourth residual over-
operation of single-phase switchgear
standard overcurrent element. voltage stage protection is available
or by single phasing conditions.
for earth faults in isolated system or
backup for the fault on busbar side.
RCA
The neutral voltage can be measured
angle directly using a VT transformer or
Directional Overcurrent derived in according to the insertion
characteristic U mode of the phase voltage.
I
Blocking logic
(P125 - P126 - P127)
When MiCOM P125 P126 P127
Forward relays are used in critical networks,
tripping zone management of protections must take
care of surrounding devices.
Two blocking logic inputs can be
Reverse configured independently from each
tripping zone other to lock any combination of the
selected elements (eg. current
elements, thermal overload, etc.)
Tripping zone is settable from:
+/-10˚ to +/-170˚ step 1˚ with reference Each blocking signal freezes its
to Torque angle (characteristic angle) associated memory (timer or thermal
Torque angle is settable form 0˚ to 359˚ step 1˚ state) after drop off, it restart from the
pre-blocking value and status if
conditions are still present.
Figure 2: Directional Characteristic
5
Selective relay scheme logic Programmable inputs and Monitoring and
(P126 - P127) outputs (P125 - P126 - P127) measurement
P126 and P127 relay include MiCOM P125 P126 and P127 Circuit Breaker monitoring
selective relay scheme logic. include up to 7 digital inputs and 8 (P126 - P127)
outputs relays + 1 watch dog relay.
A dedicated digital input can Preventive circuit breaker
temporarily alter the time delay Two of eight output relays are maintenance is the advance function
settings in response to a downstream change over type. provided by the MiCOM P126 and
relay phase/earth fault start P127 with adjustable closing and
Change over output type is typically
opening time measurements and
condition. used for tripping commands. breaker failure protection.
This function allows the MiCOM Protection and control elements can All phase currents I or I2 during the
relays to discriminate correctly when easily be assigned to any output. faults are memorised and summed.
used in a cascade scheme.
All inputs and outputs are freely Trip Circuit Supervision [TCS]
The selective relay scheme logic configurable. (P126 - P127)
function can be enabled or disabled MiCOM P126 and P127 relays
Latching of the outputs relay
by the user as required. allow trip circuit supervision via a
(P125 - P126 - P127)
specific input. Result of this
Cold load pick up Any of output relays can be monitoring can be locally or
(P126 - P127) latched. remotely transmitted.
Cold load pick-up temporarily raises Reset of all outputs is possible by Measurements
the phase overcurrent, earth logic input, a push button on front MiCOM P125, P126 and P127
overcurrent, thermal status, negative HMI or through the local area relays monitor permanently all of the
sequence overcurrent settings network. analogue inputs (voltage and current),
following closure of the circuit display the values on the LCD and
breaker, allowing the protection Circuit breaker failure store the measurements in memory.
settings to be set closer to the load protection (P126 - P127)
The measured values are the true
profile, to avoid untimely trips. The circuit breaker failure protection RMS up to the 10th harmonic with a
verifies the effective opening of the 0.1% accuracy (nominal conditions
CB by a dedicate undercurrent at 50 Hz).
400
threshold during a t_BF timer. Peak demands with a 15 minute
The circuit breaker failure function is window are also memorised.
Current (% of nominal)
300
activated by the trip of a generic All measured and calculated values
protection. can be displayed on the HMI or
200 transferred locally or remotely upon
Circuit breaker failure protection user request.
Nominal threshold
100 may be used for tripping upstream
circuit breakers. Event records (P126 - P127)
75 logic events are stored in
Autoreclose (P126 - P127) MiCOM P126 and P127 relays.
0 1 2 3 4 5 6 Time (s)
It provides three pole up to four - Events include inputs/outputs,
shots autoreclose. change of status, alarms and contact
Setting groups operations.
The user may select which
External conditions may request the All events are time stamped to 1ms.
protection elements and/or a digital
need for different settings. input may start any of four shots Disturbance records
MiCOM P125, P126 and P127 independently. (P126 - P127)
provide two setting groups, G1 and Each shot has independently Voltage and current waveforms are
G2 including all the protection, settable the dead time. captured by MiCOM P126 and
automation features and monitoring A counter stores the number of P127 relays.
functions. reclose commands incremented with Up to 5 records of 3 seconds are
The switching between group 1 and each reclose order. stored inside MiCOM relays.
Disturbance recording function is
group 2 can be achieved locally,
triggered either by any of the
remotely, via a dedicated logic input. programmed thresholds or by an
All settings are stored in E2PROM external input or through the local
(non-volatile rewriting memory) area network.
6
Fault records (P126 - P127) Programmable LEDs Hardware
The last 5 faults are stored inside the 4 freely programmable LEDs are MiCOM P125, P126 and P127
MiCOM relays. provided on all models of the models are numerical protection and
MiCOM P125 P126 and P127 control relays.
Each fault includes: relays.
Case
Record number The user can assign independently to
each LED any program function or For all directional models MiCOM
• Fault time P125, P126, P127 the unit have a
combination of thresholds.
• Active setting group draw out metal 4U case high.
Keypad
• Faulted phase The width is:
A seven button tactile keypad on the
• Protection operation front panel allows the user easy P125 20TE
access to any data in the MiCOM P126 and P127 30TE
• Magnitude
P125, P126 and P127 relays.
Fault indicator helps the user to All CTs inputs are short-circuited if
identify clearly the fault and to Local and remote the active unit is withdrawn from the
monitor the MiCOM P126 and communication case.
P127 relay settings. Two communication ports are All MiCOM relays can be panel or
available; a rear port providing rack mounted.
User Interface remote communication and a front
Battery box
port providing local communication.
Front display and menus MiCOM P125, P126 and P127
All functions including protection, Remote communication relays can also be powered by
automation, communication, LEDs, The remote communications are external battery.
inputs and outputs can be based on RS485 voltage levels.
programmed and modified using the The battery is allocated in a small
This port is available for MODBUSTM case as in figure below. When the
front panel user interface.
and IEC 60870-5-103 protocols. relay is out of its case or when the
MiCOM relays can transmit to the auxiliary power supply is failing, the
local monitoring system (eg. MiCOM battery box ensures temporary
S10) or remotely to the SCADA supply to the relay thus to read or
settings, measurements, alarms, fault modify internal data by front panel
events, and disturbance records. or by interface program MiCOM S1.
7
A
35
C B Watch Dog
Phase rotation ~/+ 33 WD 37
36
Auxiliary Voltage 4
A B C Programmable tripping output
~/- 34 RL1 6
2
10
Trip dire ction
P1 55 RL2 12
Programmable output
S1 8
1A 14
56 32N 50N 51N RL3 Programmable output
16
47 18
59N
RL4 Programmable output
5A 67N 20
48 3
RL5 Programmable output
1
7
RL6 Programmable output
5
22
MiCOM
A da
Programmable input L1
24
26
Programmable input L2
P125
B 28
17
Programmable input L3
19
21
C 39 Programmable input L4
23
N dn 40
Case earth
connection
29 Communication cable shield
30 Terminal
RS485
31
RS485
Communication Port
+ 32
C B
Phase rotation
35
A B C 37
~/+ 33 WD
36
Auxiliary Voltage 4
~/- 34
P1 RL1 6
49 2
S1 10
1A 50 51 32N
50 RL2 12
P1 51 8
14
S1 51N RL3
1A 67N 50N 16
52 18
53 RL4
P1 20
37 46 49
S1 3
1A RL5
1
54
79 BC
Trip dire ction
59N 7
55 RL6
P1 5
S1 9
1A 50BF TCS RL7
56 11
13
41 RL8
15
5A 22
42
24 Programmable input L1
43
26
5A Programmable input L2
44 28
17
45
Programmable input L3
19
5A 21
46
Programmable input L4
MiCOM
23
47
25
5A Programmable input L5
27
48
P126
58
Programmable input L6
A da 60
57
Programmable input L7
59
B
Case earth
connection
29 Communication cable shield
30 Terminal
C 73 RS485
31
RS485
N dn 74 Communication
+ 32
C B 35
Phase rotation
37
~/+ 33 WD
36
A B C Auxiliary Voltage 4
~/- 34
RL1 6
P1 49 2
S1 10
1A
50
50 51 67 RL2 12
P1 51 8
14
S1 RL3
1A 32N 50N 51N 16
52 18
53 RL4
P1 20
S1
67N 37 46
3
1A RL5
1
Trip dire ction
54
49 79 BC 7
55 RL6
P1 5
S1
9
1A 50BF TCS RL7
56 11
41 13
RL8
15
5A 59 59N 27
22
42
43 24
Programmable input L1
26
5A Programmable input L2
44 28
45 17
Programmable input L3
19
5A 21
46
Programmable input L4
MiCOM
47 23
25
5A Programmable input L5
27
48
P127
58
A a Programmable input L6
69 60
57
Programmable input L7
70 59
B b 71
Case earth
connection
72 29 Communication cable shield
30 Terminal
C c 73 RS485
31
N n 74
RS485
+ 32
70
70
B b 71
B b 71
72
n 72
C c
C 73
N dn n
N dn 74
73
Internal reconstruction voltage UC
74
11
Pe>Definite time or IDMT from 10V to 960V step 0.5V Circuit Breaker control
• IDMT curve identical to phase • Definite time: • Trip time
overcurrent Definite time: from 0 to 600s step 0.01s from 0.1 to 5s step 0.1s
from 0 to 150s step 0.01 • Closing time
Zero sequence voltage
• All wattmetric ranges are from 0.1 to 5s step 0.1s
multiplied by K; thresholds:
• Voltage input range 57 – 130V: Contacts
K=1 when Ien=1A;
K=5 when Ien=5A threshold range • Rating
from 1 to 260V step 0.1V Make current 30A (max 4s at
IeCos thresholds duty cycle 10%)
• Voltage input range 220 – 480V:
• IeCos> and IeCos>> have the Carry: 5 Amps continuous
threshold range
same ranges of Ie thresholds Break: 135 Vdc, 0.3(L/R=30ms)
from 5 to 960V step 0.5V
• IeCos>: Definite time or IDMT 220 Vac, 5A (P.F. = 0.6)
• Definite time : • Mechanical durability
• IDMTcurve identical to phase from 0 to 600s step 0.01 s >100000 operations
overcurrent; Definite delay time
from 0 to 150s step 0.01 Cold load pick up Housing
Pe/Iecos characteristic angle: • form 100% to 500% • Case: High: 4U (177mm)
Settable from 0° to 359° step 1° • Definite time MiCOM P125 20 TE,
from 0.1 to 3600s step 0.1 s MiCOM P126 30 TE,
Under current thresholds MiCOM P127 30 TE
Auto reclose (79)
• from 0.1 to 1 In step 0.01 In • Weight:
• Definite time 0 to 150s step 0.01s • 4 shots, dead, reclaim and P125 c. 3.0 Kg, P126c. 4.0 Kg,
inhibit time P127 c. 4.2 Kg
Negative sequence current • Block from external CB fail input • Mounting:
thresholds:
• Ext.CB fail time Rack or flush mounting
• Three thresholds with range from 0.01 to 600s step 0.01 s • Connections:
from 0.1 to 40 x In step 0.01 In • tD1, tD2 Rear, (double faston +
I2> Definite time or IDMT from 0.01 to 300s step 0.01 s M4 screw per connection)
• IDMT curve identical to phase • tD3, tD4 Full draw-out with automatic
overcurrent; from 0.01 to 600s step 0.01 s CT shorting
• Definite time: • tR, tI • Protection:
from 0 to 150s step 0.01s. from 0.02 to 600s step 0.01 s IEC 529; IP 52, IK 07
Broken conductor: AND logical gates High voltage withstand
Ratio I2/I1 from 20 to 100% • 4 “AND” logical gates • Dielectric withstand (50/60Hz)
Definite time from 0 to 14400s step 1s IEC 60255-5
• Pick-up time delay 2 kV in common mode
Thermal replica thresholds: from 0 to 600 s in steps of 0.01 s
1 kV in differential mode
• Reset time
• Threshold from 0.1 to 3.2 In, • Impulse voltage
from 50 to 200%, from 0 to 600 s in steps of 0.01 s IEC 60255-5
• Thermal constant from 1 to 200 min, Auxiliary timers 5 kV in common mode
delay time 0 to 150s. 1 kV in differential mode
• Two auxiliary timers
Under voltage thresholds: • Insulation resistance
• Setting time: IEC 60255-5 > 1000 MΩ
• Voltage input range 57 – 130V from 0 to 200 s step 0.01s
• thresholds range: Electrical environment
Circuit breaker control (50BF)
from 2V to 130V step 0.1V • High frequency disturbance
• Voltage input range • t_BF from 0 to 10 s step 0.01 s IEC 61000-4-12
220 – 480V : • I< BF: from 0.02 to 1In in steps 2.5 kV in common mode, class 3
• thresholds range: of 0.01In 1 kV in differential mode, class 3
from 10V to 480V step 0.5V Trip circuit supervision • Fast transient disturbance
• Definite time IEC 61000-4-4 4 kV auxiliary
• CB Sup. time supply, class 4
from 0 to 600s step 0.01s
from 0.1 to 10 s step 0.01s ANSI C37.90.1
Over voltage thresholds: • CB open sup. time 2 kV other, class 4
• Voltage input range 57 – 130V: from 0.05 to 1s step 0.01s • Electrostatic discharge
• thresholds range • CB close sup. time IEC 61000-4-2 8 kV, class 4
from 2V to 260V step 0.1V from 0.05 to 1s step 0.01s • Radio frequency impulse
• Voltage input range 220 – 480V: • CB trip operations ANSI C37.90.2 35 V/m
thresholds range from 0 to 50000 step 1 IEC 61000-4-3 10 V/m
12
Environmental withstand • Tripping curves type IEC (short • Trip circuit supervision
• Temperature time inverse, standard inverse, The relay provides complete
very inverse, extremely inverse,
IEC 60255-6 measurements and recording
long time inverse) IEEE/ANSI
Storing and transportation (short time inverse, moderately functions including
-25°C to +70°C inverse, inverse, very inverse, • True RMS values
Operation -25°C to + 55°C extremely inverse), RI and RECT • Event recorder with the
• Humidity IEC 60068-2-3 • 3 Negative phase sequence Last 75 events,
56 days at 93% RH and 40°C overcurrent thresholds - 46 1ms time stamped.
• Enclosure protection • Undercurrent - 37 • Fault recorder with the
IEC 60529 IP 52, IK 07 • 2 Thermal overload last 5 faults
• Vibration thresholds - 49 • Disturbance recorder with
IEC 60255-21-1 • 2 Phase Overvoltage storage of 5 records for
Response and endurance, class 2 thresholds - 59 3 seconds each
• Shock and bump • 2 Phase Undervoltage User interface shall include
IEC 60255-21-2 thresholds - 27
Response and withstand, class 1 • A 32 characters backlit display
• 1 Residual Overvoltage –
• Seismic thresholds - 59N • Programmable LEDs
IEC 60255-21-3, Class 2 • Output relay latching - 86 • A front panel RS232 for
EMC compliance • Broken conductor detection local settings
• 4 shot auto-recloser - 79 • A RS485 rear port compatible
with MODBUS IEC60870-5-103
89/336/EEC, • Circuit breaker failure
detection - 50 BF • An easy to use PC setting
93/31/EEC, software.
93/68/EEC • Circuit breaker monitoring
Compliance with European
Commission EMC Directive. Ordering code 0 1
13
Mechanical Drawings
102.4
158.74
156
177
C G
29.6 98.31
96.3
13.1 13.1
10.5 51.82
4.5
10
247.1
222
159
168
25.1
N.4 Ø 3.4
N.4 Ø 4.4
All dimensions in mm
99
154.2
158.74
156
C G
177
29.6 150.11
148.1
13 13
10.7 103.67
4.5
10
247.1
222
168
159
25.1
N.4 Ø 3.4
Your contact:
15
© 2003 ALSTOM - Electronic file
Publication: P12y/EN BR/Cc
Transmission & Distribution Energy Automation & Information, Le Sextant, 3 avenue André Malraux, 92300 Levallois-Perret. France
Tel: +33 (0) 1 41 49 20 00 Fax: +33 (0) 1 41 49 24 85 energy-automation.information@tde.alstom.com www.tde.alstom.com
Contact Centre on line 24 hours a day : +44 (0) 1785 25 00 70
ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and service marks of ALSTOM.
MiCOM is a registered trademark of ALSTOM. Other names mentioned, registered or not, are the property of their respective companies.
Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up to date literature, this
brochure should only be regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advice on the application of any product
referred to in it. We cannot be held responsible for any reliance on any decisions taken on its contents without specific advice.